ADTRAN 6-Amp Power User's Manual
Contents
1. AA AG BATTERY VOLTAGE a gi ga INPUT RED BOTH INPUTS SAW 120 vi THIS UNIT MAY BE POWERED BY 3 SOURCES 375A MAX DISCONNECT ALL SOURCES BEFORE SERVICING AC FAIL UNIT FAIL OVERLOAD CHARGING STATUS 60HZ GRN OK GRN CHARGING OR CHARGED RED FAIL OR OVERLOAD YEL DISCHARGING RED FULLY DISCHARGED U L LT E ALL LEDS OFF WHEN NO AC amp BATTERY VOLTAGE lt 35V CLS US ais s E NS 6A OUTPUT AN A LISTED C C 3A INPUT 3A INPUT Z i Ba e Ko B JMP JMP OTECTION AGAINST EPLACE ONLY WITH THE RATING OF FUSE Figure 1 Total Access PS BC Features The Total Access PS BC features include the following e 54 VDC at 6 amps output for multiple use e Modular connections for two backup battery packs e Modular power output connection e LED status for VAC VDC and battery charging e Full battery recharge in less than eight hours e Two PS BC configuration options available 61180043L2 5D 1 Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice A e Fuse protection e Positive ground e Battery Pack mounting hardware included e Completely automatic operation e Multiple protection features e Uninterrupted power output if backup battery connected e Meets NEBS Level 3 all requirements of GR 63 CORE and GR 1089 CORE e FCC and UL 60950 compliant Document Review This document contains important pre installation information Craft
2. ADRAN Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice Document Number 61180043L2 5D CLEI VAPUKTOC_ _ June 2005 Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice rrr Trademarks Any brand names and product names included in this manual are trademarks registered trademarks or trade names of their respective holders To the Holder of the Manual The contents of this publication are current as of the date of publication ADTRAN reserves the right to change the contents without prior notice In no event will ADTRAN be liable for any special incidental or consequential damages or for commercial losses even if ADTRAN has been advised thereof as a result of issue of this publication ADRAN 901 Explorer Boulevard P O Box 140000 Huntsville AL 35814 4000 256 963 8000 2005 ADTRAN Inc All Rights Reserved Printed in U S A Kee O li 61180043L2 5D Revision History Revision Date Description D June 2005 Updated to remove Dual PS BC Jumper Cable Document format updated with revision D Conventions The following typographical conventions are used in this document This font indicates a cross reference link First time references to tables and figures are shown in this font This font indicates screen menus fields and parameters THIS FONT indicates keyboard keys ENTER ESC ALT Keys that are to be p
3. ADTRAN will replace or repair this product within the warranty period if it does not meet its published specifications or fails while in service Warranty information can be found at www adtran com warranty Refer to the following subsections for sales support Customer and Product Service CAPS requests or further information ADTRAN Sales Pricing Availability 800 827 0807 ADTRAN Technical Support Pre Sales Applications Post Sales Technical Assistance 800 726 8663 Standard hours Monday Friday 7 a m 7 p m CST Emergency hours 7 days week 24 hours day ADTRAN Repair CAPS Return for Repair Upgrade 256 963 8722 Repair and Return Address Contact CAPS prior to returning equipment to ADTRAN ADTRAN Inc CAPS Department 901 Explorer Boulevard Huntsville Alabama 35806 2807 61180043L2 5D A 1 Carrier Networks Division 901 Explorer Blvd Huntsville AL 35806
4. Battery Charge Discharge CAUTION To prevent battery discharge prior to system operation do not con nect the battery to the PS BC until the AC power is connected or imminent Each battery has a hardwired 6 foot battery charge discharge wire that originates at the battery housing and terminates at a modular connector The PS BC has two mating connector ports each labeled 48V 3A INPUT It does not matter which battery connects to which port To prevent heat buildup the battery charge current is limited to 1 amp per battery This elimi nates the need for temperature compensation Alarm Wiring The alarm relay output originates at a modular connector with a 6 foot wire stub Wiring termination of the output is customer designated The alarm outputs AC Fail Battery Low Voltage are assigned the following wire color codes e ACF orange orange white e BV blue blue white OPERATION The PS BC starts operation when AC or battery power is applied During operation ambient temperature can increase up to 50 C without affecting output If ambient temperature increases beyond 50 C output must be derated At 70 C ambient output load is limited to 5 amps CAUTION External PS BC surfaces can become hot during operation above 50 C ambient temperature MAINTENANCE The Total Access PS BC does not require routine maintenance for normal operation ADTRAN does not recommend that repairs be attempted in the field Repair servi
