Home
        Sentry S-120-EDP Installation Guide
         Contents
1.    Slant Fin  x CERTIFIED    GAS FIRED CAST IRON BOILERS FOR eee AND L P  PROPANE GASES    HOT WATER MODELS S 34 THROUGH S 150  INSTALLATION AND OPERATING INSTRUCTIONS          CONTENTS  r              PAGE IMPORTANT                            Dimensions                      EET TTE 2 3 READ ALL OF THE FOLLOWING WARNINGS  Installation Requirements  AND STATEMENTS BEFORE READING THE  Boiler                                               3 INSTALLATION INSTRUCTIONS  Boiler Foundation    e Rp        e 3  Chimney Requirements                          4 WARNING  Minimum                                               4 SEE  WARNING  ON PAGE 4 FOR LIQUEFIED  Vent PIPING Si ie rp REED e eres 4 PETROLEUM  L P  PROPANE GAS FIRED BOILERS  Vent Damper Installation                         5  Gas                                                6 The installation must conform to the requirements of the  Electrical Controls and Wiring                  6 10 authority having jurisdiction or  in the absence of such  Boiler Water Temperature Control              10 15 requirements  to the National Fuel Gas Code  ANSI Z223 1   Sequence of Operation                         16 latest edition  The installation must also conform to the  Boiler Room Air Supply and Ventilation            17 additional requirements in this Slant Fin Instruction Book   Water Piping at                                    17  Operating Instructions  In addition  where required by the authority having jurisdic   Filling and Ven
2.   5 60 thru S 150   propane  57 58 59 59 60 60 61 62 63 63                               Orifice indicated for sea level above are factory installed in boiler unless otherwise specified by the local authority   See page 20 for burner input adjustment     Base Assembly INSTALLATION REQUIREMENTS    Sentry Boiler    The installation must conform to the requirements of the authority  having jurisdiction or  in the absence of such requirements  to the  National Fuel Gas Code  ANSI Z223 1 latest edition     This installation must also conform to the additional requirements  in this Slant Fin Instruction Book     NATURAL GAS FIRED BOILER LOCATION   Provide a level  solid foundation for the boiler  Location should be  as near as possible to chimney or outside wall so that the flue pipe  from boiler is short and direct     The location should also be such that the gas ignition system com   ponents are protected from water  dripping  spraying  rain  etc    during appliance operation and service  circulator replacement   condensate trap  control replacement  etc       BOILER FOUNDATION   A  Provide a solid  level foundation  capable of supporting the  weight of the boiler filled with water  and extending at least 2   past the jacket on all sides  See dimensions of boiler  page 2    Gas Valve B  For installation on non combustible floors only  The  Combustible Floor Kit part number printed on the boiler rating  plate is the only one to be used when installing on combustible  floors  The 
3.   NOTE  Observe operation of the pilot burner with appli   ance doors in the final operating position  Use of a mir   ror may be helpful     CARE AND MAINTENANCE    WARNING  THE FLOW OF COMBUSTION AND VENTILAT   ING AIR TO THE BOILER SHOULD NOT BE OBSTRUCTED   This section must be brought to the attention of the owner by  the installer so that the owner can make the necessary  arrangements with a qualified service agency for the periodic  care and maintenance of this boiler  The installer must inform  the owner that the gas supplier can recommend a number of  qualified service agencies  The installer must also inform the  owner that the lack of proper care and maintenance of this boil   er and any fuel burning equipment may result in a hazardous  condition    1  GENERAL MAINTENANCE   Information Manual    These operations are recommended to be performed at reg    ular intervals    A  BOILER HEATING SURFACES  clean off all coatings  found    B  BOILER CONTROLS  check contacts  settings  correct  functioning    C  PIPING  check piping and accessories for leaks    D  CHIMNEY VENTING SYSTEM  check for obstructions  and leaks    E  BOILER ROOM AIR SUPPLY  check air vents for contin   ued POSITIVE supply of air as required  Air needs are  greatest in cold weather  Air vents must be open and free  of obstruction    F  WATER SYSTEM CHECK    1  System to be full of water  and pressure to remain sta   ble at correct setting on gauge    2  Air control system  noise and air binding in ra
4.   O 120   24   120V 60HZ  RANSFORMER        HYDROLEVEL HYOROSTAT  CONTROL MODEL 3200         POWER SUPPLY  PROVIDE DISCONNECT  MEANS AND OVERLOAD PROTECTION  AS REQUIRED     L1 L2   2      B1 B2 I1 12          Figure 6  Multizoning of Sentry boiler 2 zone system pump zoning system using R882A B relays     Sentry    V8043E F    END  SWITCH    ZONE 1  THERMOSTAT    DISCONNECT  SWITCH       V8043E F    END    TH TR MOTOR SWITCH TH TR    V8043E F    END    MOTOR SWITCH    TH TR MOTOR    120   24    TRANSFORMER    OO O       HYDROLEVEL HYDROSTAT  CONTROL MODEL 3200       POWER SUPPLY  PROVIDE DISCONNECT  MEANS AND OVERLOAD PROTECTION  AS REQUIRED     BOILER  CIRCULATOR       Figure 7  Multizoning of Sentry boilers zone valve system using V8043E F zone valves     MULTIZONING  ZONE VALVE SYSTEM WITH INDIRECT  WATER HEATER  DHW PRIORITY  USING R882A B RELAY    ZONE 2  THERMOSTAT THERMOSTAT          V8043E F V8043E F V8043E F  END  SWITCH    OO    END END  TH TR MOTOR SWITCH TH TR MOTOR SWITCH TH TR MOTOR             DHW TANK  AQUASTAT DISCONNECT    SWITCH      sei              L2       120V 24V        TRANSFORMER    HYDROLEVEL HYDROSTAT  CONTROL MODEL 3200                      DHW TANK    L1L2C2CI       2 1112 CIRCULATOR                                                           HOT                     120V 60Hz SPACE HEATING   CIRCULATOR   NEUTRAL   N POWER SUPPLY  PROVIDE DISCONNECT  MEANS AND OVERLOAD PROTECTION    AS REQUIRED     JUNCTION  BOX       Figure 8  Multizoning  zone val
5.   Sentry       GAS   Was  INLET     ore  GAS CONTROL KNOB  SHOWN IN    OFF     POSITION           B S8600 Ignitor    Ignition Cable    w    Electric Ignition b  Pilot in Boiler    Side View  Gas Valve    Aluminum  Pilot Gas Tube    BURNER ADJUSTMENT  A  Adjust gas input rate     1  Consult gas supplier for higher  heating value of gas    Btu cu ft     2  Set thermostat high enough so that boiler will remain on  while checking rate    3  Measure manifold pressure at 1 8  tapping  Correct man   ifold pressure for gas used is printed on boiler rating  plate  NOTE  Gas pressure may be adjusted by turning  pressure regulator screw on combination gas valve  turn  clockwise to increase pressure  counterclockwise to  decrease pressure     a  Input for PROPANE is approximately at rating shown  on rating plate when manifold pressure is 9 1 2  water  column    b  Input for NATURAL GAS is approximately at rating  when manifold pressure is 3 1 2  water column  but  should be checked on the gas meter    Btuh Input   Btu cu  ft  x cu  ft  metered  in 3 minutes x 20   Example  1    For 1000 Btu cu ft  gas  this becomes    Btuh Input   cu  ft  metered in 3 minutes  x 1000 Btu cu ft  x 20   Example  2    For 1050 Btu cu ft  gas  this becomes    Btuh Input   cu  ft  metered in 3 minutes  x 1050 Btu cu ft  x 20    4  The higher  heating value of gas varies substantially for    different localities  Consult with Slant Fin   s Technical  Service Dept  for re orificing procedures if any of the fol 
6.   UA Gas Vah ediment Trap  16      i     S i  required            gas tapping 1   2    SOB c rV LOK I E c  Left End View Front View Right End View       Note  Height dimension increases by 1 3 4  when comustible floor kit is used     Vent damper may be installed horizontally on all models with use of a vent elbow  For more information  see figure 2  page 5     Sentry 3                                                             Dimensions Approx  CHIMNEY RECOMMENDATIONS   inches  Total Wt  HEIGHT 15 ft   minimum  from draft    Full of hood skirt to top of chimney   Boiler Mo ori  2 B    B E F G   Water Ib    INSIDE DIAMETER  Same as dimen   Model Sect   max     sion     or larger    NOTE  Larger chimney may be  S 34 2 8  14   4 33              190 required if two or more boilers      a boil   S 60 3 11   17   4 37  414  26        250 er and another appliance are vented to            it ii yn yu a single chimney   S 90 14  20  5 ud 5  25  6  PED Slant Fin supplies vent dampers by  8 120 5 17   23   6 37  TE 25        365 several manufacturers  Some         S 150 6 20   26   7 37  8    241        425 smaller than the indicated       maxi                 Orifice Sizes for High Altitudes  Orifice Includes 4  Reduction for Each 1000 Feet  Size for Elevation   Feet  Boiler Gas Sea  Model Type Level   2000   3000 4000   5000 6000   7000   8000   9000   10000  8 34 Natural   47 48 48 49 49 49 50 50 51 51  Propane  56 56 56 57 57 57 58 59 59 60  Natural   50 51 51 51 51 52 52 52 53 53
