Home
        Nordyne Q4 Series User's Manual
         Contents
1.                                                 M 12  CHARGING  CHARTS  iinan                  13 16  ACCESSORY KIT TABLE             irre tecti een eripere ecco                                 17  WIRING DIAGRAM a aar aa a ct                       aaaeaii 18    SECTION 1     OWNER INFORMATION       WINTER HEATING    1  Outdoor air enters the heat pump    2  The cold  heat transfer section  outdoor coil   extracts the heat from the air as the refrigerant  evaporates from a liquid to a cold gas    3  The refrigerant  compressed to a hot gas by  the heat pump  carries the heat to the heat   transfer section  indoor coil     4  The hot  heat transfer section  indoor coil   releases the heatas the refrigerant condenses  from a gas to a liquid    5  The blower circulates the heat throughout  the home via the supply duct    6  Therefrigerant returns to the outdoor coil and  evaporates once again to absorb more heat     SUMMER COOLING    1  Indoor air enters the return air duct    2  The cold  heat transfer section  indoor coil   extracts the heat fromthe air asthe refrigerant  evaporates from a liquid to a cold gas     3  The refrigerant  drawn to the heat pump and    compressed to a hot gas  carries the heat  outdoors     4  The hot  heat transfer section  outdoor coil     releasesthe heatasthe refrigerant condenses  from a gas to a liquid     5  The heat pump  outdoor fan  discharges the    heat to the outside air     6  The refrigerant returns to the indoor coil and    evaporate
2.     1  Set the thermostat system switch to COOL  andthe thermostat fan switch to AUTO   See  Figure 1     2  Set the thermostat temperature selector to  the desired cooling temperature  The outdoor  unit fan  the indoor blower  and the  compressor will all cycle on and offto maintain  the indoor temperature at the desired cooling  level     NOTE  Ifthe thermostat temperature level is re   adjusted  or if the thermostat system switch is re   positioned  the outdoor unit fan and the  compressor may not start immediately  A  protective timer circuit holds the compressor  and the outdoor fan off for approximately six  minutes following a previous operation or the  interruption of the main electric power    To Operate Your Heat Pump For Heating        1  Set the thermostat system switch for HEAT  andthe thermostat fan switch to AUTO   See  Figure 1     2  Set the thermostat temperature selector to  the desired heating temperature  The outdoor  unit fan  the indoor blower  and the  compressor will all cycle on and off to  maintain the indoor temperature at the desired  heating level     NOTE  If the thermostat temperature level is re   adjusted  or if the thermostat system switch is re   positioned  the outdoor unit fan and the  compressor may not start immediately      protective timer circuit holds the compressor  and the outdoor fan off for approx imately six  minutes following a previous operation or the  interruption of the main electrical power     Emergency Heat     Some the
3.    GRAY    WHITE                     Reversing Valve  Solenoid            T  Compressor    Outdoor Fan    SMS Relay    Outdoor Fan    Motor Capacitor    On units with  no pressure  switch an  orange wire  will connect  Pin6 and T1    Blower Relay    Blower Motor    Note  See Installation  Instructions for specific blower  speed setting  setting shown is   not typical for all units     Terminal Block    DEFROST BOARD OPERATION      CLOSES DURING DEFROST  RATING  1 A MAXIMUM    CLOSED WHEN    Y    iS ENERGIZED  OPEN WHEN  Y  15 DEENERGIZED   PROVIDES  OFF  DELAY TIME OF 5 MIN WHEN  Y  IS DEENERGIZED     WITH        CLOSED AND  Y  ENERGIZED  COMPRESSOR RUN TIME IS ACCUMULATED     OPENING OF DFT DURING DEFROST OR INTERVAL PERIOD RESETS THE INTERVAL  TO        Note  See Installation Instructions for wiring   application  and information concerning  accessory kits and other options     Field Wiring Eu  Factory Wiring  Low Voltage    High Voltage          INSTALLER     PLEASE LEAVE THESE  INSTALLATION INSTRUCTIONS  WITH THE HOMEOWNER                 707885A  Replaces 7078850    Specifications and illustrations   subject to change without notice and   St  Louis  MO 707885A without incurring obligations   6 00                 
4.  are shipped from the factory with the  following     1  Zero clearance to combustibles   2  Multi speed direct drive blower    3  Blower Speed Relay    4  Horizontal or Down flow duct connections     The unit dimensions are shown in Figure 3     Optional field installed electric heater kits are  available in 9 kw and 15 kw heating capacities   A separate installation instruction document for  the electric heaters and their application  accompanies this one  A two stage heat 24VAC  thermostat should be used with electric heater  kits installed     SAFETY CONSIDERATIONS    It is the responsibility of the installer to ensure  that the installation is made in accordance with  all applicable local and national codes         N WARNING     Improper installation  service   adjustment  or maintenance may cause  explosion  fire  electrical shock or other  hazardous conditions which may result  in personal injury or property damage   Unless otherwise noted in these  instructions  only factory authorized  kits or accessories may be used with  this product  Noncompliance may void    the unit s warranty        Labels  Tags     When working with this  equipment  follow all precautions in the  literature  on tags  and on labels provided with  the unit and or approved field installed kits   The type of hazard and severity are described  on each label or tag     Pressures Within The System     This  equipment contains liquid and gaseous  refrigerant under high pressure  Installation or  servi
