Home
        Trane ZN510 Controller User's Manual
         Contents
1.                                                                                                                                                         1PB1 3 2 3     LEGEND  JA DEVICE  ck   e DESCRIPTION  EQUIPMENT DESIGNATION  GROUND  1PB1 POWER BLOCK    460 VOLT   1K1 BLOWER CONTACTOR  1K2  SAH ylle SA    l 1K2 COMPRESSOR CONTACTOR 1  a te N m i x 8 i 1K3 COMPRESSOR CONTACTOR 2  na T2 ika R i a   I 1K8 RELAY REVERSING VALVE  4 JAH mily AA z     1T1 2 CONTROL POWER TRANSFORMER    aii l 281 COMPRESSOR MOTOR 1    24 VAG i 2B2 COMPRESSOR MOTOR 2  lo     MERG 2B1S1 HIGH PRESSURE CONTROL 1  3H a  2B1S5 LOW PRESSURE CONTROL 1  2B2S1 HIGH PRESSURE CONTROL 2  Ce kp Ew ge tL 2B2S5 LOW PRESSURE CONTROL 2  ba SE 3B1 FAN MOTOR  n     H 1U1 COMFORTLINK 10       mU i   se  2e  te 4L1 2 REVERSING VALVE  i 1 ym MM BLU i 4 ARTI LEAVING WIR TEMP SENSOR  CKT 1  1   24 VAC     4RT2 DISCHARGE AIR TEMP SENSOR     208 230   455 CONDENSATE OVERFLOW SWITCH  1 1 456 FREEZESTAT CIRCUIT 2  H IKB BB aoa AT ogy TBS 1    ele MU o   1TB1 TERMINAL BOARD  i y 42 w i 1TB5 TERMINAL BOARD  202A 205A cl 40   1TB5   2  1TB5   4    ra 88  IO  len ee da  17A   YEL  YY  BLU   15A  L 24 VAC J  1K3  2B2S1 28255  1181 17   17L oqe 68A B9A 66A  1K2  2B1S1 2B1S5  1181 15   17G oe 37A 54A BA  17J H 1B A   36A  1181 15     o jo  Yr   OPTIONAL   17H 1K1 40A na a  Gei FIELD SUPPLIED  ie hA 2 POSITION OUTSIDE  19 es  AIR DAMPER  1781 13    ue    a 4 RR  OND 2w d 1 2 3 4 5 67  ah  ii a a l   EELER  FREEZESTAT   BINARY OUTPUTS
2.     WSHP IOP 2  S TRANE   May 1998    Installation  Operation   and Programming    Tracer    ZN510 Controller          Literature  History    The Trane Company has a policy of continuous product improvement and it reserves the right to change    specifications and design without notice     Installation  Operation       WSHP IOP 2  and Programming       Library    Service Literature       Product Section Unitary       Product    Water Source Heat Pumps       Model 000       Literature Type Installation  O    and Programming    peration              Sequence 1  Date April 1998  File No  SL UN 000 WSHP IOP 2 0498       Supersedes New          Related Literature    e CNT IOP 1 ZN510 1 Controller   Installation  Operation  and Pro   graming    e WSHP PD 1 Water Source Heat    Pump Controller Product Data  Sheet       1998  American Standard Company       e WMCA PD 1 ZN510 Loop Con   troller Product Data sheet      WSHP IOP 3 ZN510 Water   Source Heat Pump Controller  Installation  Operation  and Pro   gramming Guide    e WMCA IOP 1 ZN510 Controller  Installation  Operation  and Pro   gramming Guide    Table of Contents                                                                   Start up Procedure 4  Power up Seguence 5  Unit Identification Tag 6  Unit Operation 7  General Information 7  Communication 7  Power 8  Binary Outputs 8  Analog Outputs 9  Binary Inputs 9  Analog Inputs 12  Zone Sensors 15  Heating or Cooling Control 18  Mode Operation  Single or Dual Compressor 19  
3.    AVERTISSEMENT    VOLTAGE HASARDEUX     DECONNECTEZ TOUTES LES SOURCES  ELECTRIQUES INCLUANT LES   DISJONCTEURS SITUES A DISTANCE  AVANT D EFFECTUER L ENTRETIEN     FAUTE DE DECONNECTER LA SOURCE  ELECTRIQUE AVANT D EFFECTUER  UENTRETIEN PEUT ENTRAINER DES  BLESSURES CORPORELLES SEVERES  OU LA MORT     IMPORTANT    USE COPPER CONDUCTORS ONLY TO PREVENT EGUIPMENT DAMAGE           cw     4A   5D      u al a                UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT ANY OTHER WIRING                                            LEGEND  DEVICE  hal ny oper DESIGNATION DESCRIPTION  i 460 VOLT    1    x ol   1K1 BLOWER RELAY  a E   1K2 COMPRESSOR CONTACTOR    m i    YEL BLU    i 24 VAC i 1m CONTROL POWER TRANSFORMER  H   2B1 COMPRESSOR MOTOR 1  INSET B  2B1S1 HIGH PRESSURE CONTROL 1                                                                         CONDENSATE    OPTIONAL    s    OVERFLOW    OCCUPANCY    ONNECTIONS                                                                            2B1S5 LOW PRESSURE CONTROL 1   1U1 COMFORTLINK 10   3B1 FAN MOTOR   3B1C1 FAN RUN CAPACITOR   4L1 REVERSING VALVE   4RT1 LEAVING WTR TEMP SENSOR  4RT2 DISCHARGE AIR TEMP SENSOR  455 CONDENSATE FLOAT SWITCH  1TB1 TERMINAL BOARD    OPTIONAL   FIELD SUPPLIED  2 POSITION OUTSIDE  AIR DAMPER    24 VAC    1 17    mA 1781 18                                                                                          a nDagganoa  BINARY OUTPUTS      P1   12 32 3      z m L      a   na PIsts 4RT2  2      d  a
4.    e Single fan speed        N TWISTED PAIR OF WIRE USED    IN INSTALLATI           are provided for direct con   nection of Rover to the ZN510  Board or provided as spare ter   minals        Two terminals  TB2 3  TB2 4   are connected to the field  terminal strip  1TB1 14   1TB1 16  for connection to the  communication link  daisy  chain         e Up to two compressors    e Reversing valve       2 position outdoor air damper   or generic binary output    Peer to peer communication across  controllers is possible even when a  building automation system is not  present  ZN510 is also adaptable as  a standalone system     COMMS    TLINKIN WATER SOURCE       Two terminals  TB2 5  TB2 6   are connected to the field  terminal strip  1TB1 5  1TB1 6   which should be connected to  the zone sensor communication  jack  This provides direct  connect of Rover to the commu   nication link without having to  connect directly to the ZN510  board or provided as spare ter   minals    e The field terminal strip 1TB1  provides screw terminations for  all field connections        Space  Communication  Connection       20 pole low voltage  terminal strip screw  connections for    field hook up Link    Figure 3  Communication Wiring    7    Communication Zone    Sensor    Power   The ZN510 controller is powered by 24  VAC  A total of two 1 4 inch guick   connect terminals are provided for 24  VAC connection to the board  See    Figure 4 for ZN510 power requirement     Note  Power for field instal
5.   CIRCUIT 2 458  74A 2 l  2  170 a   MA 4RT2     lt     wt EP E ya  CONDENSATE 2      DISCHARGE AR     OVERFLOW E 33a    5 WEN SENSOR    gr ART1  opTionaL   OCCUPANCY m J  LY  CONNECTIONS      E COMM LINK ZONE SENSOR E h   LEAVING WATER  T   3 kM 2    ptt ANSOR  es Bs dd   All A I CIRCUIT 1  is Qs afl al afl al ip i id al PS     ZONE GND SET FAN GNO    FAN MODE 24A     4  SET PONT 23A     mm ZONE SENSOR  COMMON 22A    1 2 CONNECTIONS  ZONE TEWP ZA   m1  COMM 26A  Soma COMMUNICATIONS  COMM 25A    m s ZONE SENSOR  COMM 18A     116 COMMUNICATIONS  COMM 19A    1m  LINK  NOTES    lt 1  TRANSFORMER  1T1  SHOWN IS WIRED FOR 230V  RED LEAD IS FOR 208V  SEE INSET  A  FOR 460V TRANSFORMER  5  UNLESS OTHERWISE NOTED  ALL SWITCHES ARE SHOWN AT 25  C  77  F   AT ATMOSPHERIC  PRESSURE  AT 50  RELATIVE HUMIDITY  WITH ALL UTILITIES TURNED OFF  AND AFTER A   lt _2  CONDENSATE OVERFLOW SWITCH  4S5  IS OPTIONAL  NORMAL SHUTDOWN HAS OCCURRED   6  DASHED LINES INDICATE RECONMENDED FIELD WRING BY OTHERS  DASHED LINE ENCLOSURES   lt C4   REVERSING VALVE  4L1 4L2   TRANSFORMER  172   REVERSING VALVE RELAY  1KB   AND OR DASHED DEVICE OUTLINES INDICATE COMPONENTS PROVIDED BY THE FIELD  PHANTOM  AND TERMINAL STRIP  1TB5  ARE STANDARD WTH HEAT PUMP ONLY  UNE ENCLOSURES INDICATE ALTERNATE CIRCUITRY OR AVAILABLE SALES OPTIONS  SOLID LINES    INDICATE WIRING BY TRANE CO     Specifications    Board Dimensions                Height  4     102mm   Width  5 1 2     140 mm   Depth  2 1 4   57mm              Ope
6.   switches automatically reset  The  high or low pressure cutout  diagnostic may need to be manually  reset to clear the diagnostic and  enable compressor operation for the  fault circuit     Unit Operation    24 VAC        Figure 7  High and low pressure switch    Note    The ZN510 controller includes an automatic diag   nostic reset function that allows the controller to  automatically recover after a high or low pres   sure cutout diagnostic  After 30 minutes the con   troller will reset the diagnostics  Most  diagnostics occur due to intermittent water tem   perature or flow problem  The    smart reset    may  eliminate many service calls        Analog Inputs   The ZN510 controller has five  available analog inputs  Al   These  inputs are factory configured for the  following functions     e Zone   Space temperature        e Set   Local setpoint           Fan   Fan mode input  Discharge Air      Sensor     Al 1   Leaving water tem     perature  Circuit 1      e Al 2   Discharge air tem     perature  Leaving Water    See Figure 8 for analog inputs  Sensor  Circuit     on  EF ER F  Sm om om cm Figure 8  Analog inputs   NE 5  be HE   mo nc E    Space Temperature   ZN510 controls the space  temperature according to the active  space temperature  the active  heating cooling setpoint  and the  space temperature control  algorithm  The ZN510 controller  receives the space temperature  from either a wired zone sensor or  as a communicated value  When  neither a zone sensor nor  c
