1.   1    HELP  customercare asco com  800 800 ASCO    Printed in U S A     INDEX    inspection  3 1  installation  1 1    isolating the ATS  3 2    lights  1 3  1 4    lubrication  2 1    M    maintenance  preventive  2 1    maintenance handle  2   2  warning  2 2    manual load transfer  2 2  warning  2 2    N    nameplate  cover    Normal Source Accepted light  1 3    O    operation  electrical  1   4  manual  2   2  warning  2 2    P    parts  2 1  phase rotation check  1 3  preventive maintenance  2 1    problem  2 2    R    rating label  cover   removal of shipping angles  1 1  removal of shipping skid  1 1  replacement parts  2 1    return to service  3 3    S    service  ASCO Services  Inc   ASI   2 1    settings  see Controller User   s Guide    shipping angles  1 1  warning  1 1    shipping skid  1 1    T    test  functional  1 3  14  testing power cables  1 2    time delays  2 1  see Controller User   s Guide    TS Locked Out light  2 2    Transfer Control selector switch  Retransfer Delay Bypass  1   4  Transfer Test  14    Transfer Switch Connected To  Emergency light  1 4    Transfer Switch Connected To  Normal light  1 4    transfer test  1 4  2 1  transfer to emergency  1   4  2 1  transfer to normal  1   4  2 1    troubleshooting  2 2    V    voltage checks  1 3    voltage  pickup and dropout settings  see Controller User   s Guide    Copyright ASCO Power Technologies  L P  2007    
2.   CLOCKWISE         unfold  crank    N  counterclockwise     draws out  transfer switching device    Figure 3 6  Isolation Handle     NOTE  In the TEST position the transfer  switching device solenoid operator circuit is  energized through secondary disconnects     A DANGER    Hazardous voltage capable of causing  electrical shock  burns  or death   do not touch any control circuit terminals              Automatic Transfer Switch    Figure 3 4  CONNECTED to TEST position     3  Continue turning Isolation Handle counterclockwise   approx  7 turns  until the window shows ISOLATE     Bypass Switch    Turn crank  counter   clockwise  until  window   o  shows  ISOLATE        Automatic  Transfer Switch    Figure 3 5  TEST to  SOLATE position     4  Open the lower enclosure door  Pull out the side rail  carriage then roll out the transfer switch  It can be  safely inspected in this position  The transfer switch  can also be removed for easier maintenance opera   tions        Figure 3 7  Transfer switching device isolated  and pulled out for inspection     See page 2 2 for maintenance handle use  A lifting yoke  kit 607064 is available to facilitate lifting by using an  overhead crane or similar equipment        Transfer Switch weighs 350 450 Ibs   Use lifting device 607064 or other device  capable of lifting this weight to avoid  personal injury or equipment damage        BYPASSING  amp  ISOLATING     continued    RETURN TO SERVICE    This procedure explains how to return the automa
3.  2  The two harness plugs and sockets are keyed  Care     fully align the plugs with the sockets and press  straight in until the latches click     3  Close the enclosure doors     Follow Return to Service instructions on page 3 3     TESTING  amp  SERVICE  continued     TROUBLE SHOOTING    Note any optional accessories that may be furnished on  the ACTB and review their operation  Refer to any sepa   rate drawings and or instructions that may be packed    with the ACTB     Table 2 1  Trouble Shooting Checks     A    DANGER       Hazardous voltage capable of causing shock   burns  or death is used in this switch   Do not touch the power or load terminals  of the bypass switch or transfer switch           PROBLEM    CHECK IN NUMERICAL SEQUENCE       1 OPERATION    2 GEN SET    3 VOLTAGE       Engine generator set does  not start when the Transfer  Control switch is turned and  held in Transfer Test position  or when normal source fails     Hold Transfer Test switch 15  seconds or the outage must  be long enough to allow for  Feature 1C time delay plus  engine cranking and starting     Starting control must be in the  automatic position  Batteries  must be charged and  connected  Check wiring to  engine starting contacts        Transfer switch does not  transfer the load to the  emergency source after the  engine   generator set starts     Wait for Feature 2B time delay  to time out     Generator output circuit  breaker must be closed   Generator frequency must be  at least 95 
