1.   at anytime     1  Press the AREA button until meter beeps twice  A memory location  number will appear in the top right of the display indicating the  memory location     2     Push the NEXT button to scroll thru and select the desired  location  Once you have selected the desired memory location  enter your dimension    Use the A  UP  button to change the flashing digit  After all of the digits are entered  press and hold the AREA    button  until it beeps twice  to save the area into memory  and return to CFM or CMM measuring mode   To select and use a previously stored dimension  press and hold    the AREA button until it beeps twice    Press NEXT to scroll thru the 8 memory locations  Press and  hold the AREA button until it beeps twice to return to CFM or  CMM measuring mode     Air Flow Averaging Mode    1  To enter 20 Point Averaging Mode  press and hold the AVG  button until it beeps twice  The AVG icon will be displayed     2  Take a measurement and press the AVG button  A single  beep will sound and the HOLD icon will appear in the display     3  The average reading will be displayed and number of  readings measured will appear in the upper right hand  corner of the display  After 5 seconds  the display will return  to the current reading     4  Repeat steps 2   3 until the desired number of points have  been measured     5  To return to standard airflow measuring mode press and hold  AVG button until meter beeps twice     Note  In the standard velocity measuring 
2.  3 until the desired number of points have been  measured     5  To return to standard velocity measuring mode press and hold  AVG button until meter beeps twice     Note  In the standard velocity measuring mode  press the AVG button  once to recall the previous average  The average will be cleared  when you enter the Averaging Mode again     Air Flow Measurements  CMM   CFM     Side view  1  Turn on the meter using the    ON OFF button of Vane  2  Press the UNITS button to select the desired air flow  units  CMM  cubic meters per minute  or CFM  cubic Arrow  feet per minute   NOTE  At power up the meter will a  display the last unit of measure previously entered  airflow   lt     3  To begin entering the area in m   or ft     press and  hold the AREA button until it beeps twice  The  lt   leftmost digit of the bottom display will begin to flash     4  Use the A  UP  button to change the flashing digit   After all of the digits are entered  press and hold the   AREA button  until meter beeps twice  to save the   area into memory and return to CFM or CMM   measuring mode   5  Place the sensor in the air stream  Ensure that the air enters the  vane as indicated by the arrow sticker placed inside the vane  Refer to  the diagram  The large main LCDdisplay shows the Air Velocity  reading  The upper right LCD sub display shows the temperature reading   The meter has 16 memory locations  8 for CFM and 8 for CMM  that  can be used to store commonly used area sizes that you can recall
3. Conversions       Area equation for rectangular or square ducts    Height  H     Width  W  Area  A    Width  W  x Height  H     Area equation for circular ducts    Area  A       x r   Where       3 14 and r     radius x  radius    Cubicequations          CFM  ft3 min    Air Velocity  ft min  x Area  ft    CMM  m3 min    Air Velocity  m sec  x Area  m    x 60                      NOTE  Measurements made in inches  must be converted to feet or meters before using the above formulae        Unit of Measure Conversion Table                m s ft min knots km h MPH  1m s 1 196 87 1 944 3 6 2 24  1 ft min 0 00508 1 0 00987 0 01829 0 01138  1 knot 0 5144 101 27 1 1 8519 1 1523  1 km h 0 2778 54 69 0 54 1 0 6222  1 MPH 0 4464 87 89 0 8679 1 6071 1                                                 10    