7.  are  calculated based on the hardwired  setpoint values  the configured  setpoints  and the active mode of  the controller     Setpoint Operation   The controller has three methods of  heating and cooling setpoints  operation  See Table 5 for the  methods of setpoint operation        Method    Situation used       Zone Sensor   with an adjustable hardwired  setpoint     A hardwired  adjustable setpoint is connected to the controller  Local setpoints are  enabled in the unit configuration  No communicated setpoint is present        Communicated source    A setpoint is communicated to the unit controller  typically from a building automation  system or a peer controller   If both a hardwired setpoint and a communicated setpoint  exist  the controller uses the communicated value  The configuration feature for enabling  or disabling the local setpoint does not affect the setpoint handling when communicated  setpoints are used  The communicated setpoint always takes priority over the hardwired  setpoint  even when the local setpoint is enabled        Stored default setpoints          The controller uses the locally stored default heating and cooling setpoints when neither  a local hardwired setpoint or communicated setpoint is present  When a building  automation system is present  the controller uses the default setpoints when no setpoint  is communicated to the controller and no hardwired setpoint exists  The controller uses  stored default setpoints when only a local setpoint 
8.  compressors off prior to changing the  reversing valve state   7  Heat 1 On Off On Off Closed  8  Heat 2 On Off On On Closed  9  Outdoor air damper On Off Off Off Open  10  Exit    After the outdoor air damper step  the test  sequence performs the exit step  This  initiates a reset and attempts to return the  controller to normal operation           Testing the Heat Pump  Configurations   The outputs are not subject to  minimum times during the test  sequence  However  the test  sequence only permits one step per  second which limits output time     All outputs are exercised regardless  what timer they are or are not  configured for  For example  single  compressor heat pumps function    the same as two compressor units   For single compressor units  the  cool 2 and heat 2 steps control the  appropriate binary outputs  but do  not affect unit operation     Reversing valve and damper    outputs cycle independent of  configuration     23    Pump Operation for   Systems with ZN510   Loop Controller   During Unoccupied  the pumps will  be OFF but should be energized to  test compressor operation  The user  must override the pumps either at  the ZN510 Loop Controller or by  pushing the ON button of the zone  sensor  This will send the units to an  occupied bypass  which will turn the  pumps on prior to operating  manual output test        Ouestionable Unit  Operation    Troubleshooting    Table 13  Fan output does not energize       Probable Cause    Explanation       Random star
9.  tag is factory  mounted and provided for easy  identification of an installed unit  It  contains model number  tagging   and location information  See  Figure 1     The top portion of the unit  identification tag remains  permanently affixed to the unit for  identity purposes  The bottom  portion of the tag provides pertinent  information that is removable to be  placed on building plans or in the  ZN510 IOP on page 33  This provides  identification history about the unit s  location for guick reference     These tags provide information  about unit location  unit serial  number  and NID  neuron  identification number   The NID is  similar to the serial number of the  unit but is specific to the  identification of the ZN510 Board   The location identification is a  customer defined  clear English  description  of the unit s physical  location  This is a 27 character  description of the location  For  example  if the location identification  for a unit is    Conference Room 101      the ZN510 and Rover  the Trane  Comm 5 service tool  will recognize  this clear English description so  maintenance can be performed on  the appropriate unit  If location  identification is not defined  it will  default to the unit serial number  This  provides some information so the  user has multiple references to the  unit  The blank location is provided  for field modification in case the unit  is moved from the initial location     Unit  identification  Tag    Unit Identification Tag    Mode
10.  vacant  In unoccupied  mode  the controller always uses the  default unoccupied heating and  cooling setpoints stored in the  controller  As the unit goes  unoccupied  the compressors ON  timers are ignored and the  compressors are disabled     When ZN510 controls the space to  unoccupied mode  the occupant  may have the ability to request  timed override through the Trane  zone sensor   s ON button  Based on  the controller or system setup  the    Single and Dual  Compressor  Operation    controller interprets the request and  initiates the occupied setpoint  operation  During a timed override   the controller applies the occupied  heating and cooling setpoint  but  reports the effective occupancy  mode as occupied bypass mode  In  the occupied bypass mode  a  building automation system can  detect whether the occupancy mode  was overrode     Morning Warm Up   The damper  field installed or for the  console product  remains closed  during morning warm up until the  space temperature is within two  degrees of the effective heating  setpoint  The 2 position outdoor air    19    damper normally is open during the  occupied mode when the controller  turns on the unit fan  The damper is  normally closed during     e occupied mode when the fan is  OFF       warm up cool down mode       occupied standby mode       unoccupied mode       certain diagnostic conditions     ZN510 keeps the 2 position outside  air damper closed on a transition  from unoccupied mode to occupied  mode as 
11. 2 VA 1 VAC RMS  typical  24 VAC RMS  typical   Binary Output 5  J1 6 12 VA 1 VAC RMS  typical  24 VAC RMS  typical   Binary Output 6  J1 7 12 VA 1 VAC RMS  typical  24 VAC RMS  typical                       Table 20  Analog Inputs                                              Description Terminals Function Range  Zone TB3 1 Zone temperature input 5 to 122 F   15 to 50 C   Ground TB3 2 Analog ground NA  Set TB3 3 Setpoint input 40 to 115 F  4 4 to 46 1 C   Fan TB3 4 Fan switch input OFF   4821 to 4919 Ohms   AUTO   2297 to 2342 Ohms  Ground TB3 6 Analog ground NA  Analog Input 1 J3 1 Leaving water  40 to 212 F   40 to 100 C   temperature  J3 2 Analog ground NA  Analog Input 2 J3 3 Discharge air temperature   40 to 212 F   40 to 100 C   J3 4 Analog ground NA       32       
12. Diagnostics section on  page 27        No power to the controller     If the controller does not have power  the unit fan does not operate  For the  ZN510 controller to operate normally  it must have an input voltage of 24 VAC   When the green LED is off continuously  the controller does not have sufficient  power or has failed        Unit configuration     The controller must be properly configured based on the actual installed end  devices and application        Manual output test     The controller includes a manual output test seguence that may be used to verify  output operation and associated output wiring  However  based on the current  step in the test seguence  the unit fan may not be on  Refer to the manual output  overrides on page 9        Unit wiring        The wiring between the controller outputs and the fan relays and contacts must  be present and correct for normal fan operation           24       Ouestionable Unit  Operation    Troubleshooting    Table 14  Compressor s  not running       Probable Cause    Explanation       Normal operation     The controller compressor s  turn on and off to meet the unit capacity  reguirements        Reguested mode off     The desired operating mode  such as off  heat and cool  can be communicated to  the controller  When off is communicated to the controller  the unit shuts off all  unit compressor s         Communicated disable     Numerous communicated requests may disable the compressor  including a  compressor enable in
