CyberPower UP425UIT User's Manual

image

Contents

1. and spikes POWER ON C Using Battery Indicator USG This illuminates during utility failure indicating that the battery is supplying power to the battery power supplied outlets Replace Battery Indicator RESTACE The LED illuminates when the UPS battery is no longer useful and must be replaced Please see manual Battery replacement procedure 2 9 Overload Indicator Sa ae The LED illuminates when the loads connected to the UPS exceed the UPS capacity Battery Backup and Surge Protection Outlets The UPS provides battery powered and surge protected outlets for connected equipment to insure temporary uninterrupted operation during a power failure and against surges and spikes Surge Protection Outlets j The UPS provides surge protected only outlet for connected equipments against surges and spikes Fuse for Overload Protection Fuse provide optimal overload protection When overload occurs the fuse will broken and UPS switches to battery mode You will need to change the spare fuse that provided with the unit so the UPS will provide the power from utility USB Type B Port to PC E This Port allows connection and communication from USB port on the computer to the UPS unit The UPS communicates its status to the PowerPanel Personal Edition software This interface is also compatible with the UPS service provided by Windows 2000 and Windows XP Contact Closure Serial Port to PC This port allows connection an
2. CyberPower eu cyberpowersystems com Utility Tower Plus Series UPS UP425UIT UP550UI UP750UI User Manual A SAVE THESE INSTRUCTIONS This manual contains important safety instructions Please read and follow all instructions carefully during installation and operation of the unit Read this manual thoroughly before attempting to unpack install or operate your UPS This equipment can be operated by any individuals with no previous training The socket outlet shall be installed near the equipment and easily accessible During the installation of this equipment it should be assured that the sum of the leakage currents of the UPS and the connected loads does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the mains hazardous voltage still may be accessible through supply from battery The battery supply should be therefore disconnected in the plus and minus pole at the quick connectors of the battery when maintenance or service work inside the UPS is necessary Do not dispose of batteries in a fire the battery may explode Do not open or mutilate the battery or batteries released electrolyte is harmful to the skin and eyes Do not replace the batteries of UP425UIT UNPACKING Inspect the UPS upon receipt The box should contain the following UPS Unit PowerPanel Personal Edition Software Disk x 1 USB Cable x 1 Telephone Cable x 1 IEC IEC Power Cord x 2 UPS User Manu
3. DW Eindhoven The Netherlands Phone 952 403 9500 Fax 952 403 0009 www cyberpowersystems com Phone 31 0 40 2348170 Fax 31 0 40 2340314 eu cyberpowersystems com Entire contents copyright 2005 CyberPower Systems B V All rights reserved Reproduction in whole or in part without permission is prohibited PowerPane and PowerPane Plus are trademarks of CyberPower Systems USA Inc
4. F to 95 F 0C to 35C 0 to 95 Non Condensing Windows 98 ME 2000 NT XP Server 2003 Vista Condition On Off Normal Two Beeps Utility Failure The UPS is providing battery power to battery power supplied outlets On Off Normal Rapid Utility Failure The UPS is providing Beeps battery power Rapid beeps indicate the unit will run out of power shortly n Off On Blown Long Beeps System Overload Occurs in the full time surge protection outlet Turn the UPS off unplug at least one piece of equipment from UPS Replace the fuse with the spare one then turn the UPS on On Normal Long Beeps Battery Overload Occurs when connected equipment exceeds the rating of battery outlets of the unit Turn the UPS off unplug at least one piece of equipment from battery outlets Check the fuse and do the replacement if necessary Turn the UPS on On Off Off Off On Replace Battery UPS battery is no Of Off Off Off Off On longer useful and must be replaced Please see manual Battery replacement procedure The USB cable is not the cable that was provided with the unit For more information please contact original purchase Any warranty services please contact your local dealers or distributors You must use the cable included with the unit for the software CyberPower Systems USA Inc 4241 12th Avenue East Suite 400 Shakopee MN 55379 CyberPower Systems B V Europe Flight Forum 3545 5657
