PROFIBUS NetTEST II User's Guide

image

Contents

1. 10 Screen Segment configuration 10 Screen Test with no term 13 Screen after Test with no term 13 Screen after Test with 1 term 16 Screen after Test with 2 term s 18 Screen Generate livelist 19 Screen Slave ident number 20 Screen Slave signal quality 21 Screen Baud rate detection 22 Screen Test protocol 23 Selection menu Test protocol 23 Screen Test protocol with PLC 24 Screen Test Company 26 Screen User name list 26 Screen Customer list 27 Screen Plant List 27 Screen System configuration 28 Screen Device properties 29 Screen License code 29 Screen Basic parameters 30 Screen GSD library 33 Connection Setting via COMI 35 Characteristics of the serial interface 36 Start up Screen with the PB Master 40 Screen Line test 40 Screen Profibus master mode 41 Screen Slave line up 41 Screen Slave line up 42 Sc
2. New FNL master New FNL slave NETTest master New DF32 L1 master New DF32 L1 slave Figure 39 Screen context menu in the Configurator COMSOFT 47 Systems with PROFIBUS Master Option e Select the PROFIBUS address baud rate and slot time in the NetTEST Master dialogue e Select a new Slave over the context menu of the NetTEST Master The context menu of the NetTEST Master can be accessed by pressing the right mouse button after selecting the NetTEST Master element of the tree like structure e Select the GSD of the Slave that is to be newly created from the file dialogue The Slave Configuration menu subsequently displayed enables the user to configure the bus subscriber if supported by the GSD file parameter data module definitions as well as module parameters Details to the Slave configuration may be found in the Configurator Online Documentation Configure Slave GSD Selection Slave Name Profibus Addr Ps 001 002 Cd mmm F 003 GSD Filename 004 4 Cfg Global sition xpse9510 gsd 005 xl Pim User Data DEMI GSD Description SyncModesupp 0 Read GSD MinSlavelntervall 6 E OPC Pesto MaxDiagDataLen 0x0F Conf Wdog Module Data P r Get Check Cg 32 byte inp 32 byte outp Inputs 032 Outputs 032 r Selected Module s List r Selectable Module s List Gta Em User Date t Cfg Def
3. NetTEST II format as described in chapter 5 2 3 5 Load parameter can be transmitted to the PC and saved see chapter 6 5 for procedure F In order to expand modify the parameter set it is recommended to load the existing parameter set onto the PC to modify and save it there and to eventually back load it onto the NetTEST II 32 COMSOFT NetTEST II Menu Guide 5 2 3 7 Firmware update The submenu Firmware update enables you to load possible firmware updates onto the test tool NetTEST IT see chapter 6 4 A fully charged accumulator is to be used as the update process must not be interrupted With a transition rate of 19 200 Baud the process takes approx 12 min 5 2 4 GSD library GSD Librar eu File Receive GSD File Delete GSD File Display Edit Figure 26 Screen GSD library The GSD library serves for the exchange of GSD files from the PC to the NetTEST II as well as for storing certain GSD contents Should the GSD files of the devices connected to one segment be stored on the NetTEST IL a reference between slave_ident_number and the device name can be made It is possible to store up to 128 GSD file content on the NetTEST II 5 2 4 1 New File It is not obligatory to load the GSD file onto the NetTEST II You can as well enter settings like device name slot time and ident number directly via the keyboard and store them in the data base COMSOFT 33 NetTEST II Menu Guide 5 2 4 2
4. DP Slave e CHK CFG REQ Configuration data which the DP Master transmits to the DP Slave e SLV DIAG RES Diagnostic data which the DP Slave transmits to the DP Master e DATA XCHG REQ Output data transmitted to the DP Slave e DATA XCHG RES Input data received from the DP Slave e GET CFG RES Configuration data which the DP Slave transmits to the DP Master By means of the key the event count display or the diagnostic event can be reset The event count display is updated by pressing the Bikey or after expiration of the adjusted event update time see chapter 8 9 COMSOFT 75 System with online functionality 8 9 Settings Livelist hold No Level timeout 82 s Level scrolling Ho Event update 82 s Modify with lt gt Figure 74 Screen Settings In the menu Settings the following properties regarding the online functions may be selected e Livelist hold Yes No Default No If the livelist hold is activated also sporadically detected DP Slaves at the PROFIBUS are stored in the livelist e Level timeout 2s 5s 10s 60s Default 2s If the adjusted level time expires the level measurement is proceeded with the next DP Slave With adjusted NetTEST II waits endless for a valid level measurement with the actual DP Slave This can be useful in connection with low baud rates or very slow DP Slaves e Level scrolling Yes No Default No With Level scrolling ac
5. Interface Date Time Extended Load parameters Send parameters Figure 22 Screen System configuration System configuration is for device specific settings like e g parameterization of the serial interface time settings firmware update and extended parameters Here also settings like turn on off key signal automatic switch off time of the tool illumination time for the background illumination of the screen and language selection for the screen text 5 2 3 1 RS232 Interface The built in serial interface serves for a data exchange with a PC On the PC side a terminal program is needed For a data exchange between NetTEST II and the terminal program e g Hyper Terminal Hilgraeve part of Microsoft operating systems the interface parameters like baud rate number of data bits parity number of stop bits and the used protocol must coincide The settings are needed for the menu points 5 2 2 4 5 2 3 7 as well as 5 2 4 2 For the settings on the PC side please see chapter 6 28 COMSOFT NetTEST II Menu Guide 5 2 3 2 Device properties Device properties Version SW U3 66A Serial number 666626 Master code 861B69 Online code 257T55 lt CR gt Modif Figure 23 Screen Device properties With the menu Device properties the version and serial number is displayed Additionally the options DP Master and Online functions can be activated if the appropriate license code is available Fu
6. Q Only then the recognized units are registered in the internal memory so that for these in the following test a Slave Diag Req can be run If the test is quit by no slave diagnosis can be executed afterwards COMSOFT 19 NetTEST II Menu Guide 5 2 1 6 Slave ident number Slave Ident number Slave 663 gt 6x9516 Slave 685 gt 6x6815 Slave 887 gt 8xfi fif Slave 668 gt 6x7516 uy Figure 12 Screen Slave ident number Via the Slave ident number menu the Ids for a better assignment of the DP Slave addresses to the unit type can be indicated Here a Slave_Diag_Request is executed on the respective device and this returns in its answer the ident number This will then be indicated behind the Slave address 20 COMSOFT NetTEST II Menu Guide 5 2 1 7 Slave signal quality Slave signal qualit Slave 663 Exp val 2 5U lt x lt 7 2U Real val 24 6 7 U State OK Figure 13 Screen Slave signal quality With the Slave signal quality the signal level of the addressed DP Slave is measured This should be with an impeccable unit and correctly terminated bus and a cable length of 1 m from the measuring point to the Slave at approx 6 3 Volt Per 100 m more cable between NetTEST II and the device to be scanned the level reduces by approx 0 2 Volt U lt 2 5 V Weak level or no longer detectable 2 5 7 2 V Level is ok U gt 7 2 V If the indicated level is gt 7 2 Volt this is a
7. Test with 2 terminators 18 5 2 1 5 Generate livelist 19 5 2 1 6 Slave ident number sssss 20 5 2 1 7 Slave signal quality 21 5 2 1 8 Baud rate detection seessss 22 5 2 2 Test protocol tee edes 23 5 2 2 1 Create new protocol ss 23 52 2 2 Delete is otio eere 25 5 2 2 3 Display c tn nent emus 25 5 2 2 4 Transmit esses 25 5 2 2 5 Test company 26 5 2 2 6 User name list 26 5 2 2 7 Customer list 27 5 2 2 8 Plant list esses 27 5 2 2 9 Segment list sen sennsenrcden 28 5 2 3 System configuration 28 5 2 3 1 RS232 Interface sssssssssss 28 5 2 3 2 Device properties 29 52 3 3 Date 7 Time Miss sheet et 30 COMSOFT i Contents 5 2 3 4 Basic parameters 30 5 2 3 5 Load parameters 32 5 2 3 6 Send parameters 32 5 2 3 7 Firmware update esee 33 5 24 GSD library 2 1 ie Hits 33 5241 New File oos 33 5 2 4 2 Receive GSD File 34 5 2 4 3 Delete GSD File 34 5 2 4 4 Display Edit 34 6 Communication with a PCs 35 6 1 Characteristics of HyperTerminal 35 6 2 COM Interface Configuration 36 6 3 Receive Test Protocol ett 37 6 4 Send File to NetTEST IL 38 6 5 Send file from NetTE
8. To make detections as easy as possible the generating of the livelist the Slave diagnosis and Slave related transmission level detection should be effected as well from the bus end However you can also make these from any other available measuring point within one segment Here please observe that the function of the livelist and of the SlaveDiag also work via a repeater segment coupler or optical coupler The level detection of a Slave connected via such a device reflects only the transmission level of the repeater and not the one of the detected Slaves 4 3 Measurement at the running bus The measurements at the running bus are limited to an indication of the current baud rate as well as of the general transmission level quality of the connected Slaves By this means a qualitative evaluation of the level on the bus line is made If the test tool shows reflections the reasons for those can only be found with the line detection which implies that the Master s is are being turned off 6 COMSOFT NetTEST II Menu Guide 5 NetTEST II Menu Guide 5 1 Start Up Setting in Operation Check the completeness of the scope of delivery and charge batteries before first setting in operation Remove the battery by gently pressing the locking and at the same time pulling down the battery placed at the rear lower side of the NetTEST II Now place the battery into the charging holder and check the loading procedure by means of the LED in the
9. battery charger For detailed information refer to the enclosed documentation of the battery charger Remove the battery from the charging holder and push it onto the NetTEST IT until you can hear it snapped in Now push the Okey approx Is until the PROFIBUS logo appears on the screen Then release the Okey Besides the PROFIBUS logo the firmware version and date appears for approx 2s SW U3 66A May 12 2883 15 36 66 Figure 2 Screen Start up Now the main menu is displayed automatically The test tool is ready for operation With various different text outputs the display is too small this will be indicated by at the right upper and vv at the right lower corner of the text By pressing the keys 00 you may scroll up or down in the text COMSOFT 7 NetTEST II Menu Guide 5 2 Main Menu The main menu automatically appears on the display after having started the NetTEST II Hain menu ine test Test protocol System configuration GSD library Figure 3 Screen Main menu The main menu comprises the following submenus e Line Test Test without PLC Stepwise check of cabling and test of DP Slaves without protocol generation PROFIBUS Master mode optional Set into operation of DP Slaves without PLC Test with PLC optional Detailed analysis of the telegram traffic and the physical state of the PROFIBUS line e Test Protocol Test without PLC Like Line Test Test without PL