7.   lowing apply        Sentry    a  Boiler  burner  is overfiring  CAUTION  National Fuel  Gas Code ANSI Z223 1 latest edition  does NOT per   mit firing at a higher input rate than the input rate indi   cated on the boiler rating plate in order to avoid haz   ardous conditions such as explosion or carbon  monoxide poisoning    b  Poor higher  heating value of gas is causing the actu   al input to be substantially lower than the rating plate  indication          Higher heating value  of gas is commonly known as a  heating value       GAS RATE TABLE   The gas metered in 3 minutes to obtain rated input for each  boiler model  using 1000 Btu cu  ft  gas  is tabulated in gas rate  table           Boiler rated input in                    ft  hr  of 1000 Btu cu  ft  1000 Btu cu  ft  gas  in 3  Natural Gas minutes  at rated input   T 1 70   60 3 00   B0 4 50   10 6 00   150 7 50   180 9 00   210 10 50          21    2  Safety Shutdown Checkout   a  For proper operation the pilot should engulf the thermo   couple or flame sensor as shown below    b  To adjust pilot  turn pilot flow adjustment screw on valve  clockwise or counterclockwise to give a steady flame  enveloping 3 8 to 1 2 inch of the tip of the thermocouple  or flame sensor  Note that turning the pilot adjust screw  clockwise will decrease the pilot flame    c  Check safety shutdown of gas valve by following procedure  outlined  CARE  and  MAINTENANCE  section     Manifold    Front back sliding primary air  shutter locking 
8.  Arrangement    mary secondary pumping  with a boiler loop  must be used  to provide a minimum 130  F return water temperature to  the boiler  This will prevent condensation on the cast iron  sections that can result in improper operation of the boiler     OPERATING INSTRUCTIONS    A  Fill the system with water  Vent or purge off air    B  Fire the boiler as soon as possible  see following warning  and instructions  and bring water temperature to at least  180 degrees  while circulating water in the system    C  Vent air and add water as needed to achieve operating  pressure on boiler gauge  Pressure must be between  approximately 12 psi  cold water  and 25 psi  at water tem   perature setting of high limit control   for boilers equipped  with 30 psi relief valves  Boilers rated for a higher pressure  and equipped with a matching relief valve may operate at a  higher pressure  but no higher than 5 psi below the relief  valve opening pressure    D  Check for and repair any leaks before placing system in  service    Before firing boiler  make these checks    1  System is full of water  Air is vented or purged    2  Relief valve is installed in accordance with the ASME Boiler  Pressure Vessel Code  Section IV  Valve opening is not  closed or reduced in size    3  Venting is installed according to instructions under    VENT  PIPING       4  All wiring is completed  following applicable wiring dia   grams    5  Using soap solution  check for gas leaks in all gas piping  from meter
9.  E SERI B      ee    Economy Dial   OFF or LO  1  2  3     4 5         Factory 1             Indicator Light   announces heat call     Spade Connectors  for OS 100 Outdoor  Sensor Kit    Differentials  are automatic  and will vary  based on  control settings  and boiler tem   perature     JA      ex    L2 C2 E  gt   B2    IMPORTANT NOTICE  This boiler is equipped with a feature that saves energy by reducing the boiler water  temperature as the heating load decreases  This feature is equipped with an over   ride which is provided primarily to permit the use of an external energy manage   ment system that serves the same function  THIS OVERRIDE MUST NOT BE  USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE     An external energy management system is installed that reduces the boiler water  temperature as the heating load decreases    This boiler is not used for any space heating    This boiler has an input of 300 000 BTU hr or greater    This boiler is part of a modular or multiple boiler system having a total input of  300 000 BTU hr or greater     This boiler is equipped with a tankless coil     SETTING   OFF Disables economy function  Will allow boiler to fire until hi  limit temp is reached and re fire with a 10  subtractive  differential     Provides lowest level of fuel savings  Use this setting only  if the house does not stay warm at higher settings     Recommended setting for single zone systems  Recommended setting for Two zone systems  Recommended setting 
10.  intermittent  pilot system  with main burners firing  disconnect the  ignition cable from the 58600 IGNITOR BOX  The gas  valve should shut off the main burners    If the gas valve fails to shut down main burners when the  test is performed  replace the gas valve    Check for gas leaks from valve and gas piping to burners  and pilot  If leaks are found  repair or replace as required       PROVIDING PROTECTION FROM FREEZING  A     Anti freeze is sometimes used in hydronic heating sys   tems to protect against freeze up in the event of power  failure or control shutdown when the building is unoccu   pied  It should be recognized that unless the building is  kept above freezing temperature by some means  the  plumbing system is not protected    PROPYLENE GLYCOL is used in the quick freeze food  industry  it is practically non toxic  Its use may be permit   ted when tankless heaters are used  When anti freeze  must be used  inhibited propylene glycol is recommend   ed  Useful information on the characteristics  mixing  proportions  etc  of glycol in heating systems is given in  Technical Topics No  2A  available from the Hydronics  Institute 34 Russo Place  Berkeley Heights  NJ 07922   Consult glycol manufacturers for sources of propylene  glycol  DO NOT use ethylene glycol because it is toxic       Water Treatment     A good water treatment program will not only extend the  useful life of this boiler but it will also save much of the  time and expense of repairs made necessary 
11.  to boiler pilot and manifold  DO NOT use  open flame     18    FROM THE REST  OF SYSTEM       all SPACE HEAT    FH  ZONE  2 j             ISOLATION  V                SPACE        FLOW CHECK    VALVE Ll      CIRCULATOR    HEAT    ZONE  1          ISOLATION  VALVE    PURGE   DRAIN  VALVE                  BOILER    BOILER    2    RETURN 5       AIR VENT     72 AIR SEPARATOR     a          PRESSURE  REDUCING  VALVE  ISOLATION   VALVE    EXPANSION TANK    S  DIAPHRAM TYPE                                   FLOW CHECK  VALVE    f      ARD     i  CIRCULATOR        p RELIEF    BOILER VALVE  SUPPLY                  ISOLATION  VALVE    DOMESTIC  HOT WATER  TANK    Figure 11  Zoning with circulators  optional indirect DHW tank    Sentry    TO THE REST  OF SYSTEM      lt   3       ISOLATION  vave A        SHUTOFF  VALVE    MAKE UP  WATER  SUPPLY    BACK FLOW  PREVENTOR   IF REQUIRED     HOT WATER        OUTLET    SHUTOFF  VALVE    COLD      INLET  WATER    HANC DRAIN VALVE       Sentry    FROM THE REST  OF SYSTEM                               ISOLATION       VALVE    ISOLATION  VALVE    PURGE   DRAIN  VALVE    BOILER  RETURN    SPACE HEAT      19    TO THE REST  OF SYSTEM    ZONE  2                                                            SPACE HEAT  ZONE  1    ISOLATION  VALVE    mi  FLOW CHECK  VALVE    DHW   CIRCULATOR            RELIEF    VALVE  BOILER                                                 Figure 12  Zoning with zone valves  optional indirect DHW tank    ZONE  VALVE    FL
12.  with indirect water  heater  see figure 11 and 12    AIR CONTROL SYSTEM   A  DIAPHRAGM TYPE COMPRESSION TANKS are used  to control system pressure in an AIR ELIMINATING SYS   TEM  an automatic air vent is used to REMOVE air from  the system water  See figure 8  If system pressure needs  further control  add an additional tank or install a larger  capacity tank  Locate the tank near the boiler  as illustrat   ed An automatic air vent should be installed in the top of  the boiler or air purger  See figure 10    B  PUMP LOCATION     Locating low head pump s  on  return to boiler is acceptable for smaller boiler sizes in  residences of one or two stories  The alternate pump  location shown in illustration is required in large  multi   story building installations  especially when high head  pumps are used  The compression tank must be at the  boiler or between boiler and supply main pump s    IMPORTANT  Hot water heating systems containing high  water volume  such as would occur with cast iron radia   tion  require special care with air elimination    The circulator pump should be located on the boiler sup   ply pipe and the expansion tank and air scoop should be  located near the pump suction    C  Radiant floor and low water temperature systems   A boiler by pass loop  three way valve arrangement  or pri     17    Flow  Control  Valve    3 4  Pressure  Relief Valve        Alternate  Air Vent    Alternate  Circulator          Expansion    Tonk Circulator       Figure 10  Piping
