1. Instruction manual for Powerline RT e Cabling and earthing NOTE The installation and cable laying should proceed in compliance with local laws and regulations NOTE The UPS must be earthed Prior to connecting power supply cables to the electric system terminal on the premises make sure that the earthing connection is reliable If external UPS battery packs are connected the main equipotential connection with the main UPS unit is provided by the packs power supply cables NOTE The installation must enable disconnection from the grid power supply pointe g through circuit breakers gt gt gt P NOTE In order to ensure that receivers can be disconnected from the UPS at any time emergency breaker should be installed between the UPS output terminals and receivers To enhance your safety this can be an RCD device e Battery gt NOTE When serially connecting several battery packs adhere to the same voltage same type rule 2011 04 19 www ever eu 22 Instruction manual for Powerline RT UNPACKING AND CONTROL After unpacking check the contents of the package The package should include CONTENTS OF THE PACKAGES The packages contain a UPS POWERLINE RT 1000 2000 UPS unit 2 sets of tower bases for vertical installation 1 x power supply cord CEE7 7 IEC 320 C13 10 8 x power supply cord IEC C13 IEC C14 10A 1x
2. 5 RJ11 port battery module detection 6 Supply interface to connect an external battery pack 7 SNMP card socket 8 Input circuit protection automatic fuse 9 Power supply input socket 10 Non controlled output sockets 11 Controlled output sockets group 1 and 2 12 Earthing bolt 2011 04 19 www ever eu Instruction manual for Powerline RT POWERLINE RT 2000 124 Fig 5 Rear panel 1 SNMP card socket 2 Fan 3 Supply interface to connect an external battery pack 4 RJ11 port battery module detection 5 RS232 port 6 Input circuit protection automatic fuse 7 Power supply input socket 8 Non controlled output sockets 9 Controlled output sockets group 1 and 2 10 ROO EPO terminals 11 USB port 12 Earthing bolt 2011 04 19 WWW ever eu 13 Instruction manual for Powerline RT POWERLINE RT 3000 9 1 SNMP card socket 2 Fan 3 Fan 4 Supply interface to connect an external battery pack 5 RJ11 port battery module detection 6 RS232 port 7 Input circuit protection automatic fuse 8 Power supply input socket 9 Non controlled 16A output sockets 10 Controlled 10A output sockets group 1 and 2 11 16A output sockets 12 ROO EPO terminals 13 USB port 14 Earthing bolt Fig 6 Rear panel 2011 04 19 www ever eu 14 Instruction man
3. EVER POWER SYSTEMS INSTRUCTION MANUAL POWERLINE RT EVER Sp 2 ul Grudzi skiego 30 62 020 Swarz dz Poland www ever eu ups ever com pl tel 0048 61 6500 400 fax 0048 61 6510 927 INSTRUCTION MANUA Instruction manual for Powerline RT TABLE OF CONTENTS TABLE OF CONTENTS coves esi Ree oath eec eee EHE 2 PRODUCT INTRODUCTION cease cocina vo hire a a ee WA a ets diet aes 3 HOW TD WORKS szo EE A bee etie WA eec st E dE ots 3 SYMBOLES USED o b notae ee GERE DEGREE 6 INSTRUCTIONS ABOUT FRONT PANEL INDICATORS eene nennen en rennen enne 7 REAR PANDBLEL 2 n ogensgerehecsieneneng alin AAAA uH a EUR 12 PRODUCT SPECIFICATIONS e P P E ERR eM ere UHR 17 INSTALLATION seco copes Gatch R ist teneo Oe aiio tete ide etiatn 21 SAEETY DURINGINSTALLEATION wa toz od W es enm ede ERE EIS 21 UNPACKING AND CONTROL zed anna th pa A AR tea e e ert 23 UPS and external battery pack vertical installation sessi rennen nete 25 POWER SUPPLY CONNECTION ais i biete Stet di cete ice tct e tec HS Mere cuite Det 26 Connecting an external battery pack esses eene aaa nennen eene 26 UPS power COBDeCUOD xou AT eet A O O A AE ripe eU eter nere petere 27 OPERATION 2 enean etre nee eee pee reete al Mees p rte die ipee 27 SAFE OPERATION INSTRUCTIONS E nennen aaa tentes 27 STARTING THE UPS oit tte tem leti rot bei eniti ten de ee Rete eie E
4. Overheating Reduce the ambient temperature Autonomous power supply time shorter than in the specifications Battery pack protection is set to OFF Set battery pack protection to ON Batteries are not fully charged Charge up the batteries and test their duty time in the backup mode If the problem persists contact the customer service representative Batteries are damaged Contact the customer service representative The charger is damaged Contact the customer service representative Communication error between the UPS and Incorrect serial connection cable Check whether the correct cable was used Computer interface is used Check whether other software service has a computer by another process or is access to the computer interface try to damaged select another serial interface Disruptions on data cable Relay the cable reinstall the cabling 2011 04 19 www ever eu 36 Instruction manual for Powerline RT TRANSPORT AND STORAGE The UPS should be transported only in the original packaging The UPS should be stored in a ventilated and dry place LAWS REGULATIONS AND THE WARRANTY DECLARATION OF CONFORMITY The UPS structure complies with the provisions of the pertinent standards WARRANTY The warranty for the device constitutes a separate document enclosed with the product This document must meet all the formal requirements e g the following field should b
