1. ceiling mounting 1 From the bottom for a wider detection range 2 With a corner adapter which allows the device to be ideally positioned Operating Instructions 1473 1 8103 Operating Instructions Busch Wachter Installation and electrical connection 6 2 1 4 Corner mounting Fig 5 Corner mounting The combination with a corner adapter is recommended for an optimal 280 detection range O Note Detailed user information is available via the link http www busch jaeger katalog de index php in the Busch Watchdog category under accessories 6 2 2 Installation sites e AS Sc Se Fig 6 Installation sites The distance between light and movement detector should be at least 1 5 m For optimum detection of persons the approach into the detection range should always be offset and never frontal Operating Instructions 1473 1 8103 j Operating Instructions Busch Wachter Installation and electrical connection 6 2 3 Preparing the installation To prepare the installation of the device perform the following steps Fig 7 Preparing the installation 1 Remove the locking screw 1 if installed 2 Press in clamps 2 5 on the sides of the housing with a suitable tool 3 Carefully remove the front of the device Fig 8 Opening the water drain Depending on where the device is installed the water drain may have to be opened Todo this pierce the plast
2. connection with extension unit push button O Note For more information see chapter Extension unit operation 8 4 on page 17 6 3 3 Standard connection with RC suppressor 6899 and relay Fig 12 Standard connection with RC suppressor Operating Instructions 1473 1 8103 zmqm Operating Instructions Busch Wachter Commissioning 7 Commissioning 7 1 Setting limiting the coverage and the detection range Caution Risk of damaging the device The lens of the device is sensitive and can easily sustain damage Do not press on the lens when setting the device Use the following steps to set the coverage and the detection range v Fig 13 Adjusting the lateral detection range 1 Adjust the lateral detection range by turning the head of the device Fig 14 Adjusting the coverage 2 Adjust the coverage by lifting or lowering the head of the device The minimum coverage is 6 m Operating Instructions 1473 1 8103 sjy Operating Instructions Busch Wachter Commissioning ar i Fig 15 Adjusting the detection range by masking 3 The range can be specifically limited by gluing on the enclosed foil Cut the enclosed foil to the size required The coverage and the detection range are set 7 2 Activation test The activation test can be triggered manually on the device or via the service remote control For additional control elements see separate oper
3. 1 Safety Warning Electric voltage Risk of death and fire due to electrical voltage of 230 V Work on the 230V supply system may only be performed by authorised electricians Disconnect the mains power supply prior to installation and or disassembly 2 Intended use The device is to be used exclusively with the components that are supplied and licensed as described in chapter Setup and function 3 Environment Consider the protection of the environment Used electric and electronic devices must not be disposed of with domestic waste The device contains valuable raw materials which can be recycled Therefore dispose of the device at the appropriate collecting depot All packaging materials and devices bear the markings and test seals for proper disposal Always dispose of the packaging material and electric devices and their components via the authorized collecting depots and disposal companies The products meet the legal requirements in particular the laws governing electronic and electrical devices and the REACH ordinance EU Directive 2002 96 EC WEEE and 2002 95 EC RoHS EU REACH ordinance and law for the implementation of the ordinance EC No 1907 2006 Operating Instructions 1473 1 8103 3 Operating Instructions Busch W chter Setup and function 4 Setup and function The Busch Watchdog 220 MasterLINE select is a movement detector with a detection range of 220 and is ideal for applica
4. 1473 1 8103 Rev 01 11 2012 Operating Instructions Busch W chter 6847 AGS 220 MasterLINE select O BUSCH JAEGER V Operating Instructions Busch Wachter 1 SIMI E IINE LO DLL DL LL DL 3 2 Mende d USE c a eE a 3 3 Environmemt eierens a a MIL III EE EIE EE 3 4 SOLU PANG MUMCU OM DEE 4 4 1 Features of function and equipment eecisicieecc iiis eese niae nennen dean nda aen n ae don enar dan daten done Een 4 4 2 IR ut blue DEE 5 4 2 1 Overview of the detection ranges cisci icona dentata dn edia de Poena dne aa ncmo aaa eran Ee and 5 4 2 2 Limitation of the detection range nicer anina aderidi aeran 5 5 Techmeal gies 6 6 Installation and electrical conriectlon ciere rr ror t rea ene er eap OEREN FRE SERE E ERI ER IP ETE Ves ERE Ye ERI PE Eee eS 7 6 1 Requirements for the electrician ri neto rehenes aos cran exe Rr Sea dE eegen 7 6 2 eMe II RE 8 6 2 1 MOU el une E 8 m EE CE e A 9 62 12 Wall mounting with gradient aac cote teens geseid 9 6 2 1 3 Ceiling mounting PPE A 9 6214 EE uen mec PR 10 6 2 2 Installation Stes LS 10 6 2 3 Preparing the installati n ccissccnecisscteacs teactesancetecsaeGecteaies eregacsecatsbeaestanet ceeded aevteceedaaatedansetecangeceteaduarterasee 11 6 2 4 bid cfe E HM 12 6 3 Electrical
