1.      The APS Comfort  System for Framed  Doors  fire protection  is permanently  coupled  The door  can be opened  without authorisation  of an identifier        The fitting s switch  mode is enabled  see  eLOCK system  documentation  section   Fitting modes         Disable switch mode    O Reconfigure fitting  time profile    O Authorisation with  switch IT to disable  the switch mode        16   OPERTIS    09 2013    eLOCK    GB    Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       8 Product specifications    Declaration of conformity    Report    OPERTIS GmbH hereby declares that the APS Comfort System for  Framed Doors  fire protection complies with the fundamental requirements  and other relevant provisions of the directives 1999 5 EG and 2011 65 EU   and are CE compliant     A copy of the declaration of conformity can be obtained from OPERTIS  support    Installation in profile cylinder mortice locks according to DIN 18251  Locks    Mortice locks   Part 2  Mortice locks for tubular framed doors     The lock has the building inspection test certificate from MPA Dortmund  It  is labelled accordingly     According to Report No  120004118 1 by the MPA Nordrhein Westfalen   the APS Comfort system for framed doors  fire protection can be used on  fire doors and shutters  in conjunction with lever handles to DIN 18273 FS        09 2013    OPERTIS   17    GB eLOCK  APS Comfort
2.    23    OPERTIS    ce    OPERTIS GmbH  Prof  Bier Stra  e 1 5  D 34454 Bad Arolsen    Telefon    49 5691 87741 0  Telefax    49 5691 87741 310    info opertis de  www opertis de    M7000 64GBB V001 09 2013    
3.   o R  oO   M       APS lock       Fixing screw M5x50       Profile cylinder adapter for fire doors  with antenna cable       11    Fire door plate  oval       12       Rose  for fire door       6   OPERTIS    09 2013    eLOCK GB  Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       13  M5x20 screws  14  Rose cap          15  Profile cylinder housing       16  M4 countersunk screw  door thickness dependent        17  Plastic profile cylinder cover with antenna       Functional principle    Self locking motor panic lock with integrated electronics according to DIN  18251 2     The OPERTIS locking system  eLOCK  ensures durchg  ngige  Objektausstattung  Special fittings are available for different types of door     The APS Comfort System for Framed Doors  fire protection contains a  self locking lock  which automatically locks when the door is closed   Conventional locking with knobs or keys is no longer needed  nor is  mechanical closing     With the APS Comfort System for Framed Doors  fire protection the inside  handle is always coupled  Through the integrated anti panic function  the  latch and release lever are retracted by pushing the inside handle  the  door can always be opened again from the inside  The panic function  cannot be switched off     With the APS Comfort System for Framed Doors  fire protection fire  protection the outside handle is non functional when it is
4.  Risk of property damage   Using non approved types of battery can result in  malfunction  In this case  the fitting would send no battery  warning  and would not enter the secure final state of Active  Power Off     Only use types of batteries  which are approved by  OPERTIS        09 2013    OPERTIS   9    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    AN CAUTION    Risk of being locked out   The door cannot be opened without a functional fitting  if the  latch is in the lock    Leave the door open during installation and battery  replacement  or ensure that the door can be opened at all  times without using the fitting     CAUTION  Unauthorised access    The inside handle of the APS Comfort System for Framed  Doors  fire protection is basically coupled as an anti panic  lock  This makes it possible to open the door at all times  using the inside handle  Be especially aware of this when  using the fitting on publicly accessible doors  and on doors  with inside handles  which can be easily reached from the  outside     CAUTION   Unauthorised access   The APS Comfort System for Framed Doors  fire protection is  delivered with factory settings  Access is also possible with all  non programmed OPERTIS identifiers    Programme the authorisations immediately following  installation to prevent unauthorised access  see eLOCK  system documentation software  meanwhile  ch
