Honeywell DC300K-E User's Manual
Contents
1. Key Number Table 1 Table 2 Table 3 Table 4 Table 5 D C3 0 0 0 Options 0 90 264Vac Power Output 1 1 24Vac dc Power C Current 4 20mA without Alarms B Blue Bezel with K Current 4 20mA with Alarm 1 90 264Vac Power E Relay Electromechanical 5AMP with Alarm 1 T Tan Bezel with A Relay Solid State AC 1AMP with Alarm 1 90 264 Vac Power T Open Collector Output 20mA with 1 Alarm C Blue Bezel with 24Vac dc Power Output 2 or Alarm 2 D Tan Bezel with O None 24Vac dc Power E Relay Electromechanical 5AMP SPDT 0 None A Relay Solid State AC 1AMP SPST A Approvals T Open Collector Output 20mA CSA FM UL F Approvals FM External Interface a O None 0 None 1 RS422 485 ue oe I D Tag 2 Auxiliary Output Soe DS One 4 DMCS D DIN Cutout Adapter Software Options Optional Input O None 0 None A Accutune 1 4 20mA or 1 5V B Setpoint Program and Accutune 2 Slidewire Input for Position Proportional or 3 Position Step with motor position Digital Inputs indication 0O None 3 Digital Inputs 2 o PV Input 1 T C RTD mV 1 5V 2 T C RTD mV 1 5V Figure 4 Model Number Interpretation
2. Controller Output Types Current Output Isolated Range can be set anywhere between 0 to 21 mA and as direct or reverse action Resolution 11 bits for 0 to 21 mA Accuracy 0 5 full scale Temperature Stability 0 1 F S C Load Resistance 0 to 1000 ohms Electromechanical Relays One or Two SPDT contacts Both Normally Open and Normally Closed contacts are brought out to the rear terminals Internally socketed Resistive Load 5 amps 120 Vac 2 5A at 240 Vac or 30 Vdc Inductive Load 50 VA 120 Vac or 240 Vac Motor 1 6 H P Solid State Relays One or Two SPST solid state contacts consisting of a triac N O output Internally socketed Resistive Load 1 0 amp 25 C and 120 or 240 Vac 0 5 amp 55 C and 120 or 240 Vac Inductive Load 50 VA 120 Vac or 240 Vac Open Collector Outputs One or Two Maximum Sink Current 20 mA Overload Protection 100 mA Internally powered 30 Vdc Opto isolated from all other circuits except current output but not from each other Socketed jumper assembly replaces relay Solid State Relays 10 amps One or two externally mounted triac N O outputs for use with open collector outputs Resistive Load 15 amps 25 C and 120 or 240 Vac 10 amps 55 C and 120 or 240 Vac Inductive Load 50 VA 120 Vac or 240 Vac Motor Rating 1 HP 25 C 0 75 HP 55 C Controller Output Algorithms On Off or Time Proportional One relay or open collector output Control action can be s
3. Accuracy 0 20 of span typical 1 digit for display 15 bit resolution typical Temperature Stability 0 01 of Full Scale C change Input Signal Failure Protection Thermocouple Inputs Upscale or downscale burnout Burnout Current 0 13 microamps Failsafe Output Level Configurable 0 100 Input Impedance 4 20 Milliampere Input 250 Ohms 0 10 Volt Input 200K Ohms All Other 10 Megohms Stray Rejection Common Mode AC 50 or 60 Hz 120 dB with maximum source impedance of 100 Ohms or 1 LSB least significant bit whichever is greater Normal Mode AC 50 or 60 Hz 60 dB with 100 span peak to peak maximum Alarm Output One SPDT electromechanical relay A second alarm is available using the second control relay This is not available with Relay Duplex Position Proportional or Three Position Step control Up to four setpoints are independently set as high or low alarm two for each relay Setpoint can be on either Input Process Variable Deviation Communication Shed or Output A single adjustable hysteresis of 0 0 to 100 0 is provided The controller can also be set to alarm on shed from communications The alarm can also be set as an on or off event at the beginning of a setpoint ramp soak segment Alarm Relay Contacts Rating Resistive Load 5 ampere at 120 Vac or 30 Vdc 2 5A at 240 Vac 51 52 03 07 Page 6 Specifications continued Design continued
