        Sun Storage 2500-M2 Arrays Site Preparation Guide
         Contents
1.  are generated by normal operation of the unit     TABLE 2 4 lists the environmental conditions in which the array is designed to    operate     TABLE 2 4 Controller Tray Temperature          Parameter    Requirement       Operating range  both cabinet and subsystem   Maximum rate of change   Storage range   Maximum rate of change   Transit change    Maximum rate of change    50  F to 104  F  10  C to 40  C   50  F  10  C  per hour   14  F to 122  F   10  C to 50  C   59  F  15  C  per hour      40  F to 140  F  40  C to 60  C   68  F  20  C  per hour         Tf you plan to operate a system at an altitude between 3280 feet to 9842 feet  1000 meters to 3000 meters  above  sea level  lower the environmental temperature 3 3  F  1 7  C  for every 3280 feet  1000 meters  above sea level     Humidity    TABLE 2 5 lists the relative humidity ranges of the controller tray     TABLE 2 5 Humidity  noncondensing        Parameter    Specification       Operating range  both cabinet and  subsystem     Storage range  Transit range  Operating gradient    Storage gradient    20  to 80   noncondensing     10  to 90    5  to 90    50  F  10  C  per hour maximum  59  F  15  C  per hour maximum       Chapter 2    Sun Storage 2500 M2 Arrays Specifications 7    TABLE 2 5 Humidity  noncondensing        Parameter Specification   Transit gradient 68  F  20  C  per hour maximum  Maximum dew point 79  F  26  C    Maximum gradient 10  per hour    Altitude    TABLE 2 6 lists the altitude specifications f
2.  nominal input voltage     Power Cords and Receptacles    Sun Storage 2500 M2 Arrays are shipped with either two AC power cords or two DC  power cords per tray  depending on the configuration ordered     AC Power Cords    Each AC power cord connects one of the power supplies in a tray to an independent   external AC power source  such as a wall receptacle or a UPS     If you have a cabinet with internal power cabling  such as a ladder cord  you do not  need the AC power cords that are shipped with the controller drive tray     Chapter 2 Sun Storage 2500 M2 Arrays Specifications 11    DC Power Connector Cables    Each  48 VDC power connector cable plugs into the DC power connector on the  back of the controller tray  The three source wires on the other end of the power  connector cable connect the tray to centralized DC power plant equipment  typically  through a bus bar above the cabinet     Caution     A qualified service person is required to make this DC power connection  according to NEC and CEC guidelines           Caution     Risk of electrical shock   This unit has more than one power source  To  remove all power from the unit  all DC MAINS must be disconnected by removing  all power connectors from the power supplies        Two  optionally four  DC power connector cables are provided with each controller  or expansion tray  Two DC power connectors are on the back of each tray   s DC  power supply if additional redundancy is required     Note   It is not mandatory that
3.  not block or cover the openings of your product  Never place a  product near a radiator or heat register  Failure to follow these guidelines can cause  overheating and affect the reliability of your product        Air cools the system cabinets from front to back  Air enters at the front  circulates   and is expelled at the back of the cabinet  The front and back door clearances  provide sufficient space for cooling  See Chapter 2 for specific clearance  specifications     Chapter 1 Planning for the Installation    3    Site Preparation Guide   August 2011    CHAPTER 2       Sun Storage 2500 M2 Arrays  Specifications       This chapter describes the physical  environmental  and electrical requirements for  the Sun Storage 2500 M2 Arrays  It contains the following sections            Dimension and Weight Specifications    on page 6         Environmental Requirements    on page 7           Electrical Requirements    on page 9       Dimension and Weight Specifications    The floor space at the installation site must be strong enough to support the  combined weight of the cabinet  controller trays  expansion trays  and associated  equipment  The site also requires sufficient space for installation  operation  and  servicing the arrays and sufficient ventilation to provide a free flow of air to the unit     The total weight of an expansion tray depends on the number of drives installed     TABLE 2 1 provides the physical dimensions and weight of the array     TABLE 2 1 Dimensions 