10. device with unauthorized bus coupling a branch or switch over to a inadmissible cable type Error Possible broken line of shield of signal line A B distance XX m Result of the length measurement is significantly different for the various lines and shields Error uncertain situation possibly broken line of shield or of signal line A B Please repeat measurement at the opposite segment end Result of the cable length measurement for the various different lines and shields is so different that no specific statement about the respective line segment is possible Should the measurement on the other line end give correct results then the measurement may be considered o k In particular this effect may be observed with cable coils or cable drums in the PROFIBUS network COMSOFT NetTEST II Menu Guide With each of these error messages there may be an indication of a distance Some errors e g invalid termination do not give conclusive information about the distance Moreover all error messages may also include the indication uncertain error This may be indicated if the cause of the error could be detected only roughly thus permitting only an error estimation F Also with uncertain error situations the PROFIBUS segment has problems in any case even if the measured error is relatively small Due to EMV and high baud rates 21 5 Mbit this may lead to severe communication problems An effective method for determin
11. esee ttna etna 81 13 Problematic Slaves eere eee eee eerte enne netn ntn 82 14 Frequently Asked Questions FAQ 83 15 Technical Data eere eee eerte eene enne tn neonato 85 I5 IL NetL EST IL iie o eee en ee deri 85 15 2 Plug Charger coe Spo unten 86 Tables Table 1 Segment length specification 78 Table2 Pin assignment of D SUB 9 connector 80 Table3 Key allocation NetTEST II 81 Table 4 Technical data NetTEST II 86 Table 5 Technical data Plug charger 86 iv COMSOFT Figures Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6 Figure 7 Figure 8 Figure 9 Figure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 Figure 16 Figure 17 Figure 18 Figure 19 Figure 20 Figure 21 Figure 22 Figure 23 Figure 24 Figure 25 Figure 26 Figure 27 Figure 28 Figure 29 Figure 30 Figure 31 Figure 32 Figure 33 Figure 34 Figure 35 Figure 36 Figure 37 Figure 38 Figure 39 Figure 40 Figure 41 Figure 42 COMSOFT Contents Connection NetTEST IT in the cable thread 5 Screen STATUT Rite 7 Screen Main menu 8 Screen Test without PLC 9 Screen Segment list
12. sent cyclically from Slave to Master These values may not be changed 7 3 2 8 Edit DPTag output This option opens a submenu out of which the user may select one of the defined output tags Thereafter he has the option of entering data corresponding to the type of the tag F This is above all very helpful when sending float values to the Slave 7 3 2 9 Show DPTag input This option opens a selection menu where the user may select one of the defined input tags Thereafter the data corresponding to the type of the tag are displayed COMSOFT 59 Systems with PROFIBUS Master Option 7 3 2 10 Show Slave diagnostic In case the diagnostic data of the edited Slave changes the NetTEST II signals this through a followed by the message DATA EXCHANGE in the last line This option reads out the diagnostic data and displays them in a decoded mode as far as possible Due to the fact that the SLAVE_DIAG_REQ Service was performed the Slave resets this flag until the new diagnostic data occur 7 3 3 Single DP services By selecting Single DP services single PROFIBUS services for the currently selected Slave can be performed The following PROFIBUS services are integrated in the NetTEST II e SET_PRM_REQ e CHK_CFG_REQ e SLAVE_DIAG_REQ e DATA_EXCHG_REQ e GET_CFG_REQ e SET_SLAVE_ADDRESS_REQ e GLOBAL_CONTROL_REQ e RD_OUTP_REQ e RD INP REQ single services 651 SET PRH REQ HK CFG REQ SLAVE DIAG REQ DATA_EXCHAN
13. the Configurator to the NetTEST II via a download dialogue Receive CFG file Wait for partner Figure 41 Screen Receive CFG file COMSOFT 49 Systems with PROFIBUS Master Option The user reaches the download dialogue via the context menu of the NetTEST Master in the Configurator Kermit Download x Error count Last Error EN Baud Rate 12200 gt pus Download ComPort DataBits p StopBits ven le 1 le 7 1 C Odd ee 8 None Figure 42 Download Configurator Tool dialogue Was the configuration download performed successfully then with the NetTEST II the received configuration has to be confirmed by pressing the key Receive CFG file NetTest II CFG Size 6x064244 Figure 43 Confirmation Screen Receive CFG file Word of caution An existing configuration is only over written if this action is confirmed by pressing the key Is the key pressed instead the newly loaded configuration is discarded and the original status of the Master configuration is maintained 50 COMSOFT Systems with PROFIBUS Master Option 7 2 5 Slave menu In the Slave menu the user has the possibility to add or remove Slaves to from the configuration to check or reset all configuration settings to reach the Slaves via PROFIBUS services or activate them by means of the NetTEST II Slave menu New slave Process slave Figure 44 Screen
14. 2 5 1 3 User prm The second mask shows the User Param data for the Set_Prm_Req The user can enter the size of the User Param data in the bottom line By pressing the key the user will then reach the entries of the Hex values By pressing the key the entry mode can be switched from hexadecimal entry to ASCII entry The user can return to the hexadecimal entry by pressing the Q key If the data bytes are to be changed the numeric entry may be accessed by pressing the key This is confirmed by the Qo key 52 COMSOFT Systems with PROFIBUS Master Option User Prm 828 Len 16 Pos 888 Figure 47 Entry mask User prm 7 2 5 1 4 CFG Data The third mask shows the configuration data for the Chk Cfg Request Operation runs analogously to operation of the UserParamData entry dialogue Entry of the Slave definition is concluded once this dialogue has been successfully filled out Cfg data 020 SF F x1 pe Len 2 Pos 88 Figure 48 Entry mask Cfg data Note Creation of a PROFIBUS configuration can be performed much easier with the aid of the Configurator Tool as it is capable of evaluating GSD files directly and creating a Slave configuration without the deep knowledge of the details COMSOFT 53 Systems with PROFIBUS Master Option 7 2 5 2 Copy Slave This option enables the user to generate a 1 1 copy of an existing Slave configuration All related tag definitions are included in the copy see chapt
15. 8N1 8N2 RS232 protocol Kermit Test area cable length 5m 1500 m Measuring inaccuracy with 5 connected devices Measuring inaccuracy without 2 m connected devices Measuring area line 0 Q 250 Q impedance Measuring inaccuracy 5 line impedance Measuring range RS485 level 0 0 Vss 8 0 Vss Measuring inaccuracy with level detection 200 mV Dimensions 230 x 98 x 53 mm Weight with battery 530 g Battery 4 8 V 1500 mAh NiMH Operating duration with one battery 2 4 5h without background illumination gt 4h with background illumination Operating temperature range 10 C 40 C Storing temperature 20 C 45 C Class of protection 3 COMSOFT 85 Technical Data Degree of Protection IP50 Certification DIN EN 61326 1 Table 4 Technical data NetTEST II 15 2 Plug Charger Input voltage range 100 240 VAC 50 60 Hz Max input current 120 mA Power input Max 12 VA High voltage check 4kV Charge voltage 4 8 12 VDC Charge current Max 600 mA Charge time NetTEST II 3 5h Battery Red LED The red LED plays different roles 1 Signalise the faultless contact of the rechargeable battery during the test period approx 10 min 2 Signalise the right polarity of the rechargeable battery 3 Signalise a defect rechargeable battery or a wrong num
16. C however the results of all tests are stored in a test protocol for documentation purposes Test with PLC optional Like Line Test Test with PLC however the results of all tests can be stored in a test protocol for documentation purposes e System Configuration For all device specific settings e GSD library Submenu for the administration of GSD files COMSOFT NetTEST II Menu Guide 5 2 1 Test without PLC The menu Test without PLC serves for stepwise physical analysis of lines This means that the test can be executed as often as desired Some tests are based on the reference data of the preceding test so that this one must be run beforehand The individual items are interlocked so that wrong operation is impossible For tests run under this menu no protocol is made out Test without PLC Segment list Test with no tern Test with 1 term Test with 2 term Generate livelist Figure 4 Screen Test without PLC For a linetest at first the design parameters for the PROFIBUS segment that has to be checked must be indicated These indications are necessary so that e g the PROFIBUS DP specific measurements at the line segment may be executed with the real bus settings used in your plant The settings are made in the submenu Segment list F As soon as a option is activated DP Master or Online Function the Line test menu appears under Test without PLC COMSOFT 9 NetTEST II Menu Gui
17. Event log the NetTEST II analyses the data traffic between DP Master and DP Slaves and shows all changes of the communication state for every DP Slave The Event log is depicted in the form of a table The columns are described as follows e ADD Station address ADD upon request by DP Master an error telegram occurred e DATA OK DP Slave is in state DATA EXCHANGE NR No Response DP Slave is not responding e TRY DP Slave needs more than 1 request by the DP Master e CFG DP Slave was parameterised or configured e DIA Diagnostic messages occur at the DP Slave Normally a correctly configured DP Slave connected to the DP Master indicates the status OK data exchange During long term operation the PROFIBUS network all specific changes of the network can be monitored Even DP Slaves of the DP Master not yet configured but nevertheless part of the livelist are displayed By means of the Q key the event log can be reset The event log is updated by pressing the key or after expiration of the adjusted event update time see chapter 8 9 COMSOFT 73 System with online functionality 8 7 Event count Event count Slave 616 DATA_XCHG_RES 27982 NO RESPONSE RETRY SET_PRM_REQ CHK CFG REQ SLU DIAG REQ F2 Reset F3 Figure 72 Screen Event count A problematic DP Slave detected by the event log can be examined in detail by the Event count function The function event count displays in p
