American Power Conversion AP7610 User's Manual

image

Contents

1. AP9871 Power cord available for The following power cord can be purchased from APC purchase APC SKU Description Cord Ends IEC 320 C19 AP9871 to gt Vh NEMA L6 20 2 Rack Power Distribution Unit AP7610 Safety and Grounding Read the following information before installing or operating your APC AP7610 Rack PDU The Rack PDU is intended only for use with four wire grounded connections on APC Uninterruptible Power Supplies UPS Do not plug the Rack PDU into a wall outlet or other device This Rack PDU is intended to be installed and operated only with the provided mounting hardware This Rack PDU is intended for indoor use only Do not install this Rack PDU where excessive moisture or heat is present Do not use extension cords or adapters with this Rack PDU Check that the power cord plug and socket are in good condition Disconnect the Rack PDU from the power outlet before you install or connect equipment to reduce the risk of electric shock when you cannot verify grounding Reconnect the Rack PDU to the power outlet only after you make all connections Install the Rack PDU so that the power plug may be disconnected for service The socket outlet shall be installed near the equipment and shall be readily accessible Install the Rack PDU so that there is not an uneven mechanical load Follow the nameplate ratings when connecting equipment to the supply circuit Do not overload the
2. circuits An overload condition could put your over current protection at risk or cause problems with your supply wiring This Rack PDU contains a non replaceable lithium coin cell battery Do not attempt to replace the battery A Risk of electrical shock Use only the supplied hardware to attach the mounting brackets Caution Rack Power Distribution Unit AP7610 How to Install the PDU Overview Install the AP7610 Rack PDU in the rear top two U spaces of a rack or enclosure for overhead wiring or in the rear bottom two U spaces for under floor wiring To install the Rack PDU ina NetShelter Standard Enclosure 1 Attach a bracket to each side of the Rack PDU using the pan head screws Some enclosures may require you to recess the Rack PDU so that the back doors of the enclosure will close Note when other devices are plugged in For placement flush to rack use four pan head screws provided for each bracket For a recessed placement use two pan head screws provided through the last two holes of the mounting brackets and into the first two holes on the Rack PDU 4 Rack Power Distribution Unit AP7610 How to Install the PDU 1 Insert caged nuts provided with the enclosure on the vertical mounting rails above a notched hole at the start of the top two U spaces in your enclosure and below the notched hole at the lower end of the two U spaces 2 Align the mounting holes on the brackets with the ca
3. the Password Administrator account displayed as asterisks to users Rack Power Distribution Unit AP7610 Factory Data option Logout option System Management option To change as setting 1 Type 1 and press ENTER to move the arrow cursor to the next setting Rack PDU Configuration 2 Type 2 and press ENTER to change the selected setting 3 Type the new value and press ENTER Factory Data main menu option 4 displays the following information about the Rack PDU Model number e Serial number e Hardware revision e Date of manufacture e Firmware revision Date on which the firmware was installed You cannot change any of these items Logout main menu option 5 logs you off from the interface System Management main menu option 6 is accessible only when you are logged on as Administrator Type the number of any one of the following options and press ENTER to select it Option ae Number Option Description 1 Restart Restarts the Rack PDU RMPDU while maintaining the present settings 2 Restore Resets all parameters to their Default default settings and restarts Parameters the Rack PDU and Restart 3 Firmware Prepares to download Download firmware See How to Download Firmware to a Rack PDU on page 12 Rack Power Distribution Unit AP7610 11 How to Download Firmware to a Rack PDU During firmware downloads power wi
4. 3 5 x 17 6 x 6 in 8 89 x 44 7 x 15 24 cm Weight 7 85 lb 3 57 kg Shipping dimensions 7 15x21x9 25 in Hx W xD 19 68 x 53 34 x 23 5 cm Shipping weight 10 5 lb 4 77 kg Environmental Elevation above MSL Operating 0 to 10 000 ft 0 to 3000 m Storage 0 to 50 000 ft 0 to 15 000 m Temperature Operating 23 to 133 F 5 to 45 C Storage 13 to 149 F 25 to 65 C Humidity Operating 5 95 Storage 5 95 non condensing Compliance Approvals cUL Listed FCC Part 15 Class A UL Listed VCCI Rack Power Distribution Unit AP7610 13 Radio Frequency Interference Changes or modifications to this unit not expressly approved by the party A responsible for compliance could void the Warning Uuser s authority to operate this equipment This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with this user manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference The user will bear sole responsibility for correcting such interferenc