5. gt gt Dangerous voltage may appear between the battery terminals and earthing point When working with batteries the following precautions should be applied B Take off watches rings and other metal objects m Use tools with insulated handles m Put on rubber gloves and footwear B Do not place tools or metal parts on batteries m Power source should be disconnected prior to connecting or disconnecting battery terminals A typical battery lifespan is from 3 to 5 years in the ambient temperature of 25 C Nevertheless battery lifespan also depends on the frequency and duration of grid power failures and periods in which the batteries are discharged After the end of the battery s useful life follow the battery replacement procedure The battery test should be performed periodically every 6 to 12 months in order to check general battery performance In order to replace the internal batteries manually set the UPS to the bypass mode see Bypass mode procedures and follow the sequence of actions shown on the pictures 2011 04 19 www ever eu 33 Instruction manual for Powerline RT Fig 13 POWERLINE RT 1000 Fig 14 POWERLINE RT 2000 3000 2011 0419 www ever eu 34 Instruction manual for Powerline RT Battery disposal Disposal recycling of the UPS and or batteries should be handled by a company certified in disposal recycling Used rechargeable batteries are classified as dangerous to
6. The UPS and battery packs can be installed in a rack with depth up to 800 mm For rack type installation the Rack Kit assembly set is necessary optional accessories The kit contains an instruction manual and a description of how to change the LCD panel s position In the standard version the UPS is provided as a tower version vertical 2011 04 19 www ever eu 24 Instruction manual for Powerline RT UPS and external battery pack vertical installation 1 Install two sets of tower bases supplied with the UPS and place the device between the bases as shown on the pictures Fig 10 Vertical installation of the UPS The UPS unit can be mounted in horizontal position For the necessary information see User manual quick start included in the product packaging 2 UPS Plus mounting with an external battery pack Install two sets of tower bases with the spacer supplied with the UPS and place the device between the bases as shown on the picture Then secure the UPS and the battery pack with the supplied plates and screws Fig 11 UPS Plus connection to an external battery pack 2011 04 19 www ever eu 25 Instruction manual for Powerline RT POWER SUPPLY CONNECTION Connecting an external battery pack WARNING Prior to connecting a battery pack to the UPS circuit A N protection of the pack must be in OFF After establishing the electric connection with the UPS the protection should
7. be switched to ON NOTE Each battery pack comes with two battery connections The first pack is connected to the UPS with a cable supplied with the UPS set Each subsequent battery pack is connected to the previous pack using with the battery pack cable External battery packs if used should be connected to the UPS prior to its connection to the power grid Follow the procedure below to connect external battery packs 1 Set battery pack circuit protection in each pack to OFF 2 Make the connection between the pack and the UPS with the cable supplied 3 Connect another battery pack to the already connected pack 4 Make a chain of battery packs until you connect the last pack 5 Connect the battery pack detection cable between the RJ11 port on the UPS rear panel and the RJ11 port on the back panel of the first battery pack 6 Connect the module detection cable between one RJ11 port on the back panel of the first pack with one RJ11 port on the back panel of another pack 7 Make a chain of battery packs using battery pack detection cables until you connect the last pack 8 Set battery pack circuit protection in each pack to ON When all external battery packs are connected make the necessary power supply output input connections as described below 2011 04 19 www ever eu 26 Instruction manual for Powerline RT UPS power connection 1 Connect the input power supply cord to the AC input NOTE Batte
8. 1 is displayed as first and events from 2 to 5 are displayed when the forward button is pushed After displaying the event type the next screen tells you when it occurred relative to the device s working time This is not a calendar date The time follows the format DDDD HH MM SS where DDDD is the consecutive day of the device s work HH hours MM minutes SS seconds The next screen is the next event 2011 04 19 www ever eu 10 Instruction manual for Powerline RT MENU 3 CONTROL SELECTION Submenu Function 3 1 BATTERY TEST After selecting this option the battery test is performed 3 2 MANUAL BYPASS UPS switching to the bypass mode and back 3 3 CONTROLLABLE OUTLET 1 Activation deactivation of output group 1 first group of controlled output sockets Activation deactivation of output group 2 second group of controlled output 3 4 CONTROLLABLE OUTLET 2 sockets MENU 4 SETUP Submenu Function Language selection English Spanish Italian French Polish Portuguese 4 1 LANGUAGE German 4 2 ACUSTIC ALARM Sound alarm activation deactivation buzzer 4 3 OUTPUT VOLTAGE Selection of rated output voltage 200 V 208 V 220 V 230 V or 240 V Selection of rated output frequency 50 or 60 Hz only in the frequency conversion 4 4 OUTPUT FREQUENCY mode FREQUENCY Activation deactivation of frequency conversion mode UPS must be in the standby CONVER
