Home

Superior SSDVPF-CNM-B User's Manual

image

Contents

1. v 0 EN SISTER Slo 2 e e volo 2 o 0 o e e 2o sts lt as 7 227 feos s Eras o 9 pes Pw pes 71 Po Esos ms 9 1 Fastest S mss vs pos ofa 5 za EE ES E 5 5 EN o 0 KS EA EA EN EN 7 EM ES CIE 8 KE EN EN KE o EE e 0 7 Eee pea 0 10 w EN o w r w g w N D De aes sis 0 3525 3 9 oo BENI ass oars SV4 5L24 22 1 2 SV4 5L36 34 1 2 SV4 5L48 46 1 2 Table 8 Vertical offset Installation Analyze the vent routing and determine the number of vent sections and elbows required Refer to Vertical Vent Figures and Tables on Pages 17 and 18 to select the type of vertical installation desired Refer to the Vent Section Length Charts on Page 14 for an aid in selecting ventlength combinations Elbows are available in 45 and 90 configurations Refer to Figure 23 on Page 16tor the SV4 5E45 and SV4 5E90 elbow dimensional specifications Where required a telescopic vent section SV4 5LA may be used to provide the installer with an option in installing in tight and confined spaces or where the vent run made up of fixed length pieces develops a joint in a undesirable location or will not build up to the required length The SV4 5LA Telescopic Vent Section has an
2. 270 105 d 2 y Gas Line Center of gas line is 3 in 76 mm up from floor cu ft This dimension can be reduced to 41 inches 1041 mm This results in 0 in 0 mm clearance between framing and unit framing spacers The 41 1 2 in dimension permits easier fireplace installation if unit is installed after framing is erected H3336 SSDVPF CNE 270165 52W x 27D x This dimension based on 5 8 drywall For 1 2 drywall use 25 1 2 648 mm The finished dimension should be 26 1 2 673 mm 44 1 2H 36 2 See also Side Vent Seal Cap note below cu ft ertical Venting Through the Ceiling EFFICIENCIES Frame ceiling opening Use a plumb line from the ceiling above the appliance to locate center of the vertical run Cut and or frame an opening 10 1 2 x 10 1 2 267 mm x 267 mm inside dimensions about this center mark see Figure 19 on Page 15 61 LP 72 NG Steady State 73 AP 68 N FLUE 12 305 wu 68 AP Top or Side DETAIL OF Canada FINISH WALL BRACKET Look for the EnerGuide 40 1 8 Gas Fireplace Energy 1019 Efficiency Rating in this brochure Based on CSA P 4 1 02 Top View 24 2 Le 12 43 5 8 n 63 5 305 4 102 37 940 CX Provide additional FLUE space for Side Vent Seal Cap Top or Side if installing against a solid ELECTRICAL INLETS Y GAS INLET F VW 3 76 A 6 7 8 N 16 Top and Side 58 NG FI
3. However if installed on combustible materials such as carpeting vinyl tile etc a metal or wood barrier covering the entire bottom surface must be used VENT TERMINATION CLEARANCES These instructions should be used as a guideline and do not supersede local codes in any way Install venting according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Vertical Vent Termination Clearances Terminate multiple vent terminations according to the installation codes listed above Also see Figure 4A Terminate single vent caps relative to building components according to Figure 4B 12 gt 305mm Figure 4A Multiple Terminations Vertical Vent Termination Clearances TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS Horizontal Overhang Vertical 2 FT 2 FT MIN Wall MIN Lowest Discharge Vent Opening Termination H Storm Collar X 12 EN Roof Pitch is X 12 Concentric Vent Pipe Flashing m 1 inch 25 4 mm Minimum Clearance to Combustibles H MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING OF VENT The vent air intake termination clearances above the high side of an angled roof is as shown in the following chart Figure 4B Horizontal Vent Termination Clearances The horizontal vent termination must have a minimum of 6 152 mm clearance
4. In selecting the location the aesthetic and functional use of the appliance are primary concerns However vent system routing to the exterior and access to the fuel supply are also important Due to high temperatures the appliance should be located out of traffic and away from furniture and draperies Figure 3 Enraison des temp ratures lev es l appareil devrait tre install dans un endroit o il y a peu de circulation et loin du mobilier et des tentures Figure 3 The location should also be free of electrical plumbing or other heating air conditioning ducting These direct vent appliances are uniquely suited for installations requiring a utility shelf positioned directly above the fireplace Utility shelves like these are commonly used for locat ing television sets and decorative plants NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Be aware that this is a heat producing ap pliance Objects placed above the unit are exposed to elevated temperatures Do not insulate the space between the ap pliance and the area above it see Figure 8 on Page 6 The minimum height from the base of the appli ance to the underside of combustible materials used to construct a utility shelf in this fashion is shown in Figure 8 on Page 8 The appliance should be mounted on a fully supported base extending the full width and depth of the unit The appliance may be located on or near conventional construction materials
5. accordingly All of these appliances must have hoods If flame appears weak or sooty adjust Stalled prior to operating see Figure 59 Remain Clearot 8 the air shutter incrementally to a more Combustible Combustible 16 open position until the proper flame Slide the hood into the slots on the lower edge Finished Materials appearance is achieved of the cabinet top see Figure 59 Wall Materials lf flame stays lowered blue adjust the 25 mm air shutter incrementally to a more FINISHING REQUIREMENTS Top Spacers closed position until the proper flame Wall Details appearance is achieved Drywall Leave the control knob off pilot on in the Complete finished interior wall To install the Bracket Spacer ON position and the burner OFF ON switch appliance facing flush with the finished wall OFF and remote switches if applicable position framework to accommodate the thick A 5 When satisfied that the burner flame ap ini Combustible pearance is normal close the lower control er material may Top of Appliance compartment door then proceed to finish 4 Louvers the installation See Page 5 for Cold Climate Insula of Door Frame tion and Page 8 for Clearances i Hood must be installed as shown Figure 59 Combustible Wall Framing 31 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 32 Step 12 ATTACHING SAFETY IN OPERATION WARNINGS It is the installers respon
6. inches mm Termination Kit Only 6 to 9 1 4 152 to 235 Termination Kitand 6 In Vent Section SV4 5L6 10 3 4 to 14 273 to 356 5 Termination Kit and 12 in Vent Section SV4 5L12 16 3 4 to 20 426 to 508 Termination Kit and Tele scopic Section SV4 5L12 11 8 4 to 20 299 to 508 Note See Figure 34 showing wall thickness range when using SV4 5HT 2 termination kit only Table 9 HORIZONTAL VENT FIGURES TABLES Notes e Secure Vent components rigid vent pipe and terminal are shown in the Figures Secure Flex components flexible vent pipe and terminal may also be used Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting Figures for 90 elbows must be followed if 45 degree elbows are used SV4 5VF Secure Vent SF4 5VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceil ing SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible wall It is very important that the horizontal inclined run be maintained in a straight no dips and recommended to be in a slightly elevated plane in a direction away from the fireplace of 1 4 rise per foot 20 mm per meter which is ideal though rise per foot run ratios that are smaller are acceptable all the way down to at or near level The tables show a 1 V to 5 H ratio up to a maximum hor
7. 6x9 az V H 40 feet 12 2 m Max Wall Firestop H H 20 ft 6 096 m Max Spacer SV4 5HF Owhen using Secure Flex use Firestop e Spacer SF4 5VF Example 20 feet of H horizontal When using Secure Flex use Firestop vent run is needed then 4 feet minimum of Spacer SF4 5HF V vertical vent will be required Ceiling Firestop Note See Table 9 as an aid in venting Spacer SV4 5VF This table shows a 1 V to 5 H ratio Forevery component selection fora particular range 1 foot of V vertical you are allowed 5 feet of exterior wall thicknesses of H H horizontal run up to a maximum horizontal run of 20 feet Square termination SV4 5HT 2 shown An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical Figure 38 Top Vent TWO 90 DEGREE ELBOWS component in the system See Figure 36 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE HORIZONTAL VENT FIGURES TABLES CONTINUED when using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses iam WWumm E ee ue mer s amo asm aam w ew a ar aem ris asm sae s ano m sm e eae Loan V H H4 40 feet 12 2 Max H 8 feet 2 438 meters
8. Max H Hy Ho 20 feet 6 096 meters Max Example If 20 feet total H H H horizontal vent run is needed then 4 feet minimum Square termination SV4 5HT 2 shown OF V vertical vent wil be requiread This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 Figure 39 Side Vent THREE 90 DEGREE ELBOWS feet of horizontal run up a maximum total H H H horizontal run of 20 feet Square termination SV4 5HT 2 shown Table J H H Maximum feet meter feet meten D Ls os me s ums aic 2 oso Cw usm s osu Lm Low amp zw H H 20 feet 6 096 m Max atii V Vqe H H 40 ft 12 192 Max SV4 5HF Example f20 feet total H H horizontal Owhen using Secure Flex vent run is needed then 4 feet minimum use Firestop Spacer of V vertical vent will be required SF4 5VF This table shows a 1 V to 5 H ratio For When using Secure Flex every 1 footof V vertical youare allowed 5 feet of H horizontal run up to a n Spacer maximum horizontal run of 20 feet YL 5 O Wall Firestop Anelbow is acceptable as 1 foot of vertical Note See Table 9 as an aid Spacer SV4 5HF d rise except where an elbow is the only in venting component selec vertical component in the system See tion for a particular range of vu pend Figure 36 exterior wall thicknesses pacer
9. SV4 5VF Figure 40 Top Vent THREE 90 DEGREE ELBOWS NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 24 VERTICAL OR HORIZONTAL VENTING USING SECURE FLEX KITS AND COMPONENTS Secure Flex venting kits and components may be used in any venting application in place of rigid Secure Vent SV4 5 direct vent components All restrictions clearances and allowances that pertain to the rigid piping apply to the flexible venting Secure Flex kits may not be modified also under no circumstances may separate sections of flex pipe be joined together Using adapter SV4 5RF Secure Flex kits may be added to the end of a vent run made up of rigid Secure Vent SV4 5 vent sections provided that doing so does not violate any of the venting length height routing horizontal to vertical ratio requirements or clearance considerations detailed in this manual Secure Flex kits come with an adapter that can be fitted to the inclined channel end of the last Secure Vent SV4 5 vent section in a rigid system in the exact same fashion as any other Secure Vent section Align the dimpled end of the adapter over the previously installed section or appliance collar adjusting the radial alignment until the four locking dimples of the adapter are aligned with the inlets of the four incline channels of the last vent section or collar Push on the adapter until it fully engages then twist the adapter clockwise running the dimples
10. When using Secure Flex use Firestop Spacer SF4 5HF e Example 1 20 feet total H H horizontal vent run is needed then 4 feet minimum of V verlical vent will be required y aie This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H H horizontal run up to a maximum total horizontal run of 20 feet Figure 30 Side Vent THREE ELBOWS Table D H H Maximum meter feet meter ie 1 524 1 524 3 048 4 572 0 914 6 096 1 219 H H 20 feet 6 096 m Max V V H H 40 ft 12 192 m Max Example If 20 feet total H H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required 0 305 Ceiling V Firestop Spacer 0 610 SV4 5VF This table shows a 1 V to 5 H ratio For every 1 foot of V vertical you are allowed 5 feet of H H horizontal run up to a maximum total horizontal run of 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 36 When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Figure 31 Top Vent THREE ELBOWS NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Firestop Spacer Wall Firestop Spacer SV4 5HF Ceiling Firestop BY Spacer SV4 5VF wall Firestop Spacer SV4 5HF ildi Support Bui
11. and 3 76 mm at the top 1 25 mm at sides and 1 25 mm at the bottom for all horizontal inclined runs H Frame roof opening Identify location for vent at the roof Cut and or frame opening per Roof Framing Chart and Figure 24 Framing Dimensions for Roof Inches millimeters 0 12 10 1 2 in 10 1 2 in 267 mm 267 mm 6 12 10 12 in 12 in 267 mm 305 mm 12 12 10 1 2 in 17 3 4 in 267 mm 451 mm Figure 24 Roof Framing 1 Install the roof flashing Extend the vent sections through the roof structure Install the roof flashing over the vent section and position such that the vent column rises vertically use carpenters level see Figure 25 Nail along perimeter to secure flashing or adjust roofing to overlap the flashing edges at top and sides only and trim where necessary Seal the top and both sides of the flashing with waterproof caulking J Install the storm collar Install the storm collar supplied with the flashing over the vent flashing joint See Figure 25 Loosenthe storm collar screw Slide collar down until it meets the top of the flashing Tighten the adjusting screw Apply non combustible caulking or mastic around the circumference of the joint to provide a water tight seal NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Figure 25 K Install the vertical termination The final Step involves installation of the SV4 5CGV 1 Vertical Termination Extend the vent sect
12. to do so could cause irrepa rable damage to the appliance and prove hazardous to your safety If logs are not installed according to the log instal lation instructions flame impingement and improper combustion could occur and resultin soot and or excessive production of carbon monoxide CO a colorless odorless toxic gas 29 LOG AND VOLCANIC STONE INSTALLATION PROCEDURE The log set foam package is located in the firebox and the bags of decorative volcanic stone and the glowing embers rockwool are located in the control compartment Refer to the follow ing information and Figures 52 through 55 for detailed placement instructions Install the decorative volcanic stone and glowing embers rockwool Spread the decorative volcanic stone on the simulated brick floor of the firebox around the burners to simulate ashes Maintain a 1 2 inch 13 mm gap between the bottom of the horizontal grate section and the top of the pile of decorative volcanic stone Place a few quarter sized pieces of the glowing ember material on the pan burner in front of the burned out area on both sides of the log set The glowing embers may touch one another but should not overlap each other Install the unitized log set a The bottom of the log set is notched to ac commodate the pilot b Placethe log setso thatthe fourinner notches on the underside of the log set fit over the four risers located on the burner ends See Figure 53
