Emerson FIELDVUEDVC2000 Instruction Manual

image

Contents

1. Command specific 16 Error Access Restricted Response Codes Command 44 Change Primary Variable Units Code This command is issued to change the units of the Primary Variable which is defined in the DVC2000 as the Analog Input loop current The choices for units are Percent code 57 or Milliamps code 39 This command should be sent prior to a Command 35 which sets the upper and lower Primary Variable range values In addition to changing the units code execution of this command will also change the DVC2000 s Analog Input Upper and Lower Range values to reflect the new units For example When the DVC2000 s Analog Input is configured as 4 20 mA and Command 44 with request Data Byte 57 is executed the DVC2000 s Analog Input units and range values will change to O 100 Likewise When the DVC2000 s Analog Input is configured as O 100 and Command 44 with request Data Byte 39 is executed the DVC2000 s Analog Input units and range values will change to 4 20 mA This command will be accepted when the DVC2000 s Instrument Mode is In Service but will be rejected if Write Protection is in effect Byte Format Description Allowable choices Request R Data Bytes 0 UINT8 Primary Variable Units Code Unit Code 39 mA or 57 Response Data Bytes 0 UINT8 Primary Variable Units Code Unit Code 39 mA or 57 Code Class Description Command 2 Invalid selection Units cod
2. Protected prevents configuration and calibration changes to the instrument The default setting is Not Protected Protection is controlled under software control Firmware and Language Pack Upgrade The firmware and language pack of any DVC2000 can be upgraded to the latest version using the Firmware Download tool in ValveLink software The new firmware incorporates all of the new functionality and corrections and improvements made to the technology of the DVC2000 product The firmware download process requires Around 30 minutes to complete e The DVC2000 s instrument mode must be Out of Service e The DVC2000 is powered with 12 mA or greater e That you isolate the valve from the process and equalize pressure on both sides of the valve or bleed off the process fluid because the routine will cause the DVC2000 to restart DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Dynamic Variables Four Dynamic Variables are implemented Default Meaning Units PV Analog Input mA SV Travel Setpoint TV Pressure PSI BAR KPA FV Travel Device Variables These variables represent measurements taken by the device are read only values and are all in float format These can be read with Commands 33 and 54 Variable ID Meaning Units 0 Analog Input mA 2 Pressure Port A PSI BAR KPA 3 Travel 4 Drive Signal 6
3. Travel Setpoint 9 Implied Valve Position Travel Target 10 Primary Feedback user selected either Travel or Pressure 211 Temperature Cor F Unit Codes Variable Units Code Units 0 No Units 6 Pounds per square inch psi 7 Bar 10 0A Kilograms per square centimeter kg cm 12 0C Kilopascals kPa 32 20 Celsius C 33 21 Fahrenheit F 39 27 Milliamps mA 39 Percent Instruction Manual Supplement DVC2000 Digital Valve Controller D103783x012 August 2014 Status Information Device Status The Field Device Status Byte is the only status byte defined in the HART protocol The order and meaning of each of the eight bits within the byte are fixed by the protocol This byte is one of the status bytes included with each HART response It is not part of the Command 48 data Bit Name of Status Bit Meaning Set cleared by the firmware based on self test results This bit is set if the 7 Field Device Malfunction He aen A position or temperature sensors provide invalid readings Two such bits exist internally one for each HART master Both copies are set 6 Confiduration Chanded when any variable HART message tag descriptor or date are changed from g g HART Cleared by command 38 separately for each master This bit survives loss of power 5 Cold Start Set by the firmware whenever a HARD RESET sequence is executed
4. Variable Assignment Value Units Status Last update va Additional status LOOP_CURRENT Pv 12 008 mA Good Not limited 06 16 14 10 25 17 Published data TRAVEL_SP sv 50 031 Good Not limited 06 16 14 10 25 17 Setu Soup PRESSURE Tv 26 594 PSI Good Not limited 06 16 14 10 25 17 H Help TRAVEL Qv 50 188 Good Not limited 06 16 14 10 25 17 CURRENT CURRENT 12 000 mA Good Not limited 06 16 14 10 25 17 4 Te internet Protected mode off Far Ri00 gt 7 For each Tag the Gateway provides updated values for e Variables e Additional Status e Published Data 23 DVC2000 Digital Valve Controller August 2014 Instruction Manual Supplement D103783X012 Published Data used for the Gateway s OPC and Modbus outputs falls into the following categories Field Device Identification Values Values that define the identity of the DVC2000 These include MANUFACTURER for Fisher Controls the value is 19 e DEVICE_TYPE for a DVC2000 the value is 5 e DEVICE_REVISION HARDWARE_REVISION e SOFTWARE_REVISION e DEVICE_ID e UNIVERSAL_REVISION HART version REQUEST_PREAMBLES Variable information The Gateway receives updates concerning the DVC2000 s four Dynamic Variables The information for any given device variable is displayed by 1 Dynamic Variable indicator PV SV etc 2 The Device Variable ID number assigned to that Dynamic Vari