5.  System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    Dimensions  All dimensions in mm    ES7670F or ES6670F                   18   OPERTIS 09 2013    eLOCK    Operating instructions    GB    APS Comfort System for Framed Doors  fire protection    ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       Technical data    Surface  Lock plate    Stainless steel       Profile cylinder cover    Polyamide surface       Cover cap    Power supply       Stainless steel       Supply voltage 3 volt lithium battery CR 3V  OPERTIS item no   ES0893  Battery life  Depending of conditions of use and    O Operational readiness   at  approx  10 closures per day     O Closures  total   O Standby time    Specific details  Operating temperature       type of fitting   O up to 3 years    O up to 100 000 closures  O upto 5 years    0  C to  45  C       Storage temperature     20   C to  60   C       Air humidity for operation and  storage    max  95  non condensing       Protection class  according EN 60529    IP 21       Lock strength  according to DIN 18251 class 4    Increased burglar resistance and high  user frequency       VdS  Association of German  Property Insurance Companies   inspection    The lock has been tested and approved  by the VdS                    Memory capacity in the fitting   ES6xxx ES7xxx ES7xxx  LernL  sch   Identifiers 60 000 80 000 100  Protection zones  belonging 
6.  The following residual risks  however  cannot be ruled out     O If the electromechanical components fail  there is the risk of being  locked out        8   OPERTIS 09 2013    eLOCK    GB    Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       O If the battery suddenly completely discharges  the APS Comfort  System for Framed Doors  fire protection will be non functional  It will  send no battery warning  and will not enter the Active Power Off state   It is then only possible to open the door from the outside with the  external power supply ES6781 for ES5000 plus systems or ES7781 for  eLOCK and eLOCK LernL  sch systems     4 Safety instructions    A    The safety notes are to be read prior to use  OPERTIS accepts no liability  for any personal injury or property damage resulting from failure to follow  this manual     WARNING   Risk of personal injury from the batteries   Improper handling of the batteries can be harmful to health   The following notes must be observed     O Only use types of batteries  which are delivered or  approved by OPERTIS     Do not open  solder or weld batteries    Do not throw batteries into fire    Do not recharge batteries    Immediately remove empty batteries from the fitting   Keep batteries out of the reach of children     Do not touch leaking batteries without appropriate  protection  Avoid contact with eyes and mouth     O00000    CAUTION  
7.  decoupled  It  can be pushed  but it is not connected to the the lock latch or release  lever  In this state  the door cannot be opened using the outside handle   Access is gained by brief coupling of the otherwise neutral outside handle  after holding an authorised identifier in front of the antenna  Upon  actuation of the coupled outside handle  the latch and release lever are  retracted     Conventional locking with knobs or keys is no longer needed  nor is  mechanical closing     Administration and programming  as well as the granting of access rights  is done over the eLOCK Center administration software  Optional  programming with eLOCK LernL  sch over three programming keys  without additional software is possible     To access the fittings  passive identifiers without their own power supply  are available in different designs  such as key rings  cards or custom  designs     Detailed information    You can find further information on the product in section 8  Product  specification           09 2013 OPERTIS   7    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    3 Intended use    Area of use  The APS Comfort System for Framed Doors  fire protection matches the  installation dimensions of a mortice lock in accordance with DIN 18251 2   and is designed for indoor use on narrow tubular framed doors  Use of  external doors is permissible only if the electronics 
8. OPERTIS    Operating instructions    APS Comfort system for framed doors   fire protection   ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F                         eLOCK GB    Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       Contents  1 Introduction    ann 4  Ab  urthese INSTUCUO Sins aaa en einen 4  Explanation of the symbols and signal words used                          s444s4s4s4enenenen nennen 4  O 4  OPER JIS SUPPEN ee teen een une 4  Up 1o date  MO MAN er kn 5  2   Productdescription         0 ri 6  COMPONENT Dar da io 6  FURIA PIN AAA GRAN re aS 7  Detailed IMC nta 7  3  Intended AAA    8  ARO USA 8  Condition OF the DIOQUEL ea asa 8  Ambient conditions Eee kennen nenne teen IK uous rare Re REN 8  OW SRS ONY ae ae AO AR 8  Resid    altis Keene si 8  4 Safety INStrUCHONS  i iiiad iinei ensaian aii 9  5 USE and operation oi da 11  Programming fittings and identifiers usara 11  Ghangethe Dato Vaina ii 11  Acolstie Signals anerkennen 12  6 Servicing  cleaning and maintenance           uunnsssssnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnnn 13  Intervals oran acatar 13  Cleaning  and Maintenance as ee 13  SOME aid 14  7 Problems and SOQIUNONS vvicicicccisscicccccceicccccsseecciscctccedatsdaesiaeceeccdcessncudensiaccdeewdeausnavensvee 15  8   PFOGUCE specifications carac 17  Declaration of conformity ati nennen 17  A a cas rence a tions ean R