4.  Isolation Switch  ACTB  consists of  an upper bypass isolation switch  a transfer switch  a  monitoring and transfer controller  and door   mounted  controls  The ACTB is factory wired and tested   Installation requires removal of the shipping skid then  securing the enclosure to the supporting foundation     Remove the Shipping Skid    Open the front lower door and remove the two front lag  screws securing the enclosure to the wood skid  Next  remove the rear lower panel and remove the two rear lag  screws securing the enclosure to the wood skid     Supporting foundation and mounting    The supporting foundation for the enclosure must be  level and straight  Allow at least 35 inches in front of the  enclosure for draw out of the Transfer Switch  Refer to  the enclosure outline drawing included with the 7000  Series ACTB for all mounting details including door  opening space    If bottom cable entry is used  the foundation must be  prepared so that the conduit stubs are located correctly   Refer to the appropriate enclosure outline drawing for  specified cable entrance area and location  Provide cable  bending space and clearance to live metal parts  Whena  concrete floor is poured  use interlocking conduit spacer  caps or a wood or metal template to maintain proper  conduit alignment     Mounting    Refer to the enclosure outline drawing furnished with  this switch and mount the 7000 Series ACTB according to  the details and instructions shown on the drawing     Remove thre
5.  To  Normal Emergency    To  E    Normal    Bypass    Emergency  Source Source  Accepted Accepted    iii    Figure 1 3  Standard controls and indicators     observe  these lights    Functional Test    Read all instructions on the Wiring Diagrams and labels  affixed to the ACTB  Note the control features that are  provided and review their operation before proceeding     After installing the ACTB check the following       Bypass Handle should be in the OPEN position       Isolation Handle should be in the CLOSED position       CN transfer switch should be CLOSED       CE transfer switch should be OPEN     If handles are not in correct positions  follow instructions  for Bypassing and Isolating the automatic transfer switch  in Section 3  Do not force the handles  Electrical  interlocks prevent a wrong sequence of operation     1   Voltage Checks    First check nameplate on transfer switch  rated voltage  must be the same as normal and emergency line voltages     DANGER    Use extreme caution when using a meter  to measure voltages  Do not touch power  terminals  shock  burns  or death could result      A          Perform steps 1   6 at the right  Observe the status lights   See Figure 1 3     E Black square means light is on   O White square means light is off       Tf necessary  adjust voltage regulator on generator per the  manufacturer   s recommendations  The ACTB will respond only  to rated voltage specified on the nameplate     Now continue to 2     Electrical Operation 
6.  of nominal  57 Hz  for a 60 Hz system        Voltmeter should read at least  90  of nominal phase to  phase voltage between  terminals EA and EC  or EL1  and EL2 for 2 pole switches         Transfer switch does not  transfer the load to normal  source when normal returns  or when the Transfer Control  switch is released     Wait for Feature 3A time delay  to time out     Voltmeter should read at least  90  of nominal phase to  phase voltage between  terminals NB and NC  NC and  NA  and NA and NB  or NL1  and NL2 for 2 pole switches         Gen  does not stop after load  retransfer to normal source     Wait for Feature 2E time delay  to time out        Starting control must be in the  automatic position           Failure to Synchronize  light comes on     Conditions of Normal or Emergency Sources not suitable for closed transition transfer   Recheck voltage and frequency of both sources  Press Alarm Reset pushbutton        Extended Parallel Time  light comes on     CN and CE contacts are closed longer than setting in the Control Panel  Open the discon   nected source circuit breaker  then call your nearest ASCO Service Center for assistance        TS Locked Out  light comes on           Transfer lockout operation has occured  transfer switch is disabled from automatic operation   Open the disconnected source circuit breaker  then call your nearest ASI for assistance             These are factory settings  Refer to Controller User   s Guide     If the problem is isolated to ci
