Home

Bryant 580J*08--14D User's Manual

image

Contents

1. aum mr ee DOM enn don mc 9 0 0 Y ant Y GL NEU NYL 5 deu is me Lf zz MEET E E gt a Ft tne ella a alii 5 gt 2 78 ou FAU a e TR 1m O D gt 1 ug Q3 o 1 lt gt 9 8 SE da S 3 85 D 1 2 NOLO Wm 4321101023 a G EN 480 5320V 4014 832180N023 D i 1715 30d NMOGLNHS 310438 NY 128 40220 AV13U SSOT jSVHd 580123130 39045 ONIGGY N3HM 102 34 09900 1VNINU3I NO SU3dWDC 031 91530 380583 Z 3981 111981 AJITdMIS Ol Quvog TVnLOW HOLYWM LON 300 100AV1 OILVW3H2S QuvOG TYNIWNdL 71 310N OD Qo vo IOVIS ORT 1N3W43ONVHUV LNINOdNOD and E 18055322 E 1 UD o a
2. 580J 12 3 PHASE 10 TON HORIZONTAL SUPPLY AVAILABLE EXTERNAL STATIC PRESSURE in wg CFM 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field Supplied Drive Standard Static Option Medium Static Option 3000 579 0 70 660 0 89 732 1 09 799 1 29 860 1 50 3250 613 0 85 690 1 06 760 1 27 823 1 49 883 1 71 3500 648 1 03 721 1 25 788 1 48 850 907 1 95 3750 683 1 23 753 1 47 817 1 71 877 1 96 933 2 21 4000 719 1 45 786 1 71 848 1 97 905 2 23 959 2 50 4250 756 1 71 879 2 26 934 2 53 987 2 81 4500 792 1 99 910 2 57 964 2 87 1015 3 16 4750 830 2 31 943 2 92 995 3 23 1044 3 54 5000 867 2 66 923 2 98 976 3 30 1026 1074 395 AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Medium Static Option High Static Option 3000 917 1 70 970 1 91 1021 243 1070 2 34 1117 2 56 3250 938 1 93 991 2 16 1041 2 38 1089 2 61 1134 2 85 3500 961 2 18 1013 2 42 1062 2 66 1108 2 91 1153 3 15 3750 985 2 46 1035 2 71 1083 2 97 1129 3 23 1173 3 49 4000 1011 2 76 1059 3 03 1106 3 30 1151 3 58 1194 3 85 4250 1037 3 09 1084 3 38 1130 3 66 1174 3 95 1216 4 24 4500 1064 3 46 1110 3 76 1155 4 06 1198 4 36 1239 4 66 4750 1091 3 85 1137 4 16 1180 4 48 5000 1120 4 28 1164 4 61 NOTE For more information see General Fan Performance Notes Boldface indicates field supplied drive i
3. 580J 08D F 2 Stage Cooling 7 5 Tons VOLTAGE COMP Cir 1 COMP Cir 2 OFM ea IFM V Ph Hz RANGE Max Max MIN MAX RLA LRA RLA LRA WATTS FLA TYPE WATTS AMP Draw EFF at Full Load FLA STD 1448 5 5 80 5 2 208 3 60 187 253 13 6 83 13 6 83 325 1 5 MED 2278 7 9 81 7 5 HIGH 4400 15 0 8196 15 0 STD 1448 5 5 8096 5 2 230 3 60 187 253 13 6 83 13 6 83 325 1 5 MED 2278 7 9 81 7 5 4400 15 0 81 15 0 STD 1448 2 7 80 2 6 460 3 60 414 506 6 1 41 6 1 41 325 0 8 MED 2278 3 6 8196 3 4 HIGH 4400 74 8196 7 4 STD 1379 2 5 8096 2 4 575 3 60 518 633 42 33 4 2 33 325 0 6 MED 3775 2 9 8196 2 8 HIGH 4400 5 9 8196 5 6 580J 12D F 2 Stage Cooling 10 Tons VOLTAGE COMP Cir1 COMP Cir 2 OFM ea IFM V Ph Hz RANGE Max Max MIN MAX RLA LRA RLA LRA WATTS FLA TYPE WATTS AMP Draw EFF at Full Load FLA STD 2120 5 5 80 5 2 208 3 60 187 253 15 6 110 15 9 110 325 1 5 MED 3775 10 5 8196 10 0 HIGH 4400 15 0 8196 15 0 STD 2120 5 5 80 5 2 230 3 60 187 253 15 6 110 15 9 110 325 1 5 MED 3775 10 5 8196 10 0 HIGH 4400 15 0 8196 15 0 STD 2120 2 7 80 2 6 460 3 60 414 506 7 7 52 77 52 325 0 8 MED 3775 46 81 4 4 HIGH 4400 7 4 81 7 4 STD 1390 2 1 80 2 0 575 3 60 518 633 58 39 5 7 39 325 0 6 MED 3775 2 9 8196 2 8 HIGH 4400 5 9 8196 5 6 580J 14D F 2 Stage Cooling 12 5 Tons VOLTAGE COMP Cir 1 COMP Cir 2 OFM ea IF
4. C09163 580J TETI SEE POWER LABEL ONLY TWO STAGE EN le m mr COMPONENT ARRANGEM NOTE TERMINAL BOARD SCHEMATIC LAYOUT DOES NOT MATCH ACTUAL TERMINAL TERMINAL BOARD BOARD TO SIMPLIFY CIRCUIT TRACES RTU MP FIOP DoC 1 1 lew o i PL6 R n CH Fig 43 Typical RTU MP System Control Wiring Diagram L GND CoH oros 80 6 J15 2 EXHAUST RELAYS Y2 1 10 Power 12345618 ENTH SENSR LO FROM TERM ECON 7 990080 BR S
5. MARKED WIRE ESD 5804 Table 15 RTU MP Controller Inputs and Outputs BACnet OBJECT CONNECTION PIN POINT NAME NAME TYPE OF I O NUMBERS INPUTS Space Temperature Sensor sptsens Al 10K Thermistor 420 1 2 Supply Air Temperature sat AI 10K Thermistor 42 1 2 Local Outside Air Temperature Sensor oatsens AI 10K Thermistor J2 3 4 Space Temperature Offset Pot sptopot AI 100K Potentiometer J20 3 Indoor Air Ouality iag Al 4 20 ma 44 2 3 Outdoor Air Ouality Al 4 20 44 5 6 Safety Chain Feedback safety DI 24 VAC 41 9 Compressor Safety compstat DI 24 VAC 41 2 Fire Shutdown firedown DI 24 VAC 41 10 Enthalpy Switch enthalpy DI 24 VAC 42 6 7 Humidistat Input Status humstat DI 24 VAC J5 7 8 CONFIGURABLE INPUTS Space Relative Humidit sprh 4 20 ma pem Air Relative 1 ma MW Supply Fan Status fanstat DI 24 VAC Filter Status filtstat DI 24 VAC s bL Remote Occupancy Input remocc DI 24 VAC OUTPUTS Economizer Commanded Position econocmd 4 20ma J2 5 Supply Fan Relay State sf DO Relay 24VAC 1A J1 4 Compressor 1 Relay State comp 1 DO Relay 24VAC 1A 41 8 Compressor 2 Relay State comp_2 DO Relay 24VAC 1A J1 7 Heat Stage 1 Relay State heat 1 DO Relay 24VAC 1A J1 6 Heat Stage 2 Relay State heat 2 DO Relay 24VAC 1A 41 5 Power Exhaust Relay
6. C06034 Fig 66 EconoMi er IV Controller Potentiometer and LED Locations 19 m LED ON D 17 16 LED LED ON C 15 E14 LED LED ON 13 B 12 LED OFF LED ON 11 10 LED OFF N 9 40 45 50 55 60 65 70 75 80 85 90 95 100 DEGREES FAHRENHEIT C06035 Fig 67 Outside Air Temperature Changeover Setpoints E 9 30 2 25 20 i E d I 7 10 o m 5 o z 0 0 13 0 20 0 22 0 25 0 30 0 35 0 40 0 45 0 50 o STATIC PRESSURE in wg C06031 Fig 68 Outdoor Air Damper Leakage 53 5804 Differential Dry Bulb Control For differential dry bulb control the standard outdoor dry bulb sensor is used in conjunction with an additional accessory dry bulb sensor part number CRTEMPSNOO2A00 The accessory sensor must be mounted in the return airstream See Fig 69 Wiring is provided in the EconoMi er IV wiring harness See Fig 62 ECONOMI ERIV CONTROLLER ECONOMI ERIV GROMMET RETURN AIR SENSOR AM RETURN DUCT FIELD PROVIDED C07085 Fig 69 Return Air Temperature or Enthalpy Sensor Mounting Location CONTROL CONTROL POINT CURVE APPROX deg deg AT 50 RH 16 18 21 ULB TEMPERATURE degrees F degrees C In this mode of operation the outdoor air temperature is compared to the return air temperature and the l
7. C09240 Fig 12 Cooling Charging Charts 14D F Circuit 1 COOLING CHARGING CHARTS 12 5 TON CIRCUIT2 CHARGING CHART R410A REFRIGERANT 1241 180 OUTDOOR TEMP F 115 46 1103 160 p XT 85 29 75 24 o 65 18 a F 55 13 Z 965 140 45 7 a 2 827 e 120 E 4 5 5 to 890 100 2 o 552 80 E d 414 60 30 40 50 60 70 80 90 SUCTION LINE TEMP OF 1 4 10 16 21 27 32 SUCTION LINE TEMP C09241 Fig 13 Cooling Charging Charts 14D F Circuit 2 5804 Table 1 Cooling Service Analysis PROBLEM CAUSE REMEDY Compressor and Condenser Fan Will Not Start Power failure Call power company Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker Defective thermostat contactor transformer or control relay Replace component Insufficient line voltage Determine cause and correct Incorrect or faulty wiring Check wiring diagram and rewire correctly Thermostat setting too high Lower thermostat setting below room temperature Compressor Will Not Start But Condenser Fan Runs Faulty wiring or loose connections in compressor circuit Check wiring and repair or replace Compressor motor burned out seized or internal overload open Determine cause Replace compressor Defective run start capacitor overload
8. OUTDOOR o TEMP 1241 15 A 105 41 1172 95 35 85 29 1103 n 2 1034 2 532 a 55 965 A 5 45 amp 896 821 Z 158 5 5 690 621 552 30 40 50 60 70 80 90 SUCTION LINE TEMPERATURE F 1 4 10 16 21 27 32 SUCTION LINE TEMPERATURE Fig 10 Cooling Charging Charts 08D F Both Circuits 10 C09221 COOLING CHARGING CHARTS KILOPASCALS SUCTION LINE PRESSURE TEMP F 4 115 46 1241 1 80 105 41 95 35 1172 10 85 29 15 24 1103 60 65 18 1034 z 1580 55 13 lt a 45 7 965 140 896 2130 827 4120 158 2110 5 690 5100 621 90 552 80 OUTDOOR 30 40 50 60 70 80 90 SUCTION LINE TEMPERATURE F 1 4 10 16 21 24 32 SUCTION LINE TEMPERATURE Fig 11 Cooling Charging Charts 12D F Both Circuits 11 09222 COOLING CHARGING CHARTS 12 5 TON CIRCUIT 1 CHARGING CHART R410A REFRIGERANT KPA 580J SUCTION LINE PRESS 241 80 OUTDOOR TEMP 173 70 PE PPE 115 46 105 41 103 160 95 35 o 85 29 a 75 24 035 150 65 18 55 13 o 45 1 965 o 140 Liu cc Q 897 130 MES 827 7 120 Pa o 159 10 D gt 690 00 621 90 552 80 30 40 50 60 70 80 90 SUCTION LINE TEMP F al 4 10 16 21 ol 32 o SUCTION LINE TEMP
9. 45 SENSOR SUPPLY SMOKE sensor FROM POWER SCHEMATIC RED CONTROL BOARD TRAN SMOKE CONTROL M ODULE FIOP ACCESSOR M IFM OL ALL 3PH IFM YEL RED GRA RED CE EXCEPT 5 25 1 1 EUM pup of pg aR AR S 2 l 4 JJ pe z lt l bj t2 ej ES LLI HR A NNI TN i olor comPt sn 4 eres l gt wx DDC o dd 143 BRN T STAT SEHH L dae Poe ee la im Om put thea Le ti BOARD i i PSH C08246 Fig 26 Typical Smoke Detector System Wiring Highlight B Additional Application Data Refer to Catalog No Smoke detector NC contact set will open on smoke alarm condition de energizing the ORN conductor Highlight C 24 v power signal via ORN lead is removed at Smoke Detector input on LCTB all unit operations cease immediately RTU MP Controls Unit operating functions fan cooling and heating are terminated as described above In addition Highlight D On smoke alarm condition the smoke detector NO Alarm contact will close supplying 24 v power t
10. Fan Status and input 9 Humidistat the alarm would be active unit would run compressor safety and humidistat would function normally and Fan Status inputs 5 amp 8 will be interpreted as Function Misconfigured Analog Input This occurs if more than one analog input inputs 1 amp 2 is configured for the same sensor When this happens the two inputs will be disabled as inputs This alarm will automatically be cleared when configuration is corrected An example of this would be Input 1 IAQ Sensor input 2 IAQ Sensor the alarm would be active unit would run but the IAQ Sensor inputs 1 amp 2 will be interpreted as Function Third Party Networking Third party communication and networking troubleshooting should be done by or with assistance from the front end 3rd party technician A Module Status Report Modstat can be run from the BACview see Table 19 to perform This lists information about the board status and networking state For basic troubleshooting see Table 20 Refer to the RTU MP 3rd Party Integration Guide for additional information BACnet MS TP 1 Verify that the BAS and controller are both set to speak the BACnet MS TP protocol The protocol of the controller is set via SW3 switches 3 4 5 and 6 The protocol can also be verified by getting a Modstat of the controller through the BACview Hit the FN key and the key at the same time to pull up a Modstat Scroll to t
11. 0 Brownouts 18 Commanded warm boots 22 Commanded cold boots 0 System errors 0 Watchdog timeouts System error message history Warning message history Information message history POWERUP BACnet reinitialize warmstart Menu file not found Jun 19 2007 Jun 26 2007 Type Specific 06 29 07 10 49 40 06 29 07 10 48 35 ARC156 reconfigurations during the last hour cleared upon reset Initiated by this node Core board hardware RAM 1024 kBytes Base board hardware Largest free heap space 65536 Database size 742082 used 352162 Raw physical switches 0x01280000 Module Communications Network Protocol BACnet MSTP Master Network Baud Rate 9600 bps Type 147 board 34 manufactured on 05 14 2007 S N 21A740188N FLASH 1024 kBytes type 3 Type 147 board 71 manufactured on 05 14 2007 S N RMP750037N free 389920 C07195 Fig 59 Module Status Report Modstat Example 10 In certain situations it may be necessary to tweak the MS TP Protocol timing settings through the BACview There are two settings that may be tweaked Max Masters Defines the highest MS TP Master MAC address on this MS TP network For example if there are 3 master nodes on an MS TP network and their MAC addresses are 1 8 and 16 then Max Masters would be set to 16 since this is the highest MS TP MAC address on the network This property optimizes MS TP network communications by preventing token passes
12. 28 SPARK GAP 120 TO 140 GAP 120 TO 140 SEE 240 000 180 000 BTUH INPUT DETAIL 250 000 200 000 BTUH INPUT DETAIL C C08447 Fig 38 Spark Adjustment 08 14 Burner Ignition Unit is equipped with a direct spark ignition 100 lockout system Integrated Gas Unit Controller IGC is located in the contro box See Fig 37 The IGC contains a self diagnostic LED light emitting diode A single LED on the IGC provides a visual display of operational or sequential problems when the power supply is uninterrupted See Fig 40 When a break in power occurs the IGC will be reset resulting in a loss of fault history and the indoor evaporator fan ON OFF times will be reset The LED error code can be observed through the viewport During servicing refer to the label on the control box cover or Table 9 for an explanation of LED error code descriptions If lockout occurs unit may be reset by interrupting power supply to unit for at least 5 seconds Table 9 LED Error Code Description LED INDICATION Normal Operation OFF Hardware Failure 2 Flashes Limit Switch Fault 3 Flashes Flame Sense Fault 4 Flashes 4 Consecutive Limit Switch Faults 5 Flashes Ignition Lockout Fault 6 Flashes Induced Draft Motor Fault 7 Flashes Rollout Switch Fault 8 Flashes
13. 61 5804 PRE START UP WARNING PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury or death 1 Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system Do not operate compressor or provide any electric power to unit unless compressor terminal cover is in place and secured Do not remove compressor terminal cover until all electrical sources are disconnected Relieve all pressure from system before touching or disturbing anything inside terminal box if refrigerant leak is suspected around compressor terminals Never attempt to repair soldered connection while refrigerant system is under pressure Do not use torch to remove any component System contains oil and refrigerant under pressure remove component wear protective goggles and proceed as follows a Shut off electrical power and then gas to unit b Recover refrigerant to relieve all pressure from system using both high pressure and low pressure ports Cut component connection tubing with tubing cutter and remove component from unit Carefully unsweat remaining tubing stubs when necessary Oil can ignite when exposed to torch flame WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death The unit must be electrically grounded in accordance with local codes and NEC ANSI NFPA 70 American
14. C E A 5 Ee 15 GROUND 1 24VAC 60 2 400 MAX us wu ANSI 721 20 AUTOMATIC IGNITION SYSTEMS IRT 4 SCREW REGUIRED 5 AMP MAX O FUSE Fig 40 Integrated Gas Control IGC Board Table 10 IGC Connections C08452 NNECTION TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I O EN HUN INPUTS Input power from TRAN 1 control box 24 VAC 5 Speed sensor gas section analog input J1 1 3 FS 1 Flame sensor gas section switch input Heat stage 1 LCTB 24 VAC J2 2 RS Rollout switch gas section switch input J2 5 6 LS Limit switch fan section switch input J2 7 8 CS Centrifugal switch not used switch input J2 9 10 OUTPUTS L1 CM Induced draft combustion motor gas section line VAC IFO Indoor fan control box relay J2 1 GV Gas valve heat stage 1 gas section relay J2 11 12 31 5804 Table 11 Orifice Sizes ORIFICE BRYANT DRILL SIZE PART NUMBER DIA in 30 LH32RF129 0 1285 1 8 LH32RF125 0 1250 31 LH32RF120 0 1200 32 LH32RF116 0 1160 33 LH32RF113 0 1130 34 LH32RF111 0 1110 35 LH32RF110 0 1100 36 LH32RF105 0 1065 37 LH32RF104 0 1040 38 LH32RF102 0 1015 39 LH32RF103 0 0995 40 LH32RF0
15. Input 1 Function This input is an analog input and can be configured to be one of five different inputs No Sensor IAO Sensor OAO Sensor Space RH Sensor or Outdoor RH Sensor Input 1 is wired to pin J4 5 Factory Default No Sensor Input 2 Function This input is an analog input and can be configured to be one of five different inputs No Sensor IAO Sensor OAO Sensor Space RH Sensor or Outdoor RH Sensor Input 2 is wired to pin J4 2 Factory Default No Sensor Setpoint Slider Range This sets the slider range of the space sensor with this built in function The slider is used to offset the current control setpoint Factory Default 5 Range 0 15 A F T55 56 Override Duration This sets the occupancy override duration when the override button is pushed on the space sensor Factory Default 1 hr Range 0 24 hr IAO Low Reference 4mA This is used when an IAO sensor is installed on Input 1 or 2 This value is displayed and used when 4mA is seen at the input Factory Default 0 PPM Range 0 400 PPM IAO High Reference 20mA This is used when an IAO sensor is installed on Input 1 or 2 This value is displayed and used when 20mA is seen at the input Factory Default 2000 PPM Range 0 5000 PPM NOTE IAQ low Reference 4mA and IAQ High Reference 20mA are used to set the linear curve of mA vs PPM Low Reference 4 This is used when sensor is installed on Input 1 or 2 This
16. Loosen the two screws at the GFCI duplex outlet un til approximately 1 2 in 13 mm under screw heads are exposed 3 Press the gasket over the screw heads Slip the back ing plate over the screw heads at the keyhole slots and align with the gasket Tighten the two screws un til snug do not over tighten 4 Mount the weatherproof cover to the backing plate as shown in Fig 17 COVER WHILE IN USE WEATHERPROOF BASE PLATE FOR GFCI RECEPTACLE C09244 Fig 17 Weatherproof Cover Installation 5 Remove two slot fillers in the bottom of the cover to permit service tool cords to exit the cover Check for full closing and latching Non Powered Type This type requires the field installation of a general purpose 125 volt 15 A circuit powered from a source elsewhere in the building Observe national and local codes when selecting wire size fuse or breaker reguirements and disconnect switch size and location Route 125 v power supply conductors into the bottom of the utility box containing the duplex receptacle Unit Powered Type unit mounted transformer is factory installed to stepdown the main power supply voltage to the unit to 115 v at the duplex receptacle This option also includes a manual switch with fuse located in a utility box and mounted on a bracket behind the convenience outlet access is through the unit s control box access panel See Fig 16 The primary leads to the convenience outlet transformer
17. SW3 on the board is used to set protocol and baud rate Switches 1 and 2 SW1 and SW2 are used to set the board s network address See Fig 57 for the switch setting per protocol The 3rd party connection to the RTU MP is through plug J19 Refer to the RTU MP 3rd Party Integration Guide for more detailed information on protocols 3rd party wiring and networking NOTE Power must be cycled after changing the SW1 3 switch settings BACnet MS TP BACnet Master Slave Token Passing MS TP is used for communicating BACnet over a sub network of BACnet only controllers This is the default Bryant communications protocol Each RTU MP module acts as an MS TP Master The speed of an MS TP network can range from 9600 to 76 8K baud Physical Addresses can be set from 01 to 99 Modbus The RTU MP module can speak the Modicon Modbus RTU Protocol as described in the Modicon Modbus Protocol Reference Guide PI MBUS 300 Rev J The speed of a Modbus network can range from 9600 to 76 8K baud Physical Addresses can be set from 01 to 99 Johnson N2 N2 is not a standard protocol but one that was created by Johnson Controls Inc that has been made open and available to the public The speed of N2 network is limited to only 9600 baud Physical Addresses can be set from 01 to 99 LonWorks LonWorks is an open protocol that requires the use of Echelon s Neuron microprocessor to encode and decode the LonWorks packets In order to reduce the cost of
18. adding that hardware on every module a separate LonWorks Option Card LON OC was designed to connect to the RTU MP This accessory card is needed for LonWorks and has to be ordered and connected using the ribbon cable to plug J15 The RTU MP s baud rate must be set to 38 4k to communicate with the LON OC The address switches SW1 amp SW2 are not used with LonWorks Local Access BACview Handheld The BACview is a keypad display interface used to connect to the RTU MP to access the control information read sensor values and test the RTU See Fig 58 This is an accessory interface that does not come with the MP controller and can only be used at the unit Connect the BACview to the RTU MP s J12 local access port There are 2 password protected levels in the display User and Admin The user password defaults to 0000 but can be changed The Admin password is 1111 and cannot be changed There is a 10 minute auto logout if a screen is left idle See RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50 2 Appendix A for navigation and screen content 43 5804 SW3 Protocol Selection PROTOCOL DS8 DS7 DS6 DS5 DS4 DS3 DS2 DS1 BACnet MS TP Master Unused OFF OFF OFF ON OFF Select Baud Select Baud Modbus Unused OFF OFF ON ON OFF Select Baud Select Baud Slave N2 Slave Unused OFF OFF OFF ON ON OFF OFF LonWorks Unused ON ON O
19. after completing troubleshooting EconoMi er IV Troubleshooting Completion This procedure is used to return the EconoMi er IV to operation No troubleshooting or testing is done by performing the following procedure 1 2 3 10 11 Remove Disconnect power at TR and TR1 Set enthalpy potentiometer to previous setting Set maximum position potentiometer to previous setting Set minimum position DCV setpoint and exhaust potentiometers to previous settings Remove 620 ohm resistor from terminals SR and 1 2 kilo ohm checkout resistor from terminals SO and If used reconnect sensor from terminals SO and Remove jumper from TR to N Remove jumper from TR to 1 Remove 5 6 kilo ohm resistor from T and Reconnect wires at T and T1 Remove jumper from P to P1 Reconnect device at P and 1 Apply power 24 vac to terminals TR and TR1 WIRING DIAGRAMS See Fig 73 and 74 for typical wiring diagrams 59 5804 Triopraccy C2 HH RED T1 CLO i mE BRN 3 COMP YEL V YEL ORN XT2 YEL OFR BLKA H BLK 8LK 8 H 5 4 Monen FI
20. 0 2 0 4 0 6 0 8 1 0 SEM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 2250 513 0 54 595 0 76 665 1 01 728 1 27 786 1 56 2438 541 0 65 620 0 89 688 1 14 750 806 1 71 2625 570 0 77 645 1 02 712 1 29 772 1 58 827 1 88 2813 600 0 91 672 1 18 736 1 46 794 1 76 848 2 07 3000 629 1 07 699 1 35 761 1 64 818 1 95 871 2 28 3188 660 1 25 726 1 54 787 1 85 842 2 17 894 2 51 3375 690 1 45 1 75 813 2 07 867 2 41 917 2 76 3563 783 1 98 840 2 32 892 2 67 941 3 03 3750 752 1 91 812 2 24 867 2 59 918 2 95 966 3 32 AVAILABLE EXTERNAL STATIC PRESSURE wg 1 2 1 4 1 6 1 8 2 0 SEM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Medium Static Option High Static Option 2250 839 1 86 889 2 18 935 2 52 980 2 87 1022 3 23 2438 858 2 02 907 2 35 953 2 70 997 3 06 1039 3 43 2625 878 2 20 926 2 54 972 2 89 1015 3 26 1056 3 64 2813 899 2 40 946 2 75 991 3 11 1033 3 49 1074 3 88 3000 920 2 62 966 2 98 1010 3 35 1052 3 74 1093 4 14 3188 942 2 86 987 3 23 1031 3 61 1072 4 01 3375 964 3 12 1009 3 50 1052 3 89 1093 4 30 3563 988 3 41 1032 3 80 1074 4 20 3750 1011 3 71 1054 4 11 1096 4 53 NOTE For more information see General Fan Performance Notes Boldface indicates field supplied drive is required 1 Recommend using field supplied fan pulley part no KR11AZ002 and belt part no KR29AF054 75 5804 FAN PERFORMANCE cont
21. Electrical interference is disrupting the Flashes Lockout No gas heating power reset IGC software LEGEND IGC Integrated Gas Unit Control LED Light Emitting Diode NOTES 1 There is a 3 second pause between alarm code displays 2 If more than one alarm code exists all applicable alarm codes will be displayed in numerical sequence 3 Alarm codes on the IGC will be lost if power to the unit is interrupted 34 CONDENSER COIL SERVICE Condenser Coil The condenser coil is new NOVATION Heat Exchanger Technology This is an all aluminum construction with louvered fins over single depth crosstubes The crosstubes have multiple small passages through which the refrigerant passes from header to header on each end Tubes and fins are both aluminum construction Connection tube joints are copper The coil may be one row or two row Two row coils are spaced apart to assist in cleaning Repairing NOVATION Condenser Tube Leaks RCD offers service repair kit Part Number 50TJ660007 for repairing tube leaks in the NOVATION coil crosstubes This kit includes approved braze materials aluminum flux core braze rods a heat shield a stainless steel brush replacement fin segments adhesive for replacing fin segments and instructions specific to the NOVATION aluminum coil See EPIC for instruction sheet 99TA526379 The repair procedure reguires the use of MAPP gas and torch must be supplied by servicer instead of conventional
22. LED turns off 20 Controller Alarm Test The controller alarm test checks the controller s ability to initiate and indicate an alarm state CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern This test places the duct detector into the alarm state Disconnect all auxiliary eguipment from the controller before performing the test If the duct detector is connected to a fire alarm system notify the proper authorities before performing the test Controller Alarm Test Procedure 1 Press the controller s test reset switch for seven seconds 2 Verify that the controller s Alarm LED turns on 3 Reset the sensor by pressing the test reset switch for two seconds 4 Verify that the controller s Alarm LED turns off Dirty Controller Test The dirty controller test checks the controller s ability to initiate a dirty sensor test and indicate its results CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern Pressing the controller s test reset switch for longer than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses Dirty Controller Test Procedure Press the controller s test reset switch for two seconds Verify that the controller s Trouble LED flashes Dirty Sensor Test The dirty sensor test provides an indication of the sensor s abi
23. National Standards Institute National Fire Protection Association Proceed as follows to inspect and prepare the unit for initial start up 1 Remove all access panels 2 Read and follow instructions all WARNING CAUTION and INFORMATION labels attached to or shipped with unit WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Wear refrigerants safety glasses and gloves when handling Keep torches and other ignition sources away from refrigerants and oils 3 Make the following inspections a Inspect for shipping and handling damages such as broken lines loose parts or disconnected wires etc b Inspect for oil at all refrigerant tubing connections and on unit base Detecting oil generally indicates a refrigerant leak Leak test all refrigerant tubing connections using electronic leak detector halide torch or liquid soap solution Inspect all field wiring and factory wiring connections Be sure that connections are completed and tight Be sure that wires are not in contact with refrigerant tubing or sharp edges d Inspect coil fins If damaged during shipping and handling carefully straighten fins with a fin comb 4 Verify the following conditions a Make sure that condenser fan blade are correctly positioned in fan o