9. C Automatic restart if the function is switched on after the autonomous power supply time has lapsed the device automatically starts when the grid power supply resumes If it doesn t it is necessary to start the device manually 2011 04 19 www ever eu 5 Instruction manual for Powerline RT NOTE if the function is activated and a failure of power supply occurs immediately after the automatic start of the device the autonomous power supply time will be short because the batteries have not been fully charged d The battery test can be performed in two ways manually or automatically with a fixed break between the tests e Controlled outputs the UPS is provided with two groups of controlled output sockets output 1 and output 2 Each group can be configured so that it automatically switches off when the battery charging status drops below a specific value 75 50 25 or 0 or on the user s demand NOTE It is recommended that key devices should be connected to the main outputs and less important ones to the controlled outputs f Remote control there are terminals on the rear panel of the UPS which enable the user to switch on off the device remotely ROO or switch off the device remotely without the automatic restart option EPO g Compatibility with power generators the UPS can work with most power generators available on the market SYMBOLS USED Some or all of the symbols below may be us
10. EPO contact Remote on off Yes ROO contact ENVIRONMENT Operating temperature 0 40 Storage temperature 25 50 C without batteries 2011 04 19 WWW ever eu 17 Instruction manual for Powerline RT 15 40 C with batteries Altitude above sea level 3 0 3000m Relative humidity when working lt 95 without condensation Relative humidity during storage lt 95 without condensation MECHANICAL PARAMETERS Dimensions W x H x D 438 x 86 2U x 483 mm 438 x 86 2U x 658 mm 438 x 86 2U x 658 mm Rack cabinet deepth lt 800 mm Weight 18 5 kg 30 5 kg 31 kg CONNECTIONS Input 1 x IEC320 C14 10 A 1 x IEC320 C20 16 A 6 x IEC320 C13 10 A of which Output 6 x IEC320 C13 10 A of which 3 are controlled 2 groups 3 are controlled 2 groups 1 x IEC320 C19 16 A STANDARDS CE mark Yes Safety EN 62040 1 EN 60950 RD EMC 1EC62040 2 C2 IEC61000 3 2 IEC61000 4 2 IEC61000 4 3 IEC61000 4 4 IEC61000 4 5 IEC61000 4 6 IEC61000 4 8 IEC61000 4 11 IEC61000 2 2 Efficiency EN62040 3 Note The manufacturer reserves the right to change the abovementioned parameters without notice For 200V output rated voltage the output power is reduced by 20 For 208 V output rated voltage the output power is reduced by 1096 The ports cannot be used simultaneously Notes For normal operation of the battery back u
11. PS monitoring software which ensures user friendly interface for UPS monitoring and control This exceptional piece of software ensures safe and automatic disconnection of multiple computer systems in the case of power supply failure Using this software users can monitor and control each UPS in the same LAN network regardless of the distance from the UPS 3 Winpower Manager Ver1 0 agent Read EM _ M FA i xf System Logs UFS Tools Monitor Preference Language Help Root UPS Status UPS Homnal 15 18 EB LAN 9 El agent d cow Voltage BYPASS WINES Poe S Pca Max Volt Cn Battery EB WAM Mis Volt JGGG Voltage Standard Capacity A 5 2004 10 29 12 53 25 Agent Start Fig 9 Winpower manager version 1 0 Installation procedure 1 Go to the webpage http www ups software download com winpower htm 2 Select the required operating system and follow the instruction described on the webpage to download the software 3 When downloading the required files from the Internet enter the following serial number 511C1 01220 0100 478DF24A to install the software After restarting the computer WinPower software appears as a green socket icon in the system tray next to the clock 4 Software installation can also be performed using the supplied CD 2011 04 19 www ever eu 20 Instruction manual for Powerline RT INSTALLATION SAFETY DURING INSTALLATION You must rea
12. TER mode T CONTROLLABLE OUTLET Selection of the battery charging level 7596 5096 2596 or 096 below which output 1 LEVEL 1 first group of controlled output sockets is deactivated automatically re CONTROLLABLE OUTLET Selection of the battery charging level 75 50 25 or 0 below which output 2 LEVEL 2 second group of controlled output sockets is deactivated automatically 4 8 COLD START Activation deactivation of cold start function start without grid power supply Activation deactivation of automatic restart function automatic start after the 4 9 AUTO RE START autonomy time has lapsed when the grid power supply resumes 410 ECO MODE ECO mode activation deactivation Phase detection function activation deactivation detection of incorrect input lead 4 11 SITE WIRING FAULT Sequence Selection of the automatic battery test frequency every day every week every 4 12 AUTO BATTERY TEST month Was PRE ALARM LEVEL Selection of the battery charging level 75 50 25 or 0 below which Battery low signal is activated MENU 5 ABOUT Function Displays rated power of the UPS software version and UPS working time 2011 04 19 www ever eu REAR PANEL POWERLINE RT 1000 Instruction manual for Powerline RT Fig 4 Rear panel 1 RS232 port 2 USB port 3 ROO EPO terminals 4 Fan
13. USB cable 1 x RS232 cable CD with WinPower software warranty card operation manual b UPS POWERLINE RT 3000 UPS unit 2 sets of tower bases for vertical installation 1 x power supply cord CEE 7 7 IEC 320 C19 16A 2 x power supply cord IEC C13 IEC C14 10A 1 x power supply cord IEC C19 IEC C20 16 1 x USB cable 1 x RS232 cable CD with WinPower software warranty card operation manual c Rack Kit set for UPS battery pack Rack type installation optional set of items for Rack type installation 2 front braces for rack type UPS installation and the required assembly tools 2 slides for rack type UPS installation along with and angles and screws printed pictorial instruction manual for UPS battery pack installation in the rack and LCD panel rotation to level instruction 2011 04 19 www ever eu 23 Instruction manual for Powerline RT d SNMP card SNMP card 1x RJ cable RS232 CD with software warranty card e POWERLINE RT 1000 amp 2000 3000 battery pack 1 battery pack 1 power connection cable 1 battery pack detection cable for automatic detection of connected packs RJ11 2 sets of tower bases for vertical installation binding element to join a battery pack to another battery pack or UPS warranty card Inspect the UPS and battery pack visually to make sure there it was not damaged in transport INSTALLATION