7.  reliability of the connection depends  on how clean and how tight the joint is        Table 2 1  Tightening torque values for bolted joints                       Bolt Diameter Recommended   Grade 5 hardware  Tightening Torque  in inches in foot pounds  5 16 12  3 8 20  1 2 50  5 8 95             Harnesses    All internal connections are made at the factory  The  bypass switch  transfer switch  and control panel are  joined together by an interconnecting wire harness  The  disconnect plugs are already engaged on enclosed  switches  For open   type switches  the plugs must be  engaged after installation is completed  Align harness  plugs with sockets in the control and push them together  until they are secure     Controller Ground    A grounding wire must be connected to the controller   s  lower left mounting stud  Because the controller is  mounted on the enclosure door  a conductive strap must  be used between the enclosure and the door  This  connection provides proper grounding which does not  rely upon the door hinges     Engine Starting Contacts  and Auxiliary Circuits    The engine control contact signal connections and  auxiliary circuits are located on terminal block TB as  shown on the Wiring Diagram provided with the ACTB   Connect the signal wires to the appropriate terminals     INSTALLATION  continued     ASCO 7000 SERIES    EMERSON     Network Power    Power Transfer  amp  Bypass Switch          Transfer    Transfer Switch Transfer Switch  Connected Connected 
8. ASCO 7000 Series 7ACTB    Operator   s  Manual    Automatic Closed Transition Transfer   amp  Bypass lsolation Switches    G design 1000 through 3000 amp  sizes    A DANGER    DANGER is used in this manual to warn of high  voltages capable of causing shock  burns  or death        WARNING is used in this manual to warn  of possible personal injury              CAUTION is used in this manual to warn  of possible equipment damage           TABLE OF CONTENTS  section page                Refer to the outline and wiring drawings provided  with your 7000 Series ACTB for all installation and  connection details and accessories           Refer to Group 5 Controller User   s Guide 381333 126  for ATS status display messages  time delays  pickup   amp  dropout settings  and adjustments              An experienced licensed electrician must install the  7ACTB     Rating Label    Each 7000 Series 7ACTB contains a rating label to  define the load and fault circuit withstand closing  ratings  Refer to the label on the Transfer Switch for  specific values                                            ASCO Fes                               50 Hanover Road  Flornam Park  New Jersey 07932 1591 USA    Technologies  For sales or service call 1 800 800 2726  ASCO  www ascopower com    ASCO POWER TECHNOLOGIES CANADA PO Box 1238  17 Airport Road  Brantford  Ontario  Canada N3T 5T3    telephone 519 758 8450  fax 519 758 0876  for service call 1 888 234 2726  ASCO  www asco ca    INSTALLATION  MOUNTING sr
9. Emergency  on the door  This is the  position of the Transfer Switch  If itis not in the same  position as the Bypass Handle change the position of  the Transfer Switch as follows     To change the position of transfer switch    Operate to NORMAL   OperatetoOEMERGENCY  Turn Transfer Control   Turn Transfer Control  switch to Retransfer switch to Transfer Test  Delay Bypass   hold 15 seconds     Connected To Normal   Connected To Emergency  light should come on  light should comes on                            If Feature 2B time delay is used  there will be a delay  before transfer to Emergency   NOTE  With Normal available  the automatic  transfer switch will not stay in the emergency  position unless Feature 3A time delay is used   at least 30 seconds         Do not close the isolation contacts unless  the Transfer Switch  ATS  and Bypass  Switch are in the same position        5  When the transfer switch is in the same position as  the Bypass Switch handle  continue turning the  Isolation Handle clockwise  about 16 turns  until the  window shows CONN  connected      Bypass Switch    Turn crank  clockwise  until window  shows  CONN   connected         Figure 3 10  TEST to CONNECTED position     Now continue to the next page for instructions on how to  return the Bypass Handle to the OPEN postition     BYPASSING  amp  ISOLATING     continued    RETURN TO SERVICE continued     This procedure explains how to return the Bypass Switch  Handle to the OPEN position  The Bypass Hand
