Emerson NetSure 801 DC Power System Brochures and Data Sheets
Contents
1. The output current is limited to 110 amps Internal fuse If rectifier detects over voltage it will turn off After 5 seconds it will restart if it encounters an over voltage within 5 minutes it will turn off and remain off until reset Output Power vs Temperature Output Voltage vs Output Current at Ambient Temp lt 45 C at Input Voltage gt 304VAC max Output Power 5800W 5 120 5 120 S 100 3 100 Z 50 3 80 580 y 50 3 00 S 60 5 40 5 40 3 40 2 3 20 E 20 40 L o 2 250 300 350 400 450 Input Voltage VAC Additional Information For ordering information request SAG582140001 For additional specification engineering and installation information use specification number 582140001 model number 801 NLEB 500 550 0 40 30 20 10 0 10 20 30 40 50 60 70 80 Temperature C Output Current A A EMERSON Network Power 0 O 10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 Emerson NYSE EMR based in St Louis is a global leader in bringing technology and engineering together to provide innovative solutions to customers through its network power process management industrial automation climate technologies and appliance and tools businesses For more information visit Emerson com Emerson Network Power a business of Emerson NYSE EMR is the glo
2. rectifiers provides up to 16 800 amps of power for 48 volt systems The basic components of the system include 2640 amp power bays which house the rectifiers and MCA chassis and 6000 amp distribution bays The cabled architecture allows the placement of the bays anywhere the user desires without regard to any specific order This also makes it more user friendly in applications where existing obstacles such as support columns need to be accommodated The total plant size is defined by the maximum capacity of the Main Battery Termination Bars MBTB The NetSure 801 power system contains a powerful microprocessor based meter control and alarm system capable of monitoring and controlling up to 168 rectifiers The MCA provides a 4 line 4 EMERSON Network Power 40 character alphanumeric display which can be activated at the touch of a keypad Each rectifier bay can accommodate up to 24 plug n play rectifiers which are controlled by the MCA Additional bays can be added as load requirements increase The NetSure 801 power system offers 6000 amp modular distribution bays Each bay can be configured with up to 70 positions of fuses and circuit breakers from 1 800 amps Multiple bays may be used to support load levels in excess of 16 800 amps Contact an Emerson application expert at 1 800 800 1280 Application The NetSure 801 system is ideal for wireline wireless and data center applica tions such as
3. C failure Alarm relays are programmable and will respond to SNMP gets and send traps when combined with the SNMP option Remote communication is provided using an Ethernet connection HTTP web browser Telnet or SNMP modem or RS 232 interface Rectifier Bay The NetSure 801 rectifiers are housed in modular power bays that accommodate 24 rectifiers each The rectifier bays are 7 high x 24 375 wide x 30 deep System capacity can be easily expanded with additional bays NetSure 801 nies System Specifications System Features Nominal System Voltage Control Rated Output Capacity System Power Bay Distribution Bay Rectifier Distribution Panel Physical Characteristics Framework Type Mounting H x W x D Access Environmental Operating Temperature Storage Humidity Ventilation EMI RFI Suppression Safety Compliance 48VDC 47 to 58 VDC Microprocessor MCA 16 800 amps higher capacity configurations are available 2640 amps 6000 amps 5800 watt rectifier R48 5800 1500 amps 4 per bay Box frame Power Bay 7 x 24 375 x 30 Distribution Bay 7 x 30 x 30 Front and back 32 F to 104 F 0 C to 40 C continuous operation 40 F to 185 F 40 C to 85 C 0 to 95 relative humidity non condensing Fan cooled front to rear Conforms to FCC rules Part 15 Subpart B Class A and EN55022 Class A UL Listed 1801 cUL NEBS Level 3 pending R48 5800 Rectifier General Spec
4. HI DC Power for Business Critical Continuity NetSure 801 Series DC Power System S EMERSON Key Features Modular design simple to install and operate allows incremental cost effective system growth Single point adjustment no tools required to change settings and make adjustments MCA controls up to 168 rectifiers LMS1000 monitoring witha single plug in card includes SNMP and Web interface Remote access options allow users to view control and interact with the system using an Ethernet Telnet web pages SNMP or TL1 modem or RS 232 Plug n play add rectifiers without changing the settings and making adjustments no system interruption High density compact design takes up less floor space houses 24 5800 watt rectifiers per bay distribution bays are rated for 6000 amps in continuous operation Efficiency industry leading 3 phase rectifier 93 peak 92 6 at full load Cabled plant offers unlimited configuration options PowerShare allows the reuse of existing equipment with NetSure 801 Safety compliance NEBS Level 3 compliance pending 3rd party testing UL Listed to UL subject 1801 5 800 watt rectifiers from Emerson Network Power provide up to 110 amps each With 24 units per bay these rectifiers provide up to a 2 640 amp output in a 24 375 x 30 footprint Description The modular NetSure 801 power system with 5800 watt
