1. 0 000 c eee eens 19 2 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 About this document 2 De 1 About this document 1 1 Function This operating instructions manual has all the information you need for quick setup and safe operation Please read this manual before you start setup 1 2 Target group This operating instructions manual is directed to trained qualified personnel The contents of this manual should be made available to these personnel and put into practice by them 1 3 Symbolism used Information tip note This symbol indicates helpful additional information Caution If this warning is ignored faults or malfunctions can result Warning If this warning is ignored injury to persons and or serious damage to the instrument can result Danger If this warning is ignored serious injury to persons and or destruction of the instrument can result Ex applications This symbol indicates special instructions for Ex applications List The dot set in front indicates a list with no implied sequence Action This arrow indicates a single action Sequence Numbers set in front indicate successive steps in a procedure VEGALOG 571 AA Output card analogue 3 For your safety EBA 2 For your safety 2 1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel
2. Mounting EBA Installation instructions 4 Mounting 4 1 General instructions The module cards of VEGALOG 571 can only be mounted into the 19 carrier BGT LOG 571 It is provided with a special bus board for data transmission between CPU and the individual peripheral cards LOGBUS The carrier is designed for mounting into a switching cabinet or 19 housing The plug position for the individual cards is individually selectable the system saves the card positions when switch ing on Note The plug positions must not be changed after the parameter adjustment because measurement loops that have already been set up would otherwise have to be reconfigured 4 2 Module Setup a module for the VEGALOG 571 AA card You will find the description in the operating instructions manual CPU and carrier 4 3 Coding A mechanical coding system avoids later interchanging of the various module cards in the carrier The coding system consists of e two coded pins in the female multipoint connector e two holes in the male multipoint connector of the respective component The coded pins are attached to the module Equip the female multipoint connector with the two coded pins according to the Coding chart and Position of the coded pins The function coding points out that these are module cards of VEGALOG The instrument coding is used to differentiate between the individual module cards The male multipoint connecto
3. 6 3 8 D e E E S o k 128 4mm 5 1 16 Fig 5 Dimensions VEGALOG 571 AA VEGALOG 571 AA Output card analogue 19 VEBA VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone 49 7836 50 0 Fax 49 7836 50 201 E mail info de vega com www vega com CE amp All statements concerning scope of delivery application practical use and operating conditions of the sensors and processing systems correspond to the information avail able at the time of printing VEGA Grieshaber KG Schiltach Germany 2006 Technical data subject to alterations 31949 EN 060606
4. charged The operating condition of the CPU and peripheral cards is displayed via the status LEDs in the front plate e LED failure message red flashes in case of communication problems on the LOGBUS lights during initialisation and during the self test lights permanently during a hardware error e LED operating voltage green lights when voltage supply is on 14 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 Maintenance and fault rectification 7 3 Instrument repair If a repair is necessary please proceed as follows You can download a return form 23 KB from our homepage www vega com under Downloads Forms and Certificates Repair form By doing this you help us carry out the repair quickly and without having to call back for needed information Print and fill out one form per instrument Clean the instrument and pack it damage proof Attach the completed form and possibly also a safety data sheet to the instrument Please request the address for the return shipment from the VEGA agency serving you VEGALOG 571 AA Output card analogue 15 Dismounting EBA 8 Dismounting 8 1 Dismounting procedure Warning Before dismounting be aware of dangerous process con ditions such as e g pressure in the vessel high temperatures corrosive or toxic products etc Take note of chapters Mounting and Connecting to power supply and ca
5. of line voltage e f overvoltage surges are expected overvoltage arresters should be installed In hazardous areas you should take note of the appropriate regulations conformity and type approval certificates of the sensors and power supply units The module card is powered via the common power supply unit of the VEGALOG system You can find detailed information on the power supply in the Technical data in the Supplement 5 2 Connection cable Power supply is connected with standard cable acc to the national installation standards To connect 4 20 mA instruments standard two wire cable without screen can be used If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas screened cable should be used Connect the cable screen on both ends to ground potential The screen must be connected low impedance on the 4 20 mA instrument to the potential equalisation If potential equalisation currents are expected the screen connection on the side of VEGALOG 571 AA must be made via a ceramic capacitor e g 1 nF 1500 V The low frequency potential equalisation currents are thus suppressed but the protective effect against high frequency interference signals remains Take note of the corresponding installation regulations for Ex applications In particular make sure that no potential equal isation currents flow over the cable screen In case of grounding on both sides
