Riello Sentinel Pro 1000VA
Contents
1. Check the connection to the load THE INPUT VOLTAGE IS i OUTSIDE THE PERMITTED Problem with the mains Wait until the input mains TOLERANCE RANGE FOR voltage returns within the tolerance range The UPS will THE UPS IS OPERATING MAINS OPERATION automatically return to mains operation FROM THE BATTERY DESPITE THE PRESENCE OF MAINS VOLTAGE If present reset the circuit breaker by pressing the INTERVENTION OF THE button on the back of the UPS INPUT CIRCUIT BREAKER CAUTION Check that there is no output overload to the UPS THE UPS DOES NOT COME ON AND THE DISPLAY SHOWS THE CODE A06 A08 THE TEMPERATURE OF Check the temperature of the environment in which the THE UPS IS LOWER THAN UPS is located if it is too low bring it past the minimum 0 C threshold 0 C THE DISPLAY SHOWS THE FOLLOW CODES INPUT RELAY FAULTY L10 L11 F11 Switch off and disconnect the UPS from the power supply and contact the support centre THE DISPLAY SHOWS CONTROL CARD IS Switch off and disconnect the UPS from the power THE FOLLOW CODE L02 INSERTED CORRECTLY supply and contact the support centre 20 PROBLEM POSSIBLE CAUSE SOLUTION THE BUZZER SOUNDS CONTINUOUSLY AND Reduce the load to within the threshold of 100 or user THE DISPLAY SHOWS THE LOAD APPLIED TO hea demas Erde el dd Tono xti remove ihe lesa and switch the UPS off and back on CODES A54 F50 F51 F52 F55 L50 L51
2. The effective value rms of the output frequency and voltage is constantly controlled by the microprocessor independently from the waveform of the mains voltage maintaining the output frequency synchronised to the mains within a configurable range Outside this range the UPS output de synchronises from the mains supply moving to the nominal frequency in this condition the UPS cannot use the bypass In order to optimise performance in ECO mode the load is normally powered by the bypass If the mains goes out of the permitted tolerance range the UPS switches to ON LINE operation If the mains returns within the permitted tolerance range for at least five minutes the UPS goes back to powering the load from the bypass ADDITIONAL FUNCTIONS MANUAL BYPASS Using the Manual Bypass feature the UPS can be switched to bypass In this condition the load is powered directly by the input mains any disruption in the mains directly affects the load CAUTION BEFORE CARRYING OUT THE FOLLOWING SEQUENCE OF OPERATIONS ENSURE THAT THE UPS S INPUT AND OUTPUT FREQUENCY COINCIDE AND THAT THE UPS IS NOT OPERATING FROM THE BATTERY Attention even when the UPS is switched on the load is disconnected in the event of a mains blackout If the input mains deviates from the established tolerances the UPS automatically switches to Stdby mode and disconnects the load To force the UPS into manual bypass mode press and hold down the ON and SEL keys si
3. ON button for at least 5 seconds All the icons on the display light up for 1 second 3 Switch on the equipment connected to the UPS SWITCHING OFF THE UPS In order to switch off the UPS hold down the STBY button for at least 2 seconds The UPS goes back to stand by mode and the A icon starts to flash 1 Ifthe mains power is present the ON OFF switch must be pressed to completely turn off the UPS 2 During battery mode operation with the timer not set the UPS automatically switches off after 30 seconds If on the contrary the timer is set press and hold down the STBY key for at least 5 seconds to turn off the UPS For complete shutdown press the ON OFF switch 12 DISPLAY PANEL MESSAGES This chapter describes in detail the various information that can be displayed on the LCD UPS STATUS MESSAGES ICON STATUS DESCRIPTION Indicates a fault Flashing The UPS is in stand by mode Indicates regular operation Fixed The UPS is operating from the mains The UPS is operating from the mains but the output voltage is not Flashing i synchronised with the mains voltage i The UPS is operating from the battery In this condition the UPS emits Fixed ane an acoustic signal beep at regular 4 second intervals Low battery pre alarm Indicates that battery autonomy is coming to an Flashing end In this condition the UPS emits a beep at regular 1 second intervals Indicates that the loads connected