5. CONNECtION eee ennrn nennen seen nnne e eerte ener nnne nns 13 6 3 1 Standard COMMeCHON pem 13 6 3 2 Standard connection with extension unit push button ooo eee ee eece ee eeneeeeeeeaeeeseeeaeeeeenaeeeeeeaeeeeneeaees 13 6 3 3 Standard connection with RC suppressor 6899 and relay eee eeeeeeee cence eeeeneeeeeeeeeeeseeeeeeenaeeeeneaeeees 13 7 COMMISSIONING m 14 7 1 Setting limiting the coverage and the detection range emm 14 7 2 Drei cubes E N 8 WEE 8 1 COMMON ne 8 2 Standard operation 8 3 Standard operation time and brightness dependent A 17 8 4 Auxiliary post operatton essen nennen nnne nennen e nenne en nennen e entren nns 17 8 4 1 Operation with extension unit push button eene nennen nnne 17 9 Ee eege ER 18 9 1 Control elements of the remote control cisci scies eie dace eene enin Inani aa nnne aa Enn ek dna 18 9 2 Technical data of the remote control 1 icis cene deitatem nudae doe pua dne eder ordre Eden 18 9 3 Commissioning Of remote COntrol seed ient tried eed tcd ee Ere LA eU dE pne e Kd eO Ce eu ue FERES EE Y RAE SU edv eu 19 9 4 Battery change of remote control iere eitee eec terne sued hae eed ku rod aane e aser E ud adea eed ebd cse 19 Operating Instructions 1473 1 8103 2 Operating Instructions Busch W chter Safety
6. ating manual A dcus TS 10 sek MIN Fig 16 Control elements To carry out the activation test perform the following steps 1 Set selector switch to T S The device is now in test mode for 10 minutes daytime operation switch off delay 2 sec In addition each detection is indicated by the status LED flashing quickly The device then switches back to standard operating mode 2 To carry out additional activation tests set the selector switch back to position T S or interrupt the operating voltage supply for more than 15 seconds The device is now in test mode for another 10 minutes Test mode is exited automatically after 10 minutes or by adjusting the brightness Operating Instructions 1473 1 8103 15 Operating Instructions Busch Wachter Operation 8 Operation 8 1 Control elements Fig 17 Control elements No Function 1 LED On continuous light set only possible with remote control Flashes fast detection in test mode Flashes 3 times detection in standard and normal operation Flickers incoming IR signals remote control 2 Lens 3 Trim potentiometer for switch off delay short time pulse 4 Trim potentiometer for brightness value test standard operation 5 Screw for dismantling safety 8 2 Standard operation C TS Fig 18 Standard operation The lighting during twilight remains switched on for 3 minutes after the last detection O A
7. e document and its contents or extracts thereof must not be reproduced transmitted or reused by third parties without prior written consent by ABB Copyright 2012 Busch Jaeger Elektro GmbH All rights reserved BUSCH JAEGER V 1473 1 8103 Rev 01 11 2012
8. f ballasts Operating Instructions 1473 1 8103 Operating Instructions Busch W chter Installation and electrical connection 6 Installation and electrical connection Warning Electric voltage Risk of death due to electrical voltage of 230 V during short circuit in the low voltage line Low voltage and 230 V lines must not be installed together in a flush mounted socket 6 1 Requirements for the electrician Warning Electric voltage Install the device only if you have the necessary electrical engineering knowledge and experience Incorrect installation endangers your life and that of the user of the electrical system Incorrect installation can cause serious damage to property e g due to fire The minimum necessary expert knowledge and requirements for the installation are as follows Apply the five safety rules DIN VDE 0105 EN 50110 1 Disconnect from power 2 Secure against being re connected 3 Ensure there is no voltage 4 Connect to earth and short circuit 5 Cover or barricade adjacent live parts Use suitable personal protective clothing Use only suitable tools and measuring devices e Check the supply network type TN system IT system TT system to secure the following power supply conditions classic connection to ground protective earthing necessary additional measures etc Operating Instructions 1473 1 8103 7 Operating Instructions Busch W chter Installa