13. 27 Removing Control Compartment Door Locate the two 2 latches at the top of the control compartment To disengage the two latches from the bottom vee flange of the glass enclosure panel reach for the handles located towards the back of the latches and pull the handles down toward the front of the appliance Swing the bottom of the door out and raise it slightly to lift the top flange of the door frame away from the appliance Installing Glass Enclosure Panels see Figure 56 1 N A Visually inspectthe gasket onthe backside ofthe glass panel The gasket surface must be clean free of irregularities and seated firmly Position the glass enclosure panel in front of the firebox opening at a 45 degree angle and engage the top flange over the lip at the top of the firebox opening See Figure 56 Swing the glass enclosure panel down and back Ensure the gasket seats evenly as the panel draws shut Engage the Vee flange at the bottom of the panel with the latches and close the latches to secure the panel Reinstall top louver assembly and control compartment door see installation instruc tions on Page 27 Reinstalling Control Compartment Door Bottom Vee flange Glass Door Firebox Floor Glass Door Latch Note When installing the glass door ensure the Spacing on both sides are equal Figure 56 INSTALLING OR REMOVING GLASS DOOR NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE
14. Kits the control compartment before See Figure 46 for wiring operating the appliance TP An electrical receptacle is provided for the MULA installation of the FBK 100 FBK 200 and FBK away from hotsurfaces and sharp 250 forced air blower kits Electrical power edges must be connected to this receptacle in order Do not connect the optional wall to operate these blowers Install the blower kits according to the installation instructions switch to a 120 Volt AC power provided with the kits supply Plug blower into this i Ground Green receptacle CD Neutral White 120 VAC Black d r pa 4 ___ Junction Box Ground lt Wall mounted __ ON OFF Blower Ta Switch or Variable Tab Intact Broken Speed Control Switch R d 1 Green foe C J BOX WIRING FOR Ground i WALL SWITCH Side of Side of Receptacle Receptacle BLOWER CONTROL View A J Box Wiring when using unit e Relay Module C W FBK 250 only Plug blower into J Box receptacle for FBK 100 or FBK 200 relay module application See View A for J Box wiring Optional Blower K OFF ON Switch Pilot Burner Integral with Assembly Gas Valve Leave the OFF ON switch which is integral with the gas valve in the ON position Optional Control Switches Wall Switch Wall Thermostat or Remote Control Receiver Note
15. REQUIREMENTS NOTE Local Codes Or Regulations May Require Different Clearances See D in the Text Below i i NOTE Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service 18 EJ Horizontal w Termination Ventilated Soffit Inside Corner TET Detail D ex 12 in Canada SS SERRE EEE AEE TE PM LATE EEL t 4 LEE PN Air Supply Inlet W Vent Termination gt Area where Termination is not Permitted u Minimum MinimumClearances Canadianimstallation Installation USinstallation Installation Clearance above grade veranda porch deck 30 cm 30 or balcony Clearance to window or door that may be 15 2 cm for appliances lt 10 000 BTU hr 3kW 6 in 15 2 cm for appliances lt 10 000 BTU hr 3kW dee 12 in 30 cm for appliances gt 10 000 BTU hr a lt Qin a cm for appliances gt 10 000 BTU hr s and 100 000 BTU hr 30kW 36 inches 91 cm for appliances 50 000 BTU hr 15kW 12 inches 30 cm for appliances gt 100 000 BTU hr 30kW 50 000 BTU hr 15kW C Clearance to permanently closed window 12 inches 305 mm recommended to prevent window 9 inches 229 mm recommended to prevent window condensation condensation D Vertical clearance to ventilated soffit located 1
16. SV4 5HGS Termination Guard for Square Termination Deluxe 1 pack for square termination 14 H5820 SV4 5HTSK Termination Shroud Guard for Horizontal Square Termination 1 pack NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Ref 750 109M Ref 750 246M 2 2 005 4 oy E 552595 LOA 27 BE pe D 33 cat Wo sumus SFA SFA SFA 56L74 SFVT30 Vertical Termination for flex flat to 6 12 with flex adapter section of rigid vent roof support collar assembly roof flashing and storm collar 56L75 SFVT45 Vertical Termination for flex 6 12 to 12 12 with flex adapter section of rigid vent roof support collar assembly roof flashing and storm collar 20 60L10 SF 18 18 ft 5 49 m compressed flex 20 98K03 SF 12 12 ft 3 66 m compressed flex 22 10K81 SFMP 22 89L40 SFMP 12 Mill Pac Black High Temperature Sealant Bulk 12 pack 23 91L66 SF GC4 6 Gear Clamp 4 5 in 114 mm for flex 6 pieces 23 91L67 SF GC7 6 Gear Clamp 7 5 in 190 5 mm for flex 6 pieces 25 H1988 CTSA 33 Chase Top Shroud Kit Arch Top 3X3 26 H1985 CTSO 33 Chase Top Shroud Kit Open Top 3X3 26 H1987 CTSO 44 Chase Top Shroud Kit Open Top 4 X 4 26 H1986 CTSO 46 Chase Top Shroud Kit Open Top 4X6 H2248 SF4 5HF Firestop Spacer Horizontal flex 3 1 1 spacing 10 Pack H2249 SF4 5VF Firestop Spacer Vertical 1 1 1 spacing 10 Pack All compressed flex ve
17. Step 10 BURNER ADJUSTMENTS Flame Appearance and sooting Proper flame appearance is a flame which is blue at the base and becomes yellowish orange in the body of the flame When the appliance is first lit the entire flame may be blue and will gradually turn yellowish orange during the first 15 minutes of operation After 15 minutes of operation if the flame is blue or if the flame is orange with evidence of sooting black tip the air shutter opening may need to be adjusted If the air shutter openings are closed too far sooting may develop Sooting is indicated by black puffs developing at the tips of very long orange flames Sooting results in black deposits forming on the logs appliance inside surfaces and on exterior surfaces adjacent to the vent termination Sooting is caused by incomplete combustion in the flames and lack of combustion air enter ing the air shutter opening To achieve a warm yellowish orange flame with an orange body that does not soot the shutter opening must be adjusted between these two extremes Air Shutter Adjustment Guidelines e e e e If there is smoke or soot present first check the log set positioning to ensure that the flames are not impinging on any of the logs If the log set is properly positioned and a sooting condition still exists then the air shutter opening should be increased The more offsets inthe vent system the larger the air shutter opening will need to be
18. This procedure is accomplished primarily by feel as the log set masks the burner risers as it is being installed c Asafinal check for correctlog set placement check that the four outer notches on the underside of the log set fit over the burner tines as indicated in Figure 53 Burner Grate Location Reference see Figures 54 and 55 Note If the burners have been removed for any reason rear burner must be installed before front burner See Figures 54 and 55 Glowing Embers Separate into Quarter Size separate Pieces Bag of Glowing Embers rockwool Figure 52 REFERENCE Firebox Accessories Parts Bag of Glowing Embers Bag of Decorative Volcanic Stone NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BURNER BRACKET A REAR BURNER PORTS OU o PILOT Le BURNER FRONT BURNER Note The burners are not identical Position them so that the circular burner ports run as shown Note especially the vertical run of ports relative to the pilot burner Bracket A on the rear burner will interfere with the pilot burner if an attempt is made to install the rear burner in the front burner s position Figure 54 NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER REAR BURNER Outer Log Notch Location Outer Log Notch Location Riser Inner Log E 25 Notch Location Riser Inner Log Notch Location Notch Location Pilot Assembly FIREBOX SUBFLOOR FRO
19. be applied as shown on Page 13 restrictor is taped to the enve lope 4 Hoods 2 for SSDVST models and 3 for SSDVPF models taped to the top of the fireplace 5 Carton Support must be removed from the control compartment prior to first burning 6 One plastic bag of glowing embers and a plastic bag of volcanic stone located in the control compartment INTRODUCTION The Millivolt appliances have a millivolt gas control valve with piezo ignition system If any optional accessories that will require electrical power are to be installed the electrical power must be provided at the time of appliance in stallation The Electronic appliances have an electronic intermittent pilot ignition system External electrical power is required to operate these appliances These vented gas fireplace heaters are sealed combustion air circulating gas fireplaces designed for residential applications Use Only These Approved Vent Components These fireplaces are designed tested and listed for operation and installation with the following 4 1 2 inner and 7 1 2 outer vent components only e Secure Vent Direct Vent System Compo nents manufactured by Security Chimneys International e Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter national and e Z FLEX Model GA Venting Systems listed to UL1777 and ULCS635 manufactured by Flexmaster Canada Limited These approved vent system components
20. can be adjusted by rotating the adjust ment lever from beneath the firebox floor Refer to Figure 57 Page 31 for the recommended minimum primary air opening setting NOTE Each model has two burners and 2 Orifices Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Model Nat Gas Propane Series drill size inches drill size inches 44 086 4 55 052 60J80 19152 SSDVST SSDVPF Table 10 Standard size installed at factory Standard size in LP conversion kit Part Cat Number BURNER POSITIONING BURNER ORIFICE NOTE INSTALL REAR BURNER FIRST THEN FRONT BURNER BRACKET A BURNER Figure 65 REAR BURNER PORTS Step 10 Reassemble the remaining compo nents by reversing the procedures outlined in the preceding steps Step 11 Attach the conversion label provided in the conversion kit to the rating plate on the appliance Step 12 Turn on gas supply and test for gas leaks See Test All Connections For Gas Leaks on Page 28 FRONT BURNER Note The burners are not identical Position them so Step 13 Attach manometer to the manifold that the circular burner ports run as shown Note side pressure test fitting and verify manifold especially the vertical run of ports relative to the pilot pressure reads 3 5 inches water column 0 87 burner Bracket A on the rear burner will interfere with kPa for natural gas and 10 0 inches water the pilot burner if an attempt is made to ins
21. compartment by removing the lower control compartment panel see Figure 49 The incoming gas line should be piped into the valve compartment and connected see Figures 47and 48 The millivolt control valve has a 3 8 10mm NPT thread inlet port The electronic control valve has a 1 2 13 mm NPT thread inlet port and is fitted with a 1 2 x 3 8 13 mmx 10mm NPT fitting Secure all joints tightly using appropriate tools and sealing compounds ensure propane resistant compounds are used in propane ap plications Itis recommended to seal around the gas line to prevent cold air leakage Gas line connection may be performed largely outside of the confines of the control compart ment and without having to enter the firebox behind the glass Proceed as follows Acquire the shut off valve and gas lex line and pull the assembly forward out of the compart ment Separate the shut off valve from the gas flex line Determine the length of pipe needed to route the gas line from the last fitting shown in Figure 14 on Page 12 to a point within the control compartment that will allow the shut off valve to be easily attached by hand to the gas flex line Using pipe dressing materials appropriate for the gas type securely affix the shut off valve to this determined pipe length at a convenient location outside of the appliance lower control compartment Gas Flex Line Connector Gas 3 9 1 2 x 3 8 Flare 1 Fitting Shut o
22. element Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections see Figure 20 on Page 15 l Continue installation of horizontal inclined sections Continue with the installation of the straight vent sections in horizontal inclined run as described in Step E Install support straps every 5 ft 1 52 m along horizontal inclined vent runs using conventional plumber s tape See Figure 32 It is very important that the horizontal inclined run be maintained in a Straight no dips and recommended to be in a slightly elevated plane in a direction away from the fireplace of 1 4 rise per foot 20mm per meter which is ideal though rise per foot run ratios that are smaller are acceptable all the way down to at or near level Itis important to maintain the required clear ances to combustibles 1 25 mm at all sides for all vertical runs and 3 76 mm at the top 1 25 mm at sides and 1 25 mm at the bottom for all horizontal inclined runs Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary 19 20 J Assemble vent run to exterior wall If not previously measured locate the center of the vent at the exterior wall Prepare an opening as described in Step B Assemble the vent system to point where the terminus of the last section is located relative to the exterior surface to whi
23. l interrupteur ou le thermostat mural pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur la surface de la plaque de l interrupteur mural qui contr le le foyer Figure A ou du thermostat mural Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Si une t l commande est utilis e pour contr ler le foyer nettoyez la soigneusement pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur le boitier de la t l commande Figure C Choisissez la langue qui est principalement parl e dans la r sidence du propri faire En cas de doute collez l tiquette en anglais 3 Si vous ne trouvez pas les tiquettes veuillez appeler Lennox Hearth Products ou votre distribu teur Lennox Hearth Products local pour recevoir gratuitement des tiquettes suppl mentaires Etiquettes de remplacement n cat H8024 LENNOX HEARTH PRODUCTS 1 800 9 LENNOX Remarque Le texte anglais est rouge sur un support transparent Le texte francais et espagnol est blanc sur un support noir DIAGRAMMES DES TIQUETTES DE S CURIT AVERTISSEMENT Vitre et foyer EXTREMEMENT CHAUDS Risque de br lures graves Toujours tenir les enfants a l cart du foyer EE LENNOU Figure B WARNING COLOCACI N DE ADVERTENCIAS DE SEGURIDAD EN OPERACION Se requiere
24. les instructions du fabricant et conform ment la norme Manufactured Home Constructions and Safety Title 24 CFR Part 3200 aux Unis ou la norme Can CSA 7240 S rie MM Maisons mobiles au Canada This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used Cet appareil doit tre utilis uniquement avec le type de gaz indiqu sur la plaque signal tique Cet appareil ne peut tre converti d autres gaz sauf si une trousse de conversion est utilis e CAUTION Ensure that the cross mem bers are not cut or weakened during installation The structural integrity of the manufactured home floor wall and ceiling roof must be maintained CAUTION This appliance must be ground ed to the chassis of the manufactured home in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition or the Canadian Electrical Code CSA C22 1 latest edition LS ASS LC SSS SR gt Pak ROCK Se 9 uo ju Q Vertical Offset Venting Venting one end flush with wall W ME Vertical top vent A NS side vent Figure 3 Typical Locations LOCATION