5.  outdoor installations  Choosing  the location of the unit should be based on  minimizing the length of the supply and return  ducts  Consideration should also be given to  availability of electric power  service access   noise  and shade  Sufficient clearance for  unobstructed airflow through the outdoor coil  must be maintained in order to achieve rated  performance See Figure 4 for minimum  clearances to obstructions     Air Filters     A suitable air filter must be installed  in the return air system  Air filter pressure drop  must not exceed 0 08 inches w c  at 300 fpm     Condensate Drain     Condensate is removed  from the unit through the 3 4  female pipe fitting  located on the front side of the unit   See Figure  5   Install a 2 inch condensate trap in the drain  line of the same size and prime with water   When connecting rigid drain line  hold the female  fitting with a wrench to prevent twisting  Do not  over tighten  Refer to local codes and  restrictions for proper condensate disposal  requirements    5       3 4  NPT Female  Drain Connector                   SUPPLY                         RETURN          Top View    1 8     1 75   Power Entry  Capped   Or    Q         1 25    Power Entry                   6            0 88    Control Wiring Entry    SUPPLY RETURN                                                                                                                         55 8    Back View       Side View    Center of Gravity Height  in inches     Q4S
6.  tete t doses          7  s Rigging and MOSUN   usd omite eee      eee e aed dete edes  7  s ROOTtop    ea           A ate AS s LL es 7  AIR DUCTS p                                                                        7    Unconditioned  Spaces  1    hcic ded    a RR RR FL RUE Rene da 7    Acoustical Duct WOrk        5                          8  e Horizontal to Down flow Conversion                     sssssssssseeeeeeeennennn enne 8   Olearan6es oe venis Ra teu tele techn Ads ELI LM aD IAM 8  ELECTRICAL WIRING           22 2 uertice cone tecta toc e a voe cuan ace cuz une ced          osuere rapa DE sd ial Dra              8                   E                                       8   BloWer Speed    en see titt         ES                             9  e Low Voltage Connections             ccccceccecceeeeeeeceeceeeeeaeeeceeeeeceaeeeeeaeeeesneeeeneeeeesieeeeseneeeess 9    ROOM  thermostat  5 n eie rn oie te i tci du e ERR be eis 9    Defrost Gycle Timet  52 ii e e                                  9  START UP AND SYSTEM CHECK                                                       10  gere ELE 10    System  Cooling te eno tr dee th te eeu rte he d               10    System  Healing                           tee  10                                     2  2   0                                                          11    Refrigerant Charging                                                  11      R    tine Maintenance   nprs aia          11  BLOWER TABLE ics digo          
7. 206   184   221 256   160  80 192   218   208   198   222 260   166   271 163  82 209   213   224 265   171   275   169   286   167  e          226 267   181   280   175   291   173  86                 256 269   191   282   184   295   178  88 285   194   298   187  90                    287   203   300   196  g                    303   205  Q4SA 048  OUTDOOR TEMPERATURE   F    70 75 80 85 90 95 100 105  Pres    Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   68 188   122  70 191 123   204   135  72 192   140   207   139   222   137   234   146   248   152  74 157   208   154   224   151   239   147   252   160   266   160  76 193   174   210   168   226 160   257   164   270   166   284   167  78 211 182   227 174   259   172   274   171   288   173   309   174  80 229 185   261 183   276   181   292   180   307   180  e     O   O   263   193   279   191   294   189   310   188            Ir O 297   199   312   197  86                 299   208   315   206                   317   215         Note  All pressures are listed in  psig  and all temperatures in deg  F                                      Sa     Shaded Boxes indicate flooded conditions     LLL LL      Rated Design Values  Suction Pressure will be lower than des                               ign value if indoor air    flow  entering dry bulb  or entering wet bulb temperatures are lower than design         Discharge temperatures greater than char
