Home
        Carrier 50RHE006-060 Air Conditioner User Manual
         Contents
1.                           Table 5     DIP Switch Block S2      Accessory 1 Relay Options        ACCESSORY 1 DIP SWITCH POSITION  RELAY OPTIONS 3  Cycle with Fan On  Digital NSB On  Water Valve     Slow Opening On  OAD Off  LEGEND    NSB     Night Setback  OAD     Outdoor Air Damper    NOTE  All other DIP switch combinations are invalid     Table 6     DIP Switch Block S2      Accessory 2 Relay Options    ACCESSORY 2 DIP SWITCH POSITION  RELAY OPTIONS 6  Cycle with Fan On  Digital NSB On    Water Valve     Slow Opening On  OAD Off    LEGEND  NSB     Night Setback  OAD     Ouitdoor Air Damper    NOTE  All other switch combinations are invalid     Auto Dehumidification Mode or High Fan Mode     Switch 7  provides selection of auto dehumidification fan mode or high  fan mode  In auto dehumidification fan mode the fan speed  relay will remain off during cooling stage 2 if terminal H is  active  In high fan mode  the fan enable and fan speed relays  will turn on when terminal H is active  Set the switch to ON for  auto dehumidification fan mode or to OFF for high fan mode     Switch 8     Not used     D Control Accessory Relay Configurations      The following accessory relay settings are applicable for both  D controls only     CYCLE WITH FAN     In this configuration  the relay will be  ON any time the Fan Enable relay is on     CYCLE WITH COMPRESSOR     In this configuration  the  relay will be ON any time the Compressor relay is on     DIGITAL NIGHT SET BACK  NSB      In this c
2.            PM  DISABLEFNARLE  AT  HEAT COOL HEAT PUMP    Jw2  PAS  LOW  JWI N O   OFFON                                                    ca   EA PST FUNCTIONS      GOMR    C   4 RV ON B ACC2   o   EE g RERUMIDINORMAL FUNCTIONS   EE 7  BOILERLESS  ENABLE DISABLE  H  HI FAN DEHUMID    CE 8  BOILERLESS  40  F 50  F NOT USED   S1 s2  DIP SWITCH PACKAGE DIP SWITCH PACKAGE  LEGEND  AL     Alarm Relay Contacts PM     Performance Monitor No feat a  BM     Blower Motor PSC     Permanent Split Capacitor o  Circuit Breaker  BMC     Blower Motor Capacitor RVS     Reversing Valve Solenoid     ae     ee ee TRANS     Transformer Optional Wiring A LED      Compressor Capacitor   F    ri     CB E sec ee asas ia ai ites es 00 Capacitor  co     Sensor  Condensate Overflow      ield Low Voltage Wiring oA  o      FP1     Sensor  Water Coil Freeze Protection           Printed Circuit Trace Solenoid Coil  FP2     Sensor  Air Coil Freeze Protection          ENE So          Optional Wiring        Relay Contacts     N O   HP     High Pressure Switch A oa 6 Temperature Switch  HWTS     High  Leaving  Water Temp Switch Ye Relay Contactor Coil p  JW     Clippable Field Selection Jumper A Q Switch     Loss of Charge  LOC     Loss of Charge Pressure Switch P Thermistor l  MV     Motorized Valve   Ground  P1     Field Wiring Terminal Block eo  Condensate Pan    PB     Power Block Q Wire Nut     Optional wiring     NOTES    Compressor thermally protected internally     z  3     All wiring to the unit must 
3.     If condensate pump is present on unit  be sure drain con   nections have a check valve to prevent back flow of con   densate into other units           65 mm Pitch for  Drainage    el     lt  Drain  Drain Connection    Fig  6     Horizontal Unit Pitch        gt  TO UNIT    MINIMUM PITCH  ONE IN  PER  10 FT OF LINE    SEE  NOTE       DRAIN PLUG    NOTE  Trap should be deep enough to offset maximum unit static  difference  A 102 mm trap is recommended     Fig  7     Trap Condensate Drain    Step 7     Piping Connections     Depending on the  application  there are 3 types of WSHP piping systems to  choose from  water loop  ground water and ground loop  Refer  to Piping Section of Carrier System Design Manual for addi   tional information     All WSHP units use low temperature soldered female pipe  thread fittings for water connections to prevent annealing and  out of round leak problems which are typically associated with  high temperature brazed connections  Refer to Table 1 for  connection sizes  When making piping connections  consider  the following    e Use a backup wrench when making screw connections to  unit to prevent internal damage to piping    Insulation may be required on piping to avoid condensa   tion in the case where fluid in loop piping operates at  temperatures below dew point of adjacent air    Piping systems that contain steel pipes or fittings may  be subject to galvanic corrosion  Dielectric fittings  should be used to isolate the steel parts of the s
4.    1 1 C as the limit   DO NOT clip the jumper  To select    12 2 C as the limit  clip  the jumper    ALARM RELAY SETTING     Select jumper 1  JW1 AL2  Dry  for connecting alarm relay terminal  AL2  to 24 vac  R  or  to remain as a dry contact  no connection   To connect AL2 to  R  do not clip the jumper  To set as dry contact  clip the jumper     C Control DIP Switches     The C Control has 1 DIP  switch block with five switches  See Fig  9 and 10     PERFORMANCE MONITOR  PM      DIP switch 1 will  enable or disable this feature  To enable the PM  set the switch  to ON  To disable the PM  set the switch to OFF     STAGE 2     DIP switch 2 will enable or disable compressor  delay  Set DIP switch to OFF for stage 2 in which the compres   sor will have a 3 second delay before energizing     SWITCHES 3 AND 4     Not used     1 OR 3 TRIES     DIP switch 5 provides selection of whether  there are   or 3 tries for FP1 and FP2  This only applies to FP1  and FP2  and not to any other faults  Set DIP switch 5 to ON  for 1 try or to OFF for 3 tries     NOTE  The alarm relay will not cycle during Test mode if  switch is set to OFF  stage 2     D Control Jumper Settings  See Fig  11 and 12     WATER COIL FREEZE PROTECTION  FP1  LIMIT  SETTING     Select jumper 3   JW3 FP1 Low Temp  to  choose FP1 limit of     12 2 C or  1 1 C  To select    1 1 C as the  limit  DO NOT clip the jumper  To select    12 2 C as the limit   clip the jumper    AIR COIL FREEZE PROTECTION  FP2  LIMIT SET   TING  
5.    Select jumper 2  JW2 FP2 Low Temp  to choose  FP2 limit of    12 2 C or    1 1 C  To select    1 1 C as the limit   DO NOT clip the jumper  To select    12 2 C as the limit  clip  the jumper    ALARM RELAY SETTING     Select jumper 4  JW4 AL2  Dry  for connecting alarm relay terminal  AL2  to 24 vac  R  or  to remain as a dry contact  no connection   To connect AL2 to  R  do not clip the jumper  To set as dry contact  clip the jumper     LOW PRESSURE SETTING     The D Control can be con   figured for Low Pressure Setting  LP   Select jumper 1   JW1 LP Norm Open  for choosing between low pressure  input normally opened or closed  To configure for normally  closed operation  do not clip the jumper  To configure for  normally open operation  clip the jumper        17    D Control DIP Switches     The D Control has 2 DIP  switch blocks  Each DIP switch block has 8 switches and is  labeled either S1 or S2 on the circuit board  See Fig  11 and 12     DIP SWITCH BLOCK 1  S1      This set of switches offers  the following options for D Control configuration     Performance Monitor  PM      Set switch 1 to enable or dis   able performance monitor  To enable the PM  set the switch to  ON  To disable the PM  set the switch to OFF     Compressor Relay Staging Operation     Switch 2 will en   able or disable compressor relay staging operation  The com   pressor relay can be set to turn on with stage   or stage 2 call  from the thermostat  This setting is used with dual stage units   un
6.   Book 1  4  Tab  5a   5a    Printed in U S A     Form 50RHE C1SI Pg t 2 04    Replaces  New    Follow all safety codes  Wear safety glasses and work  gloves  Use quenching cloth for brazing operations  Have fire  extinguisher available  Read these instructions thoroughly and  follow all warnings or cautions attached to the unit  Consult  local building codes and electrical codes for special installation  requirements     Understand the signal words     DANGER  WARNING   and CAUTION  DANGER identifies the most serious hazards  which will result in severe personal injury or death  WARN   ING signifies hazards that could result in personal injury or  death  CAUTION is used to identify unsafe practices  which  would result in minor personal injury or product and property  damage    Recognize safety information  This is the safety alert  symbol       When you see this symbol on the unit and in  instructions or manuals  be alert to the potential for personal  injury     A WARNING       Electrical shock can cause personal injury or death  Before  installing or servicing system  always turn off main power  to system  There may be more than one disconnect switch   Turn off accessory heater power if applicable     GENERAL    This Installation and Start Up Instructions literature is for  Aquazone    Water Source Heat Pump units bearing the Mark  of The European Community  CE   These units are designed in  accordance with European Standard EN60335 2 400     Water Source Heat Pump  WSHP 
7.   To exit Test mode   short the terminals for 3 seconds or cycle the power 3 times  within 60 seconds     NOTE  Deluxe D Control has a flashing code and alarm relay  cycling code that will both have the same numerical label   For example  flashing code 1 will have an alarm relay cycling  code 1  Code 1 indicates the control has not faulted since the  last power off to power on sequence     22    Table 13     C Control Current LED Status  and Alarm Relay Operations    LED STATUS DESCRIPTION OF OPERATION ALARM RELAY   Normal Mode Open    Cycle   on Normal Moda with  closed 5 sec     Open 25 sec    Off C Control is non functional Open  Slow Flash Fault Retry Open  Fast Flash Closed  Open   Slow Flash Over Under Voltage Shutdown  Closed after   15 minutes     Flashing Code 7  Flashing Code 2  Flashing Code 3  Flashing Code 4  Flashing Code 5  Flashing Code 6  Flashing Code 7  Flashing Code 8 Cyaing Code 8      Test Mode     FP1 FP2    Flashing Code 9 Swapped Fault in memory Cycling Code 9    LEGEND    Cycling Code 1  Cycling Code 2  Cycling Code 3  Cycling Code 4  Cycling Code 5  Cycling Code 6    Cycling Code 7    CO     Condensate Overflow  FP     Freeze Protection  HP     High Pressure   LED     Light Emitting Diode  LP     Low Pressure   PM     Performance Monitor  NOTES     1  Slow flash is 1 flash every 2 seconds    2  Fast flash is 2 flashes every 1 second    3  EXAMPLE     Flashing Code 2    is represented by 2 fast flashes followed by  a 10 second pause  This sequence wi
8.   W is active while terminal Y is not  Terminal G must be active  or the W terminal is disregarded  EH1 is immediately turned  on  EH2 will turn on after 5 minutes of continual emergency  heat demand     Units with Aquazone Deluxe D Control    STANDBY FAN ONLY     The compressor will be off  The  Fan Enable  Fan Speed  and reversing valve  RV  relays will be  on if inputs are present  If there is a Fan 1 demand  the Fan  Enable will immediately turn on  If there is a Fan 2 demand   the Fan Enable and Fan Speed will immediately turn on     NOTE  DIP switch 5 on S1 does not have an effect upon Fan 1  and Fan 2 outputs     HEATING STAGE 1     In Heating Stage 1 mode  the Fan  Enable and Compressor relays are turned on immediately   Once the demand is removed  the relays are turned off and the  control reverts to Standby mode  If there is a master slave or  dual compressor application  all compressor relays and related  functions will operate per their associated DIP switch 2 setting  on S1     HEATING STAGE 2     In Heating Stage 2 mode  the Fan  Enable and Compressor relays are remain on  The Fan Speed  relay is turned on immediately and turned off immediately  once the demand is removed  The control reverts to Heating  Stage 1 mode  If there is a master slave or dual compressor  application  all compressor relays and related functions will op   erate per their associated DIP switch 2 setting on S1     HEATING STAGE 3     In Heating Stage 3 mode  the Fan  Enable  Fan Speed and 
9.  Cycles    Only Fan Runs    LEGEND  RV     Reversing Valve           gt X lt     gt X lt    X lt     gt  lt            gt X lt     gt  lt     gt  lt     gt  lt     gt  lt     gt  lt     gt X lt     gt  lt    gt X lt     gt  lt     gt  lt     gt  lt     gt  lt     gt  lt    X lt     gt  lt     Table 16     Troubleshooting  X X Green Status LED Off Check line voltage circuit breaker and disconnect   Check for line voltage between L1 and L2 on the contactor   Check primary secondary voltage on transformer   X Reduced or no water flow in  Check pump operation or valve operation setting   cooling Check water flow adjust to proper flow rate   X Reduced or no airflow in Check for dirty air filter and clean or replace   heating Check fan motor operation and airflow restrictions   External static too high  Check Table 4   X Air temperature out of range  Bring return air temperature within design parameters   in heating  rx   x   Bad HP switch Check switch continuity and operation  Replace     x   X_ Insufficient charge Check for refrigerant leaks   X Reduced or no water flow in   Check pump operation or water valve operation setting   Plugged strainer or filter  Clean or replace   Check water flow adjust to proper flow rate     x    inadequate antifreeze level_  Check antifreeze density with hydrometer   ae el Water temperature out of Bring water temperature within design parameters   range  Bad thermistor Check temperature and impedance correlation   Check fan motor operation and air