24. P902 0301 for one gallon container and part number P902 0305 for a 5 gallon container It is recommended that all round tube coil cleaner as described below Coil cleaning should be part of the unit s regularly scheduled maintenance procedures to ensure long life of the coil Failure to clean the coils may result in reduced durability in the environment Avoid the use of coil brighteners acid cleaning prior to painting high pressure washers poor quality water for cleaning Totaline environmentally sound coil cleaner is non flammable hypoallergenic non bacterial and a USDA accepted biodegradable agent that will not harm coil or surrounding components such as electrical wiring painted metal surfaces or insulation Use of non recommended coil cleaners is strongly discouraged since coil and unit durability could be affected Totaline Environmentally Sound Coil Cleaner Application Equipment 2 1 2 gallon garden sprayer water rinse with low velocity spray nozzle CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in corrosion and damage to the unit Harsh chemicals household bleach or acid or basic cleaners should not be used to clean outdoor or indoor coils of any kind These cleaners can be very difficult to rinse out of the coil and can accelerate corrosion at the fin tube interface where dissimilar materials are in contact If there is dirt below the surface of the coil use the Tot
25. The indoor fan contactor IFC outdoor fan contactor OFC and Compressor 1 contactor C1 are energized and indoor fan motor outdoor fan and Compressor 1 start The outdoor fan motor runs continuously while unit is in Stage 1 or Stage 2 cooling 08D F and 12D F units have two outdoor fans both run while unit is in Stage 1 or Stage 2 cooling If Stage 1 cooling does not satisfy the space load the space temperature will rise until thermostat calls for Stage 2 cooling Y2 closes Compressor 2 contactor C2 is energized Compressor 2 starts and runs Heating Units Without Economizer When the thermostat calls for heating terminal W1 is energized To prevent thermostat short cycling the unit is locked into the Heating mode for at least 1 minute when WI is energized The induced draft motor is energized and the burner ignition sequence begins The indoor evaporator fan motor IFM is energized 45 seconds after a flame is ignited If Stage 1 heating does not satisfy the space load the space temperature will fall until thermostat calls for Stage 2 heating W2 closes Terminal W2 is energized and the high fire solenoid on the main gas valve is energized Firing rate increases to high fire When space load is partially satisfied terminal W2 is de energized the high fire solenoid is de energized and heating operation continues on low fire When the space heating load is fully satisfied thermostat terminal W1 is also deene
26. The operating range of temperature measurement is 0 to 1589F 18 to 70 See Table 16 for sensor temperature resistance values SUPPLY AIR TEMPERATURE SENSOR MOUNTING LOCATION SUPPLY AIR TEMPERATURE 5 SENSOR 7 06033 Fig 65 Supply Air Sensor Location The temperature sensor looks like an eyelet terminal with wires running to it The sensor is located in the crimp end and is sealed from moisture Outdoor Air Lockout Sensor The EconoMi er IV is eguipped with an ambient temperature lockout switch located in the outdoor airstream which is used to lock out the compressors below a 42 F 6 ambient temperature See Fig 60 EconoMi er IV Control Modes IMPORTANT The optional EconoMi er2 does not include a controller The EconoMi er2 is operated by a 4 to 20 mA signal from an existing field supplied controller See Fig 63 for wiring information Determine the EconoMi er IV control mode before set up of the control Some modes of operation may reguire different sensors See Table 22 The EconoMi er IV is supplied from the factory with a supply air temperature sensor and an outdoor air temperature sensor This allows for operation of the EconoMi er IV with outdoor air dry bulb changeover control Additional accessories can be added to allow for different types of changeover control and operation of the EconoMi er IV and unit Outdoor Dry Bulb Changeover The standard controller is shipped f
27. and uses a polyolester POE oil This oil is extremely hygroscopic meaning it absorbs water readily POE oils can absorb 15 times as much water as other oils designed for HCFC and refrigerants Avoid exposure of the oil to the atmosphere WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure to follow this warning could result in personal injury or death Relieve pressure and recover all refrigerant before system repair or final unit disposal Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away from refrigerants and oils Replacing Compressor The compressor used with Puron refrigerant contains a POE oil This oil has a high affinity for moisture Do not remove the compressor s tube plugs until ready to insert the unit suction and discharge tube ends Compressor mounting bolt torque is 65 75 in lbs 7 3 8 5 N m Compressor Rotation 1 Connect service gauges to suction and discharge pres sure fittings 2 Energize the compressor 3 The suction pressure should drop and the discharge pressure should rise as is normal on any start up NOTE If the suction pressure does not drop and the discharge pressure does not rise to normal levels 1 Note that the evaporator fan is probably also rotating in the wrong direction 2 Turn off power to the unit 3 Reverse any two of the unit power leads 4 Reapply power to the compressor The suction a
28. approximately 5 F 3 C below room temperature Both compressors start on closure of contactors Check unit charge Refer to Refrigerant Charge section Reset thermostat at a position above room temperature Both compressors will shut off Evaporator fan will shut off immediately To shut off unit set system selector switch at OFF position Resetting thermostat at a position above room temperature shuts unit off temporarily until space temperature exceeds thermostat setting Main Burners Main burners are factory set and should require no adjustment To check ignition of main burners and heating controls move thermostat setpoint above room temperature and verify that the burners light and evaporator fan is energized Check heating effect then lower the thermostat setting below the room temperature and verify that the burners and evaporator fan turn off Refer to Table 11 for the correct orifice to use at high altitudes Heating 1 Purge gas supply line of air by opening union ahead of the gas valve If gas odor is detected tighten union and wait 5 minutes before proceeding 2 Turn on electrical supply and manual gas valve 3 Set system switch selector at HEAT position and fan switch at AUTO or ON position Set heating temperature lever above room temperature 4 The induced draft motor will start 5 After a call for heating the main burners should light within 5 seconds If the burner does not light then the
29. belt and cause a reduction in belt life 2 Loosen the motor mounting plate front bolts and rear bolts 3 Push the motor and its mounting plate towards the blower housing as close as possible to reduce the cen ter distance between fan shaft and motor shaft 4 Remove the belt by gently lifting the old belt over one of the pulleys 5 Install the new belt by gently sliding the belt over both pulleys and then sliding the motor and plate away from the fan housing until proper tension is achieved 6 Check the alignment of the pulleys adjust if neces sary 7 Tighten all bolts 8 Check the tension after a few hours of runtime and re adjust as reguired Adjustable Pitch Pulley on Motor The motor pulley is an adjustable pitch type that allows a servicer to implement changes in the fan wheel speed to match as installed ductwork systems The pulley consists of a fixed flange side that faces the motor secured to the motor shaft and a movable flange side that can be rotated around the fixed flange side that increases or reduces the pitch diameter of this driver pulley See Fig 6 As the pitch diameter is changed by adjusting the position of the movable flange the centerline on this pulley shifts laterally along the motor shaft This creates a reguirement for a realignment of the pulleys after any adjustment of the movable flange Also reset the belt tension after each realignment Check the condition of the motor pulley f
30. compressor from restarting until the CLO has been manually reset In the lockout condition 24 v will be available at terminal X Reset is accomplished by removing the input signal at terminal 2 open the thermostat briefly or cycle the main power to the unit Phase Monitor Relay PMR The PMR protects the unit in the event of a loss of a phase or a reversal of power line phase in the three phase unit power supply In normal operation the relay K1 is energized contact set closed and red LED indicator is on steady If the PMR detects a loss of a phase or a phase seguence reversal the relay K1 is energized its contact set is opened and unit operation is stopped red LED indicator will blink during lockout condition Reset of the PMR is automatic when all phases are restored and phase seguence is correct If no 24 v control power is available to the PMR the red LED will be off Smoke Detectors Factory installed smoke detectors are discussed in detail starting on page 17 RTU MP Seguence of Operation The RTU MP will control the compressor economizer and heating outputs based on its own space temperature input and setpoints An optional IAO sensor mounted in the space can influence the economizer minimum position The RTU MP has its own hardware clock that is set automatically when the software is installed on the board The RTU MP s default is to control to occupied setpoints all the time until a type of occupancy control is se
31. determine the percentage of voltage imbalance max voltage deviation from average voltage Voltage Imbalance 100 x average voltage Determine maximum deviation from average voltage AB 227 224 3v 231 227 2 4v 227 226 2 1v Maximum deviation is 4 v Determine percent of voltage imbalance 96 Voltage Imbalance 100 x 227 1 76 This amount of phase imbalance is satisfactory as it is below the maximum allowable 2 IMPORTANT If the supply voltage phase imbalance is more than 296 contact your local electric utility company immediately 81 5804 Wiring Diagrams APPENDIX IV WIRING DIAGRAM LIST 580J SIZE VOLTAGE CONTROL POWER 208 230 3 60 48 501325 48TM501326 08D F 460 3 60 48TM501325 48TM501326 575 3 60 48TM501325 48TM501327 208 230 3 60 48 501325 48TM501326 12D F 460 3 60 48TM501325 48TM501326 575 3 60 48 501325 48TM501327 208 230 3 60 48TM501379 48TM501380 14D F 460 3 60 48TM501379 48TM501380 575 3 60 48TM501379 48TM501381 RTU MP 48TM500988 NOTE Component arrangement on Control Legend on Power Schematic RTU MP control labels overlay a portion of the base unit control label The base unit label drawing and the control option drawing are required to provide a complete unit control diagram 82 APPENDIX MOTORMASTER SENSOR LOCATIONS UNIT SIZE UNIT TONNAGE DIM A 5
32. distances of up to 500 ft Use a three conductor shielded cable for the sensor and setpoint adjustment connections If the setpoint adjustment slidebar is not reguired then an unshielded 18 or 20 gauge two conductor twisted pair cable may be used Connect T 55 See Fig 45 for typical T 55 internal connections Connect the T 55 SEN terminals to RTU MP J20 1 and J20 2 See Fig 46 CCN COM SENSOR WIRING C08201 Fig 45 T 55 Space Temperature Sensor Wiring 39 5804 C08460 Fig 46 RTU MP T 55 Sensor Connections Connect T 56 See Fig 47 for T 56 internal connections Install a jumper between SEN and SET terminals as illustrated Connect T 56 terminals to RTU MP J20 1 J20 2 and J20 3 per Fig 48 DIG CCN COM SENSOR WIRING JUMPER TERMINALS AS SHOWN C08202 Fig 47 T 56 Internal Connections lt GEN SENE Ss 120 2 08461 Fig 48 RTU MP T 56 Sensor Connections 59 59 space sensor reguires a separat
33. field supplied motor pulley part no KR11HY410 76 580J 14 3 PHASE 12 5 TON HORIZONTAL SUPPLY Available External Static Pressure in wg 0 2 0 4 0 6 0 8 1 0 CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 3438 639 0 98 713 1 20 781 1 43 843 901 1 88 3750 817 1 71 933 2 21 4063 966 2 57 4375 949 2 70 1001 2 98 4688 3 44 5000 5313 5625 5938 6250 Available External Static Pressure in wg 1 2 1 4 1 6 1 8 2 0 GEM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Medium Static Option High Static Option 3438 955 2 12 1007 2 35 1056 2 59 1103 2 83 1148 3 08 3750 985 2 46 1035 2 71 1083 2 97 1129 3 23 1173 3 49 4063 1066 3 12 1157 3 67 1200 3 95 4375 1186 4 15 1228 4 45 4688 1084 3 75 1130 4 06 1174 4 37 1216 4 68 1257 5 00 5000 1120 4 28 1164 4 61 1248 5 27 1288 5 60 5313 5625 5938 6250 NOTE For more information see General Fan Performance Notes Boldface indicates field supplied drive is reguired 77 5804 580J 14 3 PHASE 12 5 TON VERTICAL SUPPLY Available External Static Pressure in wg CFM 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard Stat
34. is in the trouble state Dirty LED Indicates the amount of environmental compensation used by the sensor flashing continuously 10096 Power LED Indicates the sensor is energized Controller s Power LED is Off 1 Make sure the circuit supplying power to the control ler is operational If not make sure JP2 and JP3 are set correctly on the controller before applying power 2 Verify that power is applied to the controller s supply input terminals If power is not present replace or re pair wiring as required Remote Test Reset Station s Trouble LED Does Not Flash When Performing a Dirty Test but the Controller s Trouble LED Does 1 Verify that the remote test station is wired as shown in Fig 27 Repair or replace loose or missing wiring 2 Configure the sensor dirty test to activate the control ler s supervision relay See Changing Sensor Dirty Test Operation Sensor s Trouble LED is On But the Controller s Trouble LED is OFF Remove JP1 on the controller PROTECTIVE DEVICES Compressor Protection Overcurrent Each compressor has internal linebreak motor protection Reset is automatic after compressor motor has cooled Overtemperature Each compressor has an internal protector to protect it against excessively high discharge gas temperatures Reset is automatic High Pressure Switch Each system is provided with a high pressure switch mounted on the discharge line The switch is stem mounted and
35. maintain proper operation of the unit Elimination of contamination and removal of harmful residues will greatly increase the life of the coil and extend the life of the unit The following maintenance and cleaning procedures are recommended as part of the routine maintenance activities to extend the life of the coil Remove Surface Loaded Fibers Surface loaded fibers or dirt should be removed with a vacuum cleaner If a vacuum cleaner is not available a soft non metallic bristle brush may be used In either case the tool should be applied in the direction of the fins Coil surfaces can be easily damaged fin edges can be easily bent over and damage to the coating of a protected coil if the tool is applied across the fins NOTE Use of a water stream such as a garden hose against a surface loaded coil will drive the fibers and dirt into the coil This will make cleaning efforts more difficult Surface loaded fibers must be completely removed prior to using low velocity clean water rinse Periodic Clean Water Rinse A periodic clean water rinse is very beneficial for coils that are applied in coastal or industrial environments However it is very important that the water rinse is made with very low velocity water stream to avoid damaging the fin edges Monthly cleaning as described below is recommended Routine Cleaning of NOVATION Condenser Coil Surfaces To clean the NOVATION condenser coil chemicals are NOT to be used only
36. minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury death and or property damage Refer to the User s Information Manual provided with this unit for more details Do not store or use gasoline or other flammable vapors and liguids in the vicinity of this or any other appliance What to do if you smell gas DO NOT try to light any appliance DO NOT touch any electrical switch or use any phone in your building IMMEDIATELY call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Before performing service or maintenance operations on unit turn off main power switch to unit Electrical shock and rotating eguipment could cause injury WARNING FIRE EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death Disconnect gas piping from unit when pressure testing at pressure greater than 0 5 psig Pressures greater than 0 5 psig will cause gas valve damage resulting in hazardous condition If gas valve is subjected to pressure greater than 0 5 psig it must be replaced
37. module and network status If Run LED shows And Error LED shows Status is 2 flashes per second Off Normal 5 fash s Wer Second 2 flashes Five minute auto restart delay after alternating with Run LED system error MW 3 flashes Control module has just been P then off formatted 4 flashes Two or more devices on this network P then pause have the same ARC156 network address Exec halted after freguent system errors p or control programs halted 5 flashes per second On Exec start up aborted Boot is running 5 flashes per second Off Firmware transfer in progress Boot is running 7 flashes per second 7 flashes per second alternating with Run LED Ten second recovery period after brownout 14 flashes per second 14 flashes per second alternating with Run LED Brownout On On Failure Try the following solutions e the RTU MP off then on e Format the RTU MP e Download memory to the RTU MP e Replace the RTU MP 45 580 Table 18 Troubleshooting Alarms BACnet ACTION TAKEN BY RESET POINT NAME NAMES CONTROL METHOD PROBABLE CAUSE Alarm Generated Safety Chain Alarm safety chain Immediate Automatic Over load Indoor Fan or Electric Heater overheat Shutdown Alarm Generated Fire Shutdown Alarm fire alarm Immediate Automatic Smoke detected by smoke detector
38. normal The IGC sensed a when the gas 3 Flame Sense Fault ane inducer Power reset for LED valve should be closed Check wiring Flashes On reset flame sensor and gas valve operation 4 Four Consecutive Limit 52 15 4 consecutive limit switch faults within Flashes Switch Fault 9 9 single call for heat Limit Switch Fault Unit unsuccessfully attempted ignition for 15 minutes Check igniter and flame 3 Ignition Fault No gas heatin sensor electrode spacing gaps eto Flashes 9 9 9 r set Check flame sense and igniter wiring Check gas valve operation and gas supply Inducer sense On when heat call Off or If heat off no gas 6 Induced Draft Motor heating Inducer sense inducer sense Off when heat call On Flashes Fault If heat on gas valve normal or heat call wiring voltage and operation of Off and inducer On W Off CC motor Check speed sensor wiring to Gas valve and igniter Rollout switch has opened Check gas 7 Off valve operation Check induced draft Flashes Indoor fan and inducer Power reset blower wheel is properly secured to motor On shaft IGC has sensed internal hardware or 8 software error If fault is not cleared by Flashes Internal Control Lockout No gas heating Power reset resetting 24 v power replace the IGC Check gas valve connections to IGC terminals BRN lead must be on Pin 11 9 Temporary Software 1 hour auto reset
39. or Shutdown configuration incorrect Space Temp Sensor Alarm Generated Faulty shorted or open thermistor caused by spt alarm Immediate Automatic D 5 Failure Shutdown wiring error or loose connection Alarm Generated Faulty shorted or open thermistor caused by SAT Sensor Alarm sat alarm Gr Automatic wiring error or loose connection The space temperature has risen above the cool High Space Temp Alarm spt_hi Alarm Generated Automatic setpoint by more than the desired amount The space temperature has dropped below the Low Space Temp Alarm lo Alarm Generated Automatic heat setpoint by more than the desired amount High Supply Air Temp sat hi Alarm Generated Automatic ER QU then 160 dedrees Tor more thanig The supply air temperature is below 35 F for Low Supply Air Temp sat lo Alarm Generated Automatic more than 5 minutes Supply Fan Failed to Alarm Generated Tripped Circuit Breaker Broken belt Bad indoor ST y sf fail Immediately Automatic fan motor Configuration incorrect Bad fan status disable Operation Switch Alarm Generated Supply Fan in Hand sf hand Ramp down Automatic Bad Fan Status Switch Configuration incorrect Operations M ressor Safety dx_compstat Alarm Generated Automatic Compressor would not start Alarm Generated STO sensor is open or shorted for more then 5 Setpoint Slider Alarm Slide alarm Offset set to zero Automatic Automatic re set timer When Dirty Filter supply fan ru
40. oxyacetylene fuel and torch While the flame temperature for MAPP is lower than that of oxyacetylene and thus provides more flexibility when working on aluminum the flame temperature is still higher than the melting temperature of aluminum so user caution is reguired Follow instructions carefully Use the heat shield Replacing NOVATION Condenser Coil The service replacement coil is preformed and is eguipped with transition joints with copper stub tubes When brazing the connection joints to the unit tubing use a wet cloth around the aluminum tube at the transition joint Avoid applying torch flame directly onto the aluminum tubing RTU MP CONTROL SYSTEM The RTU MP controller provides expanded stand alone operation of the HVAC system plus connection and control through communication with several Building Automation Systems BAS through popular third party network systems See Fig 42 The available network systems are BACnet MP TP Modbus and Johnson J2 Communication with LonWorks is also possible by adding an accessory interface card to the RTU MP Selection of the communication protocol and baud rate are made at on board DIP switches Bryant s diagnostic display tools BACviewer6 Handheld and Virtual BACview loaded on a portable PC must be used with the RTU MP controller Connection to the RTU MP board is at the J12 access port See Fig 42 The RTU MP control is factory mounted in the 48TC unit s main control box to
41. pitch pulley after the final airflow balance adjustment This will reduce the amount of vibration generated by the motor belt drive system COOLING A WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal injury death and or equipment damage This system uses Puron refrigerant which has higher pressures than R 22 and other refrigerants No other refrigerant may be used in this system Gauge set hoses and recovery system must be designed to handle Puron refrigerant If unsure about equipment consult the equipment manufacturer Condenser Coil The condenser coil is new NOVATION Heat Exchanger Technology This is an all aluminum construction with louvered fins over single depth crosstubes The crosstubes have multiple small passages through which the refrigerant passes from header to header on each end Tubes and fins are both aluminum construction Connection tube joints are copper The coil may be one row or two row Two row coils are spaced apart to assist in cleaning See Fig 8 7 7 MICROCHANNELS 07273 Fig 8 NOVATION Heat Exchanger Coils Evaporator Coil The evaporator coil is traditional round tube plate fin technology Tube and fin construction is of various optional materials and coatings see Model Number Format Coils are multiple row Coil Maintenance and Cleaning Recommendation Routine cleaning of coil surfaces is essential to
42. signal Modulation is based on the greater of DCV and supply air sensor signals between minimum position and either maximum position DCV or fully open supply air signal ttt Modulation is based on the greater of DCV and supply air sensor signals between closed and either maximum position DCV or fully open supply air signal 2 10 VDC ACTUATOR 2 84 Volts Fig 64 EconoMi er IV Functional View EconoMi er IV Table 22 provides a summary of EconoMi er IV Troubleshooting instructions are enclosed A functional view of the EconoMi er is shown in Fig 64 Typical settings sensor ranges and jumper positions are also shown An EconoMi er IV simulator program is available from Bryant to help with EconoMi er IV training and troubleshooting EconoMi er IV Standard Sensors Outdoor Air Temperature OAT Sensor C06053 The outdoor air temperature sensor HH57AC074 is a 10 to 20 mA device used to measure the outdoor air temperature The outdoor air temperature is used to determine when the EconoMi er IV can be used for free cooling The sensor is factory installed the EconoMi er IV in the outdoor airstream See Fig 60 The operating range of temperature measurement is 40 to 1009F 4 to 38 C See Fig 67 52 Supply Air Temperature Sensor The supply air temperature sensor is a 3 thermistor located at the inlet of the indoor fan See Fig 65 This sensor is factory installed
43. start relay Determine cause and replace One leg of three phase power dead Replace fuse or reset circuit breaker Determine cause Compressor Cycles other than normally satisfying thermostat Refrigerant overcharge or undercharge Recover refrigerant evacuate system and recharge to nameplate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked condenser Determine cause and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor Operates Continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low Reset thermostat Low refrigerant charge Locate leak repair and recharge Leaking valves in compressor Replace compressor Excessive Head Pressure Air in system Recover refrigerant evacuate system and recharge Condenser coil dirty or restricted Clean coil or remove restriction Dirty air filter Replace filter Dirty condenser coil Clean coil Refrigerant overcharged Recover excess refrigerant Air in system Recover refrigerant evacuate
