1. PANDUIT Installation Guidelines 10Gig SFP Direct Attach Copper Cable Assembly PN533A Introduction As virtualization consolidation and convergence initiatives continue to expand in Data Centers so do the demands placed on the physical infrastructure To meet the needs for higher bandwidth along with lower power interconnects Panduit offers 10Gig SFP Direct Attach Copper Cable Assemblies This high speed data transport capability is ideal as server virtualization becomes more prevalent 10Gig interconnects are needed to facilitate effective server utilization to run multiple virtual machines as well as server consolidation By incorporating 10Gig SFP Copper Cable Assemblies into the physical infrastructure organizations can achieve 10Gig performance without additional signal processing or conversion This provides an ideal low power low latency 10 Gbps server interconnect option for top of rack switching deployments Passive 10Gig SFP Copper Cable Assemblies generally have a reach limitation of 7 meters 23 feet and many network deployments will consist of a mixed copper fiber solution with Panduit 10Gig OM3 fiber Panduit 10Gig SFP Direct Attach Copper Cable Assemblies Panduit 10Gig SFP Copper Cable Assemblies are factory terminated and constructed of high speed twin axial shielded cable with SFP modular connectors on each end The cables are compliant to the SFF 8431 specification The Small Form Factor
2. Panduit Net Access Cabinets Tak Ty Hook and Loop Cable Ties should be used to bundle the cables together and tie them to the strain relief bars and cable managers This should be done carefully to ensure the cables are firmly in place and will not move but not so tight as to deform or stress the cable jacketing Cable Installation Tips and Best Practices There are a few practical steps that can be taken during installation to optimize the effectiveness of the layout For overhead cable routing place the switches near the top of the racks For under floor cable routing place the switches near the bottom of the racks Do not route SFP Cable Assemblies parallel to power cables they should only cross at right angles Do not route cables in front of fans or air ventilation areas of the rack Do not kink cables Do not twist connectors Use Tak Ty Hook and Loop Cable Ties to secure cables do not use plastic cable ties Slack Management Standard cables come in 1 meter 3 3 ft increments Often installers will standardize on a small number of standard lengths to simplify the bill of material One cannot always anticipate possible infrastructure obstacles on site so it is good practice to estimate long when defining cable lengths Therefore it is possible that there will be cable slack and this needs to be managed properly to ensure reliable long term performance The slack in the cable should be shaped and looped so as not to violate ben
3. committee approved and published SFF 8431 in July of 2009 with Panduit as a member and a signee The document covers host ports optical transceivers and copper cables Appendix E specifies direct attach copper cable assemblies These passive cable assemblies offer a low power low latency low cost option for a 10Gig interconnect They may be plugged into SFF 8431 SFP compliant ports and are interchangeable with fiber optic transceivers Note some system vendors have designed copper only or fiber only SFP ports so be sure to confirm host port capabilities with the active equipment vendor The Panduit 10Gig SFP Direct Attach Cable Assemblies are constructed with high frequency 10 GHz 100 ohm parallel shielded pairs with two wire pairs in the cable Panduit uses 30AWG for cables less than 4 meters in length and uses 24AWG for 4 meter and longer cables The connector consists of a paddle card with patent pending circuitry to ensure superior high frequency signal integrity is housed in a die cast backshell and incorporates a latching mechanism that allows insertion and de insertion into the mechanical cage of a host port on the active equipment The same host port cage can accept optical transceivers or direct attach cable assemblies The back of the paddle card has pads which form the contacts to the 20 pin host connector inside the cage The connector has an EMI shroud that provides 360 degrees of contact with the host cage to ensure e
4. ber serial number and cable length in meters Panduit Corporation 2010 Page 2 of 7 10Gig SFP Copper Cable Assembly Installation Guidelines PN533A SFP Cable Assembly Connector Pin Out 10 44 Bottom of Board as viewed y from top through Toward host board fononononl fnolnalnal 20 SFP Connector Module Contact Assignments Top and Bottom are backwards SFP Pin Assignment Definitions Logic 1 Symbol Power Description Sequence Order Case Note2 Modulecase _ _ o O o VeeT 1 Module transmitter ground ________ 3 Mod ABS 3 Module absent connected to VeeT or VeeR in module LVTTL O i eg Receiver loss of signal indication N A 4 4 od emco RD 3 Receiver inverted data output C veet 1 Module Transmitter Ground SSS 1 Labeling as Input 1 and Output O are from perspective of the module cable connector 2 The case makes electrical contact to the host cage before any board edge contacts are made 3 The module signal grounds VeeR and VeeT should be isolated from the module case 4 Tx fault Tx_disable rate select and loss of signal functions are not implemented in passive copper cable assemblies 5 SDA and SCL are the data and clock pins for the 12C interface to the EEPROM on board the module The registers are defined in SFF 8472 6 Mod_ABS is an output pin to indicate if the module is present in the host port It is connected to ground in the modu
