Home
        TECHNICAL MANUAL & USER HANDBOOK
         Contents
1.   Wall Vent is over 1 metre away from the appliance   Gas pressure is within the specified limits     1mBar    e Room appliance is installed in has a window which can be opened   Failure to comply with the minimum requirements of the specification will  render the appliance dangerous     IMPORTANT NOTE  LPG Propane Users     With Outside Tank  The tank must be fitted with a regulator and  suitable pipe work used to ensure the gas pressure  as stated on the data  plate  is maintained at all times      at the appliance      see commissioning     With Bottles  The minimum requirement is 2 x 47Kg bottles with a  changeover valve  Any other connections using bottles will result in  shutdown problems and damage to the fire  The bottles must be fitted with a  regulator and suitable pipe work used to ensure the gas pressure  as stated  on the data plate    is maintained at all times      at the appliance      see  commissioning     The pressure must be tested    at the appliance    NOT the bottles or tank    see commissioning     Page 32 of 34    WARRANTY INFORMATION    If the appliance develops a fault please refer to the fault diagnosis section  earlier in this booklet for possible causes     This appliance is supplied with a 12 month warranty from the date of  delivery     The Warranty covers defective parts and does not cover typical wear and  tear that occurs with a gas fire appliance     In order to make a warranty claim you will be required to supply the serial  number of the 
2.   the   installer is to advise the user against placing combustible material directly in    front of the appliance  Floor coverings  such as carpets  are considered to be  acceptable     Flueless Fire Line Dimensions      Standard and Wide       i  nn      685             630 2             450    370                Model shown above is the Standard version  The Wide version has a  fascia which is 1080mm x 705mm    Page 21 of 34    Servicing Instructions    It is advised to have this appliance serviced every 12 months by a  registered GAS SAFE engineer     Before commencing and servicing  ensure that the gas is turned off to the  appliance and that the appliance is cool  To gain access to the burner for  servicing undo the screws that locks the fascia to the enclosure   It is  important the appliance is cool  before commencing any work     FASCIA REMOVAL   REFIT    To lock the fascia to the  encloure use the screws  provided  making sure the  screws locate into the enclosure    Location holes to lock  the Fascia           Enclosure  back             Enclosure  Front       Hanging Bracket    Once the two cross headed screws have been removed it will be possible to  lift the fascia up 30mm  and gently pull the facia back from the locating  squares  It is recommended this operation be done with two persons  Take  care to stand the fascia with its back against a level wall  DO NOT LAY THE  FASCIA DOWN     Page 22 of 34       ocation for  hooks    To remove facia lift up and gently
3.   which is  supplied fitted to the appliance  A Gas Inlet Elbow is required to check inlet  pressure  This is supplied with the fire and must be position as close to the  isolation valve as possible     It is recommended that if the gas pipe work is in excess of 1 5m the size of  the pipe work should be increased in diameter after this point to ensure a  stable gas supply     IMPORTANT NOTE  LPG Propane    With Outside Tank  The tank must be fitted with a regulator and  suitable pipe work used to ensure the gas pressure  as stated on the data  plate  is maintained at all times  The pressure must be tested    at the  appliance      see commissioning    With Bottles  The minimum requirement is 2 x 47Kg bottles with a  changeover valve  Any other connections using bottles will result in  shutdown problems and damage to the fire  The bottles must be fitted with a  regulator and suitable pipe work used to ensure the gas pressure  as stated  on the data plate  is maintained at all times  The pressure must be tested     at the appliance      see commissioning     Page 14 of 34    Fitting Instructions       item  A  are the lower box securing points  See instructions     1  Refer to the section    unpacking the appliance    on page 7    2  Positioning Wall Bracket    a  The wall must be flat and level otherwise the burner flame will  be affected    b  The Wall on which the fire is to be installed must be secure and  able to withstand the weight of the Fire and Fascia    c  Decide pre
4.  Depletion Sensor which will sense any  significant oxygen depletion in the room and shut the fire down safely     The Fire Line  Flueless    CE PIN  0063B05341    These instructions are intended for use in GB and IE  Fire is approved for  other European destinations and gas categories  as shown below   Check  Packing box label and Data Plate for appliance gas type and categories  before starting to install this fire  Check the required room ventilation and  minimum room size before installing the fire     This appliance is for use with the following gas categories  gases and supply  pressures     e Natural Gas   o Ian   G20 at 20mbar  o Ia    G25 at 25mbar  o I  G20 at 20mbar  o Ine4   G20 at 20mbar  amp  G25 at 25mbar    e LPG Propane  o Isp  G31 at 37mbar  o Isg p G30 G31 at 30mbar  o I34   G30 G31 at 28 30 37mbar    Important    It is recommended  even if you have fitted these appliances before   that you take the time to read through these instructions and follow  them step by step     Page 4 of 34      Data    Ica    Techn    liance    A    CORRESPOND TO THE DATA ON THE BADGE    See Data Plate for Input    Refer to the appliance data plate  affixed behind the fascia  within the  Rating     burner carriage  ENSURE THAT THE LOCAL CONDITIONS OF USE    UoI daUU04 Ja  ore alse a O  ONELA    TRE E TN anewoarey  aoua  wp Mogg X7    AB  IYO   ONIN     Idd Lay  90 Yd  189  1  Y4 38   8438   130  M130   49 89   YO uoneunsag Jo saujung    aeea a a a equ  aunssaug fuas   dooce  oc 
