Lucent Technologies Uninterruptible Power Systems 3000 VA User's Manual
Contents
1. 3 Remove the cord connections to the back of the UPS The UPS enters Battery Mode for several seconds The Indicator turns off and the UPS shuts down 4 Turn the circuit breaker on all battery cabinets to the OFF O position 5 Disconnect the battery connector located on the UPS rear panel 6 Remove the UPS Power Input Connector Battery Connector ND LE Power Output Receptacle UPS Module J Battery Circuit Breaker Battery Module Bypass Y Cord Switch SEE BDM 60 Hz Figure 18 UPS with Bypass Module Rear Panel 60 Hz BDM Shown Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 UPS Operation Use the following procedure to reinstall the UPS and transfer the critical load from Maintenance Bypass AC Line operation to the UPS 1 Reconnect the battery modules to the battery connector on the UPS rear panel 2 Turn the circuit breaker on all battery modules to the ON position 3 Plug the Y cord of the Bypass Module into the power connectors on the UPS as shown in Figure 18 NOTE Steps 4 through 7 are for changing the output voltage The output voltage is factory configured for 230V If you do not need to change the UPS output voltage skip to Use the following table to select the correct output voltage according to your Bypass Module
2. mu Figure 1 Model 3000 UPS Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 1 Introduction UPS Model and Battery Configurations This UPS is designed to work with single phase three wire AC power sources There are two important considerations when selecting the UPS model and battery configuration to properly safeguard your equipment m Load requirements Load Requirements The load is the equipment to be protected by the UPS Select the UPS model that meets the power consumption requirements of the load in volt amperes VA The total load VA should not exceed the UPS VA rating To determine the total load requirements T Obtain the load ratings from either the nameplate or operators manual of the equipment to be protected by the UPS The ratings are listed in either watts W amperes or amperes max A or volt amperes 2 if the rating is in watts multiply by 1 4 to obtain the VA requirement this is the typical relationship between watts and volt ampere ratings in most computing equipment If the rating is in amperes or amperes max multiply by the input voltage to obtain the VA requirement 3 Add all of the resultant VA ratings together to obtain the total load requirements of the equipment to be protected see Figure 2 3 COMPUTERS 3 MONITORS EXTERNAL MODEM 200 WATTS 1 AMP EACH EACH AT 240V 50 VA 3 x 200 WA
3. Receptacles Battery Cord Bypass Switch Ao E Or E G a oo y Q Load Circuit Protectors Utility Input Connector BDM 60 Hz N Figure 5 UPS with BDM Rear Panel Depth of Unit 400 0 mm 15 75 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation 3 251 6 mm 7 9 91 4 Y Cord o NORMAL BYPASS Bypass Switch Output Breaker YY p Power Output Input Breaker ER Receptacles Utility Input LE G t onnector BIM 50 Hz mt TY Serial Port Power Input Connector 427 79 mm Battery _ Tie Wrap 16 84 Connector Mounts e Input Circuit Power Output Protector Receptacle REPO 3 UPS Module Receptacle e Battery Module Batte Circuit External Breaker Battery Connector Breaker Tie Battery Cord Figure 6 UPS with BIM
4. Figure 14 UPS Block Diagram Normal Mode During Normal Mode the Indicator illuminates and the front panel displays the percentage of UPS load capacity being used by the protected equipment see Figure 15 N a E an OVERLOAD J CD C CD CD N C C CO CO 12 Es a C O CD 13 an ep E Co Co OUTPUT ON ED an I EA gt c CD CD LOAD ON LOADON LOADON LOADON LOAD OFF APPROX APPROX APPROX APPROX NORMAL 81 100 61 80 41 60 0 40 UTILITY LOAD LOAD LOAD LOAD Figure 15 Normal Operation Indicators Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 UPS Operation 4 Bypass Mode The Indicator and the Indicator illuminate simultaneously indicating Bypass Mode see Figure 16 When the UPS is in Bypass Mode the load is powered by utility power However utility power continues to be passively filtered by the UPS CRI OVERLOAD 7 n 12 13 OUTPUT ON aw LOAD ON UNIT ON BYPASS Figure 16 Bypass Operation Indicators Battery Mode When the UPS is operating during a power outage the alarm beeps several times initially and then once every 10 seconds while in Battery Mode The Indicator illuminates The front panel displays the approximate percentage of battery capacity remaining see Figure 17 When the utility power returns the UPS switches to Normal Mode operation while the battery recharges
5. Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 5 Communication SELECT CUSTOM LAN CONFIGURATION Instructions Choose the desired contact configuration gt UTIL_FAIL is active closed LOW_BATT is active closed gt UTIL_FAIL is active open LOW_BA is active closed UTIL_FAIL is active closed LOW_BATT is active open gt UTIL_FAIL is active open LOW_BA is active open O e W D Hm Vv gt TO QUIT THIS MENU ENTER SELECTION gt gt Z gt Set Baud Rate allows you to select a new baud rate The Select Baud Rate Menu displays a list of baud rate options SELECT BAUD RATE 2 gt 300 4 gt 1200 5 gt 2400 6 gt 4800 7 gt 9600 8 gt 19200 O gt QUI THIS MENU ENTER SELECTION gt gt 5 To save the configuration settings type S at the Main Menu prompt The UPS operates and communicates under the new configuration and defaults to these settings each time it is started If you want to abandon the selections you have made type Q to quit NOTE Any changes you make to the UPS communications configuration must correspond to the communications equipment you are using In particular new baud rate selections for the UPS must match your communications equipment Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Communication 5 UPS Communications Interf
6. Power Cable Terminations Tightening Torque Wire Function Terminal Terminal Wire Entrelec Phoenix Position Size Rating Contact Input Ground l a 3 5 5 3lb in 5 6 6 8 lb in L 2 L2 Neutral 3 iu 3 5 5 3lb in ASTON Output LI 5 i 12 Neutral 6 Ground 8 due 3 5 5 3lb in 5 6 6 8 lb in o Connection 4 7 i Use 16AWG 1 5 mm 75 C copper wire minimum 23 Replace the terminal box cover 24 If you are using a Remote Emergency Power Off REPO switch follow the instructions in FREPO Installation on page 31 25 Start the UPS according to the UPS with Bypass Module Startup procedure on page 33 REPO Installation WARNING Only qualified service personnel such as a licensed electrician should perform the hardwired installation The REPO switch is a customer supplied switch that can disconnect UPS output voltage from your protected equipment To use a REPO switch you need external wiring and a switch with the following specifications m The switch should be a wall mounted momentary contact normally open pushbutton switch E Minimum ratings of 240 Vac and 35 mA m Wire should be 18 AWG minimum CAUTION The black and white REPO wires are at high voltage potential 240V Refer to your local electrical code for proper installation of the high voltage REPO wires Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 D 3 Installation 1 Place the conduit through the access hole on the ju
7. Load VA Load W 1 Module 2 Modules 3 Modules 600 402 36 8 88 146 800 533 27 6 66 110 1200 800 18 4 44 73 1600 1067 13 7 33 54 2000 1333 10 7 26 42 2500 1667 8 3 20 33 3000 2000 6 5 16 27 D NOTE If using an EBC refer to the EBC manual for approximate battery times Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 1 Introduction O Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 OAFETY WARNINGS CHAPTER IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS THIS MANUAL CONTAINS IMPORTANT SAFETY INSTRUCTIONS DANGER This UPS contains LETHAL VOLTAGES All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY There are NO USER SERVICEABLE PARTS inside the UPS CAUTION Batteries can present a risk of electrical shock or burn from high short circuit current Observe proper precautions CAUTION Proper disposal of batteries is required Refer to your local codes for disposal requirements CAUTION This UPS contains its own energy source batteries The output receptacles may carry live voltage even when the UPS is not connected to an AC supply CAUTION Never dispose of batteries in a fire Batteries may explode when exposed to flame CAUTION Never open or mutilate batteries Released electrolyte is harmful to the skin and eyes and may be extremely toxic CAUTION Use only the power supply cord provided with this UPS The power cord is wired in
8. Lucent Technologies Site Preparation Installation and Operator s Manual for Lucent Technologies Series 1 Uninterruptible Power Systems Model 3000 VA 200 240V Select Code 167 405 119 Comcode 407578822 DEFINITY is a registered trademark of Lucent Technologies IBM and AS 400 are registered trademarks of International Business Machines Corp Novell is a registered trademark of Novell Inc 3Com is a registered trademark of 3Com Corporation Copyright 1996 97 Lucent Technologies All rights reserved No part of this document may be reproduced in any way without the expressed written approval of Lucent Technologies Lucent Technologies Site Preparation Installation and Operator s Manual for Lucent Technologies Series 1 Uninterruptible Power Systems Model 3000 VA 200 240V Select Code 167 405 119 Comcode 407578822 Issue 3 Copyright 1997 Lucent Technologies All Rights Reserved Special Symbols The following common symbols may be found on the UPS H o DODGE LA e LOAD ON Press the button with this symbol to energize the output receptacles Output On LOAD OFF Press the button with this symbol to de energize the output receptacles Output Off SAFETY EARTHING TERMINAL Indicates the primary safety ground RISK OF ELECTRIC SHOCK Indicates that a risk of electric shock is present and the associated warning should be observed CAUTION REFER TO OPERAT
9. Ulostulorasioissa voi olla j nnite kun UPS ei ole liitettyn verkkoj nnitteeseen Varo l koskaan heit akkuja tuleen Ne voivat r j ht Varo l avaa tai riko akkua Paljastunut elektrolyytti on vahingollinen iholle ja silmille ja voi olla eritt in myrkyllist Varo K yt vain t m n UPS laitteen mukana toimitettua virtakaapelia Varmista ett UPS laitteen kanssa k ytetty pistorasia on johdotettu n iden samojen m ritysten mukaisesti jotta laite ei vahingoittuisi Varmista my s ett asennuksen yhteydess pistorasia varustetaan ylivirtasuojauksella Ty nn kosketin kokonaan pistorasiaan K yt pelk st n yksivaiheista kolmijohtoista maadoitettua vaihtovirtarasiaa Varo V hent ksesi tulipalon ja s hk iskun vaaraa asenna t m UPS sis tiloihin joissa l mp tila ja kosteus on s dett viss ja joissa ei ole virtaa johtavia ep puhtauksia Ymp rist n l mp tila ei saa ylitt 40 C l k yt l hell vett tai liian kosteissa oloissa 95 maksimi Varo l poista tai irrota sis ntulojohtoa kun UPS on kytkettyn T m poistaa turvamaadoituksen UPS laitteesta ja siihen liitetyst laitteistosta Varo Kansainv liset normit ja johdotusm r ykset vaativat ett kaikkien t m n UPS laitteen ulostulokytkent jen yhteinen maavuotovirta ei ylit 2 75 milliampeeria Varo P virtapistokkeen t ytyy olla 2 m n s teell laitteistosta ja k ytt j n saatavilla UPS