9. fter activating the mains supply voltage the device remains in test mode for 10 minutes see chapter Activation test Operating Instructions 1473 1 8103 16 Operating Instructions Busch Wachter Operation 8 3 Standard operation time and brightness dependent E 20 rs 10 sek MIN Fig 19 Normal operation Set the values for the brightness limit value and the switch off delay ON period of the light after the last detection Short time pulse for activating the staircase light timer switches or door bells Icon Function Ti Switching during all brightness levels Switching at nightfall C Switching during complete darkness IL Short time pulse 8 4 Auxiliary post operation 8 4 1 Operation with extension unit push button Aside from the movement detector being triggered by the infrared radiation in the detection range manual operation is possible via an extension unit push button For example when an exit is not within the detection range of the movement detector the extension unit push button can be used The lighting can there be switched on or off manually with the push button Fig 20 Operation with extension unit push button When operating with an extension unit push button the lighting for the set operating mode is switched on Operating Instructions 1473 1 8103 DE E E Operating Instructions Busch Wachter Remote control 9 Remote contr
10. ic membrane on the bottom of the device The installation is prepared Operating Instructions 1473 1 8103 sii Operating Instructions Busch Wachter Installation and electrical connection 6 2 4 Mounting steps Fig 9 Mounting the bottom of the device 1 Mount the device to the wall 26 5 mm 8 5 mm Do notuse countersunk head screws for mounting S YN Jf to the wall we po Use screws with a head diameter of 6 5 mm 8 5 e TS mm 3 5 mm 3 9 mm 2 Connect the power to the device see section 6 3 Observe the maximum admissible cable cross 1 5 2 5 mm sections max 14 5 mm The bolting dimensions of the base may be compatible with existing bores on older versions of the Busch Watchdog Latch the upper part of the device onto the base 3 To protect the device against unauthorized opening the enclosed screw can be used on the bottom of the device To protect the device against unauthorized opening screw the enclosed screw into the bottom of the device Operating Instructions 1473 1 8103 42 Operating Instructions Busch Wachter Installation and electrical connection 6 3 Electrical connection 6 3 1 Standard connection 16A L N N Q Fig 10 Standard connection With one circuit breaker the maximum sum current of 16 A is admissible for both relays 6 3 2 Standard connection with extension unit push button 16A Td N N S Fig 11 Standard
11. ol 9 1 Control elements of the remote control Fig 21 Control elements No Function 1 Resetting the switch on brightness to the settings of the potentiometers on the Busch Watchdog Press the button for at least 1 second 2 The current brightness is set as switch on brightness Press the button for at least 1 second Deactivation of presence simulation Presence simulation activation Continuous light between twilight and 22 30 p m CET or 23 30 CEST Followed by movement detection 5 Light deactivation for 4 hours No detection of movement 6 Light activation for 4 hours No detection of movement 7 Resetting to automatic movement detection O The sensitivity of the movement sensors can be adjusted to surroundings which are particularly restless or free of movement 9 2 Technical data of the remote control Designation Value Operating voltage 3VDC Battery type CR 2025 Battery life Approximately 2 years Coverage Maximum of 6 m Protection type IP 40 Operating temperature 0 C 45 C Operating Instructions 1473 1 8103 418 Operating Instructions Busch Wachter Remote control 9 3 Commissioning of remote control Fig 22 Removing the protective foil from the battery Remove the protective foil from the battery before commissioning Fig 23 Programming the remote control e Press the AUTO button on the