4. the Lr Corresponding code is corresponding code is displayed LL displayed The values shown in the images in the table are purely as an indication The FAULT LOCK codes only be displayed if they are active presence of a fault alarm or a lock 14 CONFIGURING THE OPERATING MODE The area of the display shown in the figure displays the active operating ELT mode and allows the user to choose other modes directly from the display panel SMART MODE 9 HOW TO PROCEED To access the configuration area hold down the SEL button for at least seconds e The icon corresponding to the mode currently set lights up ochange the mode press the ON button e Toconfirm the mode chosen hold down the SEL button for at least 3 seconds POSSIBLE SETTINGS The UPS is designed to be configured in various operating modes e ON LINE is the mode with the greatest load protection and the best quality of the output waveform e is the mode with which the UPS consumes the least power so is therefore the most efficient e SMART ACTIVE in this mode the UPS decides whether to operate in ON LINE or ECO mode according to a statistic about the quality of the mains power e STAND BY OFF Mode 1 the UPS operates as an emergency power supply If mains power is present the load is not powered however should the mains supply fail the load is powered by the UPS
5. Mains operation Battery operation Load powered by bypass 0 G5 IN OUT BATT LOAD TEMP FAULT LOCK SET A Cu 11111 2 VAN Hz min f 25 Tso 75 1100 AD 19 AN 5 6 7 9 49 IN OUT BATT LOAD TEMP FAULT LOCK SET 9 ES 101107 VA N Hz min Battery charge indicator Load level indicator Configuration area Maintenance request Timer Measurement display area Stand by alarm 8 BATTERY BOX ACCESSORY NOT PROVIDED WITH UPS The BATTERY BOX is an optional accessory dedicated to this range of UPSs same dimensions and aesthetic line The BATTERY BOX contains batteries which allow the operating time of the uninterruptible power supplies to be increased during extended blackouts The number of batteries contained can vary according to the type of UPS for which the BATTERY BOX is intended It is therefore necessary to take great care to ensure that the battery voltage of the BATTERY BOX is the same as the voltage permitted by the UPS It is possible to connect further BATTERY BOXES in order to create a chain suitable for achieving any autonomy time without mains power REAR VIEW 36V Battery Box 1 Battery disconnector SWBATT 2 Battery expansion connector INSTALLATION INITIAL CONTENT CHECK After opening the packaging it is first necessary to check the contents The package must contain UPS Schuko power cable IEC 10A I
6. L52 agal THE DISPLAY SHOWS THE FOLLOW CODE A61 REPLACE THE BATTERIES Contact the support centre for battery replacement BATTERIES MISSING OR On the versions with an additional battery charger in BATTERY BOX MISSING OR place of the batteries check that the Battery Box is NOT CONNECTED inserted and connected to the UPS correctly THE DISPLAY SHOWS THE FOLLOW CODE A62 THE BATTERIES ARE FLAT THE UPS IS WAITING FOR Wait until the batteries have recharged or force power THE BATTERY VOLTAGE manually by holding down the ON button for at least TO EXCEED THE SET 2 seconds THRESHOLD THE DISPLAY SHOWS THE FOLLOW CODE A63 THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS THE UPS IS If possible disconnect the power to the load switch the ONE OF THE FOLLOWING MALFUNCTIONING IT WILL UPS off and back on again if the problem occurs again CODES F03 F05 F07 PROBABLY LOCK SOON call the support centre F13 F21 F40 F41 F42 F43 THE BUZZER SOUNDS CONTINUOUSLY AND THE TEMPERATURE OF THE DISPLAY SHOWS THE DISSIPATORS INSIDE ONE OF THE FOLLOWING THE UPS IS TOO HIGH CODES F04 L04 Check that the temperature of the environment in which the UPS is located does not exceed 40 C THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS ONE OF THE FOLLOWING CODES F53 L53 THERE IS A FAULT ON ONE OR MORE OF THE UTILITIES POWERED BY THE UPS Disconnect all the utilities switch the UPS off and back on agai
