Therma-Stor Products Group PHOENIX 300 User's Manual

image

Contents

1. tubing or electrical components 8 Reassembling with the new blower is the above procedure reversed OMB WN p 4 6 Compressor Capacitor Replacement This compressor is equipped with a two terminal external overload run capacitor but no start capacitor or relay see Fig 3 CAUTION CAUTION ELECTRICAL SHOCK HAZARD Electrical power must be present to perform some tests these tests should be performed by a qualified service person Toll Free 1 800 533 7533 4 6A Checking Compressor Motor Circuits Perform the following tests if the blower runs but the compressor does not with the power switch ON 1 Turn the power switch OFF and unplug the unit remove the cabinet front 6 screws 2 Plug in the unit and turn the power switch ON Use a voltmeter to check for 110 to 120 volts between a the relay terminal that the black wire from the compressor connects to and b the capacitor terminal with the 3 white wires and 1 red wire connected If voltage is present go to step 3 If no voltage the low pressure control the time delay or the relay are open or there is a loose connection in the compressor circuit Test each component for continuity see the appropriate section if a defect is suspected 3 Turn the power switch OFF and unplug the unit then disconnect the red and yellow wires from compressor terminals R and S Using an ohmmeter check continuity between the points listed below 4 Compressor terminals C a
2. When enough frost forms the defrost thermostat will initiate the timed defrost cycle The cycle periodically turns off the compressor while allowing the blower to run The frost is melted by the air that the blower draws through the cooling coil The defrost cycle is automatic and designed for optimum performance above 50 F If the unit is used in an area that is below 50 F for more than 2 hours adjustment of the defrost timer is recommended to improve performance see Sec 2 10 DRYING TIP Air s ability to absorb moisture from wet surroundings and the Phoenix 300 s ability to remove moisture from that air is greatly improved at higher temperatures We recommend that the area to be dried be heated to over 70 F if possible Less drying time will be required and efficiency will improve To adjust the defrost timer 1 Unplug the unit 2 Remove the front cover 6 screws 3 The timer is fastened to the right inside panel Every fourth peg around the dial is pushed out from the dial center except one section with 5 pegs out in a row See figure 1 Each fourth out peg represents 15 minutes of compressor off time during every hour that the unit is in the defrost cycle 4 To improve performance below 50 F the compressor off time must be increased to 30 minutes per hour to allow the frost to completely melt To do this push the pegs out from the dial center so that the pegs alternate with 2 toward the center th
3. or drips Pump fail warning light and cut off Prevents reservoir overflow Lighted power switch Check machine status at a glance Digital hour meter Easy to read for more accurate billing Phoenix 300 PN 4022599 30 ft power cord No need for extension cords 30 ft drain hose Pump condensate to sinks or drains Specifications subject to change without notice Revised 1 07 Toll Free 1 800 533 7533 1 www thermastor com sales thermastor com Table of Contents Introd ctionN nseni 0600 2e a cerns aed a aa a a ai 1 1 Specifications ccccccccceceececeeceeeeeeseeseeeeaeseeees 2 2 Operation ss escceics ene sicedae nedevesieeesacetidend ahi slssdtestecexes 2 2 1 Transporting the Phoenix 300 c cc cceeeeeeeees 2 2 2 kogato ion aa a a e EEA 2 2 3 Electrical Requirements cccceeeeeceeeeeeees 2 2 4 Condensate REMOVAl cccccecceeceeceeeeeeeeneeeees 3 2 07 DUCUING nerenin ta nE AR EEan ao dics See 3 2 6 Power SWItch cccccseessceeesecoeesesoeesesonesesenenes 3 2 7 Pump Purge SWItCHN ccccceeceeeeeeeeeeeeeeeeeeeeeees 3 2 8 Pump Fail Light ccccccsecceeeceeeseeeseeeaeeees 3 2 9 Hour Metaf egri tei etevece a onder 3 2 10 Defrost Control Adjustment ccccceeeee eee 3 2 11 Low Pressure ContrOl cccccccseeeeeeeeeeeeeeeeeeees 4 3 Maintenance cccccccscseceseneeeeeneeeeeneeeneneeeeenensees 4 3 4 Air Filt ticccecc dccce c