4. PYLE    User s Manual  CFM CMM Thermo Anemometer  Model  PMA90       WWW PYLEAUDIO COM    Introduction       Congratulations on your purchase of the Thermo Anemometer  This    instrument measures Air Velocity  Air Flow  volume  and Temperature     The large  easy to read backlit LCD includes primary and secondary  displays plus numerous status indicators  The meter is shipped fully    tested and calibrated and with proper use will provide years of reliable    service     Meter Description       Meter   LCD Display  Power On Off  AVG   UNIT  MAX MIN  NEXT   HOLD   AREA    O 000 UN  0   O Be 2 NS       Keypad       AUTO POWER orFO Press to turn the meter ON or OFF  MAXI MIN Used to record and store the highest  lowest and average  airflow or velocity readings     LEFT  also serves as change decimal point button in AREA mode  UNITS Press to select the mode of operation  In FLOW mode    the meter displays air volume  In VELOCITY mode  the meter  displays air speed    A UP  also serves as increase number button in AREA mode   AVG Used to Average multiple readings in FLOW or VELOCITY  mode  Up to 20 readings can be averaged    HOLD Press to freeze the displayed reading  Press again to unlock  display  This button also functions as the RIGHT scroll button in  AREA mode and RECALL mode    AREA Press and hold to manually enter the area of a duct in CFM  or CMM mode    NEXT In AREA mode  used to select memory locations 1 8       C   F The button is behind of battery cover  it needs to 
5. mode  press the AVG  button once to recall the previous average  The average will be  cleared when you enter the Averaging Mode again     Data Hold  Air Velocity Air Flow     1  While taking measurements  press the HOLD button to freeze  the air velocity air flow reading     2  The HOLD indicator will appear in the bottom of the LCD display     3  Press HOLD again to return to normal operation     MAX MIN AVG Record  Air Velocity Air Flow     This allows the user to record and view the highest  MAX   lowest   MIN  and average  AVG  readings     1  Press the button MAX MIN button  The MAX indicator and  RECORD indicator along with the Max reading will appear on  the LCD display and the meter will begin keeping track of the  MAX  MIN and Average values    2  Press the MAX MIN button again to view the minimum reading   The MIN indicator along with the minimum reading will appear  on the LCD display    3  Press the MAX MIN button again to view the average reading   The AVG indicator along with the average reading will appear  on the LCD display    4  Press the MAX MIN button again to display current readings   NOTE  the meter will keep recording MAX MIN AVG readings    5  To clear and stop MAX MIN AVG recording and return to normal  operation  press and hold the MAX MIN button until the meter  beeps twice     Automatic Power OFF  To conserve battery life  the meter automatically turns off after  20 minutes  To defeat this feature   1  Turn the meter OFF   2     dis APO    will ap
6. open  the battery cover that can set     AUTO BACKLIGHT The model will be full auto backlight when  operation  it is more convenient     Battery compartment located on the back of the instrument   The rubber protective jacket must be removed from the meter  to access the compartment     Display Layout       RECALL As  MAX MIN HOLD FLOW VEL  MEM PROBE TEMP AREA    BEHA     CMMCFM m ft     MAX  top of LCD   Max Hold function  engaged for the Air Temperature function    HOLD  top of LCD   Data Hold function  engaged for the Air Temperature function          IR TEMP MAX MIN AVG HOLD    VEL  indicates that meter is in air velocity mode   FLOW  indicates that meter is in air flow mode   MAX  bottom of LCD   Max Hold for the IR Temperature and  RH function    HOLD  bottom of LCD   Data Hold for the IR Temperature  function and RH function     C     F  Temperature units of measure   CFM CMM  airflow units of measure   Ft     m7  units for area dimensions   m s  ft min  km h  MPH  knots  air velocity units of measure   X10  X100  multipliers for air flow readings   AVG  air averaging mode   RECORD  indicates that min max function is running  top for temp    bottom for air     Large LCD digits at center of display for Relative Humidity an  d IR Temperature  Smaller LCD digits at top  right of display for Probe Temperature     __   Low battery indicator  3    Operation       Connecting the Vane    1     Air  1   2     Air    1     The vane plug is inserted in the meter   s sensor jack a