13. ARK GENERATOR MODULE POWERED   S8600F OR 58600    IGNITION SPARK STARTS AND PILOT VALVE OPERATOR OPENS   S8670E  IGNITION SPARK AND PILOT VALVE OPERATOR DELAYED FOR 30 70 SECONDS                                    NATURAL GAS  S8600F  IGNI   L P  PROPANE GAS  58600          THE PILOT FLAME ESTABLISHED    gt   TION SPARK CONTINUES   S8670E  IGNITION TRIAL CONTINUES PILOT VALVE REMAINS OPEN  FOR 90 SECONDS  AFTER TRIAL FOR   YEs UNTIL SYSTEM IS RESET                 IGNITION  SYSTEM SHUTS OFF   AFTER 5 MINUTES MODULE RE   INSTATES TRIAL FOR IGNITION  IF  PILOT FLAME NOT ESTABLISHED   IGNITION TRIAL  SYSTEM SHUT OFF  AND 5 MINUTES WAIT SEQUENCE  REPEATS CONTINUOUSLY     SPARK GENERATOR OFF  MAIN VALVE  OPERATOR OPENS  MODULE MONITORS  PILOT FLAME                       WHEN THERMOSTAT IS SATISFIED OR WHEN HIGH LIMIT OR LOW WATER CUT OFF CONTACTS ARE OPEN  VALVE OPERA   TORS CLOSE  PILOT and MAIN BURNERS OFF  VENT DAMPER CLOSES  CIRCULATOR OFF  SYSTEM GOES TO STANDBY              Sentry    BOILER ROOM AIR SUPPLY AND VENTILATION   An ample supply of air is required to obtain combustion and  ventilation  ALL AIR COMES FROM OUTSIDE  directly through  wall openings to the boiler or through unsealed openings  around windows  doors  etc  in the whole building  When build   ings are insulated  caulked and weather stripped  now or later  on  direct openings to outside may be required and should be  provided  If the boiler is not near an outside wall  air may be  ducted to it from outside 
14. L TARGETING WORKS    Thermal Targeting technology analyzes thermostat activity and  continually evaluate how much heat the house requires  When  it is very cold outside  the heat demand is high and the Fuel  Smart HydroStat will raise the boiler s Target temperature to  provide needed heat to the home  When the outside tempera   ture is milder  the heat demand is lower  During these periods   the Fuel Smart HydroStat will lower the boiler s Target temper   ature     saving fuel     while continuing to provide comfort to the  house     Smart DHW Priority   During a call from indirect water heater  the control will de energize the circulator contacts  C1 C2  to heat  only the indirect tank ensuring an adequate supply of domestic hot water  The control will re energize the circuator when the  indirect tank is satisfied or if the boiler temperature reaches 1707    If the indirect call continues for 45 minutes  the control will  overide the priority function energizing the circulator to provide space heating     LED LEGEND and TEST SETTINGS BUTTON       TEMP ACTIVE Indicates that the  Fuel Smart HydroStat control is pow   ered and that the temperature function    is active   a             TEMP  HIGH TEMP Iluminates E EJE  when the boiler water temperature  lt               reaches the high limit setting  It will              remain lit until the water temperature falls    Q LOW WATER    boiler water reaches the target tempera   ture  the LED illuminates and the burner  will shut d
15. ONTROL  TWO HEATING APPLIANCES    DAMPERS    K    J    HEATING HEATING HEATING HEATING  APPLIANCE APPLIANCE APPLIANCE APPLIANCE    WRONG WAY CORRECT WAY    Figure 3        above the vent pipe  to avoid excessive heat  or below the vent pipe     to avoid possible condensate damage         Figure 2  Horizontal Installation of Vent Damper       WARNING   DANGER   Once you have begun vent damper installation procedure  DO  NOT restore electric power and gas supply until installation and  inspection have been completed  in order to prevent the main  burners from operating   DO NOT operate the boiler until the vent  damper harness is plugged into vent damper operator  Failure to  observe this warning may create a hazardous condition that  could cause an explosion or carbon monoxide poisoning        6    GAS PIPING     A  Local installation codes apply  The pipe joint compound used    on threads must be resistant to the action of liquefied petro   leum gases     B  The gas supply line to the boiler should be run directly from    the meter for natural gas or from the fuel tank for L P    propane gas  See page 2 for location of union and manual   main shutoff valve that may be specified locally    Selecting pipe size for natural gas    1  Measure or estimate the length of piping from the meter  to the installation site    2  Consult gas supplier for heating value of gas  Btu cu  ft      3  Divide boiler rated input by heating value to find gas flow  in piping  cu  ft  per hour     4  
16. OW     SYSTEM VALVE i    CIRCULATOR    SHUTOFF  PRESSURE VALVE  REDUCING  VALVE  MAKE UP  WATER  SUPPLY    BACK FLOW  PREVENTOR   IF REQUIRED     EXPANSION TANK   DIAPHRAM TYPE     ISOLATION  VALVE    HOT WATER      OUTLET  DOMESTIC  HOT WATER    SHUTOFF  VALVE    COLD      INLET  WATER      lw DRAIN VALVE       20    SAFETY INFORMATION  FOR YOUR SAFETY READ BEFORE OPERATING          WARNING   f you do not follow these instructions exactly   a fire or explosion may result causing property damage   personal injury or loss of life           TOU          10   11   12               This appliance is equipped with an ignition device which   automatically lights the pilot  DO NOT try to light the pilot   by hand    BEFORE OPERATING smell all around the appliance area   for gas  Be sure to smell next to the floor because some   gas is heavier than air and will settle on the floor    WHAT TO DO IF YOU SMELL GAS      DO NOT try to light any appliance      DO NOT touch any electric switch  DO NOT use any  phone in your building       mmediately call your gas supplier from a neighbor s  phone  Follow the gas supplier s instructions       f you cannot reach your gas supplier  call the fire  department    Use only your hand to push in or turn the gas control knob    NEVER use tools  If the knob will not push in or turn by   hand  DON T try to repair it  call a qualified service techni    cian  Force or attempted repair may result in a fire or   explosion    DO NOT use this appliance if an
17. URES Continued       RESTORE FACTORY DEFAULT SETTINGS   To restore all features to the factory default settings  see following chart for default settings   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro   2  Turn the HI TEMP dial to select feature dEF   3  Push the Test Settings Button to 4 to reset all features to the default settings    4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 11     Record      Default Your  Description Setting   Settings    Purge Inactive  Purge Active    Automatic Reset  Manual Reset    Circulator operation on T TV call only  Circulator operation on 11 12 call only  Circulator operation on call from either    Circulator Hold Off     Active  Circulator Hold Off     Inactive    Not available  on this control  Not available  on this control  Low Water Cut Off an  Function         Restore Factory u Restore Defaults    Defaults n Do Not Restore Defaults    SEE PAGE 18 FOR ADDITIONAL SETTINGS             Circulator Hold Off  feature would be  Active  if defaults are restord  Turn it OFF  Inactive  if required     Sentry    SYSTEM START UP    At initial start up  with the Economy Feature active  the control  establishes a 145  F target temperature  To test the high limit  shut off function  the Economy Dial must be turned to OFF   Once tested  restore the Economy setting  If the heating  demand is high  the target will increase over time to satisfy the  heat load     NOTE     15    HOW THERMA