5. decreases with increasing drive signal Partial Stroke Test a limited form of ramped valve diagnostic An 8 bit unsigned integer A 16 bit unsigned integer Refers to the IEEE 754 floating point format A special form of characters defined by HART in which 6 bit ASCII characters are packed into byte data A proprietary 16 bit integer format for numerical values used by some of this device s Device Specific commands Instruction Manual Supplement DVC2000 Digital Valve Controller D103783x012 August 2014 Reference Documentation HART Smart Communications Protocol Specification Revision 5 a group of documents specifying the HART Communication Protocol physical layers and Data Link Layers as defined by the HART Communications Foundation Bulletin 62 1 DVC2000 Fisher FIELDVUE DVC2000 Digital Valve Controller D103167X012 Fisher FIELDVUE DVC2000 Digital Valve Controllers Quick Start Guide D103203X012 Fisher FIELDVUE DVC2000 Digital Valve Controller Instruction Manual D103176X012 Device Identification Manufacturer Name Fisher Controls Model Name s DVC2000 Manufacture ID Code 19 13 Hex Device Type Code 5 05 Hex HART Protocol Revision 5 Device Revision 1 User Selectable HART Revision No between HART 5 and HART 7 Number of Device Variables 8 Physical Layers Supported FSK Physical Device Category Valve Positioner DVC2000 Digital Valve Controller Instruction Manual Supplemen
6. or at initial device power up Cleared by the first HART command 4 More Status Active when any bit in command 48 is active Active if the Instrument Mode of the DVC2000 is in the Out Of Service 3 Analog Input Fixed condition or if the Control Mode of the DVC2000 is in one of the digital set point modes 2 Not Used This bit is named Non Primary Variable Out Of Limits in the HART documentation for transmitters It has been renamed to reflect the fact that 1 Internal Sensor Out of Limits these variables are INTERNAL INPUTS to FIELDVUE products The firmware sets this bit when any sensor pressure position temperature exceeds its operating limits 0 Loop Current Out of Range Set when any variable 0 Analog Input is saturated DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Universal Commands The DVC2000 field device implements all HART Revision 5 Universal Commands Command 0 Read Unique Identifier Command 1 Read Primary Variable Command 2 Read P V Current and Percent of Range Command 3 Read Dynamic Variables and P V Current Command 6 Write Polling Address Command 11 Read Unique Identifier Associated with Tag Command 12 Read Message Command 13 Read Tag Descriptor Date Command 14 Read Primary Variable Transducer Information Command 15 Read Primary Variable Output Information Command 16 Read Final Assembly Number Command 17 Write Message Command 18 W
7. returned as the first variable PV in Command 3 Response 1 UINT8 ID of variable returned as the second variable SV in Command 3 Data Bytes 2 UINT8 ID of variable returned as the third variable TV in Command 3 3 UINT8 ID of variable returned as the fourth variable FV in Command 3 Code Class Description Command Specific None Response Codes Command 54 Read Device Variable Information Used to identify each of the Device Variables in the range of IDs 0 10 inclusive and 211 Responds with the Sensor Serial Number Sensor range Units Sensor ranges Damping Value and Minimum Span of the selected Variable The Variable range values will be in the same units as the Variable Units Byte Format Description Request Data 0 E Device Variable ID this command is applicable to variables 0 10 or 211 Bytes Nam All others will return invalid selection 0 UINT8 Device Variable ID 13 Device Variable Sensor Serial Number 24 bit number NOT USED always zero 4 UINT8 Device variable units code Kodi 5 8 Float Device Variable Upper Range y 9 12 Float Device Variable Lower Range Device Variable Damping Value ae moar NOT USED always w 17 20 Float Device Variable Minimum Span NOT USED always zero Code Class Description Command Specific 2 Invalid Selection Response Codes DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Device S
8. slot 3 See Device Variables on page 6 0 Variable ID Variable assigned to slot 0 1 Byte hex Slot 0 Variable units code 2 5 Float Slot 0 Variable value 6 VariableID Variable assigned to slot 1 7 Byte hex Slot 1 Variable units code Response 8 11 Float Slot 1 Variable value Data Bytes 12 Variable ID __ Variable assigned to slot 2 13 Byte hex Slot 2 Variable units code 14 17 Float Slot 2 Variable value 18 VariableID Variable assigned to slot 3 19 Byte hex Slot 3 Variable units code 20 23 Float Slot 3 Variable value Code Class Description Command Specific 2 Invalid selection Invalid Variable ID see note above Response Codes DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Command 35 Write Primary Variable Range Values In the DVC2000 the Primary Variable is defined to be the Analog Input loop current This command is used to write the ranging values reported in Command 15 It controls how the DVC2000 interprets the loop current when creating the Travel Target The upper range must be greater than the lower range This command does not do units conversion but requires that the units code supplied match the PV units configured in the device as set by Command 44 If the range values are in percent then they are assumed to be percent of 4 20 mA For example to range an increase to open unit from 8 mA to 16 mA but using percent range numbers specify lower_