18. GE GET CFG REQ Figure 53 Screen Single DP services 60 COMSOFT Systems with PROFIBUS Master Option 7 4 DPTag definitions In order to depict and modify I O data of a DP Slave in a more easy way the NetTEST II allows definition of so called tags A tag is to be imagined as a data extraction from the I O data of a DP Slave As data transport can be in principle possible in two directions there are thus input or output tags Example A DP Slave has 8 digital outputs which may be set or reset over the first output Byte NetTEST II makes it possible to define in this output Byte per Bit a tag of Boolean type over which the corresponding output may be specifically controlled The corresponding Configurator Tool also allows definition of these tags comfortably over the PC Properties of tags e Name e Type e g Boolean Int Real e Sign in part implied in the type e g Real e Byte orientation big endian little endian MOTOROLA INTEL Tag s use modif Display edit tag Create new tag Delete tag Figure 54 Screen Tag s use modify COMSOFT 61 Systems with PROFIBUS Master Option 7 4 1 Display edit tag In order to Display edit tag one of the tags from the tag selection menu must be selected Display edit tag Pumpe 666 6 Pumpe 666 1 Pumpe 666 2 Pumpe 888 3 Pumpe 666 4 Figure 55 Selection menu Display edit tag By choosing one of the entries the ta
19. I Menu Guide 5 2 2 2 Delete With this menu you can delete existing test protocols from the database This should only be done if the corresponding protocol was sent to a PC via a serial interface or if the protocol is no longer needed 5 2 2 3 Display Stored test protocols cannot only be displayed on the PC but also be displayed again with this function Here the display is analogous to the display during measurement To go through the individual screens please use the key If the contents needs more space than available on the display you can scroll the screen window with Q o o keys 5 2 2 4 Transmit The test protocols are stored under the plant name and furthermore under the segment name If there should have been made several tests in the same segment these can be distinguished due to the test date and time Select the segment you want to send to the PC by the O O ys and confirm with For the settings to be made at the PC please see chapter 6 3 COMSOFT 25 NetTEST II Menu Guide 5 2 2 5 Test company In this menu you can enter your company name The data entered are issued in the test protocol Test compan Name COMSOFT GmbH Str Wachhausstr 5a City 76227 Karlsruhe Fone 8721 95497 8 Hail info comsoft de Figure 18 Screen Test Company 5 2 2 6 User name list Here the names of all users can be stored in a data base with 10 memory locations This saves time in case of multiple tes
20. PROFIBUS NetTEST II User s Guide COMSOFT PROFIBUS NetTEST II User s Guide Rev 2 5 Date August 05 2005 COMSOFT GmbH Wachhausstrasse 5a 76227 Karlsruhe Germany Phone 49 721 9497 0 Fax 49 721 9497 129 E mail support comsoft de Web www comsoft de This manual has been made up carefully however even after the most thorough checks errors might occur If you should find some or if you would like to suggest some improvements please do not hesitate to do so The information contained in this manual can be amended without prior notice and does not represent any obligation on the part of COMSOFT We do not assume any responsibility for errors or inconsistencies and their consequences Contents Table of Contents 1 Scope of Delivery seeessseeessoesessoessssessssoessssoessssossssoesessose 1 2 Safety AAVICE ccccsccccsccssccsscscecsscssecssscssessssssesssscsseeens 2 3 Introduction TEE E AAE EE RA 3 4 Line E E EER NAAR ET ETE T 5 4 1 Line Measurement 5 4 2 LiveList SlaveDiag and Level Detection 6 4 3 Measurement at the Running Bus 6 5 NetTEST II Menu Guide ss 7 5 1 Start Up Setting in Operation 7 5 2 Main Menu 8 5 2 1 Test without PLC sssseeneeeeee 9 5 2 11 Segment Tist tuse en BE 10 5 2 1 2 Test with no terminators 12 5 2 1 3 Test with 1 terminator ssss 16 5 2 1 4
21. Receive GSD File To prepare reception of GSD files sent from a PC the following steps must be performed e Start your terminal program on your PC e Settings of the terminal program analogous to settings of NetTEST II see chapter 5 2 3 1 and 6 e Connection of NetTEST II and the PC via the attached serial cable connector e Prepare NetTEST II for reception of GSD file Receive GSD File e Then select by means of the function Send file of the terminal function via the available browser the GSD file and send it by means of the protocol setting Kermit to the NetTEST II 5 2 4 3 Delete GSD File Delete GSD File serves for the deletion of GSD contents no longer needed Selection is made by means of the Q o keys 5 2 4 4 Display Edit To gain an overview over the already existing GSD files in the data base the contents can be viewed via Display Edit Selection by means of the Q o keys 34 COMSOFT Communication with a PC 6 Communication with a PC The communication with a PC for the functions Receive GSD File see chapter 5 2 4 2 Load send parame ter data set see chapter 5 2 3 4 and 5 2 3 5 Firmware Update see chapter 5 2 3 7 and Send Test Protocol see chapter 5 2 2 4 is made by means of a terminal program via the PC s COM interface With the Microsoft operating systems Windows 3 x 95 98 NT 2000 XP it is the HyperTerminal made by Hilgraeve which is part of delivery Below please find the necessary
22. ST II to the PC 39 7 Systems with PROFIBUS Master Option 40 Vol Slave line up nee ERRORES 41 T l3 Setoutputs inten pete 43 TLZ Read mp ts eniin E et 43 J4 1 3 Set yalue ineo ree 43 TIA Read value isto eos USERS 43 7 1 5 Read diagnostics sissien ienen 43 T Extended master ii eR ed 44 7 2 1 Master parameters 44 7 2 1 1 PROFIBUS Address 45 7 2 1 2 Profibus parameters 45 7 2 1 3 Copy from segment 46 7 2 2 Config with livelist eese 46 7 2 3 COMSOFT Configurator Tool 47 7 2 3 1 Creation of a configuration 47 7 2 4 Config with download 49 1 2 5 Slave menu sic inae 51 1 2 5 D NOW slave iiie ertet ete 51 7 2 5 2 Copy slave eiecit 54 7 2 5 3 Delete slave iit 54 7 2 5 4 Process slaye anses assise At 54 ii COMSOFT Contents 7 3 Pr cess slaven eee Anse sam 55 4 3 Editiparameters sind 55 7 3 1 1 Profibus address 56 7 3 1 2 General parameters 56 7 3 L3 Prm Gata iz emi epus 56 TILA Cte d t u i nos hosp 56 7 3 1 5 DP tag definitions 56 73 2 DAne5up iiie oie teet et 56 7 3 2 T Eamedip se cous cave ei annee sen 58 7 3 2 2 Edit slave address sssss 58 7 3 2 3 Edit slave parameters 58 7 3 2 4 Edit prm data 58 7 3 2 5 Edit Cfa Da
23. Settings see Chapter 8 9 Level scrolling is activated the display window is automatically shifted to display always the actual measured DP Slaves which guarantees a complete level measurement with all selected DP Slaves Any discrepancies of the levels in comparison to the nominal range indicate severe PROFIBUS network problems U 2 5 V Weak level or no longer detectable 2 5 7 2 V Level is ok U gt 7 2 V If the indicated level is gt 7 2 Volt this is an indication for a faulty power supply of the Slaves or for reflections at the bus COMSOFT 69 System with online functionality The level measurement can be conducted by means of the current livelist or a defined filter Signal level meas deas with livelist Heas with filter Figure 65 Selection menu Signal level measurement 8 4 1 Measurement with livelist For all DP Slaves contained in the current livelist a level measurement is performed 8 4 2 Measurement with filter For Measurements with filter the bar graph display can be adapted to the spatial distribution of the network A filter consists each of a name a list of stations and their order Meas with filter INS gt Change CR gt 0K vy Figure 66 Measurement with filter 70 COMSOFT System with online functionality 8 4 2 1 Define filter In the menu Define filter network specific data can be configured for the subsequent Level measurement The data is stored in the data base u
24. Slave menu 7 2 5 1 New Slave By choosing this option the user can newly define an additional Slave to the existing configuration 7 2 5 1 1 New address At the start of the creation process the user needs to select a new PROFIBUS address Each subscriber at the PROFIBUS segment has to possess his own individual address 661 NetTEST II Hast PROFIBUS DP 32 RH65H Figure 45 Selection menu New address COMSOFT 51 Systems with PROFIBUS Master Option A new Slave address has to be selected in the address selection menu Available PROFIBUS addresses are marked with In order to complete the definition of a new Slave three more forms need to be completed Each of these dialogues is to be concluded with pressing the Q key If at any time the key is pressed then the creation process for the Slave is interrupted and all entries made up to this point are discarded 7 2 5 1 2 Parameter General Slave parameters are to be entered in the first dialogue The parameters are needed for all PROFIBUS Slaves The Slave name is needed for further referencing within the NetTEST II The other parameters are standard parameters for the Set Prm Req and can be retrieved from the appropriate GSD file Ger testammdatei Name XPS Profibus lt gt Slave ident 6x9516 Param status 6x86 Tsdr min T1 WD1 6 WD2 86 Group ident 6 Figure 46 Entry mask Parameter 7
25. Start the transmission from your PC to NetTEST II Send with HyperTerminal The firmware update may not be interrupted Therefore please plug in a new battery in the NetTEST II The whole procedure takes approx 12 min with a set baud rate of 19 200 Baud COMSOFT Communication with a PC 6 5 Send file from NetTEST II to the PC In order to e g save parameter sets data must be able to be sent from the NetTEST II to the PC In this case proceed as follows Connect NetTEST II via the serial connection line included in delivery to the COM interface set in the terminal application Start the previously configured terminal application on your PC Click on Transmission File receive in the terminal application Enter the directory over the subsequent browser where the file to be received is to be saved Set the transmission protocol to Kermit Start the transmission receive in the PC e g Receive button in the Hyper Terminal Dialogue Start the receive command in the corresponding menu in the NetTEST II COMSOFT 39 Systems with PROFIBUS Master Option 7 Systems with PROFIBUS Master Option Systems featuring the PROFIBUS Master Option can be differentiated by their modified PROFIBUS screen start up logo depicted below SW U3 66A May 12 2883 15 36 66 Figure 29 Start up Screen with the PB Master The PROFIBUS Master Options are summarized in an additional menu item contained in the Line Te
26. The diagnostic data can then be viewed in the Show Slave diagnostic see chapter 7 3 2 10 These cyclic services are processed by a background process while the system remains responsive on the user side 56 COMSOFT Systems with PROFIBUS Master Option The Slave communication state is shown on the last display line Thus the user can check every time whether the communication with the Slave functions or whether a parameter configuration problem persists Possible messages on this line could be e No Answer No communication with the Slave can be established e g wrong address e Param Fault Parameterization of the Slave is incorrect e Cfg Fault Configuration data of the Slave are incorrect e Not Ready The Slave is not yet ready for data exchange e Param Req The Slave expects parameterization by the Master e DATA EXCHANGE The Slave was properly parameterized and configured Data exchange is taking place DATA EXCHANGE The diagnostic data at the Slave has changed By selecting the menu 7 3 2 10 Show Slave diagnostic the diagnostic data can be displayed and the in the display will be acknowledged There is an additional submenu for changing the configuration data or the output data or displaying the input data of the Slave COMSOFT 57 Systems with PROFIBUS Master Option 7 3 2 1 Line up The user herewith has the opportunity to constantly modify Slave config
