1. WUF Operating instructions Gas condensing boilers MGK 130 MGK 170 MGK 210 MGK 250 MGK 300 B II wer 00c Wolf GmbH Postfach 1380 D 84048 Mainburg Tel 49 8751 74 0 Fax 49 8751 741600 Internet www wolf heiztechnik de Documen t no 3062881_0910 Subject to technical modifications WF Contents CONTOTIES vigisivecysrncndeactsasie catatuninenacwencuctusdetnitete A E E E E dhedxenniniied Page Warranty General iitOnniauOn scents 2 ccten ches oeseg cc cadedds cided date actus daaectnaenchae cat sadeuta ecsndcctevttlegs tdi databiaduntnnte 2 Safety INSUUCHONS x baccs to tccceceeeskeucceue dia ancy sung heh ndg hea naanttacaata aden EEEk ecstnadeitadeasysabiadedetausaehe dot EKEN ERTER EKE gea 3 Installation information Maintenance information cece cece cette eeeeee cette etree eeeeeaaaeeeeeeeeeeeenaaaeeeeeeeenenaea 4 Water connections and gas supply Connection 02 ccce ceccccieeeeee esses eeteneee ee edeenececen seen eeeenecdedeeeetnveseeveenmneee 5 Controlsunit Operation ives c ciiiteiecsstesevenivsaeveslendstuavasassaeeieeia desde dueadhaceaedesiaediaas AEE EA AA A EARE e een 6 Information for energy efficient operation Faults 2 c cccecc cccceeeeeeeeseeeeeenee seen ceeeceeseaeenseesceeeneetedeeees 7 8 Warranty Our warranty is subject to the installation being carried out by a recognised heating contractor and adherence to all operating and installation instructions Warra
2. a minimum clearance of 40 cm Otherwise there is a high risk of fire If necessary top up with water When filling the heating system the shut off valves must be open Connect a water hose to the boiler drain amp fill BDF valve and open the mains water tap Open the BDF valve to provide a moderate flow rate and fill the heating system to approx 1 5 bar Check the water pressure at the pressure gauge Vent the system The boiler must be topped up since heating water will only fully deaerate after several hours heating operation Generally leave the system full except where there is a risk of frost The connection required for filling between the tap water and heating water must be removed after the fill has been completed Otherwise there is a risk that your tap water will be contaminated by heating water AN The appliance may overheat if it is operated without water The siphon must be fitted and filled Regularly check the water level The pressure gauge must indicate between 2 0 and 2 5 bar Your heating contractor will explain how to top up your system Do not supplement your heating water with additives otherwise components may be damaged 3062881_0910 WOUIF Control unit operation ON OFF Heating water switch Reset button temperature selector Thermometer Illuminated DHW Pressure gauge ring temperature selector Illuminated status indicator ring Illuminated ring Explanation Flashing gre
3. been fully installed For operation in balanced flue mode only take the appliance into use if the balanced flue system has been fully installed and the wind protector is not covered up The gas condensing boiler may only be installed in rooms that are protected from frost Never isolate the appliance from the power supply when outside temperatures fall below zero otherwise there is a risk of the system freezing up Never modify the drain or the safety valve A Caution failure to observe this rule may lead to a risk of fire as well as a risk of destruction poisoning or explosion A Do not use or store explosive and or flammable materials e g petrol thinners paints paper etc inside the boiler room Never use or store sprays solvents chlorinated cleaning agents paints adhesives etc in the vicinity of the gas condensing boiler Under unfavourable conditions these materials may lead to corrosion in the gas condensing boiler and the flue system Ducted vents routed through a roof may also contain corrosive vapours For that reason maintain a sufficiently large distance to the air flue gas terminal minimum recommendation 5 m Clean the casing with a damp cloth and mild detergent The components inside the gas condensing boiler may only be cleaned by a heating contractor NB only the heating contractor offers the required knowledge and expertise The user is responsible for arranging a regular service of the
4. contractor quickly pays for itself Heating at the lowest energy level Operate your heating system where possible with a flow temperature of less than 60 C or a flat heating curve A heating system control unit also regulates your heating costs A heating system in standby mode saves energy With automatic night setback and thermostatic valves a modern weather compensated or room temperature dependent heating system control unit ensures that the system only operates when heat is required saving you money the rest of the time Equip your heating system with a weather compensated heating controller from the Wolf range of accessories Your heating contractor will be happy to advise you how to achieve optimum settings In conjunction with the Wolf control unit accessory use the night setback function to match the energy level to the actual demand period Use the optional summer mode setting Never overheat your system Adjust the room temperature as accurately as possible This leaves occupants comfortable and energy is not wasted on providing heating output that nobody needs You can differentiate between the optimum temperatures for individual rooms such as living rooms and bedrooms Aroom temperature that is one degree higher than necessary represents an additional energy consumption of approx 6 Use room thermostats to match the room temperature to the actual use of the room In any room where you have install
5. FF switch has been switched OFF AN Caution risk of electrocution The use of antifreeze is not permissible The control unit protects the gas condensing boiler against frost The risk of frost cannot be totally prevented e g during longer power failures Therefore only install the gas condensing boiler in rooms that are free from the risk of frost Should there be a risk of frost during longer idle periods e g when the heating system is switched off ask your local heating contractor to drain the boiler and the heating system to prevent pipes from bursting Caution risk of water damage and malfunction through freezing With low outside temperatures the water vapour contained in the flue gas may condense and freeze on the balanced flue This ice may fall from the roof causing injury or material losses Prevent ice from falling by taking on site measures e g the installation of a snow guard AN Caution risk of injury 3062881_0910 WOIF Installation information Maintenance information Positioning modifications Corrosion protection Care Service Your gas condensing boiler should only be installed and modified by an approved heating contractor as only they have the essential knowledge to carry out such work Never modify flue gas components Never close or restrict the ventilation apertures in doors or walls when operating the boiler in open flue mode only start the boiler when the flue has