9. DITIONAL_STATUS_3 ADDITIONAL_STATUS_4 ADDITIONAL_STATUS_5 ADDITIONAL_STATUS_6 ADDITIONAL_STATUS_7 Each of these status bytes represent eight individual bits with values that range from 00 to 255 To determine which of the eight bits are active requires converting a decimal value to its binary equivalent value Refer to Command 48 on page 17 for details on the individual alert bits inside of each Additional Status Byte ADDITIONAL_STATUS_0 According to Command 48 As defined in the Gateway Bit 7 Flash Integrity Failure FLASH_ROM_FAIL Bit 6 ee Bate TEMPERATURE_COMPENSATION_FAIL Bit 5 Reference Voltage Failure REFERENCE_VOLTAGE_FAIL Bit 4 Drive Current Failure DRIVE_CURRENT_FAIL Bit 3 Critical NVM Failure NVML_FAIL Bit 2 Temperature Sensor Failure TEMPERATURE_SENSOR_FAIL Bit 1 Pressure Sensor Failure PRESSURE_SENSOR_FAIL Bit O Travel Sensor Failure TRAVEL_SENSOR_FAIL 25 DVC2000 Digital Valve Controller August 2014 Instruction Manual Supplement D103783X012 ADDITIONAL_STATUS_1 According to Command 48 As defined in the Gateway Bit 7 Alert Record Not Empty Alert ALERT_RECORD_HAS_ENTRIES Bit 6 Auto Tune in Progress AUTO_TUNER_IN_PROGRESS Bit 5 Calibration in Progress Alert CALIBRATION_IN_PROGRESS Bit 4 Diagnostics in Progress Alert DIAGNOSTIC_IN_PROGRESS Bit 3 Pressure Fallback Active Alert PRESSURE_CONTROL_IS_ACTIVE Bit 2 Reserved Bit 1 R
10. FF LOW_IN_ EFFECT Bit 0 Drive Signal Alert DRIVE_SIGNAL_ALERT ADDITIONAL_STATUS_5 According to Command 48 As defined in the Gateway Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 Reserved Bit 2 Option Module Error LIMIT_SWITCH_ERROR Bit 1 Limit Switch 2 Status LIMIT_SWITCH_2_CLOSED Bit 0 Limit Switch 1 Status LIMIT_SWITCH_1_CLOSED ADDITIONAL_STATUS_6 According to Command 48 As defined in the Gateway Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 Reserved Bit 2 Reserved Bit 1 Reserved Bit 0 Reserved 27 DVC2000 Digital Valve Controller August 2014 Instruction Manual Supplement D103783X012 ADDITIONAL_STATUS_7 According to Command 48 As defined in the Gateway Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 Reserved Bit 2 Reserved Bit 1 Reserved Bit 0 Reserved Neither Emerson Emerson Process Management nor any of their affiliated entities assumes responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser and end user Fisher FIELDVUE and Rosemount are marks owned by one of the companies in the Emerson Process Management business unit of Emerson Electric Co Emerson Process Management Emerson and
11. Instruction Manual Supplement D103783X012 DVC2000 Digital Valve Controller August 2014 HART Field Device Specification Fisher FIELDVUE DVC2000 Digital Valve Controller HART Revision Device Type Device Revision Firmware Revision ess D HART 5 05 1 1 2 3 4 5 6 Introduction 0 cece ccc ee cee ees 2 Product Overview 00 ccc ccc cece ees 2 Purpose of this document 0 00 2 Abbreviations and definitions 2 Reference Documentation 00085 3 Device Identification 0 cece eee eee 3 Product Interfaces 0 cece cece eens 4 Control Valve Interface 00 cece ee eee 4 Host interface 0 ccc ccc cece ees 4 Output Options Circuit 008 5 Local User Interface 0 0c ccc eee cee es 5 Write Protection 0 cece cee eee 5 Firmware and Language Pack Upgrade 5 Dynamic Variables 0 cece cece eee eee 6 Device Variables 0 0 0 ccc cece cee eee 6 Status Information 0 ccc cee cece eee 7 Device Status 2 0 0 ccc cee eee eens 7 Universal Commands 0000 e cee e cence 8 Common Practice Commands 04 13 Supported Commands 0 0eee eens 13 Fo Device Specific Commands 0 00 20 Burst MOd aranin fee ee eas GRR EAS ee 20 Catch Device Variable 000005 20 Performance cc cece ce
12. Read Primary Variable Output Information This command returns the upper lower range values for the primary variable which is defined to be the loop current signal These are the loop current values for the ends of physical travel and are used to derive set point from the loop current It reports the range supplied in Command 35 For example the lower range for an increase to open valve will be the current which will produce a 0 set point However for an increase to close valve the lower range will be the loop current for a 100 set point The range values can be changed via Command 35 The DVC2000 assumes 0 4mA and 100 20mA Byte Format Description Returned Value Request Data bytes None PV Alarm Selection Code see Common Table 6 Alarm Selection Codes The Alarm Selection Code indicates the Enam action taken by the device under error conditions For a Actuators the action taken by the positioner is indicated PV Transfer Function Code see Common Table 3 Transfer Function Codes The Transfer Function Code must return 1 Enum 0 Linear if transfer functions are not supported by the 220 Nor UREN Response device Data Al Upper and Lower Range Values Units Code as supplied Bytes e Enan eS Ea g PP From CMD 35 3 6 Float Al Upper Range Value From CMD 35 7 10 Float Al Lower Range Value From CMD 35 11 14 Float PV Damping Value units of seconds 0 0 15 Enum Write Prot