6. Operating Instructions VEGALOG 571 AA Output card analogue oA O on VEGALOG 571 AA Contents ASIAN Contents 1 About this document T FUNCION s cresa e a e eee e tct 3 12 Targetgroup lees 3 1 33 Symbolism used 2 2 0 55 3 2 For your safety 2 1 Authorised personnel ellus 4 2 2 Appropriateuse llle 4 2 3 Warning about misuse 4 24 CEconformity 2 0 05 4 2 5 Environmental instructions 5 3 Product description 3 4 Configuration 1 0 2 0 cee 6 3 2 Principle of operation less 6 3 3 Operation 00 eee ee eee 6 3 4 Storage andtransport 7 4 Mounting 4 1 General instructions 000004 8 42 Module 2 eee ee 8 43 Coding ox swim Siete tse Cae wah 8 5 Connecting to power supply 5 1 Preparing the connection 11 5 2 Connection cable 5 11 5 3 Wiringplan llle 12 6 Setup 6 1 Indicating and adjustment elements 13 7 Maintenance and fault rectification 7 4 Maintenance llle elles ss 14 7 2 Fault rectification 0 0 eee eee 14 7 3 Instrument repair eee eee eee 15 8 Dismounting 8 44 Dismounting procedure 16 82 Disposal 00000 cece eee eee 16 9 Supplement 9 1 Technical data 005 17 92 Dimensions
7. authorised by the operator For safety and warranty reasons any internal work on the instruments must be carried out only by personnel authorised by the manufacturer 2 2 Appropriate use The AA card Ausgang Analog i e output analog provides together with the VEGALOG 571 processing system ten 0 4 20 MA outputs 2 3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application specific hazards e g vessel overfill or damage to System components through incorrect mounting or adjustment 2 4 General safety instructions VEGALOG 571 AA is a high tech instrument requiring the strict observance of standard regulations and guidelines The user must take note of the safety instructions in this operating instructions manual the country specific installation standards e g the VDE regulations in Germany as well as all prevailing safety regulations and accident prevention rules 2 5 CE conformity The VEGALOG 571 AA Ex module card is in CE conformity with EMVG 89 336 EWG and LVD 73 23 EWG Conformity has been judged according to the following standards e EMC Emission EN 50081 2 Susceptibility EN 50082 1 e LVD EN 61010 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 Weley For your safety 2 6 Environmental instructions Protection of the environment is one of our most important duties That is why we have introduced an enviro
8. l VEGALOG 571 CPU as well as in the online help of PACTware VEGALOG 571 AA Output card analogue 13 Maintenance and fault rectification EBA Causes of malfunction Fault rectification 24 hour service hotline Fault messages via LED sta tus indication 7 Maintenance and fault rectification 7 1 Maintenance When used as directed in normal operation the module card VEGALOG 571 AA is completely maintenance free 7 2 Fault rectification VEGALOG 571 AA offers maximum reliability Nevertheless faults can occur during operation These may be caused by the following e g e Measured value of the sensor not correct e Voltage supply e Interference on the cables The first measures to be taken are checking the input outout signal as well as processing failure messages The diagnostic information are updated cyclically in a 5 sec pattern PACTware with the suitable DTM offers comprehensive diagnostics options The integrated online help offers you additional information In many cases these causes can be thus determined and faults can be rectified If these measures are not successful you can call the VEGA service hotline in urgent cases under the phone no 49 1805 858550 The hotline is available to you 7 days a week round the clock Since we offer this service world wide the support is only available in the English language The service is free of charge only the standard telephone costs will be
9. nment management system with the goal of continuously improving company environmental protection The environment man agement system is certified according to DIN EN ISO 14001 Please help us fulfil this obligation by observing the environ mental instructions in this manual e Chapter Storage and transport e Chapter Disposal VEGALOG 571 AA Output card analogue 5 Product description EBA Scope of delivery Area of application Physical principle Power supply 3 Product description 3 1 Configuration The scope of delivery encompasses e 19 module card VEGALOG 571 AA e Documentation this operating instructions manual 3 2 Principle of operation The AA card Ausgang Analog i e output analogue provides together with the VEGALOG 571 processing system ten 0 4 20 mA outputs These can be used for transmission of the measuring results to the following instruments Indicating instruments Characteristics recorder Controller PLC The AA card makes the processing results available via up to ten analogue currents in the range of 0 20 mA A scaling as well as the definition as rising or falling characteristics can be Set via the adjustment software The module card is powered via the common power supply unit of the VEGALOG system You can find detailed information on the power supply in the Technical data in the Supplement 3 3 Operation The operation of VEGALOG 571 is carried o
10. ole Suitable female multipoint connector according to DIN 41612 with connection via standard connection technologies Current outputs Quantity Function Range Resolution Max load Load dependent error at 750 Ohm Linearity error Temperature error Displays LED displays Status indication operating voltage Status indication fault signal 10 outputs analogue output of the processing results 0 4 20 mA 0 05 of range 10 HA 750 Ohm 0 5 96 100 pA 0 025 of range 0 025 96 10 k of range 1x LED green 1x LED red Ambient conditions Ambient temperature Storage and transport temperature 20 60 C 44 140 F 20 480 C 4 176 F VEGALOG 571 AA Output card analogue 17 Supplement EBA Electrical protective measures Protection mounted in BGT LOG 571 front side completely equipped or covers Upper and lower side Wiring side Protection class Overvoltage category Electrical separating measures in carrier BGT LOG 571 Galvanic separation according to VDE 0106 part 12 Reference voltage between voltage supply LOGBUS connection and current outputs 2 All current outputs have a common reference potential GND 18 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 VEBA Supplement 9 2 Dimensions 9mm 23 64 5 5mm 7 32 162mm