4. reduces compressor short cycling after the compressor has stopped 115Vac 60Hz 1PH BLK WHT G PUMP PUMP FLOAT MOTOR CONDENSATE PUMP AE EX m H g a w Es PUMP PURGE SWITCH FLOAT SWITCH Co NOO MOTOR GRN oo BLU PUMP FAIL NCo dle Viet PUMP SAFETY SAFETY A SWITCH ey TER c MOTOR BLK GRA CA L PUMP FAIL LOW RELAY mnie PUMP PURGE LIGHT PRESSURE COIL SWITCH BLK 2 YEL CONTROL Boon K7 T TIME 35 DELAY SWITCH Reita a OPTIONAL is BLOWER DEFROST MOTOR CONTROL HOUR METER i il Or POWER SWITCH Ne POWER SWITCH BLK O WHT POWER LIGHT j WHT SWITCH ON x LIGHT TIMER Lo o o BACK VIEW HOUR ORG fi 2 25 METER LOW SWITCH ae MOTOR A i 7 z COMPRESSOR PEOR DELAY OVERLOAD H 4 6 c OPTIONAL TE x l i RELAY BLOMER DEFROST CONTASI COMPRESSOR BLK EN wHT CONTROL MOTOR GRA S 1 bac COMPRESSOR CAPACITOR mers ee Se AA BLK C VV i i o ae NA Therma Stor ART NO REV Hin OVERLOAD R Made in USA i RELAY pesega me 4022597 A Figure 3 Electrical schematic of Phoenix 300 Toll Free 1 800 533 7533 www thermastor com sales thermastor com 6 Service Parts Item 1 2 10 11 12 13 14 15 16 17 18 19 20 21 2
5. repair or replace the defective part s provided that all labor and transportation charges for the part s shall be borne by the end user End User Responsibilities Warranty service must be performed by a Servicer authorized by Therma Stor LLC If the end user is unable to locate or obtain warranty service from an authorized Servicer he should call Therma Stor LLC at the above number and ask for the Therma Stor Service Department which will then arrange for covered warranty service Warranty service will be performed during normal working hours The end user must present proof of purchase lease upon request by use of the warranty card or other reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control Limitations and Exclusions If any Phoenix 300 Dehumidifier part is repaired or replaced the new part shall be warranted for only the remainder of the original warranty period applicable thereto but all warranty periods will be extended by the period of time if any that the Phoenix 300 Dehumidifier is out of service while awaiting covered warranty service UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE PHOENIX 300 D
6. unit and remove the front cover 2 Disconnect the 2 hoses from the pump 3 Cut the pump lead wires near the old pump 4 Remove the 4 screws from the unit bottom that hold the pump to the base Attach the new pump with 4 screws Connect the new pump wiring It may be easier to splice the new and old gray leads together with a wire nut and splice the new and old yellow leads together rather than route the new ones to the pump purge switch and pump fail light 7 Connect the hoses to the new pump Carefully route the hoses so they do not contact the copper refrigerant lines or the compressor shell oo www thermastor com sales thermastor com 4 9 Relay The contacts of the single pole single throw relay complete the power circuit to the compressor The contacts are closed when power is provided to the relay coil via the control circuit The control circuit includes the power switch low pressure control time delay HP model defrost thermostat and timer 5 Wiring Diagram 4 10 Time Delay HP model only The HP model has a time delay relay in the compressor control circuit This relay delays the compressor start about 2 minutes after the power switch is turned on This reduces the unit s starting amp draw by starting the blower and compressor at different times This reduces the chance of tripping a circuit breaker during hard start situations such as when the unit has been stored in a cold place It also
7. 2 23 24 25 26 27 Toll Free 1 800 533 7533 Part No 4021818 4022636 4022614 4022624 4021083 4022622 4017777 4022563 4022557 4022600 4023645 4022595 4022634 4022615 4021908 4022611 4022593 4021597 4021089 4022616 4022219 1970010 4022740 4021997 4021796 4021822 4021470 4021648 4021823 4022878 4022613 Qty PRPPRPPORPRRRPBP BRP BB Description Accumulator Air Filter Pleated 2 x 20 x 20 Air Filter Pleated 4 x 20 x 20 MERV 8 Air Filter Pleated 4 x 20 x 20 90 95 EFFICIENT Blower w Capacitor Bumper Foot 1 50 Dia x 75 High Capillary Tubes 059 ID x 124 OD x 32 long Coil Condenser Coil Evaporator Compressor Carlyle P N EBA135111A HP Model Compressor Kit Carlyle P N EBA120111A 4022750 Compressor only Compressor Overload Carlyle included with compressor Condensate Pump Cord and Wire Harness Drain Hose 38 ID x 56 OD x 33 long Outlet Collar for Ducting Outlet Filter Drier not shown Hour Meter Indicator Light Red 125V Instruction Label not shown Low Pressure Control Relay Run Capacitor 30 MFD 370V Spring Switch Pump Purge Switch Power Thermostat Defrost Thermostat Defrost Mounting Clip Timer Defrost Time Delay HP Model Wheel 12 Plastic Items listed are not shown 4022597 1 Wiring Diagram on Cover not shown 4021950 1 Ground Fault Interrupter opt