7. UPS power off in battery operation mode if Disabled the charge is lower than 5 Output voltage 220 240 in 1V steps e Enabled e Disabled Power off due to minimum charge Autonomy limit Maximum battery operation Disabled e Disabled complete battery discharge time 1 65000 sec in 1 sec steps Estimated autonomy time remaining for the battery in 1 255 min in 1 min steps low warning Battery test Interval of time for the i beue e Disabled automatic battery test e 1 1000 h in 1 hour steps Maximum charge Selects the user overcharge Disabled e Disabled alarm threshold limi e 0 103 in 1 steps Battery low warning Selects the permitted range for the input frequency for switching to the bypass and 3 10 in 1 steps for the synchronisation of the output Input frequency tolerance range For configurations of the Fout 50 60Hz or if the sync is disabled with the input the UPS downgrades the output power 17 FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS Bypass voltage thresholds Bypass voltage threshold for ECO Intervention sensitivity for ECO Power on delay Remote power on off function Selects the permitted voltage range for switching to the bypass Selects the permitted voltage range for operation in ECO mode Selects the intervention sensitivity during operation in ECO mode Waiting time for automatic switching back after mains power r
8. in the UPSTools directory or downloaded from the web site www riello ups com CAUTION If the RS232 communication port is used it is not possible to communicate with the USB port and vice versa It is advisable to use a cable which is shorter than 3 metres for communication with the UPS To obtain additional communication ports with different functions independent from the standard USB and RS232 ports on the UPS various accessories are available which can be inserted into the communication card slot check whether new more up to date software versions are available and for more information about the accessories available consult the website www riello ups com 16 UPS CONFIGURATION The table below illustrates all the possible configurations available to the user in order to best adapt the UPS to individual requirements It is possible to perform these operations using the Upstools software FUNCTION DESCRIPTION DEFAULT POSSIBLE CONFIGURATIONS e 50 Hz e 60 Hz e Auto automatic learning of the input frequency Selects the nominal output Output frequency frequency Selects the nominal output voltage e ONLINE Selects one of the 4 e ECO different operating modes DL e SMART ACTIVE e SIAND BY OFF MODE 1 Selects the mode of use of Bypass operation the bypass line Normal e Disabled with input output synchronisation y e Disabled without input output synchronisation Automatic
9. A HH H ir Sh a It is possible to use one or more autonomy expansion units known as BATTERY BOXES optional accessories with the same dimensions and aesthetic line as the UPS alongside it require long battery powered operating times For these versions the batteries are housed in separate cabinets which The ER model UPSs fitted with upgraded battery chargers are the solution for Business Continuity applications which are designed to contain large high capacity batteries UPS VIEWS FRONT VIEW REAR VIEW 700VA 1500VA model AR x SN H P SIIA 5 15 Te Display Multipurpose buttons ON OFF switch USB communication port D 2 3 5232 communication port and contacts 5 6 Slot for communication cards e C mi E A it E L h Ed 1000VA 1000VA ER model Cooling fans Battery expansion connector IEC 10A output socket IEC 10A input plug Circuit breaker YO 9 2200VA model RS232 communication port and contacts USB communication port Slot for communication cards Cooling fans Battery expansion connector C 16A output socket only for 3000VA models IEC 10A output socket IEC 16A input plug IEC 10A input plug Circuit breaker DISPLAY PANEL VIEW 000 E SEL button Select ON button STAND BY button Regulation operation
10. BATTERY BOX ACCESSORY NOT PROVIDED WITH UPS REAR VIEW INSTALLATION INITIAL CONTENT CHECK INSTALLATION ENVIRONMENT BATTERY BOX INSTALLATION SETTING THE NOMINAL BATTERY CAPACITY USE CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME SWITCHING ON FROM THE MAINS SWITCHING ON FROM THE BATTERY SWITCHING OFF THE UPS DISPLAY PANEL MESSAGES UPS STATUS MESSAGES MEASUREMENT DISPLAY AREA CONFIGURING THE OPERATING MODE POSSIBLE SETTINGS ADDITIONAL FUNCTIONS SOFTWARE MONITORING AND CONTROL SOFTWARE CONFIGURATION SOFTWARE UPS CONFIGURATION COMMUNICATION PORTS RS232 CONNECTOR COMMUNICATION SLOT o o o iO 10 10 11 11 11 12 12 12 12 12 13 13 14 15 15 15 16 16 16 17 19 19 19 TROUBLESHOOTING ALARM CODES FAULT LOCK TECHNICAL DATA 20 22 22 23 24 PRESENTATION SENTINEL PRO uses ON LINE double conversion technology resulting in the highest levels of reliability and maximum protection for critical loads such as servers IT applications and Voice Data TA MY VA a m J bend AAA AZ TAA A B DAD ART TARA ADA HAS SIM A DANA EAE QAUM Neun er ZI T4EIZTAX iOS Ss A DEN o NND EPI IT 7 7 7 7 7 III III RAR