8. 5 34 176   126 186   132 52 206   143 62 227   155    Disch   Disch   Suc    Disch   Disch   Suc    Disch   Disch      Press   Temp   Press   Press   Temp  Press  Press  Temp                       14 136   122 21 151    123 28 165   123 35 180   124 43 193   129 53 213   139 63 234   149                                                  23H    15   143   120   22   156 121   29   170   121          183      44   200   126   54 220   134   64   241 143      16 150 162      Note  All pressures are listed in  psig  and all temperatures in deg  F                   119 30 119 187   120 123 55 227   130 65 248   136    115 194 116 118 57 241 121 67 262 124    Ss      Shaded Boxes indicate flooded conditions              Rated Design Values  Suction Pressure will be lower than design value if indoor air  flow  entering dry bulb  or entering wet bulb temperatures are lower than design                     Discharge temperatures greater than charted values indicates a refrigerant  undercharge                                        Hulo vSro      eiqer    Q4SA 036       OUTDOOR TEMPERATURE   F                                                                                                                                                              70 75 80 85 90 95 100 105  Pres    Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   72 189   153  74 190   167   204   158      76 190 184   205   170   219  78 191   201   
9. A 036  Q4SA 048    Q4SA 060       Figure 3  Dimensions             d    Figure 4  Minimum Clearances    UNIT INSTALLATION       Ground Level     When installing the unit at  ground level  provide a concrete mounting pad  separate from the building foundation  The pad  must be level to insure proper condensate  disposal and strong enough to support the unit s  weight  Refer to Figure 3  Make sure the slab  is a minimum of 2  above the grade and in an  area that drains well  See Figure 6      Rigging and Hoisting     The unit should be  lifted using slings and spreader bars  The  spreader bars are necessary to prevent damaging  the top of the unit s cabinet  Make sure that the  lifting equipment is adequate for the load  Refer  to Figure 3 for unit weights  Keep the unit in an  upright position at all times         N WARNING     To avoid the risk of property damage or  personal injury  it is the rigger s  responsibility to insure that whatever  means are used to hoist the unit are  safe and adequate            N CAUTION     All panels must be securely in place  when rigging and hoisting           The rigging must be located outside the unit s  center of gravity  Refer to Figure 3 for center of  gravity locations                                                                                                                       Condensate Drain    Figure 5  Condensate Drain    Rooftop     For rooftop installations use the  appropriate accessory roof curb and follow all  instruc
10. OM  BLOWER  RELAY    fh Green                   DEFROST  BOARD    Typical Wiring  Field Supplied   for 2 Stage Cool  1 Stage Heat                   External Static Pressure Drop   inches water column  Model Speed 0 1 0 2  Q4SA 036   High 1600 1510  Medium   1410 1330  Low 1130 1070  Q4SA 048   High 2200 2140  Medium  1940 1890  Low 1560 1510  Q4SA 060   High 2200 2140  Medium   1940 1890  Low 1560 1510                               12         Speed set at factory    Table 1  Q4 Blower Curves    EL                                          vSrO             1    Q4SA 036           Suc   Disch  Disch   Suc   Disch   Press   Press   Temp   Press   Press          OUTDOOR TEMPERATURE    F   20 30 40       Disch   Suc    Disch   Disch   Temp  Press  Press  Temp     133    Suc   Disch  Disch   Suc   Disch   Disch   Suc   Press   Temp   Press   Press   Temp   Press    Press  Temp  Press   Par  ms                 9         50        162 6                60        Disch   Press     22  22           Disch   Temp     181                                                                                                                                    158   7o   236   175    153 71 169  149 72 163  144 73 157  Q4SA 048  OUTDOOR TEMPERATURE         0 10 20 30 40 50 60  Suc   Disch  Disch   Suc   Disch   Disch   Suc   Disch  Disch   Suc   Disch   Disch   Suc   Disch  Disch   Suc   Disch  Disch   Suc   Disch  Disch   Press   Press   Temp   Press   Press   Temp   Press   Press   Temp  Press   Pr
11. Single Package Heat Pump    Installation Instructions  460 Volt Q4 Series                                                 IMPORTANT    Read these instructions thoroughly before starting the installation  Follow  all precautions and warnings contained within these instructions and on  the unit     These instructions are primarily intended to assist qualified individuals  experienced in the proper installation of heating and or air conditioning  appliances  Some local codes require licensed installation service per   sonnel for this type equipment  All installations must be in accordance  with these instructions and with all applicable national and local codes  and standards     TABLE OF CONTENTS    OWNER INFORMATION                                             3  kldaeluleyle lc                                              4  SAFETY CONSIDERATIONS                eirca ruit toda ce                   caeso se dadada cuida 5  a Eo AB E a CDU 5    Pressures Within The System    nennen nennen nennen 5  INSTALLATION REQUIREMENTS                                            5     EQUIPMENT           2   eee hohe                  5    v Requirements and Codes        c i e PERI Date      aaa RR aa FEAR 5          LOC ATION  sie        ore D aer Ee terio EOS Ce A EC Ee eb Fr de ed pics 5  gie E 5    Condensate DraMa          etie ul in tee edendo 5  UNIT INSTALLATION               2 1   2 2  22 22 1                                  esa nic usu rape          7  s Ground           eerte etui
