Honeywell 107324A User's Manual
Contents
1. Place the split plug provided with 34886A or order 107323A Split Plug separately around the tubing and move the bulb and shield into mounting position as a sin gle unit 9 Push the split plug into the hole until it is wedged securely in place 10 Fasten the shield on the wall with screws provided with 34886A 11 If the tubing is properly shaped and the split plug installed as directed the shield covers the split plug and conceals the hole in the wall amp PLUG HOLE WITH OUTDOOR SENSING xc 3 4 IN 19 mm HOLE IN WALL CAPILLARY TUBING EXTENSION m UBE T BULB SHIELD M17272A Fig 16 Mounting bulb in bulb shield Strap On Mounting Occasionally applications require the sensing bulb to be strapped to the outside of a pipe For these applications use either the 105900 Pipe Strap or metal hose clamps The pipe strap fits pipe up to 3 4 in OD External mounting of the sensor produces a slight offset in the temperature control point Typically the control temperature increases as much as 5 F 2 8 C with a bare sensor strapped to the discharge pipe Applying insulation around the sensor and pipe decreases the offset Insulation must be used if large fluctuations in ambient temperature occur near the pipe 68 0040 04 12 Mount the bulb on the pipe as follows N CAUTION Significant Calibration Shift Hazard Overtightening clamps distorts bulb calibration D
2. CLIP zl INSULATION 242 INSERTION MAX I DEPTH BULB LENGTH M17259A Fig 2 Immersion well dimensions and components 3 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS Table 1 Copper Immersion Wells Spud in Shell ID Insertion in x 14 Bulb MaxBulb Insulation Capillary Part NPT Diameter Length Depth Diameter Includes Number 1 2 3 8 3 1 1 2 5 64 121371 Mounting Clamp 121371A 123869A Spud setscrew for armored capillary plug 123732AA 3 5 64 121371 Mounting Clamp 121371L 3 1 2 1 1 2 121371 Mounting Clamp 121371P 3 3 4 1 1 2 1 8 112721 Spring Clip 112620AA Plastic sleeve on well tube 123869B 1 2 4 1 4 1 1 2 1 8 112721 Spring Clip 112622AA 4 1 4 4 1 2 112721 Spring Clip 112626AA 3 4 3 8 3 1 1 2 5 64 121371 Mounting Clamp 121371B 123870A 3 5 64 121371 Mounting Clamp 121371M 121371 Mounting Clamp plastic sleeve 123171N 123871A Plastic sleeve on well tube 123871B 4 1 2 122555D Plastic sleeve on well tube 122555A 3 1 2 1 1 2 5 64 121371 Mounting Clamp 121371Q 2 1 4 138134B 4 1 2 Plastic sleeve on well tube 122555B 122555C 3 8 5 8 3 2 1 4 Plastic sleeve on well tube 138134E 4 1 2 122555E 1 2 4 1 4 1 1 2 1 8 112721 Spring Clip 112630AA 4 112634AA 8 1 4 1 1 2 112630AB Table 2 Stainless Steel Mild Stee
3. Fig 8 Capillary compression fitting assembly 68 0040 04 10 Element Holders Use element holders to mount air temperature sensors in a duct Locate the sensing element where air at representative temperatures can circulate around it In a plenum application locate the element far enough from the combustion chamber to avoid the effect of direct radiation Bulb Holders 1 Cuta hole large enough to admit the bulb and holder in the duct or plenum at the mounting location 2 Drill holes for the bulb holder mounting screws 3 Mount the bulb and capillary on the holder See Fig 9 through 11 107324A and 131524A Bulb Holders Use these bulb holders to mount one bulb in a duct or plenum See Fig 9 and 10 If necessary shorten holders by using pliers to flex the channel at one of the notches until it separates 311266D Bulb Holder Use this bulb holder to mount one or two bulbs in a duct where temperatures do not exceed 100 F 38 C The removable plug in the mounting plate allows insertion of a thermometer to check duct air temperature See Fig 11 for installation details PINCH TOP EDGES OF HOLDER TOGETHER AT EACH SEGMENT CAPILLARY TUBING SENSING BULB BE SURE EXTENSION TUBE IS UNDER BULB HOLDER AS SHOWN M7217 Fig 9 Installing capillary in 107324A and 131524A Bulb Holders INDOOR SCREW CAPILLARY HOLES IN TUBING WALL OF ON BULB it COMBUSTION CHAMBER M17265 Fig 10 Mountin