4. Slidewire for Position 100 to 10002 Proportioning The maximum rating only applies up to 40 C 104 F For higher temperatures the RH specification is derated to maintain constant moisture content May require Field calibration to achieve rated accuracy below 1000 F for type B and below 200 F for type E thermocouple Not available on FM approved Limit models 51 52 03 07 Page 9 General Reference Data Data Isolation Functional AC Power is electrically isolated from all other inputs and outputs to withstand a HIPOT potential of 1900Vdc for 2 seconds per Annex K of EN61010 1 Analog Inputs and Outputs are isolated from each other and all other circuits at 850Vdc for 2 seconds Digital Input and Digital Output are isolated from all other circuits at 850Vdc for 2 seconds Relay Contacts with a working of 115 230 Vac isolated from each other and all other circuits at 345 Vdc for 2 seconds Surge Withstand Capability SWC Immunity ANSI IEEE C37 90 1 Surge Withstand Capability SWC Formerly IEEE 472 Mains power input and relay contact outputs 2 5 kV Common Mode and Differential Mode All other circuits 1 0 kV Common Mode and Differential Mode Radio Frequency Interference RFI Immunity No effect on performance from a 5 W walkie talkie operated at 27 151 or 450 MHz one meter from the controller Model Number Interpretation
5. process variable 4 digits Alternate information displayed during configuration mode A eight character lower display primarily shows key selected operating parameters 4 digits Also provides guidance during controller configuration Indicators Alarm Relay Status ALM 1 or 2 Control Mode A or MAN Temperature Units F or C Remote Set Point or SP2 Active RSP Control Relay Status OUT 1 or 2 Digital Input Status DI 1 and 2 Bargraph 21 segment vertical Deviation bargraph Center bar lit when on control Deviation to 10 of PV span in 1 increments Modes of Operation Manual Automatic with local setpoint Automatic with remote setpoint 2 input units only Dimensions See Figure 5 Mounting Panel mounted 5 82 inch depth Wiring Connections Screw terminals on the rear of the case See Figure 6 Power Consumption 18 VA maximum Power Inrush Current 10A Max for 4 ms under operating conditions CAUTION When applying power to more than one UDC3000 make sure that sufficient power is supplied Otherwise the controllers may not start up normally due to voltage drop from the inrush current Weight 1 3 kg 3 lbs 51 52 03 07 Page 8 Specifications continued Environmental and Operating Conditions Parameter Reference Rated Operative Limits Transportation and storage Ambient 25 3
6. to 1000 ohms Output range can be set anywhere between 0 to 21 mA and as direct or reverse action It can be configured to represent either Input PV Setpoint Deviation or Control output The range of the auxiliary output as a function of the selected variable can be scaled This output can be used as a second current output for current duplex outputs Resolution 12 bits over 0 to 21 mA Accuracy 0 2 of full scale Temperature Stability 0 01 F S C Communications Interface Optional DMCS RS422 485 Baud Rate 19200 baud Length of Link 4000 ft maximum Link Characteristics Two wire multi drop proprietary protocol 31 drops maximum Baud Rate 300 600 1200 2400 4800 or 19 200 baud Parity Odd or Even Length of Link 4000 ft maximum Link Characteristics Two wire or four wire multi drop RS422 ASCII protocol 15 drops maximum Digital Inputs Optional 15 Vdc source for external dry contacts or isolated solid state contacts The Digital Input option detects the state of external contacts for either of the two inputs On contact closure the controller will respond according to how each digital input is configured Opening contact causes return to previous state Input Filter Software Single pole lowpass section with selectable time constants off to 120 seconds available on both analog inputs Digital Displays Vacuum fluorescent alphanumeric A six character upper display dedicated to the
