Delta Electronics 1Phase User's Manual
Contents
1. X XX gt O Product Type 060 12097 120 Wat XX X XXXX XXXX X XX 240W 240 480W 480 Watt gt SEE Model XX X XXXX XXXX X XX P Power Supply gt EE Phase XX X XXXX XXXX X XX 606 aaiae Voltage 024V 24 Voltage XX X XXXX XXXX X XX gt 6 EEE Variation Eg Customer material Etc Delta standard metal case 4 13 Rev 00 1 10 2011 DELTA Switch Mode Power Suppl DRPO024V060W1BA Block Diagrams Connections Block Diagram of Power Supply e DRPO24V060W1BA Overall Block amp Wiring Diagram PRIMARY FILTER k E 5 13 1 10 2011 EDE 11414248 i i SECONDARY Rev 00 A NELTA Switch Mode Power Suppl DRP024V060W1BA Engineering Data Note 6 13 O 1 Derating Curve Both of Horizontal and Vertical Model DRPO24VO60W1BA aS D O gt lt gt O O A 10 0 10 Do not use the device in areas outside of the shaded portion shown in the above graph Internal parts may gradually deteriorate and become damaged Based on the above graph if the ambient temperature is greater than 50 C the output capacity has to be reduced by 2 5 per Celsius temperature increase If not the device will go into over temperature protection by switching off i e device will go into bouncing mode It will 1 10 2011 20 4 Ambient Temperature C 50 60 recov
2. 2 Energy Star Level Output Data 2 4 42222242 VW 7 4W gt 89 typical Residual ripple peak switching 20 MHz at nominal values Certification Standards ees Safety transformers for switched mode power supply units 1 lt lt lt TUV BAUART to EN60950 1 UL C UL recognized to Electrical safety of information technology equipment UL60950 1 CSA 22 2 No 60950 1 CB scheme to IEC60950 1 UL C UL Listed UL508 and CSA 22 2 107 1 01 CSA to CSA C22 2 No 107 1 01 file no 181564 Safety entry low voltage PELV EN60204 SELV EN60950 Protection against shock currents basic requirements for protective VDE 0106 101 separation in electrical equipment Limitation of mains harmonic currents DIN57100 410 Industrial Control Equipment 2 13 Rev 00 1 10 2011 A DELTA Switch Mode Power Suppl DRPO24V060W1BA General Data 4000 Isolation voltage Input output type test routine test 4 KVAC 3 KVAC Input PE type test routine test 1 5 KVAG 1 5 KVAC output PE type test routine test 1 5 KVAG 500 VAC Degree of protection Class of protection MTBF Type of housing Aluminium 5052 Dimensions L W H STATUS Indicator Climate Data 0 i O Ambient temperature Operating 20 C to 80 C gt 50 C de rating Ambient temperature Storage 25 to 85 10Hz to 500Hz 30 S 3G peak displacement of 0 35mm Vibration Non Operating 60min per axis for al
3. DELTA Switch Mode Power Suppl DRPO24VO60W1BA 60W 1Phase DIN Rall DRPO24VO6OW1BA Summary The new CliQ II DRPO24V060W1BA is the latest offering from one of the world s largest power supply manufacturers Delta The product offers a nominal output voltage of 24 V a wide temperature range from 20 C to 80 C and a minimum holdup time of 20 ms The state of the art design is made to withstand harsh industrial environments The rugged ultra compact metal case is shock and vibration resistant according to IEC60068 2 1 13 1 10 2011 Features Ease of wire connection to terminals Comes with detachable connectors Overload Overvoltage amp Thermal protection Efficiency gt 89 Power boost 150 for 3 seconds Expected life time 10 years Redundancy Yes with external ORing diode RoHS amp IP20 compliant Meet Energy Star Level 5 3 years warranty The 60 watts DIN Rail power supply provides overvoltage overload and thermal protection Due to the wide input voltage range from 85 to 264 VAC the Delta s CliQ II power supply is worldwide usable It also comes with multiple output terminals for fast wiring and easy installation Rev 00 A DELTA Switch Mode Power Suppl DRPO24V060W1BA Technical Data 60W1Ph Input Data 1 Nominal input voltage and frequency Voltage range 85 264VAC 120 375 VDC Frequency Range Nominal current Leakage current lt 1
4. 1 to Ground of PSU1 VA2 to Ground of PSU2 Ensure that the output voltages the same even after the 2 Power Supplies are connected to load If not adjust them with the VR available on the front panel A tolerance of 25mV would be acceptable Note 1 If the output voltage of any Power Supply is higher it will take the initial load and share the maximum load 2 If the output voltages are the same then an equal load current sharing between the 2 Power Supplies can be achieved 3 The ORing diode must be of an appropriate rating The rating must be at least 4 times of the output load current and at least reverse voltage rating of 20Vrr 4 The use of a heat sink is advised to ensure the ORing Diode does not overheat 5 Recommended Redundancy Module DRR 20A 13 13 Rev 00 1 10 2011