13. able Dynamic Variable Device Variable ID Device Variable Name s Analog Input PV 0 LOOP_CURRENT Travel Setpoint SV 9 TRAVEL_SP Pressure TV 2 PRESSURE Travel QV 3 TRAVEL Milliamp Current 245 CURRENT Either of these choices Dynamic Variable or Device Variable ID can be substituted for the sign in the Variable Identifier fields below Variable Identifier Comments Explanation See any of the variable identifiers in the table immediately above _CLASS Always 0 _CODE The Device Variable ID number in the table immediately above _HEALTHY A true or false indication of the health of the sensor providing this value _STATUS _UNITS Decimal Variable Units code number from the Units Codes table on page 6 24 Instruction Manual Supplement D103783X012 DVC2000 Digital Valve Controller August 2014 Device Status The eight standard status conditions present in ANY HART field device are all represented by a Boolean true or false state These eight conditions discussed on page 7 are DEVICE_MALFUNCTION CONFIGURATION_CHANGED COLD_START MORE_STATUS_AVAILABLE LOOP_CURRENT_FIXED LOOP_CURRENT_SATURATED NONPRIMARY_VALUE_OUT_OF_LIMITS PRIMARY_VALUE_OUT_OF_LIMITS Detailed Device Alerts The Alert Groupings are ADDITIONAL_STATUS_0 ADDITIONAL_STATUS_1 ADDITIONAL_STATUS_2 AD
14. ce cee cee ees 20 Annex A Compatibility Checklist 21 Annex B DVC2000 Parameters as part of a Rosemount 1410 1420 WirelessHART Gateway ies ciavect ode See eins eden E EE E Ginls 22 Note This document does not include the DVC2000 AC product Device Type 13F5 which only supports Device Specific HART Commands and not Universal or Common Practice Commands r s EMERSON www Fisher com Process Management DVC2000 Digital Valve Controller August 2014 Instruction Manual Supplement D103783X012 Introduction Product Overview The DVC2000 digital valve controller is a communicating microprocessor based current to pneumatic valve positioner It is designed to replace standard pneumatic and electro pneumatic valve positioners In addition to the traditional function of converting an input current signal 4 20 mA to a pneumatic output pressure the DVC2000 digital valve controller communicates via a local display panel and or via the HART protocol An option is available which provides isolated circuitry for two 2 integrated limit switches for open close valve indication and a valve position transmitter for separate valve position feedback Purpose of this document This specification is designed to be a technical reference for HART capable host application developers system integrators and knowledgeable end users It also provides functional specifications e g commands enumerations and perf
15. e Count Alert Point 4 Travel Accumulator High 2 Active if the Travel Accumulator exceeds the Travel Accumulator Alert Alert Point 2 3 Instrument Time is Invalid Active if the instrument has been powered down since the last time Alert the instrument clock was set gt Alert Record Full Alert 2 ae when the alert record contains the maximum number of 20 1 Offline Failed Alert 2 Active if a shutdown alert has put the DVC2000 in a failed state 0 Reserved Reserved bits are always set to 0 1 Sets Field Device Malfunction 2 Sets More Status Available continued 17 DVC2000 Digital Valve Controller August 2014 Instruction Manual Supplement D103783X012 Additional Device Status Byte Bit Name of Status Bit Meaning 7 Reserved 6 Reserved 5 Reserved 4 Reserved 3 3 Reserved 2 Reserved 1 Integrator Saturated High Active if the instrument integrator is saturated at the high Alert extreme 0 ae a Saturated Low 2 Active if the instrument integrator is saturated at the low extreme 7 Travel Alert Lo 2 Active when the Travel is below the Travel Alert Lo Point 6 Travel Alert Lo Lo 2 Active when the Travel is below the Travel Alert Lo Lo Point 5 Travel Alert Hi 2 Active when the Travel exceeds the Travel Alert Hi Point 4 Travel Alert Hi Hi 2 Active when the Travel exceeds the Travel Alert H
16. e did not match configured units Specific Response 7 In Write Protect Mode Codes DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Command 48 Read Additional Status Byte Format Description Request Data 0 None bytes 0 Uint8 Command 48 Response Byte 0 1 Uint8 Command 48 Response Byte 1 2 Uint8 Command 48 Response Byte 2 Response 3 Uint8 Command 48 Response Byte 3 Data Bytes 4 Uint8 Command 48 Response Byte 4 5 Uint8 Command 48 Response Byte 5 6 Uint8 Reserved 7 Uint8 Reserved Instruction Manual Supplement DVC2000 Digital Valve Controller D103783X012 August 2014 Additional Device Status Command 48 returns 8 bytes of data with the following status information Byte Bit Name of Status Bit Meaning 7 Flash Integrity Failure 1 2 Active if there is a failure associated with flash ROM read only memory 6 Temperature Compensation 4 2 Active if the microprocessor detects a fault in the temperature Data Integrity Error compensation data 5 Reference Voltage Failure 1 2 Active if there is a failure associated with the internal voltage reference 4 Drive Current Failure 1 2 Active when the drive current to the I P converter is not flowing as 0 aad o 3 Critical NVM Failure 1 2 Active if there is a failure of non volatile memory used for con
