Emerson FIELDVUEDVC6200 Instruction Manual

image

Contents

1. LCP100 Local Control Panel Instruction Manual November 2013 D103272X012 Figure 12 Fisher LCP100 Connection to Explosion Proof Ex d FIELDVUE DVC6200 SIS 24 VDC Power ZONE10R2 NON HAZARDOUS AREA 24V SUPPLY 10 100 Bem Instruction Manual D103272x012 LCP100 Local Control Panel November 2013 19 LCP100 Local Control Panel Instruction Manual November 2013 D103272X012 Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user Fisher FIELDVUE and Bettis are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co Emerson Process Management Emerson and the Emerson logo are trademarks and service marks of Emerson Electric Co HART isa mark owned by the HART Communication Foundation All other marks are the property of their respective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability All ales are governed by our terms and conditions which are available upon request
2. Instruction Manual LCP100 Local Control Panel D103272X012 November 2013 Figure 4 Wiring for 24 VDC External Power Configuration Intrinsically Safe Applications SOLVER INTRINSICALLY OUTPUT SAFE BARRIER Fene ae sunao S P arao j P 1 d DVC6200 SIS 1 9 TERMINAL BOX E NE SHIELD NOT CONNECTED mensus Eu 1 SIMPLE METHOD FOR INSTALLING AN LCP100 10 AN EXISTING 1 DVC6200 SIS INSTRUMENT WHEN 24 VDC POWER IS AVAILABLE NON HAZARDOUS LOCATION HAZARDOUS LOCATION NOTE DO NOT CONNECT THE LOOP TERMINAL IN THELCP100 TO THE LOOP TERMINAL IN THE DVCE200 SIS THIS WILL CAUSE THE LCP100 TO UNNECESSARILY CONSUME 4 mA AT THE EXPENSE OF THE DVCS200 SIS TD THIS CONNECTIONS ALSO LABELED LOOP LCP100 Local Control Panel Instruction Manual November 2013 D103272X012 Figure 5 Wiring for Loop Powered Configuration Logic Solver Wired to the Fisher LCP100 then the FIELDVUE DVC6200 SIS Explosion proof Applications icp100 TOGICSOLVER GI OUTPUT CASEGROUND 8 20 USER SUPPLIED DVCG200 SIS TERMINAL THEDVCG200 sis MUST BE IN POINT TO POINT MODE JS SHIELD NOT CONNECTED 1CP100 NOTE TD THELOGIC SOLVER MINIMUM OUTPUT MUST BEAT LEAST 8 mA THE LCP100 WHEN POWERED BY THE LOOP CO
3. Figure 2 Proper Cover Installation NOTE TIGHTEN THE SCREWS INA CRISS CROSS PATTERN TO HELP ENSURE PROPER COVER INSTALLATION ATEX IECEx ATEX 1126 Exe mb ib IICT4 Gb U3G ExicilcT4 Ge IECEX Ex e mb ib IIC T4 Gb ExiclIC T4 Gc Ta 40 C to 65 1 66 Entity parameters for intrinsically safe applications Ui 27 VDC Ci 1 1 nF and Li 0 Standards Used for Certification IEC 60079 0 2004 IEC 60079 11 2006 EN 60079 7 2007 IEC 60079 0 2007 IEC 60079 18 2004 EN 60079 11 2007 IEC 60079 7 2006 EN 60079 0 2006 EN 60079 18 2004 Instruction Manual LCP100 Local Control Panel D103272X012 November 2013 Special Conditions for Safe Use 1 For Exic installations itis not permitted to connect separate supplies to the LOOP LOOP and AUX LOOP terminals 2 If the equipment is installed in a zone 2 the installer shall take suitable steps to indicate whether the equipment is installed as Ex e mb ib or Exic Mounting Refer to figure 8 for dimensional information The LCP100 local control panel has four 4 mounting holes for on site mounting of the device The LCP100 must be installed so that the wiring connections are on the bottom to prevent accumulation of moisture inside the box Electrical Connections WARNING Select wiring andjor cable glands that are rated for the environment of use such as hazardous location ingress protection and temperature Failure to use properly rated wiring and or cab
4. We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management Marshalltown lowa 50158 USA Sorocaba 18087 Brazil x Chatham Kent ME4 4QZ UK Dubai United Arab Emirates es Singapore 128461 Singapore use EMERSON Process Management 2007 2013 Fisher Controls International LLC Al rights reserved