5. d radius Slack or loops should be securely tied in place so they do not slip or sag over time Panduit Corporation 2010 Page 5 of 7 10Gig SFP Copper Cable Assembly Installation Guidelines PN533A General Deployment Topology Guidelines Within a single 84 inch 45 RU cabinet conservatively the longest connection will be 7 ft or 2 1 meters to reach from the top U to the bottom and approximately 1 5 ft or 0 45 m to route to any port on either end A 3 meter cable should be adequate to connect any two ports within a cabinet Example cabinet with 2 top of rack switches ToR and 20 2U servers with Dual SFP NICs total of 40 SFP cables 84 inches 7ft 2 1 m Conservatively longest cable required to reach farthest port is 2 1 2 x 0 45 3m in Domme A a a ADET TA CIGG ea Swe Fe gt t jee my f n od wS gosi gt F e FO aus g M Example of 5 cabinet Pod with 80 2 RU servers distributed over 5 cabinets with 4 ToR switches in center cabinet requires 160 SFP cables with longest cable of 5m Example of 3 cabinet Pod with 40 2 RU servers distributed over 3 cabinets with 2 ToR switches in center cabinet requires 80 SFP cables with longest cable of 4m Panduit Corporation 2010 Page 6 of 7 10Gig SFP Copper Cable Assembly Installation Guidelines PN533A 6x2ft 12ft 3 6m z m gt TET a E r ie E a Ge kra a i ba ce Ee F
6. e can also misalign the plug in the equipment mounted receptacle These forces may degrade performance or even possibly damage the connector and lead to failure It is important to observe and maintain proper cable bend radius and equally important to provide adequate and secure strain relief on the cable In order to help maintain proper bend it is recommended to pre form the strain relief bend on the cable before installing The minimum recommended bend radius is 5X the cable outside diameter O D for a single time bend and 10X the OD for repeated bends Minimum Bend Radius Guide Cable Wire Gauge O D Min Bend Radius r AWG30 4 1 mm 0 16 in 20 5 mm 0 80 in AW G24 5 6 mm 0 22 in 28 mm 1 10 in To help manage the weight of bundled cable and ensure they do not sag over time a cable manager or strain relief bar should be installed to support SFP Copper Cable Assemblies and provide strain relief along the horizontal plane Strain relief bars facilitate the correct alignment of cable and connector into the port and help installers observe manufacturer and bend radius requirements of cable close to the connecior The strain relief bars also help keep cables routed clear from spaces directly behind server and switch equipment reducing thermal resistance through the equipment and promote effective cooling and airflow To ensure long term reliability it is recommended to use a rack with integral cable management features such as the
7. gt r g 3m to oe ime a g s feat T Ge ce r EAS E a farthest re os Yl E jb 4 a A ieee Os Si bis port bu a Pa ni PITTA EA a en oe ri E E ee On Oe oe Gane E a j a E Fg kg hy ENF Ser DI m Using Middle of Row switching topology an 8 cabinet row may be achieved with 7m cables This has two switch cabinets in the center and 3 server cabinets on each side If all switching were placed in a single center cabinet a 9 cabinet row with 8 server cabinets may be covered To enable longer row fiber and SFP optical transceivers are required A hybrid solution of Panduit 10Gig SFP copper for the inner cabinets and Panduit 10Gig OM3 fiber to the outer cabinets will be the cost effective solution E mail For Instructions in Local Languages and Technical Support Eny HD Ay T cs panduit com Fax www panduit com resources install_ maintain asp www panduit com 708 444 6993 Page 7 of 7
8. le cable connector ra rd S na na S ra ra Panduit Corporation 2010 Page 3 of 7 10Gig SFP Copper Cable Assembly Installation Guidelines PN533A Installing and Removing 10Gig SFP Copper Cable Assemblies To attach a cable assembly remove the purple protective EMI cap Then simply insert the connector end into the cage of the SFP host port in the active equipment Make sure the cable is fully inserted and engaged ATTENTION Observe precautions for handling electrostatic sensitive electronic devices when installing this product Ensure that you are properly grounded with a wrist strap or equivalent while installing 10Gig SFP Copper Cables To disengage gently pull the latch release and the cable assembly will easily disengage the port The Panduit 10Gig SFP Direct Attached Copper Cable Assemblies have been designed to fit into high density belly to belly faceplates Panduit Corporation 2010 Page 4 of 7 10Gig SFP Copper Cable Assembly Installation Guidelines PN533A Cable Management The weight of large bundles of SFP twin axial cables can exert a significant force along the horizontal plane and specifically on the host port of the active equipment If the cable emerges from the rear of the connecior at too sharp an angle excess mechanical stress may be transmitted both along the cable and into the circuit board located inside the connector Excessive side forces exerted by the cabl
9. xcellent EMI immunity Cross section 2 pair twin axial cable Panduit SFP connector Panduit Corporation 2010 Page 1 of 7 10Gig SFP Copper Cable Assembly Installation Guidelines PN533A Standard Cable Part Numbers o5 mCS t 7 0 m 23 0 ft 5 6 mm 0 22 in Panduit 10Gig SFP copper cables have a length tolerance of 15 0 m Add cable color code to end of part number BU for Blue WH for White BL for Black Cable Length Deployment Note Note that the Panduit 10Gig SFP Direct Attach Cable Assembly lengths are measured from cable connector tip to tip However much of the connector is inserted into the host port Therefore one may wish to add approximately 47mm or 1 87 inches to each end or approximately 0 1m total to port to port length and cord routing calculations LENGTH SEE TABLE 1i Connector EEPROM Panduit 10Gig SFP Direct Attach Copper Cable Assemblies are intelligent cables The connector has an integrated EEPROM with information populated in registers that is provided to the active equipment when queried through an IC bus Most active equipment port allow for interchangeable types of me to be plugged into its ports The registers in the EEPROM provide a method for the connector to identify itself as an SFP passive copper module to allow the active equipment to operate in the proper mode Other information contained in the memory registers includes vendor name Panduit part num
Download Pdf Manuals
Related Search
Related Contents
Pioneer CNSD 200 FM Upgrade Instructions and Operation Manual Addendum und Installationsanleitung Schiebetorantrieb PULL X, X/o, XD/o Hoshizaki KM-501MWH User's Manual Manual de Instruções Intellinet 502917 router Hague Quality Water Intl WATERMAX H3000 User's Manual LES OREILLERS ROUGES. Commissioning manual, Generator protection REG650 1.2, ANSI Copyright © All rights reserved.