10. the appropriate serial interface 2 The alarm information is provided by the units RS 232 connector via the serial output pins and does not require an adapter interface UPS with Bypass Module Installation The Bypass Module is available in a 60 Hz Distribution Module or a 50 Hz Isolation Module each with a plug receptacle or hardwired option The Bypass Modules have a Maintenance Bypass feature that supplies power to your equipment even when the UPS electronics are removed for maintenance or upgrades The Bypass Distribution Module also provides 120V output Use the following procedure to install the UPS with a Bypass Module 1 Place the UPS near the equipment to be protected Make sure the UPS is well ventilated and away from direct sunlight or other heat source Do not place more than three battery modules in one stack The modules must be stacked in the correct order Figure 3 shows the Distribution Module and Figure 4 shows the Isolation Module NOTE You can install additional battery modules while the UPS is operating but make sure the UPS is not in see page 39 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation 3 Stacking Module Cover the smaller flanges without holes face toward the front UPS Module 1 4 20 x 1 2 Screws Battery Module __e Bypass Distribution Module BDM 60 Hz Caster Base Floor Mounting P
11. Battery Module Bypass Module Height 252 mm 9 91 in 252 mm 9 91 in 252 mm 9 91 in Width 142 5 mm 5 61 in 142 5 mm 5 61 in 142 5 mm 5 61 in Depth 400 mm 15 75 in 400 mm 15 75 in 400 mm 15 75 in Weight 7 4 kg 16 25 lb 23 6 kg 52 Ib 21 4 kg 47 lb Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 53 6 Specifications Model 3000 Specifications with the 60 Hz BDM Input Output Current Total not to exceed 2000 Watts 3000 VA Voltage In Out Current gt AOV 208V 120V 120V 120V 208V 240V 240V L14 30R L6 30R L5 30R 2x5 15R 2x5 15R L6 20R 16 20R L 30R 208 120 208 13 0A 14 4A 2 5A 2 5A 240 120 240 11 3A 125A 2 5A 2 5A 208 120 3 0A 25 0A 2 5A 2 5A 240 120 1 3A 25 0A 2 5A 2 5A 208 120 208 13 0A 2 5A 25A 144A 208 120 240 13 0A 12 5A 2 5A 2 5A 240 120 240 11 3A 2 5A 2 5A 12 5A 240 120 240 11 3A 2 5A 2 5A 12 5A Model 3000 Specifications with the 50 Hz BIM Output Current Voltage In Out er Total not to exceed 2100 Watts 3000 VA IEC 320 C19 IEC 320 C13 Hardwired 220 220 12 9A 13 6A 10 0A 13 6A 230 230 12 3A 13 0A 10 0A 13 0A 240 240 11 9A 12 5A 10 0A 12 5A Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 UPS Technical Specifications Specifications Input Voltage Range 160 to 276 Vac Bypass Isolation Module 187 to 276 Vac Input Voltage Range Input
12. Distribution Module BDM AC Line operation 41 installation 22 Maintenance Bypass feature 22 operation 41 power output receptacles 26 rear panel hardwired 29 plug receptacle 26 specifications 54 startup 33 utility input connector 26 Bypass Isolation Module BIM AC Line operation 41 installation 22 Maintenance Bypass feature 22 operation 41 power output receptacles 27 rear panel hardwired 29 plug receptacle 27 specifications 54 startup 33 utility input connector 27 Bypass Mode 39 Bypass switch 26 27 C changing the output voltage 41 communication interface port 51 modes 47 UPS 45 Index Communications Mode Reference Chart 52 configuration settings abandoning 50 displaying 48 front panel 46 saving 50 contact configuration serial port 51 Continuous Dump Mode 48 Control Keys Control C 47 Control E 48 cord power 33 55 Custom LAN Configuration Menu 49 customer service 59 D Data Dump Modes 48 diagnostics 40 Display Configuration Screen 48 exiting Main Menu 50 F front panel configuring communications 46 controls 37 display functions 37 indicators 37 front panel configuration 3Com 46 AS 400 46 Novell 46 printer mode 46 H hardwired Bypass Module rear panel 29 termination blocks 30 indicators front panel 37 input cord 33 55 Input On Indicator 37 Inverter Shutdown Control 49 L LAN Configuration
13. Ges 45 67 a Access Cover Conduit Access UL f Dm ET 120 Access Cover E AD utput Screw Conduit Access Figure 7 UPS with Hardwired Bypass Module Rear Panel CAUTION For Bypass systems with hardwired outputs overcurrent protection and suitably rated disconnect switches for the output AC circuit s are to be provided by either the protected equipment or the customer s distribution panel Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 3 Installation 21 Connect standard half inch conduit through the terminal access box see Figure 7 Jand hardwire to the terminal block See Figure 8 for the 60 Hz hardwired BDM wiring or Figure 9 for the 50 Hz hardwired BIM wiring Input Output H 208V 240V la 120V 21314 5 6 7 O 000000 O10101010101010 000000 1 1213 a s 6 7 8 Ground T J Ground Line 1 Neutral Line 2 Neutral Line 2 Line 1 Figure 8 60 Hz Hardwired BDM Terminal Block Input Output gt lt 220 230 240V ES 21314 5 6 7 OIOIOIOIOI OIOI O OIOIOIOIOIOIOIO OIOIOIOIOIOI OIO 1121314 5 6 7 8 Ground 1 Lo Ground Line Neutral Line Neutral Figure 9 50 Hz Hardwired BIM Terminal Block Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation 3 22 See the following table for specifications and tightening torque
14. Ne jamais se d barrasser de batteries en les incin rant Elles risquent d exploser lorsqu elles sont expos es une flamme ATTENTION Ne jamais ouvrir ou mutiler des batteries L lectrolyte qui s en chappe est nuisible la peau et aux yeux et peut s av rer extr mement toxique ATTENTION Utiliser uniquement le cordon lectrique fourni avec VUPS Ce cordon est cable conform ment aux sp cifications du Code lectrique international IEC S assurer que le c blage de la prise de courant murale devant tre utilis e avec PUPS est galement conforme ces m mes sp cifications afin d viter tout endommagement du mat riel S assurer que la prise de courant secteur est prot g e contre les surcharges au moment de l installation S assurer que la prise d entr e est enfonc e fond dans la prise murale Utiliser uniquement une prise secteur trois fils monophas e et mise la terre ATTENTION Afin de r duire les risques d incendie et de choc lectrique installer PUPS uniquement dans un espace int rieur temp rature et humidit contr l es et sans mat riel conducteur La temp rature ambiante ne doit pas d passer 40 C 104 F Ne pas utiliser proximit d eau ou dans une atmosph re excessivement humide 95 max ATTENTION Ne pas retirer le cordon d alimentation lorsque PUPS est sous tension Ceci supprime la mise la terre de s curit de PUPS et du mat riel connect ATTENTION Afin d tr
15. ONE TWPWNET UT Z H N un E Q Select a menu option by typing the corresponding letter or number key All menu selections are single keystrokes and are not case sensitive D gt Display Configuration displays the current communication settings and the new settings that you have selected prior to saving them The new settings are not effective until you select save from the Main Menu Catalog D3023002202C Serial BP174C0998 Version 3 05 COMM mode Ser_Print Baud x100 024 LAN mode Novell Site Fault Detection Disabled New COMM ASCII New Baud 096 New LAN Novell Press space bar to continue NOTE Catalog Serial and Version are all identification numbers unique to your UPS and can also be found on the UPS nameplate 1 gt Continuous Dump The UPS regularly transmits status information to the computer Baud rates of 1200 to 2400 are recommended to reduce host computer overhead when using this mode 2 gt Polled Dump Status information is transmitted only when requested by a poll character Control E 3 gt Smart Dump Status information is transmitted when polled as in the previous mode However the transmission also occurs automatically whenever UPS status changes For example if there is a power outage UPS status information changes and is therefore automatically transmitted Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Communication 5 A
16. Power Factor 0 95 Typical Frequency Range 50 60 Hz 3 Hz Surge Protection IEC 801 4 Output Wave Form Sine wave Output Voltage without 200 208 220 230 240 Vac 3 Bypass Module Common Mode Noise Rejection gt 60 dB O 100 kHz Transverse Mode Noise gt 80 dB 100 kHz Rejection Input Cord Detachable 2 meter cord with L6 30P Outlets UPS Module IEC 320 1 Output Voltages and Outlets 120 208V 16 30R or L14 30R 4x5 15R with BDM 120 240V L6 30R or L14 3OR 4x5 15R 120 L5 30R 4x5 15R 208V Hardwired 120 208V 2AOV Hardwired 120 240V Output Voltages and Outlets 208V available with Model 2500 only with BIM 220 230 240V 1 x IEC 320 C19 3 x IEC 320 C13 220 230 240V Hardwired 220 230 240V Batteries 10 per Module 12 Vde 5 Ah maintenance free rechargeable lead acid Battery Module 120 Vde Operating Environment Temperature 10 C to 40 C 50 F to 104 F Humidity 5 to 95 noncondensing Agency Approvals Safety EN5009 1 1 UL 1778 cUL EMC FCC Part 15 Class A EN5009 1 2 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 6 6 Specifications 56 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 ROUBLESHOOTING CHAPTER MA The UPS is designed for durable automatic operation and also alerts you whenever potential operating problems may occur Use the following
17. accordance with National Electrical Code NEC specifications Be sure the wall outlet to be used with the UPS is wired in accordance with these same specifications in order to avoid damage to your equipment Be sure that overcurrent protection for the AC outlet is provided at the time of installation Be sure the input plug is completely inserted into the wall outlet Use a single phase three wire grounded AC outlet only CAUTION To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 max CAUTION Do not remove or unplug the input cord when the UPS is turned on This removes the safety ground from the UPS and the equipment connected to the UPS CAUTION To comply with international standards and wiring regulations the total equipment connected to the output of this UPS must not have an earth leakage current greater than 2 75 milliamperes CAUTION The wall outlet must be within 2 meters of the equipment and accessible to the operator The on off switch on the UPS does not electrically isolate the internal Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 5 2 Safety Warnings parts Unplug the input cord from the wall outlet when disconnecting the unit for long periods of time CAUTION Please note that the ou
18. beeps All indicators flash simultaneously Press and hold the Output On button until the alarm beeps again Two indicators corresponding with the current setting remain flashing The output voltage is factory configured for 230V TV CD Sn ME Fu E ES VET OVERLOAD 7 2886 CD CD CD n a o CD 12 3 E i B o 13 E S 3 E OUTPUTON 1 EO ro D Lao CO n AQ CO UM O 59 O A CD 240V 230V 220V 208V Figure 12 Output Voltage Indicators Press the Output Off button to scroll through the output voltage options top to bottom Each time you press the button the UPS beeps and the next two indicators flash NOTE If you do not save a selection within two minutes the setup automatically aborts and switches back to the original configuration 7 Press and hold the Output On button until the alarm beeps to select and save the output voltage Failure to release the button immediately after the beep will cause the UPS to abort the setup Turn on the equipment that is connected to the UPS Press and hold the Output On button until you hear the UPS beep approximately one second of ES AL LA The Indicator remains lit and the Output On Indicator turns on The front panel displays the percentage of full load being applied to the UPS The UPS is now in Normal Mode with the load online See Normal Mode on page 38 for more information Lucent Technologies Mod