10. Handle    amp   turn it  counter   clockwise        Figure 3 12  Un   Bypass Normal     To Un Bypass Emergency Source      Load connected to Emergency Source   The Transfer Switch Connected To Emergency light is on  and Transfer Switch Connected To Normal light is off     Pull out  the Bypass Handle then turn it counterclock   wise until Bypass Switch Position shows OPEN  green  indicator   The Unit Not in Automatic light should be off     Bypass Switch    Pull out  Bypass  Handle    amp   turn it  counter   clockwise        Figure 3 13  Un    Bypass Emergency     The Automatic Closed Transition Transfer  amp  Bypass   Isolation Switch should be left in this position       NOTE  When Accessory 66A  reversed Normal  amp  Emergency connections  is specified   the handle push pull operation is reversed  Follow instructions on the door     3 4    A    Alarm Reset pushbutton  1 4  2 2    auxiliary circuits  1 2    B    bus connections  1 2  bypassing the ATS  3 1    C    catalog number  cover  cleaning  2 1  closed transition transfer  1   4    connections  line  1 1    controller  disconnecting  2 1  see Controller User   s Guide    E    electrical operation  1   4    Emergency Source Accepted light   1 3    Engine Control selector switch  Auto position  2 1    engine starting contacts  1 2  Extended Parallel Time light  2 2    F    Failure to Synchronize light  2 2  foundation  1 1  frequency  generator  2 2    functional test  1 3  1 4    H    harness  1 2  disconnect plugs  2 
11. an cloth     Check the transfer switch contacts  Remove  transfer switch barriers and check the condition of  the contacts  Replace contacts when pitted or worn  excessively  Reinstall the barriers carefully     Maintain transfer switch lubrication  If switch is  subjected to severe dust or abnormal operating con   ditions  renew factory lubrication on all movements  and linkages  Relubricate solenoid operator if TS  coil is replaced  Don   t use oil  order lubrication kit  75 100     Check all cable connections  amp  retighten them        REPLACEMENT PARTS    Replacement parts are available in kit form  When or   dering parts provide the Serial No   Bill of Material No    BOM   and Catalog No  from the transfer switch name   plate  For service call ASCO Services at 1 800 800 2726   you will be put in contact with your local ASI office     DISCONNECTING THE CONTROLLER    The harness disconnect plugs are furnished for repair  purposes only and should not have to be unplugged  If  the control panel must be isolated  follow these steps     A       DANGER    Bypass lIsolation Switch is energized   Do not touch isolation contact fingers   shock  burns  or death could result        Disconnecting the Plugs  1  Bypass and Isolate the Automatic Transfer Switch     2   3     Open the upper enclosure door   Separate the two quick disconnect plugs by squeez   ing the latches  Do not pull on the harness wires     Reconnecting the Plugs  1  The ATS should be still bypassed and isolated    
12. e      Load connected to Emergency Source   The Transfer Switch Connected To Emergency light is on  and Transfer Switch Connected To Normal light is off     Pull out  the Bypass Handle all the way  then turn it  clockwise until Bypass Switch Position shows CLOSED on  EMERGENCY  yellow indicator   The red light Unit  Not In Automatic will flash     Bypass Switch    Pull out  Bypass  Handle    amp   turn it  clockwise        Figure 3 3  Bypass to Emergency     The automatic transfer switch can now be put in the TEST or OPEN position  See ISOLATING on page 3 2       NOTE  When Accessory 66A  reversed Normal  amp  Emergency connections  is specified   the handle push pull operation is reversed  Follow instructions on the door     3 1    BYPASSING  amp  ISOLATING     continued   ISOLATING THE ATS    Isolating is required before any service work can be  performed on the automatic transfer switch  ATS   Refer  to Figures 3 4  3 5  3 6  and 3 7     1  Bypass the closed automatic transfer switch contacts   See BYPASSING on page 3 1        Align position indicator  Do not leave   the handle in an intermediate position   2  Turn the Isolation Handle counterclockwise  approx   16 turns  until window shows TEST  The ATS can be  tested now without load interruption  see page 2 1         Bypass Switch    Turn crank  counter   clockwise  until  window  shows  TEST     position  window    ISOLATION HANDLE        CONN  TEST  ISOLATE        TO CONNECT TO ISOLATE   TRANSFER TRANSFER   WITCH TURN