13. Operation  Data Sharing 20  Configuration 21  Troubleshooting 22  Diagnostics 27  ZN510 Controller Replacement 28  Wiring Diagram 29  Hardware Specifications 31       Appendix 33       Start up  Procedure    Installation of New Units   1  Follow all instruction for  installation of water source  heat pumps as detailed in the  IOM  Installation Operation  Maintenance manual      2  Disconnect power or disable  the circuit breaker to unit     3  Run communication link wire to  field terminal strips 14 and 16    See wiring diagram in the  unit      4  Install zone sensor to low  voltage control terminals 1  through 6   See wiring diagram  in the unit and zone sensor  submittals      Zone Sensor Placement   Zone sensor location is an important  element of effective room control  and comfort     The best sensor location is typically  ona wall  remote from the HVAC unit   Readings at this location assure that  the desired setpoint is achieved  across the space  not just near the  unit itself  It may be necessary to  subdivide the zone with multiple  units to ensure adequate control  and comfort     5  Verify that water connections  have been made to unit  then  ensure that water is circulating  through the unit     6  Reapply power     7  Check for STATUS GREEN LED  operation to ensure power and  communication has been made    to the ZN510      Peel IDENTIFICATION TAG from unit  and place in the ZN510 IOP  on a  copy of Sheet 6 of this document  or  on building plans for future loc
14. Trane   s service tool  Rover  can reset  diagnostics in the ZN510 controller   For complete information about  Rover  refer to the Rover product  literature     Alarm Reset   Any device that can communicate  alarm reset information can reset  diagnostics in the ZN510 controller     ZN510 Controller Replacement  1  Disconnect power or disable  the circuit breaker to unit     2  Remove bad or questionable  ZN510 Controller     3  Install controller in the unit with  the heatsink placement at the  top of the control box   See  page 32      4  Connect the power to the ZN510  ONLY   TB1 1  amp  TB1 2 on ZN510     5  Connect Rover and properly  configure the controller  unless  a previously configured board  is purchased     6  Power down     7  Connect the remaining input  and output wiring to the  controller     8  Reapply power     9  Complete sequence 7 and 8  above in the installation section  of this manual     10  Refer to BAS manual for  instructions on how to install  the new ZN510 into BAS  system        MOTOR SPEED TAP       HIGH    MED    LOW       BLK          BLU    RED             FOR MED  amp  LOW SPEED  TIE BLACK  amp  PURPLE  ON 460V UNIT ONLY    TY UN    208 230V   Jje  OR _460V   30  LINE VOLTAGE    L       1m1          BLK  ED  ORN    Wiring Diagram    ZA WARNING    HAZARDOUS VOLTAGE     DISCONNECT ALL ELECTRIC POWER  INCLUDING REMOTE DISCONNECTS  BEFORE SERVICING     FAILURE TO DISCONNECT POWER    BEFORE SERVICING CAN CAUSE  SEVERE PERSONAL INJURY OR  DEATH  
15. air damper must be  present and correct for normal outdoor air damper operation           26       Diagnostics    Table 17  ZN510 controller diagnostics       Diagnostic Fan Other Outputs       Compressors  Off    Condensate overflow Off Damper  Closed       Compressor 1  Off  Low temp detect   Crt 1 Enabled Compressor 2  See note below   Damper  See note below        Compressor 1  See note below   Low temp detect   Crt 1 Enabled Compressor 2  Off  Damper  See note below        Compressor 1  Off  Low temp detect   Crt 1 and 2 Off Compressor 2  Off  Damper  Closed       Compressor 1  Off  High low press cutout   Crt 1 Enabled Compressor 2  See note below   Damper  See note below        Compressor 1  See note below   High low press cutout   Crt 2 Enabled Compressor 2  Off  Damper  See note below        Compressor 1  Off  High low press cutout   Crt1and2  Off Compressor 2  Off  Damper  Closed       Compressor s   Off          i    Space temperature failure Off Damper  Closed  Compressor 1  Off  Leaving water temp failure Enabled Compressor 2986 Neto Hel ow  Damper  See note below   Discharge air temp failure  Enabled Compressors  Nevaction    Damper  No Action       Maintenance required Compressor s   No action              example  Filter Status  pnebled Damper  No Action      Compressor s   Enabled     Local setpoint failure Enabled Damper  Enabled  Local fan mode failure  Enabled Gompressor s   Enabled  Damper  Enabled  Invalid unit configuration Disabled Compresseris   Disab
16. ation  use  The actual room location on the  tag may be hand written     The following are typical areas  where the zone sensor should not  be mounted        Near drafts or    dead spots      e g   behind doors or corners   e Near hot or cold air ducts       Near radiant heat  e g   heat  emitted from appliances or the  sun     e Near concealed pipes or  chimneys      On outside walls or other non   conditioned surfaces       In air flows from adjacent zones  or other units    Power Up  Seguence    Power Up Seguence   When 24 vAc power initially is  applied to the ZN510 controller  the  following seguence occurs     1  All outputs are controlled off     2  The controller reads all inputs    to determine their initial values     Note  Because the space tempera   ture can be hardwired to the con   troller or communicated  the  controller waits for several minutes  to check for the presence of a com   municated value     A random start time is hard  coded on every board and  cannot be disabled  The board  generates a random time delay  between 0 and 25 seconds   Once this time expires  the  power up control wait time  if  configured  will wait for 120  seconds  The power up control  wait allows ample time for a  communicated request to  arrive  If the power up control  wait time expires  and the  controller does not receive a  communicated occupancy  command  the unit assumes  stand alone operation     Normal operation begins     Unit Identification Tag   The unit identification
17. closed during the transition from unoccupied to  occupied  This is an attempt to bring the space under control as guickly as  possible        Requested mode off     The desired operating mode  such as off  heat and cool  can be communicated to  the controller  When off is communicated to the controller  the unit closes the  outside air damper        Manual output test     The controller includes a manual output test seguence that may be used to verify  output operation and associated output wiring  However  based on the current  step in the test seguence  the outdoor air damper may not be open  Refer to the  manual output overrides on page 9        Diagnostic present     A specific list o f diagnostics affects outdoor air damper operation  depending  whether the unit is configured as heat pump  For more information  see the  Diagnostics section on page 27        Unit configuration     The controller must be properly configured based on the actual installed end  devices and application  When the unit configuration does not match the actual  end device  the outdoor air damper may not work correctly        No power to the controller     If the controller does not have power  the compressor does not operate  For the  ZN510 controller to operate normally  a voltage input of 24 VAC must be applied   When the green LED is off continuously  the controller does not have sufficient  power or has failed        Unit wiring        The wiring between the controller outputs and the outdoor 
18. e  request and communicate this  request to the controller     e If the ZN510 controller does not  receive a hardwired or commu   nicated request for the fan  mode  the unit recognizes the  fan input as AUTO and the fan  operates according to the  default configuration     Fan Off Delay   When the heating output is  controlled off  the ZN510  automatically runs the fan ON for an  additional 30 seconds to give the fan  time to blow off any residual heat     Unit Operation    Leaving Water Temperature  ZN510 uses analog input 1  Al 1  as  the leaving water temperature input  for use with a thermistor  This input   Al 1  is automatically assigned as a  leaving water temperature input  As  explained in the binary input  section  the leaving water  temperature input protects the heat  exchanger  circuit 1  from low  temperatures  The second heat  exchanger  present in units with two  compressors is protected with a  binary low temperature detection  device  Based on the application of  the unit  circuit operation is  terminated when the leaving water  temperature falls below 35 F or   20 F  This is set when the unit is  ordered     The ZN510 controller compares the  measured leaving water  temperature to the leaving water  temperature low limit value to  determine a fault condition  When  the measured leaving water  temperature is less than the leaving  water temperature low limit  the  controller generates a Low Temp  Detect diagnostic  If the Leaving  Water Temp Sensor fails to 