19. carrer The following sections describe UPS storage requirements and the installation and startup of the UPS Unpacking and Inspection Carefully unpack the UPS and battery modules making sure to retain the packaging materials Examine each unit carefully for any signs of damage and immediately notify your service representative if damage is present UPS and Battery Module Storage If you plan to store the UPS or battery modules prior to use store them in a cool dry environment Storage temperature should not exceed 35 C 95 F in order to preserve battery life For longer term storage energize the UPS and battery module for approximately 8 hours every 90 days in order to maintain battery charge Whenever the units are not energized make sure the circuit breaker on all battery modules is returned to the OFF O position see Figure 5 on page 26 Important Installation Notes Read Before Installing the UPS UPS applications requiring a serial interface or standard LAN interface may connect directly to the 25 pin UPS alarm interface PBX systems such as the DEFINITY Communications System and processor based applications such as Call Center Conversant or Voice Processing that use a Remote Management Board require an isolated contact closure interface that is provided by a special UPS Alarm Interface Adapter PEC 24433 CAUTION For alarm connection to all systems that require a contact closure versus a serial interface exc
20. factory configured for Printer Mode 2400 baud with Novell contacts To verify the initial UPS communications configuration you can m Look at the box label with the serial number communication mode is shown in the upper right corner m Use the Display Configuration option on the UPS Serial Communications Menu see page 47 If you want to change the UPS configuration settings use the front panel or the UPS Serial Communications Menu Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 45 5 Communication Front Panel Communications Access Before you access the front panel review the following configurations and note the indicator that corresponds with the communication mode NOTE Only the Printer Mode front panel options change the baud rate Use the Serial Communications Menujto select other baud rates see page 47 FRONT PANEL COMMUNICATION OPTIONS Printer Mode 2400 Baud Novell Contacts Select this mode for the power management software Mu E OVERLOAD 7 SX Il E D CD OUTPUTON CD gt Indicator Legend Unlit Amber Green Flashing Novell Style LAN Contacts Default Any baud rate other than 2400 or 19200 with Printer Mode or not Printer Mode Ko OVERLOAD H CD n 7 S 2 B OUTPUT ON 0000 FA CD 3Com LAN Manager Any communication mode and baud rate option OVERLOAD n B OUTPUT ON AS 400 Style LAN Conta
21. immediately after the beep will cause the UPS to abort the setup 6 Press the Output On button again to return the UPS to Normal Mode GD NOTE Printer Mode selections are the only serial communication modes available from the front panel UPS Serial Communications Menu With the UPS Serial Communications Main Menu you can view or select UPS communication modes baud rates and LAN configurations To change or display the current communications configuration 1 Connect the UPS serial port to a video monitor with a serial interface or to your computer s serial port If you are using shutdown software the UPS should already be connected to your computer 2 Set your terminal so that it matches the baud rate of the UPS usually 2400 baud 8 bits No parity 1 stop bit Refer to your terminal or operating system documentation for details on configuring your terminal communication settings 3 At the terminal prompt press Control C until the UPS Serial Communications Menu appears Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 D 5 Communication PS SERIAL COMMUNICATIONS MENU ELECT OPERATION MODE DISPLAY CONFIGURATION UMP Q Z 4 H a Q a un U MINAL MINAL UMP URATION T BAUD RATE IT WITHOUT SAVING NEW CONFIGURATION VE AND RESTART TON gt gt gt O GI J GO H O VV tu Q MMV VV VV VV VV
22. laitteen virtakytkin ei erist sis osia virran saannilta Irrota sis ntulopistoke jos kytket laitteen pois k yt st pitk hk ksi ajaksi Varo Ota my s huomioon ett UPS laitteen ulostulokoskettimissa on j nnite l sn aina kun painetaan kuormituskatkaisinta riippumatta virtal hteen tilasta Varo Bypass j rjestelmiss kiintealla asennuksella kuormana olevien laitteiden ylivirtasuojaus ja erotuskytkimet tulee toteuttaa kuormapiireissa Consignes de S curit Consignes Importantes De S curit Conserver Ces Instructions Cette Notice Contient Des Consignes Importantes De S curit DANGER Cet UPS contient des tensions mortelles Toute op ration d entretien et de r paration doit tre effectu e UNIQUEMENT PAR UN PERSONNEL QUALIFI AGREE L UPS n a AUCUNE PIECE REPARABLE PAR L UTILISATEUR ATTENTION Une batterie peut pr senter un risque de choc lectrique ou de br lure par un transfert d nergie ou un court circuit Prendre les pr cautions n cessaires Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 O 2 Safety Warnings ATTENTION Une mise au rebut r glementaire des batteries est obligatoire Consulter les reglements en vigueur dans votre localit concernant la mise au rebut de batteries ATTENTION Cet UPS contient sa propre source d nergie batteries Les prises de sortie peuvent tre sous tension m me lorsque PUPS n est pas branch sur le secteur ATTENTION
23. perioder Advarsel Bem rk at udgangsstikket p UPS en er str mf rende n r der trykkes p UPS ens bl output ON t ndt knap uanset om tilgangsledningen er frakoblet Advarsel For Bypass systemer med h rdledningsudgange skal overstromsbeskyttelse for vekslestrommens udgangskredslob forsynes af andre Advarsel For Bypass systemer med h rdledningsudgange skal egnede nominelle afbryderkontakter for vekslestrommens udgangskredslob forsynes af andre Belangrijke Veiligheidsinstructies Gevaar Deze UPS bevat LEVENSGEVAARLIJKE ELEKTRISCHE SPANNING Alle N reparaties en onderhoud dienen UITSLUITEND DOOR ERKEND SERVICEPERSONEEL te worden uitgevoerd Er bevinden zich GEEN ONDERDELEN in de UPS die DOOR DE GEBRUIKER kunnen worden GEREPAREERD Opgelet Batterijen kunnen gevaar voor elektrische schok of brandwonden veroorzaken als gevolg van hoge kortsluitstroom Volg de desbetreffende aanwijzingen op Opgelet De batterijen moeten op de juiste wijze worden opgeruimd Raadpleeg hiervoor uw plaatselijke voorschriften Opgelet Deze UPS bevat zijn eigen energiebron batterijen De uitvoercontactdozen kunnen onder spanning staan wanneer de UPS niet op een wisselstroom voeding is aangesloten Opgelet Nooit batterijen in het vuur gooien De batterijen kunnen ontploffen Opgelet Nooit batterijen openen of verminken Vrijkomend elektrolyt is schadelijk voor de huid en ogen en kan uiterst giftig zijn Opgelet Uitslui
24. 20 230 240V BDM 18 407483239 60 Hz BDM 240V 120V L5 30R PDMO1 407465889 Cord connected EPDM L14 30P with 4 5 15R2 s PDMO2 407465913 Cord connected EPDM L14 30P with 2 5 15R2 s and 2 L14 30R s PDMO3 407483361 Cord connected EPDM L14 30P with 2 5 15R2 s 1 L6 30R and 1 L6 20R PDMO4 407465905 Cord connected EPDM L14 30P with a hardwired output 2 pole 20A circuit breaker PDMO5 407483353 Cord connected EPDM L5 30P with 2 5 15R2 s 1 5 20R2 and 1 5 20R2 Canadian PDM06 407505858 Cord connected EPDM L5 3OP with 1 5 15R2 and 1 L5 50R Stacking Module 3 High 407483270 Stacking Module 4 High 407483288 Stacking Module 5 High 407483296 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Onbex Numeric 3Com Network Interface front panel configuration 46 LAN Configuration Menu 49 A AC Line Byass switch 41 operation 41 alarm silencing 59 UPS 58 Alarm Conditions Battery Fault 58 Over Temperature 58 Overload 58 Self Test Failure 59 Utility Out of Spec 58 AS 400 Network Interface front panel configuration 46 LAN Configuration Menu 49 ASCII Terminal Mode 49 battery configuration 2 extension time 3 installation 22 storage 21 Battery Fault alarm 58 Battery Mode 39 Battery Start 40 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Battery Test on Demand 40 baud rates 47 50 Bypass
25. 20 x 1 2 screws provided See Figure 3 or Figure 4 for part locations 3 Stack the modules onto the caster base according to the stacking order shown in Figure 3 or Figure 4 Make sure the first module nests on the base and each additional module nests on the preceding one If multiple Stacking Modules are used the caster bases may be secured together on the side with two of the 1 4 20 x 1 2 screws provided Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 25 3 Installation 4 Slide the cover over the stacked modules and secure with four of the 1 4 20 x 1 2 screws provided Tighten the screws until the cover s flanges are pulled flat against the caster base 5 Make sure the Bypass switch on the Bypass Module rear panel is in the NORMAL position see Figure 5 or Figure 6 427 79 16 84 Power Input Connector Battery Connector Serial Port Input Circuit Protector UPS Module Circuit Breaker mm Breaker Tie 2 J SA Tie Wrap Mounts Power Output Receptacle Battery Module REPO Receptacle External Battery Connector NORMAL BYPASS Y Cord Power Output
26. Bypass Module UPS Voltage Selection Model Number 60 Hz BDM 208 120 208 208 60 Hz BDM 208 120 240 208 60 Hz BDM 208 120 208 60 Hz BDM 240 120 240 Set to 220V for 110 220V BDM output Set to 230V for 115 230V BDM output Set to 240V for 120 240V BDM output 60 Hz BDM 240 120 Set to 220V for 110V BDM output Set to 230V for 115V BDM output Set to 240V for 120V BDM output 50 Hz BIM 208 Model 2500 only 208 50 Hz BIM 220 220 50 Hz BIM 230 230 50 Hz BIM 240 240 The UPS output voltage should be set according to local mains voltage 4 Press the Output Off button until the alarm beeps All indicators flash simultaneously Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 4 4 UPS Operation 5 Press and hold the Output On button until the alarm beeps again Two indicators corresponding with the current setting remain flashing The output voltage is factory configured for 230V Aa ED Au I Bu XCD ER MD OVERLOAD F FRE O CD I n a am ED E 12 CO GB gt 13 am am OUTPUT ON I CD I Co 1 E Jan E AS DO AY O AJ O AD 240V 230V 220V 208V Figure 19 Output Voltage Indicators 6 Press the Output Off button to scroll through the output voltage options top to bottom Each time you press the button the UPS beeps and the next two indicators flash NOTE If you do not save a selection within two minutes the setup automatically aborts a
27. EE E D C b OVERLOAD C C D C N ER C C 12 SS C 13 a gt OUTPUTON cm an a e BATTERY BATTERY BATTERY BATTERY BATTERY ONLINE ONLINE ONLINE ONLINE ONLINE gt 75 gt 50 gt 25 LOW SHUTDOWN CAPACITY CAPACITY CAPACITY BATTERY IMMINENT REMAINS REMAINS REMAINS WARNING Figure 17 Battery Operation Indicators If battery capacity becomes low while in Battery Mode the 13 Indicator begins to flash and the Output On Indicator remains lit indicating approximately two minutes before UPS shutdown The alarm beeps every two seconds When shutdown is imminent the Output On Indicator flashes These warnings are approximate and the actual time to shutdown may vary significantly Once these warnings are indicated immediately complete and save your work to prevent data loss and similar difficulties When utility power is restored after the UPS shuts down the UPS automatically connects to the load when the startup is complete Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 4 UPS Operation The UPS periodically performs diagnostic tests while the unit is operating in Normal Mode ensuring proper operation These tests include Self Test Utility Verification Test m Battery Discharge Test m Over Temperature Test The UPS also runs a series of over 20 internal tests when power is first applied Ifa diagnostic test fails see Chapter 7 Troubleshooting on page 57 Bat