10.  Flushing     Once the piping is complete  units require final  purging and loop charging  A flush cart pump of at least 1 5 hp   1 12 kW  is needed to achieve adequate flow velocity in  the loop to purge air and dirt particles from the loop  Flush the  loop in both directions with a high volume of water at a high  velocity  Follow the steps below to properly flush the loop     1  Verify power is off   2  Fill loop with water from hose through flush cart before  using flush cart pump to ensure an even fill  Do not allow    the water level in the flush cart tank to drop below the  pump inlet line to prevent air from filling the line     20       NOTES   1  Based on nominal 54 L s per kW airflow and 21   C EAT heating and 26 7   194   C EAT cooling   2  Cooling air and water numbers can vary greatly with changes in humidity   3  Subcooling is based upon the head pressure at compressor service port     3  Maintain a fluid level in the tank above the return tee to  avoid air entering back into the fluid     4  Shutting off the return valve that connects into the flush  cart reservoir will allow 345 kPa surges to help purge air  pockets  This maintains the pump at 345 kPa     5  To purge  keep the pump at 345 kPa until maximum  pumping pressure is reached     6  Open the return valve to send a pressure surge through  the loop to purge any air pockets in the piping system    7  A noticeable drop in fluid level will be seen in the flush  cart tank  This is the only indication of air
11.  Ground  Water Systems 0 027 I s per kW             19    Unit Start Up Heating Mode    NOTE  Operate the unit in heating cycle after checking the  cooling cycle  Allow five minutes between tests for the pres   sure or reversing valve to equalize     1  Turn thermostat to lowest setting and set thermostat  switch to HEAT position     2  Slowly turn the thermostat to a higher temperature until  the compressor activates     3  Check for warm air delivery at the unit grille within a few  minutes after the unit has begun to operate     4  Check the temperature of both supply and discharge  water  Compare to Table 9  If temperature is within range   proceed  If temperature is outside the range  check the  heating refrigerant pressures in Table 9     5  Once the unit has begun to run  check for warm air deliv   ery at the unit grille   6  Check air temperature rise across the coil when compres     sor is operating  Air temperature rise should be between  11 1 and 16 7 C after 15 minutes at load     7  Check for vibration  noise and water leaks     Flow Regulation     Flow regulation can be accom   plished by two methods  Most water control valves have a flow  adjustment built into the valve  By measuring the pressure drop  through the unit heat exchanger  the flow rate can be deter   mined  See Table 10  Adjust the water control valve until the  flow of  027 to  054 L s per kW cooling is achieved  Since the  pressure constantly varies  two pressure gages may be needed  in some appl
12.  IS A TRAP INSTALLED   Y N   IS AN AIR FILTER INSTALLED   Y N     START UP  IS FAN OPERATING WHEN COMPRESSOR OPERATES   Y N     IF 3 PHASE SCROLL COMPRESSOR IS PRESENT  VERIFY PROPER ROTATION PER INSTRUCTIONS    Y N  ___    UNIT VOLTAGE     COOLING OPERATION    PHASE AB VOLTS PHASE BC VOLTS PHASE CA VOLTS   if 3 phase   if 3 phase    PHASE AB AMPS PHASE BC AMPS PHASE CA AMPS   if 3 phase   if 3 phase    CONTROL VOLTAGE    IS CONTROL VOLTAGE ABOVE 21 6 VOLTS   Y N     IF NOT  CHECK FOR PROPER TRANSFORMER CONNECTION     TEMPERATURES  FILL IN THE ANALYSIS CHART ATTACHED     COAXIAL HEAT COOLING CYCLE     EXCHANGER FLUID IN C FLUID OUT C kPa L S  HEATING CYCLE   FLUID IN C FLUID OUT C kPa L S  AIR COIL COOLING CYCLE   AIR IN C AIROUT C  HEATING CYCLE   AIR IN C  AIROUT C    CL 1    HEATING CYCLE ANALYSIS       SUCTION  oG o   COMPRESSOR    EXPANSION             DISCHARGE             LIQUID LINE   C   C       kPa kPa    WATER IN WATER OUT   gt  LOOK UP PRESSURE DROP IN TABLE 10    TO DETERMINE FLOW RATE          COOLING CYCLE ANALYSIS       SUCTION    COMPRESSOR    EXPANSION    VALVE DISCHARGE                LIQUID LINE   C   C       kPa kPa    WATER IN WATER OUT   gt  LOOK UP PRESSURE DROP IN TABLE 10    TO DETERMINE FLOW RATE          HEAT OF EXTRACTION  ABSORPTION  OR HEAT OF REJECTION      FLOW RATE  L S  x TEMP  DIFF   DEG  C  x FLUID FACTOR        kW   SUPERHEAT   SUCTION TEMPERATURE     SUCTION DEW POINT TEMPERATURE     DEG C   SUBCOOLING   DISCHARGE BUBBLE POINT TEMPERATUR
13.  antifreeze solutions  cut JW3 jumper       Typical heat pump thermostat wiring shown  Refer to thermostat    installation instructions for wiring to the unit     and dry contact will be available between AL1 and AL2       Transformer secondary ground via microprocessor board stand     offs and screws to control box   Ground available from top two  standoffs as shown        Fan motors factory wired for medium speed  For high or low    speed remove BLU wire from fan motor speed tap    M    and con   nect to    H    for high or    L    for low     Fig  9     Typical Aquazone    Complete C Control Wiring  Single Phase Unit     10    COMPONENT LOCATION                                              AL  BR  CAP  CB  cc  co    POWER SUPPLY  REFER TO  DATA PLATE  USE COPPER  CONDUCTORS  ONLY    LUG                                                       CB  TRANS    PE        SEE NOTE 3                                                                                                                                                                                                                                                                           SEE NOTE 8   240V   SEE  NOTE 7 i R  T CA    BRN YEL    GRY BRN SEE  NOTE 7  CCG cc           7   gt      z  TEST PINS  Ae  COMPRESSOR a RED    O  0 P  PICA  T STAT l 3 BLU oF Loc  YQ COMPR  i rs    4 BAN     DIP SWITCH     SEE NOTE 4  GRY    AA  SIAGE2 GRY                   _  FPA  OOLIN j  o H  2 NOT YSED viO vio ane UNITS   cO FAN ii  CAP T
14.  in the loop     NOTE  If air is purged from the system while using a 254 mm  PVC flush tank  the level drop will only be 25 to 51 mm since  liquids are incompressible  If the level drops more than this   flushing should continue since air is still being compressed in  the loop  If level is less than 25 to 51 mm  reverse the flow     8  Repeat this procedure until all air is purged   9  Restore power     Antifreeze may be added before  during or after the flushing  process  However  depending on when it is added in the  process  it can be wasted  Refer to the Antifreeze section for  more detail     Loop static pressure will fluctuate with the seasons  Pres   sures will be higher in the winter months than during the warm   er months  This fluctuation is normal and should be considered  when charging the system initially  Run the unit in either heat   ing or cooling for several minutes to condition the loop to a  homogenous temperature     When complete  perform a final flush and pressurize the  loop to a static pressure of 275 to 345 kPa for winter months or  105 to 135 kPa for summer months     After pressurization  be sure to remove the plug from the  end of the loop pump motor s  to allow trapped air to be  discharged and to ensure the motor housing has been flooded   Be sure the loop flow center provides adequate flow through  the unit by checking pressure drop across the heat exchanger   Compare the results to the data in Table 10     Antifreeze     In areas where enterin
15.  therefore be cleaned at  least once a year  or more often if the water is contaminated    Proper water treatment can minimize tube fouling and  pitting  If such conditions are anticipated  water treatment  analysis is recommended  Refer to the Carrier System Design  Manual  Part 5  for general water conditioning information     A CAUTION    Follow all safety codes  Wear safety glasses and rubber  gloves when using inhibited hydrochloric acid solution   Observe and follow acid manufacturer   s instructions        Clean condensers with an inhibited hydrochloric acid solu   tion  The acid can stain hands and clothing  damage concrete   and  without inhibitor  damage steel  Cover surroundings to  guard against splashing  Vapors from vent pipe are not harmful   but take care to prevent liquid from being carried over by the  gases    Warm solution acts faster  but cold solution is just as effec   tive if applied for a longer period    GRAVITY FLOW METHOD     Do not add solution faster  than vent can exhaust the generated gases    When condenser is full  allow solution to remain overnight   then drain condenser and flush with clean water  Follow acid  manufacturer   s instructions  See Fig  18    FORCED CIRCULATION METHOD     Fully open vent  pipe when filling condenser  The vent may be closed when  condenser is full and pump is operating  See Fig  19     24    Regulate flow to condenser with a supply line valve  If  pump is a nonoverloading type  the valve may be fully closed  whi
16.  units are single package  horizontal mounted units with electronic controls designed for  year round cooling and heating  Aquazone 5ORHE WSHP  units are designed for high efficiency operation using HFC   407C refrigerant     IMPORTANT  The installation of water source heat pump  units and all associated components  parts  and accessories  which make up the installation shall be in accordance with  the regulations of ALL authorities having jurisdiction and    MUST conform to all applicable codes  It is the responsi   bility of the installing contractor to determine and comply  with ALL applicable codes and regulations        INSTALLATION    Step 1     Check Jobsite     Installation  operation and  maintenance instructions are provided with each unit  Before  unit start up  read all manuals and become familiar with the  unit and its operation  Thoroughly check out the system before  operation  Complete the inspections and instructions listed  below to prepare a unit for installation  See Table 1 for unit  physical data     Horizontal units are designed for indoor installation only   Be sure to allow adequate space around the unit for servicing   See Fig  1 for overall unit dimensions  Refer to Fig  2 for an  illustration of a typical horizontal installation     A CAUTION       To avoid equipment damage  do not use these units as a  source of heating or cooling during the construction  process  The mechanical components and filters used in  these units quickly become clogged wi
17. 1 2   2 IPS SDR11 68 1   11 4 IPS SCH40 31 4   11 5 IPS SCH40 41 2   2 IPS SCH40 64 3   LEGEND  IPS     Internal Pipe Size    SCH     Schedule  SDR     Standard Dimensional Ratio    NOTE  Volume of heat exchanger is approximately 3 78 liters   Table 12     Antifreeze Percentages by Volume         MINIMUM TEMPERATURE FOR  FREEZE PROTECTION  C        ANTIFREEZE             Methanol        100  USP Food Grade  Propylene Glycol        Cooling Tower Boiler Systems     These systems typ   ically use a common loop temperature maintained at 15 6 to  32 2 C  Carrier recommends using a closed circuit evaporative  cooling tower with a secondary heat exchanger between the  tower and the water loop  If an open type cooling tower is used  continuously  chemical treatment and filtering will be necessary   The optional cupronickel heat exchanger must also be used in  this case     Ground Coupled  Closed Loop and Plateframe  Heat Exchanger Well Systems     These systems al   low water temperatures from    1 1 to 43 3 C  The external loop  field is divided up into 51 mm polyethylene supply and return  lines  Each line has valves connected in such a way that upon  system start up  each line can be isolated for flushing using  only the system pumps  Locate air separation in the piping sys   tem prior to the fluid re entering the loop field     21    OPERATION    Power Up Mode     The unit will not operate until all the  inputs  terminals and safety controls are checked for normal  operation     