27. ault Prm User Data 001 32 byte inp 32 byte outp 32 byte inp 4 byte outp 32 byte inp 8 byte outp 32 byte inp 16 byte outp 32 byte inp 32 byte outp 32 hute inn 64 hute oritn Figure 40 Slave Configuration Dialogue e Multiple Slave definitions may be created by repeating the last steps several times over e Choose the option New tag s on the context sensitive menu of the newly generated slave This menu may be opened by pressing the right mouse button provided that the slave is selected from the tree like structure 48 COMSOFT Systems with PROFIBUS Master Option e Create tag s over the dialogue by choosing from the tag properties and confirm by subsequently pressing the Add tag button In order to create several tag s this transaction may be repeated several times over e Upon completion of the configuration save the entire configuration under a unique configuration name Additional documentation relating to the COMSOFT Configurator Tool may be found in the Online Documentation of the Configurator F Should the user possess a PROFIBUS Master card or FNL from COMSOFT then the configuration may be checked in advance by setting to a DF PROFI or FNL Master by means of the Test change Expert mode and subsequently be converted to a NetTEST II Master for downloading 7 2 4 Config with download By means of Config with download the user may download the configuration file from
28. aves Currently COMSOFT knows of four PROFIBUS DP Slaves with problematic bus behaviour These are in particular the following systems e Pepperl amp Fuchs DP PA Koppler KDF2 e Beckhoff Wago older model of bus terminal 97 98 e Siemens ET200 B older model 96 98 e IFM Electronic DP ASI Gateway AC 0005 AC 0006 The problems result either from capacitive inductive screening measures on the PROFIBUS signal lines or from excessively long spur lines within the DP Slaves During the line tests with NetTEST II these devices causes the error message Error A lt gt B Capacitive load junction or Impedance changes For correct measurement of the PROFIBUS physics these devices are to be disconnected from the line It may not be excluded that in the future more PROFIBUS subscribers may become apparent through similar bus behaviour However DP Slaves that contain these screening measures do no longer pass official certification tests by accredited test labs 82 COMSOFT Frequently Asked Questions FAQ 14 Frequently Asked Questions FAQ Can NetTEST II also make measurements beyond a physical separation of the bus e g via repeaters or optical couplers No physical measurements via such bus connectors are not possible as these completely disconnect the segments by its incorporated drivers Can NetTEST II also detect devices connected to the bus via a Siemens PA Link No this is impossible as the PA Link operat
29. ber of cells 4 Signalise the discharge after pushing the discharge key Green LED Rechargeable battery is charged pulse conservation charging Output line 1 8m Dimensions w x h x d 60 x 47 x 106 mm Weight 280 g Operating temperature range 0 C 30 C Storing temperature 40 C 70 C Certification CE Table 5 Technical data Plug charger 86 COMSOFT
30. communication with NetTEST II 36 COMSOFT Communication with a PC 6 3 Receive Test Protocol To receive a test protocol from NetTEST II please proceed as follows Connect NetTEST II via the cable connector included in the delivery with the COM interface defined in the terminal program Start the configured terminal program on your PC In your terminal program click on Transfer Capture Text In the browser opening now enter the directory where you wish to save the test file Also indicate the file name for the test protocol Now click on Start Start the transmission from NetTEST II to the PC see chapter 5 2 2 4 When the transmission is finished the terminal program must be closed with Transfer Capture Text Stop COMSOFT 37 Communication with a PC 6 4 Send File to NetTEST II There are three kinds of files you can sent to the NetTEST II e g GSD files parameter data sets and firmware updates Follow the procedure below 38 Connect NetTEST II via the available serial cable connector with the COM interface defined in the terminal program Start the configured terminal program on your PC In the terminal program click on Transfer Send file Indicate in the browser opening now the directory where the file to be sent is stored Set the transmission protocol to Kermit Set NetTESTII to ready for reception in the corresponding menu either for Firmware Update 5 2 3 7 or Receive GSD File 5 2 4 2
31. complete i e all parameters have to be modified subsequently Moreover tag definitions of the process image may not be edited The user has to confirm the creation of the livelist as a possible configuration may be deleted Config with livelist Slave definitions Sure to delete lt Enter gt to delete Figure 38 Screen Config with livelist The detected Slaves are entered into the configuration for the Master 46 COMSOFT Systems with PROFIBUS Master Option 7 2 3 COMSOFT Configurator Tool By means of this tool the user can create complete PROFIBUS segment configurations inclusive all bus parameters and tag definitions 7 2 3 1 Creation of a configuration e Copy the GSD files of all used PROFIBUS Slaves into to sub directory GSD below the installation index of the COMSOFT Configurator Tool The Configurator needs these for the configuration of the DP Slaves e Start the COMSOFT Configurator The Configurator will depict a double window The left half of the window displays the configuration in the form of a tree like structure The right hand window displays the characteristics of the selected element e Choose NetTEST Master in the context menu The context menu can be accessed over the right mouse button when selecting the root element of the tree like structure Comsoft OPC Configurator File View Edit EditDatabase Help S oie x or fa New DFPROFI master New DFPROFI slave
32. de 5 2 1 1 Segment list Segment list Figure 5 Screen Segment list Under Segment list segment specific data are stored serving as basis for the following measurements The data are stored in the data base for line segments under the assigned segment name From there they can be used as basis for both individual tests and the creation of test protocols Indications must be made as to the points listed below e Name of line segment max 30 characters e PROFIBUS baud rate 9 6 Kbit s 12 Mbit s e PROFIBUS address for master operation of NetTEST II 0 126 e PROFIBUS slot time tslot 300 5000 Segment configuration Name Segment 1 PB Address 1 Baud rate 1 5 Mbaud Slot time 388 Connectors 1 Deuices 1 Figure 6 Screen Segment configuration 10 COMSOFT NetTEST II Menu Guide The PROFIBUS baud rate address and slot time are necessary for the parameterization of the installed PROFIBUS Master With these settings the tests Generate livelist Slave ident number as well as Slave signal quality are executed Moreover indications regarding number of e Connectors only number of 12 Mbit s plugs e Devices all devices with PROFIBUS plug or connected cable Connected devices and 12 Mbit s PROFIBUS plugs considerable change by their inductivity resp capacity the measuring abilities and characteristics for the NetTEST II In order to keep these measuring insecurities in a tolerable scale
33. e the data line has again to be disconnected from the segment via a bus disconnector No fault Correct termination Figure 10 Screen after Test with 2 term If the Test with 2 term was terminated successfully it can be taken for granted that the cabling in the segment was done correctly If during the test with NetTEST II an error should has been detected this would be depicted on the display by a graphic and text indication Possible error messages are described in detail in chapters 5 2 1 2and 5 2 1 3 18 COMSOFT NetTEST II Menu Guide 5 2 1 5 Generate livelist Generate livelist Device 63 found 16 656 656 657 658 659 698 R gt 0K Z ESC gt Cancel 1 Master Addr 661 Figure 11 Screen Generate livelist In the menu Generate livelist NetTEST II scans all possible bus addresses from 0 126 for PROFIBUS DP Slave participants For this a FDL request is effected several times on each address If a device answers with OK its bus address appears on the display The unit counter is incremented by one To ensure that also extremely slow units are recognized the test takes approx 30 seconds Should all connected units already be recognized the user can truncate the test with Should there be more units than depictable on one display screen the user can scroll through after the test with Q o keys To be able to execute further tests Generate livelist must by all means be terminated by
34. e detection With the function Baud rate detection the current baud rate on the running PROFIBUS is displayed During the baud rate scan additionally the all over signal level on the PROFIBUS is measured and evaluated U 2 5 V Weak level or no longer detectable 2 5 7 2 V Level is ok U gt 7 2 V If the indicated level is gt 7 2 Volt this is an indication for a faulty power supply of the Slaves or for reflections at the bus 66 COMSOFT System with online functionality 8 2 Generate livelist Device 34 Found 11 818 815 626 822 624 826 636 835 646 B44 646 CR gt OK Z ESC gt Cancel F2 Master Figure 61 Generate Slave livelist With the function Generate livelist the NetTEST II displays all active DP Slaves in connection with a DP Master All active DP Masters may be displayed as well using the o key Generate livelist 46 Found 1 CR gt OK ESC gt Cancel F2 Slave Figure 62 Generate Master livelist F The DP Master detects a new DP Slave on the PROFIBUS by sending out an FDL Request The device counter in the display Device XX indicates in which address range 0 127 the DP Master is scanning COMSOFT 67 System with online functionality 8 3 Rotation time Rotation time Value 5 6 ms 7588 tbit Hin 4 8 ms 7288 tbit Hax 14 6 ms 21888 tbit CR 0K ESC Cancel Figure 63 Rotation time The Rotation time is the time the DP Master needs to poll all confi
35. ender Changer DB9M DB9M one Gender Changer DB9F DB9F one Transport case one User s guide one COMSOFT Configurator Tool for DP Master Option COMSOFT 1 Safety Advice 2 Safety Advice The NetTEST II may only be operated with licensed NiCd batteries or NiMH batteries Do not immerse battery pack under water or expose it to open fire Do not open battery pack and do not try to replace individual battery cells Do not dispose of faulty battery packs with normal household garbage The battery pack could warm up during charging This is a normal process and not dangerous Do not use other chargers than supplied and specified by COMSOFT the batteries could otherwise be damaged Do not use NetTEST II in surroundings with explosion hazard In case that water or other liquids should have penetrated your NetTEST II remove the battery pack or the power supply adapter Then have your NetTEST II checked by our Service Department The same applies for the battery charging holder and the plug in battery charger COMSOFT Introduction 3 Introduction With the PROFIBUS NetTEST II you have acquired a high quality tool for the examination of RS485 based PROFIBUS segments COMSOFT 5 aim is to provide its users with a valuable tool for an easy check without extensive test methods of the correct cabling of their PROFIBUS net and to document this Furthermore the search for errors in already installed PROFIBUS system