4. This mounting hardware is also available separately A few wells have a setscrew in the spud These wells are designed for use on controllers with an armored capillary that has a brass plug at the sensing bulb end for example R8182H J DIRECT INSERTION APPLICATIONS Most Honeywell direct insertion controllers include provision for clamping the controller case on the immersion well spud This requires a well spud with a mounting flange at the end If the well spud has a setscrew but no mounting flange a 124904 Well Adapter can provide the necessary flange See Fig 3 The well adapter is shipped with several Honeywell TRADELINE direct insertion controllers BACK SETSCREW BOILER OF CASE IMMERSION WELL CLAMP WELL SPUD WELL ADAPTER M17261 SCREW SENSING BULB Fig 3 Mounting direct insertion controller case on well spud Capillary Compression Fittings A capillary compression fitting includes a spud several aligning washers a neoprene packing ring and a packing nut The spud is internally threaded to hold the packing material and the packing nut and externally threaded to fit standard boiler tappings The washers and packing ring are sized to fit a particular capillary diameter 68 0040 04 8 Capillary compression fittings are used to replace an immersion well when the sensing bulb of a remote bulb controller requires direct insertion into the controlled medium The fitting seals around the capillary
5. not included one required per clip Use with 1 2 in EMT thinwall conduit where duct access is limited Kit includes 4 in 101 mm cover plate 1 2 in EMT compression fitting 3 16 in 5 mm rubber grommet clamp assembly wire ties and mounting Screws c gt c _ 7640HX M17279 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS Table 5 Immersion Well Accessories Description Mounting clamp Spring clip Application Holds capillary in place on 123869A 123872A 122554A B 12255A B D E and 138134B F Immersion Wells Size in in except where noted 1 2 or 3 4 in well spud 5 64 capillary Part Number M17274 121371AA M17288 32002656 001 Holds capillary in place on 1122620AA 112639AB Immersion Wells 1 2 in well spud 5 64 capillary 1 2 in well spud 1 8 capillary 3 4 in well spud 1 8 capillary 104488 112721 112720 LA M17280 Heat conductive compound Improves heat conduction in well applications where bulb does not fit tightly 4 oz 118 ml M17281 107408 Single application tube 1 2 oz uU M17282 120650 Well Adapter Adapts well with setscrew on spud for use with direct insertion bulb or 12137 1AA Mounting Clamp M17283 124904 68 0040 04 IMMERSION WELLS AND COMPRESSIO
6. Honeywell Immersion Wells and Compression Fittings FOR TEMPERATURE CONTROLLERS 112632AA IMMERSION WELL 107324A ELEMENT HOLDER 104484A COMPRESSION FITTING APPLICATION Immersion wells compression fittings and element holders are used with Aquastat Temperature Controllers to hold the temperature sensing bulb in the controlled medium Immersion wells and compression fittings also prevent leakage of the controlled medium PRODUCT DATA FEATURES Immersion wells and compression fittings are available to fit a 1 2 14 or 3 4 14 NPT tapping with a range of insulation depths Immersion wells and compression fittings are available in a variety of lengths and diameters Immersion wells and compression fittings are available in a variety of materials to suit the application Materials include brass copper stainless steel mild steel or Monel Element holders support the capillary and bulb or an averaging element in duct applications Bulb shields protect the sensing bulb from sun and weather with the bulb installed outdoors Accessories including mounting clips heat conductive compound waste nuts a pipe strap and a well adapter are available for mounting sensing bulbs in various applications Immersion wells allow heat transfer while protecting the sensing bulb from contact with the controlled medium Immersion wells permit removal of the sensing bulb for testing or replacement without
7. However compression fittings cannot seal off against as much pressure as immersion wells Capillary compression fittings can be used in duct applications to minimize air leakage from the duct a waste nut is recommended to provide a secure mounting Material Selection Capillary compression fittings are available in brass and stainless steel In hydronic applications brass fittings with copper sensing bulbs are used and stainless steel is used with all other fittings to minimize electrolytic action Sizing Capillary compression fittings must fit the tapping and the capillary diameter Because the spud must slip over the bulb during installation 11 16 in bulbs require 3 4 in spuds Element