17. ect Code 0 Disabled 1 Enabled Oor1 16 Enum Reserved Must be set to 250 Not Used 250 Code Class Description Response Codes None Instruction Manual Supplement D103783X012 DVC2000 Digital Valve Controller August 2014 Common Practice Commands The DVC2000 field device supports the following common practice commands Supported Commands Command 33 Read Device Variables Command 35 Write Primary Variable Range Values Command 38 Reset Configuration Change Flag Command 42 Master Reset Command 44 Change Primary Variable Units Code Command 48 Read Additional Status Command 50 Read Dynamic Variable Assignments Command 54 Read Device Variable Information Command 108 Write Burst Mode Command Number Command 109 Burst Control Mode Command 33 Read Device Variables This command is used to read the value of up to four selected Device Variables The Device Variables and the Variable Units Code are listed on page 6 Note If any one of the requested variable IDs is invalid the INVALID_SELECTION error will be returned along with no data bytes Byte Format Description Allowable choices 0 Variable ID Variable assigned to slot 0 See Device Variables on page 6 Request 1 VariableID Variable assigned to slot 1 See Device Variables on page 6 Data Bytes 2 VariableID Variable assigned to slot 2 See Device Variables on page 6 3 VariableID Variable assigned to
18. eserved Bit O Auto Cal in Progress Alert AUTO_TRAVEL_CALIBRATION_IN_PROGRESS ADDITIONAL_STATUS_2 According to Command 48 As defined in the Gateway Bit 7 Reserved Bit 6 Reserved Bit 5 Cycle Counter Alert CYCLE_COUNT_ALERT Bit 4 Travel Accumulator High Alert TRAVEL_ACCUMULATOR_ALERT Bit 3 Instrument Time is Invalid Alert INSTRUMENT_TIME_IS_INVALID Bit 2 Alert Record Full Alert ALERT_RECORD_IS_FULL Bit 1 Offline Failed Alert OFFLINE_FAILED_ALERT Bit 0 Reserved ADDITIONAL_STATUS_3 According to Command 48 As defined in the Gateway Bit 7 Reserved Bit 6 Reserved Bit 5 Reserved Bit 4 Reserved Bit 3 Reserved Bit 2 Reserved Bit 1 Integrator Saturated High Alert INTEGRATOR_SATURATED_HIGH Bit 0 Integrator Saturated Low Alert INTEGRATOR_SATURATED_LOW 26 Instruction Manual Supplement D103783X012 DVC2000 Digital Valve Controller August 2014 ADDITIONAL_STATUS_4 According to Command 48 As defined in the Gateway Bit 7 Travel Alert Lo TRAVEL_ALERT_LO Bit6 Travel Alert Lo Lo TRAVEL_ALERT_LO_LO Bit 5 Travel Alert Hi TRAVEL_ALERT_HI Bit 4 Travel Alert Hi Hi TRAVEL_ALERT_HI_HI Bit 3 Travel Deviation Alert TRAVEL_DEVIATION_ALERT rae TRAVEL_LIMIT_HI_OR_ Bit 2 Travel Limit Cutoff Hi Alert TRAVEL CUTOFF_H_ IN EFFECT Sih x TRAVEL_LIMIT_LOW_OR_ Bit 1 Travel Limit Cutoff Lo Alert TRAVEL CUTO
19. figuration data critical for instrument operation 2 Temperature Sensor Failure T Active when the instrument temperature sensor fails or the sensor reading is outside of the range of 60 to 100 C 76 to 212 F 1 Pressure Sanson eailure 2 Active if the pressure sensor reading is outside the range of 24 0 to 125 0 of the calibrated pressure for more than 60 seconds 0O Travel 12 Active if the sensed travel is outside the range of 25 0 to 125 0 ravel Sensor Failure i of calibrated travel 7 Alert Record Not Empty Alert 2 Active when there are 1 or more alerts stored in the alert record 6 AutoTune in Progress 2 Active if AutoTune Routine is in progress 5 Calibration In Progress Alert 2 Active when calibration is in progress 4 Diagnostics in Progress Alert 2 Active when a diagnostic test is in progress 3 p F Active when the instrument has detected a problem with the travel ressure Fallback Active Alert i 1 feedback and is now controlling the output like an I P transducer are Custom Characterization in Effect active if the user defined Custom 2 Custom Characterization Tana Characterization is enabled 1 Input Characterization Input Characterization in Effect active if any of the user defined Characterizations other than Linear is enabled 0 Auto Cal in Progress Alert 2 Active when auto calibration is in progress 7 Reserved 6 Reserved 5 Cycle Counter Alert 2 Active if the Cycle Counter exceeds the Cycl
20. han digital setpoint values and write protect status will cause the configuration change flag to be set Byte Format Description Request none Data Bytes Response Data Bytes ee Code Class Description Command Specific none Response Codes Instruction Manual Supplement DVC2000 Digital Valve Controller D103783x012 August 2014 Command 42 Perform Master Reset This reset command has two options If no data bytes are supplied respond immediately and then perform a warm reset This is not equivalent to power up in that restart modes and default IVP are not adopted and the real time clock is not reset All other data is read from nonvolatile memory and put into effect The second option is hard reset This requires two data bytes set as described below If this form is received the unit will save modes and counters then execute a hard reset by exercising the watchdog timer The next response will have the cold_start bit set A soft reset command will be honored while the DVC2000 Instrument Mode is in the In Service condition A hard reset command requires the DVC2000 Instrument Mode be in the Out of Service condition Byte Format Description ie hai 0 1 Uint16 Optional If hex 0x6969 is supplied as request data bytes a hard bytes reset is performed Otherwise a soft reset is performed Response Data None Bytes Code Class Description