8. EHUMIDIFIER OR ANY PART THEREOF ALL OTHER WARRANTIES IMPLIED BY LAW INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE SHALL ALSO EXPIRE ALL WARRANTIES MADE BY THERMA STOR LLC ARE SET FORTH HEREIN AND NO CLAIM MAY BE MADE AGAINST THERMA STOR LLC BASED ON ANY ORAL WARRANTY IN NO EVENT SHALL THERMA STOR LLC IN CONNECTION WITH THE SALE INSTALLATION USE REPAIR OR REPLACEMENT OF ANY PHOENIX 300 DEHUMIDIFIER OR PART THEREOF BE LIABLE UNDER ANY LEGAL THEORY FOR ANY SPECIAL INDIRECT OR CONSEQUENTIAL DAMAGES INCLUDING WITHOUT LIMITATION WATER DAMAGE THE END USER SHOULD TAKE PRECAUTIONS AGAINST SAME LOST PROFITS DELAY OR LOSS OF USE OR DAMAGE TO ANY REAL OR PERSONAL PROPERTY Some states do not allow limitations on how long an implied warranty lasts and some do not allow the exclusion or limitation of incidental or consequential damages so one or both of these limitation may not apply to you Toll Free 1 800 533 7533 11 www thermastor com sales thermastor com
9. acing a Compressor Non Burn Out Remove the refrigerant from the system Replace the compressor and liquid line filter drier Charge the system to 50 PSIG and check for leaks Remove the charge and weigh in the refrigerant quantity listed on the nameplate Operate the system to verify performance 4 7 Defrost Thermostat and Timer The defrost thermostat is attached to the refrigerant suction tube between the accumulator and compressor If the low side refrigerant temperature drops due to excessive frost formation on the evaporator coil the thermostat opens The compressor is then cycled off and on by the defrost timer The blower will continue to run causing air to flow through the evaporator coil and melt the ice when the compressor is off When the air temperature and or humidity increase the evaporator temperature will rise and the thermostat will close to end the defrost cycle To improve performance in low temperatures see Sec 2 9 for defrost timer adjustment 4 8 Condensate Pump Condensate is automatically pumped when the water level in the pump s reservoir rises to close the float switch or if the pump purge switch is held in If the pump is unable to empty its reservoir due to a pump failure or blocked condensate hose a pump safety float switch is triggered before the reservoir overflows The switch turns on the pump fail light and turns off the compressor via its relay To replace the condensate pump 1 Unplug the
10. cc deen tasini naiita reiii tania iets 4 3 2 Blower OI aeaniee aeaa a aa 4 3 3 Storage neii aap a e eaea 4 4 Servicenet e a n aea E ONE 4 At Warranty Geena a aa EET 4 4 2 Technical description cccccccceceeeeeeeeeeeeees 4 4 3 TrOUDICSNOOTING cccecceeeeeeeeeeeeeeeeeneeeeeneenees 5 4 4 Refrigerant Char8ing ccccsccsseneesseneeseeneeeees 6 4 5 Blower Replacement ccccscceceeeececeeeeeeees 6 4 6 Compressor Capacitor Replacement 6 4 6A Checking Compressor Motor Circuits 6 4 6B Replacing a Burned Out Compressor 6 4 6C Replacing a Compressor Non Burn Out 7 4 7 Defrost Thermostat and TiMEel ccceeeeeeeeeer 7 4 8 Condensate PUMD ccccccccceeeececeeeeeeeaeseeees 7 ALO REAY sree en raea e ara A NEn EAEN 8 4 10 Time Delay cccscseceseserosecerosereronenerenenenenes 8 5 Wiring Diagram cccccccceeceececeeceeeeceseeceeeeaees 8 6 Service Parts List ccccccceeseeeeeeeeeeeeeeneeeeeneeeeee 9 Z Warramlyicsccs cece2 sestedecssecsceaiseoestatndeseehasetedteneerd 14 Serial No Purchase Date Dealer s Name Read the operation and maintenance instructions carefully before using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your Phoenix 300 dehumidifier Toll Free 1 800 533 7533 1 Specifications Part No 4022599 Power 12 amps 115 Vac Grounded Water 176 pints
11. day AHAM 80 F 60 RH Removal 304 pints day maximum 90 F 90 RH Blower 540 CFM without external ducting Refrigerant 2 Ibs 5 oz R 22 Charge Optional Duct 10 round outlet Connection Drain Hose 30 Vinyl Condensate Internal w 20 Lift Pump Operating 33 F to 105 F Temp Range Warranty Five Years First year 100 of Parts and Labor Second fifth year 100 of Parts of Sealed Refrigeration System Dimensions Cabinet Overall Shipping Width 24 29 30 Height 45 46 54 Depth 20 25 28 Weight 175 Lbs 210 Lbs 2 Operation 2 1 Transporting the Phoenix The Phoenix 300 must always be upright when transported by vehicle It may be tipped on to its handle and back for loading and moving by hand 2 2 Location AWARNING Note the following precautions when locating the Phoenix 300 It is designed to be used INDOORS ONLY If used in a wet area plug it into a GROUND FAULT INTERRUPTER DO NOT use the Phoenix 300 as a bench or table It must always be used in the upright position The air inlet on top and the side outlet must be at least 1 foot from walls and other obstructions to air flow If the humid area is very large dehumidification can be improved by adding an outlet duct to circulate air to stagnant areas see Sec 2 5 www thermastor com sales thermastor com 2 3 Electrical Requirements The Phoenix 300 can be plugged into a grounded 15 Amp circuit At 80 F 60 RH i