5. automatically set under Travel Alerts HiHi Lo Lo Enable Yes Lo Lo Point 1 o Hi Hi Point amp 99 Deadband X 0 5 DVC Power Up Manual Reset Continue to set up the digital valve controller according the normal set up procedure Remember to place the instrument back in service before disconnecting Note An alternative method to configure the LCP100 is through Detailed Setup Using the Field Communicator select Configure gt Manual Setup gt Instrument gt Terminal Box gt Edit Auxiliary Terminal Action gt SIS Local Control Panel When this setting is downloaded to the device an information screen will pop up advising that some additional parameters will be configured Select Yes Principle of Operation The lights indicate the state of the valve as described in table 3 Table 3 Fisher LCP100 Light and Button Operation WHAT THELCP100 LIGHTS SHOW POSSIBLE CONDITIONS BESS INDICATED BUTTON TO 3 Top Middle Bottom Solid he valve is inis normal operating state Tip Run PST The valve sin the process of running a partial stroke Stop PST Stop PST FastBlink 1 2 second The valve snot atits normal operating position because Acknowledge Try in 4 actuator pressure is low or the valve is stuck PST Failure T he valve stripped utis stuck at the normal postion E zl Slow Blink 1 second A part
6. control panel are shown in table 1 Instruction Manual LCP100 Local Control Panel D103272X012 November 2013 Table 2 Electromagnetic Immunity Performance Criteria Performance Port Phenomenon Basic Standard Test Level ores Electrostatic discharge ESD 1EC61000 4 2 EF A Endosure BO to 1000 TOV with T KHZAMat 80 Radiated EM field 1EC61000 4 3 1400 to 2000 MHz 3V m with 1 kHz AM at 80 A 2000102700 MHz 1V m with 1 kHz AMat 80 Tata aes TRV TOlines Burst fast transients 1EC61000 4 4 pio e 1O signal control surge y 1KV O lines 2I DC powerlines b Conducted RF TCT TSO KHz to 80 MHzat 3 Vims with ANGE BOY Li aE APA No degradation during testing B Temporary degradation during testing butisself recovering Installation WARNING Electrostatic charge hazard Do not rub or clean the LCP100 with solvents if a flammable vapor is present To do so could resultin an explosion Note Inside the LCP100 compartment direct all wiring to the left side away from the buttons Hazardous Area Classifications and Special Instructions for Safe Use and Installation in Hazardous Locations Certain nameplates may carry more than one approval and each approval may have unique installation wiring requirements and or conditions of safe use These special instructions for safe use are in addition to and may override the standard installati
7. point mode or voltage in multi drop mode from the logic solver The red button is not intended to perform the primary safety function for the process Maintenance WARNING Electrostatic charge hazard Do not rub or clean the LCP100 with solvents if a flammable vapor is present To do so could result in an explosion The LCP100 has four major components the housing lights conduit connections and electronics Ifa light is not working it can be replaced with the appropriate color The conduit connections do not normally need replacement The electronics module can be replaced as an assembly without having to disconnect the conduit connections or remove the box from its mounting Instrument Troubleshooting If difficulties are experienced with the LCP100 control panel refer to table 4 Table 4 Instrument Troubleshooting Symptom Possible Cause Action T Lights are not it T LEPT00 is not properly connected to the digital valve controller aux terminal T Ensure that the LCP100 is connected correctly to the digital valve controller aux terminal as described in the Installation section of this manual 2 LEPTOO is properly connected to the digital valve controller aux terminal but the lights are rot it Z Power switch is not set correctly 2 Ensure that the power switch is set correctly T Loop Power is used ensure that the switch position isset to Loop Power and NOT 24VDC and vice ve