5. PP NN 2 61180043L2 5D Description Ca QC Battery Disconnect Protection Circuit During battery operation a protection circuit disconnects battery from the main output when battery voltage drops below 39 VDC preventing over discharge When AC returns the main output provides regulated 54 VDC batteries recharge and the system returns to normal Refer to LED Indication After the protection circuit initiates the LEDs remain on red continuing to slowly drain the battery When battery voltage drops to 35 VDC all load is removed from the battery If AC power will not be available for an extended period several days disconnect the battery to prevent unnecessary discharge DC Over Voltage Protection The PS BC has a protection circuit that disables the rectifier to protect the load from a high output voltage caused by rectifier failure The backup battery or redundant PS BC supports the load in this instance The over voltage event can permanently disable the PS BC Confirm this by performing the following procedure 1 Disconnect the PS BC from the AC source 2 Wait 30 minutes minimum 3 After 30 minutes plug back into the AC source A If the unit has recovered the AC FAIL UNIT FAIL OVERLOAD LED will turn on green and the unit returns to service If the LED does not turn on green replace the PS BC Alarm Relays There are two uncommitted alarm relays associated with PS BC operation e AC Fail ACF Alarms if AC
6. Single or Dual Battery AA AA AA AA AN 2 PS BC Mounting Location 4 4 4 2 2 Battery Disconnect Protection Circuit 3 DC Over Voltage Protection 3 OA CA AA AA 3 PUSO courses else MAGANG PAL NUAMD ia a ees NAG Re ee AKDANG MAMASDAN NA 3 LFEMACICAN ON ae sensata a a NAIA a NGA aay 4 IKIWA AA AA APA 4 La IA IIIA III io ous 5 Shipping Contents 444444444444 44444 essieu eens 5 Mounting Me Pe BC sa ctcestisesrrsvan dead habeas See deena he cae AA aa mo a de 6 Alternate Mounting 6c eee eee eens 7 PIOVISIONING serpere auccdneaam rear ae eno bes ee bee ea as aes aes 7 Wiring DescriptioNS asananansnzanazanananazananzananana naa 7 GIOUN A UAE da a a WA aa kai 7 120 VAC POWER AT 7 DC Fower QUWDUU lt aaa pape NG pre apa e Ge eee ow Bein ene MA meas Ee a ee Goo NGA eres ra 8 PS BC to Battery Configurations 8 Battery Charge Discharge ee eee eee ees 9 PO AA alo oo cers ea do Shy oe en ee ee eee ee dodo E do tbe AS 9 ODOral N lt a veias Cee eee eee eee aed Sea eee eee neue oe ae ae eee eee eens 9 MGC eee eee wee eh APA ee eee See E ULE ews re wee eee 9 FUSO e rasos Soha e nee ee eee AA ee eee eee ed ees aeons 9 DOCCINICHUONS noria ee e
7. or modifications not expressly approved by ADTRAN could void the user s authority to operate this equipment BN 4 61180043L2 5D Installation INSTALLATION ka CAUTION SUBJECT TO ELECTROSTATIC DAMAGE OR DECREASE IN RELIABILITY HANDLING PRECAUTIONS REQUIRED After unpacking the Total Access PS BC inspect it for damage If damage has occurred file a claim with the carrier then contact ADTRAN Customer Service Refer to Appendix A Warranty for further information If possible keep the original shipping container for returning the PS BC for repair or for verification of shipping damage CAUTION Electronic modules can be damaged by ESD When handling mod ules wear an antistatic discharge wrist strap to prevent damage to electronic components Place modules in antistatic packing mate rial when transporting or storing When working on modules always place them on an approved antistatic mat that is electrically grounded Shipping Contents The contents include the following items e Rackmount 6 Amp Power Supply Battery Charger e Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice e Appropriate wiring PS BC to AC source hardwired PS BC to load PS BC alarm output e Battery Pack mounting hardware Separately purchased Rack Mounting Kits for the PS BC are available for the following racks e 19 inch P N 1175050L1 e 23 inch P N 1175051L1 61180043L2 5D 5 Total
8. personnel should review the entire document as part of installation planning DESCRIPTION The PS BC rectifier is part of the Total Access Rackmount AC Power Supply Backup Battery System APS BBS The unit is designed to work in conjunction with one or two ADTRAN backup battery packs P N 1175044L1 Originally designed for the Total Access 1500 system the PS BC can be used in any appli cation using 120 VAC input and requiring up to 54 VDC 6 amps output In the Total Access 1500 configuration the rectifier performs AC to DC conversion and when used with the dual battery provides up to eight hours of backup power for a fully populated Total Access 1500 bank 96 FXS circuits with up to 50 percent off hook circuits at any one time For general use the rectifier receives AC power from a standard 120 VAC wall outlet and converts this to 54 VDC 6 amp output to the designated load plus recharging the single or dual battery or maintaining battery at peak charge Each battery has four series connected 12 volt rechargeable cells Single or Dual Battery Each battery string is rated for 3 amps of current and 7 amp hours of capacity Dual batteries are required if the load exceeds these ratings during AC power failure backup battery mode PS BC Mounting Location The PS BC normally mounts to the associated battery pack The unit can also mount to a special bracket within a cabinet or mount external to a cabinet against a wall HY
9. Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice Mounting the PS BC The PS BC housing occupies a nominal area 15 35 inches with mounting tabs wide by 3 45 inches high and is designed so the four mounting tab screw holes align to threaded screw holes on the ADTRAN battery pack housing This procedure assumes that the battery pack is mounted in the designated 19 inch or 23 inch rack Hardware for mounting the PS BC to the battery pack is included To mount the PS BC perform the following steps 1 Ensure a 120 VAC wall outlet is within reach of the PS BC 10 foot power cord 2 Determine the most convenient direction to view the status LEDs and position the PS BC accordingly 3 Align the mounting tabs to the threaded mounting holes on the battery pack 4 Using the included sems screws with star washer mount the PS BC to the battery pack Tighten fasteners firmly See Figure 2 for a representative example of the PS BC mounted to the battery Figure 2 PS BC Mounted On Battery Pack EE 6 61180043L2 5D Wiring Descriptions En Alternate Mounting Two alternate mounting methods include mounting directly to a wall using customer supplied wood screws or to a 16 gauge steel bracket P N 3265555 that mounts in the cabinet Bracket mount location is normally at the battery position when batteries are mounted external to the cabinet The bracket has threaded mounting hole
10. ces may be obtained by returning the defective unit to ADTRAN Refer to Appendix A Warranty for further information Fuse If the fuse fails replace with a fuse of identical type and rating 61180043L2 5D 9 Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice a SPECIFICATIONS Power Factor specifications for the Total Access PS BC are listed in Table 2 PS BC specifica tions are listed in Table 3 Table 2 Power Factor and Efficiency Power Output vs Efficiency Efficiency 50 watts gt 98 150 watts gt 99 325 watts gt 99 gt 81 11 watts gt 89 18 watts gt 91 29 watts Table 3 PS BC Specifications Specification Description Environmental Operating Temperature Derated Operation Linear Storage Temperature Relative Humidity Max Heat Dissipation 40 C to 50 C 90 C to 70 C 0 05 amp C 40 C to 85 C 95 percent noncondensing 29 watts at 325 watts output 50 watts maximum during overload Physical Height 3 45 inches Width 15 35 inches with mounting tabs Depth 2 92 inches Weight 5 5 pounds Electrical AC Input 120 Volts 3 75 amps max 60 Hz DC Output 54 Volts 6 amps Max power up to 50 C 6 amps Max power 70 C 5 amps Power Output 325 watts Compliance NEBS Level 3 UL 60950 ETL Listed FCC Part 15 Class A 10 61180043L2 5D Appendix A Warranty WARRANTY AND CUSTOMER SERVICE
11. ek Kee eek AA 10 Appendix A MEU A 1 Warranty and Customer Service nananazanana A 1 ADTRAN Sales A 1 ADTRAN Technical Support A 1 ADTRAN Repair CAPS nnnn A 1 Repair and Return Address A 1 61180043L2 5D V Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice Figure 1 Figure 2 Figure 3 Table 1 Table 2 Table 3 vi Figures Total Access PS BC 1 PS BC Mounted On Battery Pack 6 Wiring Block Diagrams 8 Tables LED DESCUIDOS narrar Oe sa haa da ete eee ena eb PA eae 4 Power Factor and Efficiency 10 PS BC SPeCilICAONS 5 224 22 donee a bee se o eee AA ee oe we 10 AE Cc 61180043L2 5D Total Access Rackmount 6 Amp Power Supply Battery Charger GENERAL This practice is an installation and maintenance guide for the ADTRAN Total Access Rackmount 6 Amp Power Supply Battery Charger PS BC Figure 1 illustrates the PS BC P N 1180043L2 right and left side panels
12. fails the rectifier overloads or the rectifier fails e Battery Low Voltage BV Alarms if either or both battery voltage drops below 42 VDC Fuse A standard 5x20 mm 5 amp fuse adjacent to the AC power cord protects AC power feed overload in case of rectifier failure 61180043L2 5D 3 Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice 11 rrr LED Indication A set of three PS BC multi color LEDs provide status for AC DC and battery charge condi tions See Table 1 for LED descriptions Descriptions are also labeled on the PS BC Table 1 LED Descriptions LED Color Description AC FAIL UNIT FAIL OVERLOAD Green Normal 120 VAC operation Red AC fail or rectifier overload or fail BATTERY VOLTAGE Green Battery 1 and Battery 2 greater than 42 VDC Yellow Battery 1 or Battery 2 less than 42 VDC Red Battery 1 and Battery 2 less than 40 VDC CHARGING STATUS Green Battery 1 and Battery 2 charged or recharging Yellow Battery 1 or Battery 2 discharging Red Battery 1 and Battery 2 fully discharged All LEDs Off AC lost Battery less than 35 VDC Note Descriptions are the same for a single battery Compliance This device complies with Part 15 of the FCC rules Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation Changes