44. the 24 v control circuit and causes all unit operation to cease This device resets automatically when the motor windings cool Do not bypass this switch to correct trouble Determine the cause and correct it The External motor overload device is specially calibrated circuit breaker that is UL recognized as a motor overload controller It is an overcurrent device When the motor current exceeds the circuit breaker setpoint the device opens all motor power leads and the motor shuts down Reset requires a manual reset at the overload switch This device designated IFCB is located on the side of the supply fan housing behind the fan access panel 24 Troubleshooting Supply Fan Motor Overload Trips The supply fan used in 580J units is a forward curved centrifugal wheel At a constant wheel speed this wheel has a characteristic that causes the fan shaft load to DECREASE when the static pressure in the unit duct system increases and to INCREASE when the static pressure in the unit duct system decreases and fan airflow rate increases Motor overload conditions typically develop when the unit is operated with an access panel removed with unfinished duct work in an economizer open mode or a leak develops in the duct system that allows a bypass back to unit return opening Condenser Fan Motor Protection The condenser fan motor is internally protected against overtemperature Control Circuit 24 V The control circuit is protect
45. 0 Automati wiring or sensor configured incorrectly eee Dioxide co2_hi Alarm Generated Automatic CO2 reading is above 1200ppm AU Fam Runtime sf_rntm Alarm Generated ree ing Supply fan run time exceeded user defined limit Pees d Runtime dx1_rntm Alarm Generated pui me Compressor run time limit is exceeded aU TUE 2 Runtime dx2_rntm Alarm Generated ae UR Compressor run time limit is exceeded 46 Alarms Alarms can be checked through the network and or the local access All the alarms are listed in Table 18 with name object name action taken by control reset method and probable cause There are help screens for each alarm on the local access display and listed in RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50H T 2T Appendix A Help Screens Some alarms are explained in detail below Safety Chain Alarm This alarm occurs immediately if the supply fan internal overload trips or if an electric heat limit switch trips The Unit Status will be Shutdown and the System Mode will be Disable When this happens LCTB R terminal will not have 24 VAC but the RTU MP board will still be powered All unit operations stop immediately and will not restart until the alarm automatically clears There are no configurations for this alarm it is all based on internal wiring This alarm will never occur if Fire Shutdown Alarm is active Fire Shutdown Alarm This alarm occurs immediately whe
46. 1 4 SAE male flare couplings The brass fittings are two piece High Flow valves with a receptacle base brazed to the tubing and an integral spring closed check valve core screwed into the base See Fig 9 This check valve is permanently assembled into the core body and cannot be serviced separately Replace the entire core body if necessary Service tools are available from RCD that allow the replacement of the check valve core without having to recover the entire system refrigerant charge Apply compressor refrigerant oil to the check valve core s bottom O ring Install the fitting body with 96 10 in lbs Nm of torque do not overtighten R 410A REFRIGERANT This unit is designed for use with Puron R 410A refrigerant Do not use any other refrigerant in this system Puron R 410A refrigerant is provided in pink rose colored cylinders These cylinders are available with and without dip tubes cylinders with dip tubes will have a label indicating this feature For a cylinder with a dip tube place the cylinder in the upright position access valve at the top when removing liguid refrigerant for charging For a cylinder without a dip tube invert the cylinder access valve on the bottom when removing liguid refrigerant Because Puron R 410A refrigerant is a blend it is strongly recommended that refrigerant always be removed from the cylinder as a liguid Admit liguid refrigerant into the system in the disch
47. 3 25 24 RED EN 5 Voc RyAVad BLK PIS n MIN 8 Ea WHT D dvo 7 iW m oll PL6 R triop accesso Pn OPEN SENSOR pv RED BRN me 7 O max BRN IAQ O 2 Tov 1 2 GHBLU U ed A01 xcv At GRA NOT 11 RED OAT TEMP DCV 5 GRA lt ENTHALPY SEISO 50 ser YEL NOT USED 1 BLK Ith 4 ORN soll 2v Tov RED Es YEL 5 SR FREE eae CooL 1 i ACCESSORY SR a 2 RAT ENTHALPY SENSOR 2001 8 e wl i i A 0 BLK 3 5 i 4 i BRN 1 TH NAT 5X RESISTER SHOULD BE REMOVED ONLY WHEN n USING DIFFERENTIAL ENTHALPY R DRY BULB T GRA 5 2 1 SEPERATE FIELD SUPPLIED 24V TRANSFORMER IS USED FOR THE AN IAQ SENSOR POWER SUPPLY IT CANNOT HAVE THE SECONDARY OF THE 1 9 TRANSFORMER GROUNDED ORN 3 FOR FIELD INSTALLED REMOTE MINIMUM POSITION POT 1 REMOVE BLACK WIRE JUMPER BETWEEN P AND AND SET TO PWR EXHAUST 12 CONTROL MINIMUM POSITION POT TO THE MINIMUM POSITION ACCESSORY NOT USED C09023 Fig 62 EconoMi er IV Wiring TRANSFORMER GROUND 500 OHM RESISTOR U VIOLET PINK OAT SENSOR NOTE 3 Pl 50HJ540573 ACTUATOR O lo o ASSEMBLY 11 AZ 9 DIRECT DRIVE 4 20mA SIGNAL ACTUATOR m 12 YELLOW ECONOMI ER2 PLUG NO
48. 319 STD 23 7 30 25 125 25 5 30 27 127 460 3 60 MED 0 25 1 8 25 5 30 27 147 27 3 30 29 149 HIGH 28 5 35 31 151 30 3 35 33 153 m STD 17 9 20 19 95 21 7 25 23 99 575 3 60 MED 0 24 3 8 18 7 25 20 106 22 5 25 24 110 HIGH 21 5 25 23 120 25 3 30 27 124 STD 0 48 38 65 5 80 69 365 69 3 80 73 369 208 230 3 60 MED 68 0 80 72 382 71 8 80 76 386 HIGH Model not available due to high amperage draw STD 31 7 40 33 183 33 5 40 35 185 E 460 3 60 MED 0 25 1 8 32 7 40 35 192 34 5 45 37 194 HIGH 35 7 45 38 196 37 5 45 40 198 m STD 24 0 30 25 144 27 8 30 30 148 575 3 60 MED 0 24 3 8 24 0 30 25 144 27 8 30 30 148 HIGH 26 8 30 29 158 30 6 35 33 162 Example Supply voltage is 230 3 60 LEGEND AWG CO Convenient outlet 224 v DISC Disconnect C US 2 231v FLA Full load amps 226v IFM Indoor fan motor LRA Locked rotor amps 224 231 226 681 MCA Minimum circuit amps Average Voltage MOCP Maximum over current protection 3 3 PE Power exhaust UNPWRD CO Unpowered convenient outlet E 227 NOTES 1 In compliance with NEC requirements for multimotor and combination load equipment refer to NEC Articles 430 and 440 the overcurrent protective device for the unit shall be fuse or HACR breaker Canadian units may be fuse or circuit breaker 2 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply voltage is greater than 296 Use the following formula to
49. 580J 08 14D F 2 COMPRESSOR NOMINAL 7 5 to 12 5 TONS WITH PURON R 410A REFRIGERANT TER amp Service and Maintenance Instructions TABLE OF CONTENTS SAFETY CONSIDERATIONS 1 UNIT ARRANGEMENT AND ACCESS 2 SUPPLY FAN BLOWER SECTION 4 COOLING RR ERES oy 6 PURON R 410A REFRIGERANT 8 COOLING CHARGING CHARTS 10 CONVENIENCE OUTLETS 16 SMOKE DETECTORS 17 PROTECTIVE DEVICES 24 GAS HEATING SYSTEM 25 CONDENSER COIL SERVICE 35 RTU MP CONTROL SYSTEM 35 ECONOMISER 5 50 WIRING DIAGRAMS 59 5 62 START UP GENERAL 62 START UP RTU MP CONTROL 64 OPERATING SEQUENCES 67 FASTENER TORQUE VALUES A APPENDIX I MODEL NUMBER SIGNIFICANCE 72 APPENDIX II PHYSICAL DATA 73 APPENDIX FAN PERFORMANCE 75 APPENDIX IV WIRING DIAGRAM LIST 82 APPENDIX V MOTORMASTER SENSOR LOCATIONS ricetta etie FAN 83 UNIT START UP CHECKLIST 85 SAFETY CONSIDERATIONS Installation and servicing of air conditioning equipment can be hazardous due to system pressure and elec
50. 8 Follow instructions in the accessory kit to make initial readjustment Table 8 Liguid Propane Manifold Pressure Ranges UNITMODEL UNITSIZE HIGHFIRE LOW FIRE 10 0 in wg 5 0 in wg 580J All 2490 Pa 1245 Pa Supply Pressure Switch The LP conversion kit includes a supply low pressure switch The switch contacts from terminal C to terminal NO will open the gas valve power whenever the supply line pressure drops below the setpoint See Fig 32 and 33 If the low pressure remains open for 15 minutes during a call for heat the IGC circuit will initiate a Ignition Fault 5 flashes lockout Reset of the low pressure switch is automatic on rise in supply line pressure Reset of the IGC requires a recycle of unit power after the low pressure switch has closed C08238 C08239 All 580J D except DDO8 Fig 32 LP Low Pressure Switch Installed IGC LP LPS BRN Jo o NO 42 11 22 MGV IGC GWm cRA CM J2 12 TSTAT e W2 PNK H C08285 Fig 33 LP Supply Line Low Pressure Switch Wiring This switch also prevents operation when the propane tank level is low which can result in gas with a high concentration of impurities additives and residues that have settled to the bottom of the tank Operation under these conditions can cause harm to the heat exchanger system Contact your fuel supplier if this c
51. 80 558J D08 1 5 9 0 580 558J D12 10 0 11 0 TIE WRAP SENSOR Fig 75 580J 08 12D F Outdoor Circuiting C09226 NOTE The low ambient kit for the 12 5 ton unit utilizes a pressure transducer and therefore there is no Motormaster temperature sensor location for this unit 2009 Bryant Heating amp Cooling Systems 7310 W Morris St Indianapolis IN 46231 Printed in U S A Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations 83 Edition Date 5 09 Catalog No SM580J 02 Replaces NEW ross 84 UNIT START UP CHECKLIST I PRELIMINARY INFORMATION MODEL NO SERIAL NO DATE TECHNICIAN BUILDING LOCATION PRE START UP insert check mark in box as each item is completed START UP VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS VERIFY THAT FLUE HOOD IS INSTALLED CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHARP EDGES CHECK GAS PIPING FOR LEAKS CHECK THAT RETURN AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND V
52. 98 0 0980 41 LH32RF096 0 0960 42 LH32RF094 0 0935 43 LH32RF089 0 0890 44 LH32RF086 0 0860 45 LH32RF082 0 0820 46 LH32RF080 0 0810 47 LH32RFO79 0 0785 48 LH32RF076 0 0760 49 LH32RFO73 0 0730 50 LH32RF070 0 0700 51 LH32RF067 0 0670 52 LH32RF065 0 0635 53 LH32RF060 0 0595 54 LH32RFO55 0 0550 55 LH32RF052 0 0520 56 LH32RF047 0 0465 57 LH32RF043 0 0430 58 LH32RF042 0 0420 Table 12 Altitude Compensation 08 14 125 000 250 000 180 000 224 000 ELEVATION BTUH Nominal BTUH Nominal BTUH Nominal ft m NG Orifice LP Orifice NG Orifice LP Orifice NG Orifice LP Orifice Size Size Size Size Size Size 0 2000 610 311 493 130 463 311 483 2000 610 321 503 130 473 321 493 3000 914 321 503 311 473 321 493 4000 1219 331 503 311 483 331 493 5000 1524 331 514 311 483 331 503 6000 1829 341 514 311 483 341 503 7000 2134 351 514 321 493 351 503 8000 2438 361 524 331 493 361 514 9000 2743 372 524 341 503 372 514 10000 3048 382 524 351 503 382 524 11000 3353 392 534 36 515 392 525 12000 3658 141 535 372 514 141 534 13000 3962 142 544 382 524 142 534 14000 4267 143 544 140 535 143 544 LEGEND NG Natural Gas at higher altitudes T Not included in kit May be purchased separately through dealer LP Liguid Propane the height above sea level increases there is less oxygen per cubic ft of air Therefore heat input rate should be reduced 1 CRLPE
53. D Failure to follow this caution may result in personnel and authority concern Holding the test magnet to the target area for longer than seven seconds will put the detector into the alarm state and activate all automatic alarm responses Dirty Sensor Test Using an SD TRK4 1 Turn the key switch to the RESET TEST position for two seconds 2 Verify that the test reset station s Trouble LED flashes Detector Cleaning Cleaning the Smoke Detector Clean the duct smoke sensor when the Dirty LED is flashing continuously or sooner if conditions warrant 22 CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern If the smoke detector is connected to a fire alarm system first notify the proper authorities that the detector is undergoing maintenance then disable the relevant circuit to avoid generating a false alarm 1 Disconnect power from the duct detector then remove the sensor s cover See Fig 28 Sampling HVAC duct I Sensor housing Airflow I Retainer clip C07305 Fig 28 Sensor Cleaning Diagram 2 Using a vacuum cleaner clean compressed air or a soft bristle brush remove loose dirt and debris from inside the sensor housing and cover Use isopropyl alcohol and a lint free cloth to remove dirt and other contaminants from the gasket on the sensor s cover 3 Squeeze the retainer clips on both sides o
54. EDs are now off Replace all panels Troubleshooting Controller s Trouble LED is On 1 Check the Trouble LED on each sensor connected to the controller If a sensor s Trouble LED is on de termine the cause and make the necessary repairs 2 Check the wiring between the sensor and the control ler If wiring is loose or missing repair or replace as required Controller s Trouble LED is Flashin 1 One or both of the sensors is 100 dirty 2 Determine which Dirty LED is flashing then clean that sensor assembly as described in the detector cleaning section Sensors Trouble LED is On 1 Check the sensor s Dirty LED If it is flashing the sensor is dirty and must be cleaned 2 Check the sensor s cover If it is loose or missing se cure the cover to the sensor housing 3 Replace sensor assembly Sensor s Power LED is Off 1 Check the controller s Power LED If it is off de termine why the controller does not have power and make the necessary repairs 2 Check the wiring between the sensor and the control ler If wiring is loose or missing repair or replace as required 23 5804 Table 3 Detector Indicators CONTROL OR INDICATOR DESCRIPTION Magnetic test reset switch the normal state Resets the sensor when it is in the alarm or trouble state Activates or tests the sensor when it is in Alarm LED Indicates the sensor is in the alarm state Trouble LED Indicates the sensor
55. ELD BLK FOUTRE Idem p Eu ues ep cages AMO E21 BLK Fm BLK POWER BLK CLOT rl EL YEL mE YEL 13 COMP SUPPLY YEL y REL MERI eee m YEL BLU T2 YEL EQUIP BLK GN 115V YEL YEL OFM1 FIELD a M 71 1 SERGI wer 300 ORN D4 KC BRN ON POWERED CONVENIENCE MID OUTLET f a BLU YEL OFM2 BRN i L1 BLK IFCB 12 YEL 126 9 Yt 2 ew L IFC 5 lt J 74 7 BLU 136 0 3 BLU 3 IFM ACCY V anj BLK BLK 106 9 21 BLk 1 08 12 HI STATIC ONLY BLK 16C YEL Fo BRN ul BLK uud f YEL 10M 460V VIO 208 230V SEE CONTROL SCHEMATIC YEL BLK TRAN RED 24 TO 24V NY SCHEMATIC BRN LEGEND X MARKED WIRE X TERMINAL MARKED TERMINAL UNMARKED X TERMINAL BLOCK 5 C CONTACTOR COMPRESSOR 0 0 OUTDOOR OUALITY SPLICE CAP CAPACITOR 0 OUTDOOR AIR TEMP SEN SPLICE MARKED CB CIRCUIT BREAKER os OUTDOOR FAN MOTOR CCH CRANKCASE HEATER L OVERLOAD ACTOR T WIRING CC CARRIER COMFORT NETWORK PL PLUG ASSEMBLY FIELD CONTROL WIRING CMP SAFE COMPRESSOR SAFFETY PO POTENTIOMETER CLO COMPRESSOR LOCKOU PMR PHASE MONITOR RELAY a COMP COMPRESSOR MOTOR QT QUADRUPLE TERMINAL CIRCUIT BOARD TRACE DDC DIRECT DIGITAL CONTROL A RELAY FIRE SHUT DOWN URN AIR TEMP SEN 1 ACCESSORY OR OPTIONAL WIRIN
56. ERIFY SETSCREW IS TIGHT VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT ELECTRICAL SUPPLY VOLTAGE L1 L2 12413 L3 L1 COMPRESSOR 1 L1 L2 L2 COMPRESSOR 2 L1 L2 L2 INDOOR FAN AMPS L1 L2 L2 TEMPERATURES OUTDOOR AIR TEMPERATURE DB WB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR DB PRESSURES GAS INLET PRESSURE IN WG GAS MANIFOLD PRESSURE IN WG LOW FIRE IN WG HI FIRE REFRIGERANT SUCTION CIR 1 PSIG TEMP F SIUE PSIG TEMP REFRIGERANT DISCHARGE 1 PSIG TEMP F CIR2 PSIG TEMP F VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS VERIFY THAT 3 PHASE SCROLL COMPRESSORS ARE ROTATING IN CORRECT DIRECTION 85
57. FF ON OFF OFF OFF NOTE Comm Sef fo DS Dip Switch tion 5 mare 38 4k BACnet MS TP SW3 example shown Unused Baud Rate Selections BAUD RATE DS2 DS1 9600 OFF OFF 19 200 ON OFF 38 400 OFF ON 76 800 ON ON OFF ON Protocol Selector DIP Switches C07166 Fig 57 RTU MP SW3 Dip Switch Settings Virtual BACview Virtual BACview is a freeware computer program that functions as the BACview Handheld The USB Link interface USB L is required to connect a computer to the RTU MP board The link cable connects a USB port to the J12 local access port This program functions and operates identical to the handheld D BACDview 5 Cable RTU MP Troubleshooting Communication LEDs The LEDs indicate if the controller is speaking to the devices on the network The LEDs should reflect communication traffic based on the baud rate set The higher the baud rate the more solid the LEDs will appear LOCAL ACCESS PORT RNET C07170 Fig 58 BACview Handheld Connections 44 Table 17 LEDs The LEDs on the RTU MP show the status of certain functions If this LED is on Status is Power The RTU MP has power Rx The RTU MP is receiving data from the network segment Tx The RTU MP is transmitting data over the network segment DO The digital output is active The Run and Error LEDs indicate control
58. G FS FLAME SENSOR RMT OCC EMOTE OCCUPANCY 10 INDICATE COMMON POTENTIAL FU FUSE RS ROLLOUT SWITCH ONLY NOT TO REPRESENT WIRING 6 GROUND SA SUPPLY AIR TE SENSOR GVR GAS VALVE RELAY SEN SENSOR HPS HIGH PRESSURE SWITCH SE SET POINT OFFSET HS HALL EFFECT SENSOR SFS SUPPLY FAN STATUS NOTES I IGNITOR TDR ME DELAY RELAY 1 IF ANY OF THE ORIGINAL WIRE FURNISHED IAQ INDOOR AIR QUALITY SENSORS TRAN RANSFORMER MUST BE REPLACED IT MUST BE REPLACED ID INDUCED DRAFT MOTOR WITH TYPE 90 C WIRE OR ITS EQUIVALENT INDOOR FAN CONTACTOR 2 COMPRESSOR AND FAN MOTORS ARE THERMALLY IFCB INDOOR FAN CIRCUIT BREAKER PROTECTED THREE PHASE MOTORS ARE IFM INDOOR FAN MOTOR PROTECTED AGAINST PRIMARY SINGLE PHASING IGC INTEGRATED GAS CONTROL CONDITIONS IRH INDOOR RELATIVE HUMIDITY 3 208 230V UNIT TRAN IS WIRED FOR 230V UNIT JMP JUMPER IF UNIT IS TO BE RUN WITH 208V POWER SUPPLY LA LOW AMBIENT LOCKOUT DISCONNECT BLK WIRE FROM 230V TAP AND LOOP PWR CURRENT LOOP POWER CONNECT TO 200V TAP LPS LOW PRESSURE SWITCH 4 USE COPPER COPPER CLAD ALUMINUM OR LSM LIMIT SWITCH MANUAL RESET ALUMINUM CONNECTORS LS LIMIT SWITCH 5 USE COPPER CONDUCTOR ONLY MGV MAIN GAS VALVE OFR OUTDOOR FAN RELAY C09156 Fig 73 580J Typical Unit Wiring Diagram Power 08D F 208 230 3 60 60 ross 09 5 0 5 805 A AZT 80 1023000 SULA 08 pL SA 291609
59. Internal Control Fault 9 Flashes Software Lockout LEGEND LED Light Emitting Diode A3 second pause exists between LED error code flashes If more than one error code exists all applicable codes will be displayed in numerical sequence IMPORTANT Refer to Troubleshooting Table 13 and 14 for additional information 29 5804 REGULATOR m COVER SCREW PLASTIC ADJUST REGULATOR SPRING PROPANE WHITE NATURAL SILVER PRESSURE TAP MANIFOLD PRESSURE TAP 1 27 NPT OUTLET 580J08 D F 150 only C08240 Low regulator cover screw Single stage and two stage two stage only high regulator cover screw a Regulator adjust screw e Regulator spring Pilot cover screw Pilot gasket Pilot adjust screw Outlet pressure tap C08241 All 580J D F except 150 Fig 39 Gas Valve Orifice Replacement This unit uses orifice type LH32RFnnn where nnn indicates orifice reference size When replacing unit orifices order the necessary parts via Bryant RCD See Table 11 for available orifice sizes See Table 12 for orifice sizes for Natural Gas and LP fuel usage at various elevations above sea level Check that each replacement orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum value See Fig 35 30 Red LED Status 52 RSS cc D7 LED1 lt gt Sz 4 C
60. LEV001A00 2 CRLPELEV002A00 3 CRLPELEV003A00 4 CRLPELEV004A00 32 Minimum Heating Entering Air Temperature When operating on first stage heating the minimum temperature of air entering the dimpled heat exchanger is 50 continuous and 45 intermittent for standard heat exchangers and 40 F continuous and 35 F intermittent for stainless steel heat exchangers To operate at lower mixed air temperatures a field supplied outdoor air thermostat must be used to initiate both stages of heat when the temperature is below the minimum required temperature to ensure full fire operation Wire the outdoor air thermostat OALT part no HH22AG106 in series with the second stage gas valve See Fig 41 Set the outdoor air thermostat at 35 F for stainless steel heat exchangers or 45 F for standard heat exchangers This temperature setting will bring on the second stage of heat whenever the ambient temperature is below the thermostat setpoint Indoor comfort may be compromised when heating is initiated using low entering air temperatures with insufficient heating temperature rise Thermostat LCTB TH1 C08442 Fig 41 OATL Connections Troubleshooting Heating System Refer to Table 13 and 14 for additional troubleshooting topics Table 13 Heating Service Analysis PROBLEM CAUSE REMEDY Misaligned spark electrodes Check flame ignition and sensor electrode positioning Adjust as needed No gas
61. M V Ph Hz RANGE Max Max MIN MAX RLA LRA RLA LRA WATTS FLA TYPE WATTS AMP Draw EFF at Full Load FLA STD 2615 7 9 8196 7 5 208 3 60 187 253 19 0 123 22 4 149 1288 6 2 MED 3775 10 5 8196 10 0 HIGH 4400 15 0 8196 15 0 STD 2615 7 9 8196 7 5 230 3 60 187 253 19 0 123 22 4 149 1288 6 2 MED 3775 10 5 81 10 0 HIGH 4400 15 0 81 15 0 STD 2615 3 6 81 3 4 460 3 60 414 506 9 7 62 10 6 75 1288 3 1 MED 3775 4 6 8196 4 4 HIGH 4400 7 4 81 7 4 STD 3775 2 9 8196 2 8 575 3 60 518 633 7 4 50 77 54 1288 2 5 MED 3775 2 9 81 2 8 HIGH 4400 5 9 81 5 6 80 MCA MOCP DETERMINATION OR UNPWRD z COMBUSTION POWER NO C O or UNPWRD C O IFM NO P E w PE pwrd fr unit V Ph Hz TYPE FAM Er MCA MOCP DISC SIZE MCA MOCP DISC SIZE FLA LRA FLA LRA STD 43 6 50 46 198 47 4 60 51 202 208 230 3 60 MED 0 48 3 8 45 9 50 49 235 49 7 60 53 239 HIGH 53 8 60 58 261 57 6 70 62 265 a STD 20 1 25 21 97 21 9 25 23 99 460 3 60 MED 0 25 1 8 20 9 25 22 116 22 7 25 24 118 8 HIGH 25 3 30 27 129 27A 30 29 131 io STD 14 8 20 16 79 18 6 20 20 83 575 3 60 MED 0 24 3 8 15 2 20 16 94 19 0 25 21 98 HIGH 18 3 20 19 108 22 1 25 24 112 STD 48 5 60 51 263 52 3 60 56 267 208 230 3 60 MED 0 48 3 8 53 3 60 57 306 57 1 70 61 310 HIGH 58 3 70 62 315 62 1 70 67
62. PHYSICAL DATA cont Physical Data Heating 7 5 12 5TONS Gas Connection of Gas Valves Nat gas supply line press in w g PSIG LP supply line press in w g PSIG Heat Anticipator Setting Amps 580J 08 580J 12 580J 14 1 4 13 0 18 0 47 11 13 0 40 0 47 1 4 13 0 18 0 47 11 13 0 40 0 47 1 4 13 0 18 0 47 11 13 0 40 0 47 1st stage 014 014 014 2nd stage 0 14 0 14 0 14 Natural Gas Heat Propane Heat of stages of burners total 1 3 2 4 2 4 Connection size 1 2 NPT 3 4 NPT 3 4 NPT 5 Rollout switch opens Closes 195 115 195 115 195 115 Temperature rise min max 20 50 25 65 25 65 of stages of burners total 2 4 2 5 2 5 e Connection size 3 4 NPT 3 4 NPT 3 4 NPT W Rollout switch opens Closes 195 115 195 115 195 115 gt Temperature rise min max 35 65 30 65 25 65 of stages of burners total 2 5 2 5 2 5 Connection Size 3 4 NPT 3 4 NPT 3 4 NPT o Rollout switch opens Closes 195 115 195 115 195 115 Temperature rise min max 45 75 35 70 35 70 74 APPENDIX FAN PERFORMANCE 580J 08 3 PHASE 7 5 TON HORIZONTAL SUPPLY AVAILABLE EXTERNAL STATIC PRESSURE in wg CFM 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard Static Option M
63. RIPS SPONGE RUBBER REGULATOR GASKET REGULATOR RETAINER WIND CAP ASSEMBLY SHOWN INVERTED AS SHIPPED SUPPORT INSULATION ASSEMBLY INDUCER FAN MOTOR ASSEMBLY BURNER ASSEMBLY C08227 Fig 34 Heat Exchanger Assembly Burners and Igniters ORIFIOE CAUTION 100 25 4 mm EQUIPMENT DAMAGE HAZARD FN Failure to follow this caution may result in eguipment damage When working on gas train do not hit or plug WAN orifice spuds PIPE 08211 Main Burners Fig 35 Orifice Projection To access burners remove burner access panel and slide Removal and Replacement of Gas Train out burner partition At the beginning of each heating season inspect for deterioration or blockage due to See Fig 30 34 and 36 corrosion or other causes Observe the main burner flames 1 Shut off manual gas valve a 2 Shut off power to unit Orifice Projection 3 Slide out burner partition Refer to Fig 35 for maximum projection dimension for 4 Disconnect gas piping at unit gas valve orifice face to manifold tube 5 Remove wires connected to gas valve Mark each wire 27 5804 MANIFOLD PRESSURE TAP BURNERS C09154 Fig 36 Burner Tray Details 6 Remove igniter wires and sensor wires at the Integ rated Gas Unit Controller IGC See Fig 37 7 Remove the 2 screws that attach the burner rack to the vestibule plate See Fig 34 8 Slide the burner tray out of the un
64. Re position the sensor in the flange of the supply air opening or in the supply air duct as required by local codes Drill or punch a 1 2 in hole in the flange or duct Use two field supplied self drilling screws to secure the sensor probe in a horizontal orientation See Fig 43 Outdoor Air Temperature OAT Sensor The OAT is factory mounted in the EconoMi er 2 FIOP or accessory It is a nominal 10k ohm thermistor attached to an eyelet mounting ring See Table 16 for temperature resistance characteristic 38 Table 16 Thermistor Resistance vs Temperature Values for Space Temperature Sensor Supply Air Temperature Sensor and Outdoor Air Temperature Sensor TEMP TEMP RESISTANCE Ohms 40 40 335 651 35 31 242 195 30 22 176 683 25 13 130 243 20 4 96 974 15 5 72 895 10 14 55 298 5 23 42 315 0 32 32 651 5 41 25 395 10 50 19 903 15 59 15 714 20 68 12 494 25 77 10 000 30 86 8 056 35 95 6 530 40 104 5 325 45 113 4 367 50 122 3 601 55 131 2 985 60 140 2 487 65 149 2 082 70 158 1 752 SUPPLY AIR GURS TEMPERATURE T TS SENSOR SUPPLY AIR RETURN AIR Fig 44 Typical Mounting Location for Supply Air Temperature SAT Sensor on Small Rooftop Units EconoMi er 2 The RTU MP control is used with EconoMi er2 option or accessory for outdoor air management T
65. State aux 2 DO Relay 24VAC 1 J11 3 Dehumidification Relay State humizer DO Relay 24VAC 1 411 7 8 LEGEND Analog Input AO Analog Output DI Discrete Input DO Discrete Output These inputs if installed take the place of the default input on the specific channel according to schematic Parallel pins J5 1 42 6 45 3 J1 10 45 5 J1 2 are used for field installation Refer to the input configuration and accessory sections for more detail NOTE Refer to RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50H T 2T for complete configuration of operating sequences and troubleshooting information Refer to RTU MP 3rd Party Integration Guide for details on configuration and troubleshooting of connected networks Have a copy of these manuals available at unit start up The RTU MP controller requires the use of a Bryant space sensor A standard thermostat cannot be used with the RTU MP system Supply Air Temperature SAT Sensor On FIOP equipped 580J unit the unit is supplied with a supply air temperature SAT sensor 33ZCSENSAT This sensor is a tubular probe type approx 6 inches 12 7 mm in length It is a nominal 10 k ohm thermistor See Table 16 for temperature resistance characteristic The SAT is factory wired The SAT probe is wire tied to the supply air opening on the horizontal opening end in its shipping position Remove the sensor for installation