12. ay result in damage and could  cause premature failure of the system   This warning should be followed at initial  start up and any time the power has  been removed for 12 hours or longer           Air Circulation     Leave the thermostat system  switch set to  Off  and set the thermostat fan  switch to  On   The blower motor should run  continuously  Check for air delivery at the  register s   Ensurethatthere are no obstructions  atthe registers orin the ductwork  Setthermostat  fan switch to    Auto        System Cooling   1  Set the thermostat system switch to  Cool   and the thermostat fan switch to    Auto      Gradually lower the thermostat temperature  switch below room temperature and  observe that the blower  compressor  and  fan energize  Check that air cooler than  room temperature is being discharged at  the register  Listen for any unusual noises    2  After allowing the unit to run for several  minutes  set the temperature selector above  room temperature  The fan        compressor  cycles off with the thermostat  The blower  should also stop unless fan switch is set to     ON    position     System Heating     Set the system thermostat  switch to HEAT and set the thermostat fan  switch to AUTO  Verify that the compressor   outdoor fan  and blower are energized  Check  for warm air at the supply registers     UNIT MAINTENANCE        N WARNING     To avoid risk of electrical shock  personal  injury  or death  disconnect all electrical  power to the unit before pe
13. cing should only be performed by qualified  trained personnel thoroughly familiar with this  type equipment     INSTALLATION REQUIREMENTS    Equipment Check     Before beginning the  installation  verify that the unit model is correct    for the job  The unit model number is printed on  the data label  All units have been securely  packaged at the point of shipment  After  unpacking the unit  carefully inspect it for  apparent and concealed damage  Claims for  damage should be filed with the carrier by the  consignee     Requirements and Codes     The installer must  comply with all local codes and regulations  which govern this type equipment  Local codes  and regulations take precedence over any  recommendations contained in these  instructions  All electrical wiring must be made  in accordance with local codes and regulations  and with the National Electric Code  ANSI NFPA  70  or in Canada the Canadian Electric Code  Part 1 CSA C 22 1  Air Ducts must be installed  in accordance with the standards of the National  Fire Protection Association  Standards for  Installation of Air Conditioning and Ventilation  Systems   NFPA 90      Standard for Installation  of Residence Type Warm Air Heating and Air  Conditioning Systems   NFPA 90B   these  instructions and all applicable local codes     NFPA publications are available by writing     National Fire Protection Association  Batterymarch Park  Quincy  Maine 02269    Unit Location     The Q4 series heat pump is  designed only for
14. ess  Temp  Press   Press   Temp   Press   Press   Temp  Press  Press   Temp   134   20   143   135   25   158   135   31   172   136 51   200   152   62   222   162  15 136   132 21 149   133 26 162   133 32 175   134 40 185   138 52 207   147 63 229   156  16 143 130 22 155 131 27 167 131 33 179 132 41 192 136 53 214 143 64 236 150  17 150   128   2   161 129   28 172 183 130 42 199 133 54 221 138 65 243 144  18 157 167   127 29 177 186   128 43   206   130 55 228   134 66 250   137  Fu pee pue          pus pom  er pus e  m  us     mm pur m  me ep or      n  20 122 179 123 45 220 124 57   242   125 68 264 125      Note  All pressures are listed in  psig  and all temperatures in deg  F        1     Shaded Boxes indicate flooded conditions              Rated Design Values  Suction Pressure will be lower than design value if indoor air  flow  entering dry bulb  or entering wet bulb temperatures are lower than design         Discharge temperatures greater than charted values indicates a refrigerant    undercharge                                          vl                                                       ez eiqer    Q4SA 060         19   139    13 129   124 20 145    Suc    Disch                Suc    Disch   Press   Press   Temp   Press   Press     OUTDOOR TEMPERATURE    F   20 30 40 50 60             Disch   Suc   Disch   Disch   Suc   Disch  Disch   Suc   Temp  Press   Press   Temp   Press   Press   Temp     127 EXE 127 172   128 51 199   148 61 220   161    125 160   12