19. e is for information only  to be read by the building  automation system or for  troubleshooting unit operation with  Rover     Once a valid discharge air  temperature signal has been  established by the thermistor or  communicated and the value is no  longer present  the controller  generates a discharge air  temperature failure diagnostic  This  will not disable unit operation  If the  sensor returns with a valid  temperature  the diagnostic  automatically clears    Zone Sensor  The ZN510 controller accepts the  following zone sensor inputs     e Space temperature mea   surement     e Local setpoint  internal or  external on the zone sensor         Fan switch   Optional     Timed override  ON and CANCEL    e Communication Jack     If both hardwired and  communicated space temperature    Zone Sensor    values exist  the controller ignores  the hardwired space temperature  input and uses the communicated  value     Internal and External Setpoint  Adjustment   Zone sensors with an internal or  external setpoint adjustment  provide the ZN510 controller with a  local setpoint  50 to 85 F or 10 to 29 4  C   The internal setpoint adjustment  is concealed under the zone sensor s  cover  To reveal the adjustable  setpoint wheel  remove the zone  sensor cover  The external setpoint    Table 5  Methods of setpoint operation      when present  is exposed on the  zone sensor s front cover     When the hardwired setpoint  adjustment is used to determine the  setpoints  all unit setpoints
20. exists  but the local setpoint is  disabled in the configuration of the controller  The controller always uses the stored  default  unoccupied  setpoints in unoccupied mode        15       Zone Sensor Features   Fan Switch  Optional    The zone sensor fan switch provides  the controller with an occupied  and  occupied standby  fan reguest signal  of OFF or AUTO  If the fan control  reguest is communicated to the  controller  the controller ignores the  hardwired fan switch input and uses  the communicated value  The zone  sensor fan switch signal can be  enabled or disabled through  configuration in the ZN510  controller     ON or CANCEL Buttons  Momentarily pressing the ON button    Table 6  Zone Sensor Options    Zone Sensor    during unoccupied mode places the  controller in occupied bypass mode  for 120 minutes  You can adjust the  number of minutes in the unit  controller configuration using  Trane s service tool  Rover  The  controller remains in occupied  standby mode until the override  timer expires or until the CANCEL  button is pressed     Communication Jack   Use the RJ 11 communication jack  as the connection point from Rover  to the communication link  when the  communication jack is wired to the  communication link at the    controller   By accessing the  communication jack via Rover   entrance to all controllers on the link  may be gained        Part Number   X13510628010  Description      Space temperature  0 2 C  resolution       Internal setpoint      Commu
21. f BOP 6 is configured as a generic binary output  the state of the output is not affected by the low temperature  detection diagnostic or by other diagnostics     Condensate Overflow   A condensate overflow switch  detects the condensate condition   The condensate overflow switch is a  normally closed device  This switch  is physically connected to the binary  input 2  BI 2   When the  condensation reaches the trip point   the binary input detects the  diagnostic condition  A condensate  overflow signal generates a  diagnostic which disables the fan   disables all compressors  and closes  the 2 position outdoor air damper   when present   The condensate  overflow diagnostic does not affect  the generic binary output  when  present      Note    The condensate overflow switch   located in the condensate pan  auto   matically resets when the conden   sation returns to normal levels   However  you must manually reset  the controller   s condensate over   flow diagnostic to clear the diagnos   tic and restart the unit  Refer to page  28 on how to reset a unit     Occupancy   ZN510 uses the occupancy binary  input for two occupancy related  functions  For standalone  controllers  any unit not receiving a  communicated occupancy request   typically from a building automation    10    system   the occupancy binary input  determines the unit   s occupancy  based on the hardwired signal   Typically  the signal is a dry set of  binary contacts which is either  connected to a switch or t
22. figuration    Configuration    Table 8  Heat pump heating or cooling operation     information  such as the default  analog inputs  the default binary  inputs  and the default binary output  configurations  See Table 7 for    default configurations for heat  pumps        Unit Type    Heat pump       Cooling Source    Compressor       Heating Source    Compressor  none for cooling only units        Compressors    1  2 for 2 compressor units        Binary Outputs    BOP 1  Fan on  normally open    BOP 2  Reversing valve  normally open     BOP 3  Not used   BOP 4  Compressor 1  normally open    BOP 5  Compressor 2  normally open      BOP 6  Outdoor Air Damper  normally open           Binary Inputs    Bl 1  Low temperature detection  circuit 2  normally closed            Bl 2  Condensate overflow  normally closed t  BI 3  Occupancy  normally open        Analog Inputs    Zone  Space temperature  0 0 F calibration   Set  Setpoint  0 0 F calibration    Fan  Fan mode   Al 1  Leaving water temperature   Al 2  Discharge air temperature       Fan    Fan operation  heating   Cycling  Fan operation  cooling   Cycling  Fan speed default  heating   On high  Fan speed default  cooling   On high  Fan switch  hardwired   Enabled       Setpoints    Unoccupied cooling setpoint  85 F  Occupied standby cooling  78 F  Occupied cooling setpoint  74 F  Occupied heating setpoint  71 F  Occupied standby heating  67 F  Unoccupied heating setpoint  60 F  Cooling setpoint high limit  115 F  Cooling setpoi
23. imeclock  contacts     When a hardwired occupancy signal  is open  the unit switches to  occupied mode  if the occupancy  input is configured as normally  open   When a hardwired  occupancy signal is closed  the  controller switches to Unoccupied  mode     In Occupied mode  the controller  operates according to the occupied  setpoints  In Occupied Standby  Mode  the unit controller operates  according to the Occupied Standby  setpoints  When the controller  receives a communicated  unoccupied reguest  the controller    Unit Operation    operates according to the  unoccupied setpoints regardless of  the state of the hardwired  occupancy input     If neither the binary input nor the  communicated input is used to  select the occupancy mode  the    Table 4  Normally open hardwired input configuration  Bl 3     controller defaults to occupied  mode because the occupancy binary  input  if present  typically is  configured as normally open  without an occupancy device  connected                    Description Communicated Reguest Hardwired State Result  Standalone NA Open   Occupied Occupied  Standalone NA Closed   Unoccupied Unoccupied  Communicating Occupied Open   Occupied Occupied  Communicating Unoccupied Open   Occupied Unoccupied       Communicating    Occupied Standby    Open   Occupied    Occupied Standby       Communicating    Occupied    Closed   Occupied Standby    Occupied Standby       Communicating    Unoccupied    Closed   Occupied Standby    Unoccupied          Com
24. ither a hardwired nor  communicated setpoint is present   the controller uses the stored default  setpoints     e Occupied setpoints   In the occupied mode  the unit  attempts to maintain the space  temperature at the active  occupied heating or cooling  setpoint based on the measured  space temperature  the active  setpoint  and the proportional   integral control algorithm     e Occupied standby setpoints   In occupied standby mode  the  controller uses the occupied  standby cooling and heating  setpoints  Because the occupied  standby setpoints typically  cover a wider range than the  occupied setpoints  the ZN510  controller reduces the demand  for heating and cooling the  space  Also  the outdoor air  damper is normally closed  during occupied standby mode  to further reduce the heating  and cooling demands        Unoccupied setpoints   In unoccupied mode  the unit  attempts to maintain the space  temperature at the stored unoc   cupied heating or cooling  setpoint based on the measured    13    space temperature  the active  setpoint  and the proportional   integral control algorithm   regardless of the presence of a  hardwired or communicated  setpoint     Once a valid setpoint is established   through the hardwired input or  through communication  and when  neither a local setpoint or  communicated setpoint is present   the controller generates a setpoint  failure diagnostic     When a setpoint failure diagnostic  occurs  the controller operates using  the default hea