21. i Hi Point Active if the difference between the Travel Target and the Travel 4 3 Travel Deviation Alert 2 exceeds the Travel Deviation Alert Point for more than the Travel Deviation Time 2 Travel Limit Cutoff Hi Alert Active when the Travel exceeds the Hi Limit Cutoff Point 1 Travel Limit Cutoff Lo Alert Active when the Travel falls below the Lo Limit Cutoff Point 0 Drive Signal Alert 2 Active when the Drive Signal exceeds target limits lt 10 or gt 90 for more than 20 seconds when not in Cutoff condition 7 Reserved 6 Reserved 5 Reserved 5 4 Reserved 3 Reserved 2 Option Module Error 1 Limit Switch 2 Status Set to 1 if Limit Switch 2 is enabled powered and closed 0 Limit Switch 1 Status Set to 1 if Limit Switch 1 is enabled powered and closed 7 Reserved 6 Reserved 5 Reserved 6 4 Reserved 3 Reserved 2 Reserved 1 Reserved 0 Reserved Reserved bits are always set to 0 1 Sets Field Device Malfunction 2 Sets More Status Available Instruction Manual Supplement DVC2000 Digital Valve Controller D103783X012 August 2014 Command 50 Read Dynamic Variable Assignments This command returns a list of four device variable codes taken from table DVC Device Variables which are returned in Command 3 These Dynamic Variables are fixed and control the Command 3 response whether burst or by request Byte Format Description Request Data B tes None 0 UINT8 ID of variable
22. iscovery Mode ii eatin ii Configure HART Polling TAE a Configure HART Poling i Please select the primary device information you would like the THUM Overview to transmit from list below Set HART commands that the wired device reports Primary Information Type Y Service Tools a ai Time Curent z Close Help Device last synchronized 7 16 2014 9 20 45 AM I __ Select Yes if changes are required FOR SECONDARY DEVICE INFORMATION Select Device Status Configure HART Polling Please select the primary device information you would like the THUM to transmit from list below The THUM may transmit two types of information from the wired device Below is the current information that the THUM will transmit From the primary device PY SV TV and OV v Secondary Information Type Device Status Z Would you like to change this information No Cancel Help 22 Instruction Manual Supplement DVC2000 Digital Valve Controller D103783X012 August 2014 The FIELDVUE instrument is defined on the Gateway by Tag read from the device s Message field loxi Qm S eee af File Edit View Favorites Tools Help oy Favorites 2 a A D I me Pag Safety Toos A a EMERSON Smart Wireless Gateway Process Management HART Variables m admin Device name DVC2000 Diagnostics a A Explorer MER riable
23. log Input loop current The units are either mA or as configured in the device by Command 44 Byte Format Description Request ars Data Bytes Response 0 Byte hex Primary Variable Unit Code either 39 mA or 57 Data Bytes 1 4 Float Primary Variable value Code Class Description Command Specific none Response Codes Command 2 Read Primary Variable and Percent of Range This command reads the value of the DVC2000 s loop current in implied units of mA regardless of the configured setting by Command 44 and the measured Valve Travel in implied units of Byte Format Description Request noe Data Bytes Response 0 3 Float Loop Current Data Bytes 4 7 Float Valve Travel Code Class Description Command Specific none Response Codes Instruction Manual Supplement DVC2000 Digital Valve Controller D103783X012 August 2014 Command 3 Read Dynamic Variables and Loop Current This command is used to read the value of Loop Current and the four Dynamic Variables The four dynamic variables returned depend upon the variable assignment as defined by Command 51 and read back via Command 50 The default Dynamic Variable assignment and the Variable Units Codes are shown on page 6 Byte Format Description Request Nie Data Bytes 0 3 Float Loop Current implied units of mA 4 Byte hex Primary Variable PV
24. mount 1410 1420 WirelessHART Gateway A FIELDVUE DVC2000 can join a wireless network through the addition of a Rosemount 775 THUM WirelessHART adapter The wireless adapter acts both as a HART modem for communications coming to the DVC2000 from application software and as an independent master issuing commands periodically to the wired device pertaining to the device s status This independently gathered status information is relayed back to the Rosemount 1410 or 1420 Wireless Gateway and is made available to the user either through viewing the HTML interface or via mapping as Published Data parameters via the Gateway s MODBUS or OPC outputs For HART 5 devices the PV SV TV and QV variables can be mapped Configure the THUM as follows Navigate to Configure gt Manual Setup Under the Wired Device tab select Configure HART Polling Wired Device tab 07 16 2014 14 49 04 840 THUM Adapter Rev 1 lolx File Actions Help SiR x Wireless Wired Device Electronics Temperature THUM Information Other aw bared Setup p Smart Power Options gt Manual Setup 4 20 m Current pte THUN for avalable loop current 2 lt Vari a t 3 5t0 25 mA EELA High Curent Mode gt ISMA FOR PRIMARY DEVICE INFORMATION ge pe E Optimize THUM for available voltage ariable Voltage Drop g Variable 2 5 Volts or le Pred 25 vets Select PV SV TV and QV m Wired Device Set how THUM detects wired devices D