7. up PID Controller should the primary loop controller fail Since the PID control is sometimes implemented in the PLC this feature provides a very cost effective way to insure the process does not have to shutdown or remain in manual mode if the PLC should fail Switching from the Auto Manual Station to the back up control mode is accomplished using the Digital Input option Setpoint Ramp Soak Programming Enables you to program and store 6 Ramp and 6 Soak segments for setpoint programming Run or Hold of program is keyboard or remote switch selectable Physical Description The controller is housed in a 5 8 inch deep black metal case with a dark gray elastomer bezel that can be panel mounted in a 1 4 DIN cutout see Figure 5 The plug in chassis allows easy access to the controller board and its various option boards All power input and output wiring are connected to screw terminals on the rear panel see Fig 6 Blue and tan elastomer bezels are optionally available Inputs Each analog input is sampled 3 times a second amplified and then converted to a digital signal which is isolated and passed to the microprocessor The primary input can be one of various Thermocouple Radiamatic or Linear actuations see Table 1 A second input provides a remote setpoint function and accepts a 4 to 20 mA or 1 to 5 Vdc range that can be characterized All ranges are keyboard selectable External cold junctio
8. 4 20mA 3 T C RTD mV 1 5V 4 20mA 0 10V 22603 51 52 03 07 Page 10 Dimensions 0 008 96 gt lt M 0 0 p M 3 622 0 03 y 24 Max Panel 945 Thickness 12 12 12 0 008 Panel Cutout 92 0 0 3 622 0 03 runonon S945R MANUAL SEERA RUN Y A y pie 2 4 with optional E nj 10 Max 2 093 rear cover 5 82 Figure 5 UDC3000 Versa Pro Controller dimensions not to scale 22073 51 52 03 07 Page 11 Wiring Diagram UDC 3000 EXTERNAL WIRING Instrument Power 1 1 H SHIELD RX TX RX TX TX or AUX TX or AUX o oo NO oO F amp F ODN NOTE The product manual should be consulted for specific details and precautions regarding wiring Figure 6 External Wiring Diagram 22840 51 52 03 07 Page 12 Ordering Information For the complete ordering information request Model Selection Guide 51 51 16 32 for UDC3000 Universal Digital Controller or Honeywell offers a full line of Sensors Transmitters and Final Control Devices for use with the UDC3000 Universal Digital Controller These devices include Thermocouples RTDs Pressure Transmitters Flow Transmitters Liquid Level Transmitters Valve Actua
9. C 15 to 55 C 0 to 55 C 40 to 66 C Temperature 7745 F 58 to 131 F 32 to 131 F 40 to 151 F Relative Humidity 10 to 55 10 to 90 5 to 90 5 to 95 Vibration Frequency Hz 0 0 to 70 0 to 200 0 to 200 Acceleration g 0 0 1 0 5 0 5 Mechanical Shock Acceleration g 0 1 5 20 Duration ms 0 30 30 30 Voltage Vdc 244 1 20 to 27 20 to 27 a Voltage Vac 90 to 264Vac 120 1 90 to 264 90 to 264 CSA models rated to 250V max 240 2 Hes 24Vac 24 1 20 to 27 20 to 27 5s Frequency Hz 50 0 2 49 to 51 48 to 52 zE For Vac 60 0 2 59 to 61 58 to 62 Table 1 Input Actuations Range PV Input F c Thermocouples B 0 to 3300 18 to 1815 E 454 to 1832 270 to 1000 E low 200 to 1100 129 to 593 J O to 1600 18 to 871 J low 20 to 770 7 to 410 K 0 to 2400 18 to 1316 K low 20 to 1000 29 to 538 NiNiMoly NNM 32 to 2500 0 to 1371 NiNiMoly NNM low 32 to 1260 0 to 682 NIC Nicrosil Nisil 0 to 2372 18 to 1300 R 0 to 3100 18 to 1704 S 0 to 3100 18 to 1704 T 300 to 700 184 to 371 T low 200 to 500 129 to 260 W5W26 0 to 4200 18 to 2316 W5W26 low 0 to 2240 18 to 1227 RTD IEC ALPHA 0 00385 100 Ohms 300 to 1200 184 to 649 100 Ohms low 0 to 300 18 to 149 500 Ohms 300 to 1200 184 to 649 Radiamatic RH 1400 to 3400 760 to 1871 Linear Milliamps 4 to 20mA Millivolts 0 to 10mV 10 to 50mV Volts 1 to 5V 0 to 10V Optional 2nd Input Milliamps 4 to 20mA Volts 1 to 5V
10. HOLD 22816 Figure 2 Operator Interface Operator Interface Fig 2 Indicators They provide alarm control mode and temperature units Se IEN es bees te SET UP quentially displays Set Up groups and allows Tee Reese Seon E AS Function key to display individual functions status of the control relays and n whether a setpoint program is in Run FUNCTION Selects functions within each Set Up group or Hold mode A 21 segment bargraph displays Lower Selects an operating parameter to be shown in deviation to 10 of span and an DISPLAY the lower display On Control indicator Da manuaL Selects Manual or Automatic control mode sera See nD auto may be disabled via configuration able during normal operation with ar Alternately selects Local setpoint 1 and Remote alternate 6 character information seLect Setpoint or between two local setpoints displayed when in the configure may be disabled via configuration mode RUN Initiates or holds the single setpoint ramp During normal operation the lower Holp or Ramp Soak program l display shows key selected operat may be disabled via configuration ing parameters such as Output A Increases the setpoint output or Setpoints Inputs Deviation active configuration values displayed Tuning Parameter Set Timer Status or minutes remaining in a setpoint v Decreases the setpoi