36. er 7 3 1 5 DPTag definitions In the first step the user has to select from the list of existing Slaves the one that is to be duplicated Cop slave 663 Profibus DP 32 665 RH65H WINbloc 32DI B I0 K DP 885 Figure 49 Selection menu Copy slave Upon selection of one of the listed Slaves the user has to choose a new PROFIBUS address for the copy Each subscriber at the bus segment has to possess his own individual address The address selection takes place by means of the address selection menu see chapter 7 2 5 1 Further entries are not necessary for generating a Slave copy 7 2 5 3 Delete Slave Selection of a Slave to be deleted takes place analogously to the selection of the Slave to be copied in chapter 7 2 5 2 Deletion has to be reconfirmed by pressing the key 7 2 5 4 Process Slave Process Slave signifies the configuration of Slave related parameters editing modifying deleting of tag definitions of the Slave operation as well as activating the Slave through PROFIBUS single services Details of this option are described in detail in chapter 7 3 54 COMSOFT Systems with PROFIBUS Master Option 7 3 Process Slave Process Slave is the core PROFIBUS Master functionality of the NetTEST II Selection of the Slave to be edited takes place analogously to the selection of the Slave to be copied in chapter 7 2 5 2 822 XPS E Edit parameters Line up Single DP services Figu
37. es as an individual Slave in the bus and there during a Slave diagnosis only the address of the PA Link is visible Is it possible to indicate exactly the fault position e g short circuit A B between Slave 24 and Slave 25 This is certainly desirable but impossible due to the physical conditions of the PROFIBUS segment Does NetTEST II line test also work with other RS485 based buses If on the other bus no bus terminators are installed also any other RS485 based bus can be tested However as the correct termination is specifically made out to the PROFIBUS terminators the tool is rather unsuitable for testing other bus systems Why can the line test only be performed at the non active bus For checking the line physics NetTEST II carries out static level detection as well as reflection measurements If there was one active master at the bus this would strongly influence the measurements and make them useless Can NetTEST II make the tests in any place within a PROFIBUS segment No The physical line analysis can only be made from one bus end The other protocol specific tests can be made from any connection in the segment COMSOFT 83 Frequently Asked Questions FAQ 84 How is the connection to be made if only participants with PG screwing resp screw terminals are connected to the bus Should these participants be placed at both bus ends the user must provide an additional D SUB connector for test purpo
38. eters or setting the PROFIBUS Master parameter by selecting pre defined segments Haster parameters Figure 35 Screen Master parameters 44 COMSOFT Systems with PROFIBUS Master Option 7 2 1 1 PROFIBUS Address Other address 881 NetTEST II Hast PROFIBUS DP 32 RH65H Figure 36 Screen Other address From the address menu an entry may be selected that is not in use by another PROFIBUS device This is marked by in the address selection menu each device at the PROFIBUS segment has to have his own individual address 7 2 1 2 Profibus parameters By choosing this option the PROFIBUS Master parameters of the NetTEST II are displayed Modifications are done by entering new parameters and subsequently pressing the key daster configuration NetTEST II 21 5 Hbaud 388 Figure 37 Entry mask Master configuration COMSOFT 45 Systems with PROFIBUS Master Option 7 2 1 3 Copy from segment The Master parameters may also be set by choosing one of the pre defined segments The PROFIBUS segment definition contains all necessary parameters for the configuration of the NetTEST II as the PROFIBUS Master See also chapter 5 2 1 1 for more information on segments 7 2 2 Config with livelist By means of Config with livelist the user has the option of making a configuration using the current Slaves from the segment The bus configuration is however in
39. g parameters may be displayed edited T Boolean Start 8 8 End 6 6 Sign False Order Intel order Dir Output tag Figure 56 Entry mask Tag data A particularity of the tag properties is the bit granular resolution in the core image of the PROFIBUS Slave In the tag properties mask the tag start is defined by lt Startbyte Startbit gt and the tag end by lt Endbyte Endbit gt 62 COMSOFT Systems with PROFIBUS Master Option 7 4 2 Create new tag By selecting Create new tag a new tag may be entered For entering the tag properties please use the same properties mask as in chapter 7 4 1 Display edit tag 7 4 3 Delete tag When selecting Delete tag the same tag selection menu opens as in chapter 7 4 1 Display edit tag By selecting one of the tags from the list the corresponding definition may be deleted COMSOFT 63 System with online functionality 8 System with online functionality Devices with activated online functionality can be identified by their modified PROFIBUS screen start up logo depicted below SW U3 66A May 12 2883 15 36 66 Figure 57 Start up Screen with Online Function The NetTEST II online functions can be selected in a Line test menu item within the Line test menu list Test without PLC Profibus master mode Test with PLC Figure 58 Screen Line test The NetTEST II uses the online functions while operating in a completely passive monitoring mode T
40. gment length F Detections in segments with PROFIBUS plugs with a disconnection function can be tricky If e g in the middle of a segment the terminator of such a plug is activated the NetTEST II recognizes it if it is measured from the entrance side However if the measurement is made from the other end of the plug measuring is made into the open end and a cable length shorter than the one expected is indicated Therefore please check very thoroughly if all bus terminators are switched off Another possibility of finding such a plug is measuring from the other side of the bus 12 COMSOFT NetTEST II Menu Guide Test with no term Measure cable length Figure 7 Screen Test with no term The Test with no term lasts for a few seconds The duration depends on the cable length To show the user that the system is still working a star bar appears on the lower left hand side of the display as progress indication Terminate the test with Upon conclusion the result will be displayed Attention If you quit the test with QD the Test with 1 term cannot be executed any more as the just scanned data were deleted If no error is detected on the PROFIBUS segment a positive acknowledgement message will appear displaying the cable impedance and cable length according to the following figure fm Eg 8 OK No fault Cabeling ok Impedance app 156 Ohm Cable length 4m Figure 8 Screen after Tes
41. gured DP Slaves once The minima and maxima values measured here are saved and displayed The rotation time is an unambiguous indicator for performance problems i e in a sporadic non functional DP network Moreover the NetTEST II informs whether the PROFIBUS project planning meets system requirements as the PROFIBUS overall rotation time must in any case be smaller than the system reaction time required F Tbit is the time measurement unit for the transmission of a single Bit on the PROFIBUS depending on the baud rate For example 1 Tbit with 12 Mbaud 1 12 000 000 Bit s 83 ns 68 COMSOFT System with online functionality 8 4 Signal level measurement PEs 4 2 4 4 4 2 4 2 6 616 615 622 626 636 Figure 64 Signal level measurement The NetTEST II measures the RS485 driver output level of each individual DP Slave and displays them in a bar graph Below the bar graph the DP Slave address is indicated Above the bar graph the actual RS485 driver output level appears in Volt The minima and maxima values are stored right beside the bar graph as a scale line symbol The rotating slash indicates the DP Slave actual measured In the menu Settings see Chapter 8 9 the duration of the single measuring can be increased which enables the measuring even of very slow DP Slaves Only the visible DP Slaves max 5 are measured By means of the OO kcy the display window can shifted to switch to the remaining DP Slaves If in the menu
42. he equipment performs a detailed analysis of the telegram traffic and the physical state of the PROFIBUS line 64 COMSOFT System with online functionality Test with PLC Baud rate detection Generate livelist Rotation time Signal level meas Signal level sum list Event log Figure 59 Screen Test with PLC In the following the online functions Tests with PLC are listed e Baud rate detection chapter 8 1 e Generate livelist chapter 8 2 e Rotation time chapter 8 3 e Signal level measurement chapter 8 4 e Signal level summary list chapter 8 5 e Event log chapter 8 6 e Event count chapter 8 7 e Diagnostic event chapter 8 8 F The DP Slave oriented signal level measurement can be very time consuming in connection with low baud rates or low data traffic The NetTEST II can be connected directly to a free PROFIBUS plug in the network Also connection between a PROFIBUS plug and the respective DP Slave via an adapter cable PROFIBUS Y cable see accessories is possible In general you should exercise care in connecting the NetTEST II to running bus systems At higher baud rates 2 1 5 Mbit spur lines are strictly forbidden because the data traffic may be significantly disrupted COMSOFT 65 System with online functionality 8 1 Baud rate detection Baud rate detection Baud rate 1 5 Mbaud RS485 signal level Exp val 2 5U x 7 2U Level 6 1U State OK Figure 60 Baud rat
43. ing errors in their position is to divide the segment into several sub segments and to submit them to separate examinations F Allerror indications are also displayed with the Qo key COMSOFT 15 NetTEST II Menu Guide 5 2 1 3 Test with 1 terminator Prior to the Test with I term in any case the Test with no term must be completed If this was not made the user is being informed about this and can immediately make up for this test For the Test with 1 term the terminator at the bus end opposite to the NetTEST II must be switched on and set under current With a DP Slave unit or another passive bus participant the plug can be connected directly the terminator added and the unit switched on If the unit at the end of the line segment is a PROFIBUS Master take care that the bus participant does not actively send data onto the bus This can e g be realized by a bus disconnector Via the bus disconnector the bus terminator in the PROFIBUS plug is supplied with power but the bus line is interrupted by a mechanical switch in direction to the line segment Upon conclusion of the test the result will be displayed on the screen If no error is detected with the Test with I term on the PROFIBUS segment a positive acknowledgement will appear according to the following figure No fault Correct termination Figure 9 Screen after Test with 1 term 16 COMSOFT NetTEST II Menu Guide In case of errors the fol