Holders Bulb holders are used to support a remote bulb and capillary in a duct but are not suitable for hydronic applications A bulb holder must be selected according to the length needed to support the bulb in the main airstream and the need for plugging the opening in the duct wall For best response string averaging elements evenly back and forth across the duct The element is held in place with either perforated pipe strap or 314439 Mounting Clips If access to the duct is limited use the 7640HX Duct Mounting Kit Always use a grommet to protect the element from abrasion where it enters the duct NOTE To minimize heat loss through the fitting use a waste nut and compression fitting INSTALLATION Installing this Product
8. Immersion well Copper 3 4 14 NPT in 138134C insulation 3 in insertion dual bulb 123872A mmersion well Copper 1 2 14 NPT in 121371L Includes mounting insulation 3 in insertion clamp 104486B Bulb compression fitting Brass 1 2 14 NPT 104484A Capillary Compression Fitting or 1 2 14 NPT well with correct insertion length and diameter 138134C 2 1 2 in insulation 138134E 3 1 4 insulation 138134D 2 1 2 in insulation 123871A 68 0040 04 15 IMMERSION WELLS AND COMPRESSION FITTINGS 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limit e 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 479 customer honeywell com U S Registered Trademark Printed in U S A led 2008 Honeywell International Inc n haat nate paper containing at least 10 68 0040 04 M S Rev 07 08 post consumer paper fibers Honeywell
9. N FITTINGS Table 6 Accessories for Duct Mount Applications Description Application Size Part Number Bulb shield assembly Shields bulb from weather 6 in 152 mm long holds 3 8 less mounting screws in and 1 2 bulbs o 0 split plug Honeywell I O O M17284 107323A Shields bulb from weather 7 in 118 mm long clip holds includes mounting screws 3 8 in bulb o and 33578 Split Plug g M17285 34886A Pipe Strap Fastens bulb to outside of 4 1 2 in 114 mm long used pipe with up to 3 4 in OD pipe M17286 105900 GENERAL INFORMATION Immersion Wells An immersion well consists of a metal tube called the well shell closed on one end A well spud externally threaded to fit standard boiler tappings is welded or brazed on the open end See Fig 1 The well is inserted into the tank and the temperature sensing bulb is inserted into the well The sensing bulb never touches the controlled medium Because the well conducts heat rapidly the bulb responds quickly and accurately to temperature changes in the controlled medium An immersion well protects the temperature sensing bulb from mechanical damage or damage due to chemical interaction with the controlled medium Also a well permits removal of the sensing bulb for testing or control replacement without draining the system The threaded fitting of the well spud provides a tighter seal than a packing nut applied to the capillary Mater
10. Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions WARNING Severe Scalding Hazard Contact with hot liquid can cause severe injury or death Drain system before beginning well or compression fitting installation A WARNING Electrical Shock Hazard or Equipment Damage Hazard Can cause sever injury death or short equipment circuitry Disconnect all power supplies before installation Most equipment manufacturers provide a tapping for temperature controller sensing element insertion The tapping should be located to measure average system temperature IMPORTANT Always install the sensing element away from hot or cold water inlets steam coils and locations where the well pressure rating will be exceeded Turn off the power 2 If the system is filled drain it to a point below the boiler tapping or sensing element location 3 If no tapping is provided prepare one properly threaded at the desired location Immersion Well Mounting Instructions for mounting the well in the tapping and using the capillary mounting clamp or spring clip in remote bulb appl
