Honeywell TRADELINE Q7100D User's Manual

image

Contents

1. if drywall as marked For firmer material such as plaster or wood drill two 7 32 inch holes Gently tap anchors provided into the drilled holes until flush with the wall 4 Position the subbase over the holes pulling wires through the wiring opening 5 Loosely insert the mounting screws into the holes 6 Tighten mounting screws WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 9 through 15 for typical hookups A letter code is located near each terminal for identification CAUTION A Disconnect power before wiring to prevent electrical shock or equipment damage 1 Loosen the terminal screws on the back of the thermostat and connect the system wires See Fig 8 IMPORTANT Use 18 gauge color coded thermostat cable for proper wiring Securely tighten each terminal screw Push excess wire back into the hole Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat AON D Sh FORWRAPAROUND INSERTION STRIP INSERTION STRIP S11G IN GMM 7 16 IN 11 MM M4826 Fig 8 Proper wiring technique SUBBASE Oz Q Y x O O COMPRESSOR ii HEAT CONTACTOR RELAY OR VALVE COIL A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED M4831A Fig 9 Typical hookup of Q7100A1044 in a one stage heat and one stage cool conventional system 69 0931 3 Q7100A C D THERMOSTAT SUBBASES
2. ERMOSTAT SUBBASES 5 FEE 1 5 METERS Fig 1 Typical location of thermostat or remote mounted sensor SUBBASE 3 L temperature averaging network for a T7100 Q7100 Thermostat Subbase W Fig 2 Two T7047G Sensors providing a Fo Fig 4 Four T7047C Sensors providing a temperature averaging network for a SUBBASE T7100 Q7100 Thermostat Subbase SUBBASE Fig 3 Two T7047C Sensors and one T7047G Sensor providing a temperature averaging network for aT7100 Q7100 Thermostat Subbase Fig 5 Five T7047G Sensors providing a temperature averaging network for a T7100 Q7100 Thermostat Subbase 69 0931 3 2 SUBBASE como M4842 Fig 6 Nine T7047C Sensors providing a temperature averaging network for a T7100 Q7100 Thermostat Subbase Subbase Installation The subbase can be mounted horizontally on the wall or a 2 in x 4 in wiring box Position the subbase horizon tally on the wall or on a 2 in x 4 in wiring box 1 Position and level the subbase for appearance only The thermostat will function properly even when not level 2 Use a pencil to mark the mounting holes See Fig 7 WALL WIRES THROUGH WALL MOUNTING HOLES DE oe a MS MOUNTING LEDS SCREWS Me531 Fig 7 Mounting the subbase Q7100A C D THERMOSTAT SUBBASES 3 Remove the subbase from the wall and drill two 3 16 inch holes in the wall
3. Honeywell Q7100A C D Thermostat Subbases TRADELINE APPLICATION The Q7100 Thermostat Subbases provide electronic control of commercial 24 Vac single or multistage heat pump or conventional heating and cooling systems Select models have terminals for light emitting diodes LEDs remote temperature sensors and remote setback timer The LED models have up to two field configurable LEDs and up to two factory assigned LEDs Refer to Table 1 All Q7100 Thermostat Subbases require a common wire to the supply power Table 1 Description of Q7100 Subbases A _ DorF Gonvenional tor tor2 65 Co Eerr Heat pump tore rere 15 a Depends on the model RECYCLING NOTICE If this control is replacing a control that contains mercury in a sealed tube do 7ofplace your old control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application U S Registered Trademark Copyright 1996 Honeywell Inc e e All Rights Reserved INSTALLATION INSTRUCTIONS 3 Installer must be a trained experienced service technician 4 After completing i
4. OES NOT CYCLE TO TURN OFF THE EM HEAT GO TO SYSTEM SELECTION AND CHOOSE HEAT A SELECT MODELS HAVE LEDS A X2 AND X4 NEED TO BE JUMPERED TO TERMINAL X TEMPERATURE M4835 Fig 14 Typical hookup of Q7100C1008 in a two stage heat and two stage cool heat pump system Includes remote temperature sensor and remote setback timer SUBBASE REMOTE TEMPERATURE SENSOR A CAUTION EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A SELECT MODELS HAVE LEDS A X4 NEEDS TO BE JUMPERED TO TERMINAL X Fig 15 Typical hookup of Q7100C1073 in a three stage heat and one stage cool heat pump system Includes remote temperature sensor and remote setback timer Mounting Thermostat on Subbase Mount the thermostat on the subbase after the subbase is installed 1 Engage tabs at the top of thermostat and subbase See Fig 16 2 Press lower edge of case to close and latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermostat remove top last B PRESS LOWER IMPORTANT T Refer to the thermostat installation instructions for Installer Setup Settings Installer Self Test and Troubleshooting information M6799A Fig 16 Mounting thermostat on subbase 69 0931 3 Honeywell Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Mi
5. SUBBASE REMOTE TEMPERATURE COOL COMPRESSOR DAMPER CONTACTOR 2 SENSOR CONTACTOR 1 REMOTE SETBACK A HOT L2 TIMER Z CAUTION EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS A Power SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JA JUMPER RC TERMINAL TO RH TERMINAL WHEN INSTALLED ON A SYSTEM WITH ONE TRANSFORMER M4837A Fig 10 Typical hookup of Q7100A1010 in a two stage heat and two stage cool conventional system with two transformers SUBBASE SUBBASE COOL CHANGEOVER VALVE HEAT CHANGEOVER VALVE A POWER SUPPLY PROVIDE DISCONNECT MEANS AND M11088 OVERLOAD PROTECTION AS REQUIRED M4843A Fig 11 Typical hookup of Q7100C1024 in a one stage Fig 12 Typical hookup of Q7100D in a one stage heat and one stage cool heat pump system heat and one stage cool heat pump system SUBBASE HEAT CHANGEOVER VALVE COOL CHANGEOVER VALVE L1 HOT L2 M11089 Fig 13 Typical hookup of Q7100C1016 in a two stage heat and one stage cool heat pump system Includes remote temperature sensor and remote setback timer 69 0931 3 4 Q7100A C D THERMOSTAT SUBBASES SUBBASE REMOTE SENSOR A CAUTION EQUIPMENT DAMAGE WILL OCCUR IF POWER IS CONNECTED TO THE D TERMINALS A POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED A EM HEAT RELAY D
6. nneapolis MN 55408 0524 69 0931 3 Rev 2 98 L C Home and Building Control Honeywell Limited Honeywell Limit e 155 Gordon Baker Road North York Ontario M2H 2C9 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www honeywell com
7. nstallation use these instructions to check out the product operation A CAUTION Disconnect power supply to prevent electrical shock or equipment damage Location Subbase without Remote Mounted Temperature Sensor Install the subbase about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not install the subbase where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat Subbase with Remote Mounted Temperature Sensor s Install the subbase in an area that is accessible for setting and adjusting the temperature and settings Install the remote mounted sensor s about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fig 1 Do not mount the sensor s where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat If more than one remote sensor is required they must be arranged in a temperature averaging network consisting of two three four five or nine sensors See Fig 2 through 6 69 0931 3 Q7100A C D TH