44. ion menu Display edit tag 62 Entry mask Tag data 62 Start up Screen with Online Function 64 Screen Line test 64 Screen Test with PLC 65 Baud rate detection 66 Generate Slave livelist 67 Generate Master livelist 67 Rotation iMenso iiser iue ierse eses 68 Signal level measurement 69 Selection menu Signal level measurement 70 Measurement with filter 70 Screen Filter name 71 Screen DP Slave list 71 Screen DP Slave sorting 72 Screen Signal level summary list 72 Screen Event 108 73 Screen Event count 74 Screen Diagnostic event 75 Screen Settings iesu e Ute 76 COMSOFT Scope of Delivery 1 Scope of Delivery Included in the scope of delivery of the NetTEST II service case are the following items one PROFIBUS NetTEST II cable tester two battery packs NiMH 4 8 V 1500 mAh one battery charging holder one 230 VAC plug in battery charger power supply adapter one PROFIBUS Stub line 0 15 m DB9M DB9M one RS232 Cable connector DB9M DB9F one PROFIBUS Y Cable 0 15 m DB9M 2xDB9F one PROFIBUS Bus disconnector DB9M DB9F one Gender Changer DB9M DB9F mounted on NetTEST II one G
45. lines can be e g repeaters or optical couplers They do not have any negative influence on the signal quality of the bus Passive stub lines however e g bus terminals or simple cable stubs have to be avoided in every case In general it is claimed that with low baud rates lt 500 Kbit s no or only minor reflections occur however this does not comply with the reality The reflections are there even if they might not affect the data traffic with low baud rates as there is enough time for the signal to transiently match the corresponding value COMSOFT 79 Pin Assignment 11 Pin Assignment NetTEST II disposes of only one 9 pin D SUB connector This can optionally be switched to PROFIBUS or RS232 mode Pin PROFIBUS RS232 1 nc nc 2 RxD 3 TxD RxD B 4 GND 5 nc nc 6 nc nc 7 TxD 8 TxD RxD A 9 nc nc Shield Shield Shield Table 2 Pin assignment of D SUB 9 connector 80 COMSOFT Key Allocation 12 Key Allocation NetTEST II is equipped with a 24 key matrix keyboard In order to be able to enter also alphanumeric characters for the manifold data memories the following table shows the multiple key allocation 7 Q x 2 push 8 push jh T 3 a a 2 n e O6 30000000000000 mio ES L gt t o Cursor down Table 3 Key allocation NetTEST II COMSOFT 81 Problematic Slaves 13 Problematic Sl
46. lowing error messages may be displayed e Error no termination or switch defect No valid termination could be detected e Error Your terminator is not at the far end of the segment Contrary to the instruction the terminator was switched at the near segment end e Error A lt gt B twisted Mix up of signal lines e Error A lt gt shield B lt gt shield short circuit There is a low ohmic resistance in the cable between signal wire and shield e Error A lt gt B short circuit or bus terminal without power supply There is a low ohmic resistance in the cable between the signal wires e Error A lt gt B Irregularity Wrong termination or illegal termination There is an inadmissible ohmic resistance between the signal wires that stands in no relation to the magnitude of a bus termination either with or without power supply for example caused by a wrongly connected bus termination The Test with 1 term must also be terminated by the key in order to be able to execute the following test COMSOFT 17 NetTEST II Menu Guide 5 2 1 4 Test with 2 terminators Following the Test with 1 term the Test with 2 term is started Here it is checked if the bus terminator at the line end of the NetTEST II was switched on additionally For this test the terminator must also be supplied with power This can easily be done from the last unit in the segment If this should be a Master which cannot be made passiv
47. n indication for a faulty power supply of the Slaves or for reflections at the bus COMSOFT 21 NetTEST II Menu Guide 5 2 1 8 Baud rate detection Baud rate detection Baud rate 1 5 Mbaud RS485 signal level Ext val 2 5U x 7 2U Level 6 1U State OK Figure 14 Screen Baud rate detection With the menu point Baud rate detection a running bus with active Master is monitored and the current baud rate is indicated During this baud rate scan the general signal level at the bus is being measured analogous to Slave signal quality see chapter 5 2 1 7 Here the user receives immediately and without needing an oscilloscope an indication as to existing reflections at the bus or if the detected level is too weak Here the level is also indicated in Volt and a status is indicated F If the Online Function is activated the menu Baud rate detection appears under Test with PLC see chapter 8 1 22 COMSOFT NetTEST II Menu Guide 5 2 2 Test protocol Test protocol Delete Display Transmit Test company Figure 15 Screen Test protocol Test protocol serves for creating measuring protocols needed for documentation purposes In addition to the test data the user has the possibility to define plant specific data like plant name line segment name customer data for the test protocol 5 2 2 1 Create new protocol In the menu Create new protocol all steps necessary for the test protocol are execu
48. nched and the DP Master starts the DP State Machine to get the Slave into operation The actual communication state of the Slave is displayed in the last line of the display Possible messages e no response There is no response from the selected Slave e g the PROFIBUS address is wrong or the Slave is disconnected e in operation The Slave is working properly input and output data are transferred e in operation The Slave is working properly and reports external diagnostic data By selecting the menu Read Diagnostic Data the diagnostic data can be read from the Slave and the in the display is reset e Other messages The Slave is connected to the bus but the param or config data are not correct and the Slave cannot be set into in operation state If the Slave reaches the state in operation output data can be modified and input data can be displayed line up 665 et outputs Read inputs Set value Read value Read diagnostics in operation Figure 33 Screen Slave line up 42 COMSOFT Systems with PROFIBUS Master Option 7 1 1 Set outputs The output data of the Slave can be modified as described in chapter 7 2 5 1 3 7 1 2 Read inputs The input data received from the Slave are displayed Modifying of this data is not possible 7 1 3 Set value Output values are an extraction from the output data stream of the Slave With output values it is possible to access for e
49. nction release Master code Online code 861B69 247755 Figure 24 Screen License code If a wrong license code is entered and confirmed with the key the indicated license code changes to COMSOFT 29 NetTEST II Menu Guide 5 2 3 3 Date Time To furnish the test protocols with time and date indications NetTEST II is equipped with a quartz clock In the submenu Date Time the clock can be set The quartz clock is fed from the battery If this battery should be empty or removed the clock is energized by a maintenance free capacitor This capacitor provides the clock with energy for about 2 weeks If within this period of time the battery pack is not charged time settings are lost If this case should arise the user is advised that when turning on the tool the clock has to be reset 5 2 3 4 Basic parameters Basic parameters Key signal No PWR off time 36 min Illumination 18 sec Language english Modify with lt gt Figure 25 Screen Basic parameters 5 2 3 4 1 Key signal The NetTEST II is equipped with a loudspeaker If the key signal is turned on each key pressing is confirmed with an acoustic signal This can be activated or deactivated by the Qo o keys 30 COMSOFT NetTEST II Menu Guide 5 2 3 4 2 PWR off time To save battery power NetTEST II can be programmed by the PWR off time function with a time after which the tool switches off automatically The
50. nder the selected filter name In the following every single step for the filter definition is described 1 A filter name with up to 30 characters can be defined Define filter Name Filter 1 Figure 67 Screen Filter name 2 In the DP Slave list the DP Slaves for the level measurement can be selected By means of keys or DP Slave may be added or dropped Define filter LL Haster LL Slaue INS Sel Del UnSel vy Figure 68 Screen DP Slave list F All livelist members are indicated in the DP Slave list as either LL Master livelist DP Master or LL Slave livelist DP Slave COMSOFT 71 System with online functionality 3 The DP Slave selected in step 2 may be moved in the DP Slave sorting by means of keys or Define filter Slave 662 lave 616 Slave 666 Slave 614 Slave 612 DEL Cut INS Paste uu Figure 69 Screen DP Slave sorting 8 5 Signal level summary list Figure 70 Screen Signal level summary list In the Signal level summary list the result of the level measurement is displayed in table format e ADD Station Address e COUNT Number of measurements excl timeouts e MIN Minima value e AV Average value e MAX Maxima value 72 COMSOFT System with online functionality 8 6 Event log ADD DATA TRY CFG DIA 818 OK St RS eal ns est F2 Reset F3 Redo vy Figure 71 Screen Event log In the menu
51. performs a detailed analysis of the telegram traffic and the physical state of the PROFIBUS line To make installation checks and error retrieval as easy as possible we divided this manual into the following sections e Line tests e Menu guide e PC connection e DP Master functionality optional e Online functionality optional e Tips amp Tricks We hope that we can give you with our test tool NetTEST II and this manual all necessary means for a faultless function of your PROFIBUS plant In case of queries please contact our hotline we will be pleased to help you with our advice 4 COMSOFT Line Tests 4 Line Tests 4 1 Line Measurement Generally measurements regarding line physics can only be made from one end of the PROFIBUS line If you try to measure from any other place within the segment you will obtain faulty results Furthermore please make sure that during measurements no Master is polling the bus or is sending tokens Pure PROFIBUS DP Slave devices as well as e g repeaters and optical couplers must not be disconnected from the bus An oversight over the possible measuring points in line segments for line measurement is depicted below Terminator Master Slave r Repeater Segment coupler Optical coupler Segment 1 Segment 2 p Measuring point Figure 1 Connection NetTEST II in the cable thread COMSOFT 5 Line Tests 4 2 Livelist SlaveDiag and Level Detection