14. act will switch the UPS off Closing of the contact will restart the UPS and supply power to the connected receivers BATTERY MAINTENANCE CLEANING Scrubbing powders or solvents must not be used to clean the UPS Do not let any liquid ingress into the UPS Make sure that the ventilation openings on the UPS are not covered Remove dust from the ventilation openings using a vacuum cleaner The UPS casing should be cleaned from outside by wiping it with a dry or moist cloth UPS STORAGE If the UPS is stored over a longer period in the ambient temperature in excess of 25 C the batteries should be charged for five hours every four months If the ambient temperature in the storage location is higher it is recommended that storage time is shortened to two months You do not need to unpack the device to charge the batteries The UPS should be simply connected with a cord to the power grid using special openings in the packaging and the batteries should be charged for about five hours After charging the charging date should be entered on the UPS packaging 2011 04 19 www ever eu 31 Instruction manual for Powerline RT BATTERY TESTING Thee UPS does not require maintenance by the user however the batteries should be periodically inspected The UPS automatically performs battery auto test once a week If a problem appears the error LED will light up or an error message will be displayed on the LCD Testing frequency can be chan
15. attery BACKUP MODE message will appear on the LCD along with the expected autonomous supply time NOTE If the OVERLOAD message is displayed on the panel this means that too many devices are connected to the UPS If only one device is connected to the UPS and OVERLOAD appears on the display then the power demand of the receiver exceeds the UPS power supply range and a UPS with greater rated power must be used ZA NOTE If the UPS does not respond as described above go to chapter 5 Troubleshooting BYPASS MODE PROCEDURES In order to set the device to bypass mode go to menu 3 CONTROL and then submenu BYPASS SWITCH and select SWITCH TO BYPASS or press the confirm button keeping it pressed for six seconds Follow the same procedure for the UPS to return to the grid mode this time selecting SWITCH TO GRID If the UPS is in the standby or frequency conversion mode switching to the bypass mode is not possible 2011 04 19 www ever eu 29 Instruction manual for Powerline RT ECO MODE PROCEDURE If the device is off but connected to the grid go to menu 4 SETTINGS and then to the submenu ECO MODE and select ECO ON After the UPS is started it will launch in the ECO mode FREQUENCY CONVERTER MODE PROCEDURE The frequency converter can be switched on if the UPS is in the standby mode To activate the frequency conversion mode go to menu 4 SETTINGS and then
16. d the following safety information prior to installation gt gt NOTE The UPS is completely disconnected from the power grid only when the power supply cord is disconnected e Installation personnel gt NOTE The UPS should be connected by qualified and authorised personnel only e Installation environment gt NOTE This product is intended for commercial and industrial use in the second environment To prevent disruptions it may be necessary to apply additional preventive measures or limitations gt NOTE The UPS must not be installed or operated whenever water vapour condensation occurs which can take place if the UPS is taken directly from a cold into a warm environment The UPS must remain completely dry prior to installation and operation The time needed to adapt to the new environment before the installation proceeds should be at least 2 hours Otherwise there is a risk of electrocution gt NOTE Do not install the UPS in damp environments next to sources or heat or whenever it is exposed to direct sunlight Make sure that the UPS is kept away from water flammable gases and corrosion agents gt NOTE The device should be installed in well ventilated places Do not cover ventilation openings in the UPS casing keep the relevant distances from other objects to ensure appropriate air circulations 2011 04 19 www ever eu 21
17. e filled in manufacturing number model type date of sale and stamp of the seller The manufacturer has made every effort to ensure that the offered products are free of defects in materials and workmanship The liability of the company under the warranty is limited to the repair or replacement of products containing such defects The method for removal of defects shall be determined by the manufacturer The warranty shall not cover those appliances with mechanical damage that were improperly maintained or used or that were modified in any way by the user EVER Sp z o o does not provide any guarantees or warranties including the guarantees of fitness for sale or for any specific purpose other than what is set out in the warranty card EVER Sp z o o shall not be liable for any direct indirect extraordinary coincidental or consequential losses resulting from the use of the power supply unit even if the possible occurrence of such losses has been notified The company shall not be held liable for any costs such as the loss of profits or earnings equipment equipment usage software data costs of replacement products claims of third parties or for any other costs whatsoever Information on warranty and post warranty repairs as well as other maintenance services as well as this instruction in English Czech and Slovak can be obtained on our website at www ever eu 2011 04 19 www ever eu 37