18. 288 250 198      015 212 160 MED 321 302 274 241 189      LO 293 278 255 222 179      HI 326 311 283 250 203      019 264 198 MED 302 288 260 227 189      LO 293 269 245 217 179    HI 396 368 335 302 260      024 307 231 MED 387 359 326 297 255      LO 368 340 311 278 231      HI 529 496 463 425 378 330  030 349 264 MED 510 477 448 415 368 326  LO 458 439 406 378 340 297  HI 614 576 519 463 415 373  036 437 326 MED 580 543 488 434 392 349  LO 505 472 429 387 349      HI 743 691 629 566 501 435  042 530 396 MED 637 593 539 485 429      LO 498 463 421  HI 793 738 672 604 535 464  048 630 472 MED 777 723 658 592 524 455  LO 762 709 645 580 514 446       p A HI 757 668 552  High mao 630 472 MED   787 710 623 529  LO 797   748 690 612 516   HI    896 866 833 796 755 710    060 790 595 MED 818 803 779 747 707 658  LO 748 731 709 683 653 618  LEGEND NOTES   Shaded areas are below minimum CFM  This data is 1  Units factory shipped on medium speed  Other speeds require    field selection   2  For dual voltage units  airflow is rated at lowest voltage   3  Performance data shown is based n wet coil and clean air filter     provided for troubleshooting information only     Step 9     Low Voltage Wiring  See Fig  15  O      22  THERMOSTAT CONNECTIONS     The thermostat should oe ee       CLIP JW2 FP2         mi ee  be wired directly to the Aquazone    control board  See eat    JUMPER FOR  fe                 ANTI FREEZE    Fig  9 12   SYSTEMS    WATER FREEZE PROTECTION     The Aquazone co
19. 568 658 6  9 1 3 3 4 14 17  0 027 225 254 535 592 5  9 4  8 11 12 11 13 212 245 613 688 8 11 1 3 8 9  21 0 041 222 251 502 556 5  9 4 7 7 9 11 13 218 254 628 712 8 11 1 3 5 6 17 21  0 054 219 248 472 523 5  9 4  7 4  7 11 13 227 263 8 11 1 3 3 4 17 21  0 027 225 254 685 75 5  9 4  8 10 12 9 13 254 284 658 777 10 16 1 3 8 9  0 041 222 251 652 721 5  9 4  7 6  8 9 13 269 299 673 792 10 16 1 3 6 7  0 054 219 248 622 688 5  9 4  7 3  6 9 13 284 314 688 807 10 16 1 3  5  0 027 231 260 837 957 4  8 6 14 9 11 8 11  0 041 228 257 807 927 4  8 6 13 5  7 8 11  0 054 225 254 777 897 4  8 6 12 3  6 8 11          LEGEND    DB     Dry Bulb  EAT     Entering Air Temperature    Table 10     50RHE Coaxial Water Pressure Drop       UNIT PRESSURE DROP  kPa   50RHE 30  C  0 047 48   006 0 071 6 9  0 095 0 11 7   6 9 6 6   009 10 5 9 9  20 9 20 0   16 7 16 1   012 36 2 34 7  57 7 55 0     16 7 14 7 14 1   015   32 6 28 7 27 2  55 9 48 7 46 3     12 9 11 1 10 8   019 23 0 20 3 19 1  0 284 45 4 39 8 37 7   0 189 13 8 i 11 7 11 4   024 0 284 28 7   25 1 23 9  0 379 47 8 i 41 9 39 8   0 237 9 9 9 0 8 4 8 1   030 0 347 17 0 15 8 14 7 14 1  0 473 26 9 25 4 23 6 22 4   0 284 7 8 7 2 6 9 6 6   036 0 426 15 0 13 8 2 9 12 3  0 568 23 9 22 4 0 9 20 0   0 331 9 9 9 3 8 7 8 4   042 0 498 19 7 18 5 17 0 16 4  0 663 31 1 29 3 27 5 26 0   0 379 14 1 13 2 12 3 11 7   048 0 568 26 9 25 4 23 6 22 4  0 757 44 0 41 0 38 3 36 5   0 473 33 5 31 4 29 3 27 8   060 0 713 58 3 54 4 50 8 48 4    0 947 88 5 82 8 77 1 73 3   
20. Aquazone     50RHE006 060   Water Source Heat Pumps  Horizontal Unit   50 Hz  CE Mark       R 407C  Installation  Start Up  and  CONTENTS Page  Ground Coupled  Closed Loop and Plateframe  Page Heat Exchanger Well Systems                  21  SAFETY CONSIDERATIONS                     1 2 OPERATION    21 22  GENERAL is cnc tees tt ae Aaah E 2 Power Up Mode                     0 0 00 0 eee 21  INSTALLATION                 0  000 cee eee 2 16 Units with Aquazone Complete C Control        21  Step 1     Check Jobsite                         2 Units with Aquazone Deluxe D Control           21  Step 2     Check Unit                         5  2 SYSTEM TEST   fer  iren pages phage ined ae 22 23  e STORAGE Test Mode              0  cece eee eee eee eens 22  e PROTECTION Retry Mode                 0    c cece eee eens 23  e INSPECT UNIT Aquazone Deluxe D Control LED Indicators       23  Step 3     Unit Location    n    sossar 6 SERVICE p  ka aE A sane 23 25  e FIELD CONVERSION OF DISCHARGE AIR FLOPS o site a Ab icv ars EEE aad eS 23  Step 4     Mounting the Unit                        J Water Coil    L e eked ag ea tees 23  Step 5     Duct System                        4 5  7 Condensate Drain Pans                           24  e SOUND ATTENUATION Refrigerant System       0    aaeocae 24     EXISTING DUCT SYSTEM Condensate Drain Cleaning                      24  Step 6     Condensate Drain                       7 Air Coil Cleaning                        000000e  24  e VENTING     Conden
21. CONTACT ALARM SEE MICRO   j elt  RELAY NOTE   processor    6 CONTROL LOGIC                                                        SIZES  006  009  012       LEGEND          AL     Alarm Relay Contacts PM     Performance Monitor es  BR     Blower Relay PSC      Permanent Split Capacitor     Condensate Pan  CAP     Compressor Capacitor RVS     Reversing Valve Solenoid oO Circuit Breaker  CB     Circuit Breaker TRANS     Transformer Optional Wiring  CC     Compressor Contactor        Field Line Voltage Wiring O4F   Relay Contacts     N C   co     Sensor  Condensate Overflow i i f i  FP1     Sensor  Water Coil Freeze Protection         Field Low Voltage Wiring o   Solenoid Coil  ND   a Air Coil Freeze Protection   Printed Circuit Trace HH Relay Contacts     N O   HP     High Pressure Switch   tem Optional Wiring    switch Temperature  JW     Clippable Field Selection Jumper oe Relay Contactor Coil  LOC     Loss of Charge Pressure Switch reS Switch Low Pressure  P1     Field Wiring Terminal Block   l  PB     Power Block K Thermistor    Ground  C  Wire Nut   Optional wiring   NOTES   1  Compressor and blower motor thermally protected internally  6  24 v alarm signal shown  For dry alarm contact  cut JW1 jumper     2  3  4  5      All wiring to the unit must comply with NEC and local codes     Transformer is wired to 240 v  ORG  lead for 240 50 1 units     switch RED and ORG leads to PB 1  and insulate ORG lead       FP1 thermistor provides freeze protection for water  When using   
22. Compressor relays remain on  The EH1  output is turned on immediately  With continuing Heat Stage 3  demand  EH2 will turn on after 10 minutes  EH1 and EH2 are  turned off immediately when the Heating Stage 3 demand is re   moved  The control reverts to Heating Stage 2 mode     Output EH  will be off if FP1 is greater than 7 2 C and FP2   when shorted  is greater than 43 3 C during Heating Stage 3  mode  This condition will have a 30 second recognition time   Also  during Heating Stage 3 mode  EH1  EH2  Fan Enable   and Fan Speed will be ON if G input is not active     EMERGENCY HEAT     In Emergency Heat mode  the Fan  Enable and Fan Speed relays are turned on  The EH1 output is  turned on immediately  With continuing Emergency Heat de   mand  EH2 will turn on after 5 minutes  Fan Enable and Fan  Speed relays are turned off after a 60 second delay  The control  reverts to Standby mode     Output EH1  EH2  Fan Enable  and Fan Speed will be ON if  the G input is not active during Emergency Heat mode     COOLING STAGE 1     In Cooling Stage 1 mode  the Fan  Enable  compressor and RV relays are turned on immediately   If configured as stage 2  DIP switch set to OFF  then the com   pressor and fan will not turn on until there is a stage 2 demand   The fan Enable and compressor relays are turned off immedi   ately when the Cooling Stage 1 demand is removed  The con   trol reverts to Standby mode  The RV relay remains on until  there is a heating demand  If there is a master slave 
23. E     LIQUID LINE TEMPERATURE     DEG C      Use 4 16 for water  4 03 for antifreeze     Copyright 2004 Carrier Corporation    Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations   Book  1  4 Catalog No  005 00042 Printed in U S A  Form 50RHE C1SI Pg CL 2 2 04 Replaces  New  Tab 5a 5a    CUT ALONG DOTTED LINE      CUT ALONG DOTTED LINE s   i         S                     
24. EUTRAL    ONLY  L   SEE NOTE 3  CB TRANS  EE  r A YELI  BLU ORs   He   U  240V   hEm   ED BRN  SIZES  006  009  012 BRN  SEE  NOTE 7  TYPICAL HEAT   aaa og FANENABLE       PUMP T STAT _ COM2 COM1 SOM  SEE NOTE 5 NOS  GRY  Sd    COMPR   ogl COOLING com   n   FAN   5  GH     DXM NO  ROLZAVAC   MICROPROCESSOR GRY BLK  HWTS  C o COMMON a CONTROL LOGIC REDo Lo Buel  kig  ALARM    he   SEE   RED    BLK  NOTE 6 BLU LOC  ALARM   eee   SEE NOTE 6 FOR RELAY Jw4 a SEE NOTE 4  DRY CONTACT e ny  STATUS    GRY   FOR ALARM  AL2 __DRY4 test      GRY  FP1  TXV UNITS   i VIO  CAP TUBE VIO   pe FAULT B UNITS  OR aca RRA  COMPONENT LOCATION   RV RELAY  BRNS  TEST  O O   PINS yYeEL    00  TL  JIW3 SEE    cr __  IW Low LOW NOTE 4  BR2 Hp DN Fp2 LO  L  N uw M  mlp PM  AE uo Eon ere    a ay c1  acct TENE  B  UNIT STAGE  2 1 BRNA  p  8 T STAT  HEAT OOO HEAT PUMP   Em 3    FUNCTIONS    z o Lit RV ON B RV ON 0 ACC2  s    DEHUMID NORMAL FUNCTIONS YEL  Be NOT USED ee at GON m M  He U  BOILERLESS  ENABLE DISABLE H  HI FAN DEHUMID RED  Ey eqs BOILERLESS  40  F 50  F       8  NOT USED    2 S1 S2  SIZES  015 060 DIP SWITCH PACKAGE DIP SWITCH PACKAGE  LEGEND  AL     Alarm Relay Contacts P1     Field Wiring Terminal Block of F  BM     Blower Motor PB     Power Block Thermistor  BMC     Blower Motor Capacitor PM     Performance Monitor     c   gt     ondensate Pan  BR     Blower Relay f PSC     Permanent Split Capacitor ERT  CAP     Compressor Capacitor RVS     Reversing Valve Solenoid    LED  CB     Circuit Br
25. ND  FLA Full Load Amps  HACR Heating  Air Conditioning and Refrigeration    LRA     Locked Rotor Amps  RLA     Rated Load Amps    POWER CONNECTION     Make line voltage connection  by connecting the incoming line voltage wires to the L side  of the CC terminal as shown in Fig  13  See Table 3 for  correct wire and maximum overcurrent protection sizing   SUPPLY VOLTAGE     Operating voltage to unit must be  within voltage range indicated on unit nameplate    On 3 phase units  voltages under load between phases must  be balanced within 2   Use the following formula to deter   mine the percentage voltage imbalance       Voltage Imbalance    max voltage deviation from average voltage    NA average voltage    Example  Supply voltage is 460 3 60   AB   452 volts    BC   464 volts  AC   455 volts    A B C    f    Average Voltage   oe  1371  3    457    Determine maximum deviation from average voltage      AB  457     452  5v   BC  464     457  7 v   AC  457     455  2v    Maximum deviation is 7 v   Determine percent voltage imbalance     7      Voltage Imbalance   100 x BT      1 53     This amount of phase imbalance is satisfactory as it is  below the maximum allowable 2      14    Operation on improper line voltage or excessive phase  imbalance constitutes abuse and may cause damage to electri   cal components     NOTE  If more than 2  voltage imbalance is present  contact  local electric utility     220 VOLT OPERATION     All 220 240 volt units are factory  wired for 208 volts  T
26. NOTE  The compressor will have a 5 minute anti short cycle  upon power up     Units with Aquazone    Complete C Control    STANDBY     Y and W terminals are not active in standby  mode  however the O and G terminals may be active  depend   ing on the application  The compressor will be off     COOLING     Y and O terminals are active in Cooling mode   After power up  the first call to the compressor will initiate a  5 to 80 second random start delay and a 5 minute anti short  cycle protection time delay  After both delays are complete  the  compressor is energized     NOTE  On all subsequent compressor calls the random start  delay is omitted     HEATING STAGE 1     Terminal Y is active in heating  stage 1  After power up  the first call to the compressor will  initiate a 5 to 80 second random start delay and a 5 minute  anti short cycle protection time delay  After both delays are  complete  the compressor is energized     NOTE  On all subsequent compressor calls the random start  delay is omitted     HEATING STAGE 2     To enter Stage 2 mode  terminal W is  active  Y is already active   Also  the G terminal must be ac   tive or the W terminal is disregarded  The compressor relay  will remain on and EH1 is immediately turned on  EH2 will  turn on after 10 minutes of continual stage 2 demand     NOTE  EH2 will not turn on  or if on  will turn off  if FP1 tem   perature is greater than 7 2 C and FP2 is greater than 43 3 C     EMERGENCY HEAT     In emergency heat mode  terminal
27. Plugged strainer or filter  Clean or replace   Check water flow adjust to proper flow rate     i el Water temperature out of Bring water temperature within design parameters   range    X Reduced airflow in cooling  Check for dirty air filter and clean or replace   e Check fan motor operation and airflow restrictions   External static too high  Check blower Table 4   E Too much cold vent air  Bring entering air temperature within design  parameters     Check for refrigerant leaks     x   Too high airflow  Check blower Table 4   x    Poor performance  See    insufficient Capacity      x  Too high airflow  Check blower Table 4     rea Se Recheck loads and sizing check sensible cooling load and heat pump  capacity                       27    Copyright 2004 Carrier Corporation    Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations   mat 4 Catalog No  005 00042 Printed in U S A  Form 50RHE C1SI Pg 30 2 04 Replaces  New  Tab  5a 5a    50RHE R 407C UNIT  START UP CHECKLIST    CUSTOMER  JOB NAME     MODEL NO   SERIAL NO   DATE     PRE START UP  DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE   Y N     HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS  TIGHT   Y N     HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER    Y N         HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN   Y N   HAS CONDENSATE CONNECTION BEEN MADE AND