11. Honeywell UDC3000 Versa Pro Universal Digital Controller Overview The UDC3000 Universal Digital Controller is Honeywell s general purpose microprocessor based stand alone digital controller It combines the highest degree of functionality and operating sim plicity offered in a 1 4 DIN size The bright dual displays with multi language prompts make the operator interface easy to read understand and operate Programmed sequences of dis plays assure quick and accurate entry of all configurable parame ters Simple keystrokes let you select input and range configura tion set the operating parameters that meet your process control needs now and change them later to meet new ones Features Dual Displays Vacuum fluores cent alphanumeric displays and indicators with dedicated PV display Deviation Bargraph On Control indication or up to 10 deviation display Easy Configuration Multi language prompts in programmed sequence provide guidance during configuration Individual reliable tactile keys provide positive operator feedback There are no internal jumpers to set Universal Isolated Input Input 1 accepts 10 thermocouple types RTDs Radiamatic RHs mA mV or voltage inputs through keyboard configuration It is isolated from Input 2 and all other circuits See Table 1 Thermocouple Failsafe Configurable upscale or downscale burnout and failsafe output level Decimal P
12. P1 Deviation or the Control Output Communications Provides a link between the UDC3000 and a Honeywell supplied interface device capable of communicating via RS232 DMCS or direct communication via the RS422 485 communications option to a host computer Approval Body Options FM approval CSA certification and UL Recognition are available options UL Recognition applies to regulatory use only 2 Digital Inputs Allows remote dry contact closure to select one of the following for each digital input e Manual control mode e Local setpoint 1 e Local setpoint 2 Direct controller action e Reset of Limit Controller e Hold SP Ramp Programming e Select PID set 2 e PV Input 2 e External program reset e Disable PID integral action e To Run SP Ramp Program To Automatic output value e Manual mode failsafe output e Disable keyboard e Start Timer e To Auto Manual Station e ToTune Also allows the following selections to be combined with the above selections e Select PID set 2 e Direct controller action e Local setpoint 2 e Disable adaptive tune Transmitter Power Provides up to 30 volts to power a 2 wire transmitter requires use of alarm 2 open collector output selection or auxiliary output AuxOut and communications are mutually exclusive only one may be specified Auto Manual Station Plus Backup Control You can use a single UDC3000 to act as both an Auto Manual Station PLUS a back
13. ble Deviation Output Shed from communications or to alarm on manual mode It can also be used as an On or Off event at the beginning or end of a Ramp Soak segment The alarm hysteresis is configurable from 0 to 100 of range 51 52 03 07 Page 4 Upper Display Six Characters e Normal Operation four digits dedicated to display the process variable Configuration Mode displays parameter value or selection Lower Display eight characters e Normal Operation displays operating parameters and values e Configuration Mode displays function groups and parameters Indicator definition when lit F Fahrenheit being used MAN controller in manual mode C Centigrade being used _A controller in automatic mode MAN and A off communications option active R Run SP Ramp Program H Hold SP Ramp Program__ Honeyw II Indicator definition when lit ALM Alarm conditions exist MAN SL OUT 1 2 i DI Digital Input active RSP Remote SP or SP2 active OUT Control Relay 1 or 2 on Deviation Bargraph e Center bar indicates PV is within 1 of setpoint e Next bar will light if PV is between 1 but less than 2 in deviation If PV is equal to or greater than 10 deviation the center bar plus all ten deviation bars will light LOWER DISPLAY A SETPOINT SELECT MANUAL AUTO v FUNCTION Keys See below RUN SET UP