4.  page 2    Note     Do not make mechanical or electrical modifications to the equipment  Oracle  Corp  is not responsible for regulatory compliance of a modified product     Handling Precautions       Ensure that all surfaces this system will move over can withstand this load        1 Caution   A fully populated cabinet can weigh in excess of 1500 pounds  682 kg      The cabinet is equipped with wheels so you can move it  Use enough personnel  when moving the cabinet  especially on sloped loading docks and ramps  to gain  access to a raised computer room floor  Move the cabinet slowly and deliberately   and make sure that the floor is free from foreign objects and cables that the cabinet  could roll over        A Caution     To avoid injury  wear protective footwear when moving a system     Secure Installation Requirements    To minimize personnel injury in the event of a seismic occurrence  you must securely  fasten the cabinet to a rigid structure extending from the floor to the ceiling  or from  the walls  of the room in which the cabinet is located     Install the cabinet on a level surface  At each corner  on the base of the cabinet  are  adjustable nonskid pads  Extend these pads when the cabinet is installed to prevent  the cabinet from rolling  Do not use these pads to level the cabinet     Placement of a Product    Allow enough room surrounding the cabinet for access to the cabinet and arrays for  maintenance     Site Preparation Guide   August 2011    Caution     Do
5.  the second DC power connection on the array   s DC  power supplies be connected  The second DC power connection is provided for  additional redundancy only and may be connected to a second DC power bus        Battery Life    For a fully rated battery backup unit  BBU  battery life  cell limitations are listed in  TABLE 2 12     TABLE 2 12 Battery Life Specifications       Operating 50  F to 95  F  10  C to 35  C     Storage 14  F to 113  F   10  C to 45  C    up to three months     Transit  4  F to 140  F   20  C to 60  C    up to seven days        12 Site Preparation Guide   August 2011    APPENDIX A    Configuration Worksheets       Use the worksheets in this appendix to help you collect the information you need to    perform the installation     TABLE A 1 lists the information you need to collect to configure the array     TABLE A 1 Sun Storage 2500 M2 Arrays Configuration Worksheet    Controller A MAC address     Controller B MAC address        Controller A IP address        Controller B IP address        Management host IP address        Network mask        Name server domain name        IP address of the domain name server  DNS         Gateway IP address        Email notification address                 13    TABLE A 2 lists the information you need to collect for each data host connected to  Sun Storage 2500 M2 Arrays     TABLE A 2 Sun Storage 2500 M2 Arrays Data Host Information       Host name        Vendor        Model        Operating system        Patch Service p
6. Sun Storage 2500 M2 Arrays    Site Preparation Guide        amp  Sun  Part No   E20737 02     en          August 2011    Copyright    2011  Oracle and or its affiliates  All rights reserved   The Sun Storage 2500 M2 Arrays Site a age Guide describes facilities and system requirements for in   stalling Sun Storage 2500 M2 Arrays  Follow the guidelines as outlined in this document when planning your  installation     This software and related documentation are provided under a license agreement containing restrictions on use and disclosure and are protected by  intellectual property laws  Except as expressly permitted in your license agreement or allowed by law  you may not use  copy  reproduce  translate   broadcast  modify  license  transmit  distribute  exhibit  perform  publish  or display any part  in any form  or by any means  Reverse engineering   disassembly  or decompilation of this software  unless required by law for interoperability  is prohibited     The information contained herein is subject to change without notice and is not warranted to be error free  If you find any errors  please report them to us  in writing    If this is software or related software documentation that is delivered to the U S  Government or anyone licensing it on behalf of the U S  Government  the  following notice is applicable     U S  GOVERNMENT RIGHTS  Programs  software  databases  and related documentation and technical data delivered to U S  Government customers  are  commercial comp