5. Max OVP Level lt 35V Max 16 66 Nominal Auto recovery to Voltage normal output Zero output voltage Typical Over voltage condition as seen at the OP e Inrush Current Start up Time Output Hold up Time Inrush Current Inrush current is the first surge current seen on the input side when AC input is applied to the Power Supply It is the first pulse captured See below for the Inrush current in a typical Power Supply Start up Time Start up time is measured from the point AC input is applied to the point output voltage reaches within 90 of its set value See below for a typical start up time characteristic Rise Time Rise time is measured from the point output voltage rises from 10 to 90 of its set value See below for a typical rise time measurement 9 13 Rev 00 1 10 2011 A DELTA Switch Mode Power Suppl DRPO24V060W1BA Hold up Time Hold time is the time when the AC input collapses and o p voltage retains regulation for a certain period of time is called as hold up time See in the picture below a typical hold up time characteristic of a power supply The hold time is measured until the output voltage remains in regulation hence it measured until the output voltage reaches minimum regulation 2 of its set value 10 of Vo Rise Time 1 Start up Time Hold Up Time Output 2 Output Voltage Vo AC input Voltage ON N fi ay Vi V V V
6. automatically when the overload condition is removed voltage OLP OCP Output Voltage i Load gt 150 Hiccup OP load e Short Circuit Protection The Power Supply has a short circuit protection which is in line with the overload protection and activates whenever there is a short across the output voltage It will go into bouncing mode and recovers automatically when the fault is removed e Over Temperature Protection The Power Supply has an over temperature protection OTP This is activated when the overload condition persists for an extended duration and the output current is below the overload trigger point but gt 100 load In the event of a higher ambient operating condition at 100 load the Power Supply will run into OTP when the ambient temperature is gt 55 C When activated the output voltage will go into bouncing mode until the operating ambient temperature drops to 50 C or output capacity is reduced as recommended in the graph 8 13 Rev 00 1 10 2011 A DELTA Switch Mode Power Suppl DRPO24V060W1BA e Overvoltage protection The Power Supply has an overvoltage protection OVP and is activated when the power supply feedback circuit fails The output voltage will not be gt 35V under any Line Load and operating ambient temperature The Power Supply does not shut down but goes into Hiccup mode Auto Recovery The output voltage will recover back to 24VDC once the fault is removed
7. IV V lush current on input application AC Input Current N N Tal f Ay U U te input Voltage Output Voltage Adjust 24VDC connection is made using the and screw connections At the time of delivery the output voltage is 24VDC The output voltage can be set from 24 to 28VDC on the potentiometer seen as Adjust on the front panel of each power supply 10 13 Rev 00 1 10 2011 Surge Load NELTA Switch Mode Power Suppl DRP024V060W1BA See below typical surge load capability of the power supply the PSU is capable of delivering 3 secs of Surge load about 150 of max the voltage be out of regulation limits of 5 m Va drops in shaded region Output Valtage Val lo 180 lo 100 Dynamic Load The Power Supply is capable of dynamic output voltage load change from 10 to 90 within 5 of regulation limits and from 0 to 100 within 10 of regulation limits See picture below on the dynamic behavior of the Power Supply Dynamic Load Dynamic Load Output Output Voltage Vo 59 Voltage Vy 100 5 100mS 11 13 00 1 10 2011 A DELTA Switch Mode Power Suppl DRPO24V060W1BA e Redundancy amp Parallel Operation with ORing Diode See picture below for a typical Redundant Parallel operation using CliQ II Series Power Supplies Power Supply Unit 1 PSU1 and Power Supply Unit 2 PSU2 are connected through a twin diode where Ano