25. l ff  GEHBO7211JDOA10DLCO10N001100010000000    Order    L9A123A A  Serial    W97H23456  Tagging  WSHP 1 1    NID  01 001C 7B DB 00    Location ID  Conference Room 101    Trane   Waco  TX 76714       NID   01 00 1C 7B DB 00    Serial     W97H23456    Figure 1  Unit Identification Tag    Note  Fold and tear carefully along dashed  removable line     Location   Conference Room 101       Unit Operation    General Information  The ZN510 controller is a  microprocessor based direct digital  controller that controls a variety of  water source heat pump eguipment  including    e Standard efficiency horizontal   and vertical units up to 10 tons     e High efficiency horizontal and  vertical units     20 POLE TERMINAL STRIP  FACTORY INSTALLED  SEE  WIRING DIAGRAM FOR  HOOKUP        Figure 2  Communication connections i    Communication   The ZN510 controller communicates  via Trane s Commb5 protocol   Typically  a communication link is  applied between unit controllers and  a building automation system   Communication is also possible    with Trane   s service tool Rover    ZN510 provides a total of six 1 4 inch  guick connect terminals for  connection to the Comm5  communication link  These  connections include       Two terminals  TB2 1  TB2 2        e Console water source heat  pumps    ZN510 is designed to provide  accurate and reliable zone  temperature control by using  custom proportional integral  Pl   algorithms  The controller is factory  installed and configured to support  
26. leaving water temperature sensor to  protect refrigerant circuit 1 and a  binary low temperature detection  device to protect refrigerant circuit  2  Each individual refrigerant circuit  is disabled when the low    temperature condition exists for that  circuit     For two compressor units  the  controller responds to low  temperature detection by allowing  the fan to operate  while disabling  the compressor for the faulty circuit   The compressor for the normal  circuit continues to operate  The    Table 3  ZN510 response to low temperature detection diagnostic                      Saar Fan z Damper  Description Operation Compressor Operation Operation   Low Temperature Detection Enabled Circuit 1 Disabled Normal   Circuit 1  Circuit 2 Normal Operation   operation  Low Temperature Detection Enabled Circuit 1 Normal Operation   Normal   Circuit 2  Circuit 2 Disabled operation  Low Temperature Detection z Circuit 1 Disabled    Circuits 1 and 2  Disabled Circuit 2 Disabled closed                Note     outdoor air damper also operates  normally     All unit operation is disabled when  the heat pump shuts down both  circuits  due to low temperature  conditions  See Table 3 for more  information     e The low temperature detection device automatically resets when the heat exchanger temperature returns to  normal  However  you must manually reset the low temperature detection diagnostic to clear the diagnostic and  restart the unit  Refer to page 28 on how to reset a unit     e  
27. led    Damper  Disabled                   High low pressure cutout and low temperature detection diagnostics for heat pump configurations isolate  each circuit and independently disable compressor operation  For single compressor units  these diagnostics cause  the compressor to shut down  the unit fan to be controlled off  and the outdoor air damper to be closed  when  present     When BOP 6 is configured as a generic binary output  BOP 6   s state is unaffected by all unit diagnostics       Note  Non latching diagnostics automatically reset when the input is present and valid     27    Translating Multiple  Diagnostics   The controller senses and records  each diagnostic independently of  the diagnostics  It is possible to have  multiple diagnostics present  simultaneously  The diagnostics are  reported in the order they occur     Resetting Diagnostics  1  Automatically by the controller     2  By initiating a manual output  test at the controller     3  By cycling power to the  controller     4  Through a building automation  system such as ZN510 Loop  Controller     5  Through Rover  Trane s service  tool     6  Through any communicating  device with the ability to access  the controller s alarm reset  input     Automatic Diagnostic Reset  The ZN510 controller includes an  automatic diagnostic reset function   This function attempts to  automatically recover a unit when  the following diagnostics occur    e Low temperature detection    Circuit 1    e Low temperature detec
28. led ancil   lary devices is not available from the  board  It must be tapped at trans   former  See Table 21 for excess power  available     Binary Outputs   The ZN510 uses five of its binary  outputs to control heat pump units   Outputs are load side switching triacs   The triac acts as a switch by either  making or breaking the circuit  between the load  reversing valve   damper  contactor  relay  and ground     See Figure 5 for the configuration of  the five binary outputs     2 Position Damper Actuator or  Generic Binary Output   Binary output 6  BOP 6  is factory  configured to control a normally  closed 2 position outdoor air damper   It may be field modified to control a  generic output for control by a  building automation system  If set up  as a generic output  the controller  does not use BOP 6 as part of the  normal control  A building automation  system must issue commands to  control the generic binary output     Note   e During occupied mode  the  outdoor air damper is closed  when the fan is controlled off     During unoccupied mode  the  outdoor air damper normally  remains closed     2 position damper must not  exceed 10 VA power output from  board     Unit Operation    Factory Supplied Transformer    Line  Voltage    24VAC                as sg     B             Figure 4  Power Connections    Field installed  2 position    24VAC  1TB1 17    OP 6  Compressor 2         BOP 3  Not available   BOP 4  Not Used   BOP 5  Compressor 1        BOP 1  Fan           Bina
29. mands  The controller uses the    unit capacity and pulse width  modulation  PWM  logic along with  minimum on off timers to determine  the operation for compressor 1     With a dual compressor unit  if the  desired conditions are not met by    Table 7  Heat pump heating or cooling operation     controlling only the first  compressor  the controller runs  compressor 1 continuously and  controls compressor 2 according to  PWM logic along with the minimum  on off timers  See Table 6 for heat  pump heating or cooling operation        Capacity       Unit  0     Between  O and 50        Between  50 and 100     100        Single compressor i  continuously     Compressor OFF    decreases     Compressor output is controlled according to pulse width  modulation  PWM  logic between 0 and 100   The  controller calculates the compressor on off times based  on PWM logic and heating cooling capacities  The  compressor is controlled on for longer periods as the  capacity increases and shorter periods as the capacity    Compressor ON  continuously        Dual  Two  compressors          Both compressors  OFF continuously      1  ON PWM    2  OFF continuously            1  ON continuously    2  ON PWM     Both compressors ON  continuously               Note  No diagnostics present     Certain heat pump configurations  may use one or two compressors for  cooling control  Heat pumps use  reversing valve control to switch  between heating and cooling  The  controller supports cooling only  config
30. municating       Occupied Standby       Closed   Occupied Standby       Occupied Standby          Note     If configured for normally closed  all states are opposite of Table 4     Generic Binary Input   Building automation systems can  monitor the status of the generic  binary input  This input does not  affect controller operation     High and Low Pressure  Switches   The high and low pressure cutout  switches are wired in series with the  compressor contactor in the unit   The ZN510 controller detects the  state of each switch circuit by  monitoring the controller s  compressor triac outputs  If either  the high pressure switch  HPC  or  the low pressure switch  LPC  switch  opens  a fault condition occurs  This  open circuit prevents the    compressor contactor from  energizing keeping the compressor  from running  The controller  automatically detects the fault  condition by measuring the  compressor triac output signal     By default  when the HPC or LPC  switches detect a high or low  pressure condition in the refrigerant  circuit  the special input detects the  diagnostic and disables all  compressor operation for that  circuit  The unit fan continues to  operate  if only one circuit is  disabled in a two compressor unit   When the HPC LPC diagnostic is  present on both circuits  the ZN510  shuts off the unit fan and disables    11    unit operation  See Figure 7 for high  and low pressure switch     When the refrigerant circuit returns  to normal  the HPC and the LPC