5.  For use with Natural Gas or LPG       Please quote the appliance serial number when calling our customer  service team regarding warranty issues or to order spare parts     The Warranty is valid for 1 Year from date of delivery  The Warranty card    supplied is to be completed by the installer and returned to the address  below     This manual must be handed to the owner of the property once the  fire is commissioned and retained for future reference     Page 26 of 34    Page 29  Page 30  Page 32  Page 32  Page 32  Page 32  Page 32  Page 33  Page 33  Page 34  Page 36    Contents    General Information   Appliance Start Up   Shut Down Instructions  Oxygen Depletion system   Spark Failure   Decorating   Cleaning Instructions   New Fire Smell  Burn in Period  Noisy Pilot  Fire Shut Down  Important Note LPG Propane Users  Warranty Information   Contact Details    Page 27 of 34    General Information    This fire must be installed by a qualified GAS SAFE Engineer and inline with  current regulations     This fire is intended for decorative purposes  Any purpose provided  ventilation should be checked regularly to ensure that it is free from  obstruction     It is advised to have this appliance serviced every 12 months by a  registered GAS SAFE engineer     Do not throw rubbish on to the surface of the fire  Debris or soot formed   should be removed from time to time  see    Cleaning instructions        Pilot Assembly  The pilots ODS  Oxygen depletion sensor  must not be put  out 
6.  all windows and doors open during this  period     Depending on your use  the burn in period may take a few hours or a few  days  Also if you have a sensitive sense of smell you may notice slight  odours during operating after the burn in period is over  Keep your house  well ventilated during the burn in period  The odour and haze emitted during  the burn in period can be quite noticeable     Page 31 of 34    Noisy Pilot   Fire Shut Down    This appliance is fitted with a safety device  This will operate if the  requirements of the installation are not met  If the fire is run for a period of  time and starts to become noisy or suddenly shuts down this indicates a  possible problem     The most common fault is incorrect ventilation  The ventilation is quoted as     free air        it is not the size of the actual vent  Each vent has a specified     free area     Contact the manufacturer of the vent and ask for this figure and  check it complies with the minimum specified for the appliance     This is a secondary heat source appliance and is supposed to be used for  short periods of time however it can also incorrect installation     If it shuts down or is noisy   Do not use the appliance   Ask your installer to  return and confirm the following conditions are met before using the  appliance    e Minimum Room Size  Is the pilot shield fitted  see page 21      Free Air    Wall Vent of specified size is installed in room      Free Air    Wall Vent is not blocked      Free Air  
7.  g  United Kingdom   In  addition  the installer is to advise the user against placing combustible  material directly in front of the appliance     Clearance to Combustible Materials and Shelves    A non combustible shelf may be fitted to within 1500mm of the top edge of  the outlet of the fire  Note that shelves will get hot and delicate ornaments   e g  wax candles etc  should be kept away from hot surfaces     As with all flueless fires the possibility of convection staining on surfaces in  the vicinity above the fire outlet shall be considered and the user advised     Particular attention should be taken to ensure soft furnishings such as  scatter cushions  rugs and curtains are kept at least 1 5 metres from the  appliance  Material of any description should not be thrown on to the fuel  bed     Preparing the Appliance for Installation    Unpack the unit  Ensure the appliance is correctly marked for the gas it is to  be used with  Take the fascia panel and stand this against a flat surface   Do  not lay the fascia flat     DO NOT ATTEMPT TO USE THE APPLIANCE IF ANY PART OF THE  APPLIANCE IS FOUND TO BE DAMAGED     Decide upon a route for the gas supply and if this is to be a concealed supply  it needs to be located to the bottom right of the fire  Lay in the supply as  required  Where pipes pass through a wall  cavity or un vented void there  should be no joins in this area and the pipes should be fully sleeved  Before  pushing gas pipes through walls seal the pipe ends t
8.  ie  e   me me me   eg aanssangAcdng   Hee  ioc   io   so   oo   woj oo   oc   Oe  Oe    aks   Vth aee   ath  TY 3h  43h a   SCL Kaa Aloiaje  se   9d  ON UOISIa  aueidy    enuey auray   jabuy       Page 5 of 34    Warning  Minimum Requirements    Before installing this appliance the installer must check that the  property in which the fire is to be installed complies with the  requirements of CE approval     e The appliance must not be installed in a room smaller than that  specified    e The room in which the appliance is to be installed must have a    free  air    wall vent of the specified size  This vent must be a minimum of 1  metre away from the appliance    e The room in which the appliance is to be installed must have a window  which can be opened    e The Inlet Gas pressure must be maintained at the specified level and  must be within     1mbar of specification with all gas appliances in  the house switched on and also with just the Fire Line operating  If  outside of this tolerance the fault is most likely to be in the installation  pipe work or service governor at the meter  If the problem is the  meter governor  this is the property of the gas service provider  such  as Transco or Bord Gais  and they should be called to rectify this    e For gas categories 2H  2E and 2E  only  the reduced heat output  version is available at high low input of 2 7 2 0kW at burner pressures  of 12 2 6 9mbar     Noisy Pilot   Fire Shut Down    This appliance is fitted with a safety d