6. ed a room temperature sensor open the thermostatic valve fully This enables you to achieve optimum control characteristics for your heating system Ensure adequate air circulation Air must be able to circulate freely near the radiators and the room temperature sensors otherwise the heating system will lose work less effectively Badly positioned long curtains or furniture swallow up to 20 of your heat 3062881_ 0910 7 WOIF Information for energy efficient operation Faults DHW mode Faults Fault codes Keep the heat inside the room at night too At night closing shutters and drawing curtains noticeably reduces heat losses via the window areas Insulating the radiator recesses and having light coloured paintwork can save up to 4 off your heating bills Airtight joints at windows and doors also help to keep energy inside the room Minimise energy consumption through sensible ventilation Ventilating for hours loses heat stored in walls and objects As a result the room climate will only become comfortable again after prolonged heating Short and thorough ventilation is more effective and pleasant Bleeding the radiators Bleed the radiators regularly in every room This safeguards the perfect function of radiators and thermostats particularly in the upper apartments of apartment blocks The radiator responds quickly to changing heat demands Intelligent use of DHW circulation pumps Always control DHW circulatio
7. en Standby power supply ON burner OFF e g summer mode Constant green light Winter mode Pump running burner OFF Flashing yellow Emissions test mode Constant yellow light Burner operating flame ON Flashing red Fault Summer mode central heating OFF Winter mode Setting 2 to 8 amp Emissions test mode indicator ring flashes yellow un DHW temperature selector 1 15 C 9 65 C 7 55 C recommendation Heating water temperature selector 2 20 C 8 75 C The BM programming module can also be integrated into the control unit That means that all settings are made at the MGK For installation and operation see the BM programming module operating instructions ca sih as eae o TA Lie Z f A 3062881_0910 WOOF Information for energy efficient operation Heating mode Saving energy with modern heating technology gas condensing technology saves your cash In conventional heating systems energy is expelled unused to the atmosphere along with the flue gas Modern condensing technology utilises that energy for heating Use as little electrical energy as possible Operate your system with multi stage heating pumps at the lowest required level Regular heating system maintenance pays for itself A contaminated burner or poorly adjusted appliance can reduce the heating system efficiency Regular heating system maintenance through your local
8. n pumps via time switches Program these in accordance with your DHW demand patterns The optimum DHW temperature Only ever set the DHW temperature or that of the cylinder to the temperature you really require Any additional heating uses additional energy Sensible handling of DHW Showering consumes only approx 1 3 of the water volume required for a bath Repair any dripping taps immediately If the status indicator ring flashes red where possible read the fault code on the connected control unit accessory and note the code The appliance can be returned into use by pressing the reset button In case of repeated faults shut down the appliance and notify your heating contractor Gas condensing boilers are equipped with an electronic flue gas temperature limiter The appliance automatically shuts down when the flue gas temperature exceeds 110 C The boiler restarts when the reset button is pressed If this recurs ask your heating contractor to check the flue system NB risk of damage poisoning and suffocation work less effectively Keep your operating instructions safe in an easily accessible place near your gas condensing boiler 3062881_0910
9. nty period Gas condensing boilers are guaranteed for 2 years General information Gas is an environmentally friendly fuel that does not represent any danger unless handled with gross negligence Your gas condensing boiler is a high grade product that incorporates the latest safety technology A These safety instructions should protect you from potential risks AN Risk to life Non observance of these references can lead to risks to individuals and the risk of material losses AN In case of risk of fire e Immediately switch OFF the emergency stop switch of the heating system if outside the installation room e Close the gas shut off valve e In case of fire use a suitable fire extinguisher 2 3062881_0910 WOIF Safety instructions AN SAFETY INSTRUCTIONS If you smell gas If you smell flue gas When changing a fuse Frost protection Balanced flue routing Do not operate any light switch Do not operate any electrical switches Keep naked flames away Close the gas shut off valve Open windows and doors Notify your gas supply utility use a telephone outside of the danger area AN Caution risk of poisoning suffocation and explosion Shut down the system Open windows and doors Notify your local contractor AN Caution risk of poisoning Isolate the appliance from the power supply prior to changing a fuse The mains terminals of the boiler are live even when the ON O
10. system in order to ensure the reliable and safe function of the gas condensing boiler Your gas condensing boiler should be serviced annually Maintenance is explicitly detailed in the installation instructions Isolate the appliance from the power supply before any maintenance work After a service and before the gas condensing boiler is returned into use check that all components that were removed for maintenance have been refitted correctly We recommend you arrange a maintenance contract with an approved heating contractor 3062881_0910 WOIF Water connections and gas supply connection Please observe before commissioning Filling the system Filling the siphon Checking the water level Depending on your specific heating system the safety equipment must be tested by a heating contractor The heating system must be completely filled with water Subject to the boiler output and operating temperature of the heating system the water quality for heating systems is regulated by local regulations governing Water quality in heating systems with hot water boilers Observe the system pressure If necessary top up with water Never use boiler water for domestic use Check whether the ventilation of the boiler room is ensured in accordance with local regulations The air supply to the boiler must not be obstructed otherwise there is a risk of suffocation Never position objects directly on the boiler maintain