8. valve moves to its normal operating position and then the green light comes on solid Emergency Demand through Local Control Panel 1 Press the pushbutton next to the red light 2 Observe that the valve moves to it fail safe position 3 Observe that the red light comes on solid and the yellow light comes on solid ready to reset 4 Press the pushbutton next to the green light 5 Observe that the red light goes off the valve moves to its normal operating position and then the green light comes on solid Setup In order for the LCP100 to operate properly it must be connected to a DVC6200 SIS with firmware revision 3 or later ora DVC6000 SIS device with firmware revision 7 or later Once the physical connections are made use the following checklist to configure the LCP100 Refer to the DVC6200 SIS instruction manual D103557X012 or the DVC6000 SIS instruction manual D103230X012 if additional setup information is needed Using a 475 Field Communicator select Configure gt Guided Setup gt Device Setup Follow the prompts on the Field Communicator Enter Supply Pressure and Unit Enter Actuator Make Model and Size Enter Partial Stroke test Starting Point Relay Type and Zero Power Condition select the instrument connected to local control panel LCP100 option Instruction Manual LCP100 Local Control Panel D103272X012 November 2013 Follow the prompts to complete Device Setup The following parameters will be
9. 2X012 Figure 7 Wiring for Loop Powered Configuration Logic Solver Wired to the FIELDVUE DVC60200 SIS then the Fisher LCP100 Intrinsically Safe Applications SWITCHTO LOOP POSITION CASE GROUND LOGIC SOLVER OUTPUT INTRINSICALLY 8 20 mA SAFE BARRIER user DVC6200 SIS TERMINAL BOX THE DVC6200 SIS MUST BE IN POINT TO POINT MODE SHIELD NOT CONNECTED TO LCP100 NON HAZARDOUS LOCATION HAZARDOUS LOCATION nome LT THE LOGIC SOLVER MINIMUM OUTPUT MUST BE ATLEAST 8 mA POINT TO POINT MODE THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY AmA Loop 100P Instruction Manual LCP100 Local Control Panel D103272x012 November 2013 Figure 8 Fisher LCP100 Local Control Panel Dimensions 257 9 don i 129 94 t f 67 cm 110 p 43 INCH Pre Setup Testing Before connecting the LCP100 to the process conduct the following tests on the LCP100 connected to the DVC6200 SIS Successful Partial Stroke Test 1 Press the Valve Test bottom pushbutton for more than 3 seconds but less than 10 seconds 2 Observe that the green light starts flashing when the valve starts moving 3 Observe that the valve moves no more than the configured partial stroke test travel limit 4 Observe that the valve returns to the normal operatin
10. Instruction Manual LCP100 Local Control Panel 103272x012 November 2013 Fisher LCP100 Local Control Panel Contents Figure 1 Fisher LCP100 Local Control Panel with Intrdu tlan z FIELDVUE DVC6200 SIS Digital Valve Controller Scope of Manual 1 and Bettis Actuator Description 12 Specifications 22 Installation 13 Hazardous Area Classifications and Special Instructions for Safe Use and Installation in Hazardous Areas Mounting M Electrical Connections 15 Pre Setup Testing 11 Setup 12 Principle of Operation 13 Maintenance 14 Troubleshooting 14 Parts Ordering 14 Parts List 15 Common Parts 15 Introduction Scope of Manual This instruction manual includes installation and maintenance information for the Fisher LCP100 local control panel figure 1 This device is used with Fisher FIELDVUE instruments in Safety Instrumented Systems SIS Refer to the DVC62I 5 Digital Valve Controllers for Instrumented System SIS Solutions instruction manual D103557X012 or the DVC6000 SIS Digital Valve Controllers for Safety Instrumented System SIS Solutions instruction manual D103230X012 for additional information Unless otherwise noted the information in this instruction manual applies to both DVC6200 SIS and DVC6000 SIS digital valve controllers For simplicity the DVC6200 SIS model name will be used throughout Do not install operate or mai
11. NSUMES APPROXIMATELY 4 mA POINT TO POINT MODE LcP100 TOGICSOLVER CT OUTPUT zac USER SUPPLIED DVC6200 SIS TERMINAL BOX 1 THE DVC6200 SIS MUST BE IN MULTI DROP MODE JS SHIELD NOT CONNECTED TO LCP100 NOTE LT THELCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA MULTI DROP MODE Instruction Manual LCP100 Local Control Panel D103272X012 November 2013 Figure 6 Wiring for Loop Powered Configuration Logic Solver Wired to the FIELDVUE DVC60200 SIS then the Fisher LCP100 Explosion proof Applications LcP100 aux TOGICSOLVER OUTPUT Loop 8 20 mA _ 100P USER SUPPLIED DVCG200 SIS TERMINAL BOX THE DVC6200 SIS MUST BE INPOINT TO POINT MODE SHIELD NOT CONNECTED TO LCP100 7 nome LT THE LOGIC SOLVER MINIMUM OUTPUT MUST BE RT LEAST mA THE LCP100 WHEN POWERED BY THE LOOP CONSUMES APPROXIMATELY 4 mA POINT TO POINT MODE TOLOOP POSITION aids CASEGROUND TOE SOTE OUTPUT Cr 2avoc ig USER SUPPLIED F y TSAO TE CONDITIONER pycezoosis TERMINAL BOX THEDVCS200 sis MUST BEIN MULTHDROP MODE JO SHIELD NOT CONNECTED TO LCP100 wore eterna wieurowenen ov metoor COMES ARONA MULTI DROP MODE LCP100 Local Control Panel November 2013 Instruction Manual D10327