14. controller can be configured for the following control algorithms e On Off e PID A e PID B e PD with Manual Reset e Three Position Step Control The Three Position Step Control algorithm allows the control of a valve or other actu ator with an electric motor driven by two controller output relays one to move the motor upscale the other downscale without a feedback slidewire linked to the motor shaft Accutune does not apply to this algorithm Features of this algorithm are 1 The controller can use all three modes of control PID instead of PI only 2 Three Position Step is an automatic backup mode to Position Proportional Control if the feedback slidewire signal should fail Manual or Automatic control with bumpless balanceless transfer between modes is a standard feature In the manual mode the operator directly controls the controller output level In the automatic mode the controller will operate from a local setpoint or a remote setpoint provided at the second input or via communications Alarms Alarm output terminals are located at the rear terminal panel One or two electromechanical alarm relays are available to activate external equipment when preset alarm set points are reached Each of the two alarms can be set to monitor two independent set points Each alarm setpoint can be either high or low alarm The alarm type can be selected to be either of the inputs the Process Varia
15. et for direct or reverse Time Proportional Relay Resolution 3 3 msec On Off Duplex Three Position Step Conirol or Time Proportional Duplex Two relays or open collector outputs Control action can be set for direct or reverse Time Proportional Relay Resolution 3 3 msec Current Proportional A single 4 20 mA current output signal which can be configured for direct or reverse action Current Proportional Duplex A single split current output for both heat and cool 4 12 cool 12 20 heat ora combination of current proportional output Heat 50 to 100 of range and auxiliary current output Cool 0 to 50 of range Both are 4 20 mA signals which can be set for direct or reverse action Position Proportional Two SPDT electromechanical or solid state relays operate motor having a 100 ohm to 1000 ohm feedback slidewire Current Time Duplex Variation of time proportional duplex for Heat Cool applications Time proportional output heat or cool is a relay Current proportional output Heat or Cool is a 4 20 mA signal that can be fed into a negative or positive grounded load of 0 to 1000 ohms and is operational over 50 of range or the entire range Sampling Rate Inputs sampled 3 times a second 51 52 03 07 Page 7 Specifications continued Design continued Auxiliary Linear Output Optional Isolated 21 mA dc maximum into a negative or positive grounded load or non grounded load of 0
16. hown in the lower display is selectable as either time remaining or elapsed time Two Sets of Tuning Constants Two sets of PID parameters can be configured for each loop and automatically selected Heat Cool Capability Provides split range control with independent PID tuning constants one for heating one for cooling plus mixed output forms Alarm Selection None one or two relays to activate external equipment when preset high low setpoints are reached There is an indicator for each alarm Setpoint Ramp Provides single programmable setpoint ramp of up to 255 minutes duration which is repeatable and activated by the Run Hold key Output Rate Limiter A maximum output rate may be configured for both the upscale and downscale output directions Data Security Five levels of key board security protect tuning configuration and calibration data accessed by a configurable 4 digit code Nonvolatile EEPROM memory assures data integrity during loss of power Quality Support The UDC3000 is covered by a 2 year warranty and backed up by a toll free phone number for technical assistance Second Input Isolated high level input available for remote setpoint signal PV signal via digital inputs or motor slidewire input Table 1 Auxiliary Output This isolated Auxiliary Output can be scaled from 4 20 mA for 0 to 100 for any range It can be configured to represent Input 1 Input 2 PV active Setpoint Local S