28. Main Menu option 47 menu 49 laser printers 28 load definition 2 requirements 2 Load or Battery Conditions Indicators 37 LOW_BATT 49 M Main Menu 47 Maintenance Bypass feature See also Bypass Distribution Module BDM Bypass Isolation Module BIM activating 41 deactivating 43 Menu Custom LAN Configuration 49 LAN Configuration 49 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Main 47 Serial Communications 47 Set Baud Rate 50 Mode ASCII Terminal 49 Battery 39 Bypass 39 Communications 47 Data Dump 48 Normal 38 Printer 47 49 Terminal 49 VT100 Terminal 49 model specifications 53 N Normal Mode operation 38 Novell Network Interface front panel configuration 46 LAN Configuration Menu 49 O On Battery or Bypass Indicator 37 Operating Modes 38 Operation Battery 39 Bypass 39 Normal 38 UPS with Bypass Module 41 Output Off Button 37 Output On Button 37 Output On Indicator 37 output voltage changing 41 initial setting 33 Over temperature alarm 58 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Index Overload condition 58 Indicator 37 P physical UPS specifications 53 plug receptacle UPS installation optional REPO cord junction box 32 REPO switch 31 Polled Dump Mode 48 power management software 46 49 Printer Mode front panel configuration 47 Main Menu configur
29. NOTE This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications Operation of this equipment in a residential area is likely to cause interference in which case the user will be required to correct the interference at his own expense European EMC Statement Some configurations are classified under EN50091 2 as Class A UPS for Unrestricted Sales Distribution For these configurations the following applies WARNING This is a Class A UPS Product In a domestic environment this product may cause radio interference in which case the user may be required to take additional measures EC Declaration of Conformity Units that are labeled with a CE mark comply with the following EU directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact L
30. OR S MANUAL Refer to your operators manual for additional information BYPASS Indicates bypass control switches INPUT BREAKER Indicates the input breaker which shuts off utility power to the UPS electronics BATTERY BREAKER Indicates the battery breaker which shuts off battery power power transmission through the battery cord when in the OFF O position BATTERY CONNECTOR Indicates the battery connector which remains electrically hot even with the battery breaker off Keep covered when not in use OUTPUT BREAKER Indicates an output breaker y oE Batte Mod oem 00000000 o aston wer UPS with BDM Installation Quick START Je U BDM 60 Hz Bypass Distribution Module Bypass Switch NORMAL Position Battery Breaker NORMAL BYPASS Quick Start 4 OO A e JO EdE 5 The UPS output voltage is factory configured for 230V If you need
31. RVICEPERSONALE BRUKERE KAN IKKE UTF RE SERVICE P NOEN AV DELENE i UPS en Forsiktig Batterier kan for rsake elektriske st t eller forbrenning p grunn av h y kortslutningsstr m F lg instruksene Forsiktig Batterier m fjernes p korrekt m te Se lokale forskrifter vedr rende krav om fjerning av batterier Forsiktig Denne UPS en har en egen energikilde batterier Stikkontaktene kan v re str mf rende selv om UPS en ikke er tilsluttet en vekselstr mforsyning Forsiktig Kast aldri batterier i flammer da de kan eksplodere hvis de utsettes for pen ild Forsiktig Batterier m aldri pnes eller delegges Frigjorte elektrolytter er skadelige for hud og yne og kan v re ekstremt giftige Forsiktig Bruk kun den str mforsyningskabelen som f lger med denne UPS en Str mkabelen er koblet i overensstemmelse med spesifikasjonene i IECs International Electrical Code bestemmelser Sjekk at stikkontakten som anvendes for UPS en er koblet i overensstemmelsen med de samme spesifikasjonene for unng skade p utstyr Sjekk ogs at det finnes overstr mvern for vekselstr mkontakten under installeringen Sjekk at st pselet er f rt helt inn i stikkontakten Bruk kun en en faset tre tr det jordet vekselstromkontakt Forsiktig For redusere fare for brann eller elektriske stot bor denne UPS en installeres i et innendors miljo med kontrollert temperatur og luftfuktighet som er fritt for ledende forurensende sto
32. Rear Panel Depth of Unit 400 0 mm 15 75 6 Make sure the circuit breaker on all battery modules is in the OFF O position 7 Remove the battery connector guard Plug the battery cord into the battery connector on the UPS All battery connectors are polarized to prevent incorrect connection Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 3 Installation 12 13 If additional battery modules are to be used plug the battery cord of the second module into the external battery connector of the first battery module Follow this procedure for each additional battery module or Extended Battery Cabinet Remove the breaker tie from the circuit breaker on all battery modules or EBCs Turn the circuit breaker on all battery modules to the ON position Two tie wraps are included with the UPS to secure the Y cord to the input and output receptacles on the UPS rear panel Insert the tie wrap through the slot on each tie wrap mount Plug the Y cord of the Bypass Module into the power connectors on the UPS rear panel as shown in Figure 5 or Figure 6 Verify that the plugs are fully seated Loop the tie wraps around the Y cord connections and tighten to secure the cord to the rear panel NOTE Allow sufficient slack in the cord between the receptacle and the tie wrap At least 12 30 cm of slack is recommended 14 15 16 17 If your Bypass Module is a plug receptacle unit contin
33. TTS x 1 4 840 VA 3 x I AMP x 240 720 VA 50 VA 840 VA 720 VA 50 VA 1610 VA Total Load Requirements Figure 2 Volt Amperes Calculation Example If the total load requirements of the equipment exceeds the capacity of the UPS you must either reduce the equipment or use a UPS with a larger load capacity When deciding on which pieces of equipment to remove from the UPS select equipment that has a lower priority for power protection Computers monitors and modems typically have a higher priority because they could be processing or transmitting data when a power outage occurs Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Introduction 1 Battery Times for the UPS and BIM During a power failure the UPS battery supplies power to your equipment providing time to complete computing activities prior to UPS shutdown The duration of this time period is directly related to the UPS battery configuration By adding battery modules you can customize the UPS to provide enough battery time for normal processing activities Load V A EA Average Battery Time in Minutes G y IAF 1 Module 2 Modules 3 Modules 600 420 36 8 88 146 800 560 27 6 66 110 1200 840 18 4 AA 73 1600 120 13 7 33 54 2000 400 10 7 26 42 2500 750 8 3 20 33 3000 2100 6 5 16 27 Typical Power Factor PF Battery Times for the UPS with BDM Average Battery Time in Minutes
34. ace Port In addition to configuring the UPS for specific communication options you must also ensure proper use of the serial port when connecting the UPS to your network or monitoring equipment NOTE Semiconductor switch contacts are rated at a maximum current of 50 mA and a maximum of 40 Vdc across the contacts Do not apply any negative voltage to these contacts Use only the pins specified for your communications configuration The use of any additional pins for any of the following interfaces can cause interference with system communications Even though your network uses the specified signal lines the pins assigned to these signals at the network end of the cable may vary with those of the UPS serial port The connector body and style may vary as well G NOTE Standard pin for pin cables may not work correctly Consult your network software or server manuals for system shutdown pin assignments The UPS serial port complies with EIA RS 232 standards RS 232 specifies a maximum cable length of 50 feet See Figure 21 for the location of the serial port UPS Rear Panel Serial 9900000000090 Port 000000000000 Serial Port Detail 0000000000000 BOBODODOOOLLO Figure 21 Serial Port Location Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 51 5 Communication Communications Mode Reference Chart The following chart defines the UPS serial port contacts S
35. and manufacturing including ISO 9001 You now own the most reliable power protection available This family of UPS models provides a steady well regulated power supply for your computing and communications equipment while protecting it from the frequent irregularities that are inherent in commercially available power Voltage spikes power surges brownouts and power failures have the potential to corrupt critical data destroy unsaved work sessions and in some instances damage expensive hardware Now you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment The Bypass Distribution Module BDM and Bypass Isolation Module BIM have a Maintenance Bypass feature that supplies power to your equipment even when the UPS electronics are removed for maintenance or upgrades Figure 1 shows the Model 3000 UPS In addition an Extended Battery Cabinet EBC may be configured The installation of this product and connection to the battery modules is covered by a separate document shipped with the EBC 00000000 og Co MUL I 1 I gt TA I gt I gt
36. and to configure the UPS output voltage See on page 46 or anging the Output Voltage Jon page 41 OUTPUT ON Output On Button ALARM SILENCE UPS on load online Output Off Button UPS off load offline INPUT ON AL CB Input On Indicator OUTPUT OFF Indicator Legend Unlit OVERLOAD 77 e Overload Indicator Amber e Green LOAD OR am Il a r BATTERY 2 Load or Battery 30 Flashing CONDITIONS Conditions Indicators ei OUTPUT ON am Output On Indicator ON BATTERY On Battery or Bypass OR BYPASS Indicator Figure 13 UPS Front Panel Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 4 UPS Operation Operating Modes After you install and apply power to the UPS the UPS filters and regulates incoming AC power eliminating noise and voltage spikes and provides consistent power to your equipment see Figure 14 While power is applied to the UPS the maintenance free battery is automatically kept in a fully charged condition ai nn ns AC Input to BDM i Input Plug i EMI RFI Input dd Filter Circuit A i Es i bad Breaker aa N mas 3 UPS Load Fa LS I H BDM p I Optional Battery Module EBC Optional Battery Module Battery Module
37. ation 49 R rear panel BDM connectors 26 BIM connectors 27 hardwired 29 Remote Emergency Power Off switch See REPO switch REPO switch plug receptacle UPS 31 resetting the UPS 59 S Safety Warnings 5 seismic installation 25 mounting 25 Self Test failure 59 serial cable 51 serial port contact configuration 51 description 45 Index service 59 shutdown 41 Set Baud Rate Menu 50 storage 21 shutdown 41 unpacking and inspection 21 Smart Dump Mode 48 UTIL_FAIL 49 Startup Tests 40 Utility Out of Spec 58 storage temperature 21 Switch Bypass 26 27 V system requirements 2 volt amperes 2 T VT100 Terminal Mode 49 technical specifications 55 Terminal Modes 49 Tests Battery on demand 40 Startup 40 troubleshooting chart 57 tips 35 U uninterruptible power system UPS alarm silencing 59 alarms 58 block diagram 38 changing output voltage 41 communication 45 Communications Mode Reference Chart 52 front panel 37 installation 22 operations 37 resetting 59 Serial Communications Menu 47 48 serial port 45 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 FCC Statement The Lucent Technologies UPS configurations vary Some configurations may or may not be classified by the Federal Communications Commission FCC If your UPS is classified by these standards the corresponding information applies Class A