7. pear in the display  The AUTO POWER OFF  feature will now be disabled     3  Note that AUTO POWER OFF is re enabled each time the  meter is turned on    4  Also note that AUTO POWER OFF is disabled in CFM CMM or  Average mode     Battery Replacement       When E   appears on the LCD  the 9V battery must be replaced   Disconnect the sensor   Remove the meter   s rubber protective jacket  Use a Phillips screwdriver to open the rear battery compartment  Replace the 9V battery  Close the battery compartment and replace the meter   s protective  jacket   You  as the end user  are legally bound  Battery ordinance     to return all used batteries and accumulators  disposal    in the household garbage is prohibited     OY oe NDS        You can hand over your used batteries   accumulators   gratuitously  at the collection points for our branches in  your community or wherever batteries   accumulators   Disposal are sold              Follow the valid legal stipulations in respect of the disposal  of the device at the end of its lifecycle    WARNING  To avoid electric shock  do not operate the meter until  the battery cover is in place and fastened securely   NOTE   If your meter does not work properly  check the fuses and    batteries to make sure that they are still good and that they  are properly inserted     Specifications       Air Velocity   m s  meters per sec   km h  kilometers hour   ft min  feet per minute   mph  miles per hour   knots  nautical MPH   Air Flow   CMM  cubic me
8. t the top of the  meter  The plug and jack are keyed so that the plug can only fit in  the jack one way    Turn the plug carefully until it lines up with the jack and then firmly  push the plug in place  Do not apply undue force or try to twist the  plug side to side    If the vane is not connected to the meter or if the sensor is defective   the LCD display will indicate OL in place of a Temperature reading     Velocity Measurements  Single Point  Side view of Vane  Turn on the meter using the ON OFF  button    Press UNITS button to select the desired unit of Arrow  measure  NOTE  At power up the meter will   display the last unit of measure previously a  entered     Place the sensor in the air stream  Ensure that  the air enters the vane as indicated by the arrow  sticker placed inside the vane     airflow   lt        View the readings on the LCD Display  The  large main LCD display shows the Air Velocity  reading  The upper right LCD sub display shows  the temperature reading     Velocity Averaging Mode    To enter 20 Point Averaging Mode  press and hold the AVG  button until it beeps twice  The AVG icon will be displayed     2  Take a measurement and press the AVG button  A single    beep will sound and the HOLD icon will appear in the display     3  The average reading will be displayed and number of readings    measured will appear in the upper right hand corner of the display   After 5 seconds  the display will return to the current reading     4    4  Repeat steps 2  
9. ters min   CFM  cubic ft min     Air Temperature          Range  0 40   30 00 m s  1 4   108 0 km h    Resolution  0 01 m s    Accuracy     3    0 20 m s     Battery Current 8 3 mA DC approx     Weight  Dimensions    1 6 lbs   725g  including battery  amp  probe    Main instrument  7 0 x 2 9 x1 2   178 x 74 x 33mm   Sensor Head  2 75     70mm  Diameter    0 1km h        3    0 8 km hr               80     5900 ft min 1 ft min  3    40 ft m   0 9     67 0 mph 0 1 mph    3    0 4 MPH   0 8 to 58 0 knots 0 1 knots     3    0 4 knots   Range Resolution Area  0 9999 m  min 1 0 to 9 999m   0 9999 ft min 1 0 to 9 999ft   Range Resolution Accuracy  14   140  F   10   60  C  0 1  F C 4 0  F  2 0  C           Circuit  Display  Sampling rate    Sensors    Automatic Power off    Operating Temperature  Storage Temperature  Operating Humidity  Storage Humidity  Operating Altitude  Battery   Battery life    Custom LSI microprocessor circuit  Dual function 0 5   13 mm  4 digit LCD  1 reading per second approx    Air velocity flow sensor  Conventional  angled vane arms with low friction ball  bearing Temperature sensor  NTC type  precision thermistor   Auto shut off after 20 minutes to preserve  battery life   32  F to 122  F  0  C to 50  C    14 to 140  F   10 to 60  C     lt 80  RH    lt 80  RH   2000 meters  7000ft  maximum   One 9 volt  NEDA 1604  battery    80 hours approx   if the Backlight is used  continuously  battery life will be reduced  significantly     9    Useful Equations and 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Type PST30...PSTB1050 Manuel d`installation  Trust 18536  User Manual Oracle FLEXCUBE Direct Banking Corporate Bulk  Sony PCV-W20 Help Guide  DHG mode d`emploi Comment préparer au mieux la    Leica PaveSmart 3D User Manual - Surveying Technologies and  Samsung Micro Componente Samsung 800W MM-D330D Manual de Usuario  Automated condensate drain line cleaning system, method, and kit  Bunn 40410.0000G Coffeemaker User Manual    Copyright © All rights reserved. 