15. g diagram  and  the unit rating plate  Connect the line voltage  leads to the corresponding terminals on the  contactor  or the circuit breaker when the field  installed circuit breaker kits are used  inside the  control compartment  Use only copper wire for  the line voltage power supply to this unit  Use  proper code agency listed conduit and a conduit  connector for connecting the supply wires to the  unit and for obtaining proper grounding   Grounding may also be accomplished by using  the grounding lug provided in the control box         N WARNING     The unit cabinet must have and  uninterrupted or unbroken electrical  groundto minimize personal injury if an  electrical fault should occur  This  ground may consist of electrical wire or  approved conduit when installed in  accordance with existing national or  local codes        Blower Speed     The blower speed is preset at  the factory for operation at the same speed for  heating and cooling  For optimum system  performance and comfort  it may be necessary  to change the factory set speed  To change the  blower speed     1  Disconnect all electrical power to the unit  and remove the service panel    2  Cut the wire tie holding the motor lead  bundle  See Figure 9 for detailed  information on the appropriate model and  speed desired    3  If the desired heating blower speed is  different than the cooling speed  remove  and discard the jumper wire between  terminals  6 and  4  on the blower relay   Place the desired heat
16. he supply duct work  Acoustical insulation must  be in accordance with the current revision of the  Sheet Metal and Air Conditioning Contractors  National Association  SMACNA  application  standard for duct liners  Duct lining must be UL  classified batts or blankets with a fire hazard  classification of FHC 25 50 or less  Fiber duct  work may be used in place of internal duct liners  if the fiber duct work is in accordance with the  current revision of the SMACNA construction  standard on fibrous glass ducts  Fibrous duct  work and internal acoustical lining mustbe NFPA  Class 1 air ducts when tested per UL Standard  181 for Class 1 ducts     Horizontal to Down flow Conversion     The  unit is shipped ready for horizontal duct  connections  If down flow ducts are required   the unit must be converted following the steps  below for both the supply and return ducts     1  Locate the duct cap inside the duct openings  and remove the screw holding it in place    2  Lift the cap out of the unit   The cap can be  pushed up from the bottom by reaching  through the fork slot     3  Cover the horizontal duct opening with the  cap  The insulation will be on the indoor side    4  Fasten the cover with screws and seal to  prevent air leakage     Clearance     The Q4 Series is approved for 0  inch clearance     ELECTRICAL WIRING    General     Electrical power wiring must be  made in accordance with all applicable local  codes and ordinances  and with the current  revision of the Nationa
17. inals and to the unit   s low  voltage pigtails as shown in Figure 10  A  system wiring diagram is also provided on  the inside of the control panel cover and in  Figure 8 of these installation instructions    4  Secure sub base or thermostat to the wall  using screws provided with the thermostat    5  If sub base is used  install the correct  thermostat housing to sub base    6  Refer to thermostat instruction sheet for  complete detailed mounting information     Defrost Cycle Timer     The defrost cycle timer  controls the time interval of the hot gas defrost  after the defrost sensor closes  It is located in  the lower left corner of the defrost control board  on the low voltage side of the control box  Three    9    interval settings are available  30 minutes  60  minutes  and 90 minutes  Time setting selection  is dependent on the climate where the unit is  being installed     Example 1  Dry climate of Southern  Arizona     90 minute setting is  recommended     Example 2   Washington   recommended     Moist climate of Seattle   A 30 minute setting is    Tosetthe cycle timer  place the timing pin on the  defrost control board to the desired time interval  post     Note  All units are shipped from the factory with  the default time setting of 30 minutes     START UP AND SYSTEM CHECK  Pre Start Check List     Verify that the unit is level to allow proper  condensate drainage      Verify that there is free airflow to and from  the outdoor coil and that all clearance  require
18. ing blower speed  lead on terminal 46 and the desired  cooling blower speed lead on terminal   4 of the blower relay  Use another wire  tie  field supplied  to bundle the  remaining motor leads         N CAUTION     To avoid personal injury or property  damage  make certain that the motor  leads cannot come into contact with  any uninsulated metal components of  the unit        Check all factory wiring per the unit wiring  diagram and inspect the factory wiring  connections to be sure none loosened during  shipping or installation     Low Voltage Connections    Room Thermostat     Several options are avail   able for a room thermostat depending on the  accessories installed with the unit  The avail   able thermostats recommended for use with the  Q4 units are listed with the accessories in Table  5  Select a thermostat which operates in con   junction with the installed accessories  The  thermostat should be mounted about five feet  above the ground on an inside wall  The ther   mostat should be kept away from drafts  slam   ming doors  lamps  direct sunlight  or in line with  the supply air flow     To install the thermostat    1  Position the sub base on an inside wall and  mark the mounting holes and thermostat  cable openings    2  Cut out the cable opening and route the  thermostat cable from the unit s low voltage  compartment to the thermostat location   The thermostat cable is supplied by the  installer    3  Connect the cable leads to the sub base or  thermostat term