38. cts No Serial Select this mode for the monitoring software Pe ID OVERLOAD 7 CD OUTPUT ON 00080 Printer Mode 19200 Baud network devices Novell Contacts OVERLOAD Il B OUTPUT ON CA Bu 1000000 Figure 20 Front Panel Communication Options To access the front panel communication options perform the following steps If the UPS is powered on prepare your equipment for shutdown Press and hold the Output Off button until the long beep ceases approximately three seconds Unplug the UPS Wait until all indicators turn off and then continue to the next step Plug in the UPS while pressing the Output Off button until the alarm beeps All indicators begin flashing Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Communication 5 3 Press and hold the Output I Off button a second time until the alarm beeps again A single indicator corresponding with the current setting remains flashing 4 Press the Output Off button to scroll through the communication options top to bottom Each time you press the button the UPS beeps and the next indicator flashes NOTE If you do not save a selection within two minutes the setup automatically aborts and switches back to the original configuration B Press and hold the Output On button until the alarm beeps to select and save a communication option Failure to release the button
39. d retr D se i yp PP am DI B CD approximately 10 minutes Contact your service representative if OUTPUT ON CD allowing the UPS to cool down condition persists CED amp Weak battery while in Normal Allow the battery to charge for OVERLOAD 7 CD Mode The alarm beeps 24 hours then retest Have batteries ES replaced if condition persists 3 gt OUTPUTON OD Battery breaker is open 0 Make sure the battery module breaker MA O is in the ON position Battery module is not properly connected to the UPS Make sure battery cords are connected Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Troubleshooting 7 Condition Possible Cause Action gt B Weak battery while in Bypass This usually indicates that the OVERLOAD 7 CO Mode batteries need replacing or the UPS D reguires service Contact your service B E X representative OUTPUT ON gt DI GED B Self Test failure UPS internal The UPS may switch to Bypass Mode OVERLOAD H problem depending on the circumstances 5 CD Reset the UPS by pressing the B o Output On button until the alarm OUTPUTON 8 beeps MM E Contact your service representative if condition persists Resetting the UPS To reset the UPS while an alarm condition is present press the Output On button until the UPS alarm beeps Silencing the Alarm To silence the alarm for an existing fault press and h
40. dingcontactdoos moet zich op minder dan 2 meter vande apparatuur bevinden en makkelijk bereikbaar zijn voor de gebruiker De aan uit schakelaar op de UPS biedt geen elektrische isolatie voor de inwendige onderdelen De stekker uit de voedingcontactdoos halen wanneer het apparaat voor lange tijd niet wordt gebruikt Opgelet Neem er nota van dat de uitvoervoedingcontactdozen op de UPS altijd onder stroom staan wanneer de belastingschakelaar wordt ingedrukt ongeacht de aanwezigheid van de voeding Opgelet Voor Bypass systemen met vast bedrade uitgangen moet de overstroombeveiliging voor wisselstroom uitvoercircuit s door anderen worden geleverd Opgelet Voor Bypass systemen met vast bedrade uitgangen moeten de juiste hoofdschakelaars voor wisselstroom uitvoercircuit s door anderen worden geleverd T rkeit turvaohjeita Vaara T m UPS sis lt HENGENVAARALLISIA JANNITTEITA Kaikki korjaukset ja huollot on j tett v VAIN VALTUUTETUN HUOLTOHENKIL ST N TOIMEKSI T m UPS ei sis ll MIT N K YTT J N HUOLLETTAVIA OSIA Varo Akusto saattavat aiheuttaa s hk iskun vaaran tai sytty tuleen mik li akusto kytket n oikosulkuun Noudata asianmukaisia ohjeita Varo Akusto t ytyy h vitt s d sten mukaisella tavalla Noudata paikallisia m r yksi Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Safety Warnings 2 Varo T m UPS sis lt oman energial hteen akuston
41. e con le norme in merito al cablaggio tutta Vapparecchiatura collegata con l uscita del gruppo statico di continuit non deve avere una corrente di dispersione di terra superiore a 2 75 milliampere Attenzione la presa di alimentazione principale non deve trovarsi a oltre 2 metri dall apparecchiatura e deve essere accessibile all operatore L interruttore on off del gruppo statico di continuit non isola elettricamente i componenti interni Scollegare l unit dalla presa di alimentazione quando rimane in riposo per lunghi periodi di tempo Attenzione si noti che le prese di alimentazione di uscita del gruppo statico di continuit sono elettricamente energizzate ogniqualvolta viene premuto Vinterruttore azzurro di attivazione uscita a prescindere dal fatto che il gruppo statico di continuit sia alimentato o meno Attenzione nei sistemi Bypass provvisti di uscite cablate i dispositivi di protezione da sovracorrente per il i circuito i a corrente alternata in uscita devono essere forniti da terzi Attenzione nei sistemi Bypass provvisti di uscite cablate i sezionatori di corrente nominale adeguata per il i circuito i a corrente alternata in uscita devono essere forniti da terzi Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 2 Safety Warnings Viktig Sikkerhetsinformasion FArlig Denne UPS en inneholder LIVSFARLIGE SPENNINGER All reparasjon og service m kun utf res av AUTORISERT SE
42. e conforme aux normes et r glements internationaux de c blage le courant de fuite la terre de la totalit du mat riel connect la sortie de cet UPS ne doit pas d passer 2 75 milliamp res ATTENTION La prise principale secteur doit se trouver moins de 2 m tres du mat riel et tre accessible l utilisateur Vinterrupteur de marche arret de PUPS n isole pas lectriquement les pi ces internes D brancher le cordon d alimentation de la prise secteur en cas de d connexion de l appareil pour une p riode prolong e ATTENTION Veuillez noter que les prises de sortie de PUPS sont sous tension lorsque l interrupteur de charge est enfonc m me si le cordon d alimentation est d connect e du secteur ATTENTION Pour les syst mes Bypass ayant des sorties c bl es la protection contre une surintensit pour le s circuit s de sortie de courant alternatif doit tre fournie par un autre fournisseur 10 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Safety Warnings 2 ATTENTION Pour les syst mes Bypass ayant des sorties c bl es les interrupteurs de d connexion convenables pour le s circuit s de sortie de courant alternatif doivent tre fournie par un autre fournisseur Wichtige Sicherheitsanweisungen Anweisungen aufheben Dieses Handbuch enthalt wichtige Sicherheitsanweisungen A Vorsicht Lebensgefahr Diese USV enth lt T DLICHE SPANNUNGEN Alle Reparatur und Wartungsa
43. e unit plug the input power cord into the utility input connector on the Bypass Module rear panel Plug the other end of the power cord into a grounded three wire AC receptacle that has been wired in accordance with NEC specifications or national wiring rules See Figure 11 for an example Phase 1 N 200 208 220 230 240V N N Phase 2 Neutral o G gt International Ground Figure 11 L6 30 Receptacle NOTE Steps 4 through 7 are for changing the output voltage The output voltage is factory configured for 230V If you do not need to change the output voltage skip to Step 8 JUse the following table to select the correct output voltage according to your Bypass Module Bypass Module Model Number UPS Voltage Selection 60 Hz BDM 208 120 208 208 60 Hz BDM 208 120 240 208 60 Hz BDM 208 120 208 60 Hz BDM 240 120 240 Set to 220V for 110 220V BDM output Set to 230V for 115 230V BDM output Set to 240V for 120 240V BDM output 60 Hz BDM 240 120 Set to 220V for 110V BDM output Set to 230V for 115V BDM output Set to 240V for 120V BDM output 50 Hz BIM 208 Model 2500 only 208 50 Hz BIM 220 220 50 Hz BIM 230 230 50 Hz BIM 240 240 The UPS output voltage should be set according to local mains voltage Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 3 Installation Press the Output Off button until the alarm
44. el 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation 3 Troubleshooting Tips If you should encounter any problems during startup see the troubleshooting chart on page 57 The battery modules are shipped with the batteries charged However batteries may lose some of the charge during shipping and storage You can use the UPS immediately after unpacking but it may not provide the full rated backup time during a power failure Upon initial startup the UPS may need to operate for approximately 8 hours before the battery is fully charged and full battery backup time is available If the 13 Indicator flashes operate the UPS for 24 hours to fully charge the battery Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 35 3 Installation 36 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 OPs OPERATION CHAPTER This chapter covers the operation of the UPS including front panel functions operating modes using the Battery Start feature shutting down the UPS and using the Bypass Module UPS Front Panel The UPS front panel has three distinct functions m Displays the UPS operational mode Normal Bypass Jor Battery m Displays any alarm conditions present during operation the indicators flash m Displays the loading percentage during Normal Mode and the battery capacity during Battery Mode You can also use the front panel to configure UPS communication options
45. ept 3B2 do not connect the alarms without first installing the alarm interface adapter 3B2 systems require a different adapter shown on the following page Failure to install the alarm adapter will have an adverse effect on computer system operation Set the UPS for the required communication configuration according to Chapter 5 Communication on page 45 before connecting the load Failure to do this will require that the load be disconnected prior to setting the communication interface for proper alarm reporting configuration Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 21 3 Installation Systems That Require Contact Closure 1 This system has been set for the default alarm configuration For installations that require contact closures rather than a serial interface set the system for the AS 400 configuration as described in the manual shipped with this product The AS 400 configuration provides alarms which are normally open when the alarm is not present and closed when an alarm occurs This configuration does not have serial output 2 Connect the alarm adapter to the units RS 232 port and the modular output to the computer wallfield etc through an 8 pin modular plug Comcode PEC For 3B2 systems use 406707737 24024 For all other systems use 407691401 24433 Systems That Require a Serial Interface T Refer to the manual shipped with the product to configure the system for
46. erial communication is not available with 3Com and AS 400 network configurations Use only the applicable pins for the selected communication mode otherwise interference problems may occur Communication Function Signal Name Pin No True Condition Mode Serial Data to UPS RS232 TxD 2 N A Data from UPS RS232 RxD 3 N A Signal Ground 7 Novell Battery On ON AC 14 16 Open Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 Novell Battery On ON AC 14 16 Closed Lucent Technologies Default Low Battery TWO MIN 23 24 Closed Signal Ground 7 15 25 3Com Shutdown Remote SHUT DOWN 2 Positive Voltage Low Battery LOW BATT 9 Positive Voltage Battery On PWR FAIL O Positive Voltage Signal Ground 7 AS 400 UPS Available UPS Available 1 13 Closed Battery On Utility Failure 4 16 Closed Bypass UPS Offline 7 19 Closed Low Battery Low Battery 23 24 Closed Signal Ground 2 15 18 25 D NOTE Pin numbers separated by a forward slash are connected together internally Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 OPECIFICATIONS CHAPTER UPS Model 3000 Specifications Voltage VA Watts Input Current Output Current Online On Battery In Out BTU Hr BTU Hr 208 3000 2100 13 00A 14 42A 1081 1574 220 3000 2100 12 30A 13 64A 1006 1574 230 3000 2100 11 70A 13 04A 968 1574 240 3000 2100 11 30A 12 50A 923 1574 Parameter UPS Module