66. Sunday To select a daily schedule scroll to the Schedules menu off of the Menu selection Enter the User password and change the Occupancy Source to Local Schedule Scroll down and over to the Daily menu and press enter Choose one of the four Daily schedules by pressing the Next softkey and change the Use point from NO to YES by selecting the point and pressing the INCR or DECR softkey Press the OK softkey and scroll to the start and stop times Edit these times following the same steps as the Use point Finally scroll down to the Days section and highlight the days reguired for the Daily schedule by INCR or DECR softkeys and press OK softkey The Holiday schedule is created to override the Daily schedule and identify a specific day and month of the year to start and stop the unit and change control to the unoccupied heating and cooling setpoints Follow the same steps to turn on one of the twelve Holiday schedules and start and stop times Next select one out of the twelve months and one out of the thirty one days of that month The RTU MP will now ignore the Daily schedule for the specific day and time you selected and follow the Holiday Schedule for this period The Override schedules primary purpose is to provide a temporary change in the occupied heating and cooling setpoints and force the unit to control to the unoccupied heating and cooling setpoints This would occur on a set day in a particular month and last during the start and
67. TES 1 Switch on actuator must be in run position for economizer to operate 2 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500 ohm resistor 09223 Fig 63 EconoMi er2 with 4 to 20 mA Control Wiring 51 5804 Table 22 EconoMi er IV Input Output Logic INPUTS OUTPUTS Demand Cantal Enthalpy Compressor N Terminalt Ventilation DCV Outdoor Return Y Y Stage Stage DAU PP 1 2 Damper High On On On Free Cooling LED Low On Off Off Minimum position Closed Below set Off Off Of Off Off DCV LED Off Low On On off Modulating between Modulating Free Cooling LED Hiah min position and between closed and Free om 9 Of Off Off full open full open Off Off Off Off Minimum position Closed High On On Modulatingtt between b BAN Free Cooling LED Low Off Off min position and DCV DCV Above set Off off Of Off Of maximum maximum DCV LED On ow On On On Off Free Cooling LED High On Off Off Off Modulating Modulatingttt On Off Off Off Off Forsingle enthalpy control the module compares outdoor enthalpy to the ABCD setpoint t Power at N terminal determines Occupied Unoccupied setting 24 vac Occupied no power Unoccupied Modulation is based on the supply air sensor signal tt Modulation is based on the DCV
68. The timer will then begin counting its runtime again for the next maintenance interval Factory Default 0 hr NOTE Setting this configuration timer to 0 disables the alarm Cooling Number of Compressor Stages This refers to the number of mechanical cooling stages available on a specific unit Set this point to Stage if there is one compressor in the specific unit set to Two Stage if there are two compressors in the unit and set to None if economizer cooling ONLY is desired Factory Default 2 One Stage for 1 compressor units Two Stage for 2 compressor units Cooling Econ SAT Low Setpt The supply air temperature must remain above this value to allow cooling with the economizer and or compressors There is 5 F plus and minus deadband to this point If the SAT falls below this value during cooling all compressors will be staged off The economizer will start to ramp down to minimum position when the SAT this configuration 5 F Factory Default 50 F Range 45 75 Cooling Lockout Temp This defines the minimum outdoor air temperature that cooling mode can be enabled and run If the OAT falls below this threshold during cooling then compressor cooling will not be allowed Factory Default 45 F Range 0 65 Heating High Setpt The supply air temperature must remain below this value to allow heating There is 5 F plus and minus deadband to this point If the SAT rises above t
69. aline environmentally sound coil cleaner as described above CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in reduced unit performance High velocity water from a pressure washer garden hose or compressed air should never be used to clean a coil The force of the water or air jet will bend the fin edges and increase airside pressure drop Totaline Environmentally Sound Coil Cleaner application Instructions 1 Proper eye protection such as safety glasses is recom mended during mixing and application 2 Remove all surface loaded fibers and dirt with a vacu um cleaner as described above 3 Thoroughly wet finned surfaces with clean water and a low velocity garden hose being careful not to bend fins 4 Mix Totaline environmentally sound coil cleaner in a 2 1 2 gallon garden spryer according to the instruc tions included with the cleaner The optimum solution temperature is 100 F 38 C NOTE Do NOT USE water in excess of 130 F 54 C as the enzymatic activity will be destroyed 5 Thoroughly apply Totaline environmentally sound coil cleaner solution to all coil surfaces including finned area tube sheets and coil headers 6 Hold garden sprayer nozzle close to finned areas and apply cleaner with a vertical up and down motion Avoid spraying in horizontal pattern to minimize po tential for fin damage 7 Ensure cleaner thoroughly penetrates deep into finned areas 8 Int
70. and poll for master requests to non existent Master nodes i e in the above example MAC address 16 would know to pass the token back to MAC address 1 instead of counting up to MAC address 127 Each MS TP master node on the network must have their Max Masters set to this same value The default is 127 MaxInfo Frames This property defines the maximum number of responses that will be sent when our controller gets the token A valid number is any positive integer The default is 10 and should be ideal for the majority of applications In cases where the controller is the target of many reguests this number could be increased as high as 100 or 200 NOTE MS TP networks can be comprised of both Master and Slave nodes Valid MAC addresses for Master nodes are 0 127 and valid addresses for Slave nodes are 0 254 NOTE See RTU MP 3rd Party Integration Guide or alternatively RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50H T 2T Appendix for Protocol Maps 48 Table 19 Manufacture Date When troubleshooting you may need to know a control module s manufacture date Obtain the manufacture date from Notes a Module status report modstat To obtain a modstat with BACview8 1 Press Function FN key and hold 2 Then press period 3 Release both buttons The report shows the date under Main board hardware The serial numbers are unigue and contain embedded infor
71. and wiring to normal after completing troubleshooting DCV Minimum and Maximum Position To check the DCV minimum and maximum position 1 Turn Make sure EconoMi er IV preparation procedure has been performed Connect a 9 v battery to AO positive node and AO1 negative node The DCV LED should turn on The actuator should drive to between 90 and 9590 open Turn the DCV Maximum Position potentiometer to midpoint The actuator should drive to between 20 and 8090 open Turn the DCV Maximum Position potentiometer to fully CCW The actuator should drive fully closed the Minimum Position potentiometer to midpoint The actuator should drive to between 20 and 80 open Turn the Minimum Position Potentiometer fully CW The actuator should drive fully open Remove the jumper from TR and N The actuator should drive fully closed Return EconoMi er IV settings and wiring to normal after completing troubleshooting Supply Air Sensor Input To check supply air sensor input 1 Make sure EconoMi er IV preparation procedure has been performed Set the Enthalpy potentiometer to A The Free Cool LED turns on The actuator should drive to between 20 and 80 open Remove the 5 6 kilo ohm resistor and jumper T to T1 The actuator should drive fully open Remove the jumper across T and T1 The actuator should drive fully closed Return EconoMi er IV settings and wiring to normal
72. are not factory connected Selection of primary power source is a customer option If local codes permit the transformer primary leads can be connected at the line side terminals on unit mounted non fused disconnect or circuit breaker switch this will provide service power to the unit when the unit disconnect switch or circuit breaker is open Other connection methods will result in the convenience outlet circuit being de energized when the unit disconnect or circuit breaker is open See Fig 18 16 SCHEMATIC CONVENIENCE OUTLET S RED YEL BLU GRA 45 0 pu GRA CONNECT PER Lau RED LOCAL CODE TRAMA 5 95 YEL L 240V oo P RED YEL BLU GRA SECONDARY He amp S Re Sr uda te TRANS AY gt A dy H H BLK e WHT SECONDARY NN 120V GROUND FAULT TRAM aa INTERRUPTER CONVENTENCE L OUTLET 2 gt ay my GRN YEL SECONDARY _ SWITCH FUSE BLK y B 15 AMP C08283 UNIT CONNECT PRIMARY TRANSFORMER VOLTAGE AS CONNECTIONS TERMINALS 208 240 L1 RED YEL H1 230 L2 BLU GRA 2 4 11 H1 460 480 Splice BLU 4 YEL H2 L2 GRA H4 L1 RED H1 pm 600 2 GRA H2 Fig 18 Powered Convenience Outlet Wiring Duty Cycle The unit powered convenience outlet has a duty cycle limitation The transformer is int
73. arge line If adding refrigerant into the suction line use a commercial metering expansion device at the gauge manifold remove liguid from the cylinder pass it through the metering device at the gauge set and then pass it into the suction line as a vapor Do not remove Puron R 410A refrigerant from the cylinder as a vapor Refrigerant Charge Amount of refrigerant charge is listed on the unit s nameplate Refer to GTAC2 5 Charging Recovery Recycling and Reclamation training manual and the following procedures Unit panels must be in place when unit is operating during the charging procedure To prepare the unit for charge adjustment No Charge Use standard evacuating technigues After evacuating system weigh in the specified amount of refrigerant Low Charge Coolin Using Cooling Charging Charts Fig 10 11 12 and 13 vary refrigerant until the conditions of the appropriate chart are met Note the charging charts are different from the type normally used Charts are based on charging the units to the correct superheat for the various operating conditions Accurate pressure gauge and temperature sensing device are reguired Connect the pressure gauge to the service port on the suction line Mount the temperature sensing device on the suction line and insulate it so that outdoor ambient temperature does not affect the reading Indoor air cfm must be within the normal operating range of the unit To Use Cooling Charging Ch
74. arts Select the appropriate unit charging chart from Fig 10 11 12 and 13 Sizes 08D F and 12D F each have one cooling charging chart Size 14D F has two cooling charging charts Circuit A and Circuit B Take the outdoor ambient temperature and read the suction pressure gauge Refer to chart to determine what suction temperature should be If suction temperature is high add refrigerant If suction temperature is low carefully recover some of the charge Recheck the suction pressure as charge is adjusted For 14D F size perform this procedure once for Circuit A using the Circuit A chart and once for Circuit B using the Circuit B chart Part No EC39EZ067 DEPRESSOR PER ARI 720 01 035 5 8 lt 47 gt FROM FACE OF BODY This surface provides a metal to metal seal when 7 16 20 UNF RH torqued into the seat Appropriate handling is required to not scratch or dent the surface C08453 Fig 9 CoreMax Access Port Assembly EXAMPLE Model 580J 14D Circuit 1 Outdoor 85 29 Suction Pressure 125 psig 860 Suction Temperature should be 58 F 14 C Circuit 2 Outdoor Temperature 85 F 29 C Suction 120 psig 830 kPa Suction Temperature should be 60 F 16 C 5804 COOLING CHARGING CHARTS 7 5 TON CHARGING CHART R410A REFRIGERANT
75. at main burners Check gas line for air purge as necessary After purging gas line of air allow gas to dissipate for at least 5 minutes before attempting to relight unit Check gas valve Water in gas line Drain water and install drip leg to trap water Burners Will Not Ignite No power to furnace Check power supply fuses wiring and circuit breaker No 24 v power supply to control circuit Check transformer Transformers with internal overcurrent protection require a cool down period before resetting Miswired or loose connections Check all wiring and wire nut connections Burned out heat anticipator in Replace thermostat thermostat Broken thermostat wires Run continuity check Replace wires if necessary Dirty air filter Clean or replace filter as necessary Gas input to unit too low Check gas pressure at manifold Clock gas meter for input If too low increase manifold pressure or replace with correct orifices Unit undersized for application Replace with proper unit or add additional unit Restricted airflow Clean filter replace filter or remove any restrictions Inadequate Heating Blower speed too low Use high speed tap increase fan speed or install optional blower as suitable for individual units Limit switch cycles main burners Check rotation of blower thermostat heat anticipator settings and temperature rise of unit Adj
76. ation rate of 2090 or base plus 15 cfm per person Use Fig 72 to determine the maximum setting of sensor For example an 1100 ppm setpoint relates to 15 cfm per person design Use the 1100 ppm curve on Fig 72 to find the point when the CO2 sensor output will be 6 7 volts Line up the point on the graph with the left side of the chart to determine that the range configuration for the sensor should be 1800 ppm The EconoMi er IV controller will output the 6 7 volts from the CO sensor to the actuator when the concentration in the space is at 1100 ppm The DCV setpoint may be left at 2 volts since the CO sensor voltage will be ignored by the EconoMi er IV controller until it rises above the 3 6 volt setting of the minimum position potentiometer Once the fully occupied damper position has been determined set the maximum damper demand control ventilation potentiometer to this position Do not set to the maximum position as this can result in over ventilation to the space and potential high humidity levels Sensor Configuration The sensor has preset standard voltage settings that can be selected anytime after the sensor is powered up See Table 23 Use setting 1 or 2 for Bryant equipment See Table 23 1 Press Clear and Mode buttons Hold at least 5 seconds until the sensor enters the Edit mode 2 Press Mode twice The STDSET Menu will appear Table 23 CO Sensor Standard Settin
77. before use When pressure testing field supplied gas piping at pressures of 0 5 psig or less a unit connected to such piping must be isolated by closing the manual gas valve s CAUTION CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety glasses and gloves when handling parts and servicing air conditioning units UNIT ARRANGEMENT AND ACCESS General Fig 1 and Fig 2 show general unit arrangement and access locations WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death FILTER ACCESS PANEL Units with convenience outlet circuits may use multiple disconnects Check convenience outlet for power status before opening unit for service Locate its disconnect switch if appropriate and open it Tag out this switch if necessary WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could cause personal C06023 injury death and or eguipment damage Fig 1 Typical Access Panel Locations Back INDOOR COIL ACCESS PANEL Puron R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not use R 22 service equipment or compon
78. brazed into the discharge tube Trip setting is 630 psig 10 psig 4344 69 kPa when hot Reset is automatic at 505 psig 3482 kPa Low Pressure Switch Each system is protected against a loss of charge and low evaporator coil loading condition by a low pressure switch located on the suction line near the compressor The switch is stem mounted Trip setting is 54 psig 5 psig 372 34 kPa Reset is automatic at 117 5 psig 807 34 kPa Supply Indoor Fan Motor Protection Disconnect and lockout power when servicing fan motor The supply fan motor is equipped with an overcurrent protection device The type of device depends on the motor size See Table 4 Table 4 Supply Fan Motor Protection Devices Er a Overload Device Reset 1 7 Internal Linebreak Automatic 2 4 Internal Linebreak Automatic 2 9 Thermik Automatic 3 7 Thermik Automatic 52 The Internal Linebreak type is an imbedded switch that senses both motor current and internal motor temperature When this switch reaches its trip setpoint the switch opens the power supply to the motor and the motor stops Reset is automatic when the motor windings cool down The Thermik device is a snap action overtemperature protection device that is imbedded in the motor windings It is a pilot circuit device that is wired into the unit s 24 control circuit When this switch reaches its trip setpoint it opens
79. ctrical connections for tightness Tighten as required Refrigerant Service Ports Each unit system has two 1 4 SAE flare with check valves service ports one on the suction line and one on the compressor discharge line Be sure that caps on the ports are tight Compressor Rotation On 3 phase units with scroll compressors it is important to be certain compressor is rotating in the proper direction To determine whether or not compressor is rotating in the proper direction 1 Connect service gauges to suction and discharge pressure fittings 2 Energize the compressor 3 The suction pressure should drop and the discharge pressure should rise as is normal on any start up If the suction pressure does not drop and the discharge pressure does not rise to normal levels 1 Note that the evaporator fan is probably also rotating in the wrong direction 2 Turn off power to the unit and install lockout tag 3 Reverse any two of the unit power leads 4 Re energize to the compressor Check pressures The suction and discharge pressure levels should now move to their normal start up levels NOTE When the compressor is rotating in the wrong direction the unit will make an elevated level of noise and will not provide cooling Cooling Set space thermostat to OFF position To start unit turn on main power supply Set system selector switch at COOL position and fan switch at AUTO position Adjust thermostat to a setting
80. cur If the limit switch trips during this period the evaporator fan off delay will increase by 15 seconds A maximum of 9 trips can occur extending the evaporator fan off delay to 180 seconds To restore the original default value reset the power to the unit To shut off unit set system selector switch at OFF position Resetting heating selector lever below room temperature will temporarily shut unit off until space temperature falls below thermostat setting Ventilation Continuous Fan Set fan and system selector switches at ON and OFF positions respectively Evaporator fan operates continuously to provide constant air circulation When the evaporator fan selector switch is turned to the OFF position there is a 30 second delay before the fan turns off START UP RTU MP CONTROL Field Service Test explained below will assist in proper start up Configuration of unit parameters scheduling options and operation are also discussed in this section Field Service Test The Field Service Test function can be used to verify proper operation of compressors heating stages indoor fan power exhaust fans economizer and dehumidification Use of Field Service Test is recommended at initial system start up and during troubleshooting See RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50 2 Appendix A for Field Service Test Mode table Field Service Test mode has the following changes fr
81. d on many different base units As such these kits may contain parts that will not be needed for installation T 332 5 2 is an accessory CO sensor 33ZCASPCO2 is an accessory aspirator box required for duct mounted applications tt CRCBDIOX005A00 is an accessory that contains both 33ZCSENCO and 33ZCASPCO2 accessories 3 Use the Up Down button to select the preset number See Table 23 4 Press Enter to lock in the selection 5 Press Mode to exit and resume normal operation The custom settings of the CO sensor be changed anytime after the sensor is energized Follow the steps below to change the non standard settings 1 Press Clear and Mode buttons Hold at least 5 seconds until the sensor enters the Edit mode 2 Press Mode twice The STDSET Menu will appear 3 Use the Up Down button to toggle to the NONSTD menu and press Enter 4 Use the Up Down button to toggle through each of the nine variables starting with Altitude until the desired setting is reached 5 Press Mode to move through the variables 6 Press Enter to lock in the selection then press Mode to continue to the next variable Dehumidification of Fresh Air with DCV Demand Controlled Ventilation Control If normal rooftop heating and cooling operation is not adequate for the outdoor humidity level an energy recovery unit and or a dehumidification option should be considered EconoMi er IV Preparation This procedure is used
82. damper position remotely remove the factory installed jumper on the P and P1 terminals on the EconoMi er IV controller Wire the field supplied potentiometer to the P and P1 terminals on the EconoMi er IV controller See Fig 62 Damper Movement Damper movement from full open to full closed or vice versa takes 2 1 2 minutes Thermostats The EconoMi er IV control works with conventional thermostats that have a Y1 cool stage 1 Y2 cool stage 2 W1 heat stage 1 W2 heat stage 2 and G fan The EconoMi er IV control does not support space temperature sensors Connections are made at the thermostat terminal connection board located in the main control box Demand Control Ventilation DCV When using the EconoMi er IV for demand controlled ventilation there are some equipment selection criteria which should be considered When selecting the heat capacity and cool capacity of the equipment the maximum ventilation rate must be evaluated for design conditions The maximum damper position must be calculated to provide the desired fresh air Typically the maximum ventilation rate will be about 5 to 10 more than the typical cfm required per person using normal outside air design criteria A proportional anticipatory strategy should be taken with the following conditions a zone with a large area varied occupancy and equipment that cannot exceed the required ventilation rate at design conditions Exceeding the required
83. e isolated power supply of 24 VAC See Fig 49 for internal connections at the T 59 Connect the SEN terminal BLU to RTU MP J20 1 Connect the COM terminal BRN to J20 2 Connect the SET terminal STO or BLK to J20 3 o COM _ _ STO SENSOR y et eee WIRING _ SPT l SET SEN OJO NOTE Must use a separate isolated transformer C07132 Fig 49 Space Temperature Sensor Typical Wiring 33ZCT59SPT Economizer Controls Outdoor Air Enthalpy Control 57 077 The enthalpy control HH57AC077 is available as a field installed accessory to be used with the EconoMi er2 damper system The outdoor air enthalpy sensor is part of the enthalpy control The separate field installed accessory return air enthalpy sensor HH57AC078 is reguired for differential enthalpy control Locate the enthalpy control in the economizer hood Locate two GRA leads in the factory harness and connect these leads to enthalpy control sensors 2 and 3 See Fig 50 Connect the enthalpy control power input terminals to economizer actuator power leads RED connect to TR and BLK connect to TR1 LCTB ECON GRA 4 RA 17 Factory Wiring Harness C08218 Fig 50 Enthalpy Switch HH57AC077 Connections Enthalpy Switch The outdoor enthalpy changeover setpoint is set at the enthalpy controller 40 The enthalpy control receives the outdoor air enthal
84. ed against overcurrent conditions by a circuit breaker mounted on control transformer TRAN Reset is manual GAS HEATING SYSTEM General The heat exchanger system consists of a gas valve feeding multiple inshot burners off a manifold The burners fire into matching primary tubes The primary tubes discharge into combustion plenum where gas flow converges into secondary tubes The secondary tubes exit into the induced draft fan wheel inlet The induced fan wheel discharges into a flue passage and flue gases exit out a flue hood on the side of the unit The induced draft fan motor includes a Hall Effect sensor circuit that confirms adequate wheel speed via the Integrated Gas Control IGC board Safety switches include a Rollout Switch at the top of the burner compartment and a limit switch mounted through the fan deck over the tubes See Fig 30 and 31 INDUCED DRAFT MOTOR MOUNTING PLATE ROLLOUT SWITCH FLUE EXHAUST BURNER SECTION INDUCED VESTIBULE DRAFT MOTOR PLATE MANIFOLD PRESSURE ES TAP 5 7 1 GAS BLOWER VALVE HOUSING C09153 Fig 30 Burner Section Details Limit Switch and Shield C08284 Fig 31 Limit Switch Location Fuel Types and Pressures Natural Gas The 580J unit is factory equipped for use with Natural Gas fuel at elevation under 2000 ft 610 m See section Orifice Replacement for information in
85. edium Static Option 2250 505 0 52 586 0 73 657 0 97 722 1 22 782 1 50 2438 533 0 62 610 0 85 679 1 09 742 1 36 800 1 65 2625 562 0 74 635 0 98 701 1 23 762 819 1 81 2813 591 0 88 661 1 13 725 1 39 783 1 68 839 1 98 3000 621 1 03 688 1 29 749 1 57 806 1 87 859 2 18 3188 652 1 21 715 1 48 774 1 77 829 2 07 881 2 40 3375 682 1 40 743 1 68 800 1 98 853 2 30 903 2 63 3563 713 1 61 1 91 826 2 22 878 2 55 927 2 89 3750 745 1 85 801 2 15 853 2 48 903 2 82 951 3 18 AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 Medium Static Option High Static Option 2250 838 1 81 891 2A2 941 2 46 988 2 82 1033 3 19 2438 854 1 96 906 2 28 955 2 63 1001 2 99 1046 3 37 2625 872 2 12 922 2 46 970 2 81 1016 3 17 1060 3 56 2813 890 2 31 940 2 65 986 3 01 1031 3 38 1074 3 77 3000 910 2 51 958 2 86 1004 3 23 1048 3 61 1090 4 01 3188 930 2 74 977 3 10 1022 3 47 1065 3 86 3375 951 2 99 997 3 35 1041 3 74 1083 4 13 3563 973 3 26 1018 3 63 1061 4 02 3750 996 3 55 1040 3 93 1082 4 34 NOTE For more information see General Fan Performance Notes Boldface indicates field supplied drive is reguired 1 Recommend using field supplied fan pulley part no KR11AZ002 and belt part no KR29AF054 580J 08 3 PHASE 7 5 TON VERTICAL SUPPLY AVAILABLE EXTERNAL STATIC PRESSURE in wg