25. que las etiquetas de instrucciones de seguridad incluidas con la chimenea se coloquen en el punto de operaci n y control de la misma Se debe colocar una etiqueta de instrucciones de seguridad en la placa del interruptor de pared desde el cual se enciendey se apaga la chimenea verla Figura A oenel termostato de pared verla Figura B y en eltransmisor de control remoto Figura si se usa Para completar correctamente la instalaci n de esta chimenea encuentre las etiquetas adhesivas multiling es incluidas con las instrucciones de cuidado y operaci n y haga lo siguiente 1 Identifique el interruptor o el termostato de pared quecontrolalachimenea verifique queelinterruptor opera la chimenea encendi ndola y apag ndola Limpie bien la placa del interruptor o el termostato de pared para quitar el polvo y aceite Pegue la etiquetaen la superficie dela placadelinterruptor que controla la chimenea Figura A en el termostato de pared Figura B Seleccione el idioma que mas se habla en la casa Si no sabe cual es use la etiqueta en ingl s 2 Si se usa un control remoto para controlar la chimenea encuentre el transmisor y limpielo bien para quitar el polvo y aceite Pegue la etiqueta en la superficie del transmisor Figura Seleccione el idioma que mas se habla en la casa Si no sabe Cu l es use la etiqueta en ingl s 3 Si no puede encontrar las etiquetas s rvase llamar a Lennox Hearth Products o al distribuidor de Lenno
26. the dimples down and along the incline channels until they seat at the end of the channels This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 20 on Page 15 F Install firestop spacer at ceiling When using Secure Vent use SV4 5VF firestop spacer at ceiling joists when using Secure Flex use SF4 5VF firestop spacer If there is living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed opening and secure the firestop spacer with 8d nails or other appro priate fasteners at each corner Remember to maintain 1 25 mm clearance to combustibles framing members and attic or ceiling insulation when running vertical chimney sections Attic insulation shield H3907 may be used to obtain the required clearances indicated here See installation accessories Tables on Pages 33 and 34 G Support the vertical run sections See Step E on Page 15 H Change vent direction At transition from or to a horizontal inclined run install the SV4 5E45 and SV4 5E90 elbows in the same manner as the straight vent sections The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direc tion of the next vent run
27. voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par un installateur ou un service d entretien qualifi ou par le fournisseur de gaz TABLE OF CONTENTS Packaging sss Page Introduction Page General Information Page Requirements for the Commonwealth of Massachusetts Page New York City Approval Page Cold Climate Insulation Page Manufactured Home Requirements Page LOCATION eme Page Vent Termination Clearances Page Appliance and Vent Clearances Page Detailed Installation Steps Page Typical Installation Sequence Page Step 1 Page Fireplace and Framing Specifications Page Step 2 Routing Gas Line Page Step 3 Install the Vent System Page Vent Restrictor Installation Page Vertical Termination Systems Page Vent Section Length Chart Page Vertical Vent Figures and Tables Page Horizontal Termination System Page Horizontal Vent Figures and Tables Page Venting Using Flexible Vent Pipe Page Step 4 Field Wiring Page Step 5 Optional Blower Kit Wiring Page Step 6 Connecting G
28. 5 SUPERIOR P N 700031M Rev 01 2011 This manual is one of a set of two supporting this product Refer to P N 725035M for Care and Operation Instructions Ce manuel est disponible en francais simplement en faire la demande Num ro de la pi ce 700031CF INSTALLER Leave this manual with the appliance CONSOMMATEUR Conservez cette notice pour consultation ult rieure CONSUMER Retain this manual for future reference INSTALLATEUR Laissez cette notice avec l appareil INSTALLATION INSTRUCTIONS SSDV Direct Vent Gas Fireplaces MODELS SSDVST CNM B SSDVPF CNM B SSDVST CNE B MILLIVOLT ELECTRONIC SSDVPF CNE B Tested amp Portland Listed By Oregon USA US OMNI Test Laboratories Inc OTL Report No 116 F 32 5 This appliance may be installed in an aftermarket permanently located manufactured home USA only or mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gases unless a certified kit is used WARNING AVERTISSEMENT AVISO HOT GLASS WILL CAUSE e UNE SURFACE VITREE CHAUDE EL VIDRIO CALIENTE BURNS PEUT CAUSER DES BRULURES CAUSARA QUEMADURAS DO NOT TOUCH GLASS LAISSER REFROIDIR LA SURFACE USTED DEBE NUNCA UNTIL COOLED VITREE AVANT D Y TOUCHER TOCAR EL VIDRIO CALIENTE NEVER ALLOW CHILDREN PER
29. 5E45 and SV4 5E90 elbows in the same manner as the straight vent sections The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with the required direction of the next vent run element Twist elbow sections in a clockwise direction only so as to avoid the possibility of unlocking any of the previously connected vent sections see Figure 23 Swivel Joint 360 swivel SV4 5E90 90 Elbow 4 13 16 122 mm Swivel Joint 360 swivel SV4 5E45 45 Elbow Figure 23 G Continue installation of horizontal inclined sections Continue with the installation of the straight vent sections in horizontal inclined run as described in Step C Install support straps every 5 feet 1 52 m along horizontal inclined vent runs using conventional plumber s tape See Page 19 Figure 32 It is very important thatthe horizontal inclined run be maintained in a straight no dips and recommended to be in a slightly elevated plane in a direction away from the fireplace of 1 4 rise per foot 20 mm per meter which is ideal though rise per foot run ratios that are smaller are acceptable all the way down to at or near level Use a carpenter s level to measure from a constant surface and adjust the support straps as necessary It is important to maintain the required clear ances to combustibles 1 25 mm at all sides for all vertical runs
30. 8 inches 458 mm 18 inches 458 mm abovetheterminal within a horizontal distance of 18 in 458 mm from the center line of the terminal E Clearance to unventilated soffit 12 inches 30 cm 12 inches 30 cm F Clearance to outside corner 5 inches 12 7 cm 5 inches 12 7 cm G Clearance to inside corner 2 inches 5 08cm minimum SV4 5HT 2 2 inches 5 08cm minimum SV4 5HT 2 Clearance to each inside of center line extended 3 feet 91 cm within a height of 15 feet above the meter 3 feet 91 cm within a height of 15 feet above the meter above meter regulator assembly regulator assembly regulator assembly Clearance to service regulator vent outlet 3 feet 91 cm 3 feet 91 cm J Clearance to non mechanical air supply inlet 6 in 15 2 cm for appliances lt 10 000 BTU hr 3kW 12 15 2 cm for appliances lt 10 000 BTU hr 3kW 9 to building or the combustion air inlet to any other in 30 cm for appliances gt 10 000 BTU hr 3kW and in 23 cm for appliances gt 10 000 BTU hr 3kW and appliance 100 000 BTU hr 30kW 36 inches 91 cm for appliances 50 000 BTU hr 15kW 12 inches 30 cm for appliances gt 100 000 BTU hr 30kW gt 50 000 BTU hr 15kW K Clearance to mechanical air supply inlet 6 feet 1 8 meters 3 feet 91 cm above if within 10 feet 3 m horizon tally L Clearance above paved sidewalk or paved 7 feet 2 13 m t 7 feet 2 13 m t LI
31. An appliance operated with the air shutter opened too far may have flames that appear blue and transparent These weak blue and transparent flames are termed anemic Propane models may exhibit flames which candle or appear stringy If this is present and persists adjust the air shutter to a more closed position then operate the appliance for a few more minutes to ensure thatthe flame normal izes and the flames do not appear sooty The following chart is provided to aid you in achieving the correct air shutter adjustment for your installation Air Shutter Adjustment Guidelines Amount of Flame Air Shutter Primary Air Color Adjustment If air shutter is Flame will Air shutter closed too far be orange gap should be gt gt increased If air shutter is Flame will Air shutter open too far be blue gap should be decreased 30 Burner Air Shutter Adjustment Procedure Air Shutter Adjusting Rod A hir Shutter Burner I Opening Venturi ID WARNINGS Air shutter adjustment should only be performed by a quali fied professional service technician e Ensure front glass panel are in place and sealed during adjustment Main Burner Factory Air Shutter Opening Setting All Models Natural Gas Propane Gas inches millimeters inches millimeters TWO 1 8 3 Slots TWO 11 16 17 Slots ET IPEA YA Na BAKO Increase NV Be Adjustment Rod Positions viewed from above Openin
32. GCK DMOEPN Kit part numbers are listed here and the following steps detail the conversion pro cedure Refer to the instructions provided with the conversion kit when performing any gas conversion NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE INSTALLATION INSTRUCTIONS Step 1 TURN OFF THE GAS SUPPLY TO THE APPLIANCE and disconnect power supply atthe circuit breaker Ensure appliance is cold CAUTION THE GAS SUPPLY SHALL BE SHUT OFF PRIOR TO DISCONNECTING THE ELECTRICAL POWER BEFORE PROCEEDING WITH THE CONVERSION ATTENTION AVANT D EFFECTUER LA CONVERSION COUPEZ D ABORD L ALIMENTATION EN GAZ ENSUITE COU PEZ L ALIMENTATION ELECTRIQUE Step 2 Remove the front glass door assembly from the appliance see Removing Glass Enclo sure Panels on Page 30 Remove the control compartment door see Control Compartment Door Removal on Page 27 Step 3 Carefully remove the logs Exercise care so as not to break the logs Step 4 Refer to Figure 60 Remove the front burner and then the rear burner NOTE REMOVE FRONT BURNER FIRST THEN REAR BURNER J REAR BURNER VENTURI TUBE ARM LE FRONT BURNER VENTURI TUBE ARM AIR SHUTTER ADJUSTMENT LEVER FIREBOX SUBFLOOR 7 FRONT OF FIREPLACE Figure 60 Millivolt Appliances Step 5 SIT Systems Refer to Figure 61 on Page 36 and the instructions provided with the kit Using a Torx T20 with 1 4 shank and center hole tool or standard flat
33. METTEZ JAMAIS A UN ENFANT LOS NINOS DEBEN NUNCA TO TOUCH GLASS DE TOUCHER LA SURFACE VITREE TOCAR EL VIDRIO WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions f you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Ne pas entreposer ni utilizer d essence ni d autres vapeurs ou liquides inflammables dans le voisinage de cet appareil ou de tout autre appareil QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ Ne pas tenter d allumer d appareil Ne touchez aucan interrupteur Ne pas vous servir des t l phones se trouvant dans le batiment vous trouvez Appelez imm diatement votre fournisseur de gaz depuis un
34. N switch installed at Step 4 MILLIVOLT Thermocouple SON lt P Lye Min 9 mm Hood Igniter Rod q Pilot Nozzels Thermopile Figure 50 Electronic Appliance Checkout To light the burner turn ON the OFF ON switch located in the control compartment Ensure the igniter lights the pilot The pilot flame should engulf the flame rod as shown in Figure 51 ELECTRONIC Proper Flame Adjustment Pilot Nozzels 3 8 to 1 2 Ground Electrode Flame Rod Hot Surface Igniter Figure 51 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Step 8 INSTALLING LOG SET VOLCANIC STONE AND GLOWING EMBERS A WARNING DO NOT attempt to install the logs until the appliance instal lation has been completed the gas line connected and tested for leaks and the initial burner operation has been checked out The size and position of the log set was engineered to give the appliance a safe reliable and attractive flame pattern Any attempt to use a different log set in the fireplace will void the warranty and will result in incomplete combustion soot ing and poor flame quality Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Turn off all electricity to the appliance before you install grate volcanic stone vermiculite embers and logs This appliance is not designed to burn wood Any attempt
35. NISH WALL BRACKET 10 Stepped to Accept Drywall on 2 Corners Front back and left edge of unit top 254 FRAMING SPACERS 464 Louvered Control Front Vi r Right Side View Figure 13 Left Side View ront View Compartment Door g NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 12 Step 2 ROUTING GAS LINE Route a gas line along the inside of the right side framing as shown in Figure 14 Gas lines must be routed constructed and made of materials that are in strict accordance with local codes and regulations All appliances are factory equipped with a flexible gas line con nector and 1 2 inch shutoff valve see Step 6 on Page 27 Also see Figures 12 and 13 on Pages 10 and 11 5 5 8 143 mm Figure 14 ROUTE GAS LINE Proper Sizing of Gas Line Properly size and route the gas supply line from the supply regulator to the area where the appliance is to be installed per require ments outlined in the National Fuel Gas Code NFPA 54 latest edition USA or B149 latest edition Canada Never use galvanized or plastic pipe Refer to Table 7 for proper sizing of the gas sup ply line if black iron pipe is being used Gas lines must be routed constructed and made of materials that are in strict accordance with local codes and regulations We recommend that a qualified individual s
36. NT OF FIREPLACE LOG NOTCH LOCATION RELATIVE TO BURNER Figure 55 Proper Burner Flame Appearance Volcanic Stone Figure 53 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 29 30 Step 9 INSTALLATION AND REMOVAL OF GLASS DOOR WARNING e Do notattemptto substitute the materials used these doors or replace cracked or broken glass e Handle this glass with extreme care Glass is susceptible to damage Do not scratch or handle roughly while reinstall ing the glass door frame e The glass door s of this appli ance must only be replaced as a complete unit as provided by the manufacturer Do not attempt to replace broken cracked or chipped glass sepa rately e Do not attempt to touch the front enclosure glass with your hands while the fireplace is in use WARNING Do not operate appliance with the glass frontremoved cracked or broken A AVERTISSEMENT Ne pas utiliser l appareil si le panneau frontal en verre n est pas en place est craqu ou bris Only doors certified with the appliance shall be used Seules des portes certifi es pour cet appareil doivent tre utilis es CAUTION DO NOT abuse glass door by striking or slamming shut Removing Glass Enclosure Panels see Figure 56 1 2 A Remove the top louver assembly by lifting it up and pulling it out Remove the control compartment access door see removal instructions on Page
37. Number of Vent Sections 45 oss 1 o o o 0 1 Ls fone s ey Lt 15 112511 i fo EL BEI EE EC DERI EN EO zs pes o 3 ss zes 3 sis o 9 ss ses EEE us ses s ss sss Fes 2 st qaem lolo 555 4 625 o t 2 0 Papas pope pepe 1 66 525 o 2 2 o o 4 675 5 625 o o 3 o o fs 69 P575 o o p o 2 j op 2 6 f4 735 eis o o 2 o fs 79 5 66251 o t o 2 o 3 fes o o fo fs 1 21 175 o 2 P t oj t 4 91 5 7 625 o o 2 o t fl Se oe 5 2 2 1035 ees o o o0 3 2 ED BOR ee a AT 1 os i of5 185 oss 1 t 0 EN 1 Es KENNEN HEN o o EN EME v e w e m e ej e e v Ces us 9 1 5 poss Fs 15 5s fo fo Fuss res o fo ja o 2 4 Lo fe fs fa 3 9 fs po fe 4 al po SC es em e Convert inches into metric equiva lent measure as follows Millimeters mm Inches x 25 4 Centimeters cm Inches x 2 54 Meters M Inches x 0254 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE VENT SECTION LENGTH CHART Nominal Section Length inches Net Section Eua Length inches Height of Vent Number of Vent Sections ect