13. e Shipping Angles  from the Transfer Switch    Open the lower front door  The Transfer Switch carriage  is secured to the frame for shipment  Remove the three  shipping angle  1 upper left  1 upper right  1 lower right         To prevent serious damage  remove three  shipping angles from the Transfer Switch  carriage  Do not turn the Isolation Handle  until they are removed        INSTALLATION    PWEN ENE       Figure 1 1  Typical enclosure        remove 3 shipping  L   angles from transfer switch    Figure 1 2  Remove three shipping L angles     INSTALLATION  continued     A DANGER    De energize the conductors before making any  line or auxiliary circuitry connections  Be sure  that Normal and Emergency line connections  are in proper phase rotation  Place engine gen   erator starting control in the OFF position  Make  sure engine generator is not in operation              Testing Power Conductors    Do not connect the power conductors to the ACTB until  they are tested  Installing power cables in conduit  cable  troughs  and ceiling suspended hangers often requires  considerable force  The pulling of cables can damage  insulation and stretch or break the conductor   s strands   For this reason  after the cables are pulled into position   and before they are connected they should be tested to  verify that they are not defective or have been damaged  during installation        Protect the switch from construction grit  and metal chips to prevent malfunction or  shortened lif
14. e of the ACTB switch        Connecting Power Conductors    A Wiring Diagram is furnished with the ACTB  All wiring  must be made in accordance with the local codes  After  the power cables have been tested  connect them to the  appropriate terminal lugs on the Bypass Switch as shown  on the wiring diagram provided with this ACTB  Make  sure that the lugs provided are suitable for use with the  cables being installed  Standard terminal lugs are  solderless screw type and will accept the wire sizes listed  on the drawings provided with the ACTB  Be careful  when stripping insulation from conductors  avoid nicking  or ringing the conductor  Remove surface oxides from  conductors by cleaning with a wire brush  Follow    conductor manufacturer   s instructions when aluminum  conductor is used  Apply joint compound to conductor   then carefully wipe away excess compound  Tighten the  cable lugs to the torque specified on the rating label        Be sure that the Normal and Emergency power  connections are in proper phase rotation        Bus Connections    If bus connection is used  use SAE grade 5 hardware to  connect bus to appropriate terminal plates on bypass  switching device  Wipe off bus surfaces before they are  joined  If bus is dirty  gently clean surfaces with a    non flammable solvent  Avoid touching cleaned surfaces        Do not breathe cleaning solvent vapors        Use SAE grade 5 hardware and tighten the bolted joints  to the torque specified in Table 2 1        The
15. ee E eae ne packers 1 1 Do hol exceed the valuss on the tating label  Power Connections terrene eee 1 2 Exceeding the rating can cause personal injury  Engine Starting  amp  Auxiliary Circuits        1 2 or serious equipment damage   Functional Test               000 eae 1 3  1 4  TESTING  amp  SERVICE Nameplate  Transfer Test  amp  Preventive Maintenance     2 1 The Transfer Switch nameplate includes data for each  Trouble Shooting       sssssrsrrrrrrrn 2 2 specific 7000 Series 7ACTB Use the switch only within  BYPASSING  amp  ISOLATING the limits shown on this nameplate  A typical Catalog  Bypassing the ATS                  5   3 1 Number is shown below with its elements explained   Isolating the ATS                00e eee 3 2 ee  Return to Service                0005 3 3  3 4 Catalog Number Identification  Typical 7000 Series ACTB catalog no  for overlapping  INDEX cs piak inaen desea vee back cover neutral  3 pole  1200 amp   480 V  in Type 1 enclosure   G7ACTB C 3 1200 N 5 C  Neutral Phase Poles Amperes Voltage Controller Enclosure  A  solid 2  single    1000 A115 J 400 5   standard C  type 1  B   switching 3  three    1200 B 120   K 415 5X   if F  type 3R  C  overlapping 1600 C 208   L 440 accessories G  type 4  ordered  blank     none 2000 D 220   M 460 L  type 12  3000 E 230   N 480 blank     open type  F 240   P 550  G 277   Q 575  H 380   R 600    381333 136 C     amp   EMERSON    SECTION 1    The ASCO 7000 Series Automatic Closed Transition  Transfer  amp  Bypass  
