NI 9263 Operating Instructions and Specifications
Contents
1. following precautions A hazardous voltage is a voltage greater than 42 4 Na or 60 VDC to earth ground A PR Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Caution Do not mix hazardous voltage circuits and human accessible circuits on the same module Caution Make sure that devices and circuits connected to the module are properly insulated from human contact Caution When module terminals are hazardous voltage LIVE gt 42 4 V 60 VDC you must ensure that devices and circuits connected to the module are properly insulated from human contact You must use the NI 9932 connector backshell kit to ensure that the terminals are not accessible National Instruments Corp 3 NI 9263 Operating Instructions and Specifications Figure 1 shows the NI 9932 connector backshell Figure 1 NI 9932 Connector Backshell Safety Guidelines for Hazardous Locations The NI 9263 is suitable for use in Class I Division 2 Groups A B C D T4 hazardous locations Class I Zone 2 AEx nA IIC T4 and Ex nA IIC T4 hazardous locations and nonhazardous locations only Follow these guidelines if you are installing the NI 9263 in a potentially explosive environment Not following these guidelines may result in serious injury or death NI 9263 Operating Instructions and Specifications 4 ni com Caution Do not disconnect I O side wires or connectors unle
2. and Specifications 24 ni com Korea 82 02 3451 3400 Lebanon 961 0 1 33 28 28 Malaysia 1800 887710 Mexico 01 800 010 0793 Netherlands 31 0 348 433 466 New Zealand 0800 553 322 Norway 47 0 66 90 76 60 Poland 48 22 328 90 10 Portugal 351 210 311 210 Russia 7 495 783 6851 Singapore 1800 226 5886 Slovenia 386 3 425 42 00 South Africa 27 0 11 805 8197 Spain 34 91 640 0085 Sweden 46 0 8 587 895 00 Switzerland 41 56 2005151 Taiwan 886 02 2377 2222 Thailand 662 278 6777 Turkey 90 212 279 3031 United Kingdom 44 0 1635 523545 National Instruments Corp 25 NI 9263 Operating Instructions and Specifications National Instruments NI mi com and LabVIEW are trademarks of National Instruments Corporation Refer to the Terms of Use section on ni com 1legal for more information about National Instruments trademarks Other product and company names mentioned herein are trademarks or trade names of their respective companies For patents covering National Instruments products technology refer to the appropriate location Help Patents in your software the patents txt file on your media or the National Instruments Patent Notice atni com patents 2004 2009 National Instruments Corp All rights reserved 373781D 01 Feb09
3. not connect the NI 9263 to signals or use for measurements within Measurement Categories III or IV National Instruments Corp 17 NI 9263 Operating Instructions and Specifications Hazardous Locations UR d EE D Class I Division 2 Groups A B C D T4 Class I Zone 2 AEx nA IIC T4 Canada CHL Class I Division 2 Groups A B C D T4 Class I Zone 2 Ex nA IIC T4 Europe ODEMKO Ex nA IIC T4 Safety Standards This product meets the requirements of the following standards of safety for electrical equipment for measurement control and laboratory use e IEC 61010 1 EN 61010 1 e UL61010 1 CSA 61010 1 ei Note For UL and other safety certifications refer to the product label or the Online Product Certification section NI 9263 Operating Instructions and Specifications 18 ni com Electromagnetic Compatibility This product meets the requirements of the following EMC standards for electrical equipment for measurement control and laboratory use e EN 61326 IEC 61326 Class A emissions Industrial immunity e EN 55011 CISPR 11 Group 1 Class A emissions e AS NZS CISPR 11 Group 1 Class A emissions FCC 47 CFR Part 15B Class A emissions ICES 001 Class A emissions Note For the standards applied to assess the EMC of this product refer to the Online Product Certification section 3 Note For EMC compliance operate this device with shielded cabling National Instruments Corp 19 NI 9263 Operat