7. ack        Number of HBAs        HBA World Wide Name   WWN         HBA model        HBA driver                 14 Site Preparation Guide   August 2011    
8. and Weight       Components Height Width Depth Weight   Maximum    Weight   Emptyt       Controller tray 3 4 in   8 64 cm  19 in   48 26 cm  21 75 in   55 25 cm  59 52 Ib  27 kg  41 01 Ib  18 60 kg     Expansion tray 3 4 in   8 64 cm  19 in   48 26 cm  21 75 in   55 25 cm  57 98 Ib  26 3 kg  39 46 Ib  17 9 kg                  Maximum weight indicates a controller tray with all of its drives and other components installed  Because drive weights can vary  this  value can vary from the value specified as much as either 0 66 Ib  0 3 kg  times the maximum number of drives per controller tray for  3 5 in  SATA drives or 0 18 Ib  0 08 kg  times the maximum number of drives per controller tray for 2 5 in  SATA drives     Empty weight indicates a controller tray with the controller modules  the power fan modules  and the drives removed     TABLE 2 2 provides the weight for array components     TABLE 2 2 Controller Tray Component Weight       Component Weight       Controller module 4 70 Ib  2 131 kg   Power fan module 5 51 Ib  2 5 kg   2 5 in  SATA drive 0 66 Ib  0 3 kg   3 5 in  SATA drive 2 2 Ib  1 0 kg        TABLE 2 3 Controller Tray Shipping Weight       Height Width Depth       9 5 in   24 13 cm     25 in   63 50 cm  23 in   58 42 cm       Controller tray with twelve 3 5 in  drives     Site Preparation Guide   August 2011       Environmental Requirements    This section describes the environmental conditions that are prerequisite to installing  the unit  and heat conditions that
9. and wiring  AC power  requirements  DC power requirements  and power cord routing instructions     Site Wiring and Power    The controller tray uses wide ranging redundant power supplies that automatically  accommodate voltages to the AC power source or the optional  48 VDC power  source  The power supplies meet standard voltage requirements for both North  American  USA and Canada  operation and worldwide  except USA and Canada   operation  They use standard industrial wiring with line to neutral or line to line  power connections     Chapter 2 Sun Storage 2500 M2 Arrays Specifications 9    10    Note     Power for the optional  48 VDC power configuration is supplied by a  centralized DC power plant instead of the AC power source in the cabinet  Refer to  the associated manufacturer s documentation for specific DC power source  requirements     Consider the following information when preparing the array s installation site         Protective ground   Site wiring must include a protective ground connection to  the AC power source or the optional  48 VDC power source        Note     Protective ground is also known as safety ground or chassis ground            Circuit overloading   Power circuits and associated circuit breakers must provide  sufficient power and overload protection  To prevent possible damage to the  array  isolate its power source from large switching loads  such as air   conditioning motors  elevator motors  and factory loads          Power interruptions   Th
10. e controller tray can withstand the following applied  voltage interruptions  with or without an integrated uninterruptible power  supply  UPS         Input transient   50 percent of the nominal voltage    Duration   One half cycle    Frequency   Once every 10 seconds        Power failures   If a total power failure occurs  the controller tray automatically  performs a power on recovery sequence without operator intervention after  power is restored        Note     When a power failure occurs  the controller tray uses battery power to back  up the data that is in cache        Site Preparation Guide   August 2011    AC Power Input  The AC power sources must provide the correct voltage  current  and frequency    specified on the tray model and serial number label  The tray can run without  interruption within the limits shown in TABLE 2 11     TABLE 2 11 Tray AC Power Requirements             Condition Specification  Input voltage 100   240V   Input frequency 50 or 60Hz  Input current 7 0   2 9A    DC Power Input    The DC power source must provide the correct voltage  current  and frequency  specified on the array nameplate label and the serial number label     Nominal input voltages for the DC power source are as follows     Input voltage   42 to  60VDC      Operating current  21 7 to 15 3A    Controller Tray Power Factor Correction    Power factor correction is applied within the power supply  which maintains the  power factor of the controller tray at greater than 0 95 with