5. acement is not available for UP425UIT BATTERY REPLACEMENT PROCEDURE 1 Remove the 2 retaining screws then push the battery cover backward and remove the cover 2 Lean the UPS to one side and pull out the battery partially from the compartment Disconnect the battery wires from the battery and then remove the battery from the compartment 3 Install the replacement battery by connecting the red wire to the positive terminal of the battery and connecting the black wire to the negative terminal of the battery 4 Slide the battery back into the compartment Turn the UPS upside down to help the batteries entirely slide into the compartment Replace the cover and the retaining screws REMINDER Recharge the unit for 4 8 hours to ensure the UPS performs expected runtime STORAGE First turn off your UPS and disconnect its power cord from the wall outlet Disconnect all cables connected the UPS to avoid battery drain To store your UPS for an extended period cover it and store with the battery fully charged Recharge the battery every three months to insure battery life If the battery remains uncharged for an extended period of time it may suffer permanent loss of capacity The UPS does not perform expected runtime Batteries are not fully charged Recharge the battery by leaving the UPS plugged in Battery is slightly worn out Contact CyberPower Systems at service cyberpo
6. al Warranty Card HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT 1 Insure that the equipment plugged into the battery power supplied outlets does not exceed the UPS units rated capacity 425VA 255W for UP425UIT 550VA 330W for UP550UI 750VA 450W for UP750UI If rated unit capacities are exceeded an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip 2 If the power requirements of your equipment are listed in units other than Volt Amps VA convert Watts W or Amps A into VA by doing the calculations below Note The below equation only calculates the maximum amount of VA that the equipment can use not what is typically used by the equipment at any one time Users should expect usage requirements to be approximately 60 of below value TO ESTIMATE POWER REQUIREMENTS 1 Watts W x 1 6 VA or Amps A x 230 VA 2 Add the totals up for all pieces of equipment and multiply this total by 0 6 to calculate actual requirements There are many factors that can affect the amount of power that your computer system will require The total load that you will be placing on the battery powered outlets should not exceed 80 of the units capacity HARDWARE INSTALLATION GUIDE 1 Connect the equipment to your UPS outlets The IEC IEC power cords coming with the unit are used to connect your computer and monitor to the UPS Items such as copiers laser printers vacuums space heaters or oth
7. d communication from the DB 9 serial on the computer to the UPS unit Note Only one of the above two ports can be used to communicate with your computer at one time Note To install PowerPanel Personal Edition Software the computer will need Microsoft Internet Explore 5 0 or higher installed Note If using the Serial Port users need to download PowerPanel software from our website http www cyberpower eu com and order the standard serial cable Ethernet RJ 45 11 Network Protection Ports These ports are used for the protection of your network devices from the surge and spike through network cables Voltage Sensitivity Setting These DIP switch setting is used for choosing the UPS input voltage sensitivity The default verve KAN ney Value is 180Vac 266Vac which is used for most the computer systems and switching power hack REI e SUPPly The high sensitivity value is 196Vac 256Vac which is used for some precision instruments And the low sensitivity value is 160Vac 278Vac which is used for the wild voltage power supplies The below contents are for UP550UI UP750UI only CAUTION Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery Service the battery under the supervision of personnel knowledgeable of batteries and their precautions Keep unauthorized personnel away from batteries If you have questions contact your dealer or call the number in this manual for information on batt