9.  pipe work       Is there another gas appliance in the house which is causing a  pressure drop        Check for strong draughts       Check the pilot gas slot is clear       Pilot lights but  does not light  main burner    Check the pilot flame is heating the thermocouple       Check the thermocouple nut is properly tightened to the valve       Is there another gas appliance in the house which is causing a  drop in gas pressure        Check Room Size and Free Air Vent Comply to CE approval as  shown in Technical Data       Burner lights  but turns off    Check thermocouple nut is properly secured to the valve       Check that drafts are causing the pilot flame to blow off the  thermocouple                   after a few  minutes Is the gas pressure correct  Is there another gas appliance in  the house which is causing the gas pressure to drop   Check    Free Air    Wall Vent is not blocked   Noisy Pilot   Check    Free Air    Wall Vent Size complies with Approval  Appliance Shut  Down Check    Room Size    complies with CE Approval          Check Gas Pressure complies with CE Approval          Page 18 of 34       Anti Draught Shield and pilot     On certain CVO gas fires there is an    Anti   Draught Shield    fitted  These shields are only available from CVO    To fit the shield   make sure your fire is cold then simply slide the  shield over the pilot  making sure you do not interfere with the  pilot sparker too much  as itis essential the sparker is in the nght  place     A
10.  pull facia away  from the inglenook  The opposite applies for  attatching     To refit the fascia is the reversal of removal  NOTE  The fascia must be  locked in place by replacing the locking screws for safety reasons     REFER TO DIAGRAM BELOW TO IDEINTIFY ALL BURNER PARTS    injectors  amp   Aeration Holes       item  A  are the lower box securing points  See instructions     Page 23 of 34    INJECTORS  Remove the injector brackets and clean the injectors  Do  not tamper with the holes as this will change the power of the fire and  possibly make it dangerous  Once cleaned refit the injectors ensuring  they are sealed to the mixer tube    PILOT ASSEMBLY  Clean the pilot assembly ensuring that the pilot  light aeration hole and flame head are clean  Ensure the igniter gap is  set to 4mm  It is recommended to replace the pilot on appliances older  than two years old  Should the pilot assembly need to be replaced  the  original manufacturers parts must be used only  Ensure the pilot draft  shield is fitted    MANUAL VALVE  Check for smooth operation of the gas valve  With  the gas turned off check the tightness of the thermocouple connection    into the valve  The gas control valve is factory set and cannot be  adjusted on site  If the valve needs replacement this must be    done at the factory    AERATION HOLES  These are factory set to ensure the fire remains  safe  If they become clogged with dust the flame quality will  deteriorate  The holes must be clear at all times  T
11. CVOFIRED  Rev 18  PIN NUMBER  0558B05341    TECHNICAL MANUAL  amp  USER HANDBOOK    FIRE LINE FLUELESS    This Manual covers both    Classico     with Polished Interior   amp      Moderno     with Black Interior  Models with either a Standard   970mm  or Wide Screen  1080mm  Fascia  for use with Natural  Gas or LPG        Important   It is recommended  even if you have fitted  these appliances before  that you take the time to read through  these instructions and follow them step by step     Appliance Serial Number        cccsssseesseeesseseeseeeeeeas    Please quote this serial number when calling our customer service team  regarding warranty issues or to order spare parts  The Warranty is valid  for 1 Year from date of delivery  The Warranty card supplied is to be  completed by the installer and returned to the address below     This manual must be handed to the owner of the property once the  fire is commissioned and retained for future reference     Spirit Fires Ltd  4 Beaumont Square  Aycliffe Industrial Park  Newton Aycliffe  County Durham  DL5  6XN  Tel  01325 327221  Fax  01325 327292  Email  info cvo co uk  Web  www cvo co uk    WARNING  This appliance is designed to be    Wall Mounted        The gas fire is approved to be recessed into the  wall ONLY when used with the CVO manufactured  recess system  Under no circumstances should this  appliance be installed recessed into the wall using  another style of recess system  Failure to observe  this warning could render 
12. On no account must inlet or outlet grilles be  obstructed  Working services include the air outlet grille    e NOTE  In some installations  if the fire shuts down  additional  ventilation may be required  This can be due to how air circulates  within the room  If this is the case it is advised to add a second vent  positioned away from the first vent at a higher level     Page 9 of 34       ROOM SIZE REQUIREMENTS    e 3 5Kw Version   The Fire Line must not be fitted in an internal space of  less than 40m3 in volume    e 2 7Kw Version   The Fire Line must not be fitted in an internal space of  less than 27m3 in volume    e Adjoining spaces  not separated by a door may be included    e To convert cubic feet  ft   to cubic metre  m3  divide the room volume  in cubic feet by 35 3     OTHER REQUIREMENTS    The fire must not be fitted in basements which are not open on at least  one side  an open able window   bathrooms or in corridors  stairways   landings or hallways of multi occupancy dwellings  garages or rooms  containing petroleum products     Although the installation of our Flueless fires in bedrooms is permitted   CVO Fire does not recommend it   if in doubt please refer to BS5871 2007  for details or contact CVO Fire for further advice     Soft furnishings  decorations and wall coverings etc  must not be placed  within 1 5 metres of the appliance and its outlets  See Image       1000             D       a        Note   Clearances are in  millimeters and from the fire  ope