11. ailable and suggests functional replacements Table 7 Wells With and Without Mounting Clamp 121371 Part Number With Part Number Clamp Less Clamp 121371A 123869A 121371B 123870A 121371M 123871A 121371N 123871B 121371P None 1213710 1213711 123872 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS Table 8 Cross Reference Old Part Number Description Replacement Part Number Notes 121371G Immersion well Brass 1 2 14 NPT 1 1 2 in None insulation 6 1 2 in insertion includes 121371 mounting clamp 121371N IImmersion well Copper 3 4 14 NPT in 123871B No mounting insulation 3 in insertion includes plastic clamp sleeve 121371 mounting clamp 122555C Immersion well Copper 3 4 14 NPT 4 1 2 in 122555B 4 1 2 in insulation insulation 5 in insertion plastic sleeve 122555F Immersion well Copper 3 4 14 NPT 4 1 2 in None insulation 5 in insertion includes plastic sleeve dual diameter bulb 122555G Immersion well Copper 3 4 14 NPT 4 1 2 in INone insulation 5 in insertion dual diameter bulb 123870E Immersion well Copper 3 4 14 NPT 1 1 2 in 138134E 2 1 4 in insulation insulation 3 in insertion includes plastic sleeve dual diameter capsule 123871D Immersion well Copper 3 4 14 NPT in 138134E insulation 3 in insertion includes plastic Sleeve dual diameter well 123871E
12. draining the system Compression fittings seal the boiler and allow bulb insertion directly into the controlled medium Contents et Rm 1 Features Juga aan ree teras ra cesa e veste 1 Specifications essen 2 Ordering Information a 2 General Information 7 Installation a 8 Bie GONE 13 Cross Reference 13 68 0040 04 0 IMMERSION WELLS AND COMPRESSION FITTINGS SPECIFICATIONS Models Immersion Wells Allow heat transfer while protecting sensing bulb from controlled medium and seal off tapping to permit bulb removal without draining the boiler Available in copper stainless steel mild steel and Monel See Table 1 for copper See Table 2 for stainless steel mild steel and Monel Compression Fittings Allow bulb insertion directly into the controlled medium with boiler draining Can also be used to provide positive seal in duct applications Available in brass and stainless steel See Table 3 Element Holders Support bulb and capillary or averaging element in a duct See Table 4 Dimensions See Tables 1 2 3 and 4 and Fig 1 and 2 Temperature Ratings IMPORTANT Do not exceed the maximum temperature rating of the controller element Wells Copper 300 F 149 C maxim
13. ed Honeywell Limit e 35 Dynamic Drive Toronto Ontario M1V 4Z9 International Sales and Service Offices in all principal cities of the world Manufacturing in Australia Canada Finland France Germany Japan Mexico Netherlands Spain Taiwan United Kingdom U S A 68 0040 04 2 IMMERSION WELLS AND COMPRESSION FITTINGS WELL SPUD FITS 1 2 OR j lt 1 8 1 2 in OF THREADS MAY 121371A S 3 4 14 NPT TAPPED HOLE EXTEND INTO CONTROLLED MEDIUM L 123869A 123872A LESS MOUNTING CLAMP MOUNTING CLAMP Y weLL SHELL C Bi INSULATION INSERTION MAX NOTE 123870F HAS DUAL FLANGE DEPTH 7 BULB LENGTH a DIAMETER WELL SHELL 122555A B FITS 1 2 OR 3 4 14 NPT TAPPED iin i 0 l INSULATION DEPTH EE INSERTION MAX BULB LENGTH MOUNTING FLANGE A 122555E 1 2 OR 3 4 14 NPT TAPPED HOLE E DUAL DIAMETER WELL ja FLANGE INSULATION DEPTH hk INSERTION MAX BULB LENGTH 123732AA FITS 1 2 OR 3 4 14 TAPPED HOLE INSULATION p INSERTION MAX DEPTH BULB LENGTH 138134B ra FITS 1 2 OR 3 4 14 NPT TAPPED HOLE MOUNTING A FLANGE INSULATION DEPTH INSERTION MAX BULB LENGTH 138134E FITS 1 2 OR 3 4 14 NPT TAPPED HOLE DUAL DIAMETER WELL MOUNTING A FLANGE INSULATION DEPTH 4 INSERTION MAX BULB LENGTH FITS 1 2 OR 112620AA 112639AE ARDEN OLE j 1 8 1 2 in OF THREADS MAY EXTEND INTO CONTROLLED MEDIUM DOIM spaine f X WELL SHELL
14. g bulb holder in furnace plenum THERMOMETER 3 8g ADJUSTABLE SPRING CLIPS 2 CONTROLLER BULB q 2 1 4 x 2 1 4 57 x 57 APPROXIMATE HOLE IN DUCT FOR INSTALLATION RUBBER GROMET N NO 8 SHEET METAL MOUNTING SCREWS 2 M7355 Fig 11 Mounting sensing bulb and 311266D Bulb Holder in duct NOTE Dimensions shown in in mm Duct Mounting with Capillary Compression Fitting In some duct mount application it is desirable to use a compression fitting to reduce air leakage at the sensing element location For these applications first mount a waste nut on the duct to ensure secure mounting See Fig 12 See Table 6 for part numbers NOTE Do not use this mounting method for liquid applications DUCT WALL lt CAPILLARY BULB TUBING CAPSULE Fig 12 Mounting sensing bulb in duct using waste nut and compression fitting CAPILLARY COMPRESSION FITTING M17266 Averaging Element Holders The averaging element must be supported so it is distributed evenly across the entire height and width of the duct It can be fastened to perforated strap iron see Fig 13 or mounted with 314439 Mounting Clips see Fig 14 This type of mounting requires threading the element through a grommet inserted in a hole in the duct wall For ducts with limited access the 7640HX Averaging Element Mounting Kit allows mounting the element through a single hole in the side of the duct This kit