18. e permitted load power of the batter back up decreases 2011 04 19 www ever eu 18 Instruction manual for Powerline RT Communication The UPS is fitted with various communication interfaces including the RS232 and USB serial interface as well as the communication interface socket Using those interfaces users can establish direct communication between the UPS and the duty server configure the UPS as a network client with centralised monitoring using the Manage UPS SNMP adapter fitted in the interface socket as well as report UPS statuses to external systems eRS232 port and status indication Table 5 Matching of contacts and description of DB 9 interface 4 Battery low Grid power parameters out of range Bypass mode SUM alert Grid power parameters correct eUSB port The USB port is compatible with the USB 1 1 protocol AS NOTE RS232 and USB ports cannot be used simultaneously einterface socket Various cards can be connected to the interface socket Interfaces marks and codes in the socket may vary depending on the interface card used A detailed description is attached to the interface cards available as accessories Available interface cards SNMP adapter card Manage UPS to integrate the UPS with the network option AS400 card option 2011 04 19 www ever eu 19 Instruction manual for Powerline RT eWinpower Free software download WinPower WinPower is the latest U
19. ed in this instruction manual It is recommended that the user is familiar with the symbols and their meanings 2011 04 19 www ever eu 6 Instruction manual for Powerline RT Table 1 Symbols SYMBOL AND EXPLANATION SYMBOL EXPLANATION SYMBOL EXPLANATION ALERT YOU TO PAY ALTERNATING CURRENT SPECIAL ATTENCION SOURCE AC CAUTION OF HIGH DIRECTGURRENT VOLTAGE SOURCE DC TURN ON THE UPS PROTECTIVE GROUND TURN OFF THE UPS RECYCLE DO NOT DISPOSE WITH IDLE OR SHUT DOWN THE UPS ORDINARY TRASH Co mos 1 INSTRUCTIONS ABOUT FRONT PANEL INDICATORS Control panel There are several switches and LED indicators on the front panel which notify the operator of the current UPS status and options to change the UPS mode 4 5 8 6 7 Fig 2 Front panel 2011 04 19 WWW ever eu Instruction manual for Powerline RT 1 Green LED diode means that input voltage is available BYPI 2 Amber LED diode Bypass and ECO mode indication as well as indication of warnings which are also displayed on the LCD display e g when there is overload 3 Red LED diode It indicates the most critical messages relating to the device s work such as short circuit internal error 4 LCD display 5 Exit button 6 Forward button Kd 7 ON OFF button Backup mode LED diode green button light 8 Confirm button Table 2 Description of diodes LED diode nu
20. ged using the control panel or user software The option BATTERY TEST DAILY WEEKLY MONTHLY or OFF should be selected from the submenu AUTOMATIC BATTERY TEST in the SETTINGS menu BATTERY REPLACEMENT 1 NOTE Receivers connected to the UPS will not be protected against input power loss during the operation External UPS battery pack replacement The UPS does not require user maintenance although maintenance according to IEEE Recommended Practice for Maintenance Testing and Replacement of Valve Regulated Lead Acid VRLA Batteries for Stationary Applications IEEE Standard 1188 1996 is recommended If the batteries run out personnel trained on battery operation should replace them The replacement is performed in the maintenance access area The battery maintenance should be ensured or supervised by personnel familiar with battery operation using the appropriate precautions During the replacement the same type and quantity of batteries or battery sets should be used 2011 04 19 www ever eu 32 Instruction manual for Powerline RT WARNING Protect the batteries against fire explosive WARNING Do not open the batteries and protect them against damage Spilt electrolyte is harmful to the eyes and skin and could be toxic WARNING The battery set may pose a risk of electrocution WARNING The battery is not isolated from power supply lines gt gt
21. immediately disconnect the UPS from the power supply line and set circuit protection of the battery packs to OFF NOTE UPS output sockets are live when the power switch on the front panel is in ON position On Off LED is lit NOTE As required by the standards the cords may not be longer than respectively output cords 10 metres communication cables 3 gt gt gt gt metres battery pack power cables 3 metres STARTING THE UPS Initial UPS start procedure 1 When using the UPS for the first time make sure that power from the grid is connected and then press and hold the On Off button until you hear a beep 2 The UPS will respond with several sound messages and the GRID MODE message along with the UPS load indication will appear on the LCD The connected receivers are power supplied 2011 04 19 www ever eu 28 Instruction manual for Powerline RT Regular UPS start procedure 1 Press and hold the On Off button until you hear a beep 2 The UPS will respond with several sound messages and LED s will light up 3 If AC grid is connected the green LED 1 on the UPS lights up GRID MODE message will appear on the LCD which means output sockets are power supplied 4 If there is no input power green LED is not on and the cold start function is on the backup mode LED will light up on the UPS indicating that the device is drawing power from the b