5. Arc www apc com Rack Power Distribution Unit AP7610 Product Description and Inventory Description The AP7610 Rack PDU mounts horizontally in any standard 19 inch EJA 310 compliant rack or enclosure This Rack PDU is metered equipped with a sensor that measures the current being used by the Rack PDU and any devices connected to it The value shown on the display interface is the aggregate current of an individual phase This value will generate an alarm if it is outside the threshold values that you define This Rack PDU has three L5 20 outlets three L6 20 outlets and a L21 20 plug Inventory Description Part Number Quantity Serial cable 940 0144 1 Rack mount brackets 870 1466 2 Product Description and Inventory AP7610 compatible Rack The AP7610 Metered Rack PDU requires connection to an additional PDUs Rack PDU The following APC Rack PDUs are compatible with the AP7610 Compatible APC 120V PDUs PDU Plug Outlets Manageable AP9563 L5 20 Ten NEMA 5 20 No AP9551 L5 20 Fourteen NEMA 5 15 No AP9228 L5 20 Sixteen NEMA 5 15 Yes Compatible APC 208 V PDUs PDU Plug Outlets Manageable AP9558 L6 20 Twelve IEC 320 C13 No AP9559 IEC 320 C20 Ten IEC 320 C13 No Two IEC 320 C19 AP9554 IEC 320 C20 Fourteen IEC 320 C13 No AP9229 IEC 320 C20 Eight IEC 320 C13 Yes j Using these Rack PDUs with AP7610 requires an additional power cord
6. e This Class A digital apparatus complies with Canadian ICES 003 Cet appareil num rique de la classe A est conforme a la norme NMB 003 du Canada COE ISR EICAMLCWET COE ett SIRE ZON A CEAT SBA FUAPTLEAOD RISE RIZT CEMBVEF VCCI A Arc www apcec com APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways e Visit the APC Web site to find answers to frequently asked questions FAQs to access documents in the APC Knowledge Base and to submit customer support requests Wwww apc com Corporate Headquarters Connect to localized APC Web sites for specific countries each of which provides customer support information www apce com support Global support with FAQs knowledge base and e support e Contact an APC Customer Support center by telephone or e mail Regional centers APC headquarters U S Canada 1 800 800 4272 toll free Latin America 1 401 789 5735 USA Europe Middle East Africa 353 91 702055 Ireland Japan 0 35434 2021 Local country specific centers go to www apc com support contact for contact information Contact the APC representative or other distributor from whom you purchased your APC product for information on how to obtain local customer support Entire contents copyright 2003 American Power Conversion All rights reserved Reproduction in whole or in pa
7. ged nuts you installed in step 1 and insert four mounting screws provided with the enclosure to secure the brackets to the enclosure Rack Power Distribution Unit AP7610 5 Operation Display interface Press to select line Press for 10 seconds gt O APC to invert display www apc com Rack Mount Power Distribution Unit ated Q O DP LN L2 L3 Control button e Press to change the phase of the current displayed on the digital display e Press and hold for five seconds to view the orientation hold for an additional five seconds to change the orientation Display of the current used by the Rack PDU and attached devices e Shows the aggregate current for the phase corresponding to the Phase Indicator LED that is illuminated e Cycles through all three phases in 3 second intervals Phase indicator LEDs e Indicates the phase corresponding to the current listed in the digital display e Indicates normal green warning yellow or alarm red condition Rack Power Distribution Unit AP7610 Operation Rear of AP7610 Serial port Access internal menus by connecting this port RJ 11 modular port to a serial port on your computer using the supplied serial cable part number 940 0144 Status LED Indicates the status of the network connection and the state of the Rack PDU Ethernet port Connects the Rack PDU t
8. ll not be interrupted to the Rack PDU outlets Note 1 Go to www apc com tools download to see if there is a more recent firmware version for your type of Rack PDU 2 Access the Rack PDU internal menus through a serial port connection Follow the instructions in How to configure through a serial port connection on page 8 3 Log on to the Rack PDU as an Administrator 4 Type 6 for System Management on the Main menu and press ENTER 5 Type 3 for Firmware Download on the System Management menu and press ENTER 6 From the Firmware Download menu a Type 1 and press ENTER to initiate a download The menu displays C repeatedly and the display interface displays dL b Select the Transfer pull down menu from the menu bar c Select Send File from the Transfer pull down menu d Browse for and select the firmware file you copied to your computer e Set the protocol to Xmodem and press the Send button When the firmware download is complete the display interface refreshes and displays the current in amps 12 Rack Power Distribution Unit AP7610 Specifications AP7610 Electrical Input connector NEMA L21 20 plug Output connectors Three NEMA L5 20 outlet Three NEMA L6 20 outlet Nominal input voltage 208 3PH Acceptable input voltage 100 125 200 250 VAC Maximum Input Current 16A per phase Load Capacity 7200 Physical Size H x W x D