15. g clip into well spud Securing Bulb in Wells with Setscrew Wells with a spud setscrew are designed for use with controllers that have armored capillary with a brass collar at the bulb end of the armor The setscrew tightens against the brass collar See Fig 7 These wells can be adapted for use with 5 64 in capillary by adding the 124904 Well Adapter and the 121371 Mounting Clamp Assembly See Fig 3 M17264 Fig 7 Mounting armored capillary in well with setscrew Capillary Compression Fittings 1 Coat external spud threads with a moderate amount of pipe dope leaving two end threads bare See Fig 4 NOTE Teflon tape can also be used Screw the spud into the tapping and tighten securely Place the packing nut on the tubing Slide the bulb completely through the fitting Place the composition disk and the four slotted brass washers on the tubing in the order shown in Fig 8 Turn the brass washers so that the slots are 180 degrees apart and the small tabs are in the mating slots 7 Slide the seal assembly into the fitting Make sure the sensing bulb extends the desired distance into the controlled medium See Fig 2 8 Tighten the packing nut 1 2 13 mm PIPE THREAD FOR 1 2 13 CAPSULES 3 4 19 mm PIPE THREAD FOR 11 16 17 mm CAPSULES Z SPUD CAPILLARY TUBING COMPOSITION DISK ON SLOTTED LM AS SLOTTED WASHERS ASSEMBLED IN PAIRS THUS M17258
16. ial Selection The immersion well material must conduct heat readily and resist corrosive and electrolytic action especially in brine solutions and when the well is a different material than the container The material must also resist fluid contamination from chemical reaction with the well and withstand high temperatures Most Honeywell immersion wells are copper because of its high conductivity Stainless steel mild steel and Monel wells are also available for applications requiring higher maximum temperature and pressure ratings or greater corrosion resistance Some copper wells are available with a plastic sleeve over the tube to reduce electrolytic and corrosive activity Well Sizing Major factors in selecting well size are size of the boiler tapping bulb diameter insulation depth insertion length Immersion wells are available to fit standard 1 2 14 NPT and 3 4 14 NPT tappings Sensing bulbs are 3 8 1 2 or 11 16 in in diameter with well shells designed to fit these diameters The bulb should fit tightly in the shell If the bulb fits loosely fill the space between the shell and bulb with heat conductive compound to ensure maximum heat transfer Many Honeywell temperature controllers ship with heat conductive compound available in 4 oz cans and 1 2 oz single application tubes See Table 4 he nominal length of the spud including the full length of the threads and the hex defines the insulation depth De
17. ications follow Consult the appropriate Aquastat amp Controller instructions for mounting the controller on the well in direct insertion applications Direct insertion applications usually require using wells with a mounting flange on the spud 1 Coatthreads with a moderate amount of pipe dope leav ing two end threads bare See Fig 4 NOTE Teflon tape can also be used 2 Screw the immersion well into the tapping and tighten securely APPLY A MODERATE AMOUNT OF PIPE COMPOUND LEAVE TWO END THREADS BARE M17262 Fig 4 Proper application of pipe dope Insert Sensing Bulb in Well For good temperature response the immersion well must fit the sensing element or bulb tightly and rest against the bottom of the well NOTE f necessary bend the tubing to hold the bulb against the bottom of the well IMPORTANT Any bends made in the piping must be gradual to pre vent breaks in the tubing and subsequent loss of fill For faster heat transfer use heat conductive compound to fill the space between the bulb and the well A tube of heat conductive compound ships with Honeywell TRADELINE Aquastat Controllers The compound is also available as an accessory See Table 5 Use the following procedure when installing the compound IMMERSION WELLS AND COMPRESSION FITTINGS Fill the well with compound Coat the bulb generously before inserting it into the well Move the bulb up and down inside the well to ensure even dis