38. PPLIANCE OPERA TION Turn on burner then observe the individual tongues of flame on the burner Make sure all ports are open and producing flame evenly across the burner If any ports are blocked or partially blocked clean out the ports With the gas line installed run initial system checkout before closing up the front of the appliance Follow the pilot lighting instructions provided in the Care and Operation Instructions manual For piezo igniter location see Figure 48 millivolt appliances only Note The pull out Lighting instructions label can be found inthe control compartment see Figure 48 When first lighting the appliance it will take a few minutes for the line to purge itself of air Once purging is complete the pilot and burner will light and operate as indicated in the instruction manual Subsequent lighting of the appliance will not require such purging Inspect the pilot flame Millivolt Appliance Checkout The pilot flame should be steady not lifting or floating Flame should be blue in color with traces of orange at the outer edge The top 3 8 10 mm at the pilot generator thermopile and the top 1 8 minimum tip of the quick drop out thermocouple should be engulfed in the pilot flame The flame should project 1 25 mm beyond the hood at all three ports Figure 50 To light the burner rotate the gas valve control knob counterclockwise to the ON position then turn ON the OFF O
39. The horizontal termination must not be recessed into the exterior wall or siding by more than the 1 1 4 32 mm as shown in Figure 34 IMPORTANT The vent termination is hot while in operation and fora period oftime following the use ofthe fireplace Young children should be carefully supervised when they are in the same area as a hot termination To prevent contact with hot surfaces we recommend the use of a Termination Guard See Page 33 This can be purchased at your local dealer To help minimize water infiltration it is recommended that the Firestop Spacer SV4 5HF be installed on the exterior side of the wall SV4 5 2 Termination 12 w 10 308 267mm Adapter Note Centerline of Vent Piping is NOT the Same as the Centerline of the Framed Opening See Figures 12 and 13 on Pages 10 and 11 6 to 48 inch Vent Section for Min Distance to Base of Appliance Telescopic vent section Elbow or Appliance Collar Base of Appliance Figure 33 INSTALLING SQUARE HORIZONTAL TERMINATION SV4 5HT 2 xN Maximum wall thickness Use silicone caulking to seal 9 1 4 in 235mm the top and sides of the termination up to the i ia underlayment tices i Interior Surface of d Exterior Surface of Siding masonry wall surface Finished Wall Exterior Surface of E P Framing idi aximum Extent o t Siding Vent Run Sections 6 in to 9 1 4 in Caulk Relative to Exterior ph 152 t
40. VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS NEW YORK CITY NEW YORK MEA Installation of these fireplaces are approved for installation in New York City in the US state of New York COLD CLIMATE INSULATION For cold climate installations seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests if floor is above ground level Gas line holes and other open ings should be caulked or stuffed with unfaced fiberglass insulation If the fireplace is being installed on a cement slab in cold climates a sheet of plywood or other raised platform can be placed underneath to prevent cold transfer to the fireplace and into the room It also helps to sheetrock inside surfaces and tape for maximum air tightness and caulk firestops MANUFACTURED HOME REQUIREMENTS This appliance may be installed in an aftermarket permanently located manufactured home and must be installed in accordance with the manu facturer s instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR Part 3280 in the United States or the Standard for Installation in Mobile Homes CAN CSA 7240 MH Series in Canada Cet appareil peut tre install comme du mat ri el d origine dans une maison pr fabriqu e E U seulement ou mobile et doit tre install selon
41. VF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible wall Two 45 degree elbows may be used in place of one 90 degree elbow The same rise to run ratios as shown in the venting Figures for 90 elbows must be followed if 45 degree elbows are used AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 36 WARNING Under no circumstances may sepa rate sections of concentric flexible vent pipe be joined together Ceiling Firestop Spacer SV4 5VF 40 feet 12 2 meters Maximum A Vent Restrictor as shown in Figure 17 on Page 13 must be used in this application When using Secure Flex use Firestop Spacer SF4 5VF Figure 27 Top Vent STRAIGHT Table A mer Teet meta Fas Fez z Los Fuss s on Few az V H 40 feet 12 2 meters Max H 8 feet 2 4 meters Max Ratio V to H ratio is 1 2 Example If 8 feet of H horizontal vent run is needed then 4 feet minimum V vertical vent will be required This table shows a 1 V to 2 H ratio For every 1 foot of V vertical you are allowed 2 feet of H horizontal run up to a maximum horizontal run of 8 feet When using Secure Flex use Firestop Sp
42. acer SF4 5VF Figure 28 Side Vent ONE 90 DEGREE ELBOW Ceiling Firestop Spacer SV4 5VF Wall Firestop Spacer SV4 5HF When using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Table B wei Vm Tet metr s use tmwow s puse 31 Co ww 2 ose 5 us 3 ate m Los 4 29 V V4 H 40 feet 12 2 m Max H 20 feet 6 096 meters Max Example If 20 feet of H hori zontal vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio For every 1 foot of V verti cal you are allowed 5 feet of H horizontal run up to a maximum horizontal run of 20 feet An elbow is acceptable as 1 foot of vertical rise except where an elbow is the only vertical component in the system See Figure 36 Figure 29 Top Vent TWO 90 DEGREE ELBOWS NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 17 18 VERTICAL VENT FIGURES TABLES CONTINUED gm Mamam Maximum Vien v Teet e meter eer T metr rar s umo 2 uem 9 ro az om 4 rs usns 3 fous S4 Em mp s e a fon i V V4 H H4 40 feet 12 2 m Max 8 feet 2 438 meters Max H Hy 20 feet 6 096 meters Max When using Secure Flex use Firestop Spacer SF4 5VF S
43. age 15 D Attach vent components to appliance To attach a vent componentto the appliance collar align the dimpled end over the collar adjust ing the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels on the collar refer to Figure 20 on Page 15 Push the vent component against the collar until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe elements with the same procedure Sealant and securing screws are not required Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent section E Attach vent components to each other Other vent sections may be added to the previously installed section in accordance with the requirements of the vent tables To add another vent component to a length of vent run align the dimpled end of the component over the inclined channel end of the previously installed section adjusting the radial alignment until the four locking dimples are aligned with the inlets of the four incline channels of the previous section NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Push the vent component against the previous section until it fully engages then twist the component clockwise running
44. aligned with the inlets of the four incline channels of the previous section Push the vent component against the previous section until it fully engages then twist the componentclockwise running the dimples down and along the incline channels until they seat at the end of the channels This seating position is indicated by the alignment of the arrow and dimple as shown in Figure 20 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE D Install firestop spacer at ceiling When using Secure Vent use SV4 5VF firestop spacer at ceiling joists when using Secure Flex use SF4 5VF firestop spacer If there is living space above the ceiling level the firestop spacer must be installed on the bottom side of the ceiling If attic space is above the ceiling the firestop spacer must be installed on the top side of the joist Route the vent sections through the framed open ing and secure the firestop spacer with 8d nails or other appropriate fasteners at each corner Remember to maintain 1 25 mm clearance to combustibles framing members and attic or ceiling insulation when running vertical chim ney sections Attic insulation shield H3907 may be used to obtain the required clearances indicated here See installation accessories 0 n Pages 33 and 34 The gap between the vent pipe and a vertical firestop can be sealed with non combustible caulking E Support the vertical vent run sections Note Proper venting suppo
45. ance Do notallowthe flexible vent to bend in a radius tighter than 5 127 mm Refer to Figure 42 Space out the internal flex vent spacers evenly approximately every 6 inches and avoid kinking of inner pipe Support horizontal sections of flex with metal straps at 2 foot 0 61 m intervals NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Collar or secure vent sections D Install Firestop Spacers at ceilings and walls When Secure Flex penetrates a wall or ceiling a firestop spacer is required use the SF4 5 VF firestop spacer for ceilings and the SF4 5 HF firestop spacer for walls See the appropriate sections and Figuresshown throughoutthe vent ing section for their installation requirements Flexible Vent Section FN 5 127 mm Radius Minimum Figure 42 E Attach Flex Vent to Termination Secure Flex components can be purchased separately and attached to bulk lengths of Se cure Flex flexible tubing cut to size at the job site Securetheflexible ventto the Secure Flex terminations in the same manner see Figure 41 as it was attached to the adapter Note Secure Flexventmustbe attached to Secure Flexterminations only DO NOT substitute Secure Vent terminations or the Secure Vent adapter for Secure Flex components The collars of Secure Flex terminations and adapters have a different diameter than that used with the Secure Vent pipe Additionally Secure Flex components have an extended lengt
46. are labeled for identification DO NOT use any other manufacturer s vent components with these appliances GENERAL INFORMATION A WARNING Young children should be care fully supervised when they are in the same room as the appli ance Toddlers young children and others may be susceptible to accidental contact burns A physical barrier is recommended if there are at risk individuals in the house To restrict access to a fireplace or stove install an adjustable safety gate to keep toddlers young children and other at risk individuals out of the room and away from hot surfaces AVERTISSEMENT Les jeunes enfants devraient tre surveill s troitement lorsqu ils se trouvent dans la m me pi ce que l appareil Les tout petits les jeunes enfants ou les adultes peuvent subir des brilures s ils viennent en contact avec la sur face chaude Ilestrecommand d installerune barri re physique si des personnes a risques habi tent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s cu rit cette mesure emp chera les tout petits les jeunes enfants et toute autre personne a risque d avoir acces a pi ce et aux surfaces chaudes Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition Les enfants et les adultes devraient tre infor m s des dangers que posent les temp ratures de su
47. as Line Page Control Compartment Access Page Step 7 Verifying Appliance Operation Page Step 8 Install logs Volcanic Stone and Embers Page Step 9 Installing Glass Door Page Step 10 Burner Adjustments Page Step 11 Hood Installation Page Finishing Requirements Page Step 12 Attaching Safety in Operation Warnings Page Installation Accessories Page Gas Conversion Kits Page Please read and understand these instructions before beginning your installation NATIONAL FIREPLACE INSTITUTE NFI and serviced by profes the U S by the National CERTIFIED www nficertified org NFI Gas Specialists 4 A N A ol cl c OC 17 19 21 25 26 We recommend that our gas hearth products be installed sionals who are certified in Fireplace Institute NFI as PACKAGING The assembled vented gas fireplace heater is packaged with 1 log set located in firebox area 2 One envelope containing the literature package located in the firebox which consists of the care and operation manual installation instructions safety in operation warning labels warranty nailing flanges 8 for SSDVST models and 4 for SSDVPF models 3 One vent restrictor to
48. ch the termination is to be attached as shown in Figure 34 If the terminus of the last section is not within this distance use the telescopic vent section SV4 5LA as the last vent section For wall thicknesses greater than that shown in Figure 34 refer to Table 9 on Page 21 This Table lists the additional venting components needed in addition to the termination and adapter for a particular range of wall thicknesses K Attach termination adapter Attach the adapter SV4 5RCH provided with the termi nation to the vent section or telescoping vent section elbow or appliance collar as shown in Figures 33 and 34 in the same manner as any SV4 5 vent component refer to Step E L Install Firestop Spacer at exterior wall When using the square termination install SV4 5HF Secure Vent SF4 5HF Secure Flex Firestop Spacer over the opening at the exterior side of the framing long side up withthe 3 inch spacer clearance at the top as shown in Figure 33 and nail into place The Firestop Spacer may also be installed over the opening at the interior side of framing M Install the Square Termination SV4 5HT 2 For the last step from outside the exterior wall slide the collars of the termination onto the adapter until the termination seats against the exterior wall surface to which it will be attached Orient the housing of the termination with the arrow pointed upwards Secure the termination to the exterior wall
49. down and along the incline channels until they seat at the end of the channels Attach the flexible vent to the adapter as fol lows see also Figure 41 A Install the Inner Flex Pipe 1 Install the small gear clamp loosely around the inner flexible vent pipe push it back out of the way Apply a bead of Mill Pac Black 700 F high temperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end Pull and extend the inner flexible vent pipe Slide the inner flex pipe over the adapter col lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free from damage or tears Slide the gear clamp down and tighten it fully to secure the flexible vent to the adapter inner collar approximately 3 4 inch from the end of the flex Install three screws 120 degrees apart through the flexible vent pipe and into the adapter collar just below the gear clamp to provide additional security to the connec tion N Ac c NOTE Outer pipe is pulled away to show the detail of the inner pipe APPLY ONLY MIL PAC BLACK HIGH TEMPERATURE SEALANT Cat No 10K81 to the outside surface of both collars of the adapter be especially careful to fill the grooves of the outer collar to be covered by the flexible pipe and slide flexible pipe over inner and outer adapter collars 1 3 4 inch 44 mm flexible p
50. e Gas Valve Piezo Igniter Figure 48 Reinstalling Control Compartment Door To reinstall insert the hook catches on each side of the door into the corresponding slots in the control compartment opening then gently push forward and slide down until it locks in place Lift the Lower Control Compartment Door OPENING CONTROL up and pull out to COMPARTMENT DOOR remove Hook F UY T T Figure 49 ls Out Lower Compartment Door PTT 27 28 TEST ALL CONNECTIONS FOR GAS LEAKS FACTORY AND FIELD A WARNING Never use an open flame to check for leaks Turn on gas supply and test for gas leaks using a gas leak test solution also referred to as bubble leak solution Note Using a soapy water solution is an effec tive leak test solution but it is not recommended because the soap residue that is left on the pipes fittings can result in corrosion over time A Light the appliance refer to the lighting instructions label inthe control compartment or in the Care and Operation Instructions manual Brush all joints and connections with the gas leak test solution to check for leaks If bubbles are formed or gas odor is detected turn the gas control knob off pilot on to the OFF position Either tighten or refasten the leaking connection then retest as described above Whenthe gas lines aretested and leakfree be sure to rinse off the leak testing solution Step 7 VERIFYING A