11. EC 16A for 3000VA models only IEC 16 male plug 2 IEC 10A connection cables For 3000VA models only USB cable RS232 cable User manual CD Safety manual Battery expansion plug ER version only 10 INSTALLATION ENVIRONMENT The UPS and the Battery Box must be installed in ventilated clean environments which are sheltered from bad weather The relative humidity in the environment must not exceed the maximum values shown in the Technical Data table The ambient temperature whilst the UPS is in operation must remain between O and 40 C and the UPS must not be positioned in places which are exposed to direct sunlight or to hot air The recommended operating temperature for the UPS and the batteries is between 20 and 25 C The actual operating life of the batteries is 5 years on average with an operating temperature of 20 C If the operating temperature reaches 30 C the operating life is halved BATTERY BOX INSTALLATION CAUTION CHECK THAT THE BATTERY BOX VOLTAGE IS THE SAME AS THE VOLTAGE PERMITTED BY THE UPS CHECK THE RATING ON THE BACK OF THE DEVICE It is possible to connect more than one Battery Box in order to achieve any level of autonomy without mains power Connect any Battery Boxes in a cascade as shown in the figure below SETTING THE NOMINAL BATTERY CAPACITY Before installing one or more Battery Boxes the UPS must be configured in order to upda
12. Nominal voltage Vac 220 230 240 Maximum operating voltage Vac 30 Nominal frequency Hz 50 60 Nominal curent 1 A BATTERY Recharge time standard versions h lt 4h for 80 of the load Expandability and nominal Not Not voltage of the Battery Box expandable expandable TANCE Charging current Not Not OUTPUT Nominal voltage 4 Vac Selectable 220 230 240 Frequency 2 Hz Selectable 50 60 or auto sensing Nominal power VA 1000VA 1500VA 2200VA 3000VA Nominal power IW 560W 800W 1200W 1760W 2400W Bypass line available activates the bypass after 2 seconds Overload 100 lt load lt 110 locks after 120 seconds Bypass line not available locks after 60 seconds Bypass line available activates the bypass after 2 seconds gt 0 0 Overload 110 lt load lt 150 locks after 4 seconds Bypass line not available locks after 4 seconds Bypass line available activates the bypass instantly Overload load gt 150 locks after 1 second Bypass line not available locks after 0 5 seconds OTHER Ambient temperature 5 Humidity lt 90 without condensation excessively low batteries overcurrent short circuit overvoltage Protection devices iu undervoltage circuit breaker Dimensions W x Dx H mm 158 x 422 x 235 190 x 446 x 333 Not Weight for ER versions only kg applicable 7 applicable 14 15 For more details please consult the web si
13. eturns Selects the function associated with the RS232 connector Disabled 180 200 in 1V steps 250 264 in 1V steps 180 220 in 1V steps 240 264 in 1V steps Disabled 1 255 sec in 1 sec steps Disabled Remote ON Remote OFF Remote ON OFF 18 COMMUNICATION PORTS On the back of the UPS see UPS Views the following communication ports are present e RS232 connector e USB connector e Expansion slot for additional communication cards RS232 CONNECTOR SIGNAL NOTES Programmable output default UPS in lock SS Opto isolated contact max 30Vdc 35mA TXD RXD These contacts can be associated with other events using Programmable input the software provided default disabled GND Opto isolated command 5 15Vdc These contacts can be associated with other events using the software provided Power supply DC Imax 20mA Programmable input default disabled For further information about interfacing with the UPS refer to Programmable output the manual provided default low battery pre alarm Programmable output default battery operation COMMUNICATION SLOT The UPS is equipped with an expansion slot for optional communication cards see figure on right which allows the device to communicate using the main communication standards Some examples e Second RS232 and USB po