9. are installed ina  protected internal area  Use on outdoors  such as in fencing  is not  permitted     The lock meets the requirements for doors in escape and rescue routes  according to DIN EN 179 and 1125  Used in approved and tested fittings     Condition of the product    The APS Comfort System for Framed Doors  fire protection may only be  used in a technically sound condition     Unauthorised conversions or alterations of the product are not permitted     Ambient conditions    Use in particularly harsh environments  e g  corrosive gases  high  humidity  extreme temperatures or very dusty conditions  is not permitted   Please contact OPERTIS Support if you have any questions     Power supply    Enable all battery powered fittings activate audible low battery warnings   and controlled failure closures when the battery power in the fitting is  coming to an end  The battery must then be replaced immediately   Repeated disregard for the low battery warning permanently decouples  the APS Comfort System for Framed Doors  fire protection from the  handle  Active Power Off   The Active Power Off state is indicated by an  acoustic warning  See operating manual  chapter 5   Use and operation    This state is maintained until the battery is replaced or  if relevant  an  external power source was connected to the outside of the door     Residual risk    This product supports the security of your property when used as  intended  and in compliance with the maintenance instructions    
10. atan atau ET EEE ee 17  DIMENSIONS SAA 18  Te  chnicaldat   2 3  a ESPRIT O ia 19  9    DISPosal  arms 20  Product orere a a a cate ai ec 20  DAMOS NA ee 20  Producto PACKAGING nennen energie seinen dsena 20  A once agatneatedaegansestecsasertetnaswastal seed deaensusctanasertedadesteataleas 20       09 2013 OPERTIS   3    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    1 Introduction    About these instructions  This manual contains important information for operating the APS Comfort  System for Framed Doors  fire protection ES7670F  ES6670F  ES7671F   ES6671F  ES7672F  ES6672F  ES7673F and ES6673F   O Read the manual thoroughly and carefully     O Store the manual and pass on to each next user of the APS Comfort  System for Framed Doors  fire protection     Explanation of the symbols and signal words used    A WARNING da hazards that can lead to death or serious       Indicates hazards that can lead to minor or  A CAUTION moderate injury        CAUTION  Indicates hazards that can lead property damage     Highlights hints and tips for optimum use of the    noe manual and product        Target group  This manual is intended for specialist staff  who are responsible for the  service  maintenance  disposal and continued fault free operation of the  APS Comfort System for Framed Doors  fire protection and can prove that  they have the suitable training or relevant exp
11. eck the time  and reset if necessary        10   OPERTIS 09 2013    eLOCK GB    Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       5 Use and operation    Programming fittings and identifiers  Fittings and identifiers are programmed over the eLOCK Center  management software or the eLOCK LernL  sch system  You can find  detailed information about these in the eLOCK system documentation  software    Change the battery  Note  Note the information on battery types in section    Technical data        Proceed as follows     Step Activity Image       1 Screw in M3x9 screws on the  mounting plate and remove  the stainless steel cap        Remove battery        Insert the new batteries into  the battery compartment   observing the correct polarity   See image                      4 Place the stainless steel cap  on top of the mounting plate  and hook in place        5 Attach the stainless steel cap  below the mounting plate with  two M3x9 threaded pins        6 Perform a closure operation  by holding an authorised  identifier  Check the date and  time and reset if necessary   see eLOCK system  documentation software              09 2013 OPERTIS   11    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    Acoustic signals    The acoustic and visual signals of the Comfort system 