13. appliance  as shown on the front of this book  and full details  of the GAS SAFE engineer who installed the appliance   we may request a  copy of the installation receipt     To register your appliance please complete and return the warranty card  supplied with the fire     Failure to supply details of the Registered Engineer who installed the  appliance will invalidate the warranty     To raise a warranty claim call Customer Service on 01325 327221     Page 33 of 34    For further technical information please call our CVO  Technical Department on 01325 327221     Only Use Genuine Replacement Parts     CVOFIRED    Spirit Fires Ltd    4 Beaumont Square   Aycliffe Industrial Park   Newton Aycliffe   County Durham  DL5 6XN   Tel  01325 327221   Fax  01325 327292   Email  info cvo co uk     Web  www cvo co uk       The following information supplied in this manual is  correct at the time of publish  Updated on 17 Nov 2011     There may be changes made in the future as we improve    our products  If there are any queries please write or call  out Technical Department     Page 34 of 34    
14. ating the control knob accordingly   See Image above     Page 29 of 34                                                 To turn OFF the main burner  turn the control to MIN   press the knob in  gently and turn it clockwise to the PILOT position  To turn off the pilot   press knob in and turn to ofr   See image above     To Light     Step 1     Step 2     Step 3   Step 4     Step 5     Step 6     Fire Lighting Sequence Summary    From OFF press the control knob in and turn slowly anti   clockwise    When the ignition click occurs check that the pilot is lit   If  not repeat steps 1 and 2     Hold the knob in for 10  12 seconds  Release knob and check pilot remains alight    Turn knob until the high flame logo is at the top  the fire  should then ignite    Adjust flames to high or low level by turning the knob either  way without pressing in the knob    To extinguish     Step 1     Step 2     Step 3     Turning the Fire Off  Turn control knob clockwise to MIN  position     Press in the knob gently until you are able to continue  turning clockwise to PILOT     To extinguish the pilot press knob in and turn to OFF   although the pilot can be left permanently lit  if required     Page 30 of 34    Oxygen Depletion Pilot System    There is a highly sensitive oxygen depletion sensor designed into the pilot  light  If any part is damaged the entire unit must be replaced  Do not  attempt to bend or alter the flame head  thermocouple or aeration hole  Use  only genuine spare parts as sim
15. ed  around the control knob     If the main burner or pilot lights are extinguished for any reason  do not  attempt to relight the pilot within 3 minutes     The OFF position is self explanatory   preventing any gas from passing  through the control valve to either the pilot burner or to the main  burner     By pressing the control knob in  it is possible to turn it anti clockwise     The first function is to turn on the gas to the pilot   this occurs just before  reaching the PILOT position  If the fire has not been lit for some time it may  be necessary to hold the knob in this position for some seconds to clear the  air from the pipe and allow gas to reach the pilot burner                                         Once gas is available at the pilot  continued rotation  anti clockwise  will  cause the piezo igniter to spark  This is accompanied by a click at the valve  and should result in the pilot burner igniting  This can be verified by looking  at the front central area of the burner unit  Once the pilot is lit  the control  knob should be pressed in and held for 10 12 seconds  In this time the pilot  flame will have heated the flame supervision thermocouple sufficiently to  operate a hold on magnet within the valve  The knob should then be turned  so that the pointer is approximately horizontal  This allows gas at a low rate  to enter the burner and be ignited by the pilot flame  Once ignition has  taken place  the fire may be set to any level between MAX and MIN by  rot
16. evice  This will operate if the  requirements of the installation are not met  If the fire is run for a period of  time and starts to become noisy or suddenly shuts down this indicates a  possible problem  The most common fault is incorrect ventilation  The  ventilation is quoted as    free air        it is not the size of the actual vent  Each  vent has a specified    free area     Contact the manufacturer of the vent and  ask for this figure and check it complies with the minimum specified for the  appliance  This is a secondary heat source appliance and is supposed to be  used for short periods of time however it can also incorrect installation  If it  shuts down or is noisy   Do not use the appliance   Ask your installer to  return and confirm the following conditions are met before using the  appliance    e Minimum Room Size  Is the pilot shield fitted  see page 21      Free Air    Wall Vent of specified size is installed in room      Free Air    Wall Vent is not blocked      Free Air    Wall Vent is over 1 metre away from the appliance   Gas pressure is within the specified limits     1mBar   e Room appliance is installed in has a window which can be opened   Failure to comply with the minimum requirements of the specification will  render the appliance dangerous     Page 6 of 34    Unpacking the Appliance  Read these instructions fully before proceeding  Carefully examine the carton for damage before unpacking  If it is obviously    damaged  consult the supplier over w
17. ferred height of fire   NOTE   There must be at least  300mm clearance between the floor to the fire opening and  1000mm from the top of the gather to the ceiling    d  To get the desired height measure from the floor to the top of  the gather  Place the top of the wall bracket central and 40mm  lower than the gathers height  and mark out the holes    e  Drill and plug holes and attach the fixing bracket to the wall  using 3 screws    3  Place the gas burner unit enclosure onto the wall bracket  Mark out the  position of the lower securing points which are located within the  burner workings  see A above   Remove the burner and drill and plug  holes then refit the burner onto the wall bracket and secure using the  two screws provided  WARNING  This must be done as it ensures the  fire cannot be lifted from the wall and the burner cannot warp while  operating    4  A qualified GAS SAFE registered gas fitter must connect the gas to the  fire using the pressure test point provided   See    Before Connecting  the Fire    Section     Page 14    5  Once the fire is connected to the gas  fit the fascia in place by locating  the lugs on the back of the fascia into the slots on the burner housing   As the fascia is heavy  it is advisable that another person helps    6  Once fitted the fascia must be locked in place  this is done by locating  two cross headed screws through both the fascias hanging bracket and  the enclosure situated on each side of the unit   See Page 28    7  A quali