51. e 43 Millivolt Wiring Diagram NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Install OFF ON Switch millivolt models Connect the 2 wires provided in Electrical Outlet Kit to the TP TH and TH terminals on valve Pass the 2 wires through the opening where OFF ON switch will be installed left of piezo below valve Connect the two wires to the OFF ON Switch Connect wires to terminals OFF ON Switch Press the OFF ON switch into bracket as shown below it will snap into place EL EI OFF ON Switc Control Compartment Access panel Figure 44 B Electronic Wiring See Figures 45 and 46 Notes e Theelectronic appliance must be connected to the main 120 VAC power supply e The junction box can be installed in any of the 4 outside corners of the control compartment it can be found factory installed in the right front corner viewed from the valve access side where it should be reinstalled if an optional blower kit is installed 1 Route a 3 wire 120 VAC 60 Hz 1 ph power supply to the location on appliance where junction box is to be installed 2 Openthecontrol compartmentaccess panel see Control Compartment Access Instruc tions on Page 27 3 Remove the junction box outlet receptacle assembly by removing the securing screw at the front right corner of the unit See Figure 45 4 Remove the outlet receptacle from the junction box by removing the two securin
52. e minimum vent height above the roof and or adjacent walls is speci fied in ANSI Z223 1 latest edition In Canada the current CAN CSA B149 1 installation code by major building codes Always consult your local codes for specific requirements A general guide to follow is the Gas Vent Rule refer to Figure 4B on Page 6 Avent restrictor will need to be installed when vertical termination is used See nstallation of Vent Restrictor on Page 13 for guidelines Vertical Straight Installation Determine the number of straight vent sections required 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm net section lengths are avail able see Table 8 and Page 33 Item 3 It is recommended that you plan the vent lengths so that a section joint does not occur within the space defined by ceiling joists or roof rafters Refer to the Vent Section Length Chart SV4 5CGV 1 Termination ES A SV4 5FA or SV4 5FB Flashing and SV4 5SC Storm Collar 1 25 4 mm Minimum Clearance to Combustibles OSVA 5VF Firestop spacer SV4 5L6 12 24 36 48 Vent Sections When using Secure Flex use Firestop spacer SF4 5VF See Figure 21 Page 15 for support strap requirements Figure 18 14 VENT SECTION LENGTH CHART Nominal teen PEELE inches Net Section 4 10 22 34 46 EC inches Height of Vent of Vent
53. e pilot gas line to free the pilot assembly from the gas line Remove the pilot orifice and replace it with the one provided with the conversion kit Reinstall the pilot assembly by reversing the steps detailed here When reinstalling the igniter assembly use extreme care to prevent damage and break age Do not apply any leverage to the igniter assembly while restoring the retainer clip to its original position NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Orifice L Po Assembly Igniter ws Assembly Pd P Retaining Flare Nut Clip Note If the igniter is damaged a replacement kit is available order Catalog No 87L54 Figure 64 All Models Step 9 Refer to Figure 60 on Page 35 and Figure 65 on Page 37 VERIFY THE PROPER ORIFICE SIZES BEFORE INSTALLING THEM A Remove the two orifices from the manifold and replace them with the ones provided in the kit Table 10 shows the orifice sizes for natural and propane models Figure 65 illustrates the orifice Use pipe joint compound or Teflon tape on all pipe fittings before installing en sure propane resistant compounds are used in propane applications do not use pipe joint compounds on flare fittings B Install rear burner first followed by front burner as shown in Figure 66 on Page 37 Ensure thatthe arm of the venturi of each burner is hooked onto the air shutter adjustment lever refer to Figure 600n Page 35 The primary air Opening
54. effective length of from 1 1 2 38 mm to 7 1 2 191 mm The SV4 5LA is fitted with a locking inclined channel end identical to a normal vent section component anda plain end with 3 pilot holes Slip the plain end over the locking channel end of a standard SV4 5 vent component the required distance and secure with three screws Maintain a minimum 1 25 mm clearance to combustible materials for all vertical ele ments Clearances for all horizontal elements are 3 76 mm on top 1 25 mm on sides and 1 25 mm on the bottom A Frame ceiling opening Use a plumb line from the ceiling above the appliance to locate center of the vertical run Cut and or frame an opening 10 1 2 x 10 1 2 267 mm x 267 mm inside dimensions about this center mark Figure 19 10 1 2 Min 267 mm Roof DE Framing 10 1 2 Min 267 mm Ceiling Framing Figure 19 B Attach vent components to appliance Se cure Vent SV4 5 direct vent system compo nents are unitized concentric pipe components featuring positive twist lock connections see Figure 20 All of the appliances covered in this document are fitted with collars having locking inclined channels The dimpled end of the vent com ponents fit over the appliance collar to create the positive twist lock connection Align the dimple four places of the upper vent section with the opening of the locking incline channel on the e lower vent section or applia
55. elow grade penetrations of the gas line allowed etc e e e e IMPORTANT If propane is used be aware that if tank size is too small i e under 100 Ibs if this is the only gas appliance in the dwelling Ref NPFA 58 there may be loss of pressure resulting in insufficient fuel delivery which can result in sooting severe delayed ignition or other malfunctions Any damage resulting from an improper installation such as this is not covered under the limited warranty Step 3 INSTALL THE VENT SYSTEM General Information These instructions should be used as a guideline and do not supersede local codes in any way Install venting according to local codes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CSA B149 1 in Canada Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier D gagement conforme aux codes d installation locaux et aux exigences du foumisseunde gaz Use only approved venting components See Approved Vent Components on Page 2 These fireplaces must be vented directly to the outside The vent system may not service multiple appliances and must never be connected to a flue serving a solid fuel burning appliance The vent pipe is tested to be run inside an enclosed wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the ve
56. ements Inlet Gas Supply Pressure all models 5 0 WC 1 24 kPa 11 0 WC P ES 10 5 WC 2 61 kPa 13 0 WC 3 23 kPa Table 3 Manifold Gas Supply Pressure all models Low millivolt only Lo 2 2 WC Hi 3 5 WC 55 kPa 87 kPa Hi 10 0 WC Lo 6 3 WC 1 57 kPa 2 49 kPa Table 4 Test gauge connections are provided on the front of the millivolt gas control valve identi fied IN for the inlet and OUT for the manifold side A 1 8 NPT Test gauge connection is provided at the inlet and outlet side of the electronic gas control valve These appliances must be isolated from the gas supply piping system by closing their individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa These appliances and their individual shut off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures greater than 1 2 psig 3 5 kPa These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance Orifice Sizes Sea Level to High Altitude All Models These appliances are tested and approved for installation at elevations of 0 4500 feet 0 1372 meters above sea level using the standard burner orifice sizes marked with an Table 5 Forelevations above 4500 feet contact your gas supplie
57. ent Door NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 6 7 8 175 Right Side View FIREPLACE SPECIFICATIONS SSDVPF PENINSULA VIEW vines tilia Fireplace Framing Specifications SPECIFICATIONS e Minimum Framing Stud Size is 2 x 4 e See right side viewsof fireplace below for gas line inlet location options Natural amp Propane 37 500 B a inches millimeters Gas BTU Input MV Low 30 000 Ga Minimum Framing Stud Size is 2x 4 4 1 2 Inner Dimension A Pu ad S E Co axial DV Vent S n 0 axia ent Size 7 1 2 Outer Vent Center Top Secure Vent 47 1 8 1194 Vent Framing Top Vent vent 90 Secure Flex 47 7 8 1216 With One 90 Elbow egree elbow Vent Framing Rear Vent With No Elbows _ 7 e Annual Fuel Utilization Efficiency D 12 1 8 M 308 Diagrams illustrations and photographs are not to scale consult installation instruc tions Product designs materials dimen sions specifications colors and prices are Vent Center Side subject to change or discontinuance without Vent no elbows notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each Gas Line flue outlet Center of gas line 6 1 4 41 1 2 is 3 in 76 mm 199 1054 _ up from floor PRODUCT REFERENCE INFORMATION Dimension A M Cat Model Ship Secure Vent 46 1 2 men 4358 7 _ a No Volume Secure Flex 48 1 4 1226 1108
58. ff Valve Fl ntc 3 8 Union 3 8 Close Nipple Figure 47 Glass Door is Above Contro Compartment Latch for Glass Door Control Compartment Access CONTROL COMPARTMENT ACCESS LOUVER PANEL INSTRUCTIONS Ref Figure 49 NOTE The top louvered panel and the bottom louvered control panel door remove and install the same way as follows The gas controls can be found behind the control compartment access door Removing Control Compartment Door Open the door by gently lifting it upward until the hook catches on both sides clear the locating slots Then pull door out to remove On millivolt systems the piezo igniter HI LO flame adjustment knob and pilot and main gas OFF ON control knob are located below the glass panel enclosure The gas valve for electronic systems is also located below the glass enclosure panel See Figure 48 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 13 8 Flex Tubing 1 2 1 2 X 3 8 3 8 Nipple Phas Reducer GAS CONNECTION Note The gas supply line must be installed in accor dance with building codes by a qualified installer approved and or licensed as required by the locality In the Commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter 3 8 Shut off Valve Gas Solid Line Connector Gas Shut Off OFF PILOT ON Valve gas control knob HI LO flame height control knob Switch Can be Installed Her
59. g screws 25 26 Install a field provided strain relief in the cabinet knockout opening for the protection of the power supply wires Connect the power supply wires to the receptacle as shown in Figure 46 on Page 26 Connectthe ground supply wire to the green wire attached to the outlet receptacle s green ground screw Wire and install the outlet receptacle to junction box Next install into the chosen corner of the control compartment as shown in Figure 45 After the receptacle junction box wiring is complete install the field provided metal junction box cover plate see Figure 45 Note The supplied 15 feet of 2 conductor wire has one end of each conductor con nected to the gas valve circuit and the other end of each conductor placed loose on top of the appliance IMPORTANT NOTE The gas valve OFF ON switch is shown in Figure 46 on Page 26 It is integral with the gas valve and should be set to the ON position Receptacle Junction Box and Cover Plate Installation Outlet Receptacle Junction Box View Of Right TT Bottom Corner Of Unit Field provided Metal Junction Box Cover Plate With Screw Junction Box knock out 2 places each side Fireplace Press snap bushing into the knock out for control switch wires Valve Access Side Figure 45 Step 5 WIRING OPTIONAL FORCED AIR BLOWER KIT ACAUTIONS M CL OS CE EU RLU FBK 100 FBK 200 and FBK 250
60. g Secure Flex use Firestop Spacer SF4 5HF Square termination SV4 5HT 2 shown Figure 36 Top Vent ONE 90 DEGREE ELBOW NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 21 HORIZONTAL VENT FIGURES TABLES CONTINUED Maximum HMaxmum VMinimum _ feet meter feet meter teet meter 5 6529 2 1 0305 10 4 219 2 0610 eu 15 4 572 6 1 829 0914 Spacer SV SH 20 6 006 8 2 438 a 1 219 VH H4 40 feet 12 2 m Max 8 feet 2 438 meters Max Ceiling H H4 20 feet 6 096 meters M 4 Firestop Spacer Hy eet 6 096 meters Max SV4 5VF Square termination Example _ ple 1 20 feet of H horizontal 5 4 5 2 shown vent run is needed then 4 feet minimum of V vertical vent will be required This table shows a 1 V to 5 H ratio Forevery 1 foot of V vertical you are allowed 5 feet of H H horizontal run up to a maximum horizontal run of 20 feet Owhen using Secure Flex use Firestop Spacer SF4 5VF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses Figure 37 Side Vent TWO 90 DEGREE ELBOWS Wall Firestop Table G TOES H H Maximum VMinimum s two _ Ls 1 was em z rs 3 fon Em
61. g This Natural Gas fully clockwise Air Shutter Propane fully counter clockwise Adjusting eee Decrease Shutter Settings are shown for each burner Opening In This Arms Ref Air shutter Patent Direction U S Pat 5 553 603 A Note Both air shutters open and close simultaneously when the air shutter adjusting rod is moved A CAUTIONS e Soot will be produced if the air shutter is closed too much Any damage due to carboning resulting from improperly setting the air shutter is not covered under the warranty The air shutter door and nearby appliance surfaces are hot Exercise caution to avoid injury while adjusting flame appearance Note Burners are omitted in this view for clarity Figure 57 Burner Air Shutter Adjustment _ Locate adjustment rod and adjust air shutter to the standard setting as shown in Figure 57 adjustment rod is located in the lower control area Note Rotating the adjustment rod coun terclockwise decreases air and clockwise increases air N Light appliance follow lighting procedure on lighting label in control compartment or see care and operation manual Allow the burner to operate for at least 15 minutes while observing the flame continu ously to ensure thatthe proper flame appear ance has been achieved see Figure 58 f the following conditions are present adjust Step 11 HOOD INSTALLATION Figure 58 Burner Flame Appearance
62. h Wall Thermostat Or Remote Control Receiver Install snap bushing provided in Electrical Outlet Kit See Figure 44 into control switch knock out in side panel see Figures 12 and 13 on Pages 10 and 11 Wire the optional control switch withinthe millivolt control circuit as shown in Figure 43 using the 15 feet of 2 conductor wire supplied route wires through the snap bushing to the optional control switch Mountthe optional control switch or wall thermostat in a convenient location on a wall near the fireplace CAUTION Do not connect optional control switch to 120V power supply 2 Install the junction boxand receptacle outlet totheleftofthe valveinthefront foroptional blower kit See junction box and receptacle Outlet as explained in steps 1 11 for B Electronic Wiring on this page n Twist wires together to operate unit solely by manipulating the gas valve control knob or connect wires to optional control switch wall switch remote control or wall thermostat to operate unit e If any of the original wire as supplied must be replaced it must be replaced with Type AWM 105 18 gage wire Optional Control Switch foo Only Thermopile Schematic Representation Field Wired Factory Wired Optional Kits Installed ON OFF wall switch unit mounted burner ON OFF switch wall thermostat or remote control receiver Figur