12. erience for these activities     OPERTIS Support    Should you have any questions  which are not covered in this manual   please contact     OPERTIS GmbH  Prof  Bier StraBe 1 5  D 34454 Bad Arolsen    Tel    49 5691 87741 200  Fax   49 5691 87741 281  Email  support opertis de       4   OPERTIS 09 2013    eLOCK GB    Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       Up to date information    All information on the product  images  dimensions and lists correspond to  the status at the time of product delivery  We reserve the right to make  changes as a result of technical progress  and the resulting improvement  product processes     You can also find the current version of this manual and other information  on our website   www opertis de     Status 09 2013       09 2013 OPERTIS   5    GB    eLOCK    APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    2 Product description    Component parts    The following drawing shows the component parts of the APS Comfort  System for Framed Doors  fire protection              NZ             u                                                       Stainless steel cover       Battery       M3x6 screws       Housing with electronics       M5x8 screws       M3x9 threaded pins  screwed into the mounting plate       Mounting plate       COIN  OD
13. eys are not in  the horizontals  APS  Comfort System for  Framed Doors  fire  protection works  faulty      Antenna is defective     Replace antenna        Cables are crushed or  pinched     Replace APS Comfort  System for Framed  Doors  fire protection       Comfort System is  contaminated by chips  or lubricant    Latch key set is oblique  or mounted under  pressure     Replace APS Comfort  System for Framed  Doors  fire protection  Mount latch key set    correctly and check for  free movement        Latch keys are too  heavy     Replace existing latch  keys with lighter ones or  use additional retaining  springs        Every identifier has  locking authorisation     Latches do not  engage     Fitting is not  programmed   factory  setting       Latch recess in the  strike plate does not  match the latch position  of the APS Comfort  System for Framed  Doors  fire protection     Program the fitting  see  eLOCK system  documentation  software    Adapt the latch recess  in the strike plate to the  latch position of the  APS Comfort System  for Framed Doors  fire  protection        Door or door frame  warped     Adjust door  door frame  or the tapes        The lock does not  lock     The self locking is  defective     Replace immediately        The bolt does not  retract when the  inside handle or  coupled outside  handle is pushed     The panic function is  defective     Replace immediately   The door may no   longer be closed  as  the panic function is  no longer available   
14. for Framed Doors   fire protection depend on the programming  The programmed fittings in  the AddDelete system and the fittings programmed using eLOCK Center  have a different signalling concept     Note    The complete visual and acoustic signals are included in the eLOCK  system documentation  Signalling Concept  section     Acoustic signal    Meaning       1x ascending sound  sequence     Programming mode on        1x descending sound  sequence     End of programming mode  automatic         1x short high pitch     Fitting connection by authorised identifier        1x long low pitch     No fitting connection  identifier not  authorised        1x long low   5x sound  sequence short high    Battery empty  warning level 1 with  controlled failed locking       1x long low   3x sound  sequence short high    Active Power Off  battery completely  discharged       1x short high pitch     Fitting connection in construction site mode  or permanent release mode  see eLOCK  system documentation  Fitting Modes   section        1x long low pitch   4x  short low pitch       System error   Dismantle Comfort system   contact OPERTIS Support        12   OPERTIS    09 2013    eLOCK    Operating instructions    GB  APS Comfort System for Framed Doors  fire protection    ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       6 Servicing  cleaning and maintenance    Service  cleaning and maintenance may only be carried out by qualified    staff     Guarantee for damage resu
15. lting from improper handling is excluded           Intervals  Activity Interval  Cleaning and 3 months   maintenance  Service 1 year       Cleaning and maintenance    CAUTION    Property damage from improper cleaning   If cleaning is done incorrectly  the surfaces can become   attacked and damaged    O Only carry out maintenance on the APS Comfort System  for Framed Doors  fire protection from the outside  do not  remove cover caps       O O00 0    Do not use any cleaning agents  which contain alkaline   acid or chlorine     Do not use any cleaning agents  which contain abrasives   Do not use any abrasive tools  such as brushes     Do not allow oils and greases to enter the inside of the  electro mechanical lock     Do not allow cleaning agents to enter the inside of the    lock casing     Proceed as follows        Step Activity Image  1 Wipe surfaces with a damp   cloth   2          Lightly grease the raised latch  bolt on the oblique side           09 2013    OPERTIS   13    GB    APS Comfort System for Framed Doors  fire protection    eLOCK  Operating instructions    ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    Servicing    A    CAUTION  Risk of being locked out    The door cannot be opened without a functional fitting  if  the latch is in the lock     Run functional tests with door open     The following functional tests are to be carried out at least once a year     Step    Activity    Result       1    Check the secure seating of  the lock  
