APC GALAXY 990-2258B-001 User's Manual

image

Contents

1. Remove the two screws from the cable inlet at the front and remove the cable inlet plate Guide the cable through the hole in the bottom plate and up through the cable inlet Guide the cable through the side panel hole and run the cable upwards inside the panel Pull the cable out of the side panel through the hole closest to the Network Management Card area Plug the cable into the probe socket PowerChute inlet Reattach the cable inlet plate Specifications Warning The UPS must be supplied from a 380 220 V AN 400 230 V or 415 240 V L1 L2 L3 N PE 50 Hz AC input 10 kVA UPS ratings 380 V 400V 45V Input frequency Hz 40 70 40 70 40 70 Nominal input current A 13 0 12 3 11 9 Max input current A 14 3 13 5 13 1 Input current limit A 16 8 16 8 168 15 kVA 20 kVA UPS ratings 380 V 400V 415V 380V 400V 415V Input frequency Hz 40 70 40 70 40 70 40 70 40 70 40 70 Nominal input current A 19 4 18 5 17 8 26 0 24 7 23 8 Max input current A 21 4 20 3 19 6 28 6 27 2 262 Input current limit Ay 25 2 25 2 25 2 33 8 33 8 33 8 30 kVA 40 kVA UPS ratings 380 V 400V 415V 380V 400V 415 V Input frequency Hz 40 70 40 70 40 70 40 70 40 70 40 70 Nominal input current A 38 6 36 7 35 3 51 7 49 1 47 3 Max input current A 42 5 403 38 9 56 8 540 52 1 Input current limit A 50 1 50 1 50 1 66 9 66 9 66 9 AC output
2. full battery recharge and low input voltage Synchronization adjustable 10Hz 3Hz or 0 1 Hz Recommended current protection input output disconnect must be provided by the customer Q Note AC input output over current protection and AC Q1 Q3 Q2 Utility input Bypass input Output 10 kVA 16 16 16 ISkVA 25 25 25 20 kVA 35 35 35 30 kVA 50 50 50 40 kVA 63 63 63 l Required upstream current protection mains input gL type fuse Recommended cable sizes Note The recommended cable sizes are based on an Q environment with an ambient temperature of 30 C Battery input lane input fs es ram 75 C Hee input 10kVA 25 2 5 50 2 5 15 kVA 6 6 50 6 20 kVA 10 10 50 10 30kVA 16 16 50 16 40 kVA 25 25 50 25 Note Use Molex lug type or equivalent and crimp to Q manufacturer s specifications Warning At 100 switch mode load the neutral must AN be rated for 200 phase current Minimum breaker settings 150 125 800 overload overload overload normal normal bypass battery battery operation operation operation Continuously 10 kVA Mains input zi 16 4 A Bypass input 121 5 A 16 7 A Output 121 5 A 22 8 A 19 A 16 7 A Duration 500 ms 60s 10 min 15 KVA Mains input al 24 6 A Bypass input 182 A 25 1 A Output 182 A 34 2 A 254A 25 1A Duration 500 ms 60s 10 min 0 20 kVA Mains input a 32 5 A Bypass input 244 A 33 4 A Output 244 A 45 6 A 38
3. 10 kVA UPS ratings 380 V 400V 415V Nominal output current A 15 2 14 4 13 9 15 kVA 20 kVA UPS ratings 380 V 400V 415V 380V 400V 415V Nominal output current A 22 8 21 7 20 9 30 4 28 9 27 8 30 kVA 40 KVA UPS ratings 380 V 400V 415V 380V 400V 415V Nominal output current A 45 6 43 3 41 7 60 8 57 7 55 6 Battery input UPS ratings 10 kVA 15kVA 20kVA 30kVA 40kVA Nominal voltage V 192 192 192 192 192 External battery fuse A 125 125 125 125 125 1 6 1 75 V cell automatic depending on load Bypass input 10 kVA UPS ratings 380 V 400 V 415V Input frequency Hz 5010 or 50410 or 5010 or 6010 6010 6010 Nominal input current A 15 2 14 4 13 9 15 kVA 20 KVA UPS O 380V 400V 415V 380V 400V 415V ratings Input 50410 or 50 10or 50 10or 50 100r 50 10or 5010 or frequency 60 10 6010 60 10 60 10 60 10 60 10 Hz Nominal 22 8 21 7 20 9 30 4 28 9 27 8 input current A 30 kVA 40 kVA UPS ratings 380 V 400 V 415V 380 V 400 V 415 V Input 50410 or 50 10or 50 10or 50 100r 50 10or 5010 or frequency 6010 6010 60410 6010 6010 6010 Hz Nominal 45 6 43 3 41 7 60 8 57 7 55 6 input current A Notes J Input current based on rated load and batteries fully charged Input current based on full battery recharge nominal voltage and rated load 3 Current limitation through electronic current limiting is based on
4. A 33 4 A Duration 500 ms 60s 10 min w 30 kVA Mains input al 49 1 A Bypass input 364 A 50 1 A Output 364 A 68 4 A 57A 50 1 A Duration 500 ms 60s 10 min 40 kVA Mains input zi 65 6A Bypass input 487A 66 9 A Output 487 A 91 2 A 76 A 66 9 A Duration 500 ms 60s 10 min oe l At single feed use the higher value of mains and bypass Recommended lug size and torque value Note Power terminal lug diameter 6 mm Torque value 7 Nm Contact Information For local country specific centers go to www apc com support contact Appendix Wiring diagrams Diagram with Maintenance Diagram without Bypass Panel Maintenance Bypass Panel Bypass Bypass Bypass breaker breaker fuses fuses Mains Maintenance Mains Mains breaker Bypass i breaker Load fuses fuses Output Battery Battery Enclosure Enclosure
5. ArC by Schneider Electric Installation MGE Galaxy 3500 10 40 kVA 380 400 415 V with batteries XR battery enclosure UPS UPS IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS Warning ALL safety instructions in the Safety Sheet 990 2940 must be read understood and followed when installing the UPS system Failure to do so could result in equipment damage serious injury or death Warning After the UPS has been electrically wired do not start it up Start up is commissioned to authorized personnel from Schneider Electric Caution All electrical power and power control wiring must be installed by a qualified electrician and must comply AN with local and national regulations for maximum power rating 990 2258B 001 IMO 9 2009 Note Ensure that the unit is in its final location prior to installation connected until all other wiring has been completed See Also For parallel configurations see manual 990 3568 Q Note Battery and utility mains power must not be Level the Enclosure Warning The system must be installed on a level floor The leveling feet will stabilize the enclosure but will not account for a badly sloped floor gt Use a 13 14 mm wrench to adjust the four leveling feet Ensure that the system is level Caution Do not move the enclosure after the leveling feet A N have been lowered Floor Anchoring if applicable Anchor the UPS enclosure to the floor