14. lems which do not cause the lock of the UPS but reduce performance or prevent certain functions from being used Sensor1 temperature under 0 C A08 Load percentage greater than the user threshold set Alarms these are more critical problems than anomalies because if they persist they could cause the UPS to lock in a very short time Fo Incorrect auxiliary power supply Fo Dissipator overtemperature Temperature sensor1 faulty F07 Temperature sensor2 faulty Input relay faulty FN _ FM Fa Continuous ouput votage Fs Feo Waiting for load reduction to return to inverter Battery overvoltage 22 gt Active commands Indicates the presence of an active remote command Remote control 1 Switch On Off Remote control 2 load on bypass or manual bypass command Remote control 3 Switch On Off Battery test in progress Lock LOCK alerts are normally preceded by an alarm signal and their scale leads to the power off of the inverter and the load being powered by the bypass line this procedure is excluded for locks due to serious persistent overloads and short circuits Se pre charge failed Continuous a voltage 23 TECHNICAL DATA SEP 1000 SEP 2200 SEP 3000 sen zoer ser sooner INPUT
15. manuale d installazione ed uso installation and use manual installations und bedienungsanleitung manuel d installation et d utilisation manual de instalaci n y uso SENTINEL PRO ser 1000 2200 3000 r MN SENTINEL kS T Wiiellov SENTINEL RO RIELLO ELETTRONICA 7 riello ps 98 INTRODUCTION Congratulations on purchasing a UPS Sentinel Pro product and welcome to Riello UPS To use the support service offered by Riello UPS visit the site www riello ups com The company is highly specialised in the development and production of uninterruptible power supplies UPSs The UPSs in this series are high quality products carefully designed and manufactured in order to ensure the highest levels of performance This device can be installed by anyone on the condition that he she has READ THE USER AND SAFETY MANUAL CAREFULLY The UPS and the Battery Box internally generate DANGEROUS electrical voltages All maintenance operations must be carried out SOLELY by qualified operators This manual contains detailed instructions for using and installing the UPS and the Battery box For information about using and making the most of the performance of your device please keep hold of the CD containing this manual and read it carefully before operating the equipment ees ENVIRONMENTAL PROTECTION In the development of its product
16. multaneously for at least 4 seconds The code C02 appears on the display To return to the normal operation mode press the ON and SEL keys again for at least 4 sec 15 SOFTWARE RS232 USB MONITORING AND CONTROL SOFTWARE The PowerShield software guarantees effective intuitive UPS management displaying all the most important information such as input voltage applied load battery capacity It is also able to perform shutdown operations and send e mails text messages and network messages automatically when certain events selected by the user occur INSTALLATION OPERATIONS 1 Connect one of the UPS s communication ports to one of the PC s communication ports using the cable supplied 2 Download the software from the web site www riello ups com selecting the specific operating system 3 Follow the installation program instructions 4 For more detailed information please read the user manual which can be downloaded from www riello ups com CONFIGURATION SOFTWARE The UPSTools software allows the configuration and full display of the status of the UPS via USB or RS232 For a list of possible configurations available to the user refer to the UPS Configuration paragraph INSTALLATION OPERATIONS 1 Connect one of the UPS s communication ports to one of the PC s communication ports using the cable supplied 2 Follow the installation instructions shown within the software manual which can be located
17. n reconnect the utilities one at a time to identify which one is faulty THE BUZZER SOUNDS CONTINUOUSLY AND THE DISPLAY SHOWS THE UPS IS If possible disconnect the power to the load switch the ONE OF THE FOLLOWING MALFUNCTIONING UPS off and back on again if the problem occurs again CODES F60 L03 L05 call the support centre L07 L13 L20 L21 L40 L41 L42 L43 PO ee ee A REMOTE COMMAND IS_ If unwanted check the status of the command inputs on ONE OF THE FOLLOWING ACTIVE any optional contact card CODES C01 C02 C03 y op THE DISPLAY SHOWS THE MANUAL BYPASS To exit manual bypass mode press the ON SEL C02 FUNCTION IS ACTIVE buttons at the same time for at least 4 seconds ATTENTION The UPS in case of a permanent failure will be not able to supply the load To ensure total protection of your equipment we suggest you install an ATS device Automatic Transfer Switch or an external automatic by pass For more information visit www riello ups com 21 x SSS ALARM CODES Using a sophisticated self diagnosis system the UPS is able to check its own status and any anomalies and or faults which may occur during normal operation and display them on the display panel If there is a problem the UPS signals the event by showing the code and the type of active alarm on the display FAULT and or LOCK FAULT FAULT alerts can be divided into three categories gt gt Anomalies these are minor prob