31. nary input associates an  input signal of 0 VAC with open  contacts and 24 VAC with closed  contacts  See Figure 6 for typical  binary input configurations for the  heat pump     e Force compressor operation   allowing the technician to use  refrigerant gauges or other test  equipment to verify unit  operation     manual output test  See  Troubleshooting section for Green  LED and Testing Heat Pump  Configurations on page 21  amp  22     The test sequence resets unit  diagnostics and attempts to restore  normal unit operation prior to  testing the outputs  If the diagnostics  remains after a reset  the status LED  indicates the diagnostic condition is  still present and has affected the    ZN510 does not use analog outputs             Low Temperature  Detection  Circuit 2     Condensate Overflow    Binary Inputs       Field Wired  Occupancy Input    Figure 6  Binary inputs     Table 2  Binary input configurations                                        Binan Inoue Descrintion Configuratio Contact Contact  erase P n Closure Open  Low Temperature Normally    gt   BM Detection  Cir 2  closed Normal Diagnostic  Bl2 Condensate Overflow Normally Normal Diagnostic  closed  Bl3 Occupancy Normally open   Unoccupied _  Occupied  Generic Normally open   Normal Normal  Note     See Page 10 for specific information concerning Bl 1  Bl 2 and Bl 3     9    Unit Operation    Low Temperature Detection   The low temperature detection  diagnostic protects the heat  exchanger by using an analog  
32. nication jack      Vertical case with Trane logo       ADJUSTABLE                  RTI ZONE  lt    10K OHM     25  C   2 C SIGNAL  COMMON   lt   2    T 200       LV   SV ist G  SETPOINT COMM HIGH      X4       COMM LOW      GS       Mit JACK    COMMUNICATIONS                GP mr          Part Number   X13510606010  Description      Space temperature  0 2 C  resolution       External setpoint      Communication jack      Vertical case with Trane logo          ADJUSTABLE  SETPOINT              RTI ZONE  lt     10K OHM    25 C 2 20    SIGNAL  COMMON   lt   2    VRI    200  N VA CSP 3    COMM HIGH       r gt   a  COMM LOW       Xs          M     JACK    1    COMMUNICATIONS                   mwr                               16    Zone Sensor Specifications       Part Number   X13510606020  Description     Space temperature  0 2 C  resolution      External setpoint   ON and CANCEL buttons   Communication jack     Vertical case with Trane  logo           mwr                            CANCEL             Part Number   X13510635010  Description     Space temperature  0 2 C  resolution      External setpoint    Fan Switch  OFF and  AUTO     ON and CANCEL buttons   Communication jack     Vertical case with Trane  logo        mj                                  17    Heating or  Cooling Control  Mode Operation    Heating or Cooling   Operation   For both single and dual compressor  operation  the ZN510 controller  cycles the compressor s  on and off  to meet heating or cooling zone  de
33. nt low limit  40 F  Heating setpoint high limit  115 F  Heating setpoint low limit  40 F  Thumbwheel set point  Enabled       Occupied Bypass  Timer    120 minutes       Leaving Water  Temperature  Low Limit    Unit specific  20 F ground source or 35 F standard     The heating and cooling setpoint  high and low limits only apply to the  occupied and occupied standby  setpoints  These limits never apply  to the unoccupied setpoints        The occupied bypass time is used for timed  override applications  The timed override  timer is maintained in the unit controller   When the timed override is applicable  the  controller reports    Occupied Bypass    as its  effective occupancy mode        Location Identifier          Unit specific  maximum of 30 characters             BOP 2  BI1  Not used on cooling only units      BOP 5  Not used on signal compressor unit       Configured but not required    t Optional model number dependent    21    The leaving water temperature low  limit is used for freeze protection of  circuit 1 on heat pumps  Circuit 2 is  protected by a binary low  temperature detection device   freezestat  with a fixed trip point     Troubleshooting    Red Service LED  Table 9  Red LED activity       Red LED Activity Description       LED off continuously when power is applied to the    Normal operation   controller        LED on continuously  even when power is applied to  Someone is pressing the service button or the controller has  the controller  failed        U
34. ommunicated space temperatureis  present  the ZN510 controller  generates a space temperature  failure diagnostic     Note    The ZN510 controller cannot oper   ate without a valid space tempera   ture value  either hardwired or  communicated      The space temperature input can  communicate timed override ON or  CANCEL requests to the ZN510  controller  If the ON button is  temporarily pressed  the zone  sensor sends a signal to the  controller  This signal is then  interpreted as a timer override  request which places the unit into  occupied     The controller uses the timed  override request  while the zone is  unoccupied  as a request to switch  to the Occupied Bypass mode   occupied bypass   This Occupied  Bypass mode lasts for the duration  of the occupied bypass time   typically 120 minutes    or   The controller s Occupancy mode is  determined from either a system  level controller or another peer  controller     The CANCEL button cancels the timed  override request and returned the  unit to unoccupied mode  If the  CANCEL button is temporarily    Unit Operation    pressed  the zone sensor sends a  signal to the controller  This signal is  then interpreted as a timed override  cancel which places the unit into  unoccupied     Local Setpoint   The local setpoint analog input is  designed as the local  hardwired   setpoint input  This input cannot be  used for any other function  The  local input is a resistance input  intended for use with Trane zone  sensors     If ne
35. open or  close the controller generates a  Leaving Water Temp Failure  diagnostic  This disables unit  operation     Note    A low temperature detection failure  diagnostic for compressor 1 may  require you to manually reset the  unit to restore compressor opera   tion     Similarly  the ZN510 controller uses  a binary low temperature detection  device  fixed low limit trip point  to  lock out circuit 2 when a fault condi   tion is detected     14    See the Diagnostics section on page  28 for information about the  automatic diagnostic reset function     Filter Maintenance Timer   The controller   s filter maintenance  timer is based on the unit fan   s  cumulative run hours  The controller  compares the fan run time against  an adjustable fan run hours limit   maintenance required setpoint  time  stored in the controller  and  recommends unit maintenance  i e   changing the filter      Use Rover or BAS system to edit the  maintenance required setpoint time   Once the setpoint limit is exceeded  the controller generates a filter  maintenance timer diagnostic   When the maintenance required  setpoint time is zero  the controller  disables the diagnostic feature     Discharge Air Temperature  Analog input 2  Al 2  is used as the  discharge air temperature input for  use with a 10 000 ohm thermistor   Typical factory placement of the  thermistor is at the discharge area of  the unit  The discharge air  temperature sensor does not affect  unit operation  The measured  temperatur
36. pancy mode and fan status  Normally  the outdoor air damper is open  during occupied mode when the fan is running and closed during unoccupied  mode  Refer to the outdoor air damper section on page 8        Manual output test     The controller includes a manual output test sequence that may be used to verify  output operation and associated output wiring  However  based on the current  step in the test sequence  the outdoor air damper may not open  Refer to the  manual output overrides on page 9        Unit configuration     The controller must be properly configured based on the actual installed end  devices and application  When the unit configuration does not match the actual  end device  the outdoor air damper may not work correctly        Unit wiring        The wiring between the controller outputs and the compressor contacts must be  present and correct for normal damper operation           25          Ouestionable Unit  Operation    Troubleshooting    Table 16  Outdoor air damper stays closed       Probable Cause    Explanation       Normal operation     The controller opens and closes the outdoor air damper based on the controller s  occupancy mode and fan status  Normally  the outdoor air damper is open  during occupied mode when the fan is running and closed during unoccupied  mode  Refer to the outdoor air damper section on page 8        Warm up and cool down     The controller includes both a morning warm up and cool down sequence to  keep the outdoor air damper 