18. Use table A to select proper pipe size    Example  Boiler model S 150 is to be installed  Distance   from gas meter to the boiler is 30 ft  Heating value of natur    al gas is 1020 Btu cu  ft  Select proper pipe size     Gas flow   150 000 Btu hour   147 cu  ft  per hour  1020 Btu cu ft     At 30 ft  length of pipe  match required capacity from Table A   choose higher capacity  in this case is 152 cu  ft  per hour    Required pipe size is 3 4     Improper gas pipe sizing will result in pilot flame outages   insufficient heat and other installation difficulties  For more  information and also if other appliances are to be attached  to the piping system  see Appendix C of National Fuel Gas  Code ANSI Z223 1 latest edition          The boiler and its gas connection must be leak tested before    placing the boiler in operation  Use liquid soap solution for all  gas leak testing  DO NOT use open flame    This boiler and its individual shutoff valve must be disconnect   ed from the gas supply piping system during any pressure test   ing of that system at test pressures in excess of 1 2 PSIG   This boiler must be isolated from the gas supply piping sys   tem by closing its individual manual shutoff valve during any  pressure testing of the gas supply piping system at test  pressures equal to or less than 1 2 PSIG       All gas piping used should be inspected thoroughly for    cleanliness before makeup  A sediment trap must be pro   vided  as illustrated on page 2       The minimum a
19. boiler must not be installed on carpeting    C  If boiler is to be located over buried conduit containing electric  wires or telephone cables  consult local codes or the National  Board of Fire Underwriters for specific requirements        WARNING  SPECIAL ATTENTION FOR LIQUEFIED PETROLEUM   L P   PROPANE GAS FIRED BOILER INSTALLATIONS    LPG appliances  boilers  shall be installed in accordance  with applicable provisions of NFPA 58   Liquefied Petroleum  Gas Code  latest edition for installations in US and  CAN CGA B149 1 latest edition for installations in Canada     Liquefied Petroleum  LP  propane gas is heavier than air  therefore Propane gas accumulate at floor level  If you sus   pect a leak  do not attempt to operate boiler  A spark or flame  from the appliance  boiler  or other sources may ignite the  accumulated propane gas causing an explosion or fire  It is  recommended that inspections for gas leaks be performed  periodically by licensed professional and that leak detection  devices be installed as a further safety measure     CHIMNEY REQUIREMENTS   A  Sentry boilers may be vented into a masonry vitreous tile   lined chimney or type    B    venting system NOT EXPOSED to  the OUTDOORS below the roof line    Venting and sizing of venting system must be in accordance   with National Fuel Gas Code ANSI Z223 1  NFPA 54   latest   edition which will be referred to as the National Fuel Gas   Code  Local codes apply    If a masonry chimney is exposed to the outdoors on 
20. by pre   ventable occurrences    A reputable water treatment company should be consult   ed to evaluate and determine the best overall treatment  program for your boiler equipment       KEEP THE BOILER AREA CLEAR AND FREE FROM    COMBUSTIBLE MATERIALS  GASOLINE  AND OTHER  FLAMMABLE VAPORS AND LIQUIDS     Sentry    BURNERS FAIL TO OPERATE   CAUSE   Safety pilot out  or flame too low    Gas supply valve shut off    Electric switch open    Blown or defective line fuse    Operating or limit control contacts open or dirty   Defective gas valve or pressure regulator  or plugged  bleed line    Obstruction at main burner orifice    Break in wiring or loose contact at control terminals   Improper wiring     om poc        ON    10  Improper controls   11  Rollout or blocked vent safety switch open     GENERAL TROUBLESHOOTING GUIDE FOR SERVICEPEOPLE 23    REMEDY   Check  clean  re light  See instructions    Open gas valve S     Close switch    Replace fuse    Check control  Clean contacts or replace control   Repair or replace     OOV     oO ct          Check  clean and reinstall    Check with test light and correct    Check and correct in accordance with wiring diagrams  included with appliance instructions    10  Install proper controls    11  Replace rollout switch  inspect flue passages prior to  replacement  or reset blocked vent safety switch by  depressing the reset button                BURNERS WILL NOT SHUT OFF  CAUSE  1  Defective operating control  gas valve  or high limit  
21. control   2  Improper wiring or short circuit     REMEDY  1  Check  repair or replace     2  Check wiring and controls        FLASH BACK   BURNING AT ORIFICES  CAUSE     Manifold gas pressure too low   Improper primary air adjustment   Gas regulator bleed too slow    Burrs on orifice    Improperly drilled orifice plugs   Leaking automatic gas valve   Adverse draft condition in boiler room   Low main gas pressure    Safety pilot improperly installed        0o NO Oh CD  N     REMEDY   Adjust to proper manifold pressure    Adjust air to produce soft  clean flame   Adjust bleed opening    Remove burrs    Install orifice plugs with proper drilling   Repair or replace    Check air supply and venting system   Contact utility    Correct to manufacturer s recommendations      00 N O      ON       DELAYED IGNITION   CAUSE   Pilot flame too low    Pilot burner ports or pilot orifice clogged   Burners or orifices out of alignment   Excessive primary air    Excessive burner input    Adverse draft condition in boiler room     FUMES AND GAS ODORS  CAUSE  1  Leaks in gas piping or accessories   2  Gas leaks in service line or meter connections     o mre o m    3  Blocked chimney   4  Boiler flueways blocked with soot     5  Undersized breeching or too many turns in breeching   6  Adverse draft condition in boiler room   7  Overfiring     CONDENSATION IN BOILER FLUES OR IN VENT SYSTEM  CAUSE   1  Underfiring    2  Boiler water maintained at too low a temperature level     3  Long horizontal r
22. cover and re seal with furnace cement   Replace jacket top  Remove and dispose of paper  and accumulated material   8  If burner surfaces are not clean  or if uneven flame  indicates plugged burner ports  remove and clean  burners     noo    WARNING     The ceramic combustion chamber in the burner box  contains crystalline silica     Wear proper dust mask and gloves when servicing  combustion chamber or burners     Crystalline Silica has been identified as a carcinogen or  possibly carcinogenic to humans        NOTE TO REMOVE BURNERS   1  Disconnect pilot at pilot mount  or disconnect pilot gas    line at gas valve  before removing burners next to pilot     2  Lift burner and remove burner from orifice   3  Clean and replace burners  and pilot  Adjust burners as    described on page 10           clean burners run a clean flue brush up the tube until all foreign  matter is removed     4  SAFETY CHECK FOR CONTROL SYSTEM  A  High limit control test  Set thermostat high enough for    boiler water temperature to reach high limit control set   ting  When this temperature is reached  the high limit  switch should open  and the main gas valve should close    C        Sentry    JACKET    TOP FLUE COLLECTOR   FLUE COVER     BOILER CLEANING       automatically  If the high limit does not operate to close  the main gas valve  the valve  the high limit or the wiring  is faulty  Repair or replace immediately       Gas valve safety shutdown test     For boilers equipped with Honeywell S8600
23. ctivate Circulator Hold Off   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro  2  Turn the HI TEMP dial to select feature 5   3  Push the Test Settings Button to turn Circulator Hold Off or GFF   4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 11    LOW WATER CUT OFF FUNCTION   To turn off Low Water Cut Off   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro  2  Turn the HI TEMP dial to select feature 8   3  Push the Test Settings Button to turn Low Water Cut Off or GFF   4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 11     OUTDOOR RESET READY AND WARM WEATHER SHUTDOWN  Hydrostat Control model 3200   PLUS features outdoor reset ready  must use optional kit part no  430423000   See installation instructions packed with the kit     Outdoor Reset and Warm Weather Shutdown  Attach the spade connectors to the right and center posts  OR and C  for full outdoor reset functionality including warm weather  shutdown protection  Wiring this way overides the Thermal Targeting function of the Fuel Smart HydroStat control   See pg 11     Warm Weather Shutdown Only   Connect the wire ends to the left and center spade connectors  WWSD and C  to add Warm Weather Shutdown functionality  only  When wired this way  the Fuel Smart HydroSTat control will utilize its internal Thermal Targeting function to reset the boiler  temperature   See pg 10     14 Sentry    OPTIONAL FEAT