18. fied GAS SAFE registered gas fitter must commission the fire    See    Commissioning the Fire    Section     Page 16     Page 15 of 34    Commissioning the Fire    PRESSURE TEST POINT       Refer to    Lighting the Fire    Section for information on the start and shutdown  procedure  UNDER NO CIRCUMSTANCES ADJUST THE  FLOW RATES FOR THIS APPLIANCE  The inlet flow rates for the fire are  factory set and are sealed and do not need further adjustment  This ensures  that the appliance complies fully with CE approval     Test the Gas Pressure     Ensure the fire has been installed using the test point provided and  in line with the image on PAGE 11   1  Attach a manometer to an inlet test point next to the isolation valve   2  Light the Fire and set on the    maximum    heat setting   3  Check that the inlet pressure is within the allowed tolerance of    or    1mb   For example in the UK   Natural Gas  20mBar  should be within  the range of 19 to 21  Propane  37mBar  will be 36 to 38   4  Now turn on all the other gas appliances in the house and check that  the pressure still remains within the tolerance of     imb   5  Now turn off all the other gas appliances and turn the fire down to pilot  only and check that the still remains in the tolerance of     1mb     If the appliance fails the above test it must not be used until  either the gas pipe work to the appliance has been improved or the governor  to the house has been adjusted by TRANSCO  BORD GAIS or the propane  supplier  R
19. g devices  The device is not adjustable and must not be  disabled  If evacuation of combustible products is interrupted the device  shuts down both the main burner and pilot light  In the event of a single  shut down  do not attempt to re light the pilot within three minutes  once  three minutes have passed the appliance can be re started in accordance  with    Appliance Start Up   Shut Down Instructions     In the event of repeated  shut downs  do not use the appliance and have the flue and appliance  checked by a CORGI Engineer  If any part of the pilot assembly needs to be  replaced  including the pilot burner  thermocouple  electrode and injector the  complete assembly must be replaced with an original manufacturer s pilot  assembly by a CORGI Engineer     Warning      Do not adjust the system   Warning   Do not disable the flame sensing device   Warning      Use only OEM parts     The installation should only be carried out by a GAS SAFE Engineer and in  accordance with national and local regulations for gas  The installation must  also be in accordance with relevant parts of local and national building  regulations  For the Republic of Ireland  reference should be made to IS813  and ICP3 and any guidance notes from Bord Gais     Read the instructions carefully before proceeding  Failure to do so could  result in an unsafe installation and may invalidate the warranty     Failure to have the fire fitted by a qualified person will invalidate the    Warranty  and CVO Fire w
20. hether to proceed     Facia    Hanging  Bracket        Burner unit    Check Contents before proceeding   e Gas Fire  Box  1   o Gas Fire   o Wall Bracket   o Install Booklet   e Gas Fire Surround  Box  2   o Fire Fascia    Make sure the carton is stood upright and open the top  Remove the  cardboard  and place to one side  this can be used as a floor protector when  installing the fire  Remove the fire and examine its general condition  paying  particular attention to the fascia  and the stainless steel inglenook  If  satisfied by the general condition  place the decorative components to one  side and proceed with the installation  If in any doubt  seek advice from the  supplier  Read the instructions fully before proceeding     Page 7 of 34    General Installation Requirements    The installation should only be carried out by a GAS SAFE  Registered fitter and in accordance with national and local  regulations for both gas  amp  electricity     The appliance is intended for decorative purposes only     Foreign objects should not be placed on to the appliance or otherwise disturb  the fuel bed  Debris from any source  or soot formed  should be removed  from the appliance  see    Appliance Cleaning Instructions        The appliance may emit a slight smell for a period of time after  commissioning  This is quite normal and any odours will disperse within a  few hours of operation     The pilot light and flame sensing device installed to the appliance are also  atmospheric sensin
21. ilar looking parts from other appliances may  well give different or inferior performance and could lead to a hazard     Spark Failure    The gap between the pilot electrode and the pilot should be 3 5   4 5mm  and normally adjustment is not necessary  the electrode is very brittle   The  spark should jump across the gap between the electrode and the gas outlet  on the pilot head  If the ignitor fails  a lighted taper can be inserted into the  pilot area to check that gas is reaching the pilot     Decorating     Never use this appliance when decorating  Allow a number of days after  decorating for the fumes to disperse before using this appliance  Using this  appliance during or after decorating can cause fumes to enter the room     Cleaning instructions     The fascia should be cleaned with warm soapy water  a suitable metal polish  should only be used for the stainless steel parts  Care should be taken  when polishing the vanity cover  It is very important that no polish should  be used on the surface of the burner  No residue of polish should be left as  this may cause unpleasant odours and could lead to staining within the  burner opening when the appliance is used     New Fire Smell   Burn in Period    On initial light up of a new appliance  the    newness    will burn off within the  first few hours of operation  During this period some smoke may be emitted  from the outlet grill  this should be no cause for concern  Accordingly  the  room should be well ventilated with