19. l Electric Code NFPA 70  or in Canada CSA    22 1   Canadian Electrical  Code Part 1  If any of the original wire as  supplied with the unit must be replaced  it must  be replaced with material of the same gage and  temperature rating     Line Voltage     Before proceeding with the  electrical connections  make certain that the  voltage  frequency  and phase of the supply  source are the same as those specified on the  unit rating plate  Also verify that the service  provided by the utility is sufficient to handle the  additional load imposed by this equipment         N WARNING     To avoid the risk of electrical shock   personal injury  or death  disconnect  all electrical power to the unit before  performing any maintenance or service   The unit may have more than one  electrical power supply        See Figure 8 or the unit wiring label for proper  high and low voltage wiring  Make all electrical  connections in accordance with all applicable  codes and ordinances                                                  Figure 6  Ground Level Installation       Figure 7  Roof Top Installation    Use a separate branch electrical circuit for this  unit  A means of electrical disconnect must be  located within sight of and readily accessibility  to the unit  Internally mounted circuit breakers  are available as field installed options  These  circuit breakers can be used as an electrical  disconnect     Provide power supply  or supplies  for the unit in  accordance with the unit wirin
20. ments are met    e Verify that the duct workis sealed to prevent  air leakage      Verify that the line voltage power leads are  securely connected and the unit is properly  grounded        Verify thatthe low voltage wires are securely  connected to the correct leads on the low  voltage terminal strip     Q4SA 048D  amp  Q4SA 060D Blower Wiring    Blower Speed  Medium            Blower Leads Low  Red BRT3  Black BR T6  Gray BR T4  Blue TB T1  Violet TB T1  BR T     Blower Relay Terminal  number   TB T     Terminal Block Terminal  number     High  TB T2  BR T3  BR T6  BR T5  TB T1             Q4SA 036D Blower Wiring    Blower Speed    Medium            Blower Leads Low  Red BR T3  Black BR T6  Gray BR T4  Blue TB T1 TB T1  Violet BR T5 BR T5    Figure 9  Motor Lead Connection    High  TB T2  BR T3  BR T4                   10      Verify that all exterior panels are replaced  and securely fastened      Verify that the outdoor fan turns freely      Verify that the power supply branch circuit  overcurrent protection is sized properly    e Verify thatthe thermostatis wired correctly   The thermostat function switch should be  set to  Off and the thermostat fan switch  should be set to  Auto      Start Up Procedure  Close all electrical disconnects to energize the  system      N WARNING     If the unit is equipped with a crankcase  heater  allow 24 hours prior to  continuing the start up procedures to  allow for heating of the refrigerant  compressor crankcase  Failure to  comply m
21. rforming any  maintenance or service  The unitmay have  more than one electrical supply        Refrigerant Charging     The Q4 packaged  heat pumps are fully charged atthe factory   The  system refrigerant charge can be checked and  adjusted through the service ports provided in  the front panel  Use only gauge lines which have  a  Schrader  depression device present to  actuate the valve  Refrigerant charging must be  done by qualified personnel familiar with safe  and environmentally responsible refrigerant  handling procedures         N WARNING     The Q4 Single Packaged Heat Pumps  are shipped fully charged and ready for  installation  Whena systemis installed  according to these instructions  no  refrigerant charging is required  If  repairs make it necessary for  evacuation and charging  it should only  be done by qualified  trained personnel  thoroughly familiar with this equipment   Some local codes require licensed  installation service personnel to  service this type of equipment  Under  no circumstances should the owner  attempt to install and or service this  equipment  Failure to comply with this  warning could result in property  damage  personal injury  or death            N CAUTION     Use care when removing parts from  this unit  Personal injury can result  from sharp metal edges present in all  equipment of sheet metal construction        Routine Maintenance     Proper maintenance  is important to achieve optimum performance  from the heat pump  The ability 