24. d be at least 10  below the high limit setting   NOTE  For cold start operation  the low limit must be  turned OFF  IMPORTANT  If low limit temperature can   not be set above 140  F  remove jumper      Setting  range  OFF or 110   200  F         Dynamic  Display    Water Temperature    and Real Time  Verification of Setting  Adjustments        High Temperature  Limit Setting   100   220  F     Factory 190 F        Low Temperature   Limit Setting       OFF or 110   220  F   Factory OFF    SETTING THE ECONOMY FEATURE   The Economy Feature is factory set for a 1 zone heating system   To adjust  turn the ECONOMY Dial    until the number dis   played equals the number of heating zones  Do not include indi   rect water heaters in the number of heating zones  The Economy  Feature conserves fuel by reducing boiler temperature  see    How  Thermal Targeting Works    below   If the heating system is unable  to supply needed heat to the house  the ECONOMY Dial should  be turned to a lower setting  example  In a three zone house  turn  the dial to 2 or 1   Conversely  if the boiler provides adequate  heat  added fuel savings can be achieved by selecting a higher  setting  example  4 or 5   If the heating and indirect water heater  signals were not separated when wiring the control  the Economy  Feature should be turned OFF to insure the boiler supplies ade   quate temperature to heat the indirect tank     Vent Damper  Receptacle            Diagnostic LEDs  Test Settings Button           
25. diation  should not occur         Refer also to Owners    3  Water lines  slightest leaks should be corrected   4  Low water cutoff  for operation  see instructions fur   nished with unit      2  WATER LEVEL CHECK DURING HEATING SEASON  A  Check water pressure regularly and add water slowly to    system when needed  If much water is added  venting  may be necessary     B  Regular loss of water from water boiler system may indi     cate either a system leak  or a faulty air control system   or a faulty automatic fill valve     3  ANNUAL INSPECTION AND CLEANING  A  It is important that this boiler be inspected by a compe     tent serviceperson to help insure safe and reliable oper   ation     Check for gas leaks from valve and gas piping to burners  and pilot  If leaks are found  repair or replace as required     This inspection should include   1  Controls check  See  Safety Check for Control  System   No  4  below   2  Recheck of input gas rate to burners  See  Initial  Start  paragraph in  Operating instructions  section   3  Re adjusting for best flame characteristics of main  flame and pilot s    See  Initial Start  paragraph in  Operating  Instructions  section and see  Burner Adjustment   section   4  Burner and boiler flue passage cleanliness   BURNER AND FLUE CLEANING  see figure 17   It is  suggested that paper be placed on burners to collect  any foreign material when cleaning flues   Remove jacket top and flue cover   Use wire brush to clean flueways   Replace flue 
26. eing valved to the piping  system     Sentry    Separate control devices on the boiler and chiller may be used   or a single set of air and pressure controls on the common pip   ing may be preferred     If the boiler is used to supply hot water to heating coils in air  handling units  flow control valves or other devices must be  installed to prevent gravity circulation of water in the coils dur   ing the cooling cycle        IF REPLACEMENT PARTS ARE NEEDED    When parts are needed  refer to boiler model and serial num   ber shown on the boiler name rating plate  Refer to publication  number S 11PL Sentry Replacement Parts for part numbers   Whenever possible refer to the original order by number and  date     Control identification and replacement should not be attempted  by unskilled personnel  Only simple  easily identified controls  and parts may be obtained locally  All other controls and    parts should be identified by and ordered from Slant Fin   Relief Safety valves must be ASME rated for the pressure and  gross output of the boiler     For replacement parts  heating contractors should contact their  Slant Fin boiler distributor     Sentry    25    APPENDIX A    Removal of Existing Boiler from Common Vent System     At the time of removal of an existing boiler  the following steps shall be followed with each appliance remaining connected to  the common venting system placed in operation  while the other appliances remaining connected to the common venting system    a
27. erature is below 100 degrees     To change between degrees Fahrenheit and degrees Celsius   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro  2  Turn the HI TEMP dial to select feature 2   3  Push the Test Settings Button to c for Celsius or F for Fahrenheit   4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 10     MANUAL RESET LOW WATER CUT OFF   The low water cut off operation on the HydroStat can be set to operate in automatic  default  or manual reset mode  When in  manual reset mode  the control will shut down the burner immediately when a low water condition is detected  If the low water  condition is sustained for 30 seconds  the low water light will blink  indicating that the control has locked out the burner  The  control can only be reset by pushing the Test Settings button on the top of the control  The manual reset feature meets CSD 1    code requirements     IMPORTANT  The system must be checked by a qualified heating professional prior to resuming operation   WARNING  DO NOT ADD WATER UNTIL THE BOILER HAS FULLY COOLED     To activate Manual Reset LWCO mode   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro   2  Turn the HI TEMP dial to select feature 3   3  Push the Test Settings Button to R for Automatic Reset Mode or b for Manual Reset Mode  4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 10     To Test the Manual Reset Feature  Press and ho
28. ermostat Connections  Thermostat wire connections must be to T and TV screw  terminals of boiler temperature control  See figure 4    Thermostat Heat Anticipator Adjustments  If the 24V room thermostat that controls this boiler has an  adjustable heat anticipator  connect entire system to thermostat  and run the system while measuring the current drawn through  the thermostat wires  Set the heat anticipator at the value  measured  The set current should match power requirements by  zone valves and relays  Add an additional 0 1 Amp to the  measured current for vent dampers  Refer to the manufacturer s  instructions of zone valve  vent damper and relays  Also  see  instructions with the thermostat   4  Multi Zoning  For pump zoning system  see figure 5 and 6 for zone valve  system  see figure 7  DO NOT use control transformer to  power external accessories like zone valve and relay  over  load and or burned out transformer and boiler malfunction  can result   5  Indirect External Water Heater  If the system includes indirect water heater  the indirect signal  must be sepatayed from heating zone s  system  See figure 6  and 8  Follow steps below   a  Connect end switch of the indirect water heater relay to 11  and I2 of the boiler temperature control   b  Connect end switch of the heating zones s  relays to T and  TV of the boiler temperature control   c  Power DHW and heating zone s  circulators through end  switch relays as shown on figure 6  Do not connect heating  zone s  ci
29. for Three zone systems  Recommended setting for Four zone systems  Recommended setting for Five zone systems  Provides highest level of fuel savings       12 Sentry    OPTIONAL FEATURES    NOTE  The Program Mode   Pro   is accessed by turning the  LO TEMP dial to a position just above OFF    THERMAL PRE PURGE   Thermal Pre Purge is designed to maximize boiler efficiency  When activated  the control will supply latent heat that may remain  in the boiler from a previous run cycle to the next heating zone that calls  The control monitors how quickly the boiler tempera   ture is declining and activates the burner only when it determines that the latent heat is insufficient to satisfy the call    During the purge cycle  the display will indicate Pur  This feature works with single zone and multi zone heating systems utilizing    circulators or zone valves  No change in wiring is needed     To activate Thermal Pre Purge   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro  2  Turn the HI TEMP dial to select feature     3  Push the Test Settings Button to turn Thermal Pre Purge or OFF   4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 10    Note  Activation of this feature is not recommended for boilers with tankless coils     DEGREES FAHRENHEIT OR CELSIUS  The control has the ability to operate in degrees Fahrenheit or Celsius  When operating in Celsius  a will appear in the display  next to the temperature whenever the temp