28. UBE e  FP2  24VAC UNITS  OR VIO         R    BRN o  COMMON STATUS   RVS  cO tal LED ORG  ALARM     LO fit NOT USED  E   ty   CXM YEL        co  SEE NOTE 6 FOR   SEE  MICROPROCESSOR 2 1  DRY ALARM CONTACT MALARM NOTE6   CONTROL LOGIC          Alarm Relay Contacts       Blower Relay       Compressor Capacitor       Circuit Breaker       Compressor Contactor       Sensor  Condensate Overflow    COMP     Compressor    FP1  FP2  GND  HP  JW  LOC  P1  PB        Ground     Optional wiring   NOTES     High Pressure Switch   Clippable Field Selection Jumper  Loss of Charge Pressure Switch  Field Wiring Terminal Block  Power Block    Sensor  Water Coil Freeze Protection  Sensor  Air Coil Freeze Protection                                              LEGEND  PM     Performance Monitor A  PSC     Permanent Split Capacitor o   O Circuit Breaker  RVS     Reversing Valve Solenoid  TRANS     Transformer Optional Wiring O4FO Relay Contacts     N C       Field Line Voltage Wiring oA o Solenoid Coil         _ Field Low Voltage Wiring obo Relay Contacts     N O          Printed Circuit Trace ono i           Optional Wiring Switch Temperature  Ye Relay Contactor Coil a Switch Low Pressure   e Ground  KP Thermistor aq Wire Nut  l   Condensate Pan cl Splice Cap    1  Compressor and blower motor thermally protected internally     All wiring to the unit must comply with NEC and local codes     Transformer is wired to 240 v  ORG  lead for 240 50 1 units       FP1 thermistor provides freeze protection 
29. ation is not required  be sure that a proper air path is provided  for ventilation air to unit to meet ventilation requirement of the  space           Air Handler    Section      Compressor  C A Section                      DIMENSIONS  mm     ciel  e o LE  006 024 518  030 036 518  042 048 518  oso 504    Fig  5     Horizontal Hanger Bracket   Factory Installed        Step 6     Condensate Drain     Slope the unit to   ward the drain at a 6 5 mm per 30 cm pitch  See Fig  6  If it is  not possible to meet the required pitch  install a condensate  pump at the unit to pump condensate to building drain     Horizontal units are not internally trapped  therefore an ex   ternal trap is necessary  Install each unit with its own individual  trap and means to flush or blowout the condensate drain line   Do not install units with a common trap or vent  For typical  condensate connections see Fig  7     NOTE  Never use a pipe size smaller than the connection     VENTING     Install a vent in the condensate line of any  application that may allow dirt or air to collect in the line  Con   sider the following    e Always install a vent where an application requires a  long horizontal run    e Always install a vent where large units are working  against higher external static pressure and to allow  proper drainage for multiple units connected to the same  condensate main    e Be sure to support the line where anticipated sagging from  the condensate or when    double trapping    may occur   
30. be required for single   phase units where starting the unit is a problem due to low  voltage  See Fig  20 for thermistor nominal resistance     Control Sensors     The control system employs 2 nom   inal 10 000 ohm thermistors  FP1 and FP2  that are used for  freeze protection  Be sure FP1 is located in the discharge fluid  and FP2 is located in the air discharge  See Fig  21     90 0    80 0 f        70 0       60 0       50 0       40 0       30 0       Resistance  kOhm     20 0       10 0            0 0           0 0 20 0 40 0 60 0 80 0 100 0 120 0 140 0  Temperature  degF                          Fig  20     Thermistor Nominal Resistance       A                               WATER IN    AIRFLOW AIRFLOW     F     F   THERMISTOR  EXPANSION  VALVE  N FP2 FP1    SS      CONDENSATE  OVERFLOW LIQUID   CO  LIN  AIR COIL  FREEZE WATER  PROTECTION COIL  PROTECTION    LEGEND  COAX     Coaxial Heat Exchanger       c Airflow      gt  Refrigerant Liquid Line Flow           SUCTION    COMPRESSOR    DISCHARGE       WATER OUT    Fig  21     FP1 and FP2 Thermistor Location    FAULT  Main Power Problems    HP Fault     Code 2  High Pressure    LP LOC Fault     Code 3  Low Pressure Loss of  Charge    FP1 Fault     Code 4  Water Freeze Protection    FP2 Fault     Code 5  Air Coil Freeze  Protection    Condensate Fault      Code 6    Over Under Voltage      Code 7   Auto Resetting     Performance Monitor      Code 8    FP1 and FP2  Thermistors      Code 9    No Fault Code Shown    Unit Short
31. comply with NEC and local codes    Neutral of 380 415 3 50 is required  Transformer is wired to 240 v  ORG   lead for 415 3 50  For 380 3 50 switch ORG and  RED  leads at PB 3  and  insulate ORG lead  Transformer uses separate circuit breaker       FP1 thermistor provides freeze protection for water  When using antifreeze    solutions  cut JW3 jumper       Check installation wiring information for specific thermostat hookup  Refer    to thermostat installation instructions for wiring to the unit  Thermostat  wiring must be    Class 1    and voltage rating equal to or greater than unit  supply voltage       24 v alarm signal shown  For dry alarm contact  cut JW4 jumper  and dry  contact will be available between AL1 and AL2      Transformer secondary ground via microprocessor board standoffs and  screws to control box   Ground available from top two standoffs as shown       Blower motor is factory wired for medium and high speeds  For any other  combination of speeds  at the motor attach black wire to the higher of the  two desired speed taps  and the blue wire to the lower of the two desired  speed taps      Blower motor is factory wired for high and low speeds  No other combina   tion of speeds is available     Fig  12     Typical Aquazone    Deluxe D Control Wiring  3 Phase Unit     13    Table 3     Electrical Data    50RHE VOLTS PHASE VOLTAGE COMPRESSOR Peete Tore anit MAX  UNIT  50 Hz  MIN MAX FEA ELA AMP FUSE HACR    rE  onsas   sae   s2   0o   17   so   69   15    LEGE
32. de     Switch 6     Not used     Boilerless Operation     Switch 7 provides selection of boiler   less operation and works in conjunction with switch 8  In  boilerless operation mode  only the compressor is used for  heating when FP1 is above the boilerless changeover tempera   ture set by switch 8 below  Select ON for normal operation or  select OFF for boilerless operation     Boilerless Changeover Temperature     Switch 8 on S1 pro   vides selection of boilerless changeover temperature set point   Select OFF for set point of 10 C or select ON for set point  of 4 4C     If switch 8 is set for 10 C  then the compressor will be used  for heating as long as the FP1 is above 10 C  The compressor  will not be used for heating when the FP1 is below 10 C and  the compressor will operates in emergency heat mode  staging  on EH1 and EH2 to provide heat  If a thermal switch is being  used instead of the FP1 thermistor  only the compressor will be  used for heating mode when the FP1 terminals are closed  If  the FP1 terminals are open  the compressor is not used and the  control goes into emergency heat mode    DIP SWITCH BLOCK 2  S2      This set of DIP switches is  used to configure accessory relay options  See Fig  11 and 12   Switches 1 to 3     These DIP switches provide selection  of Accessory 1 relay options  See Table 5 for DIP switch  combinations    Switches 4 to6     These DIP switches provide selection  of Accessory 2 relay options  See Table 6 for DIP switch  combinations
33. e  Whenever any of these factors are at a  minimum or maximum level  the other two factors must be at a  normal level to ensure proper unit operation  See Table 7     Table 7     Operating Limits     50RHE Units    AIR LIMITS HEATING  C   Min  Ambient Air 7 2  Rated Ambient Air 21 1  Max  Ambient Air 29 4  Min  Entering Air 4 4  Rated Entering Air db wb 20 15  Max  Entering Air db wb 27  WATER LIMITS  Min  Entering Water  6 7  Normal Entering Water  1 1 to 15 6  LEGEND  db     Dry Bulb  wb     Wet Bulb    NOTE  Value in heating column is dry bulb only  Any wet bulb read   ing is acceptable     AUNE    Scroll Compressor Rotation     It is important to be  certain compressor is rotating in the proper direction  To  determine whether or not compressor is rotating in the proper  direction   1  Connect service gages to suction and discharge pressure  fittings   2  Energize the compressor   3  The suction pressure should drop and the discharge  pressure should rise  as is normal on any start up     If the suction pressure does not drop and the discharge  pressure does not rise to normal levels     1  Turn off power to the unit  Install disconnect tag   2  Reverse any two of the unit power leads   3  Reapply power to the unit and verify pressures are correct     The suction and discharge pressure levels should now move  to their normal start up levels     When the compressor is rotating in the wrong direction  the  unit makes more noise and does not provide cooling     After a few m
34. e the subcooling temperature with the normal  temperature listed in Table 9  If the measured liquid line  temperature does not agree with the required liquid line  temperature  ADD refrigerant to raise the temperature or  REMOVE refrigerant  using standard practices  to lower  the temperature  allow a tolerance of   1 7   C      Refrigerant Charging    A WARNING    To prevent personal injury  wear safety glasses and gloves  when handling refrigerant  Do not overcharge system      this can cause compressor flooding        NOTE  Do not vent or depressurize unit refrigerant to atmo   sphere  Remove and reclaim refrigerant following accepted  practices     Air Coil Fan Motor Removal    A CAUTION    Before attempting to remove fan motors or motor mounts     place a piece of plywood over evaporator coils to prevent  coil damage     Disconnect motor power wires from motor terminals before  motor is removed from unit     1  Shut off unit main power supply     2  Loosen bolts on mounting bracket so that fan belt can be  removed     3  Loosen and remove the 2 motor mounting bracket bolts  on left side of bracket     4  Slide motor bracket assembly to extreme right and lift out  through space between fan scroll and side frame  Rest       motor on a high platform such as a step ladder  Do not  allow motor to hang by its power wires     TROUBLESHOOTING   Fig  20 and 21  and Table 16     When troubleshooting problems with a WSHP  consider the  following     Thermistor     A thermistor may 
35. eaker TRANS     Transformer Optional Wiring      co     Sensor  Condensate Overflow     sri oo Solenoid Coil          Field Line Voltage Wiring  FP1     Sensor  Water Coil Freeze Protection f B HH  FP2     Sensor  Air Coil Freeze Protection      Field Low Voltage Wiring Relay Contacts     N O   GND     Ground Pri ai i    F          rint ircuit Tr on    Temperature Switch  HP     High Pressure Switch ted S a ae emp  rature Swite  HWTS     High  Leaving  Water Temp Switch          Optional Wiring aad Switch     Loss of Charge  JW     Clippable Field Selection Jumper    LOC     Loss of Charge Pressure Switch Ye Relay Contactor Coil a Ground  MV     Motorized Valve    C    Wire Nut     Optional wiring   NOTES     1   2   3     Compressor thermally protected internally     All wiring to the unit must comply with NEC and local codes     Transformer is wired to 240 v  ORG  lead for 240 50 1 units  6     switch RED and ORG leads to PB 1  and insulate ORG lead for  220 50 1       FP1 thermistor provides freeze protection for water  When using    antifreeze solutions  cut JW3 jumper       Check installation wiring information for specific thermostat    hookup  Refer to thermostat installation instructions for wiring to  the unit  Thermostat wiring must be    Class 1    and voltage rating  equal to or greater than unit supply voltage     24 v alarm signal shown  For dry alarm contact  cut JW4 jumper   and dry contact will be available between AL1 and AL2       Transformer secondary grou