86. een Minimum Position setpoint and 100 open With SAT from 50 F to 45 F the dampers will maintain at the Minimum Position setting With SAT below 45 F the outside air dampers will be closed When SAT rises to 48 the dampers will re open to Minimum Position setting Should 10096 outside air not be capable of satisfying the space temperature space temperature will rise until Y2 is closed The economizer control will call for compressor operation Dampers will modulate to maintain SAT at 50 to 55 concurrent with Compressor 1 operation The Low Ambient Lockout Thermostat will block compressor operation with economizer operation below 42 F outside air temperature When space temperature demand is satisfied thermostat Y1 opens the dampers will return to Minimum Damper position if indoor fan is running or fully closed if fan is off If accessory power exhaust is installed the power exhaust fan motors will be energized by the economizer control as the dampers open above the PE On setpoint and will be de energized as the dampers close below the PE On setpoint Damper movement from full closed to full open or vice versa will take between 1 1 2 and 2 1 2 minutes Heating With EconoMi er IV During Occupied mode operation indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation If indoor fan is off dampers will close During Unoccupied mode operation dampers will re
87. efault sensor dirty test results are indicated by The sensor s Dirty LED flashing The controller s Trouble LED flashing The controller s supervision relay contacts toggle The operation of a sensor s dirty test can be changed so that the controller s supervision relay is not used to indicate test results When two detectors are connected to a controller sensor dirty test operation on both sensors must be configured to operate in the same manner To Configure the Dirty Sensor Test Operation 1 Hold the test magnet where indicated on the side of the sensor housing until the sensor s Alarm LED turns on and its Dirty LED flashes twice approximately 60 seconds 2 Reset the sensor by removing the test magnet then holding it against the sensor housing again until the sensors Alarm LED turns off approximately 2 seconds Remote Station Test The remote station alarm test checks a test reset station s ability to initiate and indicate an alarm state CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern This test places the duct detector into the alarm state Unless part of the test disconnect all auxiliary eguipment from the controller before performing the test If the duct detector is connected to a fire alarm system notify authorities before performing the test proper 21 5804 SD TRK4 Remote Alarm Test Procedure 1 Turn the key s
88. efrig System Gas Heat Options Temp econo w baro relief amp CO2 D 2 Stage Compressor Al HX Enthalpy econo w baro relief F 2 Stage Compressor SS HX L Enthalpy econo w baro relief amp Motorized 2 pos damper Heat Level 125 125 000 Indoor Fan Options 150 150 000 1 Standard static option 180 180 000 2 Medium static option 224 224 000 3 High static option 250 250 000 2 Stage Cooling Coil Options Outdoor Indoor G Al Cu Al Cu Louvered Hail Guards Serial Number Format POSITION NUMBER 1 2 3 4 5 6 7 8 9 10 TYPICAL 1 2 0 9 G 1 2 3 4 5 POSITION DESIGNATES 1 2 Week of manufacture fiscal calendar 3 4 Year of manufacture 09 2009 5 Manufacturing location G ETP Texas USA 6 10 Sequential number 72 APPENDIX II PHYSICAL DATA Physical Data Cooling 7 5 12 5TONS 580J 08D F 580J 12D F 580J 14D F Refrigeration System Circuits Comp Type 2 2 Scroll 2 2 Scroll 2 2 Scroll Puron refrig R 410A charge per 9 Dm A dns 4 6 4 6 6 0 6 0 7 6 8 0 Oil A B oz 42 42 42 42 56 56 Metering Device Accutrol Accutrol Accutrol High press Trip Reset psig 630 505 630 505 630 505 Low press Trip Reset psig 54 117 54 117 54 117 Evaporator Coil Material Cu Cu Cu Coil type 3 8 RTPF 3 8 RTPF 3 8 RTPF Rows 3 15 4 15 4 15 Total Face Area ft 8 9 11 1 11 1 Conde
89. eguired The field installed version with display can be configured stand alone See section CO2 Sensor Configuration Mount the accessory sensor according to manufacturer specifications The IAO sensor should be wired to the AO and AOI terminals of the controller Adjust the DCV potentiometers to correspond to the DCV voltage output of the indoor air guality sensor at the user determined setpoint See Fig 72 2 SENSOR MAX RANGE SETTING 6000 E 5000 X amp z 4000 aS lt 800 ppm 2 3000 e 900 ppm iL SE 1000 ppm 2 m 1100 ppm 8 2000 2 1000 oc 0 2 3 4 5 6 7 8 DAMPER VOLTAGE FOR MAX VENTILATION RATE C06039 Fig 72 CO Sensor Maximum Range Settings If a separate field supplied transformer is used to power the IAQ sensor the sensor must not be grounded or the EconoMi er IV control board will be damaged When using demand ventilation the minimum damper position represents the minimum ventilation position for volatile organic compounds ventilation requirements The maximum demand ventilation position is used for fully occupied ventilation When demand ventilation control is not being used the minimum position potentiometer should be used to set the occupied ventilation position The maximum demand ventilation position should be turned fully clockwise Exhaust Setpoint Adjustment The exhaust set
90. ended to provide power on an intermittent basis for service tools lamps etc it is not intended to provide 15 amps loading for continuous duty loads such as electric heaters for overnight use Observe a 50 limit on circuit loading above 8 amps i e limit loads exceeding 8 amps to 30 minutes of operation every hour Maintenance Periodically test the GFCI receptacle by pressing the TEST button on the face of the receptacle This should cause the internal circuit of the receptacle to trip and open the receptacle Check for proper grounding wires and power line phasing if the GFCI receptacle does not trip as required Press the RESET button to clear the tripped condition Fuse On Powered Type The factory fuse is a Bussman Fusetron T 15 non renewable screw in Edison base type plug fuse Using Unit Mounted Convenience Outlets Units with unit mounted convenience outlet circuits will often require that two disconnects be opened to de energize all power to the unit Treat all units as electrically energized until the convenience outlet power is also checked and de energization is confirmed Observe National Electrical Code Article 210 Branch Circuits for use of convenience outlets SMOKE DETECTORS Smoke detectors are available as factory installed options on 580J models Smoke detectors may be specified for Supply Air only or for Return Air without or with economizer or in combination of Supply Air and Return Air Retur
91. ents on Puron refrigerant equipment CONTROL BOX COMPRESSORS C09239 Fig 2 Typical Access Panel Location Front Routine Maintenance These items should be part of a routine maintenance program to be checked every month or two until a specific schedule for each can be identified for this installation Ouarterly Inspection and 30 days after initial start Return air filter replacement Outdoor hood inlet filters cleaned Belt tension checked Belt condition checked Pulley alignment checked Fan shaft bearing locking collar tightness checked Condenser coil cleanliness checked Condensate drain checked Seasonal Maintenance These items should be checked at the beginning of each season or more often if local conditions and usage patterns dictate Air Conditioning Condenser fan motor mounting bolts tightness Compressor mounting bolts Condenser fan blade positioning Control box cleanliness and wiring condition Wire terminal tightness Refrigerant charge level Evaporator coil cleaning Evaporator blower motor amperage Heating Heat exchanger flue passageways cleanliness Gas burner condition Gas manifold pressure Heating temperature rise Economizer or Outside Air Damper Inlet filters condition Check damper travel economizer Check gear and dampers for debris and dirt Air Filters and Screens Each unit is equipped with return ai
92. er if available will be used for cooling in addition to the compressors The following conditions must be true in order for this algorithm to run ndoor Fan has been ON for at least 30 seconds Heat mode is not active and the time guard between modes equals zero If occupied and the SPT gt occupied cool setpoint plus the T56 slider offset Space Temperature reading is available If it is unoccupied and the SPT gt unoccupied cool setpoint plus the T56 slider offset The indoor fan will be turned on by the staging algorithm If economizer is available and active and economizer open gt 85 and SAT gt SAT low limit 5 F and SPT gt effective setpoint 0 5 F OR Economizer is available but not active OR Economizer is not available OAT gt DX Lockout temperature If all of the above conditions are met the compressors will be energized as reguired otherwise they will be de energized There is a fixed 3 minute minimum on time and a 5 minute off time for each compressor output and a 3 minute minimum time delay between staging up or down Any time the compressors are running the RTU MP will stage down the compressors if the SAT becomes less than the cooling low supply air setpoint After a compressor is staged off it may be started again after a normal time guard period and the supply air temperature has increased above the low supply air setpoint Economizer The Economizer dampers are used to p
93. eration All normal cooling alarms and alerts are functional NOTE Circuit A is always operated with Circuit B due to outdoor fan control on Circuit A Always test Circuit A first and leave it on to test other Circuits The Heating submenu is used to change output status for the individual heat stages gas or electric The fans and cooling service test outputs are reset to OFF for the heating service test All normal heating alarms and alerts are functional Configuration The RTU MP controller configuration points affect the unit operation and or control Review and understand the meaning and purpose of each configuration point before changing it from the factory default value The submenus containing configuration points are as follows Unit Cooling Heating Inputs Economizer IAQ Clock Set and User Password USERPW Each configuration point is described below under its according submenu See RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50H T 2T Appendix for display tables Unit Start Delay This refers to the time delay the unit will wait after power up before it pursues any specific operation Factory Default 5 sec Range 0 600 sec 64 Filter Service Hours This refers to the timer set for the Dirty Filter Alarm After the number of runtime hours set on this point is exceeded the corresponding alarm will be generated and must be manually cleared on the alarm reset screen a
94. erior and exterior finned areas must be thoroughly cleaned 5804 9 Finned surfaces should remain wet with cleaning solution for 10 minutes 10 Ensure surfaces are not allowed to dry before rinsing Reapply cleaner as needed to ensure 10 minute satur ation is achieved 11 Thoroughly rinse all surfaces with low velocity clean water using downward rinsing motion of water spray nozzle Protect fins from damage from the spray nozzle Evaporator Coil Metering Devices The metering devices are multiple fixed bore devices Acutrol swaged into the horizontal outlet tubes from the liguid header located at the entrance to each evaporator coil circuit path These are non adjustable Service requires replacing the entire liquid header assembly To check for possible blockage of one or more of these metering devices disconnect the supply fan contactor IFC coil then start the compressor and observe the frosting pattern on the face of the evaporator coil A frost pattern should develop uniformly across the face of the coil starting at each horizontal liguid tube Failure to develop frost at an outlet tube can indicate a plugged or a missing orifice Refrigerant System Pressure Access Ports There are two access ports in each compressor circuit system on the suction tube near the compressor and on the discharge tube near the compressor These are brass fittings with black plastic caps The hose connection fittings are standard
95. f the optic housing then lift the housing away from the printed circuit board 4 Gently remove dirt and debris from around the optic plate and inside the optic housing 5 Replace the optic housing and sensor cover 6 Connect power to the duct detector then perform a sensor alarm test INDICATORS Normal State The smoke detector operates in the normal state in the absence of any trouble conditions and when its sensing chamber is free of smoke In the normal state the Power LED on both the sensor and the controller are on and all other LEDs are off Alarm State The smoke detector enters the alarm state when the amount of smoke particulate in the sensor s sensing chamber exceeds the alarm threshold value See Table 3 Upon entering the alarm state The sensor s Alarm LED and the controller s Alarm LED turn on The contacts on the controller s two auxiliary relays switch positions The contacts on the controller s alarm initiation relay close The controller s remote alarm LED output is activated turned on The controller s high impedance multiple fan shutdown control line is pulled to ground Trouble state The SuperDuct duct smoke detector enters the trouble state under the following conditions A sensor s cover is removed and 20 minutes pass before it is properly secured A sensor s environmental compensation limit is reached 100 dirty A wiring fault between a sensor and the controller
96. for typical CO sensor wiring schematic 0 10VDC QSIG COM G 4 20mA ALARM COM RELAY NO 5 H G 24 VAC OR 24 VDC 21 C07134 Fig 52 Indoor Outdoor Air Quality CO2 Sensor 33ZCSENCO2 Typical Wiring Diagram To accurately monitor the quality of the air in the conditioned air space locate the sensor near a return air grille if present so it senses the concentration of CO2 leaving the space The sensor should be mounted in a location to avoid direct breath contact Do not mount the IAO sensor in drafty areas such as near supply ducts open windows fans or over heat sources Allow at least 3 ft 0 9 m between the sensor and any corner Avoid mounting the sensor where it is influenced by the supply air the sensor gives inaccurate readings if the supply air is blown directly onto the sensor or if the supply air does not have a chance to mix with the room air before it is drawn into the return airstream Wiring the Indoor Air Quality Sensor For each sensor use two 2 conductor 18 AWG American Wire Gauge twisted pair cables unshielded to connect the separate isolated 24 vac power source to the sensor and to connect the sensor to the control board terminals 41 5804 To connect the sensor to the control identify the positive 4 to 20 mA and ground SIG COM terminals on the sensor See Fig 52 Connect the 4 20 mA termi
97. fter the maintenance has been completed The timer will then begin counting its runtime again for the next maintenance interval Factory Default 600 hr NOTE Setting this configuration timer to 0 disables the alarm Supply Fan Service Hours This refers to the timer set for the Supply Fan Runtime Alarm After the number of runtime hours set on this point is exceeded the corresponding alarm will be generated and must be manually cleared on the alarm reset screen after the maintenance has been completed The timer will then begin counting its runtime again for the next maintenance interval Factory Default 0 hr NOTE Setting this configuration timer to 0 disables the alarm Compressor1 Service Hours This refers to the timer set for the Compressor 1 Runtime Alarm After the number of runtime hours set on this point is exceeded the corresponding alarm will be generated and must be manually cleared on the alarm reset screen after the maintenance has been completed The timer will then begin counting its runtime again for the next maintenance interval Factory Default 0 hr NOTE Setting this configuration timer to 0 disables the alarm Compressor2 Service Hours This refers to the timer set for the Compressor 2 Runtime Alarm After the number of hours set on this point is exceeded the corresponding alarm will be generated and must be manually cleared on the alarm rest screen after the maintenance has been completed
98. gs CO VENTILATION OPTIONAL RELAY SETTING EQUIPMENT OUTPUT RATE ANALOG CONTROL RELAY SETPOINT HYSTERESIS OUTPUT RANGE cfm Person ppm ppm ppm 0 10V 1 Proportional Any 4 20mA 0 2000 1000 50 Interface w Standard 2 10V 2 Building Control System Proportional Any 7 20mA 0 2000 1000 50 0 10V 3 Exponential Any 4 20mA 0 2000 1100 50 0 10V 4 Proportional 15 4 20 0 1100 1100 50 0 10V 5 Proportional 20 4 20mA 0 900 900 50 Economizer 0 10V 6 Exponential 15 4 20 0 1100 1100 50 0 10V 7 Exponential 20 4 20 0 900 900 50 8 Health amp Safet P tional 0 9999 5000 500 ea afety roportional 4 20mA Parking Air Intakes 0 10V 9 Loading Docks Proportional 4 20 0 2000 700 50 57 5804 Table 24 EconoMi er IV Sensor Usage ECONOMISER IV WITH OUTDOOR AIR DRY APPLICATION BULB SENSOR Accessories Reguired Outdoor Air None The outdoor air dry bulb sensor is Dry Bulb factory installed Differential Dry Bulb CRTEMPSNOO2A00 Single Enthalpy HH57AC078 Differential Enthalpy HH57AC078 and CRENTDIFO04A00 for DCV Control using a Wall Mounted Sensor for DCV Control using 332 5 2 and O DuctMounted 33ZCASPCO2 CRCBDIOX005A00 T CO Sensor CRENTDIF004A00 and CRTEMPSNO02A00 accessories are use
99. he active protocol and baud rate will be shown in this section 2 Verify that the BAS and controller are set for 9600 baud The baud rate of the controller is set via SW3 switches 1 and 2 The baud rate can also be verified via the BACview by obtaining a Modstat See Fig 59 3 Verify that the BAS is configured to speak 2 wire EIA 485 to the controller The BAS may have to configure jumper or DIP switches on their end 4 Verify that the BAS and the controller have the same communication settings 8 data bits No Parity and 1 stop bit 5 Verify that the controller has a unique N2 slave address on the N2 bus The controller s N2 slave address is set by its rotary address switches 6 Verify proper wiring between the BAS and the controller 7 Verify that the BAS is reading or writing to the proper network point addresses on the controller Download the latest points list for the controller to verify 8 Verify that the BAS is sending his requests to the proper slave address of our controller NOTE See RTU MP 3rd Party Integration Guide or alternatively RTU MP 3rd Party Integration Guide or alternatively RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50H T 2T Appendix for N2 Protocol Conformance Statement ECONOMISER SYSTEMS The 580J units may be equipped with a factory installed or accessory field installed economizer system Two types are available with a logic control system EconoM
100. he bottom of the page and there is a section entitled Network Communications The active protocol and baud rate will be shown in this section 2 Verify that the BAS and controller are set for the same baud rate The baud rate of the controller is set via SW3 switches 1 and 2 The baud rate can also be verified via the BACview by obtaining a Modstat See Fig 59 3 Verify that the BAS is configured to speak 2 wire EIA 485 to the controller The BAS may have to configure jumper or DIP switches on their end 4 Verify that the BAS and the controller have the same communication settings 8 data bits No Parity and 1 stop bit 5 Verify that the controller has a unique MAC address on the MS TP bus The controller s MS TP MAC address is set by its rotary address switches 6 Verify proper wiring between the BAS and the controller 7 Verify that the BAS is reading or writing to the proper BACnet objects in the controller Download the latest points list for the controller to verify 8 Verify that the BAS is sending his requests to the proper MS TP MAC address of our controller 9 Present the BAS company with a copy of our controller s BACnet PICS so that they know which BACnet commands are supported 47 5804 Device Instance 0160001 1 PRGs loaded 1 PRGs running Module status Firmware sections validated in flash memory v2 06 001 72092050 Boot16 H RTU MP DRIVER Reset counters 11 Power failures
101. he damper position is controlled directly by the RTU MP control EconoMi er 2 has no internal logic device Outdoor air management functions can be enhanced with field installation of these accessory control devices Enthalpy control outdoor air or differential sensors Space CO sensor Outdoor air sensor Field Connections Field connections for accessory sensors and input devices are made the RTU MP at plugs 72 J4 J5 111 and J20 field control wiring that connects to the RTU MP must be routed through the raceway built into the corner post as shown in Fig 37 The raceway provides the UL reguired clearance between high and low voltage wiring Pass the control wires through the hole provided in the corner post then feed the wires thorough the raceway to the RTU MP Connect to the wires to the removable Phoenix connectors and then reconnect the connectors to the board Space Temperature SPT Sensors A field supplied Bryant space temperature sensor is reguired with the RTU MP to monitor space temperature There are 3 sensors available for this application 33ZCT55SPT space temperature sensor with override button e 33ZCT56SPT space temperature sensor with override button and setpoint adjustment e 33ZCT59SPT space temperature sensor with LCD liguid crystal display screen override button and setpoint adjustment Use 20 gauge wire to connect the sensor to the controller The wire is suitable for
102. his value during heating the heat stages will begin to decrease until the SAT has dropped below this value Factory Default 120 F Range 95 150 Heating Lockout Temp This defines the maximum outdoor air temperature that heating mode can be enabled and run If the OAT rises above this threshold during heating then heating will not be allowed Factory Default 65 F Range 49 95 Inputs NOTE For installation of inputs and field installed accessories refer to the appropriate sections Input 3 This input is a discrete input and can be configured to be one of five different inputs No Function Compressor Safety Fan Status Filter Status or Remote Occupancy This input can also be configured to be either Normally Open N O or Normally Closed N C Input 3 is factory wired to pin J1 2 Field accessories get wired to its parallel pin J5 5 Do not connect inputs to both locations one function per input Factory Default 2 Compressor Safety and N O NOTE Compressor Safety input comes from the CLO board J1 2 is always factory wired to TB1 8 X terminal on the unit If the unit has a CLO board do not configure input 3 for anything but Compressor Safety 65 5804 Input 5 This input is a discrete input and can be configured to be one of five different inputs No Function Fire Shutdown Fan Status Filter Status or Remote Occupancy This input can also be configured to be either Normally Open N O or Normall
103. i er IV and without a control system EconoMi er2 for use with external control systems See Fig 60 and Fig 61 for component locations on each type See Fig 62 and Fig 63 for economizer section wiring diagrams Both EconoMi ers use direct drive damper actuators ECONOMISER IV CONTROLLER WIRING HARNESS ACTUATOR HIDDEN d LOW TEMPERATURE COMPRESSOR LOCKOUT SWITCH OUTSIDE AIR TEMPERATURE SENSOR OPERATING LOCATION C07367 Fig 60 EconoMi er IV Component Locations OUTDOOR AIR HOOD HOOD SHIPPING BRACKET GEAR DRIVEN BAROMETRIC DAMPER RELIEF DAMPER C06022 Fig 61 EconoMi er2 Component Locations 50 ECONOMIZER FIOP ACCESSORY POTENTIOMETER DEFAULTS SETTINGS MIDDLE POWER EXH L MINIMUM POS FULLY CLOSED DCV MAX MIDDLE PNK DCV SET MIDDLE ENTHALPY C SETTING VIO r BLK RED RED M XH TRI ECONOMIZER ACCESSORY 1 e MOTOR REMOTE MIN POSITION ae aW a Bru P M 135 Ohm EXH
104. ic Option Medium Static Option 3438 685 1 12 751 1 32 813 1 54 871 1 76 927 1 99 3750 797 1 63 910 2 10 963 2 35 4063 951 2 49 1001 2 75 4375 993 2 94 1041 3 21 4688 3 44 5000 5313 5625 5938 6250 Available External Static Pressure in wg 1 2 1 4 1 6 1 8 2 0 Medium Static Option High Static Option 3438 981 2 23 1032 2 47 1082 2 72 1130 2 97 1177 3 23 3750 1063 2 86 1157 3 39 1202 3 66 4063 1186 3 85 1230 4 14 4375 4 37 4688 5000 5313 5625 5938 6250 NOTE For more information see General Fan Performance Notes Boldface indicates field supplied drive is reguired General fan performance notes 1 2 Interpolation is permissible Do not extrapolate External static pressure is the static pressure difference between the return duct and the supply duct plus the static pressure caused by any FIOPs or accessories Tabular data accounts for pressure loss due to clean filters unit casing and wet coils Factory options and accessories may add static pressure losses Selection software is available through your salesperson to help you select the best motor drive combination for your application The Fan Performance tables offer motor drive recommendations In cases when two motor drive combinat
105. ifference between the outdoor and return air temperatures To determine the minimum position setting perform the following procedure 1 Calculate the appropriate mixed air temperature using the following formula OA TR x RA To Outdoor Air Temperature OA Percent of Outdoor Air Tg Return Air Temperature RA Percent of Return Air Mixed Air Temperature As an example if local codes require 10 outdoor air during occupied conditions outdoor air temperature is 60 and return air temperature is 75 60 x 10 75 x 90 73 5 2 Disconnect the supply air sensor from terminals T and T1 3 Ensure that the factory installed jumper is in place across terminals P and Pl If remote damper positioning is being used make sure that the terminals are wired according to Fig 62 and that the minimum position potentiometer is turned fully clockwise 4 Connect 24 vac across terminals TR and TR1 5 Carefully adjust the minimum position potentiometer until the measured mixed air temperature matches the calculated value 6 Reconnect the supply air sensor to terminals T and Remote control of the EconoMi er damper is desirable when requiring additional temporary ventilation If a field supplied remote potentiometer Honeywell part number S963B1128 is wired to the EconoMi er IV controller the minimum position of the damper can be controlled from a remote location To control the minimum