4. 3 NI 9263 Operating Instructions and Specifications 8 ni com Each channel has a digital to analog converter DAC that produces a voltage signal Each channel also has overvoltage and short circuit protection Refer to the Specifications section for more information about the overvoltage and short circuit protection Refer to Figure 4 for an illustration of the output circuitry for one channel of the NI 9263 i i i Overvoltage AO Isolated DAC Short Circuit O Protection i i i i Amplifier Figure 4 Output Circuitry for One Channel of the NI 9263 When the module powers on the channels output the startup voltage Refer to the Specifications section for more information about startup voltage Refer to the software help for information about configuring startup output states in software National Instruments Corp 9 NI 9263 Operating Instructions and Specifications Wiring for High Vibration Applications If an application is subject to high vibration National Instruments recommends that you either use ferrules to terminate wires to the detachable screw terminal connector or use the NI 9932 backshell kit to protect the connections Refer to Figure 5 for an illustration of using ferrules Refer to Figure 1 for an illustration of the NI 9932 connector backshell Es Figure 5 10 Terminal Detachable Screw Terminal Connector with Ferrule NI 9263 Operat
5. IEC 60068 2 2 40 to 85 C Ingress DrotecHon IP 40 Operating humidity IEC odp 7361 10 to 90 RH noncondensing Storage humidity IEC odp 7361 5 to 95 RH noncondensing National Instruments Corp 21 MI 9263 Operating Instructions and Specifications Maxtmum alptude 2 000 m Pollution Degree IEC 60664 2 Environmental Management National Instruments is committed to designing and manufacturing products in an environmentally responsible manner NI recognizes that eliminating certain hazardous substances from our products is beneficial to the environment and to NI customers For additional environmental information refer to the NI and the Environment Web page at ni com environment This page contains the environmental regulations and directives with which NI complies as well as other environmental information not included in this document Waste Electrical and Electronic Equipment WEEE S EU Customers At the end of the life cycle all products must be sent to a WEEE recycling center For more information about WEEE recycling centers and National Instruments WEEE initiatives visit ni com environment weee NI 9263 Operating Instructions and Specifications 22 ni com BES mises SEAS ChE RoHS HEA National Instruments 4 p Hla Fa A KA 7 dP Be Hl HI NIE RS ROHS CT National Instruments F E ROHS Zb D WER ni com environment rohs_china For information about China ROHS compliance go to ni com
6. OPERATING INSTRUCTIONS AND SPECIFICATIONS NI 9263 4 Channel 10 V 16 Bit Analog Voltage Output Module Fran ais Deutsch HARE S30 fH ni com manuals SSSSSEEssy9 Qy NATIONAL gt INSTRUMENTS This document describes how to use the National Instruments 9263 and includes specifications and terminal assignments for the NI 9263 Visit ni com info and enter rdsoftwareversion to determine which software you need for the modules you are using For information about installing configuring and programming the system refer to the system documentation Visit ni com info and enter cseriesdoc for information about C Series documentation ei Note The safety guidelines and specifications in this document are specific to the NI 9263 The other components in the system might not meet the same safety ratings and specifications Refer to the documentation for each component in the system to determine the safety ratings and specifications for the entire system Visit ni com info and enter cseriesdoc for information about C Series documentation Safety Guidelines Operate the NI 9263 only as described in these operating instructions Hot Surface This icon denotes that the component may be hot Touching this component may result in bodily injury NI 9263 Operating Instructions and Specifications 2 ni com Safety Guidelines for Hazardous Voltages If hazardous voltages are connected to the module take the