12. e installation of liquid and suction line filter driers will probably clean up the system If sludge is evident in the discharge line it will likely be found in the suction line this indicates the compressor burned out will running Sludge and acid have been pumped throughout the system Several changes of the liquid and suction filter driers will probably be necessary to cleanse the system 5 Correct the system fault that caused the burn out Consult the factory for advice 6 Install the replacement compressor with a new capacitor and an oversized liquid line filter In a running burn out install an oversized suction line filter drier between the accumulator and compressor Thoroughly flush the accumulator with refrigerant to remove all trapped sludge and to prevent the oil hole from becoming plugged A standing burn out does not require a suction line filter drier 7 Evacuate the system with a good vacuum pump and accurate vacuum gauge Leave the pump on the system for at least an hour 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plugged Replace the suction filter drier if pressure drop occurs If a severe Toll Free 1 800 533 7533 running burn out has occurred several filter driers may have to be replaced to remove all of the acid and moisture NOTE NEVER use the compressor to evacuate the system or any part of it 4 6C Repl
13. en 2 out from the center all the way around the dial except for the section now with 6 pegs out in a row see Fig 1 www thermastor com sales thermastor com 5 Replace the cover Change the timer pegs back to the original pattern for use above 50 F Above 50 F Below 50 F Figure 1 Defrost Control Timer 2 11 Low Pressure Control If the low side refrigerant pressure drops to 15 PSIG the low pressure control opens and shuts off the compressor and blower It is an automatically reset control Its primary function is to prevent damage to the compressor if a leak develops in the refrigeration system It may also open if the unit is A used in a cool area below 50 F and the defrost timer is not adjusted see Sec 2 10 or B stored where it is below 40 F and then started Under these conditions the unit will restart within several minutes Until the unit warms up it may cycle several times 3 Maintenance 3 1 Air Filter The Phoenix 300 is equipped with MERV 8 pleated fabric air filter that must be checked regularly Operating the unit with a dirty filter will reduce the dehumidifier s capacity and efficiency and may cause the compressor to cycle off and on unnecessarily on the defrost control Two optional filters are available A a 2 pleated filter that has the same efficiency as the 4 standard filter but less surface area This filter would need to be changed more often than the 2 versi
14. esulting high temperature arc causes a portion of the refrigerant oil mixture to break down into carbonaceous sludge a very corrosive acid www thermastor com sales thermastor com and water These contaminants must be carefully removed otherwise even small residues will attack replacement compressor motors and cause failures The following procedure is effective only if the system is monitored after replacing the compressor to insure that the clean up was complete 1 This procedure assumes that the previously listed compressor motor circuit tests revealed a shorted or open winding If so cautiously smell the refrigerant from the compressor service port for the acid odor of a burn out AWARNING WARNING The gas could be toxic and highly acidic If no acid odor is present skip down to the section on changing a non burn out compressor 2 Remove and properly dispose of the system charge DO NOT vent the refrigerant or allow it to contact your eyes or skin 3 Remove the burned out compressor Use rubber gloves if there is any possibility of coming in contact with the oil or sludge 4 To facilitate subsequent steps determine the type of burn out that occurred If the discharge line shows no evidence of sludge and the suction line is also clean or perhaps has some light carbon deposits the burn out occurred while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A singl