12. one of approximately one meter from the ground 4 2 2 Limitation of the detection range The horizontal detection range of the Busch Watchdog is 220 The detection range can be limited in case of special local circumstances To do this proceed as follows 1 Cutthe included adhesive film to the desired length 2 Glue the section of covering foil from the front onto the area of the sensor of your Busch Watchdog where the detection is to be blocked out O Note For an illustration see chapter 7 1 on page 14 Operating Instructions 1473 1 8103 5 Operating Instructions Busch Wachter Technical data 5 Technical data Designation Value Nominal voltage 230 V AC 10 50 60 Hz Switching capacity 3680 W VA Maximum switching current 16 AX Maximum power loss 1W Horizontal detection Busch Watchdog 220 220 Twilight sensor 0 5 300 lux Switch off delay 10 seconds 30 minutes Short time pulse Pulse duration Pause time Pause time with continuous light presence simulation 1 second 9 seconds 55 seconds Coverage if mounted 2 5 m high Maximum of 16 m Operating temperature 25 C 55 C Protection type IP 55 O Information for the connection of ballasts Please observe the following points regarding high inrush currents for ballasts The ballast manufacturer s specification determines the possible number o
13. remote control for at least 3 seconds within the period of 10 minutes after activating the power on the Busch Watchdog The Busch Watchdog must be de energized beforehand for at least 30 seconds The remote control will then automatically connect itself to the Busch Watchdog and the Busch Watchdog will flash if the reception is correct Repeat these steps to program a maximum of 9 additional remote controls 9 4 Battery change of remote control Fig 24 Changing the battery 1 Pull the battery holder out of the remote control 2 Insert a new battery of type 2025 The plus pole of the battery must be on top 3 Push the battery holder back into the device Operating Instructions 1473 1 8103 19 Operating Instructions Busch Wachter A member of the ABB Group Busch Jaeger Elektro GmbH PO box 58505 Ludenscheid Freisenbergstrake 2 58513 L denscheid Germany www BUSCH JAEGER com info bje de abb com Central sales service Phone 49 0 2351 956 1600 Fax 49 0 2351 956 1700 Notice We reserve the right to at all times make technical changes as well as changes to the contents of this document without prior notice The detailed specifications agreed to at the time of ordering apply to all orders ABB accepts no responsibility for possible errors or incompleteness in this document We reserve all rights to this document and the topics and illustrations contained therein Th
14. tion and electrical connection 6 2 Mounting Warning Electric voltage Risk of death and fire due to electrical voltage of 230 V Work on the 230 V supply system may only be performed by authorised electricians Disconnect the mains power supply prior to installation and or disassembly Caution Risk of damaging the device The lens of the device is sensitive and can easily sustain damage Do not press on the lens when setting the device 6 2 1 Mounting methods There are four methods of mounting the Busch Watchdog MasterLINE range The mounting hole is compatible with all previously available Busch Watchdog models The possible mounting methods are described in the following O Note The adapters for the following mounting methods must be ordered separately Wall mounting with gradient Ceiling mounting for the desired position Corner adapter Operating Instructions 1473 1 8103 8 Operating Instructions Busch Wachter Installation and electrical connection 6 2 1 1 Wall mounting Fig 2 Wall mounting Classic wall mounting 6 2 1 2 Wall mounting with gradient Fig 3 Wall mounting with gradient Wall mounting with gradient is recommended on a building situated on a hill or with a gradient This allows the detection ranged to be used effectively 6 2 1 3 Ceiling mounting a i Fig 4 Ceiling mounting There are two options for
15. tion in the commercial or private sector and is suitable for mounting to walls or ceilings At the appropriate installation height it offers a detection free zone of approximately one meter The Busch Watchdogs are passive infrared movement detectors which switch loads via the KNX bus when sources of heat move within its detection range Busch Watchdog is not an intrusion or attack alarm 4 1 Features of function and equipment Coverage of 16 m Continuous light switching Presence simulation e Storage of brightness switching threshold can be adjusted separately Operation with IR remote control possible e Extension unit operation e Detection free zone of a height of approximately 1 meter Dismantling protection e Display for detection and operation mode Disc type detection level Operating Instructions 1473 1 8103 RE Gs Operating Instructions Busch W chter Setup and function 4 2 Detection ranges 4 2 1 Overview of the detection ranges P s z Le 13 Le 16m gt Y gt a 0 7 m Fig 1 Detection ranges Detection range The detection range is 220 and the coverage is 16 m Ceiling mounting e toffers precise surveillance in small corridors if mounted to the ceiling at a maximum height of 8 m It forms a type of curtain in the detection range Ceiling mounting in a detection free zone Ata mounting height of 1 5 m the movement detector offers a detection free z