47. erstromschutz fiir die Ausgangswechselstromkreise anderweitig bereitgestellt werden Vorsicht F r Bypass Systeme mit festverdrahteten Ausg ngen m ssen Trennschalter f r die Ausgangswechselstromkreise mit passendem Nennwert anderweitig bereitgestellt werden Importanti istruzioni di sicurezza Pericolo la TENSIONE contenuta in questo gruppo statico di continuit LETALE Tutte le operazioni di riparazione e di manutenzione devono essere effettuate ESCLUSIVAMENTE DA PERSONALE TECNICO AUTORIZZATO All interno del gruppo statico di continuit NON vi sono PARTI RIPARABILI DALL UTENTE Attenzione le batterie possono presentare rischio di scossa elettrica o di ustioni Pp p provocate da alta corrente dovuta a corto circuito Osservare le apposite istruzioni Attenzione le batterie devono essere smaltite in modo corretto Per i requisiti di smaltimento fare riferimento alle disposizioni locali Attenzione questo gruppo statico di continuit contiene una fonte di energia autonoma le batterie Le prese di uscita possono condurre tensione energizzata quando il gruppo statico di continuit non collegato con una fonte di alimentazione a corrente alternata Attenzione non gettare mai le batterie nel fuoco poich potrebbero esplodere se esposte alle fiamme Attenzione mai aprire n mutilare le batterie poich Velettrolita da esse rilasciato nocivo alla cute e agli occhi e pu essere altamente tossico Attenzione usare e
48. es A Perigo O UPS contem VOLTAGEM MORTAL Todos os reparos e assistencia t cnica devem ser executados SOMENTE POR PESSOAL DA ASSISTENCIA TECNICA AUTORIZADO N o h nenhuma PECA QUE POSSA SER REPARADA PELO USUARIO dentro do UPS Cuidado As baterias podem apresentar o risco de choque el trico ou queimaduras provenientes de alta corrente de curto circuito Observe as instruc es adequadas Cuidado Siga os devidos regulamentos ao desfazer se das baterias Consulte os c digos do local para maiores informac es sobre os regulamentos de descarte de produtos Cuidado Este UPS cont m sua pr pria fonte de energia baterias Os recept culos de sa da podem conter voltagem ativa quando o UPS n o se encontra conectado a uma fonte de alimentac o de corrente alternada Cuidado Nunca se desfaca das baterias jogando as no fogo H risco de explos o quando expostas a chamas Cuidado Nunca abra ou danifique as baterias O eletr lito liberado prejudicial a pele e aos olhos e pode ser extremamente t xico Cuidado Utilize somente o cabo de alimentac o el trica fornecido com o UPS Este cabo foi manufaturado de acordo com as especificac es do IEC International Electrical Code Certifique se de que a tomada de parede foi montada de acordo com estas mesmas especificac es a fim de evitar damos ao seu equipamento Na hora da instalac o certifque se de que foi fornecida uma protec o contra sobrecarga de circuito para a tomada de cor
49. ew communication mode see Chapter 5 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 7 Troubleshooting Condition Possible Cause Action No output load voltage Load plug s not fully seated Verify load plug s are fully seated Load circuit protectors tripped Reset load protectors a Power requirements exceed UPS Your UPS continues to operate OVERLOAD 7 38 capacity If overload is greater Reduce load a E than 105 the alarm b D am than 6 the alarm beeps B en every second and the UPS may OUTPUT ON EB switch to Bypass Mode FA O JE E The UPS switched to Bypass Reduce load OVERIOAD 7 ZEE Mode because the overload If the Overload Indicator remains lit 5 increased above 105 The reset the UPS by pressing the B CD alarm beeps Output On button until the alarm OUTPUTON O beeps sa You may need to obtain a larger capacity UPS gt WB The utility line voltage and The inverter remains online deriving OVERLOAD CD freguency are out of power from the utility until it is no Di specification longer acceptable 12 s u ES Check the unit configuration OUTPUT ON CO Refer to the product specifications Co see page 53 gt GB UPS internal temperature is too Shut down the UPS Clear vents OVERLOAD 7 high The alarm beeps and the Remove any heat sources Wait ja UPS switches to Bypass Mode for approximately 5 minutes an
50. ffer Romtemperaturen m ikke overskride 40 C 104 F Den m ikke brukes i neerheten av vann eller ved meget hoy luftfuktighet 95 maks Forsiktig Stromforsyningskabelen m ikke fjernes eller trekkes ut n r UPS en er p slik at ikke sikkerhetsjordingen fjernes fra UPS en og det utstyret som er forbundet med den Forsiktig Alt utstyr som er forbundet med utgangen av denne UPS en m ikke ha en sterkere total lekkasjestr m enn 2 75 milliampere for v re i overensstemmelse med internasjonale standarder og forkablingsbestemmelser Forsiktig Stikkontakten m befinne seg innen 2 m fra utstyret og m v re tilgjengelig for operat ren Av P bryteren p UPS en isolerer ikke de interne delene Trekk ut ledningen fra stikkontakten n r utstyret frakoples over lengre tidsrom Forsiktig UPS ens stikkontakter for utgangsstr mforsyning er str mf rende n r lastbryteren trykkes uavhengig av str mforsyningen Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 Safety Warnings 2 Forsiktig For Bypass systemer med fastkoplete uttak m overstromvern for vekselstromuttak ene stilles til r dighet av andre Forsiktig For Bypass systemer med fastkoplete uttak m passende utkoplingsbrytere for vekselstromuttak ene stilles til r dighet av andre Regulamentos de Seguranca Instruc es De Serguranca Importantes Guarde Estas Instru es Este Manual Cont m Instru es De Seguran a Important
51. gt ASCII Terminal The UPS displays the formatted data on the attached video terminal B gt VT100 Terminal The UPS displays the formatted data on the attached video terminal P gt Printer Dump The UPS prints the formatted data on the attached printer L gt LAN Configuration allows you to configure the UPS for a new LAN mode and displays the Select LAN Configuration Menu SELECT LAN CONFIGURATION NOVELL AS400 3 COM LAN MANAGER CUSTOM CONFIGURATION TO QUIT THIS MENU O AUNE VVVVV ENTER SELECTION gt gt Select the AS400 option if you are using monitoring software to monitor the UPS The Custom Configuration option has two screens the first screen has options available for inverter shutdown and the second screen has options available for the contact configuration Consult your shutdown software documentation for details on the required signal states for configuring LAN communications ti SELECT CUSTOM LAN CONFIGURATION Instructions Choose the desired inverter shutdown function Warning It is recommended that this feature should not be used with normal RS 232 communications conflicts may occur gt Inverter shutdown control is enabled active HIGH 12V gt Inverter shutdown control is enabled active LOW 12V W gt Inverter shutdown control is disabled gt TO OUIT THIS MENU Q 10 ENTER SELECTION gt gt
52. icator turns off and the UPS shuts down 3 When all LEDs are no longer illuminated on the UPS switch the circuit breaker to the OFF O position on each battery module or cabinet Changing the Output Voltage To change the operating voltage of the UPS 1 Perform a UPS shutdown as described in the previous section 2 Follow the instructions in UPS with Bypass Module Startup on page 33 Using the Bypass Module The Bypass Module provides continuous online power for your equipment With the Bypass Module you can replace the UPS without losing power to the load Using Maintenance Bypass Use the following procedure to transfer the critical load to Maintenance Bypass AC Line operation and remove the UPS 1 Turn the Bypass switch on the Bypass Module to the BYPASS position see Figure T8 The Bypass Module is now powering your equipment from utility power 2 Press and hold the Output I Off button until the long beep ceases approximately three seconds The Indicator remains lit Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 41 4 UPS Operation
53. lar som ANVANDAREN KAN UTFORA SERVICE PA inuti UPS enheten Varning Batterierna kan ge elektriska st tar eller br nnskador fr n h g kortslutningsstr m F lj till mpliga anvisningar Varning Batterierna m ste kasseras enligt anvisningarna i lokal lagstiftning Varning Denna UPS enhet har en egen energik lla batterier De utg ende kontakterna kan vara sp nningsf rande n r UPS enheten inte r ansluten till en v xelstr msenhet Varning Anv nda batterier f r aldrig br nnas upp De kan explodera Varning ppna aldrig batterierna eller ta is r dem Utsl ppt elektrolyt r skadlig f r hud och gon och kan vara mycket giftig Varning Anv nd endast den kabel som medf ljer denna UPS enhet Kabeln r lindad enligt IEC specifikationerna International Electrical Code Kontrollera att det v gguttag som ska anv ndas med UPS enheten r draget enligt samma specifikationer s att skada p utrustningen undviks Kontrollera att det finns versp nningsskydd f r v Dxelstr msuttaget vid installationstillf llet Kontrollera att UPS kontakten r helt inskjuten i v gguttaget Anv nd endast ett enfasigt jordat v xelstr msuttag med tre ledare Varning Minska risken f r elektriska st tar genom att installera denna UPS enhet inomhus d r temperatur och luftfuktighet r kontrollerade och d r inga ledande f roreningar f rekommer Omgivande temperatur f r ej verstiga 40 Celcius Anv nd inte utrustningen n
54. late 1 4 20x 1 2 Screws Figure 3 UPS with Distribution Module Setup Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation Stacking Module Cover the smaller flanges without holes face toward the front Bypass Isolation Module BIM 50 Hz H N 1 4 20 x 1 2 Screws UPS Module Battery Module Caster Base Floor Mounting Plate 1 4 20 x 1 2 Screws Figure 4 UPS with Isolation Module Setup Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 Installation 3 2 If you are using the floor mounting plate complete Steps A and B This plate is required only for seismic applications but can also be used to prevent rolling or tipping of the assembled rack A For Seismic Installation Prepare the floor by referring to the hole pattern shown below The mounting plate has four 0 375 diameter floor mounting holes for earthquake bolts not provided Secure the plate to the floor WALL 11 0 minimum recommended for Y cabling Seismic Mounting Holes 16 16 Unit Depth P Y EM FRONT 3 5 30 A g La lt gt lt 125 Unit Width For Stability The plate does not need to be mounted to the floor but must be secured to the caster base to prevent the stack from rolling B Secure the caster base to the mounting plate using four of the 1 4
55. le elektricitetslov IEC For at undg beskadigelse af Deres udstyr b r De kontroller at stikkontakten hvor UPS en skal tilkobles ogs er tr df rt if lge disse specifikationer Kontroller at vekselstr mskontakten er forsynet med overstr msbeskyttelse under installeringen Kontroller at tilf rselsstikket er sat helt ind i stikkontakten Brug kun en enkelt fase tre ledning jordbundet vekselstr mskontakt Advarsel Installer UPS en i et temperatur og fugtighedskontrolleret milj frit for konduktiverende materiale for at reducere risikoen for brand og elektrisk st d Omgivelsestemperaturen m ikke overskride 40 C Betjen ikke udstyrer i n rheden af vand eller urimelig fugtighed 95 maksimum Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 Safety Warnings 2 Advarsel Fjern eller frakobl ikke indgangsledningen mens der er t ndt for UPS en Dette eliminerer den beskyttende jordbinding fra UPS en og Deres tilkoblede udstyr Advarsel For at overholde internationale standard og tr dforingsreguleringer m udstyret der er tilkoblet ydelsen af denne UPS ikke have afledningsstrom til jord p mere end 2 75 milliamperer Advarsel Stikkontakten skal vere hojest 2 meter fra udstyret og skal vare tilgangeligt til operatoren Hovedafbryderen p UPS en yder ikke elektrisk isolering til de interne dele Tag tilgangsledningen ud af stromforsyningens stikkontakt n r De onsker at frakoble gennem lengere