9. o the InfraStruXure network using a CAT 5 network cable Link LED Indicates whether there is activity on the network Alarm conditions Configure warning and alarm limits through the internal menus using a serial port connection The Rack PDU shows warning and alarm conditions as follows Phase Indicator LED Displays yellow for a warning and red for an alarm Digital display If one phase is at or above the warning or alarm limit the display shows the current for that phase If more than one phase is at or above the warning or alarm limit the display cycles among those phases displaying their current Control Button Pressing this button causes the digital display to display the current for the next phase for 30 seconds Then it returns to the display of the current for any phases that are at or above the warning or alarm limits A Do not exceed the maximum voltage and current ratings listed on the rear panel of the Rack PDU Warning Rack Power Distribution Unit AP7610 7 Rack PDU Configuration How to configure through a serial port connection 1 Connect an available serial port on your computer to the serial port on the Rack PDU shown below using the supplied configuration cable 940 0144 2 Run a terminal emulation program such as Windows HyperTerminal 3 Configure the following settings for the serial port 19 200 bps no parity 8 data bits 1 s
10. rt without permission is prohibited APC the APC logo InfraStruXure and NetShelter are trademarks of American Power Conversion Corporation and may be registered in some jurisdictions All other trademarks product names and corporate names are the property of their respective owners and are used for informational purposes only 990 1474 xQ 14 4 08 2003 InfraStruXure APC
11. top bit no flow control Some terminal emulation programs require that a device be disconnected and then reconnected for Note the new serial port settings to take effect 4 Press any key on the computer to display the Rack PDU login screen which contains the username and password prompts 5 Log on by using the user name and password for the appropriate access level Access Level Default Default Password User Name Administrator Press Type ape in ENTER lowercase User Press Press ESC ENTER Rack Power Distribution Unit AP7610 Using the menus Status Information option Rack PDU Configuration To view a menu type the associated number and press ENTER Users can view all data but only administrators can configure parameters The main menu has the following options Option Number Option Access 1 Status User and Administrator Information 2 Rack PDU Users can display the Configuration parameters Administrators can configure them 3 Device Data Users can display the parameters Administrators can configure them 4 Factory Data User and Administrator 5 Logout User and Administrator 6 System Available only when you Management are logged in as Administrator Status Information main menu option 1 displays the output current in amps for each phase from the Rack PDU and reports if the load is at or above the configured limits for ou
12. tput current Rack Power Distribution Unit AP7610 Rack PDU Configuration Rack PDU Configuration Rack PDU Configuration main menu option 2 provides the following option options Ri ane Option Access 1 Warning and Alarm Users can display Threshold Data for output the parameters current Administrators can configure them 2 Audio Visual Indicator Settings to enable or disable the audible alarm and digital display and to set the orientation of the display Settings are displayed for each phase e To change a warning and alarm threshold type the number of the setting press ENTER type the new value and press ENTER again e To change an audio visual indicator setting a Type 1 and press ENTER to move the arrow cursor to the next setting b Type 2 and press ENTER to change the selected setting c Type the number listed for the setting you want and press ENTER Device Data option Device Data main menu option 3 has the following settings 10 Setting Description Access Product A unique name that you Users can Name assign to the device display the parameters Product For example the enclosure Administrators Location in which the Rack PDU is can configure installed t r Contact For example a name or Information phone number of a person to contact Log The number of minutes a Timeout user can be inactive before mins being logged off Admin The password of