106. ions at J5 42 Remote Occupancy The remote occupancy accessory is a field installed accessory This accessory overrides the unoccupied mode and puts the unit in occupied mode When installing this accessory the unit must be configured for remote occupancy by setting MENU Config Inputs input 3 5 8 or 9 to Remote Occupancy and normally open N O or normally closed N C Also set MENU Schedules occupancy source to DI on off Input 8 or 9 is recommended for easy of installation Refer to Fig 42 and Table 15 for wire terminations at J5 Power Exhaust output Connect the accessory Power Exhaust contactor coil s per Fig 56 Power Exhaust LCTB C08464 Fig 56 RTU MP Power Exhaust Connections Space Relative Humidity Sensor Space Relative Humidity Sensor The RH sensor is not used with 580J models at this time Communication Wiring Protocols General Protocols are the communication languages spoken by control devices The main purpose of a protocol is to communicate information in the most efficient method possible Different protocols exist to provide different kinds of information for different applications In the BAS application many different protocols are used depending on manufacturer Protocols do not change the function of a controller just make the front end user different The RTU MP can be set to communicate on four different protocols BACnet Modbus N2 and LonWorks Switch 3
107. ions would work Bryant recommended the lower horsepower option For information on the electrical properties of Bryant motors please see the Electrical information section of this book For more information on the performance limits of Bryant motors see the application data section of this book 78 APPENDIX FAN PERFORMANCE cont Pulley Adjustment UNIT MOTOR DRIVE MOTOR PULLEY TURNS OPEN COMBO 00 05 10 15 20 25 30 35 40 45 50 Standard Static 747 721 695 670 644 618 592 566 541 515 489 2 8 Medium Static 949 927 906 884 863 841 819 798 776 755 733 High Static 1102 1083 1063 1044 1025 1006 986 967 948 928 909 Standard Static 838 813 789 764 739 715 690 665 640 616 591 Medium Static 1084 1059 1035 1010 986 961 936 912 887 863 838 High Static 1240 1218 1196 1175 1153 1131 1109 1087 1066 1044 1022 Standard Static 838 813 789 764 739 715 690 665 640 616 591 8 Medium Static 1084 1059 1035 1010 986 961 936 912 887 863 838 a High Static 1240 1218 1196 1175 1153 1131 1109 1087 1066 1044 1022 NOTE Do not adjust pulley further than 5 turns open EM _ Factory settings 79 5804 ELECTRICAL INFORMATION
108. iring to normal after completing troubleshooting Single Enthalpy To check single enthalpy 1 Make sure EconoMi er IV preparation procedure has been performed 2 Set the enthalpy potentiometer to A fully CCW The Free Cool LED should be lit 3 Set the enthalpy potentiometer to D fully CW The Free Cool LED should turn off 4 Return EconoMi er IV settings and wiring to normal after completing troubleshooting DCV Demand Controlled Ventilation and Power Exhaust To check DCV and Power Exhaust 1 Make sure EconoMi er IV preparation procedure has been performed 2 Ensure terminals AQ and 1 are open The LED for both DCV and Exhaust should be off The actuator should be fully closed 3 Connect a 9 v battery to positive node and AO1 negative node The LED for both DCV and Exhaust should turn on The actuator should drive to between 90 and 95 open 4 Turn the Exhaust potentiometer CW until the Exhaust LED turns off The LED should turn off when the potentiometer is approximately 90 The actuator should remain in position 58 5 Turn the DCV setpoint potentiometer CW until the DCV LED turns off The DCV LED should turn off when the potentiometer is approximately 9 v The actuator should drive fully closed Turn the DCV and Exhaust potentiometers CCW until the Exhaust LED turns on The exhaust contacts will close 30 to 120 seconds after the Exhaust LED turns on Return EconoMi er IV settings
109. is detected An internal sensor fault is detected upon entering the trouble state The contacts on the controller s supervisory relay switch positions See Fig 29 f a sensor trouble the sensor s Trouble LED the controller s Trouble LED turn on If 100 dirty the sensor s Dirty LED turns on and the controller s Trouble LED flashes continuously If a wiring fault between a sensor and the controller the controller s Trouble LED turns on but not the sensor s Test reset switch C07298 Fig 29 Controller Assembly NOTE All troubles are latched by the duct smoke detector The trouble condition must be cleared and then the duct smoke detector must be reset in order to restore it to the normal state Resetting Alarm and Trouble Condition Trips Manual reset is required to restore smoke detector systems to Normal operation For installations using two sensors the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition Check each sensor for Alarm or Trouble status indicated by LED Clear the condition that has generated the trip at this sensor Then reset the sensor by pressing and holding the reset button on the side for 2 seconds Verify that the sensor s Alarm and Trouble LEDs are now off At the controller clear its Alarm or Trouble state by pressing and holding the manual reset button on the front cover for 2 seconds Verify that the controller s Alarm and Trouble L
110. it See Fig 36 9 To reinstall reverse the procedure outlined above Cleaning and Adjustment 1 Remove burner rack from unit as described in Re moval and Replacement of Gas Train section 2 Inspect burners if dirty remove burners from rack Mark each burner to identify its position before re moving from the rack 3 Use a soft brush to clean burners and cross over port as reguired 4 Adjust spark gap See Fig 38 5 If factory orifice has been removed check that each orifice is tight at its threads into the manifold pipe and that orifice projection does not exceed maximum valve See Fig 35 6 Reinstall burners on rack in the same locations as factory installed The outside crossover flame re gions of the outermost burners are pinched off to pre vent excessive gas flow from the side of the burner assembly If the pinched crossovers are installed between two burners the flame will not ignite prop erly INTEGRATED GAS UNIT RACEWAY CONTROLLER IGC HOLE IN END PANEL HIDDEN C08454 Fig 37 Unit Control Box IGC Location 7 Reinstall burner rack as described in Removal and Replacement of Gas Train section above Gas Valve unit sizes are eguipped with 2 stage gas valves See Fig 39 for locations of adjustment screws and features on the gas valves To adjust gas valve pressure settings IMPORTANT Leak check all gas connections including the main service con
111. lity to compensate for gradual environmental changes A sensor that can no longer compensate for environmental changes is considered 10096 dirty and reguires cleaning or replacing You must use a field provided SD MAG test magnet to initiate a sensor dirty test The sensor s Dirty LED indicates the results of the dirty test as shown in Table 2 CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern Holding the test magnet against the sensor housing for more than seven seconds will put the duct detector into the alarm state and activate all automatic alarm responses Table 2 Dirty LED Test FLASHES DESCRIPTION 1 0 2596 dirty Typical of a newly installed detector 2 25 50 dirty 3 51 7596 dirty 4 76 9996 dirty Dirty Sensor Test Procedure 1 Hold the test magnet where indicated on the side of the sensor housing for two seconds 2 Verify that the sensor s Dirty LED flashes CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern Changing the dirty sensor test operation will put the detector into the alarm state and activate all automatic alarm responses Before changing dirty sensor test operation disconnect all auxiliary eguipment from the controller and notify the proper authorities if connected to a fire alarm system Changing the Dirty Sensor Test By d
112. main closed unless a DCV demand is received When the room temperature calls for heat W1 closes the heating controls are energized as described in Heating Unit Without Economizer above Demand Controlled Ventilation If a field installed sensor is connected to the Economize IV control a Demand Controlled Ventilation strategy will operate automatically As the CO2 level in the space increases above the setpoint on the EconoMi er IV controller the minimum position of the dampers will be increased proportionally until the Maximum Ventilation setting is reached As the space CO level decreases because of the increase in fresh air the outdoor damper will follow the higher demand condition from the DCV mode or from the free cooling mode DCV operation is available in Occupied and Unoccupied periods with EconoMi er IV However a control modification will be reguired on the 580J unit to implement the Unoccupied period function Supplemental Controls Compressor Lockout Relay CLO The CLO is available as factory installed option or as field installed accessory Each compressor has a The CLO compares the demand for compressor operation via a 24 v input from Y at CLO terminal 2 to operation of the compressor determined via compressor current signal input at the CLO s current transformer loop if the compressor current signal is lost while the demand input still exists the CLO will trip open and prevent the
113. mation Sticker on the back of the main control module board RMP _ These first three digits are unique to RTU MP and are used as an identifier Serial No RMPYMxxxxN YM _ These two digits identify the last digit of the year and month in hex A 10 Oct Bar Coded amp Typed Number of manufacture 74 would represent a date of manufacture of April 2007 _ These four digits represent the sequential number of units produced for a given product for the mentioned manufacturing time period N _ This final digit represents the decade and toggles between N and M every ten years Table 20 Basic Protocol Troubleshooting Corrective action Verify and correct switch settings Cycle power to RTU MP after changing switch settings Verify has correct power supply Possible bad driver on board Possible cause Incorrect settings on SW1 SW2 and SW3 Problem No communication with 3rd party vendor RS485 Port has no voltage output check with RTU MP disconnected from RS485 communication bus Bacnet 9600 19 2K 01 to 045vdc Check RS485 bus for external before reconnecting to the bus Voltage shorts or grounding before reconnecting to the bus Bacnet 38 4K 06 to 09vdc Bacnet 76 8K 1vdc Modbus 9600 76 8K 124vdc N2 2 9600 124vdc Verify devices are daisy chained and repeaters and bias termina
114. modifying this unit for installation at elevations above 2000 ft 610 m Gas line pressure entering the unit s main gas valve must be within specified ranges See Table 5 Adjust unit gas regulator valve as reguired or consult local gas utility Table 5 Natural Gas Supply Line Pressure Ranges UNIT MODEL UNIT SIZE MIN MAX 4 0 in wg 13 0 in wg Pa 2 996 Pa 8240 Pa Manifold pressure is factory adjusted for NG fuel use See Table 6 Adjust as required to obtain best flame characteristic Table 6 Natural Gas Manifold Pressure Ranges UNIT UNIT HIGH LOW MODEL SIZE FIRE FIRE RANGE 3 5 in wg 1 7 in wg 2 0 5 0 in wg Hi 580 Al 423Pa 498 1245 Pa Liguid Propane Accessory packages are available for field installation that will convert the 580J unit to operate with Liguid Propane LP fuels These kits include new orifice spuds new springs for gas valves and a supply line low pressure switch See section on Orifice Replacement for details on orifice size selections Fuel line pressure entering unit gas valve must remain within specified range See Table 7 25 5804 Table 7 Liguid Supply Line Pressure Ranges UNIT MODEL UNIT SIZE MIN MAX 11 0 in wg 13 0 in wg A 2740 Pa 3240 Pa Manifold pressure for LP fuel use must be adjusted to specified range See Table
115. n Air smoke detectors are arranged for vertical return configurations only All components necessary for operation are factory provided and mounted The unit is factory configured for immediate smoke detector shutdown operation additional wiring or modifications to unit terminal board may be necessary to complete the unit and smoke detector configuration to meet project requirements System The smoke detector system consists of a four wire controller and one or two sensors Its primary function is to shut down the rooftop unit in order to prevent smoke from circulating throughout the building It is not to be used as a life saving device Controller The controller includes a controller housing a printed circuit board and a clear plastic cover See Fig 19 The controller can be connected to one or two compatible duct smoke sensors The clear plastic cover is secured to the housing with a single captive screw for easy access to the wiring terminals The controller has three LEDs for Power Trouble and Alarm and a manual test reset button on the cover face 17 5804 Duct smoke sensor controller Conduit nuts supplied by installer S ES MUI Conduit support plate Ores _ s NL N N KS Ni Cover gasket NON ordering option SS 3 lt Fastener 2X Controller housing _ and electronics 8 Conduit couplings supplied by i
116. n the smoke detector senses smoke The Unit Status will be Shutdown and the System Mode will be Disable unit operations stop immediately and will not restart until the alarm automatically clears If there is not a smoke detector installed or the smoke detector did not trip check input configurations Space Temp Sensor Failure This alarm occurs if the space sensor wired to the RTU MP is disconnected or shorted for more then 10 seconds When this occurs the Unit Status will be Shutdown and the System Mode will be Run Sensor sensor connections wiring board connection and configurations should be checked for faults or errors Alarm will reset automatically when cause is fixed SAT Sensor Alarm This alarm occurs immediately when the supply air temperature sensor wired to the RTU MP is disconnected or shorted When this occurs the Unit Status will be Shutdown and the System Mode will be Run Sensor sensor connections wiring board connection and configurations should be checked for faults or errors Alarm will reset automatically when cause is fixed Switch Configuration Alarm This occurs if more than one binary input inputs 3 5 8 and 9 is configured for the same function When this happens the two inputs or more configured wrong will be disabled as an inputs This alarm will automatically be cleared when configuration is corrected An example of this would be Input 3 Compressor Safety input 5 Fan Status input 8
117. n time exceeded filter Dirty Filter Alarm filter Alarm Generated a switch configuration wrong without switch Alarm Generated c 7 More than binary input is configured for the sw_cfg_alarm Eu red swit h AU same purpose More then one discrete input is eine y configured to provide the same function Misconfigured Analog an alarm e Configure More then one analog input is configured to Input rez analog inputs correctly provide the same function Alarm Generated Economizer and Low Faulty shorted or open thermistor caused by OAT Sensor Alarm gata ambient DX cooling wiring error or loose connection lockout disabled Generated Sensor reading is out of range Bad sensor bad Space RH Sensor Alarm sprh_alarm eid AR Automatic wiring or sensor configured incorrectly Outdoor RH Sensor Sensor reading is out of range Bad sensor bad Alarm Aarm Generated wiring or sensor configured incorrectly High Space Humidity sprh hi Alarm Generated Automatic UL then 10 Low Space Humidity sprh_lo Alarm Generated Automatic IRH is less then 3596 for more then 10 minutes Alarm Generated Disables IAO sei Sensor reading is out of range Bad sensor bad Sensor Alarm iaq_alarm eE NM moves Automati wiring or sensor configured incorrectly to minimum position Alarm Generated Set 3 Sensor reading is out of range Bad sensor bad GRAA to 40
118. nal to RTU MP J4 2 and connect the SIG COM terminal to RTU MP J4 3 See Fig 53 IAG Sensor MARC 04 3 24 C08462 Fig 53 RTU MP Indoor CO Sensor 337 2 Connections Outdoor Air Quality Sensor 337 2 plus Weatherproof Enclosure The outdoor air CO sensor is designed to monitor carbon dioxide CO levels in the outside ventilation air and interface with the ventilation damper in an HVAC system The OAQ sensor is packaged with an outdoor cover See Fig 54 The outdoor air sensor must be located in the economizer outside air hood 4 41 4 e 33 4 6 1 2 COVER REMOVED SIDE VIEW C07135 Fig 54 Outdoor Air Ouality Sensor Cover Wiring the Outdoor Air CO Sensor A dedicated power supply is required for this sensor A two wire cable is required to wire the dedicated power supply for the sensor The two wires should be connected to the power supply and terminals 1 and 2 To connect the sensor to the control identify the positive 4 to 20 mA and ground SIG COM terminals on the OAQ sensor See Fig 52 Connect the 4 to 20 mA terminal to RTU MP J4 5 Connect the SIG COM terminal to RTU MP 14 6 See Fig 55 OAQ Sensor RH Sensor 24 VAC C08463 Fig 55 RTU MP Outdoor CO Sensor 33ZCSENCO2 Connections On 580J units eguipped with factory installed Smoke Detector s the smoke detector controller im
119. nd discharge pressure levels should now move to their normal start up levels NOTE When the compressor is rotating in the wrong direction the unit makes an elevated level of noise and does not provide cooling Filter Drier Replace whenever refrigerant system is exposed to atmosphere Only use factory specified liquid line filter driers with working pressures no less than 650 psig Do not install a suction line filter drier in liquid line A liquid line filter drier designed for use with Puron refrigerant is required on every unit Condenser Fan Adjustment 08D 12D F size 1 Shut off unit power supply Install lockout tag 2 Remove condenser fan assembly grille motor and fan Loosen fan hub setscrews Adjust fan height as shown in Fig 14 Tighten setscrews to 84 in lbs 9 5 N m Replace condenser fan assembly ON RU 0 0 0 03 C08448 Fig 14 Condenser Fan Adjustment 08D 12D F Condenser Fan Adjustment 14D F size 1 Shut off unit power supply Install lockout tag Remove condenser fan grille Loosen fan hub setscrews Adjust fan height as shown in Fig 15 Tighten setscrews to 84 in lbs 9 5 N m Replace fan grille RU 2 C09094 Fig 15 Condenser Fan Adjustment 14D F Troubleshooting C
120. nd torque the cap screw to 65 70 in lb 7 4 7 9 Nm See Fig 7 C08121 Fig 7 Tightening Locking Collar Motor When replacing the motor also replace the external tooth lock washer star washer under the motor mounting base this is part of the motor grounding system Ensure the teeth on the lock washer are in contact with the motor s painted base Tighten motor mounting bolts to 120 12 in lbs 13 5 1 3 Nm 5804 Changing the Fan Wheel Speed by Changing Pulleys The horsepower rating of the belt is primarily dictated by the pitch diameter of the smaller pulley in the drive system typically the motor pulley in these units Do not install a replacement motor pulley with a smaller pitch diameter than provided on the original factory pulley Change fan wheel speed by changing the fan pulley larger pitch diameter to reduce wheel speed smaller pitch diameter to increase wheel speed or select a new system both pulleys and matching belt s Before changing pulleys to increase fan wheel speed check the fan performance at the target speed and airflow rate to determine new motor loading bhp Use the fan performance tables or use the Packaged Rooftop Builder software program Confirm that the motor in this unit is capable of operating at the new operating condition Fan shaft loading increases dramatically as wheel speed is increased To reduce vibration replace the motor s adjustable pitch pulley with a fixed
121. ne EconoMi er IV use The controller selects the lower enthalpy air return or outdoor for cooling For example when the outdoor air has a lower enthalpy than the return air the EconoMi er IV opens to bring in outdoor air for free cooling Replace the standard outside air dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location See Fig 60 Mount the return air enthalpy sensor in the return air duct See Fig 69 Wiring is provided in the EconoMi er IV wiring harness See Fig 62 The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi er IV controller When using this mode of changeover control turn the enthalpy setpoint potentiometer fully clockwise to the D setting Indoor Air Quality IAQ Sensor Input The IAQ input can be used for demand control ventilation control based on the level of CO2 measured in the space or return air duct There is both a factory installed FIOP option sensor 8001B with no display which is mounted on the side of the EconoMi er and a field installed CO option sensor 8002 with display which is mounted on the return air duct While performing the same function they differ in their ability to be configured The FIOP version is preset and reguires no changes in most applications If a configuration change is required service kit UIP2072 software CD cables and instructions and a laptop PC are r
122. nection gas valve gas spuds and manifold pipe plug All leaks must be repaired before firing unit Check Unit Operation and Make Necessary Adjustments NOTE Gas supply pressure at gas valve inlet must be within specified ranges for fuel type and unit size See Table 5 6 7 and 8 1 Remove manifold pressure tap plug from manifold and connect pressure gauge or manometer See Fig 36 2 Turn on electrical supply 95 Turn on unit main gas valve 4 Set room thermostat to call for heat Verify high stage heat operation before attempting to adjust mani fold pressure 5 When main burners ignite check all fittings mani fold and orifices for leaks 6 Adjust high stage pressure to specified setting by turning the plastic adjustment screw clockwise to in crease pressure counter clockwise to decrease pres sure 7 Set room thermostat to call for low stage heat Adjust low stage pressure to specified setting 8 Replace regulator cover screw s when finished 9 With burner access panel removed observe unit heat ing operation in both high stage and low stage opera tion Observe burner flames to see if they are blue in appearance and that the flames are approximately the same for each burner 10 Turn off unit remove pressure manometer and re place the 1 8 in pipe fitting on the gas manifold See Fig 36 Limit Switch Remove blower access panel Limit switch is located on the fan deck See Fig 31
123. noccupied mode Whenever the remote occupancy switch is closed during DI On Off schedule type or if occupancy is forced occupied by the BAS during BAS On Off schedule type When transitioning from unoccupied to occupied there will be a configured time delay of 5 to 600 seconds before starting the fan The fan will continue to run as long as compressors heating stages or the dehumidification relays are on when transitioning from occupied to unoccupied with the exception of Shutdown mode If Fire Shutdown safety chain SAT alarm or SPT alarm are active the fan will be shutdown immediately regardless of the occupancy state or demand The RTU MP has an optional Supply Fan Status input to provide proof of airflow If this is enabled the point will look for a contact closure whenever the Supply Fan Relay is on If it is not enabled then it will always be the same state as the Supply Fan Relay The cooling economizer heating dehumidification CO2 and power exhaust routines will use this input point for fan status 69 5804 Cooling The compressor outputs are controlled by the Cooling Control PID Loop and Cooling Stages Capacity algorithm They will be used to calculate the desired number of stages needed to satisfy the space by comparing the Space Temperature SPT to the Occupied Cool Setpoint plus the T56 slider offset when occupied and the Unoccupied Cool Setpoint UCSP plus the T56 slider offset if unoccupied The economiz
124. nsate Drain Conn Size 3 4 3 4 3 4 Evaporator Fan and Motor 2 Motor Qty Drive Type 1 Belt 1 Belt 1 Belt 1 7 2 4 2 9 55 RPM Range 489 747 591 838 652 843 52 Motor Frame Size 56 56 56 8 Fan Qty 1 Centrifugal 1 Centrifugal 1 Centrifugal o Fan Diameter in 15x15 15x15 15x15 o Motor Gty Drive Type 1 Belt 1 Belt 1 Belt S Max BHP 2 9 3 7 3 7 28 RPM Range 733 949 838 1084 838 1084 56 Motor Frame Size 56 56 56 Bo Fan Qty Type 1 Centrifugal 1 Centrifugal 1 Centrifugal gt Fan Diameter in 15x15 15x15 15x15 Motor Gty Drive Type 1 Belt 1 Belt 1 Belt lt a Max BHP 47 47 4 7 a 8 RPM Range 909 1102 1022 1240 1022 1240 145 145 145 T Fan Qty Type 1 Centrifugal 1 Centrifugal 1 Centrifugal Fan Diameter in 15x15 15x15 15x15 Condenser Coil Material Al Al Al Al Al Coil type NOVATION NOVATION NOVATION Rows FPI 1 20 1 20 2 20 Total Face Area ft 20 5 25 1 25 1 Condenser fan motor Qty Motor Drive Type 2 Direct 2 Direct 1 Direct Motor HP RPM 1 4 1100 1 4 1100 1 1175 Fan diameter in 22 22 30 Filters RA Filter Size in 4 16x20x2 4 20x20x2 4 20x20x2 OA inlet screen Size in 1 20x24x1 1 20x24x1 1 20x24x1 AI Al Aluminum Tube Aluminum Fin Al Copper Tube Aluminum Fin RTPF Round Tube Plate Fin 575V motor utilizes 3 7 73 5804 APPENDIX II
125. nstaller S Controller cover Trouble Power Test reset switch C08208 Fig 19 Controller Assembly Sensor The sensor includes a plastic housing a printed circuit board a clear plastic cover a sampling tube inlet and an exhaust tube See Fig 20 The sampling tube when used and exhaust tube are attached during installation The sampling tube varies in length depending on the size of the rooftop unit The clear plastic cover permits visual inspections without having to disassemble the sensor The cover attaches to the sensor housing using four captive screws and forms an airtight chamber around the sensing electronics Each sensor includes a harness with an RJ45 terminal for connecting to the controller Each sensor has four LEDs Power Trouble Alarm and Dirty and a manual test reset button on the left side of the housing Air is introduced to the duct smoke detector sensor s sensing chamber through a sampling tube that extends into the HVAC duct and is directed back into the ventilation system through a shorter exhaust tube The difference in air pressure between the two tubes pulls the sampled air through the sensing chamber When a sufficient amount of smoke is detected in the sensing chamber the sensor signals an alarm state and the controller automatically takes the appropriate action to shut down fans and blowers change over air handling systems notify the fire alarm control