15. fective time delay Sec 4 10 No dehumidification Blower runs but compressor does not Pump fail light not lit 1 Bad connection in compressor circuit Fig 3 Defective compressor capacitor Sec 4 6A Defective compressor overload Sec 4 6A Defective compressor Sec 4 6 Defective relay Sec 4 9 Defective time delay Sec 4 10 DARON No dehumidification Pump Fail Light lit Blower runs but not compressor 1 Bad connection in pump circuit Fig 3 2 Pump float switch or safety switch defective Sec 4 8 3 Pump motor defective Sec 4 8 Blower does not run Compressor runs briefly but cycles on and off 1 Loose connection in blower circuit Fig 3 2 Obstruction prevents impeller rotation 3 Defective blower Sec 4 5 Unit removes some water but not as much as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 2 10 and 4 7 Air filter dirty Sec 3 1 5 Defrost timer incorrectly set for conditions Sec 2 10 and 4 7 6 Defective defrost thermostat Sec 4 7 7 Low refrigerant charge Sec 4 4 8 Air leak such as loose cover 9 Defective compressor Sec 4 6 10 Restrictive exhaust ducting Sec 2 5 gt Unit runs but does not pump water 1 Hose kinked or plugged 2 Pump check valve plugged Sec 4 8 3 Bad connection in pump circuit Fig 3 4 H
16. he collar clockwise It may be quickly removed to transport the unit more easily 2 6 Power Switch The power switch on left side of hour meter lights up when the unit is turned on The unit will continue to run in all conditions until the switch is turned off there is no dehumidistat 2 7 Pump Purge Switch This switch on right side of hour meter minimizes the water left in the condensate pump reservoir for moving or storage Pressing and holding the pump purge switch will cause the condensate pump to run Hold the switch in until the flow from the condensate hose stops Toll Free 1 800 533 7533 2 8 Pump Fail Light If the condensate pump fails water draining into the pump reservoir will fill above its normal level A safety float switch will then turn on the pump fail light located next to the pump purge switch and stop the compressor This prevents water from overflowing and wetting the floor The safety switch will not allow the compressor to restart until water has been removed from the pump reservoir 2 9 Hour Meter The digital hour meter measures the cumulative time that the unit is turned on to tenths of an hour It stores its total when the unit is unplugged the previous total will be displayed when the unit is next turned on It resets to zero after 99 999 9 hours of operation 2 10 Defrost Control Adjustment When the Phoenix 300 is used in a cool area frost will form on the cooling coil as it dehumidifies
17. ional 4023079 1 Coupling Body Quick Connect 38 Tube 4023080 1 Coupling Insert Quick Connect 38 Tube EE my uy uy uy uy uy uy uy uy uy IN IN IN IN IN IN IN IN IN TN VAMM NE AE AE AE MT www thermastor com sales thermastor com Specifications subject to change without notice This page intentionally left blank Toll Free 1 800 533 7533 10 www thermastor com sales thermastor com Phoenix 300 Dehumidifier Limited Warranty Warrantor Therma Stor LLC PO Box 8680 Madison WI 53708 Telephone 1 800 533 7533 Who Is Covered This warranty extends only to the original end user of the Phoenix 300 dehumidifier and may not be assigned or transferred First Year Warranty Therma Stor LLC warrants that for one 1 year the Phoenix 300 dehumidifier will operate free from any defects in materials and workmanship or Therma Stor LLC will at its option repair or replace the defective part s free of any charge Second Through Fifth Year Warranty Therma Stor LLC further warrants that for a period of five 5 years the condenser evaporator and compressor of the Phoenix 300 dehumidifier will operate free of any defects in material or workmanship or Therma Stor LLC at its option will