52. please indicate before each measurement the number of installed 12 Mbit s plugs as well as the number of the devices connected to the bus Please only indicate the plugs which dispose of incorporated direct axis inductances Devices stands for all units connected to a bus segment This applies to Master and Slaves as well as to net components like segment couplers repeaters optical couplers etc Once the data are stored in the data base they can always be used for new tests The data in this data base cannot be deleted only changed by overwriting In order to have enough spare capacity for this function 20 memory locations are available The respective memory locations can be reached by actuating the Q or the o key COMSOFT 11 NetTEST II Menu Guide 5 2 1 2 Test with no terminators At the beginning of each test the Test with no term must be carried out For this the NetTEST II must be connected to one end of the PROFIBUS segment Now the user makes sure that all bus termination resistors terminators in the bus segment are switched off resp removed Furthermore no Master may send data via the bus Then the Test with no term can be carried out If by accident a bus terminator or Master should be active in the segment the NetTEST II recognizes and indicates this at once Only if no more resistance in the thread is activated and all Masters are deactivated the NetTEST II informs about e Line impedance e Line length se
53. re 50 Screen Process slave 7 3 1 Edit parameters With Edit parameters another menu selection is entered that further defines the possible parameters 822 XPS E Profibus address Generel parameters Prm data Cfg data DPTag definitions Figure 51 Screen Edit parameter COMSOFT 55 Systems with PROFIBUS Master Option 7 3 1 1 PROFIBUS address Changing these parameters takes place analogously to editing a Slave see chapter 7 2 5 1 7 3 1 2 General parameters Changing these parameters takes place analogously to editing a Slave see chapter 7 2 5 1 7 3 1 3 Prm data Changing these parameters takes place analogously to editing a Slave see chapter 7 2 5 1 7 3 1 4 Cfg data Changing these parameters takes place analogously to editing a Slave see chapter 7 2 5 1 7 3 1 5 DP tag definitions Selecting this menu option launches the Tag editing menu The user may find further documentation in chapter 7 4 DP 7 3 2 Line up Selecting Line up will start the DP State Machine in the NetTEST II for the currently selected Slave The PROFIBUS services SET_PRM_REQ CHK CFG REQ and SLAVE_DIAG_REQ continue to be performed in this case until the result of the SLAVE_DIAG_REQ signals that the Slave is ready for the DATA_XCHG_REQ Thereafter the DATA_XCHG_REQ service is performed cyclically If the Slave signals a diagnostic change the NetTEST II reads the diagnostic data from the Slave
54. reen Extended master 44 Screen Master parameters 44 Screen Other address 45 Entry mask Master configuration 45 Screen Config with livelist 46 Screen context menu in the Configurator 47 Slave Configuration Dialogue 48 Screen Receive CFG file 49 Download Configurator Tool dialogue 50 Contents Figure 43 Figure 44 Figure 45 Figure 46 Figure 47 Figure 48 Figure 49 Figure 50 Figure 51 Figure 52 Figure 53 Figure 54 Figure 55 Figure 56 Figure 57 Figure 58 Figure 59 Figure 60 Figure 61 Figure 62 Figure 63 Figure 64 Figure 65 Figure 66 Figure 67 Figure 68 Figure 69 Figure 70 Figure 71 Figure 72 Figure 73 Figure 74 Confirmation Screen Receive CFG file 50 Screen Slave Menu 51 Selection menu New address 51 Entry mask Parameter eeeeeeeeereeeeeeeeee 22 Entry mask User prm n se 53 Entry mask Cfg data 53 Selection menu Copy slave 54 Screen Process slave 55 Screen Edit parameter 55 Screen Line Up hassan ns 58 Screen Single DP services 60 Screen Tag s use modify 61 Select
55. rinciple the same events as the Event log but the status changes of the DP Slave can be analysed in detail The following events are counted 0 99999 e DATA XCHG RES DATA Station is in state DATA EXCHANGE e NO RESPONSE DATA DP Slave doest not respond e SET PRM REQ CFG DP Slave was parameterized e CHK CFG REQ CFG DP Slave was configured e SLV DIAG REQ DIA Diagnostic messages occur at the DP Slave e TRY DATA Number of repeated requests by the DP Master until the DP Slave responds e ERR DATA Error Telegram upon request by the DP Master By means of the o key the event count display can be reset The event log is updated by pressing the Bikey or after expiration of the adjusted event update time see chapter 8 9 74 COMSOFT System with online functionality 8 8 Diagnostic event SLU DIAG RES 618 SLU DIAG Data nn 88 64 66 81 75 u 42 83 B Ext Diag 1 8x7518 Figure 73 Screen Diagnostic event The Diagnostic event is an extended function of the Event count and provides the detailed analysis of an event NetTEST II offers a selection of 6 different events that may be triggered With the occurrence of the selected event all relevant data are displayed Depiction is in plaintext as far as possible depiction in binary ASCII mode is also possible The following events can be selected e SET_PRM_REQ Parameter data which the DP Master transmits to the
56. s shall be as easy as possible We guess that we reached this target with NetTEST II the 2 generation of COMSOFT PROFIBUS test tools Therefore it goes without saying that with NetTEST II the checks can be run with connected and disconnected devices It does not matter if the devices are powered or not For physical testing you only have to ensure that there is no active Master PLC polling the bus Besides the standard cable test i e the verification of the lines regarding cable length line impedance correct termina tion cable rupture broken shield stub lines inhomoge neous cable segments mixed up cables short circuits faulty PROFIBUS connectors and faulty device connec tions NetTEST II disposes of PROFIBUS DP specific test functions So e g the livelist and the Slave Ident Number are indicated also the transmission level of the Slaves connected to the bus is detected per device Furthermore NetTEST II detects the current baud rate at the running bus During the baud rate scan a signal analysis indicates faults or errors in the cabling COMSOFT 3 Introduction Apart from these basic functions the following options are available for NetTEST II e DP Master Option With the DP Master Option the set into operation of DP Slaves is possible without the PLC The DP Slaves can be configured with the COMSOFT PROFIBUS configuration tool based on the DP Slaves appropriate GSD file e Online Function This function
57. selection is made by the Qo o keys The character in the selection means the system does not shut down F For the creation of test protocols in large plants the off time should be set to 30 min to make sure that e g test results of the Test with no term needed for the following Test with 1 term will not get lost by an untimely switch off of the tool 5 2 3 4 3 Illumination With Illumination the O kys serve for setting the period of screen illumination time after the last key touch If not absolutely necessary we recommend to turn it off due to the higher current consumption tt The character in the selection means the system does not turn off the background lighting 5 2 3 4 4 Language You can select between two languages for the display screen English and German Setting again via the Qo o keys COMSOFT 31 NetTEST II Menu Guide 5 2 3 5 Load parameters In the submenu Load parameters the user can receive parameter data sets from the PC see chapter 6 4 for procedure The parameter data set comprises all parameters that are or may be set by the user of the NetTEST II e General parameters e Customers e Test persons e Plant e Segments e Test company e GSD definitions Additionally will be stored for systems with Master Option e Master Parameter e Slave Parameter e Tag Definitions 5 2 3 6 Send parameters In the submenu Send parameters the parameter set of the
58. ses COMSOFT will soon offer a spring clip terminal block as accessory for the one core connection Please ask our sales department for availability Can NetTEST II detect double allocated PROFIBUS DP Slave addresses No sorry in the current version this is not possible We are working on a clear detection of such errors Is it possible to implement in NetTEST II a PROFIBUS bus monitor for monitoring the telegram traffic on the bus No For monitoring telegrams neither the screen possibilities nor the memory are sufficient Can NetTEST II also perform further test functions e g parameterization and configuration of a Slave Yes parameterization and configuration of a PROFIBUS DP Slave is possible with the DP Master Option With this option it is also possible to line up a DP Slave If a DPSlave supports the Set Slave Addr Service the address of the DP Slave can be changed COMSOFT 15 Technical Data 15 1 NetTEST II Technical Data Display LCD 128 x 64 pixel Matrix Screen with background illumination and protective glass Keyboard 4 x 6 Key Silicone Keyboard Loudspeaker Piezo Beeper Quartz clock Backup without t 14 tags battery Connections DB9 connector PROFIBUS data rates 9600 bit s 12 Mbit s PROFIBUS Slot Time Range 300 5000 RS232 data rates 300 115200 bit s RS232 interface protocol Data bits parity stop bit 7El 7E2 701 702 7N1 7N2 8E1 8E2 801 802
59. settings for the communication with NetTEST II 6 1 Characteristics of HyperTerminal NetTEST II Properties Connect To Settings B NetTEST II Country code Ge Enter the area code without the lona distance prefix Area code pns Phone number I Connect using pn A Configure code end erea code Figure 27 Connection Setting via COM1 After having started HyperTerminal the connection must be made directly to one of the PC s serial interfaces via File Properties These are usually COM1 or COM2 If available any other free COM interface can be used COMSOFT 35 Communication with a PC 6 2 COM Interface Configuration COM1 Properties Pott Settings Bits per second poo H Data bits f lt H EN B Stop bits 1 7 Flow control a Bestore Defaults J Figure 28 Characteristics of the serial interface The interface set under 6 1 must now be configured To make transmission as fast as possible it is recommended to adjust the max serial baud rate of NetTEST II to 115200 Baud The setting of data bits parity as well as stop bits is made analogous to the settings of NetTEST II see chapter 5 2 3 1 As NetTEST II does not support a hard or software handshake please select under the point Flow control None No further settings have to be made at the terminal program Now it can be stored with File Save As as a standard file for the
60. st menu No protocol is drawn up for the tests under this menu item Test without PLC rofibus master mode Test with PLC Figure 30 Screen Line test The NetTEST II offers you the complete functionality of a PROFIBUS DP MONO Master with extended diagnostic functions DP MONO Master stand for the fact that the NetTEST II cannot share the bus with other Masters For reasons of clarity the NetTEST II processes only one of the DP Slaves on the PROFIBUS at a time 40 COMSOFT Systems with PROFIBUS Master Option The PROFIBUS Master Option is divided in 2 different modes e A simple user mode to check the problem free communication with the connected Slaves e An extended user mode where all Slave parameters can be changed or modified Profibus master mode Extended master Figure 31 Screen PROFIBUS Master mode 7 1 Slave line up Before using Slave line up NetTEST II needs a valid Slave configuration This can be done either by creating and downloading a configuration via the COMSOFT Konfigurator Tool or by creating the configuration directly on NetTEST II Entering Slave Line up launches the Slave selection menu where the Slave to be tested can be selected Profibus DP 32 RH65H WINbloc 32DI B I0 K DP 665 Figure 32 Screen Slave line up COMSOFT 41 Systems with PROFIBUS Master Option After the selection of the Slave to be tested the operation dialogue is lau