22. mber 1 2 3 7 Standby mode correct input power Standby mode no correct input power Bypass mode output connected e e Power grid mode e Backup mode e ECO mode Critical error mode e e Continuous light 2011 04 19 WWW ever eu Instruction manual for Powerline RT Menu and functions Functions available in the menu and submenu are explained below CA gt STATUS 2 3 LOGGING 31 P MANUALBYPASS 1 45 3 r e START LL CONTROL gt BATTERYTEST 3 3 p CONTROLLABLE OUTLET 1 r 3 4 p CONTROLLABLE OUTLET 2 m41 LANGUAGE 4 4 2 b ACOUSTIC ALARM gt SETUP gt INN i 4 3 b OUTPUTVOLTAGE 44 gt OUTPUT FREQUENCY 4 5 FREQUENCY 1 gt CONVERTER ABOUT 4 6 gt CONTROLLABLE OUTLET 1LEVEL 4 7 CONTROLLABLE OUTLET 2LEVEL 4 8 COLDSTART 4 9 b AUTORE START 4 4 10 gt ECO MODE CO SITE WIRING gt FAULT 4 12 p AUTOBATTERY TEST r 4 13 PRE ALARM LEVEL gt SELECTION Fig 3 Menu 2011 04 19 www ever eu Instruction manual for Powerline RT INFORMATION SCREEN Function Displays the current working mode messages about warnings and errors MENU 1 STATUS Function Di
23. ne and the grid supply parameters are within the tolerance the output is supplied with power directly from the input using the internal bypass The device in this mode is highly efficient while saving the energy When the ECO mode is on and the grid supply parameters are not within the tolerance the device automatically begins to supply power to the receiver using the inverter If the UPS is in the ECO mode the internal battery charger is working e Error mode If there is an internal error in the UPS and it is necessary to switch off the inverter the UPS switches to the error mode producing a sound and the relevant message on the LCD panel is displayed In the error mode there is a risk of losing the power supply by receivers because the output voltage will be generated through the bypass only after the error is actually encountered by the UPS e Extra functions a Green Power function energy saving mode If the device is in the backup mode and no receiver is connected to the output or the load is smaller than the predefined threshold see table of parameters the UPS will switch off automatically after five minutes in order to save the battery and energy b Cold Start if the function is switched on it is possible to start the UPS without power supplied from the grid and the receiver is supplied directly from the battery A NOTE If the UPS is started for the first time AC power supply must be connected
24. p the load connected to its output should not exceed 80 of value indicated in the table Reserve power is essential to ensure continuous operation of connected devices in case of momentary rushes in load current Continued exposure of the battery back up to the temperature of the surrounding exceeding 25 will shorten the life of batteries If the altitude above sea level increases beyond the provided limit the permitted load power of the batter back up decreases Battery packs Table 4 Technical parameters DRRAMETESSUMODEE ERES Fd POWERLINE RT 2000 3000 Casing Rack Tower Rack Kit optionally available Battery configuration 2x3x9Ah 2x6x9Ah Protection 70 A 80 VDC fuse 70 A 80 VDC fuse MECHANICAL PARAMETERS Dimensions W x H x D 438 x 86 2U x 438 mm 438 x 86 2U x 657 mm Rack cabinet deepth lt 800 mm Weight 32 kg 52 kg ENVIRONMENT Operating temperature 0 40 C Storage temperature 15 40 C Altitude above sea level 0 3000 m Relative humidity when working lt 95 without condensation Relative humidity during storage lt 95 without condensation Note The manufacturer reserves the right to change the abovementioned parameters without notice Note Continued exposure of the battery back up to the temperature of the surrounding exceeding 25 will s horten the life of batteries If the altitude above sea level increases beyond the provided limit th
25. ries are being charged from the moment when the input power supply is provided 2 Connect a receiver to the UPS It is recommended that key devices should be connected to the main outputs and less important ones to the controlled outputs NOTE You can select disconnection threshold for controlled output A N sockets using the control panel This helps to save energy for top priority receivers 3 To start the UPS and external battery packs when all the connections are made following the instructions in the subsequent chapter operation OPERATION A N NOTE UPS intended to provide backup for IT devices SAFE OPERATION INSTRUCTIONS NOTE You must read the following safety information prior to operation of the device e Warnings about operation NOTE The UPS is completely disconnected from the power grid only when the power supply cord is disconnected NOTE Never disconnect the earthing cable at the UPS device or on 1 terminals of the building wiring because this will remove the earthing connection used to protect the UPS system and all receivers connected to it 2011 04 19 www ever eu 27 Instruction manual for Powerline RT NOTE UPS output sockets may be live even when the UPS system is not connected to the power grid NOTE Prevent the ingress of liquids and foreign bodies into the UPS NOTE In case of electrocution or fire threat