56. n Para cumplir con los est ndares internacionales y con las disposiciones sobre cableado la totalidad del equipo conectado a la salida de este UPS no debe tener una corriente de fuga a tierra superior a los 2 75 miliamperes Precauci n El tomacorriente de pared debe encontrarse dentro de los 2 metros de distancia del equipo y ser accesible para el operador El interruptor de encendido apagado en el UPS no aisla el ctricamente las piezas internas Desenchufe el equipo del recept culo principal cuando se encuentre desconectado por per odos prolongados Precauci n Tenga en cuenta que los recept culos salida en el UPS tendr n corriente cada vez que se haya pulsado la tecla agul de encendido de salida del UPS a pesar de que el cable de entrada est desconectado Precauci n Para los sistemas Bypass con salidas cableadas permanentamente la protecci n contra exceso de corriente para el los circuito s de CA de salida ser suministrada por terceros Precauci n Para los sistemas Bypass con salidas cableadas permanentemente los interruptores de desconexi n debidamente clasificados para el los circuito s de CA de salida ser n suministrados por terceros Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 17 2 Safety Warnings Viktig sakerhetsinformation Fara Denna UPS enhet inneh ller LIVSFARLIG SPANNING ENDAST AUKTORISERAD SERVICEPERSONAL far utf ra reparationer eller service Det finns inga de
57. nction box see Figure 10 Connect the exposed conduit wires to the corresponding compression terminals see the following table Tighten the compression terminals with a screwdriver 2 Pivot the REPO receptacle guard out of the way plug the REPO plug receptacle UPS connector into the REPO receptacle on the UPS rear panel see Figure 5 on page 26 or Figure 6 on page 27 Twist the connector in place Mounting Hol ii Plug Receptacle UPS Connector Access Hole S for Conduit L e Three Foot Cord Terminal Block D Sala IS 2 CJ pS Figure 10 REPO Cord Junction Box Power Cable Terminations Tightening Torque Wire Function Terminal Terminal Wire Entrelec Phoenix Position Size Rating Contact REPO LI TB1 4 12 22 AWG 3 2 TB1 5 4 0 mm 3 5 5 3 Ib in 5 6 6 8 lb in Ground TB 1 6 Suggested wire size is 18 AWG 0 75 mm 75 C copper wire minimum NOTE The REPO function activates when L1 and 2 are shorted together Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation 3 UPS with Bypass Module Startup To start up the UPS 1 Make sure the Bypass switch on the Bypass Module rear panel is in the NORMAL position see Figure 5 on page 26 or Figure 6Jon page 27 2 If your Bypass Module is a hardwired unit supply utility power 3 If your Bypass Module is a plug receptacl
58. nd switches back to the original configuration 7 Press and hold the Output On button until the alarm beeps to select and save the output voltage Failure to release the button immediately after the beep will cause the UPS to abort the setup 8 Press and hold the Output On button until you hear the UPS beep approximately one second The Indicator remains lit and the Output On Indicator turns on indicating the UPS is online 9 Turn the Bypass switch on the Bypass Module to the NORMAL position The front panel displays the percentage of full load being applied to the UPS The UPS is now in Normal Mode with the load online Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 GoMMUNICATION our IG The UPS is equipped with a communications interface port that allows communication with a wide variety of external devices including m Video or dumb terminal m Serial printer m Computer with power management or shutdown software The serial port enables you to monitor and record diagnostic data with the following communication interfaces m Serial Communications Interface Terminal Mode Data Dump Mode Printer Mode 2400 Baud with Novell Contacts default Printer Mode 19200 Baud with Novell Contacts m LAN Configuration Novell Style Network Interface 3Com Style Network Interface AS 400 Style Network Interface Custom User Configurable Interface Initial Communications Settings The UPS is
59. nt Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Safety Warnings 2 Precauci n Nunca abra o mutile las bater as El electrolito liberado es peligroso para la piel y los ojos y puede ser extremadamente t xico Precauci n Utilice solamente el cable de suministro de alimentaci n provisto con este UPS puesto que est cableado de acuerdo con las especificaciones del IEC C digo El ctrico Internacional Aseg rese de que el tomacorriente en la pared a utilizarse con este UPS est cableado en virtud de las especificaciones mencionadas para evitar as da os a su equipo Aseg rese de que en el momento de efectuarse la instalaci n el tomacorriente de CA haya recibido protecci n contra exceso de corriente Aseg rese de que el enchufe de entrada est totalmente insertado en el tomacorriente en la pared Utilice solamente un tomacorriente de CA fase nica tres hilos y con descarga a tierra Precauci n Para disminuir el riesgo de incendio o descargas el ctricas instale este UPS en un ambiente interior a temperatura y humedad controladas y sin contaminantes conductores La temperatura ambiente no debe superar los 40 C 104 F No lo haga funcionar cerca del agua o de condiciones de humedad excesivas 95 como m ximo Precauci n No retire ni desenchufe el cable de entrada mientras el UPS est encendido Esta acci n quita la descarga a tierra de seguridad del UPS y de su equipo conectado a l Precauci
60. old the Output On button for one second The alarm becomes quiet If UPS status changes the alarm beeps overriding previous alarm silencing Press the Output On button again to silence the alarm Service and Support The troubleshooting chart on page 57 covers most of the difficulties you may encounter during normal operations If you have any questions or problems with your UPS call your Lucent Technologies service representative or the appropriate telephone number on the service label of your UPS Please have the following information ready when you call Model number m Serial number m Version number if available m Date of failure or problem m Symptoms of failure or problem m Customer return address and contact information Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 59 7 Troubleshooting Parts List Item Comcode Description 3000 Electronics 407801968 UPS Module Battery Module 407464296 5 Ah Battery Module 1 String BDM 09 407505825 60 Hz BDM 208V Hardwired BDM 10 407496389 60 Hz BDM 208V 120V L5 30R BDM 11 407496397 60 Hz BDM 208V 120 240V 114 30R BDM 12 407464031 60 Hz BDM 240V 120 240V 114 30R BDM 13 407483247 60 Hz BDM 240V Hardwired BDM 16 407464304 50 Hz BIM 220 230 240V Hardwired BDM 17 407464049 50 Hz BIM 2
61. ra vatten eller vid h g luftfuktighet max 95 Varning Ta aldrig bort ing ngskabeln n r UPS enheten r p slagen Detta tar bort s kerhetsjordningen b de fr n UPS enheten och fr n den anslutna utrustningen Varning F r att verensst mma med internationell standard och dragningsf reskrifter f r inte den totala utrustning som anslutits till uttaget p denna UPS enhet ha jordslutningsstr m som verstiger 2 75 milliampere Varning Huvudkontakten m ste vara h gst 2 meter fr n utrustningen och inom r ckh ll f r anv ndaren UPS enhetens str mbrytare isolerar inte elektriskt de interna delarna Vid l ngre avst ngning b r UPS enheten fr nkopplas Varning Observera att UPS enhetens utkontakter r str mf rande n r den bl laddningsstr mbrytaren tryckts ned oberoende av om sp nningsk llan r tillkopplad eller inte Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 Safety Warnings 2 Varning Overstr msskydd f r de utg ende v xelstr mskretsarna ska tillhandah llas av andra f r Bypass system med fasta utg ngar Varning Bortkopplingsswitchar med passande dimensionering f r de utg ende v xelstr mskretsarna ska tillhandah llas av andra f r Bypass system med fasta utg ngar Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 2 Safety Warnings 20 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 ONSTALLATION
62. rbeiten sollten NUR VON AUTORISIERTEM WARTUNGSPERSONAL durchgef hrt werden In dieser USV befinden sich KEINE VOM BENUTZER ZU WARTENDEN TEILE Vorsicht Batterien k nnen aufgrund von Kurzschlufshochstrom Elektroschocks oder Verbrennungen verursachen Entsprechende Anleitungen befolgen Vorsicht Die Batterien miissen ordnungsgem fs weggeworfen werden Entsorgungsanweisungen sind den rtlichen Vorschriften zu entnehmen Vorsicht Diese USV enth lt ihre eigene Stromguelle Batterien An den Ausgangssteckdosen kann Spannung anliegen selbst wenn die USV nicht an eine Wechselspannungsguelle angeschlossen ist Vorsicht Batterien niemals verbrennen da sie explodieren k nnen Vorsicht Batterien nie ffnen oder gewaltsam aufbrechen Austretender Elektrolyt ist f r Haut und Augen sch dlich und kann extrem giftig sein Vorsicht Nur das Netzkabel verwenden das dieser USV beiliegt Dieses Kabel ist gem f den Spezifikationen des International Electrical Code IEC verdrahtet Sicherstellen dafs die Wandsteckdose die f r die USV verwendet wird gem fs den selben Spezifikationen verdrahtet ist um eine esch digung der Ger te zu vermeiden Sicherstellen daf bei Installation ein Uberstromschutz f r die Wechselstromsteckdose vorhanden ist Sicherstellen daf der Eingangsstecker vollst ndig in die Wandsteckdose eingesteckt wurde Nur eine einphasige geerdete Dreileiter Wechselstromsteckdose verwenden Vorsicht Um die Brand oder Elek
63. rente alternada Certifique se de que o plugue de entrada esteja completamente inserido na tomada de parede Utilize somente uma tomada de corrente alternada aterrada trifilar monof cica Cuidado Para reduzir o risco de inc ndios ou choques el tricos instale o UPS em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutiveis A temperatura ambiente n o deve exceder 40 C 104 F N o opero o pr ximo a gua ou em umidade excessiva m x 95 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 15 2 Safety Warnings Cuidado N o remova ou desconecte o cabo de entrada quando o UPS estiver ligado Isto remover o aterramento de seguranca do UPS e do equipamento conectado Cuidado Para estar de acordo com os padr es internacionais e regulamentos de fiac o o equipamento total conectado a saida deste UPS n o deve ter uma corrente de fuga a terra maior que 2 75 miliamp res Cuidado O soquete de alimentac o principal deve estar no m ximo dois metros do equipamento e acess vel ao operador O interruptor on off do UPS n o isola eletricamente as pecas internas Desconecte o do soquete de alimenta o se n o for us lo por um longo per do de tempo Cuidado Favor observar que o soquete de alimentac o de sa da no UPS estar eletricamente ativo todas as vezes que o interruptor estiver pressionado indiferente a presenca de energia el trica na rede de alimen