126. o GRA conductor Highlight E GRA lead at Smoke Alarm input on LCTB provides 24 v signal to FIOP DDC control RTU MP The 24 v signal is conveyed to RTU MP s J1 10 input terminal This signal initiates the FSD sequence by the RTU MP control FSD status is reported to connected BAS network Using Remote Logic Five conductors are provided for field use see Highlight F for additional annunciation functions HKRNKA 1XA for discussions on additional control features of these smoke detectors including multiple unit coordination See Fig 26 Sensor and Controller Tests Sensor Alarm Test The sensor alarm test checks a sensor s ability to signal an alarm state This test requires that you use a field provided SD MAG test magnet CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern This test places the duct detector into the alarm state Unless part of the test disconnect all auxiliary eguipment from the controller before performing the test If the duct detector is connected to a fire alarm system notify authorities before performing the test proper Sensor Alarm Test Procedure 1 Hold the test magnet where indicated on the side of the sensor housing for seven seconds 2 Verify that the sensor s Alarm LED turns on 3 Reset the sensor by holding the test magnet against the sensor housing for two seconds 4 Verify that the sensor s Alarm
127. om normal operation Outdoor air temperature limits for cooling circuits economizer and heating are ignored Normal compressor time guards and other staging delays are ignored The status of Alarms except Fire and Safety chain is ignored but all alerts and alarms are still broadcasted on the network Field Service Test can be turned ON OFF at the unit display or from the network Once turned ON other entries may be made with the display or through the network To turn Field Service Test on change the value of Test Mode to ON to turn Field Service Test off change the value of Test Mode to OFF NOTE Service Test mode is password protected when accessing from the display Depending on the unit model factory installed options and field installed accessories some of the Field Service Test functions may not apply The independent outputs IndpOutputs submenu is used to change output status for the supply fan economizer and Power Exhaust These independent outputs can operate simultaneously with other Field Service Test modes All outputs return to normal operation when Field Service Test is turned off The Cooling submenu is used to change output status for the individual compressors and the dehumidification relay Compressor starts are not staggered The fans and heating service test outputs are reset to OFF for the cooling service test Indoor fans and outdoor fans are controlled normally to maintain proper unit op
128. ondition is suspected Flue Gas Passageways To inspect the flue collector box and upper areas of the heat exchanger 1 Remove the combustion blower wheel and motor as sembly according to directions in Combustion Air Blower section See Fig 34 2 Remove the flue cover to inspect the heat exchanger 3 Clean all surfaces as reguired using a wire brush Combustion Air Blower Clean periodically to assure proper airflow and heating efficiency Inspect blower wheel every fall and periodically during heating season For the first heating season inspect blower wheel bi monthly to determine proper cleaning freguency To access burner section slide the sliding burner partition out of the unit To inspect blower wheel shine a flashlight into draft hood opening If cleaning is reguired remove motor and wheel as follows 1 Slide burner access panel out 2 Remove the 7 screws that attach induced draft motor housing to vestibule plate See Fig 34 3 The blower wheel can be cleaned at this point If ad ditional cleaning is reguired continue with Steps 4 and 5 4 To remove blower from the motor shaft remove 2 setscrews 5 To remove motor remove the 4 screws that hold the motor to mounting plate Remove the motor cooling fan by removing one setscrew Then remove nuts that hold motor to mounting plate 6 To reinstall reverse the procedure outlined above 26 HEATER ASSEMBLY SEAL ST
129. ooling System Refer to Table 1 for additional troubleshooting topics 15 5804 CONVENIENCE OUTLETS WARNING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death Units with convenience outlet circuits may use multiple disconnects Check convenience outlet for power status before opening unit for service Locate its disconnect switch if appropriate and open it Tag out this switch if necessary Two types of convenience outlets are offered on 580J models Non powered and unit powered Both types provide a 125 volt GFCI ground fault circuit interrupter duplex receptacle rated at 15 A behind a hinged waterproof access cover located on the end panel of the unit See Fig 16 Pwd CO Transformer Conv Outlet C08128 Fig 16 Convenience Outlet Location Installing Weatherproof Cover A weatherproof while in use cover for the factory installed convenience outlets is now reguired by UL standards This cover cannot be factory mounted due to its depth It must be installed at unit installation For shipment the convenience outlet is covered with a blank cover plate The weatherproof cover kit is shipped in the unit s control box The kit includes the hinged cover a backing plate and gasket IMPORTANT Disconnect all power to unit and convenience outlet 1 Remove the blank cover plate at the convenience out let discard the blank cover 2
130. or DIP switches on their end Verify that the BAS and the controller have the same communication settings 8 data bits No Parity and 1 stop bit Verify that the controller has a unigue Modbus slave address The controller s Modbus slave address is set by its rotary address switches Verify that the BAS is using the proper Modbus function codes to access data from our controller Supported function codes are shown above Verify proper wiring between the BAS and the controller Verify that the BAS is reading or writing to the proper Modbus register numbers on the controller Download the latest points list for the controller to verify Verify that the BAS is sending his reguests to the proper slave address of our controller 5804 NOTE See RTU MP 3rd Party Integration Guide or alternatively RTU MP 3rd Party Integration Guide or alternatively RTU MP Controls Start Up Operation and Troubleshooting Instructions Form 48 50H T 2T Appendix for Modbus Protocol Conformance Statement 2 1 Verify that the BAS and controller are both set to speak the N2 protocol The protocol of the controller is set via SW3 switches 3 4 5 and 6 The protocol can also be verified by getting a Modstat of the controller through the BACview Hit the FN key and the key at the same time to pull up a Modstat Scroll to the bottom of the page and there is a section entitled Network Communications T
131. or signs of wear Glazing of the belt contact surfaces and erosion on these surfaces are signs of improper belt tension and or belt slippage Pulley replacement may be necessary To change fan speed 1 Shut off unit power supply 2 Loosen belt by loosening fan motor mounting nuts See Fig 5 3 Loosen movable pulley flange setscrew See Fig 6 4 Screw movable flange toward fixed flange to increase speed and away from fixed flange to decrease speed Increasing fan speed increases load on motor Do not exceed maximum speed specified 5 Set movable flange at nearest keyway of pulley hub and tighten setscrew to torgue specifications To align fan and motor pulleys 1 Loosen fan pulley setscrews 2 Slide fan pulley along fan shaft Make angular align ment by loosening motor from mounting 3 Tighten fan pulley setscrews and motor mounting bolts to torgue specifications 4 Recheck belt tension STRAIGHT EDGE MUST BE PARALLEL WITH BELT MOVABLE FLANGE MOTOR AND FAN SHAFTS MUST BE PARALLEL N SETSCREWS FIXED FLANGE SINGLE GROOVE C07075 Fig 6 Supply Fan Pulley Adjustment Bearings This fan system uses bearings featuring concentric split locking collars The collars are tightened through a cap screw bridging the split portion of the collar The cap screw has a Torx T25 socket head To tighten the locking collar Hold the locking collar tightly against the inner race of the bearing a
132. ower temperature airstream is used for cooling When using this mode of changeover control turn the enthalpy setpoint potentiometer fully clockwise to the D setting See Fig 66 Outdoor Enthalpy Changeover For enthalpy control accessory enthalpy sensor part number HH57AC078 is reguired Replace the standard outdoor dry bulb temperature sensor with the accessory enthalpy sensor in the same mounting location See Fig 69 When the outdoor air enthalpy rises above the outdoor enthalpy changeover setpoint the outdoor air damper moves to its minimum position The outdoor enthalpy changeover setpoint is set with the outdoor enthalpy setpoint potentiometer on the EconoMi er IV controller The setpoints are A B C and D See Fig 70 The factory installed 620 ohm jumper must be in place across terminals Sp and SR on the EconoMi er IV controller 5 100 105 110 38 41 43 27 29 32 35 38 41 43 C06037 Fig 70 Enthalpy Changeover Setpoints 54 i I T C06038 Fig 71 EconoMi er IV Control Differential Enthalpy Control For differential enthalpy control the EconoMi er IV controller uses two enthalpy sensors HH57AC078 and CRENTDIFOO4A00 one in the outside air and one in the return air duct The EconoMi er IV controller compares the outdoor air enthalpy to the return air enthalpy to determi
133. own delay 70 Indoor Air Ouality If the optional indoor air guality sensor is installed the RTU MP will maintain indoor air guality within the space at the user configured differential setpoint The setpoint is the difference between the indoor air guality and an optional outdoor air guality sensor If the outdoor air guality is not present then a fixed value of 400ppm is used The following conditions must be true in order for this algorithm to run The mode is occupied Indoor Fan has been ON for at least 30 seconds Indoor Air Ouality sensor has a valid reading As air guality within the space changes the minimum position of the economizer damper will be changed thus allowing more or less outdoor air into the space depending on the relationship of the indoor air guality to the differential setpoint If all the above conditions are true the IAO algorithm will run and calculates an IAO minimum position value using a PID loop The IAO minimum damper position is then compared against the user configured economizer minimum position and the greatest value becomes the final minimum damper position of the economizer output If the calculated IAO minimum position is greater than the IAO maximum damper position configuration then it will be clamped to the configured value Demand Limit If the RTU MP receives a level 1 one degree offset 2 two degree offset or a 3 4 degree offset to the BACnet demand limit variable the cont
134. panel etc The sensor uses a process called differential sensing to prevent gradual environmental changes from triggering false alarms A rapid change in environmental conditions such as smoke from a fire causes the sensor to signal an alarm state but dust and debris accumulated over time does not Duct smoke sensor a Exhaust tube Exhaust gasket Sensor housing andelectronics 2 Cover gasket y ordering option TSD CO2 ordering option Plug Sampling tube A ordered separately M P Sensor cover B Coupling Detail A N S Magnetic test reset switch le Alarm d L Power Trouble Dirty Fig 20 Smoke Detector Sensor C08209 For installations using two sensors the duct smoke detector does not differentiate which sensor signals an alarm or trouble condition Smoke Detector Locations Supply Air The Supply Air smoke detector sensor is located to the left of the unit s indoor supply fan See Fig 21 Access is through the fan access panel There is no sampling tube used at this location The sampling tube inlet extends through the side plate of the fan housing into a high pressure area The controller is located on a bracket to the right of the return filter accessed through the lift off filter panel C08245 Fig 21 Typical Supply Air Smoke Detector Sensor Location 18 Return Air Without Economizer The sampling
135. plements the unit shutdown through its NC contact set connected to the unit s LCTB input The FSD function is initiated via the smoke detector s Alarm NO contact set The RTU MP controller communicates the smoke detector s tripped status to the BAS building control See Fig 26 for unit smoke detector wiring The Fire Shutdown Switch configuration MENU Config Inputs input 5 identifies normally open status of this input when there is no fire alarm Alarm state is reset when the smoke detector alarm condition is cleared and reset at the smoke detector in the unit Connecting Discrete Inputs Filter Status The filter status accessory is a field installed accessory This accessory detects plugged filters When installing this accessory the unit must be configured for filter status by setting MENU Config Inputs input 3 5 8 or 9 to Filter Status and normally open N O or normally closed N C Input 8 or 9 is recommended for easy of installation Refer to Fig 42 and 43 for wire terminations at J5 Fan Status The fan status accessory is a field installed accessory This accessory detects when the indoor fan is blowing air When installing this accessory the unit must be configured for fan status by setting MENU Config Inputs input 3 5 8 or 9 to Fan Status and normally open N O or normally closed N C Input 8 or 9 is recommended for easy of installation Refer to Fig 42 and 43 for wire terminat
136. point will determine when the exhaust fan runs based on damper position if accessory power exhaust is installed The setpoint is modified with the Exhaust Fan Setpoint EXH SET potentiometer See Fig 66 The setpoint represents the damper position above which the exhaust fans will be turned on When there is a call for exhaust the EconoMi er IV controller provides a 45 x 15 second delay before exhaust fan activation to allow the dampers to open This delay allows the damper to reach the appropriate position to avoid unnecessary fan overload Minimum Position Control There is a minimum damper position potentiometer on the EconoMi er IV controller See Fig 66 The minimum damper position maintains the minimum airflow into the building during the occupied period When using demand ventilation the minimum damper position represents the minimum ventilation position for VOC volatile organic compound ventilation requirements The maximum demand ventilation position is used for fully occupied ventilation When demand ventilation control is not being used the minimum position potentiometer should be used to set the occupied ventilation position The maximum demand ventilation position should be turned fully clockwise 55 5804 Adjust the minimum position potentiometer to allow the minimum amount of outdoor air as reguired by local codes to enter the building Make minimum position adjustments with at least 10 F temperature d
137. py from the outdoor air enthalpy sensor and provides a dry contact switch input to the RTU MP controller A closed contact indicates that outside air is preferred to the return air An open contact indicates that the economizer should remain at minimum position Differential Enthalpy Control Differential enthalpy control is provided by sensing and comparing the outside air and return air enthalpy conditions Install the outdoor air enthalpy control as described above Add and install a return air enthalpy sensor Return Air Enthalpy Sensor Mount the return air enthalpy sensor HH57AC078 in the return air duct The return air sensor is wired to the enthalpy controller HH57AC077 See Fig 51 ENTHALPY CONTROLLER OUTDOOR Lis AIR 1 ENTHALPY SENSOR LIS RETURN AIR ENTHALPY SENSOR WIRE HARNESS GRAv RED IN UNIT NOTES 1 Remove factory installed jumper across SR and before connecting wires from return air sensor 2 Switches shown in high outdoor air enthalpy state Terminals 2 and 3 close on low outdoor air enthalpy relative to indoor air enthalpy 3 Remove sensor mounted on back of control and locate in outside air stream C06019 Fig 51 Outside and Return Air Enthalpy Sensor Wiring To wire the return air enthalpy sensor perform the following 1 Use a 2 conductor 18 or 20 AWG twisted pair cable to connect the return air enthalpy sensor to the enthalpy controller 2 At
138. r exhaust will be on all the time when in occupied mode and will be off when in unoccupied mode If set to NO the power exhaust will be controlled by the Power Exhaust Setpoint Factory Default NO IAO Max Differential Setpt If the difference between indoor an outdoor air guality becomes greater then this value the damper position will stay at the IAO Greatest Min Dmpr Pos configuration point Factory Default 650 PPM Range 300 950 PPM IAO Greatest Min Dmpr Pos This is the greatest minimum position the economizer will open to while trying to control the indoor air quality CO2 differential Factory Default 5090 open Range 10 60 open Clockset This submenu screen allows you to set the date and time manually The Daylight Savings Time DST can also be changed here The date and time is automatically set when ever software is downloaded The clock is a 24 hour clock and not am pm The time should be verified and maybe changed according to unit location and time zone Factory Default Eastern Standard Time USERPW This submenu screen allows you to change the user password to a four number password of choice The User password change screen is only accessible with the Administrator Password 1111 The ADMIN password will always override the user password OPERATING SEOUENCES Base Unit Controls Cooling Units Without Economizer When thermostat calls for Stage 1 cooling terminals G and Y1 are energized
139. r Screen This air screen is retained by spring clips under the top edge of the hood See Fig 3 5804 lt 22 3 8 569 mm DIVIDER OUTSIDEN N CLEANABLE ALUMINUM FILTER BAROMETRIC RELIEF FILTER CAP C08634 Fig 3 Filter Installation To remove the filter open the spring clips Re install the filter by placing the frame in its track then closing the spring clips Manual Outside Air Hood Screen This inlet screen is secured by a retainer angle across the top edge of the hood See Fig 4 C07156 Fig 4 Screens Installed on Outdoor Air Hood Sizes 7 1 2 to 12 1 2 Tons Shown To remove the screen loosen the screws in the top retainer and slip the retainer up until the filter can be removed Re install by placing the frame in its track rotating the retainer back down and tighten all screws SUPPLY FAN BLOWER SECTION 4 WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could cause personal injury or death Before performing service or maintenance operations on the fan system shut off all unit power and tag out the unit disconnect switch Do not reach into the fan section with power still applied to unit Supply Fan Belt Drive The supply fan system consists of a forward curved centrifugal blower wheel on a solid shaft with two concentric type bearings one on each side of the blower housing A fixed pi
140. r filters If the unit has an economizer it will also have an outside air screen If a manual outside air damper is added an inlet air screen will also be present Each of these filters and screens will need to be periodically replaced or cleaned Return Air Filters Return air filters are disposable fiberglass media type Access to the filters is through the small lift out panel located on the rear side of the unit above the evaporator return air access panel See Fig 1 To remove the filters 1 Grasp the bottom flange of the upper panel 2 Lift up and swing the bottom out until the panel dis engages and pulls out 3 Reach inside and extract the filters from the filter rack 4 Replace these filters as required with similar replace ment filters of same size To re install the access panel 1 Slide the top of the panel up under the unit top panel 2 Slide the bottom into the side channels 3 Push the bottom flange down until it contacts the top of the lower panel or economizer top IMPORTANT DO NOT OPERATE THE UNIT WITHOUT THESE FILTERS Outside Air Hood Outside air hood inlet screens are permanent aluminum mesh type filters Check these for cleanliness Remove the screens when cleaning is required Clean by washing with hot low pressure water and soft detergent and replace all screens before restarting the unit Observe the flow direction arrows on the side of each filter frame Economizer Inlet Ai
141. re is a 22 second delay before another 5 second try If the burner still does not light the time delay is repeated If the burner does not light within 15 minutes there is a lockout To reset the control break the 24 v power to W1 6 The evaporator fan motor will turn on 45 seconds after burner ignition 7 The evaporator fan motor will turn off in 45 seconds after the thermostat temperature is satisfied 8 Adjust airflow to obtain a temperature rise within the range specified on the unit nameplate 63 5804 NOTE The default value for the evaporator fan motor on off delay is 45 seconds The Integrated Gas Unit Controller IGC modifies this value when abnormal limit switch cycles occur Based upon unit operating conditions the on delay can be reduced to 0 seconds and the off delay can be extended to 180 seconds If the limit switch trips at the start of the heating cycle during the evaporator on delay the time period of the on delay for the next cycle will be 5 seconds less than the time at which the switch tripped Example If the limit switch trips at 30 seconds the evaporator fan on delay for the next cycle will occur at 25 seconds To prevent short cycling a 5 second reduction will only occur if a minimum of 10 minutes has elapsed since the last call for heating The evaporator fan off delay can also be modified Once the call for heating has ended there is a 10 minute period during which the modification can oc
142. rgized All heating operations cease The IFM stops after a 45 second time off delay Cooling Unit With EconoMi er IV For Occupied mode operation of EconoMi er IV there must be a 24 v signal at terminals TR and N provided through PL6 3 from the unit s IFC coil Removing the signal at N places the EconoMi er IV control in Unoccupied mode During Occupied mode operation indoor fan operation will be accompanied by economizer dampers moving to Minimum Position setpoint for ventilation If indoor fan is off dampers will close During Unoccupied mode operation dampers will remain closed unless a Cooling by free cooling or DCV demand is received When free cooling using outside air is not available the unit cooling sequence will be controlled directly by the space thermostat as described above as Cooling Unit Without Economizer Outside air damper position will be closed or Minimum Position as determined by occupancy mode and fan signal 67 5804 When cooling is available as determined by the appropriate changeover command dry bulb outdoor enthalpy differential dry bulb or differential enthalpy a call for cooling Y1 closes at the thermostat will cause the economizer control to modulate the dampers open and closed to maintain the unit supply air temperature at 50 to 55 Compressor will not run During free cooling operation a supply air temperature SAT above 50 will cause the dampers to modulate betw
143. rifice See Condenser Fan Adjustment section for more details b Make sure that air filter s is in place c Make sure that condensate drain trap is filled with water to ensure proper drainage d Make sure that all tools and miscellaneous loose parts have been removed START UP GENERAL Unit Preparation Make sure that unit has been installed in accordance with installation instructions and applicable codes Gas Piping Check gas piping for leaks 62 WARNING UNIT OPERATION AND SAFETY HAZARD Failure to follow this warning could result in personal injury or death Disconnect gas piping from unit when leak testing at pressure greater than 1 2 psig Pressures greater than 1 2 psig will cause gas valve damage resulting in hazardous condition If gas valve is subjected to pressure greater than 1 2 psig it must be replaced before use When pressure testing field supplied gas piping at pressures of 1 2 psig or less a unit connected to such piping must be isolated by manually closing the gas valve Return Air Filters Make sure correct filters are installed in unit see Appendix II Physical Data Do not operate unit without return air filters Outdoor Air Inlet Screens Outdoor air inlet screen must be in place before operating unit Compressor Mounting Compressors are internally spring mounted Do not loosen or remove compressor hold down bolts Internal Wiring Check all factory and field ele
144. roller will expand the heating and cooling setpoints by the configured demand limit setpoint value and remain in effect until the BACnet demand limit variable receives a 0 value FASTENER TOROUE VALUES See Table 25 for torgue values Table 25 Torgue Values Supply fan motor mounting 120 12 in Ibs 13 5 1 4 Nm Supply fan motor adjustment plate 120 12in lbs 13 5 1 4 Nm Motor pulley setscrew 72 5in lbs 8 1 0 6 Fan setscrew 72 5 165 8 1 0 6 Nm Blower wheel hub setscrew 72 5in lbs 8 1 0 6 Nm Bearing locking collar setscrew 65 to 70 in lbs 7 3 to 7 9 Nm Compressor mounting bolts 65 to 75 in lbs 7 3 to 7 9 Nm Condenser fan motor mounting bolts 20 2in lbs 2 3 0 2 Nm Condenser fan hub setscrew 84 12 in Ibs 9 5 1 4 Nm 71 5804 APPENDIX I MODEL NUMBER SIGNIFICANCE Model Number Nomenclature 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 5 80 JlE 0 8 D1 2 5 1 A Unit Type uU Design Revision 580J Cooling Gas Heat RTU First Revision Voltage Packaging 460 3 60 A Standard P 208 230 3 60 B LTL T 575 3 60 Factory Installed Options Cooling Tons None 08 7 5 Ton 12 10 Ton Intake Exhaust Options 14 12 5 Ton A None B Temp econo w baro relief R
145. rom the factory configured for outdoor dry bulb changeover control The outdoor air and supply air temperature sensors are included as standard For this control mode the outdoor temperature is compared to an adjustable setpoint selected on the control If the outdoor air temperature is above the setpoint the EconoMi er IV will adjust the outside air dampers to minimum position If the outdoor air temperature is below the setpoint the position of the outside air dampers will be controlled to provided free cooling using outdoor air When in this mode the LED next to the free cooling setpoint potentiometer will be on The changeover temperature setpoint is controlled by the free cooling setpoint potentiometer located on the control See Fig 66 The scale on the potentiometer is A B C and D See Fig 63 for the corresponding temperature changeover values FAN SET POINT WHEN EXHAUST CONTACT IS MADE MIN POSITION SETTING DEMAND CONTROL VENTILAT LED DEMAND CONTROL VENT IS ABOVE SET POINT DEMAND CONTROL VENTILATI LED OUTDOOR AIR IS SUITABLE FOR FREE COOLING EXHAUST LED LIGHTS MUM DAMPER MUM DAMPER SET POINT LIGHTS WHEN LATION INPUT SET POINT LIGHTS WHEN ENTHALPY CHANGEOVER SET POINT