8. de 1 1 is connected to the Ve of PSU1 2 is connected to the Ve of PSU2 and both output ground are shorted together The output of PSU1 and PSU2 is drawn from the Cathode K of the twin diode making the Power Supply work in Redundant Parallel operation Redundant Operation When 2 Power Supplies are connected in parallel the Power Supply with the higher output voltage will take the maximum load while the other will operate in standby mode at no load In case the first Power Supply fails the second will take over the load and supplies the required power to the end system 0 11010248 f 3 9 0 11010248 24V 2 5A 24V 2 5A 12 13 Rev 00 1 10 2011 DELTA Switch Mode Power Suppl DRPO24V060W1BA Parallel Operation When 2 Power Supplies are connected in parallel they can share the load if the following steps are taken Step 1 Measure the output voltages at no load from 1 to Ground i e 1 to Ground of PSU1 VA2 to Ground of PSU2 If the voltages are not the same follow Step 2 If they are the same skip to Step 3 Step 2 Adjust the output voltages with the help of VR on the Power Supply front panel market as ADJUST to the same level For e g if PSU1 is measuring 24 15Vdc and PSU2 is measuring 24 25Vdc adjust the output voltage of one to be the same as the other Step 3 Connect the Power Supply to the end system load and measure the output voltages from 1 to Ground i e
9. er when ambient temperature drops to 50 C or output capacity is reduced as recommended in the graph If the device has to be mounted in any other direction please contact your service provider for more details In order for the device to function in the manner intended it is also necessary to observe a lateral spacing of 2cm from other equipments Depending on the ambient temperature and output capacity of the device the device housing can be very hot Rev 00 NELTA Switch Mode Power Suppl DRP024V060W1BA Mechanical drawing Device description Fig 1 1 Input terminal block connector 2 Output terminal block connector 3 DC voltage adjustment potentiometer 4 DC OK control LED green 5 Universal mounting rail system 7 13 Rev 00 1 10 2011 A DELTA Switch Mode Power Suppl DRPO24V060W1BA e Overload Protection The Power Supply is provided with an overload protection OLP function which protects the power supply from possible damage caused by excess current The Power Supply also has an over temperature protection OTP in case overload condition persists for an extended duration and is below the overload trigger point but gt 100 load Typically the overload current loi is gt Isurcse 150 output voltage will start dropping when the power supply reaches max power limit It will go into bouncing mode when the output reaches UVLO under voltage point The output voltage will recover
10. l X Y Z direction in acc with IEC 68000 2 6 In conformance with EMC guideline 89 336 EEC and low voltage directive 73 23 EEC DINRAIL 1AC 24V DC 2 5A 11010248 EMC electromagnetic compatibility Immunity to interference according to EN 61000 6 2 EN 61000 4 2 Housing LEVEL 4 Discharge of static electricity ESD Contact discharge 8 KV Air Discharge 15 KV EN 61000 4 3 Housing LEVEL 3 Radiate Field Immunity Frequency Field intensity 80MHz 1GHz 10V M with 1kHz tone 80 modulation EN61000 4 4 2KV Fast transients Burst EN61000 4 5 2KV 2KV Level 3 Surge voltage Immunity Surge e Conducted Immunity Frequency 0 0 15MHz 80 2 10Vrms Voltage dips Noise emission according to EN 61000 6 3 Emitted radio interface EN55011 EN55022 CLASS e Radio interference voltage EN55011 EN55022 CLASS EN55011 corresponds to CISPR11 EN55022 corresponds to CISPR22 EN 61000 corresponds to IEC 61000 1 Criterion A Normal operating behavior within the defined limits Temporary impairment to operational behavior that is corrected by the device itself Symmetrical Conductor to conductor Asymmetrical Conductor to ground Class B Area of application industry and residential 3 13 Rev 00 1 10 2011 DELTA Switch Mode Power Suppl DRPO24V060W1BA Numbering for DIN Rail Power Supply For example DRP024V060W1BA XX X XXXX XXXX X XX XX
Download Pdf Manuals
Related Search
Related Contents
High Definition PoE IP Phone (1-Line) Scaricare manualmente Sony VAIO SVE1413RCX Samsung Galaxy Tab 2 (10.1) Užívateľská príručka Sierra Conversion Project Update January 11, 2013 - San Diego State University User Manual DVX402 nos conditions générales pour les consommateurs User`s Manual - Best Service Chapter 1 Copyright © All rights reserved.