16. icator   and the Isolation Handle must be in the CLOSED  position  window   See Figures 3 1  3 2  and 3 3           BYPASS             Indicator shows     green   OPEN when the  ATS is not bypassed     To Bypass Normal push in handle  all the way  amp  turn it clockwise      BYPASS SWITCH HANDLE      EMERGENCY          You can only bypass to the same source  that the Transfer Switch is connected   Solenoid interlock prevents incorrect operation        1  Observe which Transfer Switch Connected To light is  on  Normal or Emergency  on the door  This is the  position of the automatic transfer switch    2  Bypass to the same source as connected to transfer  switch as follows  select Normal or Emergency      Indicator shows     yellow   EMERGENCY CLOSED  when ATS is bypassed to Emergency  or   yellow   NORMAL CLOSED when  ATS is bypassed to Normal Source     To Bypass Emergency pull out han   dle all the way  amp  turn it clockwise      Figure 3 1  Bypass Handle and position indicators     To Bypass Normal Source      Load connected to Normal Source   The Transfer Switch Connected To Normal light is on  and Transfer Switch Connected To Emergency light is off     Push in  the Bypass Handle all the way  then turn it  clockwise until Bypass Switch Position shows CLOSED on  NORMAL  yellow indicator   The red light Unit Not In  Automatic will flash     Bypass Switch    Push in  Bypass  Handle    amp   turn it  clockwise        Figure 3 2  Bypass to Normal     To Bypass Emergency Sourc
17. ion of the  Transfer Switch and Control Panel  Turn the Engine Con   trol switch to Auto and put the engine   generator starting  control  at the engine generator set  in automatic mode     In the following test the generator will start  the load will  be transferred to the Emergency source  then back to the  Normal source  An interruption to the load will occur   unless the the Transfer Switch contacts are bypassed be   fore the test  See pages 3 1 and 3 2 for bypassing  amp  iso   lating instructions if no interruption of load is required        Be sure to close the enclosure door  before proceeding to prevent personal injury  in case of electrical system fault        Perform the four step Electrical Operation     Transfer  Test procedure on page 1 4     PREVENTIVE MAINTENANCE  Reasonable care in preventive maintenance will insure  high reliability and long life for the 7000 Series ACTB   An annual preventive maintenance program is recom   mended     ASCO Services  Inc   ASI  is ASCO Power  Technologies    national service organization  ASI    can be contacted at 1 800 800 2726 for informa   tion on preventive maintenance agreements        Checklist for Yearly Inspection    A    Hazardous voltage capable of causing shock   burns  or death is used in this switch   Deenergize both Normal   Emergency power  sources before performing inspections     DANGER          Clean the ATS enclosure  Brush and vacuum away  any excessive dust accumulation  Remove any mois   ture with a cle
18. le must  be in the CLOSED position  yellow indicator on NOR   MAL or EMERGENCY  and the Isolation Handle must  be in the TEST position  window   If the handles are not  in these positions  refer to Return to Service on page 3 3   See Figures 3 11  3 12  and 3 13                 Indicator shows     green   OPEN when the  ATS is not bypassed     To un Bypass Normal push in handle  all the way  amp  turn it counterclockwise         You can only bypass to the same source  that the ATS is connected  Solenoid  interlock prevents incorrect operation        1 Observe which Bypass Switch Position indicator is  yellow  VORMAL or EMERGENCY  at the Bypass  Switch Handle  This indicates the source connected  to the