7. be installed on power supply inputs near power entries to modules and controllers Power supply and module cables must be separated on opposite sides of the enclosure and must enter and exit through opposing enclosure walls NI 9263 Operating Instructions and Specifications 6 ni com Connecting the NI 9263 The NI 9263 has a 10 terminal detachable screw terminal connector that provides connections for 4 analog output channels AOO COM AO1 COM AO2 COM AO3 COM NC COM Glelel Aelolzleelal Jele Figure 2 NI 9263 Terminal Assignments National Instruments Corp 7 NI 9263 Operating Instructions and Specifications Each channel of the NI 9263 has an AO terminal to which you can connect the positive lead of a load Each channel also has a common terminal COM and there is an additional COM terminal at the bottom of the connector All of the COM terminals are internally connected to the isolated ground reference of the module When connecting a load to the NI 9263 connect the positive lead of the load to the AO terminal and the ground of the load to the corresponding COM terminal Refer to Figure 3 for an illustration of connecting a load to the NI 9263 i Load Figure 3 Connecting a Load to the NI 9263 er Note You must use 2 wire ferrules to create a secure connection when connecting more than one wire to a single terminal on the NI 926
8. el max Output impedance eee 0 1 Q Accuracy Percent of Percent of Reading Range Measurement Conditions Gain Error Offset Error Calibrated max 40 to 70 C 0 35 0 75 Calibrated typ 25 C 5 C 0 01 0 1 Uncalibrated max 40 to 70 C 2 2 1 7 Uncalibrated typ 25 C 5 C 0 3 0 25 Range equals 10 7 V Stability Re EE 6 ppm C Offset drift energiakriis 80 uV C Protection Overvoltage oo 30 V Short circuit National Instruments Corp Indefinitely 13 NI 9263 Operating Instructions and Specifications Update time Update Time for Number of cRIO 9151 R Series Update Time for Channels Expansion Chassis All Other Chassis 1 3 5 us 3 us 2 6 5 Us 5 us 3 9 us 7 5 us 4 12 us 9 5 us Noge eck EE EE Slew rate Crosstalk Settling time 100 pF load to 1 LSB Full scale step Glitch energy 256 steps worst case NI 9263 Operating Instructions and Specifications 14 ni com Capacitive drive occ eeeeeees 1 500 pF min Monotonieita ce eeeeseeeseeeeeeeees 16 bits DNE sra nE E 1 to 2 LSBs max INL endpomnt ee eeeeeceeeeeeeeeee 16 LSBs max OR NEI KEE 1 732 619 hours at 25 C Bellcore Issue 2 Method 1 Case 3 Limited Part Stress Method 3 Note Contact NI for Bellcore MTBF specifications at other temperatures or for MIL HDBK 217F specifications Power Requirements Power consumpt
9. environment rohs_china Calibration You can obtain the calibration certificate and information about calibration services for the NI 9263 at ni com calibration Calibration interval sssssssseeeeeeeees 1 year National Instruments Corp 23 NI 9263 Operating Instructions and Specifications Where to Go for Support The National Instruments Web site is your complete resource for technical support At ni com support you have access to everything from troubleshooting and application development self help resources to email and phone assistance from NI Application Engineers National Instruments corporate headquarters is located at 11500 North Mopac Expressway Austin Texas 78759 3504 National Instruments also has offices located around the world to help address your support needs For telephone support in the United States create your service request at ni com support and follow the calling instructions or dial 512 795 8248 For telephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 662 457990 0 Belgium 32 0 2 757 0020 Brazil 55 11 3262 3599 Canada 800 433 3488 China 86 21 5050 9800 Czech Republic 420 224 235 774 Denmark 45 45 76 26 00 Finland 358 0 9 725 72511 France 01 57 66 24 24 Germany 49 89 7413130 India 91 80 41190000 Israel 972 3 6393737 Italy 39 02 41309277 Japan 0120 527196 NI 9263 Operating Instructions
10. ing Instructions and Specifications CE Compliance C This product meets the essential requirements of applicable European Directives as follows e 2006 95 EC Low Voltage Directive safety e 2004 108 EC Electromagnetic Compatibility Directive EMC Online Product Certification Refer to the product Declaration of Conformity DoC for additional regulatory compliance information To obtain product certifications and the DoC for this product visit ni com certification search by module number or product line and click the appropriate link in the Certification column Shock and Vibration To meet these specifications you must panel mount the system and either affix ferrules to the ends of the terminal wires or use the NI 9932 backshell kit to protect the connections Operating vibration Random IEC 60068 2 64 5 Sons 10 to 500 Hz Sinusoidal IEC 60068 2 6 5 g 10 to 500 Hz NI 9263 Operating Instructions and Specifications 20 ni com Operating shock IEC oOOeg 220 30 g 11 ms half sine 50 g 3 ms half sine 18 shocks at 6 orientations Environmental National Instruments C Series modules are intended for indoor use only but may be used outdoors if installed in a suitable enclosure Refer to the manual for the chassis you are using for more information about meeting these specifications Operating temperature IEC 60068 2 1 IEC 60068 2 2 40 to 70 C Storage temperature IEC 60068 2 1