22. ill not accept any claims for incorrect  installation     Page 8 of 34             Input Rating Minimum Room Minimum    Free  Power Version     Size Requirements Air    Wall Vent   m3  Requirements   cm2   2 7kKW Input Rating 27m3 100 cm2  3 5Kw Input Rating 40m3 125 cm2                  See Data Plate within fire for Input Rating        VENTILATION REQUIREMENTS    e NOTE  The    FREE AIR    quoted above is the area of air which can pass  through the air vent  It is not the size of the grille on the wall  If in  doubt please contact the vent manufacturer and get the specification  for the vent    e 3 5Kw Version   The area the fire is to be installed in must have a wall  vent of at least 125cm  of ventilation  FREE AIR  and an open able  window    e 2 7Kw Version   The area the fire is to be installed in must have a wall  vent of at least 100cm  of ventilation  FREE AIR  and an open able  window    e The wall vent must be positioned at least 1 metre away from the  appliance    e Republic of Ireland   Two free air wall vents of not less that 60 cm2  each  one not less that 1 6m above the other  must be installed in the  room    e When providing ventilation openings consideration must be given to  the avoidance of locations where discomfort from draughts may cause  the user to block the openings  Similarly the possibility of curtains or  furniture blocking ventilation openings must be considered    e Floor vents  window vents or chimneys are not suitable means  of ventilation  
23. ning     Be aware of curtains etc  that could be blown towards the appliance     Page 10 of 34       SECONDARY HEATING  The fire is intended as a secondary heat source and should  not be used as a primary heat source  Check that a primary heat source  such as  radiators  is present in the room before installing the appliance  The fire should not be  operated if the room temperature is below 15 deg C  If the fire is used in a room without  the primary heat source operating to raise the initial room temperature above 15 deg C  there may be a build up of condensation and it is likely the stone fascia will crack due to  heat shock  When the appliance is used properly there is no risk of the fascia stone cracking  and this damage is not covered by the warranty  Houses with warm air heating systems   solid walls  or no damp proof course may be unsuitable for flueless appliances  This  appliance does not contain Asbestos     ROOM AIR QUALITY  The fire must not be used in rooms where the atmosphere is likely  to contain water or chemical vapours that may adversely affect the appliance or its finish  e g  a kitchen    DECORATING  Do not use the fire while painting or decorating even if it is in an adjoining  room  When decorating the residue can linger for some time and this will lead to unpleasant  smells from the appliance  It may be some weeks before this odour clears and it is advised  not to use the appliance during this period  Always completely cover the appliance while  decora
24. nti   Draught  Sparker Shi eld       as slot     lt is essential that you have a good  spark across the sparker to the  pilot gas slot for a good pilot light   so that the thermocouple has time  to heat up  which then lights the  burner     Page 19 of 34    Fitting Replacement Components  Spare Parts     There are no user serviceable parts on this appliance  The installation of gas  parts should only be carried out by a qualified Gas Safe Registered fitter and  in accordance with National and local Regulations  Failure to do so will    invalidate the Warranty and CVO Fire will not accept any claims for incorrect  installation        Manual Valve  V4 28  AC027  This part can only be changed at the factory   Call Customer Service on 01325 327221             Natural Gas   0 4 x 7   ACO76  LPG   0 6 x 1   ACO89                   Pilot Natural Gas   P4 37D AC043  Pilot LPG Propane   P4 45 AC044                      Page 20 of 34    WARNING  FIRE GUARDS    A fireguard is not supplied with this appliance and it is recommended that a  fireguard conforming to the requirements of BS6539 or BS6778 be fitted if   the fire is used in the presence of young children  the elderly or the infirm    Fireguards are readily available online or from most large DIY Stores     The installer is to advise the user not to stand too close to the appliance for  prolonged periods of time and warn that loose clothing is particularly at risk  of burning due to the presence of an unguarded flame  In addition
25. nufacturer for guidance     Page 24 of 34    Replacement Components List    Item Description Code  Isolation Tap AC026  Pilot Natural Gas  Manual  P4 37D AC043  Pilot LPG  Manual  P4 45 AC044  Injector Natural Gas 0 30mm AC076  Injector LPG 0 60mm AC089  Anti Draft Shield Cc041    Note  As this is a Flueless appliance in order to ensure that it is  calibrated correctly and operates safely it is Spirit Fires Policy not to sell  any other parts for this fire other than those listed above    All other repairs must be done at the factory     When ordering replacement components or requesting technical  assistance  you should at all times quote the following     e Type of fire   shown on front of booklet     e Gas supply  LPG or Natural Gas    when using LPG please supply  details of supply type   bottles or tank     e Control System   Manual Control Version  e Unit serial number as shown on Data Sheet    e Component part number or description of fault    WARNING      Never adjust the flow rates or valve settings on this appliance   Failure to comply with this will render the appliance dangerous  If  you suspect the appliance has been tampered with   DO NOT USE   Consult a GAS SAFE Registered Engineer before using the appliance     Page 25 of 34    USER HANDBOOK    FIRE LINE FLUELESS     Manual Ignition Version     This Manual covers     Fire Line    Classico     Polished Interior   Fire Line    Moderno     Black Interior     Both Standard  970mm  and Wide Screen  1080mm  Width   