36. ere  the refrigerant circuit of this unit must only be  serviced by technicians which meet local  state and federal  proficiency requirements     IMPORTANT  To prevent injury or death due to electrical  shock or contact with moving parts  open unit disconnect  switch before servicing unit        Filters     Filters must be clean for maximum performance   Inspect filters every month under normal operating conditions   replace when necessary     IMPORTANT  Units should never be operated with     out a filter        Water Coil     Keep all air out of the water coil  Check  open loop systems to be sure the well head is not allowing air  to infiltrate the water line  Always keep lines airtight     Inspect heat exchangers regularly  and clean more frequent   ly if the unit is located in a    dirty    environment  Keep the heat  exchanger full of water at all times  Open loop systems should  have an inverted P trap placed in the discharge line to keep  water in the heat exchanger during off cycles  Closed loop  systems must have a minimum of 105 kPa during the summer  and 275 kPa during the winter     Check P trap frequently for proper operation     Table 15     Aquazone    D Control Current LED Status and Alarm Relay Operations    DESCRIPTION  Normal Mode    Normal Mode with PM    Test Mode  Night Setback    STATUS LED TEST LED  elon  FAULT LED  Red   o_o E Flash Last Fault Code in Memory Open    D Control is non functional ai o  0o  L   o   Flash Last Fault EKT in Memory Cycling A
37. flow before 45 seconds  and it Ga                CLIP JW3   JW3 6   FP1 Low Temp  FOR JW2 6   FP2 Low Temp                                                                                                       Typical  Water  Valve    activates the compressor only after the valve is completely  opened by closing its end switch  When wired as shown  the  valve will have the following operating characteristics   A  O    1  Remain open during a lockout  2  Draw approximately 25 to 35 VA through the    Y    signal Fig  17     Typical D Control Accessory Wiring  of the thermostat     IMPORTANT  Connecting a water solenoid valve can  overheat the anticipators of electromechanical thermo   stats  Only use relay based electronic thermostats  PRE START UP    System Checkout     When the installation is complete   follow the System Checkout procedure outlined below before  starting up the system  Be sure     1  Voltage is within the utilization range specifications of the  unit compressor and fan motor and voltage is balanced  for 3 phase units       Fuses  breakers and wire are correct size      Low voltage wiring is complete    Piping and system flushing is complete      Airis purged from closed loop system    System is balanced as required  Monitor if necessary     Isolation valves are open      Water control valves or loop pumps are wired      Condensate line is open and correctly pitched      Transformer switched to lower voltage tap if necessary     Blower rotates freely     shipp
38. flow restrictions   External static too high  Check Table 4   X Air temperature out of range   Too much cold vent air  Bring entering air temperature within design  parameters   x Improper freeze protect set    Normal airside applications will require    1 1 C only   ting   1 1 C vs  12 2 C   Blocked drain Check for blockage and clean drain   Improper trap Check trap dimensions and location ahead of vent      X  Moisture on sensor  Check for moisture shorting to air coil   X X Under voltage Check power supply and 24 vac voltage before and during operation   Check power supply wire size   Check compressor starting   Check 24 vac and unit transformer tap for correct power supply voltage     x    Heating mode FP2 gt  51 7 C  Check for poor airflow or overcharged unit   X Cooling mode FP1 gt  51 7 C  Check for poor water flow or airflow   OR FP2 lt  4 4 C  X FP2 temperature is higher  Swap FP1 and FP2 thermistors   than FP1 temperature   rx   x   No compressor operation See scroll compressor rotation section   rx   x   Control board Reset power and check operation     x   X _  Dirty air filter Check and clean air filter   rf x   x   Unit selection Unit may be oversized for space  Check sizing for actual load of space     x   x  Compressor overload Check and replace if necessary   rx   x    Unit locked out Check for lockout codes  Reset power   Compressor overload Check compressor overload  Replace if necessary     HEATING   COOLING POSSIBLE CAUSE SOLUTION  Check for 24 vac betwee
39. for water  When using  antifreeze solutions  cut JW3 jumper     2  3  switch RED and ORG leads to PB 3  and insulate ORG lead   4  5      Typical heat pump thermostat wiring shown  Refer to thermostat  installation instructions for wiring to the unit     11    6    7       24 v alarm signal shown  For dry alarm contact  cut JW1 jumper    and dry contact will be available between AL1 and AL2    Transformer secondary ground via microprocessor board stand    offs and screws to control box   Ground available from top two   standoffs as shown       Fan motors factory wired for medium speed  For high or low  speed remove BLU wire from fan motor speed tap    M    and con   nect to    H    for high or    L    for low     Fig  10     Typical Aquazone    Complete C Control Wiring  3 Phase Unit                                                                                                START ASSIST   WHEN NEEDED                    SEE NOTE 8                                                                                                                                                                                                                                                                                                                                                                                                                                                                            power suppLy   EARTH  GRD   RED  BLU   REFER TO ree  DATA PLATE  USE COPPER  CONDUCTORS   N  N
40. g and shipping information to verify that the 9  Remove any access panel screws that may be difficult to    correct unit has been shipped     2  Verify that the unit is the correct model for the entering  water temperature of the job     remove once unit is installed     Table 1     Physical Data     Aquazone    50RHE006 060 Units    UNIT 50RHE 060  COMPRESSOR  1 each  Scroll  FACTORY CHARGE R 407C  kg  2 41  PSC FAN MOTOR AND BLOWER   Fan Motor Type Speeds PSC 3  Fan Motor  Hp   w  1  746   Blower Wheel Size  D x W   mm  279 x 254       HORIZONTAL  Air Coil  Dimensions  H x w   mm  254 x 406 406 x 406 457 x 559 457 x 787 508 x 889  Total Face Area  m    0 103 0 165 0 255 0 360 0 452  Tube Size  mm  9 5   i   9 5  Distance Between Fins  mm  2 2 2 7  Number of Rows 2   4  Filter Standard Throwaway 1     305 x 508   Qty     Size  mm  Teena eae 1     635 x 508  Weight 25 4 mm  kg   Operating 146 8  Packaged 153 6  LEGEND NOTES     PSC     Permanent Split Capacitor    1  All units have spring compressor mountings  TXV  thermostatic expan   sion valve  expansion devices  and 1 2  and 3   in  electrical knockouts   2  Size 048 available as high static unit         WATER  OVERALL anra    CABINET    Cond   win  oi Depth Height BARAL    ELECTRICAL KNOCKOUTS a    DISCHARGE CONNECTION RETURN CONNECTION    Duct Flange Installed   0 10 in   Using Return Air Opening             50RHE    3  UNITS EARM oc    duit    Low Power  Supply sone Return Retai  rics Supply o   fege Depth Depth   Heig
41. g loop temperatures  drop below 4 4 C or where piping will be routed through areas  subject to freezing  antifreeze is needed     Alcohols and glycols are commonly used as antifreeze  agents  Freeze protection should be maintained to 8 3 K below  the lowest expected entering loop temperature  For example  if  the lowest expected entering loop temperature is    1 1 C  the  leaving loop temperature would be    5 6 to    3 9 C  Therefore  the  freeze protection should be at  9 4 C     1 1 C 8 3 C  94C         IMPORTANT  All alcohols should be pre mixed and  pumped from a reservoir outside of the building or    introduced under water level to prevent fuming        Calculate the total volume of fluid in the piping system  See  Table 11  Use the percentage by volume in Table 12 to deter   mine the amount of antifreeze to use  Antifreeze concentration  should be checked from a well mixed sample using a hydrome   ter to measure specific gravity    FREEZE PROTECTION SELECTION     The  1 1 C FP1  factory setting  water  should be used to avoid freeze damage  to the unit    Once antifreeze is selected  the JW3 jumper  FP1  should  be clipped on the control to select the low temperature  anti   freeze 13 F  set point to avoid nuisance faults     Table 11     Approximate Fluid Volume  L   per 30 m of Pipe       PIPE DIAMETER  in   VOLUME  I    Copper 1 15 5  1 25 24 2   1 5 34 8   Rubber Hose 1 14 7  Polyethylene 3 4 IPS SDR11 10 6  1 IPS SDR11 17 0   11 4 IPS SDR11 30 0   1 2 IPS SDR11 4
42. he transformers may be switched to  220 volt operation by switching the red  220 volt  wire with  the orange  240 volt  wire at the TB1 1 terminal for single   phase and TB1 3 for 3 phase         Unit Power Supply  See electrical table for  wire and breaker size       Fig  13     50RHE Typical Single Phase Line  Voltage Power Connection    PSC  PERMANENT SPLIT CAPACITOR  BLOWER SPEED CONNECT THE BLUE WIRE TO     SELECTION     All Water Source Heat Pumps are factory set H FOR HIGH SPEED FAN   to deliver rated airflow at nominal static  37 Pa  on medium MEOR low SPEED EAN TAN  speed  Where higher static is needed  high speed can be BLU   utilized  100 to 125 Pa   Low speed will deliver approximately fa    85  of rated airflow  25 Pa   The PSC blower fan speed can  be changed on all units by swapping wires connected to the  relay contacts that control the fan  See Table 4 and Fig  14     NOTE  Available airflow for all units is shown in Table 4     MEDIUM FACTORY SETTING       FAN MOTOR  Fig  14     50RHE Blower Speed Selection    Table 4     50RHE Blower Performance    BORE NOMINAL MINIMUM AIRFLOW  L s   AIRFLOW AIRFLOW External Static Pressure  Pa     UNIT  o        50   75   100   125  HI 133 123 112 89 78      006 81 61 MED 110 99 87 68          LO 98 90 75 60          HI 165 151 142 118 99      009 113 85 MED 160 146 127 113 94      LO 151 137 123 109 90              HI 170 165 151 137 123 109  012 140 104 MED 165 151 142 127 118      LO 146 137 127 118 104      HI 345 316 
43. ht                    006 012 22 4 43 1   11 3 aA Ea oe E HR 5 8 8 0 Ea 1 5 17 1 9 3 2 2  56 8   109 5   28 7 1 5 E Ea 14 7 20 3 3 8 43 4 23 6 5 6  015 024 22 4 43 1   17 3   2 4 E 0 6 3 5      10 2 EA 10 4 9 3 Ea 1 5 17 1 15 3 2 2  56 8   109 5   43 9   6 1  12 4 1 5 8 9 19 1 25 9 26 4 23 6 12 7   3 8 43 4 38 9 5 6  22 4 53 2   19 3   2 4   5 4  06 5 7 9 7 12 2 5 0  6 8  10 4 9 3 5 0   2 1 23 1 17 3 22  56 8   135 1   49 0   6 1   13 7 1 5 14 5 24 6 31 0 12 7   17 3   26 4 23 6 12 7   5 3 58 7 43 9 5 6  22 4 53 2   19 3   2 4 0 6 5 7 9 7 12 2 2 9  3 8  13 5 13 1 2 9   19 23 1 17 3 2 2  56 8   135 1   49 0   6 1 1 5 14 5 24 6 31 0 7 4 a 34 3 33 3 7 4   4 8 58 7 43 9 5 6              22 4 62 2   19 3   2 4   5 4  56 8   158 0   49 0   6 1  13 7  25 4 71 2   21 3   2 4 ae  64 5   180 8   54 1   6 1   1  NOTES     1  Condensate is 3 4 in  FPT copper    2  Horizontal unit shipped with filter bracket only  This bracket should be removed for return duct connection  front    3  Hanger kit is factory installed  Isolation grommets are provided    4  Right and left orientation is determined by looking at water connection side     13 5 13 1  9   1 9 32 1 17 3  34 3 33 3 4   48 81 5 43 9  13 6 13 3  8   2 9 36 1 19 3  34 5 33 8 14 7   7 4 91 7 49 0    NN  an  DN        0Oj 0  a    woja    060    oe  P  an  DN    LEFT RETURN RIGHT RETURN          Legend  CAP Control Access Panel 2  61cm  Service    elo ee Optional J 61em  CSP Compressor Service Panel ont Access    Access  Front i es BSP B
44. ications     An alternative method is to install a flow control device   These devices are typically an orifice of plastic material  designed to allow a specified flow rate that are mounted on the  outlet of the water control valve  Occasionally these valves  produce a velocity noise that can be reduced by applying some  back pressure  To accomplish this  slightly close the leaving  isolation valve of the well water setup        A WARNING    To avoid possible injury or death due to electrical shock   open the power supply disconnect switch and secure it in  an open position before flushing system     Table 9     Typical Unit Operating Pressures and Temperatures                                                                                HEATING                                                    ENTERING   water COOLING  WATER FLOW Suction   Discharge   Super   Sub    Water Temp   Air Temp   Suction   Discharge   Super   Sub    Water Tem Air  TEMP  C     i s per kw    Pressure   Pressure   heat   cooling Rise Drop  C    Pressure Pressure   heat   cooling   Drop  C  DS   Temp   EWT   kPa   kPa   C   C   C  DB  kPa   kPa   C   C  P Rise  C   225 254 269 314 14 22 7 11 12 13 12 14 102 117 499 556 7 9 1 2 4 5 8 11   1 14 22 0 7 9 12 14 1 7 9 1 2 3 4 9 12  14 22 6  9 6 12 14 5 6 7 9 1 2 3 9 12  0 027 225 254 374 463 7 11 6 10 11 13 11 14 150 179 538 628 6  9 1 3 6 7  10 222 251 359 425 7 11 5  9 7  8 11 14 158 185   6  9 1 3 4 5 13 17  219 248 344 413 7 11 4  8 4 7 11 14 164 194 