11. rry out the listed steps in reverse order 8 2 Disposal The instrument consists of materials which can be recycled by specialised recycling companies We use recyclable materials and have designed the electronic modules to be easily separable WEEE directive 2002 96 EG This instrument is not subject to the WEEE directive 2002 96 EG and the respective national laws in Germany e g ElektroG Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points These may be used only for privately used products according to the WEEE directive Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials Materials see Technical data If you cannot dispose of the instrument properly please contact us about disposal methods or return 16 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 VEGA Supplement 9 Supplement 9 1 Technical data General data Series Dimensions Weight 19 module card for BGT LOG 571 W 25 4 mm 1 in H 128 4 mm 5 06 in D 166 mm 6 54 in approx 400 g 0 882 Ibs Voltage supply Operating voltage PIN d2 z2 Power consumption Electrical connection 24 V DC 18 36 V max 9 W Module card Module in the carrier BGT LOG 571 Multipoint connector according to DIN 41612 series F 48 pole d b z with coding h
12. rs of the individual module cards point to the holes suiting the pin positions VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 Wiss Mounting Instrument coding Function coding CPU card al c3 EP card a3 c3 and c23 with Ex AA card a5 c3 AR card a7 c3 AT card a9 c3 EA card a11 c3 VEGACOM 557 a27 c3 c11 VEGACOM 558 a29 c11 VEGASTAB 593 D zbd moO rl al 19 a3 o3e c3 a5 e50 a7 e70 a9 e9o a11 etie c11 a13 0130 0150 0170 0190 0210 8 a23 e23e c23 a25 0250 a27 0270 0290 0310 LT o Li Fig 1 Positioning of the coded pins on the male multipoint connector 1 Instrument coding 2 Function coding 3 Ex coding VEGALOG 571 AA Output card analogue 9 Mounting EBA Fig 2 Detail coded pin mounting 1 Coded pin 10 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 Connecting to power supply Note safety instructions Take note of safety instructions for Ex applications Select power supply Selecting the connection ca ble Cable screening and ground ing Select connection cable for Ex applica tions 5 Connecting to power supply 5 1 Preparing the connection Always observe the following safety instructions e Connect only in the complete absence
13. this can be achieved by the use of a capacitor or a separate potential equalisation The total capacitance of the cable and of all capacitors must not exceed 10 nF in Ex applications VEGALOG 571 AA Output card analogue 11 Connecting to power supply EBA 5 3 Wiring plan z14 z16 z18 z20 z22 z24 z26 z28 z30 z32 Fig 3 VEGALOG 571 AA 1 2 Power supply for VEGALOG 571 AA 4 20 mA outputs Information The outputs are only floating for voltage supply among each other they are connected by a common ground D Broken lines Connections on the AA card 12 VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 Vis Set up 6 Set up 6 1 Indicating and adjustment elements Z D H Fig 4 Indicating and adjustment elements 1 LED for fault signal 2 LED for operating voltage Description of the status e LED fault signal 1 LEDs flashes in case of communication problems on the LOGBUS lights during initialisation and during the self test lights permanently during a hardware error e LED operating voltage 2 lights when voltage supply is on The module cards of the VEGALOG system have no own adjustment elements All adjustment measures are carried out with the PC through the adjustment software PACTware Setup information is available in the operating instructions manua
14. ut via a PC which can be connected via the RS232 interface of the CPU As an alternative connection via Ethernet and VEGACOM 558 is possible The adjustment software PACTware with the corresponding DTMs is installed under Windows and ensures easy configuration of measuring systems as well as parameter adjustment of connected VEGA sensors For this purpose PACTware provides a clear adjustment interface with menu structure window technology and graphic support In addition online help is available which describes the available functions VEGALOG 571 AA Output card analogue 909090 N3 6v61 31949 EN 060606 Weley Product description and parameter adjustment options For earlier VEGALOG systems with CPU software 1 xx the previous software VVO VEGA Visual Operating must be used for operation 3 4 Storage and transport Packaging Your instrument was protected by packaging during transport Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180 The packaging of standard instruments consists of environ ment friendly recyclable cardboard For special versions PE foam or PE foil is also used Dispose of the packaging material via specialised recycling companies Storage and transport tem e Storage and transport temperature see Supplement perature Technical data Ambient conditions e Relative humidity 20 85 VEGALOG 571 AA Output card analogue 7

Download Pdf Manuals

image

Related Search

Related Contents

Operation Guide - Easy Interactive Tools Ver.3.0  第816号 全 ページ  HCS-4100/50 Series Fully Digital Congress System  Dell PowerEdge R810 Owner's Manual  Sanyo VPC-S1275 User's Manual  Dossier Liaison Documentaliste/Remplaçant "Eléments de survie"  Woxter 50 BL Instruction Manual  GFI MailEssentials Administrator Guide  Produits Catalogue  カムスプロケットカバー 取扱説明書  