18. l and Monel Immersion Wells Spud in Shell ID Insertion in x 14 Bulb Max Bulb Insulation Capillary NPT Diameter Length Depth Diameter Material Includes Part Number 1 2 3 8 3 1 1 2 5 64 Stainless 121371 Mounting Clamp 121371E steel 1 2 4 1 4 1 1 8 Mild steel 112721 Spring Clip 112623AA Stainless 112721 Spring Clip 112624AA steel 4 1 8 Stainless 112721 Spring Clip 112628AA steel 1 1 8 Stainless 112721 Spring Clip 112632AA steel 68 0040 04 Table 3 Capillary Compression Fittings IMMERSION WELLS AND COMPRESSION FITTINGS Material Spud Maximum Bulb Diameter Insulation Depth Capillary Diameter Part Number Brass 1 2 14 NPT 1 2 in 1 5 16 in 5 64 in 104484A 1 8 in 7617M 1 1 2 in 5 64 in 104484C 2 in 5 64 in 7617ABY 3 4 14 NPT 1 5 8 in 5 64 in 104484B 11 16 in 1 1 2 in 1 8 in 7617P Table 4 Element Holders for Duct Mount Applications Application Length Plate Size Description Part Number Bulb holders 8 5 8 in 2 3 4 in Supports capillary and bulb in duct x 1 3 4 in mounting screws not included M17275A 107324A 2 3 4 in x 3 in S M17276A 131524A 14 in 3 1 4 in x Holds 1 or 2 elements in 0 F to 3 1 4 in 100 F air grommet holds one P d 5 64 in and one 1 8 in diameter capillary helps reduce airflow through opening in duct gt M17277A Averaging Mounting clip use with grommet element holders mounting screws
19. o not overtighten hose clamps 1 Seoure the bulb to the pipe with a 105900 Pipe Strap or metal hose clamps See Fig 17 and 18 2 If necessary cover the bulb and pipe with foam rubber insulation that extends at least 6 in 152 mm beyond both ends of the bulb See Fig 19 IMPORTANT Do not allow the duct tape to come into contact with the pipe 3 Secure foam rubber with duct tape T CLAMP E CAPILLARY TUBING N SUPPLY WATER PIPE M8836 Fig 17 Mounting bulb to pipe with pipe strap NOTE When using a pipe strap the maximum pipe OD is 3 4 CAPILLARY TUBE M17267 METAL HOSE CLAMPS Fig 18 Mounting bulb to pipe with metal hose clamps CAPILLARY DUCT FOAM RUBBER WRAP EXTEND TUBE TAPE a 6 in 152 mm BEYOND ENDS OF BULB M17268 Fig 19 Covering bulb and pipe with foam rubber insulation CHECKOUT When installation is complete check it as follows 1 Visually inspect the fittings in hydronic applications for leakage If necessary tighten these fittings Ensure excess capillary is coiled beneath the controller case Ensure proper operation by observing the system through one complete cycle 13 IMMERSION WELLS AND COMPRESSION FITTINGS CROSS REFERENCE Some series 121371 Wells are also available without the mounting clamp These pairs are listed together in Table 1 and in Table 7for your convenience The cross reference in Table 8 lists wells and fittings no longer av
20. pending on the characteristics of the tapping 1 8 to 1 2 in of the 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS threaded end of the spud can extend into the controlled medium Consider this additional length when determining how far the well extends into the controlled medium The length of the well shell starting at the end of the spud defines the insertion length This is the active part of the well where the fastest heat transfer occurs The bulb should be the same length as the well shell however the well shell can be longer but not shorter than the length of the bulb Longer shells require inserting the bulb until the end touches the well bottom Shorter shells do not expose the full length of the bulb to the temperature of the controlled medium inhibiting proper temperature controller operation Securing Bulb in Well REMOTE BULB APPLICATIONS Securing the capillary at the spud with a spring clip or a mounting clamp holds the sensing bulb securely in place See Fig 1 Use the spring loaded clip on well spuds with no mounting flange Slip it over the capillary and snap it in place in the end of the spud The mounting requires sizing to fit both the spud and the capillary diameter The mounting clamp requires wells with a mounting flange at the spud end The jaws adjust to fit both 1 2 and 3 4 in spuds and it holds a 5 64 in capillary Wells are available with and without the matching spring clip or mounting clamp