45. in Pans     Check condensate drain  pans for algae growth twice a year  If algae growth is apparent   consult a water treatment specialist for proper chemical treat   ment  Applying an algaecide every three months will typically  eliminate algae problems in most locations     Refrigerant System     Verify air and water flow rates  are at proper levels before servicing  To maintain sealed circuit   ry integrity  do not install service gauges unless unit operation  appears abnormal     Check to see that unit is within the superheat and subcool   ing temperature ranges shown in Table 16  If the unit is not  within these ranges  recover and reweigh in refrigerant charge     Condensate Drain Cleaning     Clean the drain line  and unit drain pan at the start of each cooling season  Check  flow by pouring water into drain  Be sure trap is filled to main   tain an air seal     Air Coil Cleaning     Remove dirt and debris from evap   orator coil as required by condition of the coil  Clean coil with  a stiff brush  vacuum cleaner  or compressed air  Use a fin  comb of the correct tooth spacing when straightening mashed  or bent coil fins     Condenser Cleaning     Water cooled condensers may  require cleaning of scale  water deposits  due to improperly  maintained closed loop water systems  Sludge build up may  need to be cleaned in an open water tower system due to  induced contaminants     Local water conditions may cause excessive fouling or  pitting of tubes  Condenser tubes should
46. indoor installation only     Operating Limits   ENVIRONMENT     This equipment is designed for indoor  installation ONLY  Extreme variations in temperature  humidi   ty and corrosive water or air will adversely affect the unit per   formance  reliability and service life     POWER SUPPLY     A voltage variation of   10  of name   plate utilization voltage is acceptable     UNIT STARTING CONDITIONS     Depending on the mod   el  units start and operate in an ambient temperature of 7 2 C  with entering air temperature at 4 4 C or 10 C  entering water  temperature at    6 7 C or 10 C and with both air and water at the  flow rates used    NOTE  These operating limits are not normal or continuous  operating conditions  Assume that such a start up is for the  purpose of bringing the building space up to occupancy tem   perature  See Table 7 for operating limits     A WARNING    When the disconnect switch is closed  high voltage is  present in some areas of the electrical panel  Exercise  caution when working with the energized equipment          Restore power to system     Turn thermostat fan position to ON  Blower should start     Balance airflow at registers     Adjust all valves to the full open position and turn on the  line power to all heat pump units   5  Operate unit in the cooling cycle  Refer to Table 7 for unit  operating limits   NOTE  Three factors determine the operating limits of a unit    1  entering air temperature   2  water temperature and  3   ambient temperatur
47. ing support is removed     Blower speed is on correct setting      Air filter is clean and in position      Service access panels are in place       Return air temperature is between 4 4 to 26 7 C heating  and 10 to 43 3 C cooling       Air coil is clean     Control field selected settings are correct          TODD RARUN    Aquazone  C     See Note l    eS Se  AUN    Low Voltage         n       I    NOTE  Low voltage connector may be removed for easy installation   Fig  15     Low Voltage Field Wiring    men  eN       jan         16    AIR COIL     To obtain maximum performance  clean the air  coil before starting the unit  A ten percent solution of dish   washing detergent and water is recommended for both sides of  the coil  Rinse thoroughly with water     FIELD SELECTABLE INPUTS    Jumpers and DIP  dual in line package  switches on the  control board are used to customize unit operation and can be  configured in the field     IMPORTANT  Jumpers and DIP switches should only  be clipped when power to control board has been turned    off     C Control Jumper Settings  See Fig  9 and 10     WATER COIL FREEZE PROTECTION  FP1  LIMIT  SETTING     Select jumper 3   JW3 FP1 Low Temp  to  choose FP1 limit of    12 2 C or  1 1 C  To select    1 1 C as the  limit  DO NOT clip the jumper  To select    12 2 C as the limit   clip the jumper    AIR COIL FREEZE PROTECTION  FP2  LIMIT SET   TING     Select jumper 2  JW2 FP2 Low Temp  to choose  FP2 limit of    12 2 C or    1 1 C  To select 
48. inutes of reverse operation  the scroll com   pressor internal overload protection will open  thus activating  the unit lockout  This requires a manual reset  To reset  turn the  thermostat on and then off     NOTE  There is a 5 minute time delay before the compressor  will start     Unit Start Up Cooling Mode    1  Adjust the unit thermostat to the warmest position   Slowly reduce the thermostat position until the compres   sor activates     2  Check for cool air delivery at unit grille a few minutes  after the unit has begun to operate     3  Verify that the compressor is on and that the water flow  rate is correct by measuring pressure drop through the  heat exchanger using P T plugs  See Table 8  Check the  elevation and cleanliness of the condensate lines  any  dripping could be a sign of a blocked line  Be sure the  condensate trap includes a water seal     4  Check the temperature of both supply and discharge wa   ter  Compare to Table 9  If temperature is within range   proceed  If temperature is outside the range  check the  cooling refrigerant pressures in Table 9    5  Check air temperature drop across the coil when com   pressor is operating  Air temperature drop should be  between 8 3 and 13 9     Table 8     Water Temperature Change  Through Heat Exchanger  HEATING    COOLING  RISE  C    DROP  C       Min   Max   Min   Max                 WATER FLOW RATE  I s         For Closed Loop  Ground  Source or Cooling Boiler  Systems at 0 054 I s per kW    For Open Loop 
49. its with 2 compressors and 2 D controls  or in master slave  applications  In master slave applications  each compressor and  fan will stage according to its switch 2 setting  If switch is set to  stage 2  the compressor will have a 3 second delay before ener   gizing during stage 2 demand    NOTE  If DIP switch is set for stage 2  the alarm relay will not  cycle during Test mode     Heating Cooling Thermostat Type     Switch 3 provides selec   tion of thermostat type  Heat pump or heat cool thermostats  can be selected  Select OFF for heat cool thermostats  When in  heat cool mode  Y1 is used for cooling stage 1  Y2 is used for  cooling stage 2  W1 is used for heating stage 1 and O W2 is  used for heating stage 2  Select ON for heat pump applications   In heat pump mode  Y1 used is for compressor stage 1  Y2 is  used for compressor stage 2  W1 is used for heating stage 3 or  emergency heat  and O W2 is used for RV  heating or cooling   depending upon switch 4 setting     O B Thermostat Type     Switch 4 provides selection for heat  pump O B thermostats  O is cooling output  B is heating out   put  Select ON for heat pumps with O output  Select OFF for  heat pumps with B output     Dehumidification Fan Mode     Switch 5 provides selection  of normal or dehumidification fan mode  Select OFF for dehu   midification mode  The fan speed relay will remain OFF dur   ing cooling stage 2  Select ON for normal mode  The fan speed  relay will turn on during cooling stage 2 in normal mo
50. lative humidity is no greater than  75     e Provide sufficient space for water  electrical and duct  connections    e Locate unit in an area that allows easy access and  removal of filter and access panels    e Allow enough space for service personnel to perform  maintenance    e Return air must be able to freely enter the space if unit  needs to be installed in a confined area such as a closet    NOTE  Correct placement of the horizontal unit can play an  important part in minimizing sound problems  Since duct   work is normally applied to these units  the unit can be  placed so that the principal sound emission is outside the oc   cupied space in sound critical applications  A fire damper  may be required by the local code if a fire wall is penetrated     FIELD CONVERSION OF DISCHARGE AIR     The dis   charge air of the SORHE horizontal units can be converted  between side and back discharge in the field  The conversion  process is the same for right and left return configurations  See  Fig  3 and 4     NOTE  It is not possible to convert return air between left or  right return models in the field due to refrigerant piping  changes     Preparation     The unit should be on the ground in a well lit  area for conversion  Hung units should be taken down to  ground level before converting     Side to Back Discharge Conversion    1  Remove screws to free the top and discharge panels  See  Fig  3     2  Remove the access panel and set aside     3  Lift the discharge panel from 
51. le pump is running    For average scale deposit  allow solution to remain in con   denser overnight  For heavy scale deposit  allow 24 hours   Drain condenser and flush with clean water  Follow acid manu   facturer   s instructions     Checking System Charge     Units are shipped with  full operating charge  If recharging is necessary    1  Insert thermometer bulb in insulating rubber sleeve on  liquid line near filter drier  Use a digital thermometer for  all temperature measurements  DO NOT use a mercury  or dial type thermometer    2  Connect pressure gage to discharge line near compressor     3  After unit conditions have stabilized  read head pressure  on discharge line gage   NOTE  Operate unit a minimum of 15 minutes before  checking charge    4  From standard field supplied Pressure Temperature chart  for R 407C  find equivalent bubble point temperature                 FILL CONDENSER WITH  CLEANING SOLUTION  DO  NOT ADD SOLUTION  MORE RAPIDLY THAN  VENT CAN EXHAUST  GASES CAUSED BY    CHEMICAL ACTION  FUNNEL    VENT    PIPE 5    APPROX    3    TO 4     CONDENSER    Fig  18     Gravity Flow Method    GAS VENT    gt      PRIMING  SONN  GLOBE    j        U  a   lt   D                 MP SS  SUPPORT        van  TANK  K REMOVE WATER  REGULATING VALVE  FINE MESH RETURN  SCREEN       Fig  19     Forced Circulation Method    5  Read liquid line temperature on thermometer  then  subtract from bubble point temperature  The difference  equals subcooling temperature     6  Compar
52. ll continue normal  operation    NOTE  If 3 consecutive faults occur without satisfying the  thermostat input call to terminal Y  the control will go into  lockout mode  The last fault causing the lockout is stored in  memory and can be viewed by entering Test mode     Aquazone    Deluxe D Control LED Indica   tors     There are 3 LED indicators on the D Control     STATUS LED     Status LED indicates the current status or  mode of the D control  The Status LED light is green     TEST LED     Test LED will be activated any time the D  control is in test mode  The Test LED light is yellow     FAULT LED     Fault LED light is red  The fault LED will  always flash a code representing the last fault in memory  If  there is no fault in memory  the fault LED will flash code 1 on  the and appear as 1 fast flash alternating with a 10 second  pause  See Table 15     SERVICE    Perform the procedures outlined below periodically  as  indicated     IMPORTANT  When a compressor is removed from this  unit  system refrigerant circuit oil will remain in the com     pressor  To avoid leakage of compressor oil  the refrigerant  lines of the compressor must be sealed after it is removed        IMPORTANT  All refrigerant discharged from this unit  must be recovered without exception  Technicians must fol   low industry accepted guidelines and all local  state and fed   eral statutes for the recovery and disposal of refrigerants     IMPORTANT  To avoid the release of refrigerant into the  atmosph
53. ll repeat continually until the fault is  cleared     Table 14     C Control LED Code and  Fault Descriptions  LED    CODE FAULT DESCRIPTION  1 No fault in memory There has been no fault since  the last power down to power up  sequence    High Pressure Switch HP Open Instantly  3 Low Pressure Switch LP open for 30 continuous sec   onds before or during a call   bypassed for first 60 seconds   4 Freeze Protection Coax FP1 below Temp limit for 30 con      FP1 tinuous seconds  bypassed for  first 60 seconds of operation   5 Freeze Protection Air Coil   FP2 below Temp limit for 30 con       FP2 tinuous seconds  bypassed for  first 60 seconds of operation   6 Condensate overflow Sense overflow  grounded  for  30 continuous seconds  7 Over Under Voltage  R  power supply is  lt 19VAC or   Autoreset    Shutdown  gt 30VAC  8 PM Warning Performance Monitor Warning  has occurred   9 FP1 and FP2 Thermistors   FP1 temperature is higher than  are swapped FP2 in heating test mode  or FP2    temperature is higher than FP1  in cooling test mode     N       LEGEND  FP     Freeze Protection  HP     High Pressure  LED     Light Emitting Diode  LP     Low Pressure  PM     Performance Monitor    Retry Mode     In Retry mode  the status LED will start to  flash slowly to signal that the control is trying to recover from  an input fault  The control will stage off the outputs and try to  again satisfy the thermostat used to terminal Y  Once the ther   mostat input calls are satisfied  the control wi