12. arting on page 3 for specific approval information Electrical Housing IP66 Electromagnetic Interference EMI Meets EN 61326 1 First Edition Immunity Industrial locations per Table 2 of EN 61326 1 Standard Performance is shown in table 2 below Emissions Class A ISM equipment rating Group 1 Class A Connections Conduit 3 4 NPT or M20 Wiring 14to 26 AWG Torque Specifications Wiring terminals 0 5 Nem 4 5 inelbs Electrical Installation Wire connections are polarity sensitive Compatibility DVC6200 SIS with Firmware revision 3 or later DVC6000 SIS with Firmware revision 7 or later Installation Orientation Wiring entrance must be pointed down for self draining Dimensions 253 1 mm 10 inches long by 109 5 mm 4 3 inches wide by 127 8 mm 5 inches deep See figure 8 Construction Materials Housing material filled polyester Approximate Weight 2 2 kg 4 9 Ibs 1 The pressureftemperature limits in this document and any applicable standard or code imitation should not be exceeded 2 DVCB000 SIS Cable length is limited by maximum cable capacitance of 18000 p Description The LCP100 local control panel is used with the HART communicating DVC6200 SIS digital valve controller This panel is used to manually open and close a safety shutdown valve The LCP100 also provides a manual reset feature as well as a button for initiating a partial stroke test Specifications Typical specifications for the LCP100 local
13. g position and the green light comes on solid Manually Aborted Partial Stroke Test 1 Press the Valve Test bottom pushbutton for more than 3 seconds but less than 10 seconds 2 Observe that the green light starts flashing when the valve starts moving 3 Before the valve reaches the travel limit of the configured partial stroke test press the Valve Test pushbutton or the pushbutton next to the green light 4 Observe that the valve immediately returns to the normal operating position and the green light comes on solid LCP100 Local Control Panel Instruction Manual November 2013 D103272X012 Emergency Demand through the Logic Solver 1 Reduce the current to the DVC6200 SIS to 4 mA for de energize to trip operation Note Fora loop powered installation a minimum current of 8 mA is required at the trip state Safety Demand for proper functioning ofthe pushbuttons and lights 2 Observe that the valve moves to its fail safe state 3 Observe that the red light comes on solid and the yellow light stays off 4 Press the pushbutton next to the green light and observe that the valve does not move 5 Increase the current to the DVC6200 SIS to 20 mA for de energize to trip and observe that the valve remains in its fail safe state 6 Observe that the red light stays on solid and the yellow light comes on solid ready to reset 7 Press the pushbutton next to the green light 8 Observe that the red light goes off the
14. ial stroke test has failed Mind my RunPST The valves tripped due to loss of actuator pressure Acknowledge ri a e g solenoid valve trip PST Failure mare Solid The valve is tripped due to a command from the logic FA x i Jolver or LCP100 he valve ts stuck in the Wipped state i The valve is at mid travel after a trip The valve maybe moving or stuck in this position gt es E i Resetto ww The valve maybe eset tothe normaloperatingstate Resett ius ES NOTES ifthe green red and yellow lights are blinking in sequence then DVC5200 SIS is out of service In point to point mode the DVCS200 SIS w l not respond to a trip from the logic sober 2 Depending on the emergency shutdown valve configuration the top button could be labeled Vave Open and the middle button could be labeled Valve Close or vice versa The bottom button will aways be labeled Valve Test Acknowledgment ofa PST failure means that the LCP100 will return the blinking green light to solid green The PST alert wil stil be visible via HART communication with the DVC6200 SIS 4 ifthe red and green lights are both solid the vale is throttling in mid trave 5 The information contained in this table applies to firmware 9 and later B Instruction Manual D103272X012 LCP100 Local Control Panel November 2013 Note The primary safety function should be implemented by controlling the current in point to