18. rt e Serial duplicator e Ethernet network card with TCP IP HTTP and SNMP protocols JBUS MODBUS protocol converter card e PROFIBUS protocol converter card e Card with relay isolated contacts check whether further accessories are available consult the website www riello ups com 19 TROUBLESHOOTING Irregular UPS operation is most likely not an indication of a fault but due to simple problems or distraction It is therefore advisable to consult the table below carefully as it summarises information which is useful for solving the most common problems PROBLEM POSSIBLE CAUSE SOLUTION ON OFF SWITCH NOT PRESSED Press the ON OFF switch on the front panel MAIN Check that the power cable is connected correctly THE DISPLAY DOES NOT LIGHT UP NO MAINS VOLTAGE Check that the power reaches the socket where the UPS BLACKOUT is connected try it with a table lamp for example If present reset the circuit breaker by pressing the INTERVENTION OF THE button on the back of the UPS INPUT CIRCUIT BREAKER CAUTION Check that there is no output overload to the UPS THE UPS IS IN STAND BY the ON button on the front panel to power the MODE loads It is necessary to change mode THE STAND BY OFF MODE IS SELECTED The STAND BY OFF emergency power supply mode THE DISPLAY IS ON BUT THE LOAD IS NOT POWERED in fact only powers the loads in the event of a blackout NO v
19. s the company devotes abundant resources to analysing the environmental aspects All our products pursue the objectives defined in the environmental management system developed by the company in compliance with applicable standards No hazardous materials such as CFCs HCFCs or asbestos are used in this product When evaluating packaging the choice of material has been made favouring recyclable materials For correct disposal please separate and identify the type of material of which the packaging is made in the table below Dispose of all material in compliance with applicable standards in the country in which the product is used Cardboard Box Packaging corner Stratocell Protective bag Polythene DESCRIPTION MATERIAL Bo E s DISPOSING OF THE PRODUCT The UPS and the Battery Box contain electronic cards and batteries which are considered TOXIC and HAZARDOUS waste When the product reaches the end of its operating life dispose of it in accordance with applicable local legislation Disposing of the product correctly contributes to respecting the environment and personal health The reproduction of any part of this manual in whole or in part is forbidden without the prior consent of the manufacturer In order to make improvements the manufacturer reserves the right to modify the product described at any moment and without notice CONTENTS PRESENTATION UPS VIEWS FRONT VIEW REAR VIEW DISPLAY PANEL VIEW
20. te at nominal load nominal voltage of 230 Vac battery charging 2 If the mains frequency is within 5 of the selected value the UPS is synchronised with the mains If the frequency is out of the tolerance range or operating from the battery the frequency is the one selected 0 1 9 20 25 C for longer battery life To keep the output voltage within the indicated range of precision recalibration may be necessary after a long period of operation 24 BATTERY BOX JSEP036 NPA JSEP036 NPM JSEP072 NPA JSEP072 NPM Nominal battery voltage Vdc 36Vdc 72Vdc Dimensions WxDxH 158 x 422 x 235 190 x 446 x 333 The symbol replaces an alphanumeric code for internal use 25 RIELLO ELETTRONICA RPS SPA Viale Europa 37045 LEGNAGO VR Tel 39 0442 635811 Fax 39 0442 629098 www riello ups com riello riello ups com OMNSEP700RUENUC