54. lower Service Panel                                                                                                                                                                                                                                                                                                                                                                                                                            ASP Alternate Service Panel Optional 2     61cm   Service Access    NS Left Return Power Supply Right Return  we    lt  lt  3 4    Knockout  wg 1 2  N Knockout  3 25   82 6mm   826mm   Low Voltage Ko  1 2    Knockout      o  k   CAP  A J O   7     Discharge  a O  e e i  Cond t  pigs e oy  ERT C Condensate  7 Front View Sieber    Discharge  Unit Hanger Detail E R  Q p  3 3  B a Blower BSP    slic cls Outlet o W  Blower    A S  Ol  Outlet   Ys Z 2  Jl z x z a     g D    Q     A  A   Left Return Back Discharge x Right Return Back Discharge  P M        N o  Blower BSP     p  ASP BSP 9  Outlet fe  Blower CSP  Outlet oO  N  Front L Front  Left Return Right Discharge Hm  Right Return Left Discharge  1 Air Coil  v U Ss Air Coil  27 9mml  S u  V   P o ie  o  cT CSP       ASP T  Front Front  B  B  Left Return Left View   Right Return Right View    Air Coil Opening Air Coil Opening      Note  Shaded areas are recommended service areas  not required     Fig  1     50RHE Dimensional Data    ReturnLoop               3 8    threaded rods     by others  ee  Filter Acce
55. mperature    Connect boiler drains and other valves using a    T    con   nector to allow acid flushing for the heat exchanger    Do not overtighten connections    Route piping to avoid service access areas to unit    Use PVC SCH80 or copper piping material     NOTE  PVC SCH40 should not be used due to system high  pressure and temperature extremes        Water Flow Pressure  Control Regulator Tank  Valve  me  e Water Out  Water In  e Ns  lt 5 From Pump  e i ve A  D  es  q KS  k  Shut Off  iS    SS e  Valve     e N  cnc  C2 Strainer     Field Installed Accessory   gt    amp   16 to 20 mesh recommended for    filter sediment   Boiler  n Drains  Pressure      Temperature    Plugs    Fig  8     Typical Ground Water Piping Installation    Water Supply and Quantity     Check water supply  Water  supply should be plentiful and of good quality  See Table 2 for  water quality guidelines           IMPORTANT  Failure to comply with the above required  water quality and quantity limitations and the closed   system application design requirements may cause damage  to the tube in tube heat exchanger that is not the responsi   bility of the manufacturer     In all applications  the quality of the water circulated  through the heat exchanger must fall within the ranges listed in  the Water Quality Guidelines table  Consult a local water treat   ment firm  independent testing facility  or local water authority  for specific recommendations to maintain water quality within  the published limi
56. n R and C on controller   X Water temperature out of Bring water temperature within design parameters   range in cooling  Dirty air coil     construction dust etc     x   X__ Overcharged with refrigerant  Check superheat subcooling vs typical operating condition Table 9   Compressor pump down at  Check charge and start up water flow   start up  X Improper freeze protect set   Clip JW2 jumper for antifreeze     12 2 C  use   ting   1 1 C vs  12 2 C   X Reduced or no airflow in Check for dirty air filter and clean or replace   cooling  Bad thermistor Check temperature and impedance correlation   X Poor drainage Check for piping slope away from unit   Check slope of unit toward outlet   Poor venting  Check vent location   X X Over voltage Check power supply voltage and 24 vac before and during operation   Check 24 vac and unit transformer tap for correct power supply voltage   X FP1 temperature is higher  Swap FP1 and FP2 thermistors   than FP2 temperature   i ae ee  eee Compressor overload Check and replace if necessary   rf x   x   Unit in    Test Mode  Reset power or wait 20 minutes for auto exit   fr x   x   Thermostat position Ensure thermostat set for heating or cooling operation   Thermostat wiring Check Y and W wiring at heat pump  Jumper Y and R for compressor  operation in Test mode     x  x            x  x    26    FAULT  Only Compressor Runs    Unit Does Not Operate in  Cooling    Insufficient Capacity   Not Cooling or Heating  Properly    High Head Pressure    Low S
57. n working on air conditioning equipment  observe precau   D Control DIP Switches          press tee ees 17 tions in the literature  tags and labels attached to the unit  and  D Control Accessory Relay Configurations       18 other safety precautions that may apply   Water Valve  Slow Opening                      18 Improper installation  adjustment  alteration  service  main   Outdoor Air Damper  OAD                      18 i prop sacJusiment  ax eee  enance  or use can cause explosion  fire  electrical shock or  START UP eRe 18 21 other conditions which may cause personal injury or property  Operating Limits          Pee 18 damage  Consult a qualified installer  service agency  or your  Scroll Compressor Rotation                      19 distributor or branch for information or assistance  The  Unit Start Up Cooling Mode                      19 qualified installer or agency must use factory authorized kits or  Unit Start Up Heating Mode                       19 accessories when modifying this product  Refer to the individ   Flow Regulation                       see e ee eee 19 ual instructions packaged with the kits or accessories when  Flushing relies E coed Pee wet Ott ad ea T case tart 20 installing   Antifreeze    estes ccd oe dhe oh te eee ooh 21  Cooling Tower Boiler Systems                    21    Manufacturer reserves the right to discontinue  or change at any time  specifications or designs without notice and without incurring obligations     Catalog No  005 00042  
58. nation up to 24 hours after sampling  A low pH and high  alkalinity cause system problems  even when both values are within ranges shown  The term pH refers to the  acidity  basicity  or neutrality of the water supply  Below 7 0  the water is considered to be acidic  Above 7 0   water is considered to be basic  Neutral water contains a pH of 7 0     NOTE  Hardness in mg l is equivalent to ppm     POWER SUPPLY   EARTH  GRD    e264    REFER TO  DATA PLATE  USE COPPER  CONDUCTORS  ONLY    SEE NOTE 3  TRANS    COMPONENT LOCATION    CR  AN  a    N  NEUTRAL      START ASSIST          E        WHEN NEEDED   BLU        RED        2 4  BR yer CAPACITOR                   3 AIR FLOW SETTINGS   FCTRY SETTING   MED     SEE NOTE 8  G Y                                                                                                                                                                                                                                                    ca 7 SEE  Ka NOTE 7   9 0   Loo    ae  Pl   eee    TEST PINS    tet Fe   SEE   COMPRESS       RED  NOTE 5 Lo RELAY   ep ed HP  TYPICAL    TSTAT   COMPR    NOTE 4 aa  amp  _ Loc  SIZES  015 036 YO fae es BRN  laws DIP SWITCH   GRY  SFE NOTE 4  FP1  LOW TEMP ary          o COOLING   awe E  o v    TXV UNITS   FAN cap  TuBE VIOS  GO   LOW TEMP UNITS  OR vio       FP2  24 VAC OFF  nO COMMON q see f RVS  cO i status    ORG  ALARM    LO FH   uwi  LED   NOT USED  i ejs d    YEL         _ co  SEE NOTE 6 FOR   CXM wma  DRY ALARM 
59. nd via microprocessor board stand     offs and screws to control box   Ground available from top two  standoffs as shown        Blower motor is factory wired for medium and high speeds  For    any other combination of speeds  at the motor attach black wire  to the higher of the two desired speed taps  and the blue wire to  the lower of the two desired speed taps     Fig  11     Typical Aquazone    Deluxe D Control Wiring  Single Phase Unit     12    COMPONENT LOCATION                   DATA PLATE  USE COPPER  CONDUCTORS   ONLY                      yer CB ver  gs                   EARTH  GND      POWER SUPPLY   N  NEUTRAL      REFER TO                                                                                                                                                                                                                                                                                        24V  BLU     SEE NOTE 8   240V   BRN  BRN  SEE RED  NOTE 7 RED SEE  TYPICAL HEAT   mae  SS   FAN ENABLE  PUMP T STAT   CoM CONT  SEE NOTE 5 i con  Y SL COMPR  1 nog  2  COOLING 2  OST  FAN 2  SSF z4vac 5 OPROCESS    MICROPROCESSOR  lt  HWTS  sd COMMON 8 CONTROL LOGIC BLK aay  K 7 r  xi    ALARM 3 e A   Bik  SEE NOTE 6 FOR SaN A OC  DRY CONTACT SEE NOTE 4  FOR ALARM status    _   GRY SE p  y  TEST Y  vio NITS  FAULT   B  VIO  FP2    TEST  PINS co              e 2                         SEE  PIELEN LOW NOTE4                                  UNIT STAG        Z  7  7  O     
60. nt   Low refrigerant charge Check superheat and subcooling Table 9     Restricted metering device _  Check superheat and subcooling Table 9  Replace   O0    x   Defective reversing valve Perform RV touch test     X X Thermostat improperly Check location and for air drafts behind thermostat   located  X X Unit undersized Recheck loads and sizing check sensible cooling load and heat pump  capacity   X X Scaling in water heat Perform scaling check and clean if necessary   exchanger    Inlet water too hot or cold _  Check load  loop sizing  loop backfill  ground moisture     X Reduced or no airflow in Check for dirty air filter and clean or replace   al heating Check fan motor operation and airflow restrictions   External static too high  Check blower Table 4   X Reduced or no water flow in   Check pump operation or valve operation setting   rn Check water flow  adjust to proper flow rate  See Table 8      x inlet watertoo hot  Check load  loop sizing  loop backfill  ground moisture     X Air temperature out of range   Bring return air temperature within design parameters   in heating  X Scaling in water heat Perform scaling check and clean if necessary   exchanger    Unit overcharged Check superheat and subcooling  Reweigh in charge     X X Non condensables in Vacuum system and reweigh in charge   system    Restricted metering device _  Check superheat and subcooling per Table 9  Replace     X Reduced water flow in Check pump operation or water valve operation setting   heating 
61. ntrol  allows the field selection of source fluid freeze protection points  through jumpers  The factory setting of jumper JW3  FP1  is set ae  for water at    1 1 C  In earth loop applications  jumper JW3   should be clipped to change the setting to    10 6 C when using   antifreeze in colder earth loop applications  See Fig  16     AIR COIL FREEZE PROTECTION     The air coil freeze  protection jumper JW2  FP2  is factory set for    1 1 C and Lc G  should not need adjusting  Suwi arz ony    TED    ACCESSORY CONNECTIONS     Terminal A on the control   is provided to control accessory devices such as water valves    electronic air cleaners  humidifiers  etc  This signal operates CLIP   with the compressor terminal  See Fig  17  Refer to the specific FOR DRY  agen     CONTACT   unit wiring schematic for details     NOTE  The A terminal should only be used with 24 volt AQUAZONE CONTROL  C Control Shown   signals     not line voltage signals     WATER SOLENOID VALVES     Water solenoid valves may Fig  16     Typical Aquazone Control Board  be used on primary secondary pump and ground water installa  Jumper Locations   tions  A typical well water control valve wiring approach    which can limit waste water in a lockout condition  is shown in   Fig  17  A slow closing valve may be required to prevent water Terminal Strip P2  hammer  When using a slow closing valve  consider special   wiring conditions  The valve takes approximately 60 seconds  c  O  to open  very little water will 