17. n compensation is provided You can select upscale downscale or failsafe sensor break protection A configurable digital filter of 0 to 120 seconds for each Input provides input signal smoothing if required 51 52 03 07 Page 3 Output Types Output Algorithms cont Configuration The following output types are available per the model selection guide e Current output Electromechanical relays Solid state relays Open collector output Solid state relay 10 amp externally mounted optional e Auxiliary current output optional Output Algorithms The UDC3000 is available with one or more of the following output algorithms Time Proportional provides On Off or Time Proportional Relay output Current Proportional supplies proportional direct current output for final control elements which require a 4 20 mA signal Position Proportional positions a reversible motor with a feedback slidewire in proportion to the output of the control algorithm Requires 2 output relays Time Proportional Duplex depending on which control algorithm you select this duplex output algorithm can provide On Off Duplex Time Proportional Duplex or 3 Position Step Control The time proportional duplex output provides independent PID tuning constants and two time proportional outputs one for heat zone above the 50 output and one for cool zone below 50 output Current Proportional Duplex similar t
18. nt output or ramp 4 digits It also provides configuration values displayed 22071 guidance through prompts for the operator during controller configuration 8 characters Figure 3 Key Functions 51 52 03 07 Page 5 Specifications Design CE Conformity Europe Product Classification Enclosure Rating Installation Category Overvoltage Category Pollution Degree EMC Classification Method of EMC Assessment Declaration of Conformity This product is in conformity with the protection requirements of the following European Council Directives 73 23 EEC the Low Voltage Directive and 89 336 EEC the EMC Directive Conformity of this product with any other CE Mark Directive s shall not be assumed Class Permanently Connected Panel Mounted Industrial Control Equipment with protective earthing grounding EN61010 1 Panel Mounted Equipment IP 00 this controller must be panel mounted Terminals must be enclosed within the panel Front panel IP 65 IEC 529 Category Il Energy consuming equipment supplied from the fixed installation Local level appliances and Industrial Control Equipment EN 61010 1 Pollution Degree 2 Normally non conductive pollution with occasional conductivity caused by condensation Ref IEC 664 1 Group 1 Class A ISM Equipment EN 55011 emissions Industrial Equipment EN 50082 2 immunity Technical File TF 51309303 000
19. o current proportional but provides a second set of tuning parameters and a split range current output or a second current output via the Auxiliary output option for the heat and cool zones Current Relay Duplex Relay Heat a variation of Duplex with Current active for 0 to 50 output Tuning Set 2 and Relay active 50 to 100 output Tuning Set 1 Current Relay Duplex Relay Cool a variation of Duplex with Current active for 50 to 100 output and Relay is active for 0 to 50 output Universal Output Model Flexibility of the Output Algorithms allows the Current Output Model with 2 Alarms DC300K E to be also configured for time simplex time duplex or three position step control plus of course the original capability of current simplex and current time duplex control A Relay Output Model with Auxiliary Output can also be configured for these output algorithms You decide how the controller is to interact with the process by select ing through simple keystrokes the functions you want Multi language prompts guide the operator step by step through the configuration process assuring quick and accurate entry of all configurable parameters There are no internal jumpers all configu ration is via the keyboard Five languages are available via configuration English French German Spanish and Italian Control Modes Control Algorithms Depending on the output algorithms specified the