30. ge    C  All minimum clearances shown above must be met  This  may result in increased values of some minimum clearances  in order to maintain the minimum clearances of others    D  Clearance from hot water pipes shall be 1 inch         At points where hot water pipes emerge from a floor wall or ceiling  the  clearance at the opening through the finished floor  wall or ceiling boards    may not be less than 1 2 inch  Each such opening shall be covered with  a plate of non combustible material     SAFETY        KEEP THE BOILER AREA CLEAR AND FREE FROM  COMBUSTIBLE MATERIALS  GASOLINE AND OTHER    FLAMMABLE VAPORS AND LIQUIDS        VENT PIPING      A  Vent piping installation must be in accordance with ANSI  Z223 1 latest edition  National Fuel Gas Code  Venting of  Equipment  Other local codes may also apply and must be  followed    B  Boiler vent pipe must be the full diameter of the boiler outlet   See dimensions  page 2    C  If more than one appliance vents into a common breeching   the area of the breeching must be equal to the area of the  largest vent plus 50  of the area of the additional vent  areas  Vent connectors serving appliances vented by natur   al draft shall not be connected into any portion of mechani   cal draft systems operating under positive pressure   Horizontal breeching or vent pipe should be as high as pos   sible  consistent with codes  so that vertical vents from appli   ances will have a high rise above draft diverter openings  All  horizontal ru
31. ld the Test Settings button located on the top of the control for 30 seconds to  simulate a low water condition  After 30 seconds  the Low Water light will blink indicating that the control is locked out  To reset  the lock out condition  press the Test Settings button momentarily     MORE OPTIONAL FEATURES ON NEXT PAGE    Sentry 13    OPTIONAL FEATURES Continued    CIRCULATOR ACTIVATION OPTIONS  When in the default mode  the HydroStat activates the circulator  C1 C2 contacts  on calls to T TV  The control can be pro   grammed to activate the circulator on calls to 11 12 in place of  or in addition to  calls to T TV     To change how the Circulator is activated   1  Turn the LO TEMP dial to access the Program Mode   indicated in the display as Pro  2  Turn the HI TEMP dial to select feature   3  Push the Test Settings Button to select between the following options      Circulator on T TV call only     Circulator on 11 12 call only     Circulator on both          amp  11 2 calls   4  Reset LO TEMP and HI TEMP settings to desired temperatures  see page 11    CIRCULATOR HOLD OFF  ENHANCED CONDENSING PROTECTION    To reduce the potential for condensing  on a call for heat the control will allow the boiler to heat to 125  F prior to energizing the  circulator  Once energized  the circulator will remain on for the duration of the heating call unless the boiler temperature drops  below 115  F  If this occurs  the circulator will re energize when the boiler returns to 125  F     To a
32. llation conforms with the  National Fuel Gas Code  ANSI Z223 1 latest edition  When  resizing any portion of the common venting system  the  common venting system should be resized to approach the  minimum size as determined using the appropriate tables in  Appendix G in the National Fuel Gas Code  ANSI Z223 1   latest edition     26    Sentry    Sentry    27     SlantFin Corp  2014  Printed in the U S A  414  Publication No  5 41  P N 46 0602       Slant Fin     BOILERS  amp  BASEBOARD       SLANT FIN CORPORATION  Greenvale  N Y  11548     Phone   516  484 2600  FAX   516  484 5921    Canada  Slant Fin LTD LTEE  Mississauga  Ontario          Ony N  r Ho            You Want Heating You i  www slantfin com    
33. nd maximum gas supply pressure  at the    inlet of gas valve  are shown on the boiler rating plate for the  type of gas used  Gas supply pressure should never be less  than minimum or more than maximum pressure when the  boiler or any other appliance is turned on or off     Sentry                Length Gas Flow In Piping    cu  ft  per hr    of Pipe Iron Pipe Size  IPS      inches   in Feet   1 2 3 4 1 1 1 4 1 1 2  10 132 278 520 1050 1600  20 92 190 350 730 1100  30 73 152 285 590 890  40 63 130 245 500 760  50 56 115 215 440 670  60 50 105 195 400 610  70 46 96 180 370 560  80 43 90 170 350 530  90 40 84 160 320 490  100 38 79 150 305 460                         At pressure drop of 0 3 in  water  specific gravity   0 60     ELECTRICAL WIRING  DANGER  Before wiring  always turn off electric power supply   otherwise  shock or death can result   1  Power Supply  A separately fused circuit is recommended  Use a standard  15 amp  fuse or breaker and 14 gage conductors in BX  cable or conduit   Provide disconnect means and overload protection as  required  See boiler wiring diagram  Figure 4    Boiler must be electrically grounded in accordance with the  requirements of the authority having jurisdiction  or  in the  absence of such requirements  with the National Electrical  Code  ANSI NFPA 70 latest edition   2  Power Connection  Connect hot and neutral to L1 and L2 terminal of the  boiler control  See figure 4   Connect ground wire to ground  screw inside boiler control   3  Th
34. ns must slope upwards not less than 1 4 inch  per foot of run  Horizontal portions of the venting system  must be supported to prevent sagging by securing each joint  with metal screws and by providing hanger spaced no  greater than 5 feet apart     Sentry 5    D  Vent or breeching into chimney should not be inserted past    insi i i SENTRY PACKAGED  P  BOILERS  the inside wall of the chimney liner  MGOELS S 34 TO S 150    E  All venting means should be inspected frequently  See Care  and Maintenance and separate User s Information Manual  VENT DAMPER    VENT DAMPER INSTALLATION  The vent damper referred to in the following instructions is  the Slant Fin Corporation vent damper     This device is design certified by A G A  for use ONLY on spe    cific Slant Fin Corp  gas boiler models  These boilers must also   be equipped with a plate which states that the boiler may be   used with a Slant Fin Corp  automatic vent damper device and BOILER   indicates the proper vent damper model number  TEMPERATURE  CONTROL   A  INSTALLATION INSTRUCTIONS BEFORE YOU START TO   INSTALL   1  Read this installation manual  the  DANGER  plate  attached to the top of the boiler  the  WARNING  on the  wiring diagrams  vent damper carton and operator cover    2  Perform pre installation inspection as required by ANSI  specification Z21 66   See Vent Damper Instructions     3  Select a proper  convenient location for vent damper  Vent  damper may be installed vertical or horizontal on all mod   els  
35. one or   more sides below the roof line  exterior chimney   ONE of   the following options apply    1  Chimney must be re lined with a metallic liner  When this  is done  the chimney will be considered NOT exposed to  the outdoors and the requirements of the National Fuel  Gas Code for NON exposed chimneys and or local codes  will apply    2  If an exposed tile lined chimney is to be used WITHOUT  a metallic liner  the boiler must first meet the require   ments of the National Fuel Gas Code    B  If an existing boiler is removed from a common venting  system  the common venting system may be too large  for proper venting of the remaining appliances connected to  the common vent  Follow the test procedure shown in  Appendix  A  of this manual to insure proper operation of  venting system and appliances    C  Inspect for proper and tight construction  Any restrictions or  obstructions must be removed  An existing chimney may  require cleaning    D  Chimney or vent must extend at least 3 feet above any  ridge within 10 feet of the chimney        Sentry    MINIMUM CLEARANCES FROM COMBUSTIBLE  CONSTRUCTIONS  A  Minimum boiler clearances shall be as follows     SENTRY SERIES  MINIMUM CLEARANCE FOR COMBUSTIBLE CONSTRUC   TION  MINIMUM ALCOVE AND CLOSET CLEARANCE     S 34 through  S 150    Front e   Rear e   Left Side e   Right Side 12   Top  above boiler  12   Flue Connector e     B  Provide accessibility clearance of 24  on sides requiring  servicing and 18  on sides used for passa
36. onomy feature is activated  using the ECONOMY dial   See  How Thermal Targeting Works   on page 4 for more information         ECONOMY  TARGET When the Economy feature is active   the Fuel Smart HydroStat continually sets target temperatures  below the high limit setting to maximize fuel efficiency  When the         TEST SETTINGS Button    To Test Low Water Cut Off  Press and hold the Test Settings but   ton for 5 seconds  The display will read LCO     LWCOTEST                  red Low Water light should illuminate and the burner circuit   B1 and B2  should de energize  NOTE  The control must be  installed with a Hydrolevel Electro Well for low water cut off func   tionality  see page 2 for more details      To View Current Settings  Press and release the Test Settings Button  in short intervals to sequentially display the following settings     HIGH LIMIT SETTING         LOW LIMIT SETTING LL  ECONOMY                CUBBENTTARGET TENERETUR 000  PRE PURGE SETTING PUR    The display will return to boiler temperature  default  if  Test Settings Button in not pressed for 5 seconds     16 Sentry    SEQUENCE OF OPERATION FOR SENTRY BOILERS       THERMOSTAT CALLS FOR HEAT                         CIRCULATOR ENERGIZED HIGH LIMIT CONTACTS CLOSED  NO  LOW WATER CUT OFF NO FURTHER              CONTACTS CLOSED                             5    VENT DAMPER RELAY ENERGIZED   VENT DAMPER MOTOR OPENS VENT DAMPER   END SWITCH CLOSES                   IGNITION CONTROL ENERGIZED                SP