63. h center tube for use in attaching the flexible vent Step 4 FIELD WIRING A CAUTION Ground supply lead must be con nected to the wire attached to the green ground screw located on the outletbox See Figure 46 Failure to do so will resultin a potential safety hazard The appliance must be electrically grounded in accordance with local codes or inthe absence of local codes the National Electrical Code ANSI NFPA 70 latest edition In Canada the current CSA C22 1 Canadian Electrical Code CAUTION Label all wires prior to disconnec tion when servicing controls Wiring errors can cause improper and dangerous operation ATTENTION Au moment de l entretien des commandes tiquetez tous les fils avant de les d brancher Des erreurs de c blage peu vent entrainer un fonctionnement inad quat et dangereux Verify proper operation after servicing S assurer que l appareil fonctionne ad quatement une fois l entretien termin Refer to Section A for millivolt appliances and Section B for electronic appliances The gas valve is set in place and pre wired at the factory on both models A Millivolt Wiring See Figure 43 1 Install and wire in the burner control switch Install either a or b below NOT BOTH installing both may resultin improper burner operation a Optional OFF ON Switch Install the OFF ON burner control switch rocker switch as shown in Figures 43 and 44 b Optional Wall Switc
64. injury A AVERTISSEMENT Risque de dommages ou de blessures si les pi ces ne sont pas install es conform ment a ces sch mas et ou si des pi ces autres que celles sp cifiquement approuv es avec cet appareil sont utilis es DETAILED INSTALLATION STEPS The appliance is shipped with all gas controls and components installed and pre wired 1 Remove the shipping carton Remove the shipping pad exposing the front glass door 2 Open the two latches located under the firebox floor securing the glass door Re move the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Removing Glass Panels on Page 30 2 Remove the top louvered panel and locate the pressure relief plates 3 Lift the pressure relief plates and remove the cardboard from beneath each plate be careful not to damage the white gasket See Figure 10 NOTE INSTALLATION DIAGRAMS AND INSTRUCTIONS SHOW THE FRONT OF THE APPLIANCE AS THE SIDE WHICH HAS VALVE ACCESS EXCEPT WHERE NOTED Pressure Relief Plates Remove Cardboard Before Using Appliance Figure 10 TYPICAL INSTALLATION SEQUENCE The typical sequence of installation is outlined below However each installation is unique and may result in variations to the steps described Seethe Page numbers references in the follow ing steps for detailed procedures Step1 Page 9 Construct the appliance framing Posi
65. install the vent restrictor in the appliance top flue outlet as shown in Figure 17 when vertically terminating the vent system above the roof It may be installed either from inside or outside the appliance in the inner fireplace collar It is press fitted in place Note The restrictor is included within the firebox Restrictor _ Vent Restrictor Installation Top Vent Appliance Top Vent Outlet Figure 17 Select Venting System Horizontal or Vertical With the appliance secured in framing determine vent routing and identify the exterior termination location The following sections describe vertical roof and horizontal exterior wall vent applications Refer to the section relating to your installation A list of approved venting components is shown on Pages 33 and 34 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 13 VERTICAL TERMINATION SYSTEMS ROOF See Figure 18 and Figures 27to 31 Pages 17 and 18 and their associated Vertical Vent Tables illustrate the vertical venting configurations that are allowed to be used with these appliances Secure Vent pipe applications are shown in these figures Secure Flex pipe may also be used See Page 24 A Vertical Vent Table sum marizes each system s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications Both these vertical vent systems terminate through the roof Th
66. ions to the height as shown in the Vertical vent termination section Page 6 Figure 4B The SV4 5CGV 1 Vertical Termination Figure 26 can be installed in the exact same fashion as any other Secure Vent section Align the termination over the end of the previously installed section adjusting the radial alignment until the four locking dimples of the termination are aligned with the inlets of the four incline channels of the last vent section Push the ter mination down until it fully engages then twist the termination clockwise running the dimples down and along the incline channels until they are seated at the end of the channels Figure 26 If the vent system extends more than 5 feet 1 5 m above the roof flashing stabilizers may be necessary Additional screws may be used at section joints for added stability Guide wires may be attached to the joint for additional sup port on multiple joint configurations VERTICAL VENT FIGURES TABLES Notes e Secure Vent rigid vent pipe is shown in the Figures Secure Flex flexible vent pipe may also be used It is very important that the horizontal inclined run be maintained ina straight no dips and recommended to be ina slightly elevated plane in a direction away from the fireplace of 1 4 rise per foot 20 mm per meter which is ideal though rise per foot run ratios that are smaller are acceptable all the way down to at or near level SV4 5VF Secure Vent SF4 5
67. ipe and adaptor outer collar overlap Adapter SV4 5RF Securing Screw 3 places equally spaced just below gear clamp 1 3 4 in 44 mm flexible pipe and adaptor inner collar overlap Securing Screw 3 places 120 apart equally spaced just below gear clamp Attach adaptor to appliance Figure 41 Install the Outer Flex Pipe Install the large gear clamp loosely around the outer flexible vent pipe push it back out of the way Apply a bead of Mill Pac Black 700 F high temperature sealant Catalog No 10K81 to the outer adapter collar to the grooves of the collar which extend approximately 1 inch from the end and to the flat surface approximately 1 3 8 inches from the end Pull and extend outer flexible vent pipe Slidethe outerflex pipe overthe adapter col lar Ensure the flexible vent pipe completely engages the adapter collar to a distance of 1 3 4 inches from the end and that it is free from damage or tears Slide the gear clamp down and tighten it fully to secure the flexible vent to the adapter outer collar approximately 3 4 inch from the end of the flex Install three screws 120 degrees apart through the flexible vent pipe and into the adapter collar just below the gear clamp to provide additional security to the connec tion 0 N A Route Flex Vent Ensure that the flex vent is properly routed to provide the required clear
68. isoning Note Installation and repair should be done by a qualified service person The appliance Should be inspected before use and at least annually by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bed ding material etcetera It is imperative that contro compartments burners and circulating air passageways of the appliance be kept clean Remarque L installation et la r paration devrait tre confi es un technicien qualifi L appareil devrait faire l objet d une inspec tion par un technicien professionnel avant d tre utilis et au moins une fois l an par la suite Des nettoyages plus fr quents peuvent tre n cessaires si les lapis la literie et celera produisent une quantit importante de pous si re Il est essentiel que les comparti ments abritant les commandes les br leurs et les conduits de circulation d air de l appareil soient tenus propres Do not use these appliances if any part has been under water Immediately call a qualified professional service technician to inspectthe appliance and to replace any parts of the control system and any gas control which have been under water Ne pas utiliser cetappareil s il a t plong m me partiellement dans l eau Ap peler untechnicien qualifi pour inspecter l appareil et remplacer toute partie du syst me de commande ettoute commande qui a t plong e dans l eau Only trim ki
69. izontal run of 20 feet except for installations where an elbow is the only vertical vent section in the system see Figure 36 AN ELBOW IS ACCEPTABLE AS 1 FOOT OF VERTICAL RISE EXCEPT WHERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 36 A WARNING Under no circumstances may separate sections of concentric flexible vent pipe be joined together 28 in 711 mm 21 in 533 mm Maximum Square termination SV4 5HT 2 shown 7 in 711 mm AP 32 lt B 9 Wall Firestop Spacer LT SV4 5HF When using Secure Flex use Firestop Spacer SF4 5HF Note See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses Figure 35 Side Vent NO ELBOWS Example If 20 feet of H horizontal vent run is needed then 4 feet minimum of V vertical vent will be required Table E HMaxmum Fen meer en s Loue Cs Las 10 3 048 15 4 572 20 This table shows a 1 V to 5 H ratio For every 1 foot of vertical you are allowed 5 feet of H horizontal run up to a maximum H horizontal run of 20 feet Elbow Only 0 610 0 914 121 V H 40 feet 12 2 m Max H 20 ft 6 096 m Max de 3 048 2 3 EY Square termination SV4 5HT 2 shown Wall Firestop Spacer SV4 5HF when using Secure Flex use Firestop Spacer SF4 5VF When usin
70. l degrade the performance of this system and may be dangerous These fireplaces are designed as supplemental heaters Therefore it is advisable to have an alternate primary heat source when installed in a dwelling These appliances must not be connected to a chimney or flue serving a separate solid fuel burning appliance Millivolt Models The millivolt appliances are manually controlled and feature a spark igniter piezo that allows the appliance s pilot gas to be lit without the use of matches or batteries This system provides continued service in the event of a power outage Millivolt models come standard with a manually modulated gas valve flame appearance and heat output can be controlled at the gas valve The BTU Input for these appliances is shown in Table 1 Input BTU Manually Modulated Gas Valves millivolt models Fuel Type Input Rate BTU HR SSDVST Natural or 37 500 high SSDVPF Propane Gas 30 000 low Table 1 Electronic Models These electronic appliances feature an electronic intermittent pilot ignition system External elec trical power is required to operate these units These electronic models have a fixed rate gas valve The BTU input for the electronic models is shown in Table 2 Input BTU Fixed Rate electronic models Fuel Type Input Rate BTU HR SSDVST Natural or Table 2 Gas Pressure All Models Tables 3 and 4 show the appliances gas pressure requir
71. lding Support Brackets Framing Horizontal Inclined Run SV4 5HT 2 SV4 5E90 Elbow Termination Shown Firestop Spacer SV4 5VF Ceiling Vertical Rise vent section support Xl j Support Bracket Spacing When Using Secure Flex Use Firestop Spacer SF4 5VF See Figures 21 and 22 on Pages 15 and 16 for vertical Fireplace SV4 5L6 12 24 36 48 Vent Sections Every 5 ft 1 52 m SV4 5HT 2 Termination Shown Figure 32 TYPICAL HORIZONTAL VENT INSTALLATION HORIZONTAL OUTSIDE WALL TERMINATION SYSTEM See Figure 32 and Figures 35 to 40 Pages 21 to 23 and their associated Horizontal Vent Table which illustrates the horizontal venting configu rations that are allowed to be used with these appliances Secure Vent pipe applications are shown in these figures Secure Flex pipe may also be used see Page 24 A Horizontal Vent Table summarizes each system s minimum and maximum vertical and horizontal length values that can be used to design and install the vent components in a variety of applications Both of these horizontal vent systems terminate throughan outside wall Building Codes limit or prohibit terminating in specific areas Refer to Figure 6 on Page 7 for location guidelines Secure Vent SV4 5 direct vent system compo nents are unitized concentric pipe components featuring positive twi
72. located on public property Clearance under veranda porch deck or 12 in 30 cm 12 in 30 cm ea Figure 6 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE MINIMUM CLEARANCES TO COMBUSTIBLES Hearth Extension A hearth extension is not required with this appliance If a hearth extension is used do not block the lower control compartment access door Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation requirements Wall Finishes Surrounds Mantels Note Combustible wall finish materials and or surround materials must not be allowed to encroach the area defined by the appliance front and back faces black sheet metal Never allow combustible materials to be positioned in front of or overlapping the appliance front and back faces See Figure 59 on Page 31 Non combustible materials such as surrounds and other appliance trim may be installed on the appliance front and back faces with the following exception If the optional radiant panels are installed the non combustible material may cover any portion of the top radiant panel or the air gaps surrounding the top radiant panel down to the top edge of eyebrow hood The material must NOT cover any portion of the glass door or louvered panels Vertical installation clearances to combustible mantels vary according to the depth of the mantel See Figure 7 Mantels constructed of non combustible materials may be in
73. lts in 0 0 mm clearance between framing and unit framing spacers The 41 1 2 in dimension permits easier fireplace installation if unit is installed after framing is erected This dimension based on 5 8 drywall For 1 2 drywall use 25 1 2 648 mm The finished dimension should be 26 1 2 673 mm See also Side Vent Seal Cap note below Vertical Venting Through the Ceiling Frame ceiling opening Use a plumb line from the ceiling above the appliance to locate center of the vertical run Cut and or frame an opening 10 1 2 x 10 1 2 267 mm x 267 mm FINISH WALL BRACKET Front and back edge of unit top FRAMING SPACERS Top and Both Sides FLUE Top or Side 3 1 2 89 m 1 2 13 y 4 102 40 1 8 1019 Top View oe 3 1 2 89 411 8 9X9 12 13 1197 ai 1041 37 940 2 1 2 63 5 Provide additional space for Side Vent Seal Cap if installing against a solid wall 3 76 Front View inside dimensions about this center mark see Figure 19 on Page 15 ENER 3UIDE Look for the EnerGuide Gas Fireplace Energy Efficiency Rating in this brochure Based on CSA P 4 1 02 Stepped to Accept Drywall all 4 corners 2 1 2 63 5 i o FLUE Top or Side ELECTRICAL INLETS GAS INLET ELECTRICAL o m INLETS N Louvered Control Compartm