37. part of the morning warm  up seguence     Master Controller   ZN510 can send or receive data   such as setpoint  heat cool mode   fan reguest and space temperature   to and from other controllers on the  communication link  with or without  a building automation system  This  includes applications where  multiple unit controllers share a  common space temperature sensor   both for standalone and building  automation applications     The master controller  the unit  controller with the hardwired zone  sensor  in peer to peer  communication can send its zone  temperature to one or more slave  controllers which allows the slave  controllers to track each other s  zone temperature  For these  applications  Rover is used in set up  of the controller     See Figure 9 for Master Slave  setpoint operation for peer to peer  set up     Setpoint Operation   Controllers sharing information  peer to peer can share a variety of  data  including the heating cooling  setpoint  communicated from a  master to a slave      The standalone master controller  derives its setpoint from either the  local hardwired setpoint input or  from its default setpoints  Peer to   peer applications often reguire the  use of one hardwired setpoint to be  shared across two or more  controllers  This can be achieved by  wiring the adjustable setpoint   typically included as a part of the  Trane zone sensor module  to the  controller defined as the master   Trane s service tool  Rover may be  used to set up the ma
38. put  Depending on the state of the communicated request   the unit may disable the compressor        Manual output test     The controller includes a manual output test sequence that may be used to verify  output operation and associated output wiring  However  based on the current  step in the test sequence  the compressor s  may not be on  Refer to the manual  output overrides on page 9        Diagnostic present     A specific list o f diagnostics affects compressor operation  depending whether  the unit is configured as heat pump  For more information  see the Diagnostics  section on page 27        Unit configuration     The controller must be properly configured based on the actual installed end  devices and application  When the unit configuration does not match the actual  end device  the compressor may not work correctly        No power to the controller     If the controller does not have power  the compressor does not operate  For the  ZN510 controller to operate normally  a voltage input of 24 VAC must be applied   When the green LED is off continuously  the controller does not have sufficient  power or has failed        Unit wiring        The wiring between the controller outputs and the compressor contacts must be  present and correct for normal compressor operation           Table 15  Outdoor air damper stays open       Probable Cause    Explanation       Normal operation     The controller opens and closes the outdoor air damper based on the controller   s  occu
39. r 10 seconds     Wink    mode is sent from Comfort Link  Controller        e Power off   LED off  e Abnormal condition   e Test button is pressed           Yellow Service LED          Table 11  Yellow LED activity       Yellow LED Activity Description       The controller is not detecting any communication     PEP OF ante   Normal for standalone applications         The controller detects communication   normal for    BEE Pinks  communicating applications  including data sharing                  LED on continuously  Abnormal condition        22    Troubleshooting                                                    Manual Output Testing the Heat for at least three seconds to 3  Press the Test button several  Pump Configurations start the test mode  more times  no more than once  The procedure for testing heat pump per second  to advance through      WN 2  The test seguence resets  configurations is      the test sequence   diagnostics and turns off all  1  Press and hold the Test button outputs   Table 12  Test sequence  Ste Fan Reversing Valve Compr 1   Compr 2 Damper  8 BOP 1 BOP 2 BOP4   BOP5 BOP 6  1  Off Off Off Off Off Closed  2  Fan on  At the beginning of step 2  the On off Off Off Closed  controller attempts to clear all diagnostics    3  Reversing Valve On On Off off Closed  4  Cool 1 On On On off Closed  5  Cool 2 On On On On Closed  6  Compressor s  off  This stage helps avoid compressor cooling  and heating in sequential steps by turning the  On Off Off Off Closed 
40. rating Environment  32 to 140 F  0 to 60 C   5 to 95  non condensing       A        Hardware  Specifications    Storage Environment    40 to 185 F   40 to 85 C    5 to 95  non condensing  Power Requirements   18 to 32 VAC  24 VAC nominal   50 or 60 Hz   300 mA    Agency Listings   UL and CUL 916 Energy  Management System  Agency Compliance    IEC 1000 4 2  ESD   IEC 1000 4 4     EFT   IEC 1000 4 5  Surge   FCC Part  15  Class A     Input Output Summary    e Three binary inputs     e Six binary outputs only five are  used     Five analog inputs     Timed override ON and CANCEL     Comm5 communication     Heat sink is mounted to the top    of the control box    ZN510     Actual Size 4 0 x5 5      Dre    COMMMUNICATION     coum    comum    comm     L       5 1 2        BINARY  OUTPUTS    ComfortLink tm  10  12 34 56 78 9A BC    NID     STATUS    BEE SENSOR       _  m               FEF       Figure 10  ZN510 Circuit Board    31    Hardware                                                                   Specifications  Table 18  Binary Inputs  Description Terminals Function  Binary Input 1 J2 1 24 VAC  J2 2 Input  Binary Input 2 J2 3 24 VAC  J2 4 Input  Binary Input 3 J2 5 24 VAC  J2 6 Input  Table 19  Binary Outputs  Description Terminals Sup us Load Energized Load De energized  Rating  Binary Output 1  J1 1 12 VA 1 VAC RMS  typical  24 VAC RMS  typical   Binary Output 2  J1 2 12 VA 1 VAC RMS  typical  24 VAC RMS  typical   Binary Output3  J1 4 NOT USED  Binary Output 4  J1 5 1
41. ry Outputs    Figure 5  Binary outputs    Table 1  BOP 6 control of a 2 position outdoor air damper                         Model Fan Operation Outdoor Air Damper    On or cycling Open   Occupied Off Closed  Occupied war uor On or cycling Closed  cool down   Occupied standby On or cycling Closed  Unoccupied Cycling Closed  Diagnostic present Diagnostic dependent Closed                damper actuator    Unit Operation    Output Overrides   The ZN510 controller includes a  manual outputtest function  Use this  feature to manually exercise the  outputs in a defined seguence  The  purpose of the test seguence  is to  verify output and end device  operation  Use the manual output  test to     e Verify output wiring and  operation without using Trane s  service tool  Rover     Analog Outputs    Binary Inputs   The ZN510 controller has three  available binary inputs  Bl   These  inputs are factory configured for  the following functions        Bl 1  Low temperature  detection  freezestat   Circuit 2      e BI 2   Condensate overflow     e BI 3   Occupancy or generic  binary input     Each binary input may be  configured as not used depending  on options selected  BI 3 is  configured as a normally open  occupancy input  but may be field  modified for generic binary input  which is only supported by a build   ing automation system     Note    The diagnostic functions related to  binary inputs such as low tempera   ture detection and condensate  overflow are fixed sequences     Each bi
42. se Rover  Trane s service tool  to restore the unit to normal    LED flashes once every second        operation or unconfigured                 IWarning  Service Button  The black Service button on the ZN510 board allows the user to send a service pin message  which allows  efficient identification of the unit s location  However  if the Service button is held for more than 10    seconds  the ZN510 will shut down the software application and disable the unit s operation  The only  method to restore the unit is through the use of Rover service tool  We strongly suggest that this function  only be exercised under the strict direction of factory service personnel        Green Status LED    The green LED normally indicates Table 10  Green LED activity  whether the controller is powered       on  24 VAC   Green LED Activity Description       LED on continuously  Power on  normal operation         Manual output test mode  2 second hold   No    LED blinks  one blink   diagnostics present       Manual output test mode  2 second hold      BED blinks PAVO OIS  One or more diagnostics are present           Wink    mode    This feature allows the identification of a  controller  By sending a request from a device   such as Rover  Trane   s service tool or ZN510  LED blinks  1 4 second on  Loop Controller  a request to the controller  1 4 second off for 10 seconds  can be made to    wink    a notification that the  controller received the signal  When the zone  sensor ON button is held fo