11. ml    Support https   support oracle com              Training https   education oracle com    Site Preparation Guide   August 2011    CHAPTER 1       Planning for the Installation       This chapter describes the requirements for preparing the customer site for  installation of Sun Storage 2500 M2 Arrays  It contains the following sections     m    Customer Obligations    on page 1           Safety Information    on page 1       Customer Obligations    The customer is obliged to inform Oracle Corporation of any and all ordinances and   regulations that might affect the installation  The customer is responsible for meeting   all government codes and regulations concerning facilities  The customer is also   required to do the following      Comply with all local  national  and international codes covered in this  specification  The subjects covered include fire and safety  building  and electrical  codes         Document and inform Oracle Corporation of any deviations from this  specification        Safety Information    Install Sun Storage 2500 M2 Arrays in accordance with the local safety codes and  regulations at the facility site  Make sure that you read the safety precautions in the  Sun Storage 2500 M2 Arrays Regulatory and Safety Compliance Manual    The following sections contain additional safety information for the local facility            Handling Precautions    on page 2           Secure Installation Requirements    on page 2           Placement of a Product    on
12. ns fournies dans ce document sont susceptibles de modification sans pr  avis  Par ailleurs  Oracle Corporation ne garantit pas qu elles  soient exemptes d erreurs et vous invite  le cas   ch  ant     lui en faire part par   crit     Si ce logiciel  ou la documentation qui l accompagne  est conc  d   sous licence au Gouvernement des Etats Unis  ou    toute entit   qui d  livre la licence de  ce logiciel ou l utilise pour le compte du Gouvernement des Etats Unis  la notice suivante s applique      U S  GOVERNMENT RIGHTS  Programs  software  databases  and related documentation and technical data delivered to U S  Government customers  are  commercial computer software  or  commercial technical data  pursuant to the applicable Federal Acquisition Regulation and agency specific        regulations  As such  the use  duplication  disclosure  modification  and adaptation shall be subject to the restrictions and license terms set  forth in the applicable Government contract  and  to the extent applicable by the terms of the Government contract  the additional rights set forth in FAR  52 227 19  Commercial Computer Software License  December 2007   Oracle America  Inc   500 Oracle Parkway  Redwood City  CA 94065     Ce logiciel ou mat  riel a   t   d  velopp   pour un usage g  n  ral dans le cadre d applications de gestion des informations  Ce logiciel ou mat  riel n   est pas  con  u ni n   est destin        tre utilis   dans des applications    risque  notamment dans des application
13. or the array     TABLE 2 6 Altitude Ranges for the Controller Tray       Environment Specification   Operating 100 ft  30 5 m  below sea level to 9840 ft  3000 m  above sea level  Storage 100 ft  30 5 m  below sea level to 9840 ft  3000 m  above sea level  Transit 100 ft  30 5 m  below sea level to 40 000 ft  12 000 m  above sea level    Airflow and Heat Dissipation    TABLE 2 7 Airflow and Minimum Clearance          Position Clearance  Front 30 in   76 cm   Back 24 in   61 cm     TABLE 2 8 Power and Heat Dissipation for the Controller Tray    Component KVA Watts  AC     Btu Hr       Controller modules with two power fan 0 400 399  modules and 12 drives    1366       Site Preparation Guide   August 2011    Acoustic Noise    