22. rmostats will  include a system switch position termed EM HT  or AUX HT  etc  This is a back up heating mode  to be used only if there is a suspected problem   With the system switch set to EM HT  etc   the  compressor and outdoor fan will be locked off  and supplemental heat  electric resistance  heating  will be used as a source of heat   Sustained use of electric resistance heat in  place of the heat pump will result in an increase  in electric utility costs     4       SYSTEM SWITCH    FAN SWITCH    TEMPERATURE SCALES  TEMPERATURE SELECTOR    Figure 1  Typical Thermostat    Defrost     During cold weather heating  operation  the outdoor unit will develop a coating  of snow and ice on the heat transfer coil  This is  normal andthe unit will periodically defrost itself   During the defrost cycle  the outdoor fan will  stop  while the compressor continues to run and  heat the outdoor coil  causing the snow and ice  to melt  During defrost  there may be some  steam rise from the outdoor unit as the warm coil  causes some melted frost to evaporate     SPECIFICATIONS    Model Series Q4 Single Package Heat Pumps  are designed for outdoor rooftop or ground level  slab installations  The units are shipped ready  for horizontal duct connections and are easily  converted for down flow applications        Cooling  Thermostat    Furance  Thermostat       Double Throw  Double Pole Switch             To Heat Pump To Furance          Figure 2  Thermostat Interlock System       All models
23. s once again to absorb more heat     It is the sole responsibility of the homeowner to  make certain that heat pump has been correctly  set up and adjusted to operate properly     NORDYNE warrants the heat pump to be free  from defects in material or workmanship for a  period of one year  A warranty certificate with  full details is included with the heat pump  How   ever  NORDYNE will not be responsible for any  costs found necessary to correct problems due  to improper setup  improper installation  adjust   ments  improper operating procedure on the  part of the user  etc     Some specific examples of service calls which  are not included in the limited warranty are     1  Correcting wiring problems in the electrical  circuit supplying the heat pump     2  Resetting circuit breakers or other switches     3  Adjusting or calibrating of thermostat     To avoid misunderstandings at a later date   carefully review these responsibilities with your  dealer or service company     The heat pump system will heat and cool your  home and save your energy dollars     During the summer  a heat pump cools a house  by absorbing heat from within the house and  exhausting it outdoors  During the winter  a heat  pump heats a house by absorbing heat outdoors  and exhausting it indoors  This is an efficient  heating means because you pay for  moving   heat from outdoors to indoors  but do not pay to  generate the heat     3    OPERATING INSTRUCTIONS    To Operate Your Heat Pump For Cooling    
24. ssory Kits          8l    weibeig                               8           4    Convertible Packaged Heat Pump 460 Volt Three Phase    NOTES   Disconnect all power before servicing  1  Couper le courant avant de faire letretien     2  Employez uniquement des conducteurs    On units with  no pressure  switch an    1   2  For supply connections use copper conductors only   3    If any of the original wire as supplied with the furnace must be replaced  it must be  replaced with wiring material having a temperature rating of at least 105  C   For supply wire ampacities and overcurrent protection  see unit rating plate     el To Indoor  Thermostat    CONTROL    LOGIC  Defrost Control Board    BR   BLOWER RELAY   cc   COMPRESSOR CONTACTOR  CCH   CRANKCASE HEATER   IF EQUIPPED    DFT   DEFROST THERMOSTAT           OUTDOOR THERMOSTAT OPTIONAL   RVS   REVERSING VALVE SOLENOID   PS   PRESSURE SWITCH  SELECT MODELS    ODFR   OUTDOOR FAN RELAY    Be      INDICATES PLUG CONNECTION  LETTER INDICATES WHICH PLUG  1 6 INDICATES PIN NUMBER     en cuivre     To 460 VAC  Power Supply     Li 1 CCH  1        If Equipped     1  1  1 1      YELLOW              Ground On  Location  Provided   Inside   Compressor   Terminal    Detrost Control Board  Low Voitage Connections Switch         orange wire  will connect To  Pin 6 and   1 Discharge  Air Sensor              RED       3    To Indoor  Thermostat    High Pressure     Select Models          Economizer    LA Accessory Plug    EI    YELLOW    BLACK
25. ted values indicates a refrigerant    undercharge     Buljooy             29H    9L                               Duioo  vsro    ee eiqer    Q4SA 060       OUTDOOR TEMPERATURE   F                                                                                                                 Note  All pressures are listed in  psig  and all temperatures in deg  F                                OCO         Shaded Boxes indicate flooded conditions              Rated Design Values  Suction Pressure will be lower than design value if indoor air             70 75 80 85 90 95 100 105  Pres    Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   Pres    Temp   68 192   157  70   193   165   208   164      72 194   182   210   172  74 195   199   211  76 195   216   213  78 214  so       295   188   309   185  82         298   197   313   192    84 300   206   315   201  86        303   216   318   210              320   219          flow  entering dry bulb  or entering wet bulb temperatures are lower than design         Discharge temperatures greater than charted values indicates a refrigerant    undercharge                                29H       Q4 ACCESSORIES                                                 Circuit Breaker Kit Single Phase 913554  Circuit Breaker Kit Three Phase 913740       4 pole single circuit adapter kit  Single Phase Units Onl 913350  6 pole single circuit adapter kit  Single Phase Units Onl 913556    Descrip