21. te the nominal capacity value total Ah UPS s internal batteries external batteries using the dedicated configuration software UPSTools contains in the CD ROM supplied with the UPS The battery box must be installed while the UPS is switched off and disconnected from the main CAUTION The connection cables cannot be extended by the user After connecting the UPS to its Battery Boxes insert the fuses and turn the Battery Box battery isolators SWBATT to the ON position It is not possible to connect more than one UPS to a single battery box or to several Battery Boxes connected in a series A a gt y check whether a new version of the most up to date software is available consult the website www riello ups com 11 SE A A A A _ CONNECTIONS AND SWITCHING ON FOR THE FIRST TIME 1 Check that there is a protection device against overcurrents and short circuits in the system upstream from the UPS The recommended protection value is 10A for the 700VA 1000VA and 1500VA versions and 16A for the 2200VA 3000VA and ER versions with a B or C trip curve 2 Power the UPS using the input cable provided 3 Press the ON OFF switch located on the front panel 4 After a few moments the UPS will switch on the display will light up there will be a beep and the A icon will start to flash The UPS is in stand by mode meaning that it is only consuming a small amount of power The microcontroller is powered which super
22. to the UPS are powered by the bypass EAJEJEJ 100 Dynamic Indicates the estimated percentage charge of the batteries BATTERY 25 50 75 400 Dunne Indicates the percentage of charge applied to the UPS compared with y the nominal value Flashing Maintenance is required Contact the support centre Fixed Indicates that the timer is active programmed switch on and switch off 4 The timer can activated deactivated using software provided Flashing 1 minute until the UPS switches back on or 3 minutes until it switches off 13 MEASUREMENT DISPLAY AREA It is possible to display the most important measurements regarding the UPS in sequence on the display When the UPS is switched on the display shows the main voltage value To display a different measurement press the SEL button repeatedly until the desired measurement appears In the event of a fault alarm FAULT or a lock LOCK the display will automatically show the type and code of the corresponding alarm Some examples are shown below GRAPHIC EXAMPLE DESCRIPTION GRAPHIC EXAMPLE DESCRIPTION Battery charge Mains voltage percentage Mains frequency g Total battery voltage UPS output voltage Applied load percentage Current absorbed by the Output voltage frequency load Temperature of the Residual battery autonomy electronics cooling system inside the UPS E Fault Alarm 2 the gt TNT Lie Lock
23. vises the self diagnoses the batteries are charging everything is ready for UPS activation Battery operation is also in stand by mode provided that the timer is active 5 Connect the equipment to be powered to the sockets on the back of the UPS using the cable supplied or a cable no longer than 10 metres CAUTION do not connect equipment which absorbs more than 10A to the IEC 10A sockets For equipment which exceeds this level of absorption use the IEC 16A socket only available on the 3000VA version 6 Check which operating mode is set on the display and if necessary see the Configuring operating modes paragraph to set the required mode For advanced UPS configurations execute the software UPSTools which can be downloaded from the web site www riello ups com SWITCHING ON FROM THE MAINS 1 Press the ON button for 1 second After pressing it all the icons on the display light up for 1 second and the UPS beeps 2 Switch on the equipment connected to the UPS When switching on for the first time only after 30 seconds check that the UPS is operating correctly 1 Simulate a blackout by disconnecting power to the UPS 2 The load must continue to be powered the icon on the display must light up and there must be a beep every 4 seconds 3 When power is reconnected the UPS must go back to operating from the mains SWITCHING ON FROM THE BATTERY 1 Press the ON OFF switch located on the front panel 2 Hold down the
Download Pdf Manuals
Related Search
Related Contents
Philips Multimedia Speakers 2.1 SPA4355 WR series / User`s Manual - DAS Audio Copper User Manual Nobo 1902117 Installation and User Guide CNG Vehicles Refueling Appliance téléchargez ici le jugement controller user's manual Contents How do I update the BIOS of my Area-51 m9750 to XP Copyright © All rights reserved.