64. sclusivamente il cavo di alimentazione in dotazione con il gruppo statico di continuit Il cavo di alimentazione cablato in conformit con le specifiche del Codice Elettrico Internazionale IEC Assicurarsi che la presa a muro nella quale si Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Safety Warnings 2 deve inserire il gruppo statico di continuita sia cablata in conformita con le medesime specifiche onde evitare di danneggiare Vapparecchiatura Accertarsi che al momento dell installazione la presa a corrente alternata sia protetta contro le sovracorrenti Assicurarsi che la spina di ingresso sia completamente inserita nella presa a muro Usare esclusivamente una presa a corrente alternata monofase a tre fili collegata a terra Attenzione per ridurre il rischio di incendio o di scossa elettrica installare il gruppo statico di continuit in un ambiente interno a temperatura ed umidit controllata privo di agenti contaminanti conduttivi La temperatura ambiente non deve superare i 40 C Non utilizzare l unit in prossimit di acqua o in presenza di umidit eccessiva 95 max Attenzione non rimuovere n scollegare il cavo di ingresso quando il gruppo statico di continuit acceso poich in tal modo si disattiverebbe il collegamento a terra di sicurezza del gruppo statico di continuit e dell apparecchiatura ad esso collegata Attenzione per conformit con gli standard internazionali
65. tac o Cuidado Para sistemas Bypass com sa das conectadas a protec o de sobrecarga para circuitos de sa da de corrente alternada deve ser fornecida por outros Cuidado Para sistemas Bypass com sa das conectadas interruptores de desconex o devidamente qualificados para circuitos de sa da de corrente alternada devem ser fornecidos por outros Requisitos de seguridad Instrucciones importantes de seguridad Guarde estas instrucciones Este manual contiene importantes instrucciones de seguridad Peligro Este UPS suministro de alimentaci n permanente contiene VOLTAJES LETALES Todas las reparaciones y el servicio t cnico deber n ser realizados por PERSONAL DE SERVICIO TECNICO AUTORIZADO SOLAMENTE Este UPS NO CONTIENE PARTES QUE PUEDAN SER REPARADAS POR EL USUARIO Precauci n Las bater as pueden presentar un riesgo de descargas el ctricas o de quemaduras debido a la alta corriente de cortocircuito Preste atenci n a las instrucciones correspondientes Precauci n Es necesario deshacerse de las bater as adecuadamente Consulte las disposiciones locales para conocer cu les son los requisitos pertinentes Precauci n Este UPS contiene su propia fuente de energ a bater as Es posible que los recept culos de salida tengan tensi n cuando el UPS no est conectado a un suministro de corriente alterna CA Precauci n Nunca arroje las bater as al fuego ya que pueden explotar cuando son expuestas a las llamas Luce
66. tend het elektriciteitssnoer gebruiken dat bij deze UPS wordt geleverd Het snoer is volgens de specificaties van de IEC International Electrical Code bedraad Controleer of wandcontactdoos waarop de UPS wordt aangesloten volgens deze zelfde specificaties is bedraad teneindeschade aan uw apparatuur te voorkomen Controleer of Lucent Technologies Model 3000 UPS Operator s Manual 167 405 1 19 Issue 3 O 2 Safety Warnings er tijdens de installatie overstroombeveiliging voor het wisselstroom stopcontact wordt geleverd Controleer of de voedingsstekker goed in het stopcontact is gestoken Gebruik uitsluitend een enkelfasig geaard wisselstroom stopcontact met randaarde Opgelet Teneinde de kans op brand of elektrische schok te verminderendient deze UPS in een gebouw met temperatuur en vochtigheidregeling te worden geinstalleerd waar geen geleidende verontreinigingen aanwezig zijn De omgevingstemperatuur mag 40 C 104 F niet overschrijden Niet gebruiken in de buurt van water of bij zeer hoge vochtigheid max 95 Opgelet Verwijder het invoersnoer niet of haal de stekker van het invoersnoer er niet uit terwijl de UPS aan staat Hierdoor zou de UPS en uw aangesloten apparatuur geen aardebeveiliging meer hebben Opgelet Om aan de internationale normen en bedradingsvoorschriften te voldoen mag de gehele apparatuur die op de uitgang van deze UPS is aangesloten geen aardlekstroom van meer dan 2 75 milliampere hebben Opgelet De hoofdvoe
67. tery Test on Demand You can perform a battery test on the UPS while it is operating in Normal Mode by pressing the Output On button The UPS automatically distributes some of the load to the batteries for 30 seconds and tests the battery s performance NOTE Before using this feature the UPS must have been powered by utility power at least once This feature allows you to start the UPS without utility power After utility power has been unavailable for one minute press and hold the Output On button until the alarm beeps The UPS supplies power to your equipment and goes into Battery Mode The Indicator remains lit and the front panel displays the percentage of battery capacity remaining to the UPS This process should take about 15 seconds Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 UPS Operation 4 UPS Shutdown Performing a UPS shutdown turns off the power to your protected equipment Make sure the equipment is prepared for a power off before shutting down the UPS NOTE Do not perform a UPS shutdown if you want to use the Maintenance Bypass feature on the Bypass Module see Using the Bypass Module on page 41 To perform a UPS shutdown 1 Press and hold the Output 4 Off button until the long beep ceases approximately three seconds The Indicator remains lit indicating Normal Mode load offline 2 Unplug the UPS The UPS enters Battery Mode for several seconds The Ind
68. to change the output voltage see UPS with Bypass Module Startup on page 33 S IN CNS A Quick Start UPS with BIM Installation O GEE O N I 3508 2 2 8535 3 5 5 ae 82 eo 50 Aa 52 az es Tara Ever o o o 000000000 orm NORMAL BYPASS Bypass Switch NORMAL Position Quick Start am ere a C 0 0 5 The UPS output voltage is factory configured for 230V If you need to change the output voltage see UPS with Bypass Module Startup on page 33 ABLE OF CONTENTS 1 Introduction ccc cece cece cece cee ccc cece nenn Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 0 Table of Contents A Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 NTRODUCTION CHAPTER Congratulations on the purchase of your Lucent Technologies Series 1 uninterruptible power system UPS The Model 3000 VA UPS meets the toughest measures of superior design
69. tput sockets on the UPS are electrically live whenever the UPS Output On button is pressed even if the input cord is disconnected CAUTION For Bypass systems with hardwired outputs overcurrent protection for the output AC circuit s is to be provided by others CAUTION For Bypass systems with hardwired outputs suitably rated disconnect switches for the output AC circuit s are to be provided by others Sikkerhedsanvisninger Fare Denne UPS ubrudt str mforsyning indeholder LIVSFARLIG SP NDING Al reparation og service bor KUN foretages af AUTORISERET SERVICEPERSONALE Der er INGEN DELE i UPS en hvorp en BRUGER BOR FORETAGE SERVICE Advarsel Batterier kan give risiko til elektrisk st d eller forbr nding fra st rk kortslutningsstrom Observer korrekte forholdsregler Advarsel Korrekt afkastning af batterier kraves Henvend Dem til deres lokale love m h t affaldsreguleringer Advarsel Denne UPS indeholder en selvforsynende energikilde batterier Udgangskontakterne kan overf re stromforende spending n r UPS en ikke er forbundet med en vekselstr msforsyning Advarsel Br nd aldrig batterierne Batterierne kan eksplodere n r de uds ttes for flammer Advarsel Batterierne b r aldrig bnes eller skilles ad Udl st elektrolyt er skadeligt for hud og jne og kan v re yderst giftigt Advarsel Brug kun det el kabel der kom sammen med UPS en El kablet er tr dviklet if lge specifikationerne i den internationa
70. troschockgefahr zu verringern diese USV nur in Geb uden mit kontrollierter Temperatur und Luftfeuchtigkeit installieren in denen keine leitenden Schmutzstoffen vorhanden sind Die Umgebungstemperatur darf 40 C nicht bersteigen Die USV nicht in der N he von Wasser oder in extrem hoher Luftfeuchtigkeit max 95 betreiben Vorsicht Das Eingangskabel nicht entfernen oder abziehen w hrend die USV eingeschaltet ist weil hierdurch die Sicherheitserdung von der USV und den daran angeschlossenen Ger ten entfernt wird Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 D 2 Safety Warnings Vorsicht Um internationale Normen und Verdrahtungsvorschriften zu erf llen dirfen die an den Ausgang dieser USV angeschlossenen Ger te zusammen einen Erdschlufsstrom von insgesamt 2 75 Milliampere nicht berschreiten Vorsicht Die Netzsteckdose die zur Hauptversorgung verwendet wird darf sich nicht weiter als 2 Meter vom Ger t weg befinden und mufs fir den Bediener erreichbar sein Der Ein Aus Schalter der USV bietet keine elektrische Isolation der internen Teile Wenn das Ger t l ngere Zeit nicht benutzt wird sollte es von der Netzsteckdose abgezogen werden Vorsicht Beachten daf die Ausgangssteckdosen auf der USV jedesmal Strom f hren wenn der Belastungsschalter gedr ckt wird ungeachtet dessen ob die USV mit Strom versorgt wird Vorsicht F r Bypass Systeme mit festverdrahteten Eing ngen mu der Ub
71. troubleshooting chart to determine the UPS alarm condition Indicator Legend Unlit Amber GEB Green Flashing i YT TN Condition Possible Cause Action UPS does not turn on UPS is not plugged in Plug UPS into working outlet Dead wall socket Test wall socket repair as required UPS input breaker is tripped Reduce load then reset breaker Load does not turn on UPS has not been activated Press the Output On button for one second then release UPS beeps occasionally Normal operation None UPS is protecting your system UPS input breaker trips Load fault Check the load Disconnect faulty load equipment Wait several minutes before resetting the UPS input breaker Restart the load Indicator remains lit even though line voltage is present Utility line is out of specification Test wall socket repair as required UPS input breaker is tripped Reduce load then reset breaker UPS does not provide the expected backup time Low battery capacity Allow battery to charge for 24 hours then retest Protected equipment power requirements exceed UPS capacity Reduce load then retest Communications do not function properly Incorrect communications cabling Verify cable integrity see page 51 Incorrect baud rate Select a new baud rate see page 50 Incorrect communication mode Select a n
72. ucent Technologies Attn Quality Assurance Department
73. ue to Step 15 If your Bypass Module is hardwired skip to Step 19 If an Extended Power Distribution Module EPDM is required plug the EPDM into the power output receptacle on the Bypass Module rear panel The equipment to be protected by the UPS should be powered off Plug the equipment into the power output receptacles on the Bypass Module rear panel DO NOT protect laser printers with the UPS because of the exceptionally high power requirements of the heating elements If you are using a Remote Emergency Power Off REPO switch follow the instructions in REPO Installation Jon page 31 Start the UPS according to thef UPS with Bypass Module Startup procedure on page 33 Lucent Technologies Model 3000 UPS Operator s Manual 167 405 119 Issue 3 Installation 3 19 Refer to your national and local electrical codes for acceptable external wiring practices WARNING Only qualified service personnel such as a licensed electrician should perform the hardwired installation 20 Remove the three screws on the terminal block access cover with a Phillips screwdriver and remove the cover see Figure 7 NORMAL BYPASS Access Cover o e I L Access Cover Screw ai Screw CCOO E E O CO e Bypass Switch olololololo LD Input Breaker olojojojojo O L inal Block 0 e Terminal Bloc 1 2 Input