16. st the  strike plate           Read the fitting information   see eLOCK system  documentation software        7 Problems and solutions       Problem Possible cause Solution  APS Comfort System   Identifier is not an Use OPERTIS  for Framed Doors  OPERTIS identifier of identifier     fire protection does  not open or close     Identifier is not    authorisation     programmed or does  not have the required    the locking system     Program the identifier   see eLOCK system  documentation  software        Identifier is defective     Replace identifier        Fitting has the wrong  date or wrong time     Reset the time  see  eLOCK system  documentation  software        Battery is empty or  defective     Replace battery and  single operation of the  APS Comfort System  for Framed Doors  fire  protection through an  identifier    Provide external power  supply on the outside of  the APS Comfort  System for Framed  Doors  fire protection   Then replace the  battery and operate the  APS Comfort System  for Framed Doors  fire  protection at least once  by means of an  identifier           Antenna plug has  become loose        Fully plug in the  antenna plug           09 2013    OPERTIS   15    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    Problem    Possible cause    Solution       APS Comfort System  for Framed Doors   fire protection does  not open or close     Latch k
17. the mounted fittings  and the screws     All component parts of the  APS Comfort System for  Framed Doors  fire protection  are securely fixed  The latch  and the release lever move  smoothly        Push the outside handle     The outside handle is in  neutral mode  The latch does  not retract        Hold authorised OPERTIS  identifier in front of the reader   then push the outside handle        Push the inside handle     The latch retracts and rises  again after it is released        Check self locking   Push down the release lever     The lock latch and release  lever should  pop out  The latches and the    release lever can no longer be  pushed down        Check panic function    Push inside handle when the  lock is locked    Check panic function     Push coupled outside handle  when the lock is locked     The lock latch and release  lever are retracted through  actuation           CAUTION   Risk of being locked out  When closing the door from  the outside  an authorised  identifier must be available  in  order to subsequently reopen  the door     Close door from the inside        The lock latch should pop out        14   OPERTIS    09 2013    eLOCK  Operating instructions    GB    APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       Step    Activity    Result       9    Push the inside or coupled  outside handle     Lock latches and release  levers are retracted  and the  bolt must not rub again
18. to  296 30    a group of fittings   Event memory  authorisation 512 628    attempts    09 2013 OPERTIS   19    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F    9 Disposal    Product  E Disposal in accordance with WEEE Directive 2012 19 EU   O Do not dispose of the product with the local household waste   O Return the product to OPERTIS or dispose at a municipal  collection point for electrical hazardous waste   Batteries    E O Do not dispose of batteries with the local household waste  but  at a public battery collection point     O Do not throw batteries into fire   O Do not store used batteries together     O Dispose of the batteries only when they are completely  discharged     Product packaging    Dispose of the product packaging with the local household and paper  waste     Notes        20   OPERTIS 09 2013    eLOCK GB  Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F          09 2013 OPERTIS   21    GB eLOCK  APS Comfort System for Framed Doors  fire protection Operating instructions  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F       22  OPERTIS 09 2013    eLOCK GB  Operating instructions APS Comfort System for Framed Doors  fire protection  ES7670F  ES6670F  ES7671F  ES6671F  ES7672F  ES6672F  ES7673F  ES6673F          09 2013 OPERTIS
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
cliquez ici  Spreed Online Meeting User Manual  (+44-171) 418 8400 Fax: (+44-171) 418 8551 E_Mail: mail@emea    FDL-02取扱説明書  Bricscad V9 Benutzerhandbuch  取扱説明書を参照する(PDF 512KB) - Arts Intelligence Inc. [アーツ  保存用 - 嵯峨電機工業  User Manual Polar CS200™ Polar CS200cad™ Manuel d  NXT User Guide    Copyright © All rights reserved. 