TABLE 2 9 Acoustic Noise at 25  C for the Controller Tray          Measurement Level  Sound power  standby operation  6 2 bels maximum  Sound pressure  normal operation  6 2 bels maximum       Shock and Vibration    TABLE 2 10 lists the shock and vibration specifications for the controller tray     TABLE 2 10 Shock and Vibration          Condition Parameter Specification  Vibration Operating 5 500 5 Hz  sinusoidal   Nonoperating  unpacked  5 500 5 Hz  sinusoidal  1 octave per minute  flat profile  50 G  Shock Operating  no damage  10 g peak acceleration  5 ms duration  1 2 sine pulse    Nonoperating  unpacked  20 g peak acceleration  8 ms duration  trapezoidal pulse          Electrical Requirements    This section provides information regarding site power 
14. s Guide    Before you begin to install Sun Storage 2500 M2 Arrays  you must have already read  the regulatory and safety requirements described in this book         Sun Storage 2500 M2 Arrays Regulatory and Safety Compliance Manual       Related Documentation       Task    Title       Review safety information    Review known issues and  workarounds    Prepare the site  Install the array    Install the management  software    Install multipath driver    Manage the array    Troubleshooting and hardware  replacement procedures    Sun Storage 2500 M2 Arrays Safety and Compliance Manual  Important Safety Information for Sun Hardware Systems   Sun Storage 2500 M2 Arrays Hardware Release Notes   Sun Storage Common Array Manager Release Notes   Sun Storage 2500 M2 Arrays Site Preparation Guide   Sun Storage 2500 M2 Arrays Hardware Installation Guide    Sun Storage Common Array Manager Quick Start Guide    Sun Storage Common Array Manager Installation and Setup  Guide    Sun StorageTek MPIO Device Specific Module Installation  Guide  For Microsoft Windows OS   Sun StorageTek RDAC Multipath Failover Driver Installation  Guide  For Linux OS    Sun Storage Common Array Manager Array Administration  Guide and Online Help    Service Advisor  launched from Sun Storage Common  Array Manager          vi    Documentation  Support  and Training    These web sites provide additional resources         Documentation    http    www oracle com technetwork documentation oracle   unified ss 193371 ht
15. s affili  s ne sauraient   tre tenus pour responsables des pertes subies  des co  ts  occasionn  s ou des dommages caus  s par l acc  s    des contenus  produits ou services tiers  ou    leur utilisation     E   Li        Adobe PostScript    Contents    About This Guide v    Planning for the Installation 1  Customer Obligations 1  Safety Information 1   Handling Precautions 2   Secure Installation Requirements 2    Placement of a Product 2    Sun Storage 2500 M2 Arrays Specifications  Dimension and Weight Specifications 6  Environmental Requirements 7   Humidity 7   Altitude 8   Airflow and Heat Dissipation 8   Acoustic Noise 9   Shock and Vibration 9  Electrical Requirements 9   Site Wiring and Power 10   AC Power Input 11    5    DC Power Input 11  Controller Tray Power Factor Correction 11  Power Cords and Receptacles 11   AC Power Cords 11   DC Power Connector Cables 12  Battery Life 12    A  Configuration Worksheets 13    iv Site Preparation Guide   August 2011    About This Guide       The Sun Storage 2500 M2 Arrays Site Preparation Guide describes facilities and system  requirements for installing Sun Storage 2500 M2 Arrays  Follow the guidelines as  outlined in this document when planning your installation     This guide helps you make decisions about ventilation  electrical power  floor  loading  and network configuration  Conduct a power survey to make sure that the  storage array  and input power is free of noise  spikes  and fluctuations        Before You Read Thi