25. ormance requirements used during field device development maintenance and testing This document assumes the reader is familiar with HART Protocol requirements and terminology Additional product information is available in DVC2000 product literature available from Emerson Process Management Abbreviations and definitions AR Configuration Variables Device Variable Enumeration MV NV Point PS1 PS2 PST Byte Word Float Packed ASCII Standard Span Format Alert Record Variables which represent nonvolatile values of manufacturing initialized data or user specified configuration information These variables cannot be enumerated via Command 54 and as such stand on their own with no associated units or range information Measured variables that are exposed to HART and can be enumerated using Command 54 Generally there are variables whose ID is in the range of 0 to 10 and are associated with units codes status and range values A pre defined set of values or text Measured Variable a physical input to the instrument Named Variable a logical point inside the device hard mapped to a given MV as the source of NV data Aterm that applies to diagnostic data packets It is defined as a collection of periodically sampled variables captured at a single instant in time It does not include the Monitor point The PORT A output pressure which increases with increasing drive signal The PORT B output pressure which
26. pecific Commands The DVC2000 field device supports device specific commands However these device specific commands require use of the ValveLink software application or DD methods and cannot be utilized outside of those controlled environments Burst Mode This field device supports Burst Mode Catch Device Variable This field device does not support Catch Device Variable Performance Refer to the DVC2000 Instruction Manual D103176X012 or Product Bulletin 62 1 DVC2000 D103167X012 for details on DVC2000 performance 20 Instruction Manual Supplement D103783X012 DVC2000 Digital Valve Controller August 2014 Annex A Compatibility Checklist Manufacturer Model and Revision Fisher Controls DVC2000 Device Revision 1 Device Type Pneumatic Control Valve Positioner HART Protocol Revision 5 User switchable between HART 5 mode and HART 7 mode ne Device Description Available Yes Number and type of process connections None Number of host connections Input Control signal to Loop terminals Number of Dynamic Variables 4 Mappable Dynamic Variables No Number of Device Variables 8 Number of Supported Common Practice 10 Commands Burst Mode Yes Capture Device Variables No Write Protection Yes 21 DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Annex B DVC2000 Parameters as part of a Rose
27. range 25 and upper_range 75 This ranging is done in conjunction with the zero power condition For an Increase to Open valve the lower range is the 0 setpoint level valve plug in the valve seat while the upper range is the 100 setpoint level An Increase to Close valve is exactly opposite This command will be accepted when the DVC2000 s Instrument Mode is In Service but will be rejected if Write Protection is in effect Byte Format Description Allowable choices 0 UINT8 Upper and Lower Range Values Unit Code Unit Code 39 mA or 57 Bice 1 4 Float Primary Variable Upper Range Value y 5 8 Float Primary Variable Lower Range Value 0 UINT8 Upper and Lower Range Values Unit Code Unit Code 39 mA or 57 neues 1 4 Float Primary Variable Upper Range Value y 5 8 Float Primary Variable Lower Range Value Code Class Description Command 2 Invalid selection Units code did not match configured units Specific 7 In Write Protect Mode Response 16 Access Restricted other master has access locked Codes 32 Busy Command 38 Reset Configuration Change Flag Resets the configuration changed flag in the DVC2000 The DVC2000 contains two configuration changed bits one for each master Both bits are set when any write operation occurs This command clears the bit corresponding to the master sending this command leaving the other bit unmodified Any write to the DVC2000 other t
28. rite Tag Descriptor Date Command 19 Write Final Assembly Number Instruction Manual Supplement DVC2000 Digital Valve Controller D103783X012 August 2014 Command 0 Read Unique Identifiers Byte Description Format Value Request nore Data Bytes 0 Data type expansion code Byte hex FE 1 Manufacturer identification code Byte hex 13 2 Manufacturer s Device Type code Byte hex 03 3 Number of preambles Byte hex 05 Response 4 Universal command revision Byte hex 05 Data Bytes 5 Device revision Byte hex 01 6 Software revision Byte unsigned integer See table 1 below 7 Hardware revision Byte unsigned integer See table 2 below 8 Device function flags Not Used 00 9 Device Identification number 3 Bytes hex Code Description Command Specific Response NONE Codes Table 1 Device and Software Revision Device Revision Software Revision Description 01 Firmware Revision 1 02 Firmware Revision 2 03 Firmware Revision 3 m 04 Firmware Revision 4 05 Firmware Revision 5 06 Firmware Revision 6 Table 2 Hardware Revision Hardware Revision Description 08 Hardware Revision 1 11 Hardware Revision 2 DVC2000 Digital Valve Controller Instruction Manual Supplement D103783X012 August 2014 Command 1 Read Primary Variable This command reads the value of the DVC2000 s Primary Variable which is Ana