61. t for a renewed indication in the test protocol At the corresponding place the user name can be selected by simply using the QO o keys when issuing a test protocol The indication is made in alphanumeric order via keyboard see chapter 12 The name length is limited to 40 characters User name list User 1 User 2 User 3 User 4 User 5 Figure 19 Screen User name list 26 COMSOFT NetTEST II Menu Guide 5 2 2 7 Customer list The entry of customer data is made analogous to the entry of the test company see chapter 5 2 2 5 Here a list with max 10 customers can be created The entries can be made before executing a test This saves time at the customer s site Customer list COMSOFT GmbH Machhausstr 5a 76227 Karlsruhe 49 721 9497 6 info comsoft de Figure 20 Screen Customer list 5 2 2 8 Plant list In order to have a reference to the plant name where the tests were made the plant name can be entered here The name length is limited to 40 characters The maximum number of plant names is 10 Plant List lant 1 Plant 2 Plant 3 Plant 4 Plant 5 Figure 21 Screen Plant List COMSOFT 27 NetTEST II Menu Guide 5 2 2 9 Segment list The submenu Segment list has under Test protocol the same task as the menu point under Line test The functionality is therefore analogous to the one described in 5 2 1 1 5 2 3 System configuration System configuration RS232
62. t with no term The following error indications that impede correct length and impedance measurement may occur e No error Impedance not detected Cable length for the impedance measurement is too short e Error No length measured Cable length is either too short for length measurement or there is no cable connected e Error A lt gt shield B lt gt shield short circuit There is a low ohmic resistance between signal wire and shield COMSOFT 13 NetTEST II Menu Guide 14 Error A lt gt B Short circuit or unpowered termination There is a low ohmic resistance between the signal wires which might be caused for example by a bus termination without power supply Error A lt gt B Irregularity wrong termination or illegal termination There is an unacceptable ohmic resistance between the signal wires that stands in no relation to the magnitude of a bus termination either with or without power supply The cause might be for example an incorrectly connected bus termination Error A lt gt B Terminator There is a powered bus termination possibly along the line which impedes impedance and length measurement Error A lt gt shield B lt gt shield high imp fault There is a high ohmic resistance between signal wire and shield Error A lt gt B Capacitive load junction or Impedance changes There is a capacitive resistance between the signal wires which might be caused by a PROFIBUS
63. ta iiis 59 7 3 2 6 Edit xchg dat nee 59 7 3 2 7 Show xchg data 59 7 3 2 8 Edit DPTag output 59 7 3 2 9 Show DPTag input 59 7 3 2 10 Show Slave diagnostic 60 7 3 3 Single DP services 60 7 4 DPTag definitions eeeeeee 61 7 4 1 Display edit tag 62 7 4 2 Create Mew tag electi 63 7 4 3 Delete tag zs aspetti trente 63 8 System with Online Functionality 64 8 1 Baud rate detection 66 8 2 Generate livelist etes 67 8 5 Rotation time nre per iA 68 8 4 Signal level measurement 69 8 4 1 Measurement with livelist 70 8 4 2 Measurement with filter esses 70 8 4 2 1 Define filter 71 8 5 Signal level summary list 72 8 6 Eventlos 5c oed eee 73 8 7 EyentCOunt e no eee te egeris 74 8 8 Diagnostic event 75 8 0 Seti BS ur nie e o Hee ED Eten Pe P ed 76 COMSOFT iii Contents 9 Operation of the Battery Charger 77 10 Tips amp Tricks eeessseeossoeosssoessssscsssocsessoesessoesssssssssossee 78 10 1 Cable Lengths in PROFIBUS Segments 78 10 2 Segment Cascading see 78 10 3 Use of Stub Lines 79 11 Pin Assignment crees eee eren eee eee eese tenent tenaeseno 80 12 Key Allocation eeeee eee e eren eene eene netta
64. ted successively The tests are run in the following order e Select user name from User list e Select customer name from Customer list e Select plant name from Plant list e Select segment name from Segment list e Selection menu Test protocol only with option Online Function Test without PLC Test with PLC Figure 16 Selection menu Test protocol COMSOFT 23 NetTEST II Menu Guide 5 2 2 1 1 Test without PLC Contrary to individual measurements the test order instructed by the NetTEST II must be considered The cable tester always instructs the user how to perform the next test If a test fails it can be repeated as long as the problem is fixed The failed test is only stored in the test protocol if the protocol compilation is canceled at this point F By means of the key the single test is confirmed and the protocol compilation continues By means of key the protocol compilation is canceled 5 2 2 1 2 Test with PLC The test protocol compilation for the test with PLC is only available with the option Online Functions Contrary to the Test without PLC no test order must be considered All performed tests will be stored in the test protocol If a test is repeated only the last test result will be stored By the o key the test protocol compilation is finished and the results are stored Test with PLC aud rate detection Figure 17 Screen Test protocol with PLC 24 COMSOFT NetTEST I
65. tivated the bar graph display is automatically shifted to display always the actual measured DP Slave which guarantees a complete level measurement with all selected DP Slaves e Event update 2 s 5 s 10 s 60 s Default 2 s The event update is responsible for the event protocol for the event count and for the diagnostic event If the set update time is reached then the display window is updated During updating events occurring at the PROFIBUS cannot be registered Thus it is recommended to set to especially for higher baud rates 2 1 5 Mbit and to update the display window manually by means of the key WM 76 COMSOFT Operation of the Battery Charger 9 Operation of the Battery Charger The battery charger comes in two components a desktop battery holder and a plug charger Connect the desktop holder with the plug charger Insert a NetTEST IT battery into the battery holder Now plug in the charger plug into a 230 VAC mains socket Check the charging process by means of the control LED of the battery charger it is a time charger Charge time starts with mains ON and lasts for approx 6 hours During this time the charge control lamp is on if a battery is in the charger When the charge cycle is finished the unit automatically switches over to maintaining charge The charge control lamp then blinks in the interval 5 seconds ON 20 seconds OFF F Avoid quick insert removal of the battery in
66. to the battery holder because the battery charger may be left in an undefined state Wait approx 5s after removal before you insert the next battery into the battery holder COMSOFT 77 Tips amp Tricks 10 Tips amp Tricks 10 1 Cable Lengths in PROFIBUS segments The maximum cable lengths of PROFIBUS segments are specified in the standard EN 50170 part 2 in dependency from the transmission rate used Here the indicated value applies only for segments with copper cables type A without using repeaters The following table shows the maximum segment lengths depending on the baud rate Transmission rate Max segment length 9 6 Kbit s 1200 m 19 2 Kbit s 1200 m 45 45 Kbit s 1200 m 93 75 Kbit s 1200 m 187 5 Kbit s 1000 m 500 0 Kbit s 400 m 1 5 Mbit s 200 m 3 0 Mbit s 100 m 6 0 Mbit s 100 m 12 0 Mbit s 100 m Table 1 Segment length specification 10 2 Segment Cascading According to the standards it is permissive to make a cascade connection with 4 cable segments separated by repeaters For individual applications this guideline can be deviated from However if there should be sporadic errors in the bus segment we recommend a timing check with a bus monitor and possibly a reduction to the specified 4 segments 78 COMSOFT Tips amp Tricks 10 3 Use of stub lines When speaking about stub lines one must distinguish between active and passive stub lines Active stub
67. uration data in the case of uncertainty about the right configuration Moreover if the Slave has reached the Data Exchange status the user can modify output data to the Slave or display and evaluate input data from the Slave Line up 622 Edit slave address Edit slave parameters Edit Prm data Edit Cfg data Edit xchg data DATA_EXCHANGE vu Figure 52 Screen Line up 7 3 2 2 Edit slave address With this option the user can modify the PROFIBUS address of the Slave Address selection takes place over the address menu see chapter 7 2 5 1 7 3 2 3 Edit slave parameters The user can view modify several more important parameters Modification of these parameters functions in the same way as described in chapter 7 2 5 1 7 3 2 4 Edit prm data Here the user can view modify the user specific parameters Modification of these parameters functions in the same way as described in chapter 7 2 5 1 58 COMSOFT Systems with PROFIBUS Master Option 7 3 2 5 Edit cfg data Here the user can view modify the configuration data for the CHK_CFG_REQ service Modification of these parameters functions in the same way as described in chapter 7 2 5 1 7 3 2 6 Edit xchg data Here the output data for the Slave can be entered Changing these values functions in the same way as described in chapter 7 2 5 1 3 7 3 2 7 Show xchg data Input data received by the Slave are displayed here The data packets
68. xample a digital output or a analogous real value directly Output values are defined via tags in the DP Master configuration This can be very helpful especially if REAL values are processed with the Slave 7 1 4 Read value Input values are an extraction from the input data stream of the Slave With input values it is possible to examine for example a digital input or a analogous real value directly Input values are defined via tags in the DP Master configuration 7 1 5 Read diagnostics Reads the diagnostic data of the Slave and shows a decoded representation Not read diagnostic data are shown by an additionally in the status message of the Slave e g in operation With reading the diagnostic data the is deleted from the status message COMSOFT 43 Systems with PROFIBUS Master Option 7 2 Extended master The Extended master option can be subdivided into four partial units listed in the following depiction Extended master aster parameters with livelist with download Figure 34 Screen Extended master The NetTEST II stores the configuration of up to 32 Slaves Moreover the segment configuration bus address baud rate and slot time can be downloaded from the COMSOFT Configurator to the NetTEST II 7 2 1 Master parameters The menu Master parameters will lead you to another menu selection where you have the option of either viewing or modifying the PROFIBUS segment param