26. o clean use a  vacuum cleaner as this will ensure that debris does not fall into the  mixer tube and block the injector  Do not Adjust the Aeration   BURNER  Clean the burner bar to remove any deposits    OTHER  Use a vacuum cleaner to remove any dust and debris that  may have built up within the fire box chamber    GAS CIRCUIT  Test all joints for leaks if the burner has been  dismantled    RE LIGHT  Light the fire using the method in the instructions and  ensure that the pilot lights constantly and the pilot flame envelopes  the thermocouple  The pilot should hold in for 20 seconds before  lighting the main burner    COMMISSION  Now follow the instructions on Page 17     Commissioning the Fire    to ensure the fire still complies with the  installation instructions    COMBUSTION CHECK  Typical levels for this appliance are 69pm and  0 6   Run appliance for 30 minutes  ensuring burner flames settle  evenly  A combustion analysis check to establish the correct operation  of the appliance should then be carried out using an analyser to  BS7927    a  Zero the equipment and sample the entire width of the  combustion product outlet grille at the top of the  appliance    b  Take a reading for CO ppm  and CO2       c  Using the formula  CO CO2    10000  The result should  be less than 0 0015    d  Example 6ppm 0 6    10  10000   0 001   pass   Readings can vary depending on the analyser being used therefore if  the combustion is suspect  disconnect the appliance and contact the  ma
27. o prevent debris  entering the pipes     The instructions for installation and maintenance and the user instructions  shall be handed to the user  The installer shall instruct the user in the safe  use and regular maintenance of the appliance and advise that the ventilation  opening shall not be blocked or restricted in any way     Page 13 of 34    Before Connecting the Fire    Check ROOM SIZE REQUIREMENTS   Check VENTILATION REQUIREMENTS   Check GAS PRESSURE REQUIREMENTS     Fully purge pipes of air and any debris and connect the gas supply to the  8mm supply on the fire  Leak test the supply using an approved method   Note  An isolating valve must be situated near the appliance for servicing   In the even of gas leakage from the appliance the gas supply must be  turned off at the nearest isolating valve     Before lighting  if the pipes have not been purged of debris do so  now before lighting the fire  Failure to do so will result in blockages  within the pilot     All CVO gas fires are bench run and thoroughly tested  CVO is in the unique  position of knowing that every fire that leaves the factory in perfect working  order with accurate test records kept for every fire  This ensures every fire  complies with the CE approval     Connect the 8mm gas inlet to a gas inlet test elbow  This should be  positioned as shown in the images  The elbow should be connected to the  isolation valve as shown in the images     Gas Inlet Supply   This is via an 8mm gas tap  isolation valve
28. of operation  The user must not adjust the pilot     If any of its parts are damaged and need to be exchanged the original  manufacturers parts must be used  There are no user replacement parts     The pilot light and flame sensing device fitted to this fire is also an  atmosphere sensing device  which shuts off both the main burner and pilot if  evacuation of the combustion products is interrupted  If the fire shuts itself  off  restart the fire following the procedure in section    Lighting the fire     If  the fire continues to shut itself off do not use the fire and have the fire  checked by a suitably qualified person     Once the fire has been checked and remedial action taken  the fire is ignited  in the manner depicted in section    Lighting the fire        Due to the newness of materials  the fire may give off a slight smell for a  period of time after commissioning  This is quite normal and any odours  should disperse within a few hours of operation     Fire Guards  A fireguard is not supplied with this appliance and it is  recommended that a fireguard conforming to the requirements of BS6539 or  BS6778 be fitted if the fire is used in the presence of young children  the  elderly or the infirm  Fireguards are readily available online or from most  large DIY Stores     Page 28 of 34    Appliance Start U Shut Down Instructions    The manual switch is located on the right side behind the fascia  The  positions of the control valve are depicted on the control panel fitt
29. the appliance highly  dangerous  it will no longer comply with the CE  approval or the Manufacturers Warranty  If in  doubt call 01325 327221 before starting to install  the appliance     Contents  Page 3 Parts List   Construction Drawing  Page 4 Introduction  Page 5 Appliance Technical Data  Page 7 Unpacking the Appliance  Page 8 General Installation Requirements  Page 12 Side View of Fire  Page 13 Warning For Fire Guards and Hearths  Page 13 Clearance to Combustible Materials  Page 13 Preparing the Appliance  Page 14 Before Connecting the Fire to Gas Line  Page 15 Fitting Instructions  Page 15 Commissioning the Fire  Page 17 Installation Completion  Page 18 Fault Diagnosis  Page 20 Fitting Replacement Components  Page 21 Warning For Fire Guards and Hearths  Page 21 Flueless Fireline Dimensions  Standard and Wide  Page 22 Servicing Instructions  Page 25 Replacement Components List  Page 27 User Handbook    Page 2 of 34    Construction Drawin    Parts List    6r zo    creID  Buisnoy 10palu           Jur  yoous 6u   al reoo  Jauing    gA ZEZQO SISSEYD    j  f  j   ZSZ99 do  sewing  ero    gel    LE    BEZIO   s aeg EM  LSZ90  13409   apeg   Bui Bue      AY 9E7939 ASYIED    Note that the    Moderno     Black Interior  Version of this fire does not include Liner CC249     Page 3 of 34    Introduction    This appliance is 100  efficient  90  SAP Rating   The burner system is  very clean burning and does not require glass or catalytic converters  The  fire is fitted with an Oxygen