5. al Continuity NetSpan NetReach NetXtend and NetSure are trademarks of Emerson Electric Co and or one of its subsidiaries Emerson Network Power Energy Systems North America 4350 Weaver Parkway Warrenville IL 60555 Toll Free 800 800 1280 USA and Canada Telephone 440 246 6999 Fax 440 246 4876 Web EmersonNetworkPower com EnergySystems EnergyNet Secure EmersonNetworkPower com Emerson Network Power The global leader in enabling Business Critical Continuity EI Ac Power BI Embedded Computing BI Outside Plant BI Racks amp Integrated Cabinets BI Connectivity MH Embedded Power BI Power Switching amp Controls ll Services Hi DC Power BI infrastructure Management amp Monitoring BI Precision Cooling E Surge Protection 2010 Emerson Network Power Energy Systems North America Inc All rights reserved Code PPB CODCP 085 January 2010
6. bal leader in enabling Business Critical Continuity from grid to chip for telecommunication networks data centers health care and industrial facilities Emerson Network Power provides innovative solutions and expertise in areas including AC and DC power and precision cooling systems embedded computing and power integrated racks and enclosures power switching and controls monitoring and connectivity All solutions are supported globally by local Emerson Network Power service technicians For more information on Emerson Network Power s full suite of solutions specifically supporting the communications network infrastructure including NetSpan NetReach and NetXtend outside plant enclosures and equipment NetSure DC power systems and turnkey services visit EmersonNetworkPower com EnergySystems Learn more about Emerson Network Power products and services at EmersonNetworkPower com This publication is issued to provide outline information only which unless agreed by Emerson Network Power Energy Systems North America Inc in writing may not be used applied or reproduced for any purpose or form part of any order or contract or be regarded as a representation relating to the products or services concerned Emerson Network Power Energy Systems North America Inc reserves the right to alter without notice the specification design or conditions of supply of any product or service Emerson Emerson Network Power Business Critic
7. ced 50 from 145 176VAC 45 Hz to 65 Hz gt 0 98 from 50 to 100 load Power Factor PF Total Harmonic Distortion Input Current Inrush Current Input Protection Operating Efficiency lt 5 from 50 to 100 load Max 20 amp Inrush current does not exceed 150 of the rated input steady state peak value If the input voltage decreases or increases beyond a non adjustable predetermined value the recti fier circuitry shuts down disabling the output The rectifier will recover automatically when the AC input is re established and exceeds 260VAC low voltage restart point or when it decreases to 530VAC high voltage restart point Overcurrent is protected by an internal fuse 93 peak 92 6 at full load DC Output Output Voltage Range Output Power Output Current Regulation Voice Band Noise Wide Band Noise Psophometric Noise Protection Current Limiting Over Current High Voltage Shutdown Specify R48 5800L for 208V Output Power vs Input Voltage 42 0VDC to 58 0VDC 5800W maximum from 304VAC to 530VAC Nominal 110 amps adjustable from 10 110 amps Steady state output voltage remains within 0 25 for any combination of input voltage from 5 to 100 load The voice frequency noise generated by a rectifier does not exceed 32dBrnC output noise from 10 to 100 load Does not exceed 250 mv peak to peak or 100 mv rms per Telcordia GR 947 CORE Does not exceed 1 mv from 10 to 100 load