26. tion Part Number   Roof Curb  8   Roof Curb  14    Manual Fresh Air Damper 547832  Economizer  downflow  Supply return transition  16   Supply return transition  18  547835  Concentric diffuser  flush  16   Concentric diffuser  flush  18  547837  Concentric diffuser  step down 16   Concentric diffuser  step down 18   Motorized Fresh Air Damper 547840  Economizer  horizontal  special order  Power Exhaust  downflow economizer  special order   Power Exhaust horizontal economizer  special order 547843  Hail guard 30x76  special order  see Note 1  Hail guard 34x76  special order  see Note 2   Filter Kit  Downflow  See Note 1 547887  Filter Kit  Downflow  See Note 2   Filter Rack  Downflow 547885  T stat  HP  2 stage htg 1 stage cool  auto    M  brand  T stat  HP  2 stage htg 1 stage cool  auto    I  brand   T stat  HP  2 stage htg 1 stage cool  manual    M  brand 912932  T stat  HP  2 stage htg 1 stage cool  manual    1  brand  T stat  AC  2 stage htg 1 stage cool    T  P  F  brand   T stat  HP  2 stage htg 1 stage cool    T  P  F  brand 917005  12  Flex duct adapter kit  14  Flex duct adapter kit 913812  12  Flex duct adapter kit  amp  P Trap  14  Flex duct adapter kit  amp  P Trap  Universal Hard Start Kit 912933  Low Pressure Switch Kit  High Pressure Switch Kit  Low Ambient Kit 913770  Outdoor Thermostat Kit 913852         913554         913556      Note 1  Q4SA 036     Note 2  Q4SA 048     Q4SA 060     Q4SC 036     Note 3  Q4SC 048K  Q4SC 060K    Table 4  Field Installed Acce
27. tions included with it  Locate the unit  according to local building codes and ordinances   The curb must be level to insure proper  condensate drainage  See Figure 7      The roof must be capable of handling the weight  of the unit   See Figure 3  for unit weights   Reinforce the roof if required     AIR DUCTS    This unit is designed only for use with a  supply and return duct  Air ducts should be  installed in accordance with the standards of  the National Fire Protection Association   Standard for Installation of Air Conditioning  Systems   NFPA 90A    Standard for  Installation of Residence Type Warm Air  Heating and Air Conditioning Systems   NFPA  90B   and all applicable local codes     Design the duct work according to methods  described by the National Warm Air Heating and  Air Conditioning Association  ACCA   The ducts  must be properly sized not to exceed  2  w c   pressure drop at 400 scfm per nominal ton of  cooling capacity     Duct work should be attached directly to the unit  flanges for horizontal applications  On roof curb  installations the ducts must be attached to the  curb hangers  not the unit     Unconditioned Spaces     All duct work passing  through unconditioned space must be properly  insulated to minimize duct losses and prevent  condensation  Use insulation with an outer  vapor barrier  Refer to local codes for insulation  material requirements     Acoustical Duct Work     Certain installations  may require the use of acoustical lining inside  t
28. to properly  perform maintenance onthis equipment requires  certain mechanical skills and tools  If you do not  possess these skills  contact your dealer for  maintenance  Consult your local dealer about  the availability of maintenance contracts  At a  minimum  routine maintenance should include  the following     1  Inspect and clean or replace air filters at  the beginning of each heating and cooling  season  or more frequently if required    2  Inspect the condensate drain and outdoor  coil atthe beginning of each cooling season   Remove any debris  Clean the outdoor coil  and louvers as necessary using a mild  detergent and water  Rinse thoroughly  with water    3  Inspect the electrical connections for  tightness at the beginning of each heating  and cooling season  Service as necessary         N CAUTION     The unit should never be operated  without a filter in the return air system   Replace disposable filters with the same  type and size        11    ECONOMIZER    PLUG  1                                        1         O1  I  C9                          1    Optional Check    INDOOR       Thermostat l  Optional Check  Instructions    0  Thermostat     Instructions        ECONOMIZER  PLUG                   ni                            OJN     On         I                              INDOOR  THERMOSTAT DEFROST THERMOSTAT  SUB BASE BOARD    Typical Wiring  Field Supplied   for 1 Stage Cool  1 Stage Heat    SUB BASE       Figure 10  Typical Thermostat Connection    FR
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
minox 35gt - Babar de Saint Cyr  指定居宅サービス等及び指定介護予防サービス等に関する  SuperMicro SuperServer 6023L-8R  取扱説明書 設置・工事編  Samsung RF266AEWP User Manual  Black & Decker WM2000 User's Manual  SiSky 2.0 User Manual    Samsung Combi Micro-onde (35L)  Viewsonic PLED-W200 data projector    Copyright © All rights reserved. 
   Failed to retrieve file