30. ting     WALL MOUNTED  The appliance has been designed to be installed onto a wall  It must be   placed on a non combustible surface of minimum of 12mm thickness  The surface on which   the appliance is to be mounted must be flat  level and square to the back panel  Care should  be taken with all wall coverings as it may discolour them in time     GAS SUPPLY    Before working on any pipe work  plug the ends to prevent the entry of  debris  Decide upon the route for the gas and lay pipe work as required   Where pipes pass through the walls they must be sleeved  Before  connecting any pipes to the appliance  fully purge pipes of debris or grease  etc  Inlet is via an 8mm gas tap  isolation valve  which is supplied fitted to  the appliance  Connect gas supply to the supplied pressure test point and  then to the 8mm isolation valve as shown below  The pressure test point  MUST BE as close to the isolation valve as possible to ensure  accurate inlet pressure testing when the fire is commissioned              Page 11 of 34    SIDE VIEW of the Flueless Fire Line  below       On no account must inlet or outlet grilles be obstructed           Heat outlet    Y ascia  y   lt    Wall Inglenook  Burner  and  Air inlet to Remote  remote Housing          Only the fascia supplied with the appliance must be used  Any other type  could affect combustion or overheat the gas controls  Any other types of  Fascia must be passed by CVO        If fitting over an existing fireplace  the flue and cavi
31. ty must be blocked off  completely to prevent suction on the back of the appliance  The top of the  flue should also be capped off to prevent the entry of moisture etc  Consult  building control if in any doubt     Any under grate draught devices must be sealed off  A hearth will be  required in accordance with both CORGI and local regulations on a non   combustible surface if the fire is to be mounted on the wall less than 300mm  from the base of the burner to the floor     The client installer can construct supply their own hearth or CVO can supply  it as an extra item     Unless a dress guard is fitted  this appliance shall be installed with a hearth  that projects at least 300mm in front of the naked flame incandescent fuel   bed  and extends at least 150mm at either side  and around its periphery is  a height of at least 50mm above finished floor level     Page 12 of 34    Warning for Fire Guards and Hearths    The appliance is not installed with an integral guard  In normal use  consideration may be given to the use of a fireguard conforming to BS6539  or BS6778  so that the approach to the appliance is limited such that access  to the flame is minimised  It is recommended that a fireguard conforming to  the requirements of BS6539 or BS6778 be installed if the appliance is used  in the presence of young children  the elderly or the infirm  For some  countries a non combustible hearth must be installed in front of the  appliance in accordance with national regulations  e
32. unning this type of appliance with incorrect gas pressure can  result in harmful emissions being released into the room and will render the  appliance dangerous    Disconnect the pressure gauge then replace the pressure test  point sealing screw and test for gas soundness  Replace the cover and the  control knob  if removed      Page 16 of 34                         Installation Completion  amp  Final Check List       Brief the customer on the operation of the appliance and give them the  instruction booklet  The customer must be told of the need for regular  servicing of the appliance  every 12 months   this will be at least once a  year  and they must be made aware that no rubbish is to be thrown onto the  fire bed  The customer must also be aware that purpose provided  wall vent    free air    ventilation should be checked regularly and must     never    be intentionally blocked  The Fire is supplied with a  Warranty Card this should be completed by the installing Engineer  and handed to the customer for return to the factory     e Is the Gas Pressure Correct   within 1mb of rating    e Is the Air Vent fitted and providing the specified amount of      free air        if in doubt contact the vent manufacturer for vent      free area    sizing    Does the room comply to the minimum size or greater    Does the Room have a window that can be opened    Has the customer being shown how to operate the appliance    Has the customer been told of the reason for the air vent and   wh
33. y it must never be blocked    e Has the warranty card been completed and given to the  customer     If you have any questions  or the fire is not operating correctly   please use the fault diagnosis section or call the CVO Technical team  on 01325 327221 BEFORE you leave the installation  As part of our  Customer Service procedure you will be asked for the Fire Serial  number  on the front cover of the booklet  and Gas Safe  Registration     If the appliance is not fitted in strict accordance with these  instructions  CVO cannot be held responsible for any damage caused  and reserve the right to charge for any corrective work    Page 17 of 34    All CVO Fires are given a full function test at the factory including    Fault Diagnosis    being run for a number of minutes to ensure there are no faults  It is  highly unlikely that if the unit has been installed correctly as set out  in the manual that the fire will not function  The cause is normally   due to an installation fault        Symptom    Check List    Tick       Unit sparks but  does not light  pilot    Check for a good spark       Check the spark is in the right area       Check the ventilation is not too strong       Check there is gas running through       There is no gas    Check isolation tap shut off valves are free from grease       Check isolation tap shut off valves are on       Check for blockages       There is gas  but pilot does  not light    Check inlet gas pressure is correct       Check for blockages in
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Télécharger - association Mode d`emploi  Bedienungsanleitung Guide d'utilisation  User manual - CONRAD Produktinfo.  WT1000-LCD - Primax Balanças  User Manual - Comkit Online  Manuel d`installation  Big Bass Wheel Pro Service Manual  Philips Meat mincer coupling HR3955  Road Models in Adams/Tire  ASLP3507 - Autec-VLT Automotive Equipment    Copyright © All rights reserved. 
   Failed to retrieve file