load     Un Bypass to same source as the Bypass Switch  Position as follows  select Normal or Emergency         Indicator shows     yellow   EMERGENCY CLOSED    when ATS is bypassed to Emergency  or    yellow   NORMAL when ATS is  bypassed to Normal Source     To un Bypass Emergency pull out  handle all the way  amp  turn it  counterclockwise      Figure 3 11  Bypass Handle and position indicators     To Un Bypass Normal Source      Load connected to Normal Source   The Transfer Switch Connected To Normal light is on  and Transfer Switch Connected To Emergency light is off     Push in  the Bypass Handle then turn it counterclockwise  until Bypass Switch Position shows OPEN  green indica   tor   The Unit Not in Automatic light should be off     Bypass Switch    Push in  Bypass  
19. on next page     Control  Retransfer Transfer  Delay ast       HEIDE    15 FECONDS     1 3    Closed Transition Alarms    Extended  Parallel To  Time    i    Alarm  Reset     Push To Reset     Failure    Synchronize    TS  Locked  Out   Push To Reset     Closed  Transition  Bypass   Push To Bypass           Close the normal source circuit  breaker  The Transfer Switch  Connected To Normal and the  Normal Source Accepted lights  should come on           Use an accurate voltmeter to  check phase to phase and  phase to neutral voltages pres   ent at the transfer switch normal  source terminals                                Close the emergency source  circuit breaker  Turn the Engine  Control switch to Run to start  the generator  The Transfer  Switch Connected To Normal  amp   Emergency Source Accepted  lights should come on           Use an accurate voltmeter to  check phase to phase and  phase to neutral voltages pres   ent at the transfer switch emer   gency source terminals                                  Use a phase rotation meter to  check phase rotation of emer   gency source  it must be the  same as the normal source     ABC             Turn Engine Control switch to  Auto to stop the generator  The  Emergency Source Accepted  light should go off  Then put the  starting control selector switch   on generator set  in automatic  position  Close enclosure door                    observe  these lights    INSTALLATION  continued     ASCO 7000 SERIES    Power Transfer  amp  B
20. rcuits on the controller or the transfer switch  call your local ASCO Power Technologies sales  office or ASI at 1 800 800 2726  Furnish the Serial No  and Catalog No  from the transfer switch nameplate     MANUAL LOAD TRANSFER    This procedure manually transfers load to other source if  the Transfer Switch or Control Panel are out of service        Close enclosure doors to prevent personal  injury in case of electrical system fault        1  Besure that the Bypass Handle is CLOSED on either  Emergency or Normal  see page 3 1      2  Be sure that the Isolation Handle is in the TEST or  ISOLATE position  see page 3 2      3  Turn the Bypass Handle counterclockwise to OPEN  the Bypass Switch  Then Bypass to the other source     see page 3 1      MAINTENANCE HANDLE    A    DANGER       Bypass and isolate the Transfer Switch before  using the maintenance handle  See pages 3 1  and 3 2  Remove the hub and handle after  using them and store on frame        Turn counterclockwise    to OPEN contacts     Turn clockwise to  CLOSE contacts     slide hub  onto shaft   amp  insert pin         Pull out shaft to operate  Emergency contacts     2 2        Grasp  handle  firmly    Push in shaft to operate  Normal contacts     SECTION 3 BYPASSING  amp  ISOLATING    BYPASSING THE ATS     This procedure explains how to Bypass the closed  automatic transfer switch contacts  Bypassing is required  before the ATS can be tested or isolated  The Bypass  Handle must be in the OPEN position  green ind