16. s pouvant causer des dommages corporels  Si vous  utilisez ce logiciel ou mat  riel dans le cadre d applications dangereuses  il est de votre responsabilit   de prendre toutes les mesures de secours  de  sauvegarde  de redondance et autres mesures n  cessaires    son utilisation dans des conditions optimales de s  curit    Oracle Corporation et ses affili  s  d  clinent toute responsabilit   quant aux dommages caus  s par l   utilisation de ce logiciel ou mat  riel pour ce type d applications     Oracle et Java sont des marques d  pos  es d Oracle Corporation et ou de ses affili  s  Tout autre nom mentionn   peut correspondre    des marques  appartenant    d   autres propri  taires qu Oracle     AMD  Opteron  le logo AMD et le logo AMD Opteron sont des marques ou des marques d  pos  es d   Advanced Micro Devices  Intel et Intel Xeon sont des  marques ou des marques d  pos  es d Intel Corporation  Toutes les marques SPARC sont utilis  es sous licence et sont des marques ou des marques  d  pos  es de SPARC International  Inc  UNIX est une marque d  pos  e conc  d  e sous licence par X Open Company  Ltd     Ce logiciel ou mat  riel et la documentation qui l accompagne peuvent fournir des informations ou des liens donnant acc  s    des contenus  des produits et  des services   manant de tiers  Oracle Corporation et ses affili  s d  clinent toute responsabilit   ou garantie expresse quant aux contenus  produits ou  services   manant de tiers  En aucun cas  Oracle Corporation et se
17. tion  All SPARC trademarks are used under license and are trademarks or registered trademarks of  SPARC International  Inc  UNIX is a registered trademark licensed through X Open Company  Ltd     This software or hardware and documentation may provide access to or information on content  products  and services from third parties  Oracle  Corporation and its affiliates are not responsible for and expressly disclaim all warranties of any kind with respect to third party content  products  and  services  Oracle Corporation and its affiliates will not be responsible for any loss  costs  or damages incurred due to your access to or use of third party  content  products  or services        Copyright    2011  Oracle et ou ses affili  s  Tous droits r  serv  s     Ce logiciel et la documentation qui sr ng sont ag    par les lois sur la propri  t   intellectuelle  Ils sont conc  d  s sous licence et soumis    des  restrictions d utilisation et de divulgation  Sauf disposition de votre contrat de licence ou de la loi  vous ne pouvez pas copier  reproduire  traduire   diffuser  modifier  breveter  transmettre  distribuer  exposer  ex  cuter  publier ou afficher le noel m  me partiellement  sous quelque forme et par  quelque proc  d   que ce soit  Par ailleurs  il est interdit de proc  der    toute ing  nierie inverse du logiciel  de le d  sassembler ou de le d  compiler  except       des fins d interop  rabilit   avec des logiciels tiers ou tel que prescrit par la loi     Les informatio
18. uter software  or  commercial technical data  pursuant to the applicable Federal Acquisition Regulation and agency specific  supplemental regulations  As such  the use  duplication  disclosure  modification  and adaptation shall be subject to the restrictions and license terms set  forth in the applicable Government contract  and  to the extent applicable by the terms of the Government contract  the additional rights set forth in FAR  52 227 19  Commercial Computer Software License  December 2007   Oracle America  Inc   500 Oracle Parkway  Redwood City  CA 94065     This software or hardware is developed for general use in a variety of information management applications  It is not developed or intended for use in any   inherently dangerous applications  including ln which may create a risk of personal injury  If you use this software or hardware in dangerous   applications  then you shall be responsible to take all appropriate fail safe  backup  redundancy  and other measures to ensure its safe use  Oracle  orporation and its affiliates disclaim any liability for any damages caused by use of this software or hardware in dangerous applications     Oracle and Java are registered trademarks of Oracle and or its affiliates  Other names may be trademarks of their respective owners     AMD  Opteron  the AMD logo  and the AMD Opteron logo are trademarks or registered trademarks of Advanced Micro Devices  Intel and Intel Xeon are  trademarks or registered trademarks of Intel Corpora
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Cooler Master HAF XM  SOLAR BATTERY USER MANUAL  FLENDER couplings - Service, Support  Intel® Rapid Start Technology Driver  Personnel de soutien Syndicats indépendants La présente lettre d  GE 00019577 Telephone User Manual  Article  Bedienungsanleitung SPS24 SENCOM® PC-Software  USBスマートメディアカードリーダ取扱説明書 ADR-SMU  Philips L 1250 - HPM User's Manual    Copyright © All rights reserved. 
   Failed to retrieve file