37. own  The boiler water will con   tinue to circulate and heat the house as  long as the thermostat call continues   The LED will stay lit until the boiler tem   perature drops to the differential set point   see Target Temp Differential on page 4   at which point the boiler will be allowed to  fire again  NOTE  This LED illuminates      TARGET SETTINGS    Gp ACTIVE    TARGET       10   see High Limit Differential on page     TEMP   LWCO   ECONOMY     regularly during normal boiler operation           4   The Fuel Smart HydroStat prevents          burner operation while this LED is on        LWOO ACTIVE Indicates that the low water cut off  LWCO   function of the Fuel Smart HydroStat is active  When the  control is installed with a Hydrolevel Electro Well  this LED will be  on at all times when the control is powered    IMPORTANT  If the control is installed with a well other than the  Electro Well  this LED will not illuminate indicating that the control  is not providing low water cut off functionality      WCOLOW WATER luminates if the boiler is in a low water  condition  The Fuel Smart HydroStat will prevent burner operation  during this condition  IMPORTANT  The system must be checked  by a qualified heating professional prior to resuming operation   WARNING  DO NOT ADD WATER UNTIL THE BOILER   HAS FULLY COOLED     G  ECONOMY ACTIVE Indicates that the Thermal Targeting  function is active and the Fuel Smart HydroStat will reduce boiler  temperature to conserve fuel  The Ec
38. rculators to C1 and C2 of the control        Note  For single heating zone with external indirect water  heaters  see figure 9     Sentry    WIRING DIAGRAM FOR SENTRY S   amp  SENTINEL SE  BOILERS    HYDROLEVEL HYDROSTAT CONTROL  MODEL 3200    24    THERMOSTAT    VENT DAMPER  HARNESS    Li L2   2       BJ B2    HONEYWELL IGNITION MODULE    NEUTRAL  CIRCULATOR    BLOCKED VENT ROLL OUT  SAFETY SWITCH 7 SWITCH    ELECTRIC  IGNITION    WIRE LEGEND       FACTORY WIRED         FIELD WIRED  FIELD SUPPLIED    PILOT GAS PIPE    PROVIDE DISCONNECT MEANS AND    OVERLOAD PROTECTION AS REQUIRED  IF ANY OF THE ORIGINAL WIRE AS SUPPLIED  WITH THE APPLIANCE MUST BE REPLACED   IT MUST BE REPLACED WITH TYP 105 OR  ITS EQUIVALENT     CAUTION     LABEL ALL WIRE PRIOR TO DISCONNCTION WHEN SERVICING CONTROLS     WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION    VERIFY PROPER OPERATION AFTER SERVICING      46 1014 000       Figure 4     Sentry        ZONE 3 ZONE 2   ZONE 1  f 2 THERMOSTAT 2x THERMOSTAT   THERMOSTAT    R845A   RB45A   R845A  RELAY ZONE 3 i RELAY ZONE 2   RELAY ZONE 1    HYDROLEVEL HYDROSTAT  CONTROL MODEL 3200             POWER SUPPLY  PROVIDE DISCONNECT  MEANS AND OVERLOAD PROTECTION  AS REQUIRED     L1 L2   2      81821112    EE E       Figure 5  Multizoning of Sentry boilers pump zoning system using R845A relay      MULTIZONING WITH INDIRECT WATER HEATER   PUMP ZONING SYSTEM USING R882A B RELAY    DHW TANK ZONE 2 ZONE 1  AQUASTAT THERMOSTAT THERMOSTAT    DISCONNECT  W  
39. re not in operation       a  Seal any unused openings in the common venting system     b  Visually inspect the venting system for proper size and hor   izontal pitch and determine there is no blockage or restric   tion  leakage  corrosion and other deficiencies which could  cause an unsafe condition     c  Insofar as is practical  close all building doors and windows  and all doors between the space in which the appliances  remaining connected to the common venting system are  located and other spaces of the building  Turn on clothes  dryer and any appliance not connected to the common vent   ing system  Turn on any exhaust fans  such as range hoods  and bathroom exhausts  so they will operate at maximum  speed  DO NOT operate a summer exhaust fan  Close fire   place dampers     d  Place in operation the appliance being inspected  Follow the  lighting instructions  Adjust thermostat so appliance will  operate continuously      e  Test for spillage at the draft hood relief opening after 5 min      f     utes of main burner operation  Use the flame of a match or  candle  or smoke from a cigarette  cigar or pipe    After it has been determined that each appliance remaining  connected to the common venting system properly vents  when tested as outlined above  return doors  windows   exhaust fans  fireplace dampers and any other gas burning  appliance to their previous conditions of use      g  Any improper operation of the common venting system    should be corrected so the insta
40. rinted in U S A  414 PUBLICATION S 41 Rev C  Part No  46 0602    Sentry    Dimensions  Install manual gas main  MODEL      shutoff valve 5 ft  above  floor  when required by    n local code  Install      sediment trap and connect     with ground joint union       Dotted piping by installing             i p Vent Damper                                                        H EP         Integral Han nd  i contractor   FPT Supply Draft Diverter ontroi a  E  Supply  by others             behind draft diverter  Ignition E  1 Control E  15  Blocked Vent I         Satety Switch TIT  a integral Circulator  H  Draft Diverter 117   Circ  Flange 1  124     1222    j  Rolout Safet 1 2           Tapping pese 4           Safety  Switch  behind  front panel  Combination x      Sediment Tra   161  Gas Valve     159   __ requie       gas tapping 1         19     Left End View Front View Right End View  Dimensions 3 4  to air eliminating  MODELS S 60 to S 150 system  by others      j c B       to alternate E Vent Damper    Y _ ne air eliminating High Limit  G hd system  by others  Control  i Install manual gas main  x shutoff valve 5     above  Supply floor  when required by        others  Ignition local code  Instail  Contro  sediment trap and connect  with ground joint union   Pressure Temp  Dotted ee te eset   Gauge The   Circulator       11    Circ  Flange 1 Blocked Vent  44  Drain 1    n 1 Safety Switch  Rollout Safety 1     Heturn Tapping  Switch  behind HAT   front panel  Combination me
41. screw on top           PILOT FLAME Y  3 8  TO 1 2     4    FLAME SENSOR                B  Main Burners   1  Fire the boiler continuously for at least 15 minutes  to reach  burner operating temperature    2  Observe the flames  all burners  The base of all flame jets  should be blue  The tips should be blue shading to orange   NOTE  Dust  disturbed by any movement  will cause bright  orange flames  Wait for dust to settle    3  For one burner  close the air shutter until some of its flame   jet tips turn yellow white  indicating insufficient primary air   Then open shutter until whitish tips disappear completely   Set all burner shutters to the same opening  Observe to  make sure that no yellow white tips appear over any portion  of the flame  Small yellow tips at the pilot location are per   mitted   NOTE  This adjustment method gives MINIMUM primary air  setting for safe combustion  DO NOT attempt to make this  adjustment unless burners are at operating temperature   Adjustment should be made with burner access panel in  final operating position  Use of a mirror may be helpful to  observe flames  Note that burner ports are on top of main  burner tube     C  Main Burner Ignition Checkout and Pilot Adjustment    1  The pilot flame must not smother or snuff out when test   ed as follows   a  Main burner ignition from cold start repeat   b  Continued operation of main burner   c  Main burner ignition with appliance at maximum oper    ating temperature after prolonged operation  