146. rovide free cooling and Indoor Air Quality if optional CO sensor is installed when the outside conditions are suitable The following conditions must be true for economizer operation Indoor Fan has been on for at least 30 seconds Enthalpy is Low if the Enthalpy input is enabled SAT reading is available OAT reading is available SPT reading is available OAT lt High OAT economizer lockout configuration default 75 OAT lt SPT If any of the mentioned conditions are not true the economizer will be set to its configured minimum position The minimum damper position can be overridden by the IAO routine described later in this section If the above conditions are true the Economizer Control Master Loop will calculate a damper position value based on the following calculation Damper Position minimum position PID SPT econ setpoint Econ setpoint is half way between the effective cool and heat setpoints If the SAT drops below the cooling low supply air setpoint 5 the economizer will ramp down to minimum position Power Exhaust If RTU MP is also controlling an exhaust fan it can be enabled based on damper position or by occupancy If configured for continuous occupied operation it will be energized whenever the controller is in the occupied mode and disabled when in the unoccupied mode If configured for damper position control it will be energized whenever the economizer exceed
147. s reguired 1 Recommend using field supplied fan pulley part no KR11AD912 and belt part no KR29AF051 2 Recommend using field supplied motor pulley part no KR11HY410 580J 12 3 PHASE 10 TON VERTICAL SUPPLY AVAILABLE EXTERNAL STATIC PRESSURE in wg CFM 0 2 0 4 0 6 0 8 1 0 RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard Static Option Medium Static Option 3000 616 0 79 689 0 97 757 1 16 821 1 36 882 1 57 3250 655 0 96 724 1 16 788 1 37 849 907 1 80 3500 695 1 17 760 1 38 821 1 60 879 1 83 934 2 06 3750 736 1 41 797 1 63 855 910 2 10 963 2 35 4000 889 2 16 942 2 41 993 2 67 4250 4 925 2 49 976 2 75 1025 3 02 4500 860 2 32 912 2 58 962 2 85 1010 3 13 1057 3 41 4750 902 2 69 951 2 97 999 3 26 1046 3 55 1091 3 84 5000 944 3 11 991 3 40 1037 3 70 1082 4 00 1125 4 31 AVAILABLE EXTERNAL STATIC PRESSURE in wg 1 2 1 4 1 6 1 8 2 0 VEM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Medium Static Option High Static Option 3000 939 1 79 994 2 01 1047 2 24 1098 2 47 1147 2 71 3250 962 2 03 1015 2 26 2 50 1115 2 75 1163 3 00 3500 987 2 30 1038 2 54 1135 3 05 1181 3 32 3750 1014 2 60 1063 2 86 1157 3 39 1202 3 66 4000 1136 3 48 1180 3 76 1224 4 04 4250 1162 3 87 1205 4 16 4500 1103 3 70 1147 4 00 1190 4 29 1232 4 60 4750 1135 4 14 1177 4 45 5000 1167 4 63 NOTE For more information see General Fan Performance Notes Boldface indicates field supplied drive is reguired 1 Recommend using
148. s the power exhaust setpoint and disabled when the economizer drops below the setpoint by a fixed hysteresis of 1090 Heating The heating outputs are controlled by the Heating Control PID Loop and Heating Stages Capacity algorithm They will be used to calculate the desired number of stages needed to satisfy the space by comparing the SPT to the Occupied Heat Setpoint plus the T56 slider offset when occupied and the Unoccupied Heat Setpoint plus the T56 slider offset if unoccupied The following conditions must be true in order for this algorithm to run ndoor Fan has been ON for at least 30 seconds Cool mode is not active and the time guard between modes equals zero f occupied and SPT occupied heat setpoint plus T56 slider offset SPT reading is available If it is unoccupied and the SPT lt unoccupied heat setpoint plus T56 slider offset The indoor fan will be turned on by the staging algorithm OAT High OAT lockout temperature If all of the above conditions are met the heating outputs will be energized as required otherwise they will be de energized If the SAT begins to exceed the high supply air setpoint a ramping function will cause the Heat Stages Capacity algorithm to decrease the number of stages until the SAT has dropped below the setpoint There is a fixed one minute minimum on time and a one minute off time for each heat output Heat staging has a 3 minute stage up and 30 second stage d
149. steps Return Air Sampling Tube C08129 Fig 23 Return Air Sampling Tube Location Completing Installation of Return Air Smoke Sensor 1 Unscrew the two screws holding the Return Air Sensor detector plate See Fig 24 Save the screws 2 Remove the Return Air Sensor and its detector plate 3 Rotate the detector plate so the sensor is facing out wards and the sampling tube connection is on the bot tom See Fig 25 EXHAUST TUBE FLEXIBLE EXTENSION TUBE SAMPLING C08126 Fig 24 Return Air Detector Shipping Position 4 Screw the sensor and detector plate into its operating position using screws from Step 1 Make sure the sampling tube connection is on the bottom and the ex haust tube is on the top See Fig 24 5 Connect the flexible tube on the sampling inlet to the sampling tube on the basepan 6 For units with an economizer the sampling tube is in tegrated into the economizer housing but the connec tion of the flexible tubing to the sampling tube is the same C08127 Fig 25 Return Air Sensor Operating Position FIOP Smoke Detector Wiring and Response All Units FIOP smoke detector is configured to automatically shut down all unit operations when smoke condition is detected See Fig 26 Smoke Detector Wiring Highlight A JMP 3 is factory cut transferring unit control to smoke detector 19 5804 FE Z ACCESSORY POWE RETURN _24 VAC SMOKE
150. stop time configured The Override schedule is enabled by following the same steps to create the Holiday schedule NOTE Push button override is only available when running a local or BACnet Schedule BACnet Schedule For use with a Building Automation System that supports native BACnet scheduling is scheduling the unit With the Occupancy Source set to BACnet schedule the BAS will control the unit through network communication and it s own scheduling function BAS On Off The Building Automation System is scheduling the unit via an On Off command to the BAS ON OFF software point The Building Automation System can be speaking BACnet Modbus or N2 and is writing to the BAS On Off point in the open protocol point map NOTE If the BAS supports NATIVE BACnet scheduling then set the Occupancy Source to BACnet schedule If the BAS is BACnet but does NOT support NATIVE BACnet scheduling then set the Occupancy Source to BAS On Off DI On Off hard wired input on the RTU MP will command the unit to start stop Inputs 3 5 8 and 9 on plug J5 can be hard wired to command the unit to start stop NOTE Scheduling can either be controlled via the unit or the BAS but NOT both Indoor Fan The indoor fan will be turned on whenever any one of the following conditions is true It is in the occupied mode This will be determined by its own internal occupancy schedule Whenever there is a demand for cooling or heating in the u
151. system and recharge Condenser air restricted or air short cycling Determine cause and correct Head Pressure Too Low Low refrigerant charge Check for leaks repair and recharge Compressor valves leaking Replace compressor Restriction in liquid tube Remove restriction Excessive Suction Pressure High head load Check for source and eliminate Compressor valves leaking Replace compressor Refrigerant overcharged Recover excess refrigerant Suction Pressure Too Low Dirty air filter Replace filter Low refrigerant charge Check for leaks repair and recharge Metering device or low side restricted Remove source of restriction Insufficient evaporator airflow Increase air quantity Check filter and replace if necessary Temperature too low in conditioned area Reset thermostat Outdoor ambient below 25 F Install low ambient kit Evaporator Fan Will Not Shut Off Time off delay not finished Wait for 30 second off delay Compressor Makes Excessive Noise Compressor rotating in wrong direction Reverse the 3 phase power leads 14 Compressors Lubrication Compressors are charged with the correct amount of oil at the factory CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in damage to components The compressor is in a Puron refrigerant system
152. t Occupancy types are described in the scheduling section The following sections describe the operation for the functions of the RTU MP All point objects that are referred to in this seguence will be in reference to the objects as viewed in BACview Handheld 68 Scheduling Scheduling is used to start heating or cooling become occupied based upon a day of week and a time period and control to the occupied heating or cooling setpoints Scheduling functions are located under occupancy determination and the schedule menu accessed by the Menu softkey see Appendix for menu structure Your local time and date should be set for these functions to operate properly Five scheduling functions are available by changing the Occupancy Source to one of the following selections Always Occupied Default Occupancy The unit will run continuously RTU MP ships from the factory with this setting Local Schedule The unit will operate according to the schedule configured and stored in the unit The local schedule is made up of three hierarchy levels that consist of two Override schedules twelve Holiday and four Daily schedules and are only accessible by the BACview screen handheld or virtual The Daily schedule is the lowest schedule in the hierarchy and is overridden by both the Holiday and Override schedule It consists of a start time a stop time both in 24 hour mode and the seven days of the week starting with Monday and ending in
153. tch driven pulley is attached to the fan shaft and an adjustable pitch driver pulley is on the motor The pulleys are connected using a V type belt See Fig 5 C07087 Fig 5 Belt Drive Motor Mounting Belt Check the belt condition and tension guarterly Inspect the belt for signs of cracking fraying or glazing along the inside surfaces Check belt tension by using a spring force tool such as Browning s Part Number Belt Tension Checker or equivalent tool Tension should be 6 Ibs at 5 8 16 mm deflection when measured at the centerline of the belt span This point is at the center of the belt when measuring the distance between the motor shaft and the blower shaft NOTE Without the spring tension tool place a straight edge across the belt surface at the pulleys then deflect the belt at mid span using one finger to a 1 2 in 13 mm deflection Adjust belt tension by loosening the motor mounting plate front bolts and rear bolt and sliding the plate toward the fan to reduce tension or away from fan to increase tension Ensure the blower shaft and the motor shaft are parallel to each other pulleys aligned Tighten all bolts when finished To replace the belt 1 Use a belt with same section type or similar size Do not substitute a FHP type belt When installing the new belt do not use a tool screwdriver or pry bar to force the belt over the pulley flanges this will stress the
154. the enthalpy control remove the factory installed resistor from the SR and terminals 3 Connect the field supplied RED wire to spade connector on the return air enthalpy sensor and the SR terminal on the enthalpy controller Connect the BLK wire to S spade connector on the return air enthalpy sensor and the SR terminal on the enthalpy controller NOTE The enthalpy control must be set to the D setting for differential enthalpy control to work properly The enthalpy control receives the indoor and return enthalpy from the outdoor and return air enthalpy sensors and provides a dry contact switch input to the RTU MP controller A closed contact indicates that outside air is preferred to the return air An open contact indicates that the economizer should remain at minimum position Indoor Air Quality CO Sensor The indoor air quality sensor accessory monitors space carbon dioxide CO2 levels This information is used to monitor IAO levels Several types of sensors are available for wall mounting in the space or in return duct with and without LCD display and in combination with space temperature sensors Sensors use infrared technology to measure the levels of present in the space air The CO sensors are all factory set for a range of 0 to 2000 ppm and a linear mA output of 4 to 20 Refer to the instructions supplied with the CO sensor for electrical reguirements and terminal locations See Fig 52
155. the left of the LCTB See Fig 43 Factory wiring is completed through harnesses connected to the LCTB Field connections for RTU MP sensors will be made at the Phoenix connectors on the RTU MP board The factory installed RTU MP control includes the supply air temperature SAT sensor The outdoor air temperature OAT sensor is included in the FIOP accessory EconoMi er 2 package Refer to Table 15 RTU MP Controller Inputs and Outputs for locations of all connections to the RTU MP board 35 5804 J4 J1 Board Power E 5 5 aoaoga amp N 55 c2 9op992u R NR 2 5958 Svogeezae oe2o zXg 5285 HK50AA047 012311 Rev 3 amp 4 RTU MP AO 2 GND 0 10V only Kore Y I ACCESS C PORT gt 12 voc Tt MSB LSB Rnet 0 0 CR2022 EA SW1 SW2 Protocol Selector Remove Input 10 T 55 Accy both for 0 5V ut 41 T 56 Accy cC N 6 Jn SOd NO93 190 2 OVA vZ 19 9 ojgeunbyuos ajqesnByuog ajqeunByuo5 OVA e3sipiunH OVA vZ I OVA I OVA L3 9 Jn e e lt a p0 6 e LL n Humidistat I 00 7 Spare le i e ia oe Exhaust Fig 42 RTU MP Multi Protocol Control Board 36 Como
156. to prepare the EconoMi er IV for troubleshooting No troubleshooting or testing is done by performing the following procedure NOTE This procedure requires a 9 v battery 1 2 kilo ohm resistor and a 5 6 kilo ohm resistor which are not supplied with the EconoMi er IV IMPORTANT Be sure to record the positions of all potentiometers before starting troubleshooting Disconnect power at TR and TR1 LEDs should be off Exhaust fan contacts should be open 2 Disconnect device at and 1 95 Jumper P to 4 Disconnect wires at T and T1 Place 5 6 kilo ohm resistor across T and T1 5 Jumper TR to 1 6 Jumper TR to N 7 If connected remove sensor from terminals SO and Connect 1 2 kilo ohm 4074EJM checkout resistor across terminals SO and 8 Put 620 ohm resistor across terminals SR and 9 Set minimum position DCV setpoint and exhaust potentiometers fully CCW counterclockwise 10 Set DCV maximum position potentiometer fully CW clockwise 11 Set enthalpy potentiometer to D 12 Apply power 24 vac to terminals TR and TRI Differential Enthalpy To check differential enthalpy 1 Make sure EconoMi er IV preparation procedure has been performed 2 Place 620 ohm resistor across SO and 3 Place 1 2 kilo ohm resistor across SR and The Free Cool LED should be lit 4 Remove 620 ohm resistor across SO and The Free Cool LED should turn off 5 Return EconoMi er IV settings and w
157. tors are correctly installed Check 3rd party vendor RS485 communication wiring guidelines and troubleshooting procedures Table 21 Modbus Exception Codes that May be 2 Verify that the BAS and controller are set for the Returned From This Controller same baud rate The baud rate of the controller is set CODE MEANING via SW3 switches 1 and 2 The baud rate can also The Modb sf nction code used be verified via the BACview by obtaining a Modstat 01 Illegal Function in the query is not supported by See Fig 59 the controller 3 Verify that the BAS is configured to speak 2 wire The register address used in the query is not supported by the controller Illegal Data Address The Modbus Master has attempted to write to a non existent register or a read only register in the controller Slave Device Failure Modbus 1 Verify that the BAS and controller are both set to speak the Modbus RTU protocol The protocol of the controller is set via SW3 switches 3 4 5 and 6 The protocol can also be verified by getting a Modstat of the controller through the BACview Hit the FN key and the key at the same time to pull up a Modstat Scroll to the bottom of the page and there is a section entitled Network Communications The active protocol and baud rate will be shown in this section 49 EIA 485 to the controller The BAS may have to configure jumper
158. trical components Only trained and qualified service personnel should install repair or service air conditioning equipment Untrained personnel can perform the basic maintenance functions of replacing filters Trained service personnel should perform all other operations When working on air conditioning equipment observe precautions in the literature tags and labels attached to the unit and other safety precautions that may apply Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for unbrazing operations Have fire extinguishers available for all brazing operations Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions attached to the unit Consult local building codes and National Electrical Code NEC for special requirements Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in
159. tube is located across the return air opening on the unit basepan See Fig 22 The holes in the sampling tube face downward into the return air stream The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location This sensor is shipped in a flat mounting location Installation reguires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected See installation steps Return Air Detector module shipping position shown Controller module 55 D Return Air Detector Sampling Tube RA detector must be moved from shipping position to operating position by installer C07307 Fig 22 Typical Return Air Detector Location Return Air With Economizer The sampling tube is inserted through the side plates of the economizer housing placing it across the return air opening on the unit basepan See Fig 23 The holes in the sampling tube face downward into the return air stream The sampling tube is connected via tubing to the return air sensor that is mounted on a bracket high on the partition between return filter and controller location This sensor is shipped in a flat mounting location Installation requires that this sensor be relocated to its operating location and the tubing to the sampling tube be connected See installation
160. ust as needed Too much outdoor air Adjust minimum position Check economizer operation Incomplete combustion lack of combustion air results in Aldehyde odors CO sooting flame or floating flame Poor Flame Characteristics Check all screws around flue outlets and burner compartment Tighten as necessary Cracked heat exchanger Overfired unit reduce input change orifices or adjust gas line or manifold pressure Check vent for restriction Clean as necessary Check orifice to burner alignment Burners Will Not Turn Unit is locked into Heating mode Off for a one minute minimum Wait until mandatory one minute time period has elapsed or reset power to unit 33 5804 Table 14 IGC Board LED Alarm Codes LED FLASH DESCRIPTION ACTION TAKEN BY RESET METHOD PROBABLE CAUSE CONTROL CODE On Normal Operation Loss of power to the IGC Check 5 amp 3 fuse on IGC power to unit 24V circuit Olt gas heating breaker transformer and wiring to the IGC High temperature limit switch is open Gas valve and igniter 1 the indoor 2 DN Off Limit switch closed itx Flashes Limit Switch Fault Indoor fan and inducer or heat call W Off ma the supply air temperature On rise is within the range on the unit nameplate Check wiring and limit switch operation Flame sense
161. value is displayed and used when 4mA is seen at the input Factory Default 0 PPM Range 0 400 PPM High Reference 20mA This is used when an OAO sensor is installed on Input 1 or 2 This value is displayed and used when 20mA is seen at the input Factory Default 2000 PPM Range 0 5000 PPM NOTE low Reference 4mA and High Reference 20mA are used to set the linear curve of mA vs PPM Economizer Economizer Exists This point tells the controller if there is an economizer installed on the unit Factory Default NO if no economizer YES if there is an economizer installed Economizer Minimum Position This defines the lowest economizer position when the indoor fan is running and the building is occupied Factory Default 20 Range 0 100 Economizer High OAT Lockout If the outdoor air temperature rises above this value economizer cooling will be disabled and dampers will return and stay at minimum position Factory Default 75 Range 55 80 66 Power Exhaust Setpt When the economizer damper position opens above this point the power exhaust operation will begin When the damper position falls 10 below the setpoint the power exhaust will shutdown Factory Default 50 Range 20 90 NOTE This point is only used when Continuous Occ Exhaust NO Continuous Occ Exhaust This point tells the controller when to run the power exhaust if eguipped on the unit If set to YES the powe
162. ventilation rate means the equipment can condition air at a maximum ventilation rate that is greater than the required ventilation rate for maximum occupancy A proportional anticipatory strategy will cause the fresh air supplied to increase as the room CO level increases even though the setpoint has not been reached By the time the CO level reaches the setpoint the damper will be at maximum ventilation and should maintain the setpoint In order to have the CO sensor control the economizer damper in this manner first determine the damper voltage output for minimum or base ventilation Base ventilation is the ventilation required to remove contaminants during unoccupied periods The following equation may be used to determine the percent of outside air entering the building for a given damper position For best results there should be at least a 10 degree difference in outside and return air temperatures OA RA occ e etu To Outdoor Air Temperature OA Percent of Outdoor Air Tg Return Air Temperature RA Percent of Return Air TM Mixed Air Temperature Once base ventilation has been determined set the minimum damper position potentiometer to the correct position 56 The same eguation can be used to determine the occupied or maximum ventilation rate to the building For example an output of 3 6 volts to the actuator provides a base ventilation rate of 5 and an output of 6 7 volts provides the maximum ventil
163. water is approved as the cleaning solution Only clean potable water is authorized for cleaning NOVATION condensers Carefully remove any foreign objects or debris attached to the coil face or trapped within the mounting frame and brackets Using a high pressure water sprayer purge any soap or industrial cleaners from hose and or dilution tank prior to wetting the coil Clean condenser face by spraying the coil core steadily and uniformly from top to bottom directing the spray straight into or toward the coil face Do not exceed 900 psig or a 45 degree angle nozzle must be at least 12 in 30 cm from the coil face Reduce pressure and use caution to prevent damage to air centers fins Do not fracture the braze between air centers and refrigerant tubes Allow water to drain from the coil core and check for refrigerant leaks prior to start up NOTE Please see the NOVATION Condenser Service section for specific information on the coil CAUTION PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury or eguipment damage Chemical cleaning should NOT be used on the aluminum NOVATION condenser Damage to the coil may occur Only approved cleaning is recommended Routine Cleaning of Evaporator Coil Surfaces Monthly cleaning with Totaline amp environmentally sound coil cleaner is essential to extend the life of coils This cleaner is available from Bryant Replacement parts division as part number
164. witch to the RESET TEST position for seven seconds 2 Verify that the test reset station s Alarm LED turns on 3 Reset the sensor by turning the key switch to the RESET TEST position for two seconds 4 Verify that the test reset station s Alarm LED turns off Remote Test Reset Station Dirty Sensor Test The test reset station dirty sensor test checks the test reset station s ability to initiate a sensor dirty test and indicate the results It must be wired to the controller as shown in Fig 27 and configured to operate the controller s supervision relay For more information see Changing the Dirty Sensor Test Smoke Detector Controller TB3 OH OH 4 eguipment 3 5 m SD TRK4 upervision relay contacts 3 Z Trouble 5 RY AQ 1 9 9 M Wire must be Alam gt added by installer 15 d e Reset Test oad 7 1 18 Vdc NE C08247 Fig 27 Remote Test Reset Station Connections CAUTION OPERATIONAL TEST HAZARD Failure to follow this caution may result in personnel and authority concern If the test reset station s key switch is left in the RESET TEST position for longer than seven seconds the detector will automatically go into the alarm state and activate all automatic alarm responses CAUTION OPERATIONAL TEST HAZAR
165. y Closed N C Input 5 is factory wired to pin J1 10 Field accessories get wired to its parallel pin J5 3 Do not connect inputs to both locations one function per input Factory Default Fire Shutdown and N C NOTE Fire Shutdown input comes from TB4 7 J1 10 is always factory wired to TB4 7 Only change input 5s function if absolutely needed Input This input is a discrete input and can be configured to be one of five different inputs No Function Enthalpy Switch Fan Status Filter Status or Remote Occupancy This input can also be configured to be either Normally Open N O or Normally Closed N C Input 8 is factory wired to pin J2 6 Field accessories get wired to its parallel pin J5 1 Do not connect inputs to both locations one function per input Factory Default No Function and N O Input 9 This input is a discrete input and can be configured to be one of five different inputs No Function Humidistat Fan Status Filter Status or Remote Occupancy This input can also be configured to be either Normally Open N O or Normally Closed N C Input 9 is factory and field wired to pin J5 7 Do not connect inputs to both locations one function per input Factory Default Humidistat and N O Space Sensor Type This tells the controller what type of space sensor is installed to run the unit The three types that can be used are the T55 space sensor the T56 space sensor or the RS space sensor Factory Default T55 Type

Download Pdf Manuals

image

Related Search

Related Contents

M ic ro N o v a I023 idro Controllore per stufa a pellet  Wild Fruit - J-h  E-Safety: Blocking Inappropriate Content On Television Freeview  株式会社ノジマからの省エネ製品の寄贈について 寄贈年月  MANUAL DO ENTREVISTADOR  Battery&Dock取扱説明書(PDF)  Publikation 7000-UM150_-DE-P  Interface OB  Instruction Manual - Black & Decker Service Technical Home Page  Samsung ES20 Korisničko uputstvo  

Copyright © All rights reserved.
Failed to retrieve file