26. s mode using buttons on the front panel In the bypass mode most UPS settings can be changed with the panel or communication software e Power grid mode In the power grid mode the input current is rectified converted by the AC DC section and then converted into stable output current by the DC AC section supplying the current to the receivers If the grid parameters become incorrect the UPS uninterruptedly switches to the backup mode e Backup mode In the backup mode power supply from the battery goes through the DC DC section to the inverter DC AC where stable output voltage is generated If the grid parameters go back to normal the UPS uninterruptedly switches to the grid mode e Frequency conversion mode UPS may be used as a frequency converter providing 50 Hz or 60 Hz at the output depending on the choice on the condition that the frequency of the input current is within 40 70 Hz If the device operates in the frequency conversion mode the available supply power is reduced by 5096 This means that only 5096 of the UPS rated power can be used when the device is in this mode If the device is used as a frequency converter the ECO mode cannot be activated and the bypass mode cannot be used N NOTE The frequency conversion mode can be switched on off only when the device is in the standby mode 2011 04 19 www ever eu 4 Instruction manual for Powerline RT e ECO mode When the ECO mode is o
27. splays input and output values voltages frequency load MENU 2 LOGGING Function Displays five most recent events errors warnings 1 EPO RELEASE UPS stopped working because EPO was activated remote power supply off BATT ERROR 2 Battery error detected CALL SERVICE OVERLOAD 3 Inverter overload detected grid power or backup mode CHECK OUTPUT BYPASS OVERLOAD kw 4 Overload detected when the device is in the bypass mode OUTPUT UNPROTECT 5 FAN ERROR Fan failure detected CHARGER 1 6 The charger supplies too high voltage internal error TOO HIGH VOLT DC BUS rot 7 DC voltage in the DC bus is too high internal error TOO HIGH VOLT DC BUS 3 8 DC voltage in the DC bus is too low internal error TOO LOW VOLT DC BUS 9 DC voltage in the DC bus is unstable internal error UNSTABLE INVERTER 10 The inverter supplies too high voltage internal error TOO HIGH VOLT INTERVERT 11 The inverter supplies too low voltage internal error TOO LOW VOLT SHORT CIRCUIT MAYOR 12 Inverter short circuit internal error CHECK OUTPUT PHASE ERROR 13 Reverse input lead sequence detected CHECK AC INPUT OVERHEAT 14 Device overheated REDUCE TEMP 15 NO EVENTS No events in the register The LCD displays shows five most recent events They are numbered from 1 to 5 where 1 is most recent and 5 oldest event Event
28. ter systems by filtrating disruptions on the receiver s power supply line AC input can be adjusted depending on the grid voltage waveform it is a high power factor system PWM control ensures that output voltage can have an undisrupted and stable waveform e f the power grid parameters are incorrect the driver will stop the AC DC section and launch the DC DC section immediately to ensure uninterrupted work of the DC AC section inverter When the power grid parameters are back to regular the DC DC section will stop and the AC DC will resume its work This ensures that the receiver is uninterruptedly supplied with power by the inverter if the UPS is on e The UPS ensures an internal bypass to allow the receivers to obtain power grid input when the UPS is damaged e The UPS is fitted with an internal battery charger which recharges the battery when the grid parameters are acceptable with the exception of the backup mode or battery testing mode 2011 04 19 www ever eu 3 Instruction manual for Powerline RT MODE DESCRIPTION e Stand by mode The UPS is deactivated output disconnected no power supply e Bypass mode The bypass mode means that the UPS provides power supply to the receiver directly through the internal bypass without regulation If the driver detects incorrect power supply parameters the output is disconnected and the UPS goes into the bypass mode to protect the receiver The user can enforce the bypas
29. to the submenu FREQ CONVERSION and select FREQ CONVERSION ON After the UPS is started it will launch in the frequency conversion mode NOTE In the frequency conversion mode the available supply power N of the UPS is reduced by 50 This means that only 50 of the UPS rated power can be used when the device is in this mode UPS STOP PROCEDURE Press and hold the On Off button until the it goes into standby mode and then disconnect the power line The UPS will disconnect all outputs and switch off REMOTE POWER SUPPLY OFF EPO REMOTE ON OFF ROO Three output connector for EPO ROO circuits is on the rear panel of the device see picture NW ROO EPO Fig 12 Remote UPS on off diagrams 2011 04 19 www ever eu 30 Instruction manual for Powerline RT The UPS comes with factory installed jumper connecting outputs 1 and 2 These outputs must be joined in order for the device to operate properly In order to use the remote power off EPO remove the jumper and join outputs 1 and 2 using a standard volt free closed contact If the contact is open the UPS will switch off In order to resume regular work close the contact and restart the device following the procedure described previously In order to use the remote on function RPO join outputs 1 and 2 with the jumper UPS comes with factory made jumper and then joint outputs 2 and 3 using a standard volt free closed contact Opening of the cont
30. ual for Powerline RT POWERLINE RT 1000 BATTERY PACK 1 Battery pack power supply interface 2 RJ11 port signal lead 3 Battery pack power supply interface 4 Current protection i T Fig 7 Rear panel 2011 04 19 WWW ever eu Instruction manual for Powerline RT POWERLINE RT 2000 3000 BATTERY PACK TIT ILI ILL Fig 8 Rear panel 1 Battery pack power supply interface 2 RJ11 port signal lead 3 Battery pack power supply interface 4 Current protection 2011 04 19 www ever eu Instruction manual for Powerline RT PRODUCT SPECIFICATIONS Table 3 Technical parameters PARAMETERS MODEL POWERLINE RT 1000 POWERLINE RT 2000 POWERLINE RT 3000 Output power 1000 VA 800 W 2000 VA 1600 W 3000 VA 2400 W Casing Rack Tower Rack Kit optionally available Topology Double conversion VFI Intended application Backup for IT devices INPUT Rated input voltage 200 240 VAC Input voltage operating range 1 Cubase d ice Rated input frequency 50 60 Hz Input frequency operating range 40 70 Hz input output synchronisation range 50 60 Hz 5 Power factor 0 99 batteries charged OUTPUT Voltage waveform Sine Rated output voltage 200 208 220 230 VAC default 240 V configured using user software and LCD display Voltage regulation 2 Ouput frequenc