21. terclock   wise until the OPEN indicator shows green     This completes the Functional Test of the ACTB     Closed Transition Alarms    Extended Failure  Parallel To  Time Synchronize    Alarm  Reset   Push To Reset     operate  this switch       TS  Locked  Out   Push To Reset     Closed  Transition  Bypass   Push To Bypass        Turn and hold Transfer Control  switch clockwise to Transfer  Test until the engine starts   and runs  within 15 sec    The  Emergency Source Accepted  light should come on        Transfer switch CE closes and  then Transfer Switch CN opens   closed transition overlap   The  Transfer Switch Connected to  Emergency light should come  on and the Transfer Switch Con   nected to Normal light should  go off  you might see and hear  the brief overlap transfer         Transfer switch will operate  back to Normal position after  Feature 3A time delay  For im   mediate retransfer turn Transfer  Control counterclockwise to  Retransfer Delay Bypass  The  Transfer Switch Connected To  Normal light should come on   Transfer Switch Connected to  Emergency light should go off                 The engine generator will stop   after the Feature 2E time delay    unloaded running engine cool   down   The Emergency Source  Accepted light should go off                 SECTION 2 TESTING  amp  SERVICE    TRANSFER TEST    Test the Automatic Closed Transition Transfer Switch  portion of the 7000 Series ACTB at least once a month   This procedure checks the electrical operat
22. tic  transfer switch  ATS  to service after inspection and  maintenance  Observe the Bypass Switch Position indica   tor and lights   Refer to Figures 3 7  3 8  3 9  and 3 10        1  Slide the transfer switch  ATS  into the enclosure   isolation contacts facing inward  until its crank pins  engage the latch plates on both sides  Next push in  side rail carriage  Then close enclosure door     Close the enclosure door to prevent personal  injury in case of electrical system fault     Align position indicator  Do not leave  the handle in an intermediate position                 position  window       ISOLATION HANDLE         CONN  TEST  ISOLATE    TO CONNECT  TRANSFER   WITCH TURN  CLOCKWISE       TO ISOLATE  TRANSEEB            ARGA OH  MEN OT BYES PeR i V        clockwise     draws in the Transfer Switch    Figure 3 8  Isolation Handle     2  Turn the Isolation Handle clockwise  approx  7  turns  until the window shows TEST  The ATS can be  tested now without load interruption  see page 2 1      Bypass Switch    Turn crank  clockwise  until  window  shows  TEST        Figure 3 9  ISOLATE to TEST position        Solenoid interlock prevents you from closing  the isolation contacts until the ATS is in the  same position as the Bypass Switch        3  Observe which Bypass Switch Position indicator is  black  NORMAL or EMERGENCY  at the Bypass  Switch Handle  This indicates the source connected  to the load    4  Observe which Transfer Switch Connected To light is  on  Normal or 
23. ypass Switch    EMERSON     Network Power          Transfer  Transfer Switch Transfer Switch Control  Connected Connected  Retransfer Transfer   To Delay es    Normal Emergency    To  E    Normal    CHI FOS  Bypass ooo onoe     Emergency  Source Source  Accepted Accepted    aie    Figure 1 4  Standard controls and indicators     2   Electrical Operation    This procedure checks electrical operation of the ATS        Be sure to close the enclosure door  before proceeding to prevent personal injury  in case of electrical system fault        Transfer Test    The ATS should be bypassed and isolated  Both normal  and emergency sources must be available and the  emergency source generator  if used  must be capable of  being started  put engine starting control in automatic  position  The Transfer Switch Connected to Normal light  and the Normal Source Accepted light should be on     1     Turn the Isolation Handle clockwise  approximately  7 turns  until the window shows TEST position   NOTE  The engine generator may be signalled   to start while turning the Isolation Handle  If  emergency source is available  the ATS may  operate to the emergency position  If it does   operate Retransfer Delay Bypass switch     Perform steps 1   4 at right  Observe the status lights     E Black square means light is on   O White square means light is off     Turn the Isolation Handle clockwise  approximately  16 turns  to the CONN  connected  position     Push in the Bypass Handle and turn it coun
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Fluke 53 & 54 Series User's Manual  User Manual  TG3 Electronics TG103  Manual de Usuario - Intranet SGM  User Manual - SenseWear  Illumine CLI-EMM030819 Installation Guide  Manuale - Cateye  Rust-Oleum Marine 207009 Use and Care Manual  HERMA Movables® „single-print“-Vorlage / Template / Modèle  Sony XM-2252HX Operating Instructions    Copyright © All rights reserved. 