8. ifications Status Alarm Indicators and Monitoring Visual Indicators Status Settings Physical Characteristics Mounting Dimensions H x W x D Weight Environmental Temperature Altitude Ventilation Audible Noise Safety Compliance Specify R48 5800L for 208V Status Visual indicator color Normal operation Green Alarm Yellow Rectifier failure alarm Red Fan failure alarm Flashing red The MCA controller establishes all rectifier settings Plug in installation 3 36 x 8 83 x 14 62 85 5 x 224 5 x 371 5mm 17 6 Ibs 8kg 40 F to 113 F 40 C to 50 C at full rated output 96 Amps at 55 C Up to 6562 2000m at full rated output Front to back with speed controlled fan field replaceable The rectifier does not produce sound levels above 50dB A measured 0 6m in front of the rectifier at the same horizontal line as the middle of the rectifier at 25 C UL recognized UL60950 for USA amp Canada CE marked S EMERSON Natiusarl Dawwsar N etwol k Powel Emerson Network Power a complete spectrum of best in class reliable power precision environmental and connectivity solutions for today s telecommunications and data network infrastructure R48 5800 Rectifier Electrical Specifications AC Input Nominal Voltage Operating Voltage Range Frequency Three phase 380 480VAC R48 5800 304VAC to 530VAC output reduced 50 from 260 304VAC R48 5800L 145VAC to 230VAC output redu
9. ont of the MCA panel or remotely using the optional LMS1000 monitor The MCA provides local indicators and the ability to transmit various alarm conditions such as rectifier failure high voltage The NetSure 801 power system is designed to operate in conjunction with existing equipment Leverage our patented PowerShare technology to deploy a true hybrid power plant by reusing existing power and or distribution Alarming and telemetry are centralized within the NetSure 801 providing a single point of contact PowerShare offers significant cost savings through the reuse of existing equipment already onsite e Rectifier The modular R48 5800 is a high frequency rectifier designed with the latest patented DSP Digital Signaling Processing switch mode technology DSP reduces cost by optimizing system operation and requiring fewer components System configuration is easily accomplished with these plug n play rectifiers Rectifiers are simply added to an existing rectifier bay or R48 5800 Rectifier newly added power bay to increase capacity no adjustments or setup are required NetSure 801 power systems accommodate up to 264 rectifiers which provide load power and battery recharge current The rectifiers are monitored and controlled by the MCA The R48 5800 rectifiers enable the power plant to easily grow to meet specific application needs S EMERSON B MCA Meter Control amp Alarm shutdown and A
10. switch sites co location MTSO and data processing centers i NetSure 801 System Elements 1 Main Power Bay Individual Feed No Breakers 2 Distribution Bay 3 ACPanel Dual Feed with Breakers 4 MCA N EMERSON Network Power 5 Rectifiers 6 Bullet Fuse Breaker Panel Optional 7 4 1500 Amp Fuse Breaker Distribution Buses SER ERR EATes Ee RE iau 4 Distribution Bay with Fuses and Breakers Installed TET The NetSure platform is globally renowned with over 500k units deployed and an unmatched reliability of less than 0 5 failure rate 200 years MTBF Modules amp Options AC Input Two types of AC input are offered dual feed or twin feed With the dual feed option two sources of AC are brought into the termination panels The AC is internally distributed to the individual rectifiers by 12 on board circuit breakers and the rectifiers are divided evenly between sources With the twin feed option each pair of rectifiers is sourced separately from a customer provided PDSC This enables existing AC infra structure to be used for 200 amp rectifiers If individual rectifier feeds are required simply remove the factory installed jumpers Conduit sizes up to 2 can be accommodated DC Output Termination Panel Q EMERSON Network Power Distribution The NetSure 801 distribution bay is modular There are a total of 48 distribu tion positions for GJ
11. type circuit breakers as well as an optional 24 position bullet nose panel In addition to E Trip and E M Circuit breakers from 1 to 800 amps the system will accommodate TPS TLS and TPL fuses ranging from 1 to 800 amps Each GJ circuit breaker and TPL fuse is individually monitored The system can also be expanded with additional 6000 amp bays that do not need to be adjacent to each other The only bay to bay connection required is the CAN bus control cable The power feeds are cabled from the MBTBs Distribution device options include 1 to 250 amp plug in circuit breakers 3 to 100 amp TPS TLS style fuses in plug in holders 100 to 800 amp G 218 style circuit breakers and 70 to 800 amp TPL style fuses Emerson Network Power The NetSure 801 power system s extensive monitoring capabilities easy configuration and maintenance are all backed by the resources and quality reputation of a nationwide service organization SETE Ot i La aan bl ee Monitoring Control The MCA provides a single point of adjustment for such features as float voltage test equalize voltage high voltage shut down and current limit for all rectifiers in the entire power system The MCA provides local indicators and the ability to transmit various alarm conditions system measurements and Hybrid Applications system settings All measurements and adjustments can be performed locally via the alphanumeric display on the fr