31. va 28 Initial UPS start procedure sets is cies te ERR PUE e bei dinesqu mier bee 28 Regular UPS Start procedure re Pee eod ate e ia hereto 29 BYPASS MODE PROCEDURES secu ywe o nien Ie ee A OEE 29 ECO MODE PROCEDURE teer pi he sert OS ES bite tcp hat eu uices 30 FREQUENCY CONVERTER MODE PROCEDURE eerte eene ener nent nennen 30 UPS STOP PBROCEDURE 5 vehere e e men ete e er be e res 30 REMOTE POWER SUPPLY OFF EPO REMOTE ON OFF 30 BATTERY MAINTENANCE aaa O NZL A di a e ee eh 31 CLEANING ete bere Ba O z adh O setae LS a ICE 31 UPS STORAGE 5 attra etant b 31 BATTERY TESTING ren oh ted rite ete er che t rere d ndi ale eit ei mete 32 BATTERY REPLACEMENT nino OOO i alte RA a Pe ee eR A 32 External UPS battery pack replacement cisarina te reco Wsz 32 TROUBLESHOOTING ree 2 tret ter een ate ed i re E eq dr RE 36 TRANSPORT AND STORAGE nre np ed i BD Rete 37 LAWS REGULATIONS AND THE WARRANTY eese nennen 37 WARRANTY eet ere deci peret e tede or ee aee tee Ede ege se e Eden 37 2011 04 19 www ever eu 2 Instruction manual for Powerline RT PRODUCT INTRODUCTION HOW IT WORKS BYPASS ACIDC PFC EXTERNAL BATTERY PACK CONNECTOR Fig 1 Block diagram e A series of double conversion on line topology UPS which provides excellent protection for the connected receivers such as compu
32. w a is there correct supply voltage at the UPS input b Is the input fuse damaged Did battery pack fuses switch off automatically Table 6 Recommendations Problem Possible cause Corrective measures No recommendation No alarm sound UPS off Grid power switched off Switch on the grid power switch No grid power voltage Order grid power inspection from a qualified electrician Burnt input fuse or circuit protection automatically switched off Replace with a fuse of the same type or Switch on circuit protection If the problem persists contact the appropriate customer Service representative Overload message on the LCD display Receiver connected Overload error UPS is overloaded Check the value of the current supplied by the receivers Reduce the number of the connected receivers Restart the UPS A battery error message is displayed on the LCD Battery error detected during the automatic battery test Inspect if the battery connector is properly connected Replace the battery pack Battery error LED flashes long sound signal approx every hour Battery lifespan is ending battery duty time is reduced Switch off the alarm by pressing the ESC button for 3 seconds Replace the battery pack An internal error message is displayed on the LCD UPS error Contact the authorised customer service representative Overheat error message is displayed on the LCD
33. xic waste and under the law must be disposed of or recycled by an authorised recycling centre The manufacturer s service centre is fully equipped to handle such batteries in compliance with the law and paying utmost attention to environmental protection Contact the customer service representative to arrange for battery maintenance and or replacement After the battery replacement the certified disposing recycling company must dispose of recycle the used batteries The appropriate utilisation of used electric and electronic equipment helps protect human health and the natural environment against the negative effects brought about by the presence of hazardous materials and components and the improper storage and processing of such equipment Act of 29 July 2005 on Waste Electric and Electronic Equipment Article 22 1 Point 1 2 Z 9 The crossed out waste container symbol means that in the European Union a used product should be handed over to a special waste handling outlet This concerns both the device itself NN and all the accessories marked with this symbol Such products should not be disposed of together with unsorted municipal waste 2011 04 19 www ever eu 35 Instruction manual for Powerline RT TROUBLESHOOTING Although the UPS is highly reliable certain problems may appear and users are advised to check whether they match the descriptions of most common problems and how to solve them belo
34. y 50 60 Hz 0 5 same as for the input or selected in the frequency conversion mode Harmonic distortion THDV linear non linear receiver PETRO Switching time grid backup grid 0 ms Overload range network power mode for the load having PF 0 8 110 warning 111 135 96 12 seconds UPS switching to bypass mode 135 96 1 5 second UPS off Short circuit protection Yes GREENPOWER function activation threshold SW BATTERIES Type Sealed maintenance free lead acid VRLA Configuration 1x3x9Ah 1x 6x9Ah 1x6x9Ah kk ea internal galleries 7 10 17 5 min 7110 17 5 min 3 5 10 5 min only 100 80 50 Pmax Support time with battery modul 100 80 50 Pmax 27 1 35 60 min 27 1 35 60 17 5 22 38 min Advanced battery control Yes Battery management Automatic battery pack detection automatic autonomy time calculation deep discharge protection GENERAL INFORMATION Bypass mode Yes automatic Grid mode efficiency 86 88 90 ECO mode efficiency gt 93 Maximum noise level at a distance of tante 41 dB 47 dB 47 dB Variable fan speed Yes Option to connect external battery packs Yes maximum 4 pcs CONNECTION Communication ports 1 x DB9 RS 232 1 x USB Communication socket 1 x socket for SNMP TCP IP Web interface or for voltage less contact card Remote power supply off EPO Yes