21. requires a length of 1 2 in EMT conduit See Fig 15 GROMMET AVERAGING 4 79 ELEMENT USE NO 10 SHEETMETAL SCREWS IMMERSION WELLS AND COMPRESSION FITTINGS CAPILLARY TUBING x mm DUCT WALL B B WIRE FASTENINGS M17269 Fig 13 Mounting averaging element with perforated strap iron CAPILLARY TUBING 314439 CLIP DUCT WALL BEND HERE IF NECESSARY M17289 Fig 14 Mounting averaging element with 314439 Mounting Clips 1 2 in EMT CONDUIT OBTAIN LOCALLY Ed GROMMET WIRE TIES CAPILLARY a CONDUIT COMPRESSION FITTING 4in COVER PLATE AVERAGING M17270 ELEMENT Fig 15 Mounting averaging element with 7640HX Averaging Element Mounting Kit 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS Bulb Shields A bulb mounted outdoors requires protection of a bulb shield 1 Expose the bulb to representative air temperature but not direct sunlight 2 Mount it high enough so a Accumulated snow leaves or other debris can not obstruct air circulation around it b Children cannot reach it c Avoid vents from the building Drill a 3 4 in 19 mm hole in the outside wall Bring the sensing bulb through the hole Mount the bulb in the bulb shield See Fig 16 If the seal off tube extends outside the shield bend it under the shield Hold the shield over the mounting location and form a small radius bend in the tubing 8
22. tribution of compound mM Securing Bulb with Mounting Clamp Use the 121371 Mounting Clamp only on wells with a mounting flange on the spud end 1 Loosen the draw nut and spread the jaws of the clamp with a screwdriver See Fig 5 2 Slide the clamp jaws over the spud mounting flange point A in Fig 5 3 Adjust the tubing to fit through the mounting clamp groove point B in Fig 5 IMPORTANT When tightening the draw nut be careful not to damage the capillary 4 Tighten the draw nut so that the retainer clamp attaches firmly to the well spud and holds the tubing securely in place SPREAD JAWS TO FIT OVER RIDGE ON WELL SPUD SCREWDRIVER MOUNTING CLAMP NUT MOUNTING Fig 5 Fastening bulb in well using mounting clamp Securing Bulb with Spring Clip The spring clip can be used with any well with the appropriately size spud Wells without a mounting flange on the spud require a spring clip NOTE The spring clip does not hold the capillary as securely as does the mounting clamp See Table 5 for spring clip part numbers 1 Slide the clip over the capillary with the prongs facing the well 2 Push the clip as far as possible into the spud See Fig 6 NOTE Make sure the bulb remains bottomed in the well 68 0040 04 IMMERSION WELLS AND COMPRESSION FITTINGS FITTING INCLUDING WELL APPROX 3 3 8 IN INSERTION LENGTH TUBING SPRING CLIP BULB M17263 Fig 6 Mounting sprin
23. um Other Materials Maximum temperature rating limits of the controller sensing bulb and capillary Capillary Compression Fittings 250 F 121 C maximum ORDERING INFORMATION Element Holders 3112660 Bulb Holder 40 F to 100 F 40 to 38 Other Element Holders Maximum temperature rating limits of the controller sensing bulb and capillary Maximum Pressure Ratings Copper Wells 255 psi 1758 kPa at 300 F 149 C Other Wells 1500 psi 10 342 kPa at 700 F 371 C Capillary Compression Fittings Water 50 psi 345 kPa Air 15 psi 103 kPa Accessories See Tables 5 and 6 PACKING NUT MUS TUBING j SLOTTED BRASS WASHERS 4 INSULATION DEPTH FITTING FOR 1 2 OR 3 4 14 NPT TAPPED HOLE MINIMUM INSERTION LENGTH Po APPROXIMATELY 4 3 4 IN M17260 COMPOSITION DISK Fig 1 Capillary compression fitting dimensions and components When purchasing replacement and modernization products from your TRADELINE wholesaler or distributor refer to the TRADELINE Catalog or price sheets for complete ordering number If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Automation and Control Products Sales Office check white pages of your phone directory 2 Honeywell Customer Care 1885 Douglas Drive North Minneapolis Minnesota 55422 4386 In Canada Honeywell Limit
Download Pdf Manuals
Related Search
Related Contents
Professional 3400 und 5400N Electrolux K180F385 User's Manual Mode d emploi des postes analogiques a clavier GroupShield 5.0 Service Pack 2 for Microsoft Exchange 5.5 Vinículos HP GP537AA User's Manual MartinYale 1616 mechanical letter opener Le carnet de route de Cyril catamaran - Suministros Salper Copyright © All rights reserved.