8. er large electrical devices should not be connected to the UPS Please make sure that the total loads of your equipments are less than the maximum total power load of your UPS PLUGIN eed Boe Bang pog Boer ololo lt a eolo 2 Use your computer power cord to connect the UPS to a wall outlet Please avoid using extension cords and adapter plugs To maintain optimal battery charge leave the UPS plugged in at all times 3 Press the UPS power button to turn it on The Power On indicator will be illuminated in Green 4 Install your software and accessories To use the software simply connect the enclosed USB Serial interface cable to the USB Serial port on the UPS and an open USB Serial port on the computer FRONT PANEL AND REAR PANEL DESCRIPTION Hom ose bot tel UP750UI UP425UIT UP550UI UP750UI Power Switch Press the power button to turn the UPS ON or OFF D Power On Indicator This LED is illuminated when the utility condition is normal and the UPS outlets are providing clean power free of surges
9. ery replacement CAUTION Use only the specified type of battery See your dealer for replacement batteries CAUTION The battery may present the risk of electrical shock Do not dispose of batteries in a fire as it may explode Follow all local ordinances regarding proper disposal of batteries CAUTION Do not open or mutilate the batteries Release electrolyte is harmful to the skin and eyes and may be toxic CAUTION A battery can present a high risk of short circuit current and electrical shock Take the following precautions before replacing the battery 1 Remove all watches rings or other metal objects 2 Only use tools with insulated handles 3 DO NOT lay tools or other metal parts on top of battery or any battery terminals 4 Determine if the battery is inadvertently grounded If inadvertently grounded remove source of ground CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance applicable to a UPS and a remote battery supply not having a grounded circuit 5 Batteries are consider HAZARDOUS WASTE and must be disposed of properly Contact your local government for more information about proper disposal and recycling of batteries Turn off and unplug all connected equipment Turn the UPS off and unplug it from the AC power source Turn the UPS upside down Oo oOo nN OO Note The battery repl
10. ter and turn the UPS off Wait 10 seconds and turn the UPS back on This should reset the unit om Power Using Replace Overload Fuse Alarm Battery Battery Bi CyberPower warrants to you the original purchaser that CyberPower UPS will be free from defects in design assembly materials and workmanship for two years battery is only one year from the date of Model ists UP425UIT UP550UI UP750UI Capacity VA 425VA 550VA 7T50VA Capacity Watts 255W 330W 450W 160Vac 278Vac User Configuration 50 60 Hz On Battery Output Voltage Simulated Sine Wave at 230Vac 5 On Battery Output Frequency 50 60 Hz 1 Surge Protection and Filtering Lightning Surge Protection Yes Network Protection RJ11 RJ45 One In One Out Physical Total of UPS Receptacles 2 UPS 1 Surge 3 UPS 1 Surge Input Voltage Range Frequency Range Maximum Dimensions cm 23 8 x 8 0 x 13 7 28 3 x 9 1 x 16 4 Weight Kg 5 6 8 7 5 Battery Sealed Maint f ealed Maintenance Free 12V 145 AH x1 12V 8 AH x1 12V 9AH x1 Lead Acid Battery User Replaceable No Yes Hot Swappable Battery Pack Typical Recharge Time Indicators Power on Using Battery Overload Replace Battery Audible Alarms On Battery Low Battery Overload Environmental Operating Relative Humidity Communication PowerPanel Personal Edition Software Management Yes Auto Restart Yes All specifications are subject to change without notice 32
11. wer eu com The UPS will not The on off switch is turn on designed to prevent damage by rapidly turning it off and on Turn the UPS off Wait 10 seconds and then turn the UPS on The unit is not connected to The unit must be connected to a 220 240V an AC outlet 50 60Hz outlet The battery is worn out Contact CyberPower Systems at service cyberpower eu com Mechanical problem Contact CyberPower Systems at service cyberpower eu com Outlets do not Fuse is blown due to provide power to overload equipment Turn the UPS off and unplug at least one piece of equipment Unplug the power cord of the UPS then remove the fuse compartment beneath the power inlet of the UPS and replace the blown fuse with a spare one Lock the compartment back to the UPS Connect power cord then turn the UPS on Make sure that your spare fuse meets the specification 6 3A 250V 5x10mm Batteries are discharged Allow the unit to recharge for at least 4 hours Unit has been damaged by Contact CyberPower Systems at a surge or spike service cyberpower eu com PowerPanel The USB cable is not Connect the USB cable to the UPS unit and an Personal Edition is connected open USB port on the back of the computer inactive all icons You must use the cable that came with the are gray unit The USB cable is connected to the wrong port Try another USB port of your computer The unit is not providing battery power Shut down your compu