18. nd S No continuity indicates an open start winding the compressor must be replaced 5 Compressor terminals C and R No continuity indicates an open run winding the compressor must be replaced 6 Compressor terminal C and overload terminal 1 No continuity indicates a defective overload lead 7 Overload terminals 1 and 3 If there is no continuity the overload may be tripped wait 10 minutes and try again If there is still no continuity it is defective and must be replaced 8 Compressor terminal C and compressor case Continuity indicates a grounded motor the compressor must be replaced 9 Disconnect the wires from the capacitor Set the ohmmeter to the Rx1 scale the capacitor is shorted and must be replaced if continuity exists across its terminals If there is no needle movement with the meter set on the Rx100000 scale the capacitor is open and must be replaced 10 Reconnect the wires to the compressor and capacitor plug in and turn on the unit If the compressor fails to start replace the run capacitor 11 If the unit still does not start adding a hard start kit will provide greater starting torque If this does not work the compressor has an internal mechanical defect and must be replaced 4 6B Replacing a Burned Out Compressor The refrigerant and oil mixture in a compressor is chemically very stable under normal operating conditions However when an electrical short occurs in the compressor motor the r
19. on B a 95 efficient 4 filter that acts as an air scrubber to catch mold and mildew spores The filter can generally be vacuumed clean several times before needing replacement Replacement filters can be ordered from the factory or purchased locally if available DO NOT operate the unit without the filter or with a less effective filter as the heat exchange coils inside the unit could become clogged and require disassembly to clean 3 2 Blower Oiling The blower motor is lubricated for life from the factory and does not require oiling by the owner Toll Free 1 800 533 7533 3 3 Storage There are two issues to consider when the Phoenix 300 is stored between uses and both pertain to the water trapped in the unit damage caused by freezing and biological growth The effect of the trapped water can be greatly reduced if precautions are taken to remove as much as possible before storage 1 Use the pump purge switch see Sec 2 7 and Fig 3 to reduce the water level in the reservoir 2 Stretch the hose flat to drain it completely If the unit will not be exposed to freezing temperatures an alternative way to reduce biological growth is to flush the unit with a bio fungicide that is approved for use with copper aluminum and polyethylene To flush 1 Run the hose to a drain 2 Plug in the unit but do not turn it on 3 Remove the air filter Slowly pour a quart of the chemical through the top grille so that it drains into
20. ose disconnected internally Unit pumps water automatically but not when purge switch is pushed 1 Bad connection in purge switch circuit Fig 3 2 Defective purge switch Sec 2 7 www thermastor com sales thermastor com Evaporator coil frosted continuously low dehumidifying capacity 1 Defrost thermostat loose or defective Sec 2 10 and 4 7 2 Defrost timer incorrectly set or defective Sec 2 10 and 4 7 2 Low refrigerant charge Sec 4 4 3 Dirty air filter or air flow restricted Sec 3 1 Compressor runs with power switch OFF 1 Defective relay Sec 4 10 2 Defective power switch Sec 2 6 4 4 Refrigerant Charging If the refrigerant charge is lost a new charge must be accurately weighed in If any of the old charge is left in the system it must be removed before weighing in the new charge Refer to the unit nameplate for the correct charge weight and refrigerant type 4 5 Blower Replacement The centrifugal blower has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1 Unplug the power cord Remove the cabinet front 6 screws Disconnect the blower leads Pull the oil tubes out of the motor Tip the unit on its back From the bottom remove the 2 screws that fasten the blower housing to the base Remove the four screws holding the blower outlet flange to the cabinet end 7 Remove the blower Use care to avoid hooking wiring
21. s Phoenix 300 High Capacity Dehumidifier nA Therma Stor uc sae Part number TS 218 Driven by performance Powered by design PO Box 8680 Madison WI 53708 Owner s Manual Phoenix 300 Installation Operation and Service Instructions Read and Save These Instructions The Phoenix 300 Dehumidifier is designed to maximize the water removal capacity from a single 110V 15 amp circuit The multiple ducting options on the Phoenix 300 allows for ducting both the intake air and the filtered and dehumidified supply air This makes it possible to easily combine the Phoenix 300 with a HEPA air scrubber air conditioner or desiccant dehumidifier Phoenix dehumidifiers feature significant air filtration Even the standard 57 MERV 8 filters remove over 90 of seven micron particles the size of a human red blood cell This filtration dramatically improves the air quality in the areas being dried and assures continued optimal performance of the refrigeration system The Phoenix 300 High Capacity Dehumidifier High capacity Up to 38 gallons per day High energy efficiency Plugs into a grounded 115V outlet Pleated media filter Built in air filter reduces dust and mold Twist on duct collar Direct the drying power where you need it Optional high efficiency filter Removes 95 of one micron particles Reservoir pump system Strong and dependable 20 ft of lift Pump purge switch Drains reservoir no spills