74. me If unknown affix the English language label 3 If you are unable to locate the labels please call Lennox Hearth Products or your nearest Lennox Hearth Products dealer to receive additional safety instruction labels free of charge Cat No H8024 Replacement Label Kit LENNOX HEARTH PRODUCTS 1 800 9 LENNOX Note English is red text on clear label French and Spanish are white text on black label SAFETY LABEL DIAGRAMS WARNING EXTREMELY HOT glass and fireplace Risk of Severe Burns ALWAYS KEEP CHILDREN AWAY FROM FIREPLACE Figure A APPOSITION DES MISES EN GARDE RELATIVES ALA SECURITE D UTILISATION ll est imp ratif que les tiquettes de s curit fournies avec le foyer soient coll es c t des dispositifs de contr le du foyer Une tiquette de s curit doit tre coll e sur la plaque de l interrupteur contr lant l allumage du foyer voir Figure A ou surlethermostat mural voir Figure B et le cas ch ant sur le boitier de la t l commande Figure C Pour achever l instal lation correcte de ce foyer proc dez comme suit avec les tiquettes adh sives en langues trang res fournies avec les instructions d utilisation et d entretien 1 Rep rez l interrupteur ou le thermostat mural qui contr le le foyer v rifiez que l interrupteur contr le le fonctionnement du foyer en le faisant basculer de Marche Arr t et vice versa Nettoyez soigneusement la plaque murale de
75. nce col SE lar Twist vent component clockwise to engage and seal until arrow and dimple align Arrow Dimple l Locking Incline Channel c Connected Vent Sections Appliance Collar or Vent Section Figure 20 To attach a vent component to the appliance collar align the dimpled end over the collar adjusting the radial alignment until the four locking dimples are aligned with the inlet of the four inclined channels on the collar refer to Figure 20 Push the vent component against the collar until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at the end of the channels The unitized design of the Secure Vent components will engage and seal both the inner and outer pipe without the need for sealant or screws If desired a 6 x 1 2 screw may be used at the joint but it not required as the pipe will securely lock when twisted Note An elbow may also be attached to the appliance collar Attach in the same manner as you would a vent section C Attach vent components to each other Other vent sections may be added to the previously installed section in accordance with the requirements of the vertical vent Figures and Tables To add another vent component to a length of vent run align the dimpled end over the inclined channel end of the previously installed section adjusting the radial alignment until the four locking dimples are
76. nifold Pressure Electronic Gas Control Valve Figure 2 Honeywell Electronic Gas Valve REQUIREMENTS FOR THE COMMON WEALTH OF MASSACHUSETTS These fireplaces are approved for installation in the US state of Massachusetts if the following additional requirements are met nstall this appliance in accordance with Massachusetts Rules and Regulations 248 C M R nstallation and repair must be done by a plumber or gas fitter licensed in the Com monwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut off must be a T handle type valve Massachusetts Horizontal Vent Requirements Inthe Commonwealth of Massachusetts hori zontal terminations installed less than seven 7 feet above the finished grade must comply with the following additional requirements A hard wired carbon monoxide detector with an alarm and battery back up must be installed on the floor level where the gas fireplace is installed The carbon monoxide detector must comply with NFPA 720 be ANSI UL 2034 listed and be ISA certified A metal or plastic identification plate must be permanently mounted to the exterior of the building ata minimum height of eight 8 feet above grade and be directly in line with the horizontal termination The sign must read in print size no less than one half 1 2 inch in size GAS
77. nt pipe REMOVE VENT SEAL CAP From the vent that will be used only Top Vent See Figure 15 and Side Vent See Figure 16 Preparing the Appliance Vent Collar Each of the appliances two vent collars are sealed with a seal cap which must be removed from the vent collar being used Refer to Figure 15 for top vent installations and Figure 16 for side vent installations and the following steps to prepare the appropriate collar for use From the vent collar being used remove the two screws securing the vent seal cap Twist the cap counterclockwise Pull it away from the appliance and discard along with the piece of insulation Securing Screws OUTSIDE OF APPLIANCE Insulation Top Vent Vent Seal Cap ToT CROSS SECTION Cabinet Top Firebox Top INSIDE of Appliance TOP VENT SEAL CAP REMOVAL TOP VENT INSTALLATIONS ONLY Figure 15 Insulation Vent Seal Cap CROSS SECTION INSIDE of Appliance OUTSIDE of Appliance lt Securing Screws Cabinet Back SIDE VENT SEAL CAP REMOVAL SIDE VENT INSTALLATIONS ONLY WARNING The VENT SEAL CAP must remain securely installed on unused vent collar Failure to do so could result in leakage of flue products into living space Side Vent Figure 16 Installation of Vent Restrictor Top Vent Installations with Vertical Terminations Only Avent restrictor provided may be needed with this appliance If needed
78. nts can be CTS0 46 Shroud expanded up to two times for double terminations c o o o Mill Pac Black High Temperature Sealant Ref Form 750 194M Inches millimeters Inches millimeters in m in jj 37 5 8 37 5 8 7 12 24 12 3 48 5 8 48 5 8 7 12 24 12 4 48 5 8 731 4 7 1 2 2412 3 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE GAS CONVERSION KITS A WARNING This conversion kitshall be installed by a qualified service agency in accor dance with the manufacturer s instructions and all applicable codes and requirements of the authority having jurisdiction Ifthe information inthese instruction is not followed exactly a fire explosion or production of carbon monoxide may result causing property damage personal injury or loss of life The qualified service agency is responsible for the proper installation of this kit The installation is not proper and complete until the operation of the converted appliance is checked as specified in the manufacturer s instructions supplied with the kit The qualified service agency performing this installation assumes responsibility for this conversion AVERTISSEMENT Cette trousse de conversion doit tre install e par un technicien agr selon les instructions du fabricant et selon toutes les exigences et tous les codes pertinents de l autorit comp tente Assurez vous de bien suivre les instructions dans cette notice pour r d
79. o 235 mm Surface of Framing A Last Vent Section Use Telescopic Vent Section SV4 5LA If Necessary SV4 5 HT 2 ENS Termination SV4 5 HT 2 Termination Adapter SV4 5RCH 1 1 4 Maximum Recess of Square Termination Stucco into Exterior Finishing Material For thicknesses greater than 9 1 4 see Table 9 P Venting Connection and Exterior Wall Recessing of the Horizontal Square Figure 34 Termination SV4 5HT 2 Horizontal terminations have been designed to perform in a wide range of weather condi tions Our terminations meet or exceed industry standards When selecting the locations of your horizontal terminations do not place the termina tion where water from eaves and adjoining rooflines may create a heavy flow of cascad ing water onto the termination cap If the cap must be placed where the possibility of cascading water exists it is the responsibility of the builder to direct the water away from the termination cap by using gutters or other means Take care to carefully follow the installation instructions for the termination including the use of silicone caulking where required NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE See Table 9 as an aid in venting component selection for a particular range of exterior wall thicknesses Venting Components Required for Various Exterior Wall Thick nesses when using Square Termination Kit SV4 5HT 2 Vent Components Required Exterior Wall Thickness
80. r or qualified service technician Deration At higher elevations the amount of BTU fuel value delivered must be reduced by either Using gas that has been derated by the gas company Changing the burner orifice to a smaller size as regulated by the local authorities having jurisdiction and by the USA National Fuel Gas Code NFPA 54 ANSI 2223 1 latest edition or in Canada the CAN CSA B149 1 codes latest edition Install the appliance according to the regulations of the local authorities having jurisdiction and in the USA the National Fuel Gas Code NFPA 54 ANSI 2223 1 latest edition or in Canada the CAN CSA B149 1 latest edition NOTE Flame appearance will diminish 4 per thousand feet NOTE Each model has two burners and 2 Orifices Burner Orifice Sizes Elevation 0 4500 feet 0 1372 meters Series drill size inches drill size inches 44 086 60J80 SSDVST SSDVPF Table 5 55 052 19152 Standard size installed at factory Standard size in LP conversion kit Part Cat Number Gas Valve Diagrams See Figure 7 for Millivolt models and Figure 2 For Electronic Models HI LO Variable Flame Height Adjustment Inlet Pressure Tap Manifold Pressure Tap Main Gas Control Knob Pilot Adjustment OFF PILOT ON Screw Figure 1 SIT Millivolt Gas Valve NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE ON OFF Switch Inlet Pressure Port Ma
81. rams illustrations and photographs are not to scale consult installation instruc tions Product designs materials dimen sions specifications colors and prices are subject to change or discontinuance without notice Appliance has a factory installed vent seal cap see Figures 15 and 16 on Page 13 in each flue outlet FIREPLACE SPECIFICATIONS SSDVST SEE THROUGH 25 1 4 4 61 Dimension Secure Vent 47 1 8 1194 Secure Flex 47 7 8 1216 W 289 10 12 97 4 267 Vent Center Vent no elbows PRODUCT REFERENCE INFORMATION Cat Model Ship No Volume H3333 SSDVST CNM 282 Ibs SSDVSTCNE 282 Ibs 52W x 27D x 44 1 2H 36 2 cu ft 52W x 27D x 44 1 2H 36 2 cu ft 7779088 O 61 NG 72 NG Steady State 73 VP 68 LP a T Detail fo Finish Wall Bracket 24 T 610 GAS ELECTRICAL INLETS o B INLET 3 76 10 1 2 gt Figure 12 267 Left Side View lt Side e Inches millimeters Minimum Framing Stud Size is 2 x 4 See side views of fireplace below for gas line inlet location options 11 3 8 48 12 1108 Gas Line Center of gas line is 3 in 76 mm up from floor Vent Framing Top Vent With One 90 Elbow Vent Framing Rear Vent With No Elbows nm a9 This dimension be reduced to 41 inches 1041 mm This resu
82. rface lev es et se tenir a distance afin d viter des br lures ou que leurs v tements ne s enflamment DO NOT ATTEMPT TO ALTER OR MODIFY THE CONSTRUCTION OF THE APPLIANCE OR ITS COMPONENTS ANY MODIFICATION OR ALTERATION MAY VOID THE WARRANTY CER TIFICATION AND LISTINGS OF THIS UNIT A WARNING Improper installation adjust ment alteration service or maintenance can cause injury or property damage Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier A WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change tothis appli ance and or its operating controls is dangerous A WARNING Clothing or other flammable material should not be placed on or near the appliance AVERTISSEMENT On ne devrait pas placer de v tements ni d autres mati res inflammables sur l appareil ni proximit WARNING Any safety screen or guard removed for servicing the appli ance must be replaced prior to operating the appliance AVERTISSEMENT Tout cran ou protecteur retir pour permettre l entretien de l appareil doit tre remis en place avant de mettre l appareil en marche WARNING Improper installation or use of this appliance can cause serious injury or death from fire burns explosion or carbon monoxide po
83. rtis very important The weight of the vent must not be supported by the fireplace in any degree Supportthe vertical portion of the venting system every 8 feet 2 4 m above the fireplace vent outlet One method of support is by utilizing field provided support straps conventional plumber s tape Secure the plumber s tape to the framing members with nails or screws Loop the tape around the vent securing the ends of the tape to the framing If desired sheet metal screws 6 x 1 2 length may be used to secure the support straps to the vent pipe See Figure 21 Support Straps 8feet 2 4 m Maximum mm minimum clearance to combustibles Figure 21 Another method where the vent is not adjacent to a wall is illustrated in Figure 22 on Page 16 Here support straps 96K93 and support plates 96K92 can be used to support the weight of the vent 15 16 SV4 5CGV 1 SV4 5FA or Hi Termination SV4 5FB Flashing and SV4 5SC Storm Collar As 25 4 when using secure Flex usi Firestop Spacer SF4 5VF Minimum Clearance to Combustibles SV4 5VF Firestop spacer Ceiling Framing sv4 5SP Support Plate OSV4 5SU Support Strap 8 ft 2 4 M Maximum d GO Secured to Vent with Appropriate Fasteners Figure 22 F Change vent direction to horizontal inclined run At transition from or to a horizontal in clined run install the SV4
84. s 1 If any of the original wire as supplied must be replaced use Type AWM 105 C 18 gage wire ONLY BLACK BLUE Optional Control Switch R RED W WHITE 2 120 VAC 60 Hz Less than 3 Amps W G GREEN Caution label all wires prior to disconnection when servicing controls Field Wired Wiring errors can cause improper and Factory dangerous operation Wired Schematic Representation Only Electronic Wiring Diagram Honeywell Showing Blower Wiring for Optional FBK 100 FBK 200 amp FBK 250 Kits Figure 46 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Step 6 CONNECTING GAS LINE All codes require a shut off valve mounted in the supply line The orientation of the shut off valve should face the front Figure 47illustrates two methods for connecting the gas supply A Sediment Trap is recommended to prevent moisture and debris in gas line from damaging the valve The flex line method is acceptable in the U S A where local codes permit however Canadian requirements vary depending on locality Instal lation must be in compliance with local codes These appliances are equipped with a gas flex line for use in connecting the unit to the gas line See Figure 47 for flex line description The flex line is rated for both natural gas and propane gas A manual shut off valve is also provided with the flex line The gas control valve is located in the lower control compartment Access the valve
85. s installed with one side flush with a wall the wall on the other side of the appliance must not extend beyond the front edge of the appliance In addition when the appliance is installed inthe middle ofa room the side walls surrounding the appliance must not extend beyond the front edge of the appliance See Figure 3 MINIMUM CLEARANCES Inches millimeters 1 2 13 Top Spacers Bottom of Appliance To Ceiling 64 1626 3 76 Top 1 25 4 Sides amp Bottom SERVICE CLEARANCES Feet meters Front amp Back Faces 3 ft 0 9 m Table 6 Note 3 in 75 mm above any horizontal inclined vent component Side Clearances Combustible materials may project beyond the sides of the fireplace opening as long as they are kept within the shaded areas illustrated in Figure 9 Combustible Materials Allowed In Shaded Area Safe Zone Com bustible Walls shown in dark gray At 14 mini mum side wall clearance a wall clearance combustible wall combustible can project to any wall can project length 12 14 At 8 1 4 side Lun Protected wall shown in white 8 1 4 209 Minimum Distance to Unprotected Side Wall Inches millimeters Figure 9 A WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifi cally approved with this appliance may result in property damage or personal