15. le glands can result in personal injury or property damage from fire or explosion Wiring connections must be in accordance with local regional and national codes for any given hazardous area approval Failure to follow the local regional and national codes could result in personal injury or property damage from fire or explosion Electrical connections for explosion proof applications are shown in figures 3 5 and 6 Electrical connections for intrinsically safe applications are shown in figures 4 and 7 Note For intrinsically safe applications the LCP100 forms an intrinsically safe explosion protection system when used with intrinsically safe associated apparatus a barrier or with any other intrinsically safe devices The following requirements must be met Uo lt Ui lo lt li Po lt Pi Co gt Ci Cc Lo Li Lc There are two methods to power the LCP100 Method one requires an external 24 VDC source to power the LCP100 Method two uses loop power wiring in series In method one shown in figure 3 or 4 signal wiring is brought to the enclosure through a 3 4 NPT or M20 housing conduit connection connection type is identified on nameplate Method two can be accomplished in two ways with the wiring going first to the LCP100 then to the DVC6200 SIS as shown in in figure 5 or with the wiring going first to the DVC6200 SIS then to the LCP100 as shown in figure 6 or 7 However because the LCP100 does consume e
16. nergy to drive the pushbuttons and lights the minimum current signal from the logic solver must be 8 mA If the logic solver cannot provide an output range of 8 20 mA then method one must be used LCP100 Local Control Panel Instruction Manual November 2013 0103272 012 When connections are complete move DIP switch to the appropriate power setting If external 24 VDC is used to power the LCP100 make sure the switch is on the side that says 24VDC If loop power is used slide the switch to the side that says LOOP Note Factory default for the DIP switch power selector is 24VDC When installing the cover tighten the screws evenly in a criss cross pattern such as the one indicated in figure 2 to help ensure the cover is properly installed Figure 3 Wiring for 24 VDC External Power Configuration Explosion proof Applications LOGIC SOLVER OUTPUT 4 20 mA iE SWITCHTO 10 100 24VDC POSITION CASE GROUND 2avoc 24vpc SOURCE USER SUPPLEED 1 DVC6200 SIS TERMINAL BOX J SHIELD NOT CONNECTED TO LCP100 SIMPLE METHOD FOR INSTALLING AN LCP100 TO AN EXISTING DVC6200 SIS INSTRUMENT WHEN 24 VDC POWER IS AVAILABLE NOTE DO NOT CONNECT THELOOP TERMINAL IN THELCP100 TO THE LOOP TERMINALIN THE DVC5200 SS THIS WILL CAUSE THE LCPIOD TO UNNECESSARILY CONSUME 4 mA AT THE EXPENSE OF THE DVC6200 S D THIS CONNECTIONS ALSO LABELED LOOP
17. ntain an LCP100 local control panel without being fully trained and qualified in valve actuator and accessory installation operation and maintenance To avoid personal injury or property damage itis important to carefully read understand and follow all of the contents of this manual including all safety cautions and warnings If you have any questions about these instructions contact your Emerson Process Management sales office s EMERSON www Fisher com Process Management LCP100 Local Control Panel November 2013 Instruction Manual D103272X012 W External 24 VDC 10 50 mA maximum continuous current 100 mA maximum inrush W Loop 8 20 mA LCP100 and DVC6200 SIS combined Temperature Limits 40 to 65 C 40 to 149 Maximum distance between LCP100 and DVC6200 SIS digital valve controller Cable length is limited by maximum cable capacitance of 100 000 pF 2 Typical 314 meters 1030 feet with 18 AWG shielded Audio Control and Instrumentation Cable Electrical Classification CSA Exem IIC T4 Suitable for Zone 1 and Zone 2 locations ATEX Exe mb ib IIC T4 Gb Suitable for Zone 1 and Zone 2 locations ExiclIC T4 Suitable for Zone 2 locations IECEx Exe mb ib IIC T4 Gb Suitable for Zone 1 and Zone 2 locations ExicllC T4 Gc Suitable for Zone 2 locations Refer to Hazardous Area Classifications and Special Instructions for Safe Use and Installation in Hazardous Locations st