42. see figures 1 and 2     4  Carefully unpack the unit  DO NOT FORCE IT OPEN OR  CLOSED  Forcing the damper may damage the gear  train and void the warranty    B  1  This device must be installed after the boiler draft hood   between the draft hood outlet and the connector to the out   door chimney or vent  as close to the draft hood as practi   cable  and without modification of the draft hood or the vent  damper   See figures 1  2 and 3     2  The inlet size of the vent damper must be the same nomi   nal trade size as the outlet of the draft hood    3  This device must be located in a venting system or section  of a venting system so that it serves only the single appli  5 34 TO 5 150  ance for which it is installed   See figure 3     4  Clearances of not less than 6 inches  152MM  must be  maintained from combustible materials  with provisions for       Figure 1  Vertical Installation of Vent Damper on Sentry  S   Boilers    Service access    Install operator in any position as shown above  DO NOT install the operator      AFTER INSTALLATION    1  Operate system through two complete cycles to check for  opening and closing in proper sequence  and proper burn   er operation  DAMPER MUST BE IN OPEN POSITION  WHEN BOILER MAIN BURNERS ARE OPERATING    2  Perform installation checks as required by ANSI specifica   tion Z21 66   See Vent Damper Instructions     3  Checkthe troubleshooting section if problems arise with the  installation     CAUTION  DO NOT USE ONE VENT DAMPER TO C
43. ting Water Systems                17 tion  the installation must conform to American Society of  Initial Start  Mechanical Engineers Safety Code for Controls and Safety  Safety Information and Lighting Instruction         20 Devices for Automatically Fired Boilers  No  CSD 1  If there  B Adi Checking Gas   is any conflict in the above requirements  then the more  urner Adjustment  Checking Gas Input         20 21 stringent requirement will apply   Care and Maintenance  General Maintenance                          21  Water Level                                       22 This manual must be left with owner and should be hung  Annual Inspection and Cleaning                  22 on or adjacent to the boiler for reference   Safety Check for Control Systems                22  Protection from Freezing Water Treatment          22                 Area     22 WARNING  PEPINI ATSA aM EL         This boiler  gas piping and accessories must be installed   Troubleshooting Guide                            23 connected  serviced and repaired by a trained  experienced  Piping a Heating Cooling System  Ll  24 service technician  familiar with all precautions required for  Replacement                                         24 gas fired equipment and licensed otherwise qualified  in                       s id pupu E         25 Compliance withthe authority naving jurisdiction           Heating Contractor Boiler Model Number    Address Boiler Serial Number    Phone Number Installation Date       P
44. un of smokepipe   4  Inadequate chimney or venting system     REMEDY   Increase gas supply to pilot    Clean ports or orifices    Realign burners or manifold    Adjust primary air shutters    Check and reduce to input shown on rating plate   Check air supply and venting system     o gre ou    REMEDY  1  Locate leaks and repair   2  Close service supply valve   shut down appliance and  notify utility   3  Check and repair chimney   4  Clean flueways and adjust burners as described in the  installation instructions   Check manufacturer s recommendations   Check air supply and venting system   Adjust gas input to that shown on boiler rating plate               REMEDY   1  Increase firing rate to that shown on rating plate    2  Set low limit controls to maintain a higher water temper   ature  If boiler is not equipped with low limit replace  with one which has a combination low limit high limit  aquastat    3  Relocate boiler or insulate breeching    4  Check chimney and venting recommendations        24    PIPING A HEATING   COOLING SYSTEM TO A WATER  BOILER AND CHILLER    The chiller must be piped in parallel with the boiler  Figure below  illustrates a method of piping a heating cooling system to a  water boiler and a chiller  Hand valves  shown  or automatic  valves must be installed to prevent circulation of chilled water in  the boiler or hot water in the chiller     The air control system and pressure control system must oper   ate with chiller only  or the boiler only  b
45. ve system with indirect water heater  DHW Priority  using R882A B relay     10 Sentry    SINGLE ZONE WITH INDIRECT WATER HEATER   DHW PRIORITY  USING R882A B RELAY    DHW TANK   AQUASTAT  HYDROLEVEL HYDROSTAT p  Y ro DISCONNECT  CONTROL MODEL 3200 SWITCH    e       11    9   R882A B gilla L2  ECONOMY 120V 24V 120V 60HZ    TRANSFORMER    A       DHW TANK  CIRCULATOR  1112  2  1 B182 I1 12 N                                                                               P2 2 2 4                     GREEN    ped    120V 60Hz   SPACE HEATING  WHITE CIRCULATOR    NEUTRAL T        POWER SUPPLY  PROVIDE DISCONNECT  JUNCT ION MEANS AND OVERLOAD PROTECTION  BOX AS REQUIRED        Figure 9  Single zone with indirect water heater  DHW Priority  using R882A B relay     11    Sentry    BOILERS EQUIPPED WITH HYDROSTAT CONTROL    SETTING THE CONTROL    NOTE  Settings can be checked  using the TEST SETTINGS Button     SETTING THE HIGH LIMIT   The high limit is factory set at  190 F  To adjust  turn the HI  TEMP Dial   until the desired  setting is displayed   Setting  range  100   220  F     SETTING THE LOW LIMIT   The low limit is designed to main   tain temperature in  boilers  equipped with tankless coils used  for domestic hot water  The low  limit is factory set to OFF  Prior to  adjusting  remove the jumper  not  equipped on all units    Then  turn the LO TEMP Dial  9  clock   wise until the desired temperature is displayed  For  proper operation  the low temperature limit setting  shoul
46. wall openings    Provisions for combustion and ventilation air must be made in  accordance with section    Air for Combustion and Ventilation   of  the National Fuel Gas Code  ANSI Z223 1 latest edition  or  applicable provisions of the local building codes  The following  recommendation applies to buildings of energy saving con   struction  fully caulked and weather stripped    Provide one GRILLED opening near the floor and one near the  ceiling on an outside wall near the boiler  or duct from such  openings to the boiler   EACH opening to be a minimum of one  square inch per 2000 Btuh input to ALL APPLIANCES in the  area  For a total appliance input of 200 000 Btuh  each open   ing will be 100 square inches  A grilled opening 10 X10  has  100 square inches of area  If fly screen must be used over  openings  double the area and inspect and clean the screen  frequently  Openings must never be reduced or closed  If doors  or windows are used for air supply  they must be locked open   Protect against closure of openings by snow and debris   Inspect frequently  No mechanical draft exhaust or supply fans  are to be used in or near the boiler area  The flow of combus   tion and ventilating air to the boiler must not be obstructed     WATER PIPING   A  Packaged water boilers are equipped with a water circu   lating pump  mounted to return the water into the boiler   For some installations  the pump should be on  the supply main  See figure 10    B  For zoning and piping arrangement
47. y part has been underwa    ter  Immediately call a qualified service technician to   inspect the appliance and to replace any part of the control   System and any gas control which has been underwater     Operating Instructions  STOP  Read the safety information above   Set the thermostat to lowest setting   Turn off all electric power to the appliance   This appliance is equipped with an ignition device which  automatically lights the pilot  DO NOT try to light the pilot  by hand   Remove control access panel     Turn gas control knob clockwise    Y till knob stops then  continue to  OFF   DO NOT force    Wait five  5  minutes  longer for propane  to clear out any  gas  then smell for gas  including near the floor  If you then  smell gas  STOP  Follow  B  in the safety information  above on this page  If you don t smell gas  go to next step     Turn gas control knob counterclockwise      to          Replace control access panel    Turn on all electric power to the appliance    Set thermostat to desired setting    If the appliance will not operate  follow the instructions  To  Turn Off Gas To Appliance  and call your service techni   cian or gas supplier     To Turn Off Gas To Appliance    Set the thermostat to lowest setting       Turn off all electric power to the appliance if service is to    be performed       Remove control access panel     Turn gas control knob clockwise CN till knob stops     then continue to  OFF   DO NOT force       Replace control access panel      
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
HARMAN KARDON® SOUNDSTICKS® WIRELESS  Symantec Intruder Alert 3.6 (10007266)  Samsung GT-E2350B Benutzerhandbuch  DrillManager - Horsch Maschinen GmbH    PRO-VOL Stereo Volume pedal - Choose-AV  Detachable Jaw True  Manuel d`utilisation Thermomètre hygromètre Modèle RH210  téléchargez - Amarine Club  Grabación Reproducción    Copyright © All rights reserved. 
   Failed to retrieve file