86. screwdriver remove and discard the three pressure regulator mounting screws Remove the pressure regu lator spring poppet diaphragm and bushing Discard all removed components Ensure the rubber gasket installed on the back of the replacement pressure regulator is properly positioned and install the new pressure regula tor using the new screws supplied with the kit Tighten screws to 25 In Ib torque 35 SIT Millivolt Gas Valve Pressure Regulator Remove Components Figure 61 Step 6 See Figure 62 and remove the pilot hood assembly to access the hexed pilot orifice Remove and replace the orifice with the one provided with the kit Orifice Figure 62 Electronic Appliances Step 7 Honeywell Electronic Valves See Figure 63 and the instructions provided with the kit Remove the slotted cap screw o ring pressure regulating adjusting screw and spring Retain all parts for possible later use Install new components from the kit Black cap and red spring for propane gas appliances Silver cap and stainless steel spring for natural gas appliances Manifold Pressure Test Port Slotted ap ew west Adjusting mM Screw Figure 63 Step 8 See Figure 64 and replace the pilot orifice as follows Remove the igniter assembly retainer clip and carefully remove the igniter assembly Remove the screw securing the pilot assembly to its mounting bracket Back off the flare nut at the end of th
87. sibility to ensure these warnings are properly affixed during installation These warning labels are a critical step in informing consumers of safe operation of this appliance ATTACHING SAFETY IN OPERATION WARNINGS It is required that the safety instruction labels furnished with the fireplace be affixed to the op eration and control point of the fireplace A safety instruction label must be affixed to the wall switch plate where the fireplace is turned on and off See Figure A or wall thermostat See Figure B and if used on the remote control handheld transmitter Figure C To properly complete the installation of this fireplace locate the multi lingual adhesive labels provided with the Care and Operation Instructions and proceed as follows 1 Locate the wall switch or wall thermostat that controls the fireplace verify the switch operates the fireplace by turning it on and off Clean the wall switch plate or wall thermostat thoroughly to remove any dust and oils Affix the label to the surface of the plate of the wall switch that controls the fireplace Figure A or the wall thermostat Figure B Choose the language primarily spoken in the home If unknown affix the English language label 2 faremotecontrolis used to control the fireplace locate the transmitter and clean it thoroughly to remove any dust and oils Affix the label to the surface of handheld transmitter Figure C Choose the language primarily spoken in the ho
88. st lock connection refer to Figure 20 on Page 15 All of the appli ances covered in this document are fitted with collars having locking inclined channels The dimpled end of the vent components fit over the appliance collar to create the positive twist lock connection A Plan the vent run Analyze the vent routing and determine the types and quantities of sections required 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm net section lengths are available It is recom mended that you plan the vent lengths so that a section joint does not occur within the space defined by ceiling joists roof rafters or wall studs Make allowances for elbows as indicated in Figure 23 on Page 16 Maintain a minimum 1 25 mm clearance to combustibles on the vertical sections Clear ances for the horizontal runs are 3 76 mm on top 1 25 mm on sides and 1 25 mm at the bottom B Frame exterior wall opening Locate the center of the vent outlet on the ex terior wall according to the dimensions shown in Figures 12 and 13 on Pages 10 and 11 Cut and or frame an opening 10 1 2 x 12 1 8 267 mm x 308 mm inside dimensions about this center C Frame ceiling opening If the vertical route isto penetrate a ceiling use plumb lineto locate thecenterabovethe appliance Cutand orframe an opening 10 1 2 x 10 1 2 267 mm x 267 mm inside dimensions aboutthis center refer to Figure 19 on P
89. stalled at any height above the appliance opening however do not allow anything to hang below the hood NOTE We recommend the use of high temperature paint rated 175 F or higher on the under side of the mantel Minimum Mantel Clearances 14 356 12 305 10 254 inches millimeters 8 203 Top of Appliance 6 152 4 102 12 10 8 6 4 2 305 254 203 152 102 51 Hood _ Front or Rear Face of Appliance gt Figure 7 Do not insulate this space above the appliance Do not insulate this space above the appliance Shelf Height see table Shelf Height see table Shelf Above Fireplace With Side Venting Shelf Above Fireplace With Top Venting To achieve the lowest possible shelf height use the side vent outlet Do not insulate space between appliance and the area above it Maintain the minimum height from appliance base to the underside of combustible materials used to construct a utility shelf as shown here SSDVST amp SSDVPF Shelf Height Inches millimeter Side Vent Straight Out Back Top Vent with One 90 Degree Elbow Secure Vent amp Secure Flex Secure Vent SecureFlex 41 1 8 1045 53 7 8 1366 55 5 8 1410 Figure 8 Shelf Height Minimum Clearances Appliance and Vent Clearances Maintain clearances from appliance to combustible materials as detailed in Table 6 with the following exception When the appliance i
90. t s supplied by the manufacturer shall be used in the installation of this ap pliance Seules les trousses de garniture fournies par le fabricant doivent tre utilis es pour l installation de cet appareil These appliances comply with National Safety Standardsandaretestedand listed by OMNI Test Laboratories Inc Report No 116 F 32 5 to ANSI Z21 88b in Canada CSA 2 33b and CAN CGA 2 17 M91 in both USA and Canada as vented gas fireplace heaters Both millivolt and electronic versions of these appliances are listed by OMNI Test Laboratories for installation in bedrooms and Manufactured Homes Misc Codes Standards The Installation must conform to local codes or in the absence of local codes with the National Fuel Gas Code ANSI 2223 1 NFPA 54 latest edition In Canada the current CAN CSA B149 1 installation code The appliance when installed must be electri cally grounded and wired in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 latest edition or the Canadian Electrical Code CSA C22 1 latest edition Provide adequate clearances around air open ings and adequate accessibility clearance for service and proper operation Never obstructthe front or back openings of the appliance These millivolt and electronic fireplaces are designed to operate on natural gas or propane gas only The use of other fuels or combination of fuels wil
91. tall the column 2 49 kPa for propane gas rear burner in the front burner s position ALWAYS TEST PRESSURES WITH THE VALVE j REGULATOR CONTROL AT THE HIGHEST Figure 66 SETTING NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE 38 NOTES 39 NOTES 39 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information HEARTH PRODUCTS Printed in U S A 2005 Lennox Hearth Products P N 700031M REV F 01 2011 1508 Elm Hill Pike Suite 108 Nashville TN 37210
92. the appliance top spacers but must not be sup ported by them or notched to fit around them All construction above the appliance must be self supporting DO NOT use the appliance for structural support Side Nailing Flanges The fireplace should be secured to the fram ing at the side s of the appliance using the factory provided nailing flanges Install the 8 nailing flanges as shown in Figure 11 using the existing screws Position the fireplace within the framing When required the tabs may be bent 90 degrees by hand or with the assistance of a hammer Use wood screws to secure the nailing flanges to the framing See Table 6 on Page 8 for clearances of framing members to cabinet parts The nailing flange itself can directly contact framing Floor Nailing Tabs Secure the fireplace to the floor as shown in Figure 11 SSDVST Shown SSDVPF No nailing flanges on end with glass panel Remove these screws and use them when installing nailing flanges A RW bs iR 7 Nailing Flanges Turn nailing tabs down and secure to floor with 8d nails or other appropriate fasteners on both sides of appliance which do not have viewing glass panels Figure 11 Nailing Flanges 10 SPECIFICATIONS Natural and Propane Gas BTU Input Co axial DV Vent Size NOTES 37 500 MV Low 30 000 4 1 2 Inner 7 1 2 Outer Vent Center Top Vent with one 90 degree elbow e Annual Fuel Utilization Efficiency Diag
93. tion the appliance within the framing and secure with nailing flanges Page 12 Route gas supply line to appliance location Page 13 Install the vent system and exterior termination Page 25 Field Wiring a Millivolt Appliances Install the OFF ON burner control switch and bring in electrical service line for forced air circulating blower op tional equipment b Electronic Appliances Connect 120 VAC electrical power to the appliance receptacle Page 26 Install blower kit optional equipment Page 27 Make connection to gas supply Page 28 Verify appliance operation Page 28 Install the logs decorative volcanic stone and glowing embers Page 30 Install glass door assem blies Step 10 Page 30 Adjust burner primary air shutter to achieve proper flame ap pearance Step 11 Page 31 Install the decorative trim and hoods Step 12 Page 32 Attach Safety in Operation Warnings Step 2 Step 3 Step 4 Step 5 Step 6 Step 7 Step 8 Step 9 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Step 1 FRAMING Framethese appliances as illustrated in Figures 12 and 13 on Pages 10 and 11 All framing details must allow for a minimum clearance to combustible framing members as shown in Table 6 on Page 8 If the appliance is to be elevated above floor level a solid continuous platform must be constructed below the appliance Headers may be in direct contact with
94. to any overhead ss see Figure 5 For projections exceeding 2 1 2 combustible projection of 2 1 2 64 mm or le 64 mm see Figure 5 For additional vent loc Termination Heights For Vents Above Flat Or Sloped Roofs Ref NFPA 54 ANSI 2223 1 Roof Pitch Feet Flat to 6 12 1 0 6 12 to 7 12 1 25 7 12 to 8 12 1 5 8 12 to 9 12 2 0 9 12 to 10 12 2 5 10 12 to 11 12 3 25 11 12 to 12 12 4 0 12 12 to 14 12 5 0 14 12 to 16 12 6 0 16 12 to 18 12 7 0 18 12 to 20 12 7 5 20 12 to 21 12 8 0 Meters 0 3 0 38 0 46 0 61 0 76 0 99 1 22 1 52 1 83 2 13 2 29 2 44 ation restrictions refer to Figure 6 on Page 7 Horizontal Vent Termination Clearances Combustible Projection 2 1 2 inches or less in length Combustible Projection greater than 2 1 2 inches in length Ventilated Soffit Unventilated P 12 12 152 457 mm 305 mm Fd Side Elevation View Termination Kit Figure 5 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE All horizontal terminations may he located as close as 6 152mm to any non combustible and combustible exterior sidewall This distance may he decreased to 2 51mm for non combustible exterior sidewalls only if the SV4 5HT 2 termination is used Termination Kit Qm Note See Figure 34 on Page 20 for the exterior wall recess allowances of the square horizontal termination EXTERIOR HORIZONTAL VENT TERMINATION CLEARANCE
95. uch as a plumber or gas fitter be hired to correctly size and route the gas supply line to the appliance Installing a gas supply line from the fuel supply to the appliance involves numerous considerations of materials protection sizing locations controls pressure sediment and more Certainly no one unfamiliar and unqualified should attemptsizing or installing gas piping Schedule 40 Black Iron Pipe Inside Diameter Inches Schedule 40 Pipe Length feet 0 10 10 40 40 100 100 150 150 200 Table 7 Propane Gas 3 8 1 2 1 2 1 2 1 2 NOTE DIAGRAMS amp ILLUSTRATIONS ARE NOT TO SCALE Notes All appliances are factory equipped with a flexible gas line connector and 1 2 inch shutoff valve see Figure 47 on Page 27 See Massachusetts Requirements on Page 4 for additional requirements for installations in the state of Massachusetts in the USA The gas supply line should Not be connected to the appliance until Step 6 Page 27 A pipe joint compound rated for gas should be used on the threaded joints Ensure propane resistant compounds are used in propane applications Be very careful that the pipe compound does not get inside the pipe It is recommended to install a sediment trap in the supply line as close as possible to the appliance see Figure 47 Appliances using Propane should have a sediment trap at the base of the tank Check with local building official forlocal code requirements i e are b
96. uire au minimum le risque d incendie d explosion ou la production de monoxyde de carbone pouvant causer des dommages mat riels des blessures ou la mort Le tecnicien agr est responsable de l installation de cettetrousse L installation n est pas ad quate ni complete tant que le bon fonctionnement de l appareil converti n a pas t v rifi selon les instructions du fabricant fournies avec la trousse Le fournisseur de service qualifi ayant r alis l installation assume les responsabilit s li es la conversion In Canada THE CONVERSION SHALL BE CAR RIED OUT IN ACCORDANCE WITH THE REQUIREMENTS OF THE PROVINCIAL AUTHORITIES HAVING JURISDICTION AND IN ACCORDANCE WITH THE RE QUIREMENTS OF THE CAN CSA B149 1 INSTALLATION CODE Natural Gas to Propane Gas Conversion Kits Fireplace Cat No Type model 85L65 FGCK DMOMNP 85L79 FGCK DMOENP LACONVERSION DEVRAETREEFFECTUEE CONFORMEMENT AUX RECOMMANDA TIONS DES AUTORITES PROVINCIALES AYANT JURIDICTION ET CONFORME MENT AUX EXIGENCES DU CODE D INSTALLATION CAN CSA B149 1 Propane Gas to Natural Gas Conversion Kits Fireplace Cat No Type model ee 85L72 Gas conversion kits are available to adapt your FGCK DMOMPN appliance from the use of one type of gas to the use of another These kits contain all the ecrans necessary components needed to complete the task including labeling that must be af fixed to ensure safe operation 85L86 F
97. x Hearth Products m s cercano para recibir etiquetas de instrucciones de seguridad adicionales gratuitas Juego de etiquetas de repuesto N de cat H8024 LENNOX HEARTH PRODUCTS 1 800 9 LENNOX Nota La etiqueta en ingl s es transparente con texto rojo Las etiquetas en franc s y espa ol son negras con texto blanco DIAGRAMAS DE ETIQUETAS DE SEGURIDAD ADVERTENCIA Vidrio y chimenea EXTREMADAMENTE CALIENTES Riesgo de quemaduras graves Siempre mantenga a los ni os alejados de la chimenea Figure C INSTALLATION ACCESSORIES Lee me Horizontal Square Termination With Firestop spacer H2246 amp Adapter 74L61 Vertical Termination Cap 6 Inch 152 mm Vent Section 12 Inch 305 mm Vent Section 24 Inch 610 mm Vent Section 3 36 Inch 914 mm Vent Section mm susus 48 Inch 1219 mm Vent Section Telescopic Section 1 1 2 to 7 1 2 effective length The following flashings come packaged with a storm collar s mus sus s mu Festa amp miso sus 7202 H246 SV4SHF Firestop Spacer Horizontal 3 1 1 spacing 10 Pack 8 He swsw Firestop Spacer Vertical 1 1 1 spacing 10 Pack 9 9693 SVASSU SuppotStap 12 17M52 SV4 5HGS 1 Termination Guard Square 1 pack for square termination 12 17M53 SV4 5HGS 12 Termination Guard Square 12 pack for square termination 13 87L02

Download Pdf Manuals

image

Related Search

Related Contents

Shure RK244G User Guide  1 - IRD  Part Two: Basic Maintenance and Management of Medical Equipment  Philips AVENT SCF750  2N VoiceBlue Next VoIP GSM Gateway User Manual  Bosch MFW1550 mixer  Zanussi CH 6029 GR Instruction Manual  Manual para Registro del Presupuesto 2011  Page 1 Page 2 AVANT DE COMMENCER... Manuel de I`utilisateur  Código de Barras  

Copyright © All rights reserved.
Failed to retrieve file