11. ing Instructions and Specifications 10 ni com Sleep Mode This module supports a low power sleep mode Support for sleep mode at the system level depends on the chassis that the module is plugged into Refer to the chassis manual for information about support for sleep mode If the chassis supports sleep mode refer to the software help for information about enabling sleep mode Visit ni com info and enter cseriesdoc for information about C Series documentation Typically when a system is in sleep mode you cannot communicate with the modules In sleep mode the system consumes minimal power and may dissipate less heat than it does in normal mode Refer to the Specifications section for more information about power consumption and thermal dissipation National Instruments Corp 11 NI 9263 Operating Instructions and Specifications Specifications The following specifications are typical for the range 40 to 70 C unless otherwise noted All voltages are relative to COM unless otherwise noted Output Characteristics Number of channels 4 analog output channels DAC resolution cece eeeeeeeeetees 16 bits Type of DA String Power on output state oe Channels off Startup power down voltage Output voltage range Nominal is eege 10 V Minimum 10 3 V Typical oe eceeeeeseeeneeeneeees 10 7 V Maximum sinenion 11V NI 9263 Operating Instructions and Specifications 12 ni com Current deeg Steen 1 mA per chann
12. ion from chassis Active mode esssssssesesesesereeseee 625 mW max Sleep mode eect 25 uW max Thermal dissipation at 70 C Active mode sursisinizienisiirn 625 mW max Sleep mode nspernseraisaiiss 25 uW max National Instruments Corp 15 NI 9263 Operating Instructions and Specifications Physical Characteristics If you need to clean the module wipe it with a dry towel 3 Note For two dimensional drawings and three dimensional models of the C Series module and connectors visit ni com dimensions and search by module number Screw terminal wiring 0 0 0 0 eee 12 to 24 AWG copper conductor wire with 10 mm 0 39 in of insulation stripped from the end Torque for screw terminals 0 5 to 0 6 N m 4 4 to 5 3 Ib in 0 25 mm to 2 5 mm 150 g 5 3 oz NI 9263 Operating Instructions and Specifications 16 ni com Safety Safety Voltages Connect only voltages that are within the following limits Isolation Channel to channel 0 None Channel to earth ground Continuous uu ieee 250 Vms Measurement Category H Withstand oo eee 2 300 Vms verified by a 5 s dielectric withstand test Measurement Category II is for measurements performed on circuits directly connected to the electrical distribution system This category refers to local level electrical distribution such as that provided by a standard wall outlet for example 115 V for U S or 230 V for Europe A Caution Do
13. ss power has been switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of components may impair suitability for Class I Division 2 Caution For Zone 2 applications install the system in an enclosure rated to at least IP 54 as defined by IEC 60529 and EN 60529 gt be amp Special Conditions for Hazardous Locations Use in Europe This equipment has been evaluated as Ex nA IIC T4 equipment under DEMKO Certificate No 07 ATEX 0626664X Each module is marked II 3G and is suitable for use in Zone 2 hazardous locations in ambient temperatures of 40 C lt Ta lt 70 C If you are using the NI 9263 in Gas Group IIC hazardous locations you must use the device in an NI chassis that has been evaluated as Ex nC IIC T4 EEx nC IIC T4 Ex nA IIC T4 or Ex nL IC T4 equipment National Instruments Corp 5 NMI9263 Operating Instructions and Specifications Special Conditions for Marine Applications Some modules are Lloyd s Register LR Type Approved for marine applications To verify Lloyd s Register certification visit ni com certification and search for the LR certificate or look for the Lloyd s Register mark on the module Caution To meet radio frequency emission requirements for marine applications use shielded cables and install the system in a metal enclosure Suppression ferrites must