22. t draws 11 e Amps Due to the high percentage of a 15 Amp circuit s capacity that the unit uses the circuit should be dedicated to running it only Amp draw decreases at lower loads and increases at higher loads At extremely high loads a 20 Amp circuit may be required The unit briefly draws more amps to start if it has been stored in a cold area This may cause a 15 Amp circuit breaker to trip A 20 Amp circuit is recommended in such situations Some models have a time delay to delay the compressor start about 2 minutes after the power switch is turned on This reduces the unit s starting amp draw by starting the blower and compressor at different times If an extension cord is required it must have a minimum of 12 gauge conductors if 25 feet long or less and 10 gauge conductors if greater than 25 feet long 2 4 Condensate Removal The Phoenix 300 is equipped with an internal condensate pump to remove the water that is condensed during dehumidification This allows the condensate to be pumped 30 with the attached hose If the condensate must be pumped more than 20 feet above the unit a second pump must be added to relay the condensate 2 5 Ducting A detachable 10 round exhaust collar is supplied that will allow a 10 round flexible duct to be attached to the Phoenix 300 outlet The duct and collar may be quickly attached to the Phoenix 300 by sliding the 4 collar tabs into the slots around the blower outlet and rotating t
23. tem of Phoenix The evaporator operates in a flooded condition which means that all the evaporator tubes contain liquid refrigerant during normal operation A flooded evaporator should maintain constant pressure and temperature across the entire coil from inlet to outlet The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil The accumulator prevents any liquid refrigerant from reaching the compressor The compressor evacuates the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature to repeat the process 4 3 Troubleshooting No dehumidification Neither blower or compressor run Power switch does not light when ON 1 Unit unplugged or no power to outlet 2 Power switch defective Sec 2 6 3 Loose connection in internal wiring Fig 3 No dehumidification Neither blower or compressor run Power switch ON and lit 1 Low pressure control open Sec 2 11 2 Power switch defective Sec 2 6 3 Loose connection in internal wiring Fig 3 Some dehumidification blower runs continuously but compressor only runs sporadically 1 Unit is in defrost cycle Sec 2 10 and 4 7 2 Defrost thermostat defective or loose Sec 2 10 and 4 7 3 Loose connection in compressor circuit see Fig 3 4 Defective compressor overload Sec 4 6A Toll Free 1 800 533 7533 5 Defective compressor Sec 4 6 6 Defective relay Sec 4 9 7 De
24. the white plastic slots 4 Hold in the pump purge switch to reduce the water level in the reservoir 4 Service CAUTION CAUTION Servicing the Phoenix 300 with its high pressure refrigerant system and high voltage circuitry presents a health hazard that could result in death serious bodily injury and or property damage Only qualified service people should service this unit 4 1 Warranty A warranty certificate has been enclosed with this unit read it before any repair is initiated If a warranty repair is required call the factory first at 1 800 533 7533 for warranty claim authorization and technical assistance 4 2 Technical Description The Phoenix 300 uses a refrigeration system similar to an air conditioner s to remove heat and moisture from incoming air and to add heat to the air that is discharged see Fig 2 Hot high pressure refrigerant gas is routed from the compressor to the condenser coil See Figure 2 The refrigerant is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit The refrigerant liquid then passes through a filter drier and capillary tubing which cause the refrigerant pressure and temperature to drop It next enters the evaporator www thermastor com sales thermastor com coil where it absorbs heat from the incoming air and evaporates EVAPORATOR FILTER DRIER 7 COMPRESSOR CONDENSER Figure 2 Refrigeration sys