43. ster and one or  more slaves to share that setpoint   For this application  each  communicating controller uses the  same setpoint     Data Sharing    Master Controller             Communication Link                      c       Zone Sensor             Figure 9  Master slave setpoint operation for peer to peer setup    Note    Each controller derives it s effective  setpoint and default setpoints   including deadbands between set   points  from the setpoint input   hardwired or communicatea   To  make sure the peer to peer setpoint  application results in identical set   points for each communicating con   troller  each controller must have  exactly the same default setpoints     Simplified Peer to Peer  Master   Slave  Setup   To simplify setting up master slave  applications  the controller provides  information that groups all  necessary shared data into one  communication variable  This  master slave variable includes the  following information     e Space temperature     e Setpoint     20    e Heating cooling mode    e Occupancy    e Fan status      Unit control algorithm capacity     This information is communicated  from the master to the slave to  ensure similar unit operation     Use Rover  Trane s service tool  to  set up peer to peer applications     Refer to the Rover product literature  for more information on setting up  applications     Configurable Parameters   Rover  Trane s service tool  uses the  unit type    heat pump    to determine  and download unit con
44. t Nr DISCHARGE AIR  33a   m   5 2 T  42A  gt  SENSOR  4 32 5  7 3 53 Pi 3 4RT1     3 43A     o uu     2 COMM LINK ZONE SENSOR   LEAVING WATER  x  gt  TMM 7 z M ssa bd SENSOR  he ls i      CIRCUIT 1  ME d  ZONE GND SET FAN GND    FAN MODE 24A    1m4  SET POINT 25A    10 3 ANE NER  COMMON 22A    1m1 2 CONNECTIONS  ZONE TEMP ZA    1m   COMM  28A    1m s COMMUNICATIONS  COMM 25A    1mi 5 ZONE SENSOR  COMM  18A    11 16 COMMUNICATIONS  COMM 19A    1m1 14 LINK       29       Wiring Diagram    noo  NWARNING A AVERTISSEMENT       Git  LINE VOLTAGE HAZARDOUS VOLTAGE  VOLTAGE HASARDEUX   yo air DISCONNECT ALL ELECTRIC POWER DECONNECTEZ TOUTES LES SOURCES  PAE INCLUDING REMOTE DISCONNECTS ELECTRIQUES INCLUANT LES  ELA BEFORE SERVICING  DISJONCTEURS SITUES A DISTANCI  If fi FAILURE TO DISCONNECT POWER AVANT D EFFECTUER L ENTRETIEN   in A   l BEFORE SERVICING CAN CAUSE FAUTE DE DECONNECTER LA SOURCE  LY yl SEVERE PERSONAL INJURY   R ELECTRIQUE AVANT D EFFE     CTUER  DEATH  LENTRETIEN PEUT ENTRAINER DES  BLESSURES CORPORELLES SEVERES  OU LA MORT     IMPORTANT    USE COPPER CONDUCTORS ONLY TO PREVENT EQUIPMENT DAMAGE   UNIT TERMINALS ARE NOT DESIGNED TO ACCEPT ANY OTHER WIRING     HE EFE erat                                                                                                                                                                                                                                                                                                               
45. t observed     After power up  the controller always observes a random start from 0 to 25  seconds  The controller remains off until the random start time expires        Power up control wait     When power up control wait is enabled  non zero time   the controller remains  off until one of two conditions occurs   e The controller exits power up control wait once it receives commu   nicated information     e The controller exits power up control wait once the power up control  wait time expires        Cycling fan operation     When configured to cycle with capacity  normally the unit fan cycles off with  heating or cooling  The heating cooling sources cycle on or off periodically with  the unit fan to provide varying amounts of capacity to the space        Unoccupied operation     Even when the controller is configured for continuous fan operation  the fan  normally cycles with capacity during unoccupied mode  While unoccupied  the  fan cycles on or off with heating cooling to provide varying amounts of heating  or cooling to the space        Fan mode off     When a local fan mode switch determines the fan operation  the off position  controls the unit fan off        Requested mode off     The desired operating mode  such as off  heat and cool  can be communicated to  the controller  When off is communicated to the controller  the unit controls the  fan off  There is no heating or cooling        Diagnostic present     A specific list of diagnostics affects fan operation  See 
46. ting and cooling  setpoints  These setpoints are  factory configured  but may be  changed using the Trane service  tool  Rover     The ZN510 controller uses the  following validation sequence for  the setpoints     1  Check for a communicated  setpoint  If present  validate this  setpoint     2  Check for a hardwired setpoint  and validate the setpoint     3  Use the default setpoint and  validate this setpoint     Fan Mode Input   The fan mode analog input  Fan  is  designed to operate as the fan mode  switch input  This input cannot be  used for any other function  The fan  switch on a Trane zone sensor  generates the fan mode signal     The ZN510 controller detects the  unique resistance corresponding to  each position of the fan switch  By  measuring the resistance  the  controller determines the requested  fan mode        Possible  Fan Modes    Heat Pump   1 speed        OFF Fan Off       Continuous   Field  Modified         n occupied mode  the  fan runs continuously   In unoccupied mode   the fan cycles OFF  when no heating or  cooling is reguired     AUTO       Cycling   Factory Default       The fan cycles ON and  OFF with compressor  operation     AUTO                The ZN510 controller receives the  fan mode from either a wired zone  sensor or as a communicated valve   When neither a zone sensor nor  communicated fan mode are  present  the ZN510 controller will  default unit operation to AUTO     Note       A building automation system  can also generate a fan mod
47. tion   Circuit 2    e Low temperature detection   Circuit 1 and 2       High low pressure cutout   Circuit 1       High low pressure cutout   Circuit 2    Diagnostics       High low pressure cutout   Circuit 1 and 2    When one or more of these special  diagnostics occurs  the controller  responds to the diagnostic as  defined in the table 17 on page 27   After the controller detects the first  special diagnostic  listed on page  27   the unit waits 30 minutes before  invoking the automatic diagnostic  reset function  The automatic  diagnostic reset function clears all  special diagnostics and attempts to  restore the controller to normal  operation  The controller resumes  normal operation until another  diagnostic occurs     If a special diagnostic occurs within  24 hours after an automatic  diagnostic reset  the diagnostic  must be manually reset     Cycling Power   When the 24 VAC power to the  controller has been turned off  the  unit cycles through a power up  sequence  By default  the controller  attempts to reset all diagnostics at  power up  Diagnostics present at  power up and those that occur after  power up are handled according to  the table on page 27     Building Automation System   CLC    Some building automation systems  can reset diagnostics in the ZN510  controller  The ZN510 Loop  Controller can reset diagnostics in  the ZN510 Controller  For complete  information  refer to the building  automation system product  literature     28    Rover Service Tool   
48. urations and heat pump  configurations     For heat pump configurations  the  unit   s reversing valve is energized in  cooling and de energized in heating   For cooling  the reversing valve  output is energized simultaneously  with the compressor  compressor 1  in two compressor applications    The reversing valve remains  energized until the controller turns  on the compressor for heating     simultaneously de energizing the  reversing valve  The reversing valve  only changes state when the  controller turns on compressor 1     When a power failure occurs  the  reversing valve output defaults to  the heating  de energized  state  To  reduce noise due to refrigeration  migration after compressor  shutdown  the controller does not  immediately operate the reversing  valve  The reversing valve changes  state only when the compressor  controls on  except when the  controller is in off mode     For cooling only configurations  no  reversing valve is present and the    18    controller uses the compressor  stages for cooling     Compressor Minimum  ON OFF Timers    e When fan mode   OFF  Com   pressor minimum ON timers are  ignored       When fan mode   AUTO  Com   pressor minimum OFF timers are  observed     e The diagnostic reset ignores the  compressor timers ON and OFF       A communicated compressor  disabled or unoccupied signal  ignores minimum ON times     Other Modes   Occupancy Operation  Unoccupied operation normally is  associated with evening hours when  the space is
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Ma responsabilité de PLC, PLP, PEPS - Lettre d`informations  I. Immersion Suit Repair Kit (Set of Servicing Equipment)  Window Thermometer  Catálogo - Schneider Electric  MAN006 - MANUAL DO USUÁRIO REP FAMÍLIA R100 R11  Sanyo ECD-780 User's Manual  Artsound AS-C100 BE loudspeaker  Mode d`emploi feuille de présence La feuille de présence  Tucano Termo  Manual del usuario    Copyright © All rights reserved. 
   Failed to retrieve file