18. on Process Management may void your warranty and hazardous area approval might adversely affect the performance of the instrument and could cause personal injury and property damage Parts Kits Description Part Number LED Assemblies Kit Includes LED s qty 3 Yellow Red and Green keys 11 12 and 13 see figure 9 fasteners qty 6 key 8 see figure9 GE25751X012 Enclosure Labels Kit Includes labels ty 6 OPEN CLOSED VALVE OPEN VALVE CLOSE READY TO RESET and VALVE TEST GEIS750X012 Parts List Common Parts see figures 9 and 10 Key Description 3 3 4 NPT Conduit 2 req d M20 Conduit 2 req d Machine Screw 4 req d 5 3 Electronics Module see figure 10 Part Number GE24442X012 GE34487X012 GE22073X012 GE39919X012 Figure 9 Fisher LCP100 Assembly Recommended spare parts available in the LED Assemblies Parts Kit LCP100 Local Control Panel Instruction Manual November 2013 0103272 012 Figure 10 Key 9 Electronics Module Instruction Manual LCP100 Local Control Panel D103272x012 November 2013 Figure 11 Fisher LCP100 Connection to Explosion Proof Ex d FIELDVUE DVC6200 SIS Loop Power ZONE1 NON HAZARDOUS AREA LOGICSOLVER 1 xam LOOP POWERED LOGIC SOLVER WIRED TO LCP100 FIRST ZONE 1 OR2 NON HAZARDOUS AREA LOGIC SOLVER LOOP POWERED LOGIC SOLVER WIRED TO DVC6200 SIS FIRST
19. on procedures Special instructions are listed by approval WARNING Failure to follow these conditions of safe use could result in personal injury or property damage from fire or explosion and area re classification Note This information supplements the nameplate markings affixed to the product Always refer to the nameplate itself to identify the appropriate certification If the LCP100 is connected to a DVC6200 SIS in a zone 1 explosion proof d environment there must be a conduit seal installed between the DVC6200 SIS and the LCP100 in order to maintain the explosion proof integrity of the DVC6200 SIS Refer to figures 11 and 12 LCP100 Local Control Panel Instruction Manual November 2013 D103272X012 The LCP100 can be connected to a DVC6200 SIS that is part of an intrinsically safe system provided that you follow the instructions for the LCP100 Ex ic installation as shown in figures 4 and 7 The overall intrinsically safe system would be rated as an Ex ic system For all other approvals use zone 1 approved wiring practices CSA Exem IC IP66 Rated 30 VDC maximum 100 mA maximum temperature code rating T4 ambient temperature range 40 C to 65 C Special Conditions of Use 1 Install in an area that has a low risk of mechanical damage 2 Install the cover tightening the screws evenly in a criss cross pattern such as the one indicated in figure 2 to help ensure the cover is properly installed
20. rsa 3 The power switch is set correctly but the lights are 3 Loop Power option is selected but there is not enough current 3 The Loop Power Option requires mA current to operate Ensure that there is sufficient current 4 The LCPTO0 and the digital valve controller are properly connected and there is sufficient current but the lights are not lit 4 The ED may be damaged 4 Replace LED 5 Lights are blinking S Valves notatits normal stop S Check for proper calibration Re run calibration if necessary 6 Proper calibration but lights are blinking Lo Lo alerts settings not correctly set 6 Ensure that the Hi Hi Lo Lo Alert settings are 99 and 1 respectively For large rotary valve adjust settings to 98 and 2 and observe Parts Ordering When corresponding with your Emerson Process Management sales office about this equipment mention the serial number found on the nameplate 10 figure 9 of the unit When ordering replacement parts state the complete 11 character part number of each part required as found in the following parts list 14 Instruction Manual 0103272012 LCP100 Local Control Panel November 2013 WARNING Use only genuine Fisher replacement parts Components that are not supplied by Emerson Process Management should not under any circumstances be used in any Fisher instrument Use of components not supplied by Emers