29. rom each other and from the digital valve controller s primary feedback If only one switch is to be used you must use channel 1 Although electrically isolated per Intrinsic Safety requirements channel 2 derives its power from channel 1 Therefore channel 2 cannot be used alone Position Transmitter On units that are supplied with an integral valve position transmitter additional terminals provide the field wiring connection point The position transmitter circuit in the DVC2000 derives it s operating power from the 4 20 mA control system input in the same manner as a 2 wire transmitter In addition the transmitter function gets position information through an opto isolator from the digital valve controller so the 4 20 mA position control loop must also be powered in order for the position transmitter to provide an output representing the valve position Local User Interface The local user interface is available on all DVC2000 digital valve controllers The interface consists of a liquid crystal display four pushbuttons and a switch for position transmitter configuration The DVC2000 is supplied with one of three different language packs preinstalled depending on the firmware revision and ordering option Refer to the DVC2000 instruction manual for additional details on using the Local User Interface to configure and calibrate the DVC2000 Write Protection There are two Write Protection states for the DVC2000 Not Protected or Protected
30. t August 2014 D103783X012 Product Interfaces Control Valve Interface The DVC2000 digital valve controller is mechanically attached to the valve s actuator by means of a mounting bracket The control valve s position is conveyed to the travel sensor of the DVC2000 digital valve controller by means of the feedback bracket and magnet assembly attached to the actuator s stem or rotating travel sensor bid MAGNET ASSEMBLY ATTACHED TO VALVE STEM Pneumatic tubing connected to the DVC2000 brings instrument supply air to the DVC2000 and takes controlled output air from the DVC2000 to the actuator A pressure sensor in the DVC2000 measures the pressure signal and presents it as a device variable Host interface The input to the DVC2000 can either be two wire 4 to 20 mA current loop in point to point mode This input is connected in the DVC2000 s terminal box on two terminals marked LOOP and LOOP Refer to the DVC2000 quick start guide for connection details Instruction Manual Supplement DVC2000 Digital Valve Controller D103783x012 August 2014 Output Options Circuit All three options circuits transmitter switch 1 and switch 2 control current from an external power source similar to the operation of a 2 wire transmitter Limit Switches On units that are supplied with integral limit switches additional terminals provide the field wiring connection point The limit switches are isolated f
31. the Emerson logo are trademarks and service marks of Emerson Electric Co HART and WirelessHART are marks owned by the HART Communication Foundation All other marks are the property of their respective owners The contents of this publication are presented for informational purposes only and while every effort has been made to ensure their accuracy they are not to be construed as warranties or guarantees express or implied regarding the products or services described herein or their use or applicability All sales are governed by our terms and conditions which are available upon request We reserve the right to modify or improve the designs or specifications of such products at any time without notice Emerson Process Management Marshalltown lowa 50158 USA Sorocaba 18087 Brazil Chatham Kent ME4 4QZ UK Dubai United Arab Emirates Singapore 128461 Singapore www Fisher com 2013 2014 Fisher Controls International LLC All rights reserved Tal CJ J EMERSON pi
32. units code 5 8 Float Primary Variable PV value 9 Byte hex Secondary Variable SV units code Response 10 13 Float Secondary Variable SV value Data Bytes ondary y 14 Byte hex Tertiary Variable TV units code 15 18 Float Tertiary Variable TV value 19 Byte hex Fourth Variable FV or QV units code 20 23 Float Fourth Variable FV or QV value Code Class Description Command Specific 8 Warni PAST i arning Value read invalid one of the variables is out of range Response Codes Command 14 Read Primary Variable Transducer Information The transducer limits reported in this command indicate that these values are set to Not Used Note The Transducer Serial Number is not applicable to the DVC2000 and is set to 0 The other parameters will be set to Ox7F OxA0 0x00 or 250 Not Used when they are not applicable Byte Format Description Returned Value Request Data bytes None 0 2 UINT24 Transducer Serial Number 000000 3 Enum Transducer Limits and Minimum Span Units Code 250 Not Used Response Data 4 7 Float Upper Transducer Limit 7FA00000 Not A Number NAN Bytes 8 11 Float Lower Transducer Limit 7FA00000 Not A Number NAN 12 15 Float Minimum Span 7FA00000 Not A Number NAN Code Class Description Response Codes MONE DVC2000 Digital Valve Controller Instruction Manual Supplement August 2014 D103783X012 Command 15

Download Pdf Manuals

image

Related Search

Related Contents

NanoVue - GE Healthcare Life Sciences  USER MANUAL XLCT - series  Silcoseal Select : Quick User Guide  Rabbit ® 6000 Microprocessor User`s Manual  MANUEL D`UTILISATION DU MULTIMETRE B&K 2408  USeR ManUal  Toshiba Satellite C75-A7390    ficha tecnica  Sea Gull Lighting 49851BLE-782 Installation Guide  