6. Note Floor anchoring bolts are not provided with the UPS Q Purchase the bolts locally minimum size M8 Follow the specifications given by the manufacturer of the floor anchoring system when bolting the UPS system to the floor Reuse the two transport brackets one on each side that were used to secure the UPS to the pallet during transport Drill two to six holes in the floor for each bracket Attach with bolts Prepare for Cables Bottom cable entry From the rear of the UPS loosen the six M4 screws from the upper cover the cable landing area on the back and remove Route the cables from the slanted back plate up cs through the punched ae bracket and into the cable landing area Fasten the cables with cable ties Note A conduit box part no SUVTOPT001 or Q SUVTOPT002 is available as an option Connect the AC Input and AC Output Cables Warning Use compression type lugs ONLY Do not loosen or add cables to any factory preinstalled cables on busbars Use the front part of busbar for connection only See Also For different grounding configurations please ca see manual 990 3606 Single mains Connect the AC input cables and the neutral to the input Z A RN cable landings Connect the AC output cables and the neutral to the output cable landings D Li kes Connect the ground cables to L Eea 2 the stu
7. ds earth symbol L3 2 beneath using a screw o o N PR L o patted n Dual mains p Ip i TONE al ae NVA Me ore F E Tro fel o ETE J 5 LZ 5 l I Ip D w i Remove the three busbars A B and C by removing two M6 screws from each busbar Connect the AC input cables and the neutral to the input cable landings Connect the bypass cables and the neutral to the bypass cable landings Connect the output cables and the neutral to the output cable landings Connect the ground cables to the studs earth symbol beneath using a screw Connect the DC Battery Cables if applicable Connect battery cables BAT BAT and N to the battery cable landings Connect the Communication Cables A Warning Make sure that the UPS is completely OFF as the connectors are very close to the power busbars J106 XR Battery Enclosure and J108 EPO Note Use only 1 12 mm copper wire for the connection of the Emergency Power Off EPO and other optional equipment Note The UPS must be connected to either a dry contact or a 24 VDC EPO Emergency Power Off switch Note The external EPO 24 VDC 1500 mA circuit can be supplied through other vendors Note Always follow the pin connection p
8. rocedures from the top and work down J106 8 1 J108 1 6 J108 pin connections Normally open EPO Normally open EPO return Normally closed EPO Normally closed EPO return 24 V SELV supply SELV ground ooh whd J106 pin connections Ext charging control return External control of charging Q3 active return Q3 active Battery measurement supply Battery unit quantity Max battery temperature DO wo fF Oo D SN o 1 Battery measurement return Should be used with MGE Galaxy 3500 XR Enclosures EPO wiring pin connections J108 Connect the EPO cable using one of the following four wiring configurations 1 Dry Contacts Normally Open EPO is activated when pin 1 is connected to pins 3 and 5 Connections 2 4 6 3 5 and 1 2 24 V Normally Open EPO is activated when an isolated SELV 24 VDC voltage is supplied on pin 1 with reference to pin 2 Connections 3 5 and 4 6 3 Dry Contacts Normally Closed EPO is activated when a connection from pin 3 to pin 5 is opened Connections 4 6 4 24 V Normally Closed EPO is activated when a SELV 24 VDC voltage is removed from pin 3 with E EPO circuit reference to pin 4 Pin connections J106 UPS Pins 1 to 4 are for battery measurement only applicable to Charging control MGE Galaxy 3500 XR Battery Enclosures see J200 drawing switc Pins 5 and 6 are for external maintenance bypass Q3 auxilia
9. ry switch N C type When Q3 is closed signals are fed back to the UPS controller see Q3 drawing 3 J200 XR Pins 7 and 8 are for external charge control When 7 and 8 are E 2 Batteries closed the UPS charges batteries with a pre defined 1 percentage 0 25 50 75 100 of the maximum charging power To be used in generator applications or if special codes require control of charging When Q3 is closed signals are fed back to the UPS controller XR battery enclosure Za fiil 44 a hae LRU A E y I J BAT MEY 4 q N Dee d ha e z m a e rer oe mo Note When connecting the Q3 auxiliary signal use gold plated N C auxiliary switch Q Note Reinstall the cable landing cover Connect APC communication options Note The cable routing of the power chute software and Q the temperature sensor is identical Note The temperature sensor is provided in a plastic bag attached to the front of the UPS behind the front panel Front panel removal Use a coin or similar to turn the two black lock devices on either side of the f display in the direction of each other to a vertical positon Push the front panel upwards and pull it outwards to disengage the locking device at the top of the enclosure Lift the front panel free of the two slots at the bottom of the enclosure