13. ressed simulta neously are shown with a plus sign ALT X indicates that the ALT key and X key should be pressed at the same time This font indicates references to other documentation and is also used for emphasis This font indicates on screen messages and prompts This font indicates text to be typed exactly as shown This font indicates silkscreen labels or other system label items This font is used for strong emphasis NOTE Notes inform the user of additional but essential information or features CAUTION Cautions inform the user of potential damage malfunction or dis ruption to equipment software or environment WARNING Warnings inform the user of potential bodily pain injury or death 61180043L2 5D lil Total Access Rackmount 6 Amp Power Supply Battery Charger Installation and Maintenance Practice Training ADTRAN offers training courses on our products These courses include overviews on product features and functions while covering applications of ADTRAN s product lines ADTRAN provides a variety of training options including customized training and courses taught at our facilities or at customer sites For more information about training please contact us Training Phone 800 615 1176 ext 7500 Training Fax 256 963 6700 Training Email training adtran com BE ice IV 61180043L2 5D Contents AA ii AA KU AA AAA 1 Se o E A 1 Document Review 22 aaa ee eee eee ee 2 DESC ULAP AA AA AA A 2
14. s that align to the PS BC mounting tabs The PS BC can be mounted to either side of the bracket or two PS BCs can be mounted one on each side Openings in the bracket allow for wire management Hardware for bracket mounting is purchased from ADTRAN When determining the alternate mounting location ensure supplied cabling reaches the designated termination point including dressing and lacing Provisioning Aside from various PS BC and battery mounting and wiring configurations there are no end user controls adjustments or options associated with the PS BC WIRING DESCRIPTIONS The wiring required for the single PS BC and dual battery configuration is included CAUTION All grounds must terminate at a known ground location Check metal to metal contact on all ground connections Do not stack or combine grounds Ensure ground circuit continuity Ground A ground post adjacent to the PS BC fuse is available for frame ground WARNING Do not connect AC power or make battery connections until all other connections have been made for the designated installation and protective covers and shields have been installed 120 VAC Power Input AC input is through a 10 foot wire with a three prong grounded plug on the end The line is hardwired to the PS BC NOTE In the optional two PS BC configuration a fully redundant system requires that each PS BC have an independent AC source 61180043L2 5D 7 Total Access Rackmount 6 Amp Power S
15. upply Battery Charger Installation and Maintenance Practice E a DC Power Output The 4 foot long three conductor PS BC power output wire originates at the 54V 6A OUTPUT modular connector and terminates at three 6 ring lugs for customer designated connection Wire color code is as follows e Red 54 VDC e Black Return e Green Ground PS BC to Battery Configurations The basic design configuration consists of one PS BC with two batteries A variety of other configurations are possible with more or less redundant capability see Figure 3 for standard configurations I and II Configuration I Ia Ib I PS BC no battery Ia PS BC 1 battery string Ib PS BC 2 battery strings A Load B Configuration II Ila IIb IIc IHd IT 2 PS BC no battery Ila 2 PS BC 1 battery string IIb 2 PS BC 2 battery strings IIc 2 PS BC 3 battery strings Ild 2 PS BC 4 battery strings This configuration shows adding battery strings alternately to PS BC A and B Other wiring configurations are optional Figure 3 Wiring Block Diagrams These would include one or two PS BCs none one or two batteries or some combination of PS BC and battery The most reliable configuration would be two PS BCs with two batteries each and with independent AC sources The two PS BC outputs would terminate at a single load that has primary and secondary power sharing terminals BE ice 8 61180043L2 5D Operation Aaaa
Download Pdf Manuals
Related Search
Related Contents
Memup POP KEY 2GB Solar LED L-858Y/R/L/B Signs (SSS) OPERATORS MANUAL IMPULSE®.Link 4.1 Wireless Diagnostics System Tektronix Pill Reminder Device DC 504 User's Manual Tiger Select - Ion Science 取扱説明書 - Clarion 9399-APSIE - Introducing the APS Import/Export Utility Chapter 3 - AutomationDirect Copyright © All rights reserved.