20. oint Location Configurable for none one or two places 51 52 03 07 2 97 Page 1 of 12 Specification Honeywell ALM 12 FC DI 12 RSP OUT 12 MAN LOWER FUNCTION DISPLAY SETPOINT MANUAL AUTO SELECT A RUN HOLD y 22069 Figure 1 UDC3000 Versa Pro Controller Accutune II Provides a new truly plug and play tuning algorithm which will at the touch of a button or through a digital input accurately identify and tune any process including those with deadtime and integrating processes This speeds up and simplifies startup plus allows retuning at any setpoint Also included is the original Accutune SP Adaptive tuning that can automatically retune whenever a SP step change is implemented Fuzzy Logic This new feature uses fuzzy logic to suppress process variable overshoot due to SP changes or externally induced process disturbance It operates independently from Accutune tuning It does not change the PID constants but temporarily modifies the internal controller response to suppress overshoot This allows more aggressive tuning to co exist with smooth PV response It can be enabled or disabled depending on the application or the control criteria Manual Automatic Modes Bumpless balanceless transfer between control modes Two Local Setpoints Can be configured to provide two local setpoints keyboard or optional remote
21. switch selectable Universal Switching Power Operates on any line voltage from 90 to 264 Vac 50 60 Hz without jumpers 24V ac dc instrument power available as an option Limit Control provides a latching relay which is activated whenever the PV goes above or below a preset setpoint value An alarm indicator will light when the output is activated Reset is through a key on the front of the controller or an external switch Setpoint Rate Lets you define a ramp rate to be applied to any local setpoint change A separate upscale or downscale rate is configurable A single setpoint ramp is also available as an alternative Industrial Automation and Control 110 Virginia Drive Fort Washington PA 19034 Printed in U S A ll Copyright 1997 Honeywell Inc 51 52 03 07 Page 2 Features continued Optional Features Fig 4 Optional Features continued CE Mark Conformity with 73 23 EEC Low Voltage Directive and 89 336 EEC the EMC Directive Moisture Resistant Front Panel Capable of meeting NEMA 3 and IEC529 IP65 i e hosedown requirements Timer This standard feature pro vides a configurable time period of 0 to 99 hours 59 minutes Alarm 1 is dedicated to be active at the end of the timeout period Timer start is selectable as either the RUN HOLD key or Alarm 2 The optional Digital Input can also be configured to start the Timer in addition to either the keyboard or Alarm 2 The Timer status s
22. tors and Electric Motors Specifications are subject to change without notice Distributor For more information contact your nearest Honeywell Response Center listed below Industrial Automation and Control Honeywell Inc In the U S A Honeywell Industrial Automation and Control 16404 North Black Canyon HWY Phoenix AZ 85023 800 343 0228 In Europe Honeywell S A 80084 Amiens Cedex 2 33 22 54 56 56 Honeywell Control System Ltd Honeywell House Bracknell UK RG 12 1 EB 44 1344 826000 In Japan Yamatake Honeywell Co Ltd Nagai Int l Bldg 2 12 19 Shibuya Ku Tokyo 150 Japan 81 3 3486 2051 In Asia Honeywell Asia Pacific Inc Room 3213 3225 Sun Hung kai Centre No 30 Harbor Road Wanchai Hong Kong 852 829 8298 In the Mediterranean Africa and Middle East Region Honeywell SpA Via Vittor Pisani 13 20124 Milano Italy 39 2 67731 Honeywell Pacific Division Honeywell Pty Ltd 5 Thomas Holt Drive North Ryde Sydney NSW Australia 2113 61 2 353 7000 In Canada The Honeywell centre 155 Gordon Baker Road Ontario M2H 3N7 1 800 461 0013 In Latin America Honeywell Inc 14505 Commerce Way Suite 500 Miami Lakes Florida 33016 1556 305 364 2300
Download Pdf Manuals
Related Search
Related Contents
Targa WR 500 VoIP Outdoor Unit SERVICE MANUAL - Systemy klimatyzacji LG w • OPERATING INSTRUCTIONS - p.2 • MODE D`EMPLOI user Manual in PDF あんし ASA Electronics Voyager VOM78T User's Manual Produkt- und Preisinformation 2012 für fachhandel Advanced Global Technology RR101 Satellite Radio User Manual Copyright © All rights reserved.