62. onfigura   tion  the relay will be ON if the NSB input is connected to  ground C     NOTE  If there are no relays configured for digital NSB  then  the NSB and OVR inputs are automatically configured for  mechanical operation     MECHANICAL NIGHT SET BACK     When NSB input is  connected to ground C  all thermostat inputs are ignored  A  thermostat set back heating call will then be connected to the  OVR input  If OVR input becomes active  then the D control  will enter Night Low Limit  NLL  staged heating mode  The  NLL staged heating mode will then provide heating during the  NSB period     Water Valve  Slow Opening      If relay is config   ured for Water Valve  slow opening   the relay will start 60 sec   onds prior to starting compressor relay     Outdoor Air Damper  OAD      If relay is configured  for OAD  the relay will normally be ON any time the Fan  Enable relay is energized  The relay will not start for 30 min   utes following a return to normal mode from NSB  when NSB  is no longer connected to ground C  After 30 minutes  the relay  will start if the Fan Enable is set to ON          A CAUTION    To avoid equipment damage  DO NOT leave system filled  in a building without heat during the winter unless anti     freeze is added to system water  Condenser coils never  fully drain by themselves and will freeze unless winterized  with antifreeze        START UP    Use the procedure outlined below to initiate proper unit  start up   NOTE  This equipment is designed for 
63. onnection     7  Provide adequate clearance for filter replacement and  drain pan cleaning  Do not allow piping  conduit  etc  to  block filter access     8  Provide sufficient access to allow maintenance and  servicing of the fan and fan motor  compressor and coils   Removal of the entire unit from the closet should not be  necessary     9  Provide an unobstructed path to the unit within the closet  or mechanical room  Space should be sufficient to allow  removal of unit if necessary     10  Provide ready access to water valves and fittings  and  screwdriver access to unit side panels  discharge collar   and all electrical connections     11  Where access to side panels is limited  pre removal of the  control box side mounting screws may be necessary for  future servicing     STORAGE     If the equipment is not needed immediately at  the jobsite  it should be left in its shipping carton and stored in a  clean  dry area of the building or in a warehouse  Units must be  stored in an upright position at all times  If carton stacking is  necessary  stack units a maximum of 3 high  Do not remove  any equipment from its shipping package until it is needed for  installation     PROTECTION     Once the units are properly positioned on  the jobsite  cover them with either a shipping carton  viny  film   or an equivalent protective covering  Cap open ends of pipes  stored on the jobsite  This precaution is especially important in  areas where painting  plastering  or spraying of firep
64. or dual  compressor application  all compressor relays and related func   tions will track with their associated DIP switch 2 on S1     COOLING STAGE 2     In Cooling Stage 2 mode  the Fan  Enable  compressor and RV relays remain on  The Fan Speed  relay is turned on immediately and turned off immediately  once the Cooling Stage 2 demand is removed  The control re   verts to Cooling Stage 1 mode  If there is a master slave or dual  compressor application  all compressor relays and related func   tions will track with their associated DIP switch 2 on S1     NIGHT LOW LIMIT  NLL  STAGED HEATING     In NLL  staged Heating mode  the override  OVR  input becomes ac   tive and is recognized as a call for heating and the control will  immediately go into a Heating Stage 1 mode  With an addition   al 30 minutes of NLL demand  the control will go into Heating  Stage 2 mode  With another additional 30 minutes of NLL  demand  the control will go into Heating Stage 3 mode     SYSTEM TEST    System testing provides the ability to check the control  operation  The control enters a 20 minute Test mode by  momentarily shorting the test pins  see Fig  9 12   All time  delays are reduced by a factor of 15     Test Mode     To enter Test mode on C or D controls  cycle  the power 3 times within 60 seconds  The LED  light emitting  diode  will flash a code representing the last fault when enter   ing the Test mode  The alarm relay will also power on and off  during Test mode  See Tables 13 and 14
65. ppropriate Code  Flashing Code2           Flash Last Fault Code in Memory        ALARM RELAY    Cycle  closed 5 sec   open 25 sec          Open    ESD Flashing Code3          Flash Last Fault Code in Memory        Invalid T stat Inputs  No Fault in Memory    Flashing Code4           Flash Last Fault Code in Memory      Flashing Code 1 Open    HP Fault Slow Flash Flashing Code 2 Open  LP Fault Slow Flash Flashing Code 3 Open    FP1 Fault  FP2 Fault    Slow Flash Flashing Code 4 Open  Slow Flash Flashing Code 5 Open    CO Fault Slow Flash Flashing Code 6 Open    Over Under Voltage  HP Lockout  LP Lockout  FP1 Lockout  FP2 Lockout    CO Lockout  LEGEND  CO     Condensate Overflow  ESD     Emergency Shutdown  FP     Freeze Protection  HP     High Pressure  LP     Low Pressure  PM     Performance Monitor    Open  closed after 15 minutes   Closed  Closed  Closed  Closed  Closed    NOTES      If there is no fault in memory  the Fault LED will flash code 1      Codes will be displayed with a 10 second Fault LED pause      Slow flash is 1 flash every 2 seconds      Fast flash is 2 flashes every 1 second      EXAMPLE     Flashing Code 2    is represented by 2 fast flashes  followed by a 10 second pause  This sequence will repeat contin   ually until the fault is cleared     akon       A CAUTION    To avoid fouled machinery and extensive unit clean up   DO NOT operate units without filters in place  DO NOT  use equipment as a temporary heat source during  construction     Condensate Dra
66. roof mate   rial  etc  is not yet complete  Foreign material that accumulates  within the units can prevent proper start up and necessitate  costly clean up operations    Before installing any of the system components  be sure to  examine each pipe  fitting  and valve  and remove any dirt or  foreign material found in or on these components     3  Do not remove the packaging until the unit is ready for  A CAUTION installation     4  Verify that the refrigerant tubing is free of kinks or dents   and that it does not touch other unit components        DO NOT store or install units in corrosive environments or  in locations subject to temperature or humidity extremes   e g   attics  garages  rooftops  etc    Corrosive conditions 5  Inspect all electrical connections  Be sure connections are  and high temperature or humidity can significantly reduce clean and tight at the terminals    performance  reliability  and service life  Always move 6  Compressors are internally isolated  Compressors  units in an upright position  Tilting units on their sides may equipped with external spring vibration isolators must  cause equipment damage  have bolts loosened and shipping clamps removed     7  Remove any blower support cardboard from inlet of the    INSPECT UNIT     To prepare the unit for installation  com  blower   plete the procedures listed below  8  Locate and verify any accessory kit located in compressor   1  Compare the electrical data on the unit nameplate with section   orderin
67. ser Cleaning                      000005  24  Step 7     Piping Connections                      8 Checking System Charge                         24    WATER LOOP APPLICATIONS Refrigerant Charging                         05  25    N a ts ROR Air Coil Fan Motor Removal                      25  Step 8     Electrical Wiring                         9 Ree OOnNS BS Fc ak EES Aree Cg os    Suey ee ae Control Sensors                   0   0 0 2 eee  25  e 220 VOLT OPERATION START UP CHECKLIST ee ed CL 1  CL 2  St ESC BLOWER OED SELECTION IMPORTANT  Read the entire instruction manual before  ep 9     Low Voltage Wiring                     16 cari ne installation  e THERMOSTAT CONNECTIONS g i  e WATER FREEZE PROTECTION  e AIR COIL FREEZE PROTECTION SAFETY CONSIDERATIONS    ae ao Lote Installation and servicing of air conditioning equipment can  be hazardous due to system pressure and electrical compo   PRE START UP                      0  0 eee eee 16 17 nents  Only trained and qualified service personnel should  System Checkout                          00  16 install  repair  or service air conditioning equipment   FIELD SELECTABLE INPUTS EE TE asc sie  eG 17 18 Untrained personnel can perform basic maintenance func   C Control Jumper Settings                      17 tions of cleaning coils and filters and replacing filters  All other  C Control DIP Switches aha A nr 17 operations should be performed by trained service personnel   D Control Jum per Settings                      17 Whe
68. side of unit and rotate it to  back using care not to damage blower wiring        4  Check blower wire routing and connections for excessive  tension or contact with sheet metal edges  Re route if  necessary    5  Check refrigerant tubing for contact with other compo   nents  Adjust if necessary    6  Reinstall top panel using screws set aside in Step 1   NOTE  Location for some screws at bottom of discharge panel  may have to be changed    7  Manually spin fan wheel to check for obstructions    Adjust for any obstruction found    8  Replace access panel    Back to Side Discharge Conversion     Follow instructions    above for Side to Back Discharge Conversion  noting the  panels would be reversed           Move to Side    Replace Screws        Return Air    Drain    Back Discharge Discharge Air    Fig  3     Conversion Left Return   Side Discharge to Back Discharge    Water  Connection End        Return Air    LJ       b  Side Discharge Water    Connection End        Back Disch  Discharge Air ack Discharge    Fig  4     Conversion Right Return   Side Discharge to Back Discharge    Step 4     Mounting the Unit     Horizontal units  should be mounted using the factory installed hangers  Proper  attachment of hanging rods to building structure is critical for  safety  See Fig  2 and 5  Rod attachments must be able to sup   port the weight of the unit  See Table 1 for unit operating  weights     Step 5     Duct System     Size the duct system to han   dle the design airflow quie
69. ss    Return Air   Ductwork  not shown          Supply Loop  Water In         Water Out           Thermostat  Wiring         Field supplied transition to  minimize pressure loss           Power Wiring Balancing Valve  Field  installed and calibrated    accessory            Field supplied  stainless steel  braid hose   with integral     J    swivel    Supply Air              Low Pressure Drop Water  Control Valve  optional    field installed accessory        Flexible    Insulated supply duct with Connection  at least one 90 degree elbow Field Supplied Unit Power d    to reduce air noise Electric Heat Disconnect   field supplied   if applicable                    A Water Out    Water In    Ball Valve with optional  integral P T plug  typical for supply  and return piping     Unit Hanger                3 8    Threaded  Rod  by others        Vibration Isolator   white compressor end   and red blower end   size 042 070     by others     Double Hex Nuts   by others     50RHR  RHS  Install screw as shown  Sizes 042 060  Optional on smaller sizes             50RHC  Screw must only be    1 2    long to Integral hanger support   prevent damage pre attached in factory    UNIT HANGER ISOLATION DETAIL    Fig  2     Typical Installation     50RHE Units    Step 3     Unit Location     The following guidelines  should be considered when choosing a location for a WSHP  unit     e Units are for indoor use only    e Locate in areas where ambient temperatures are between  4 4 C and 37 8 C and re
70. th construction  dirt and debris which may cause system damage     Step 2     Check Unit     Upon receipt of shipment at  the jobsite  carefully check the shipment against the bill of  lading  Make sure all units have been received  Inspect the car   ton or crating of each unit  and inspect each unit for damage   Ensure the shipping company makes proper notation of any  shortages or damage on all copies of the freight bill  Concealed  damage not discovered during unloading must be reported to  the shipping company within 15 days of receipt of shipment     NOTE  It is the responsibility of the purchaser to file all  necessary claims with the shipping company     1  Verify unit is correct model for entering water tempera   ture of job     2  Be sure that the location chosen for unit installation pro   vides ambient temperatures maintained above freezing   Well water applications are especially susceptible to  freezing     3  Be sure the installation location is isolated from sleeping  areas  private offices and other acoustically sensitive  spaces     NOTE  A sound control accessory package may be used  to help eliminate sound in sensitive spaces     4  Check local codes to be sure a secondary drain pan is not  required under the unit     5  Be sure unit is mounted at a height sufficient to provide  an adequate slope of the condensate lines  If an appropri   ate slope cannot be achieved  a field supplied condensate  pump may be required    6  Provide sufficient space for duct c
71. tly     NOTE  Depending on the unit  the fan wheel may have a ship   ping support installed at the factory  This must be removed  before operating unit     SOUND ATTENUATION     To eliminate the transfer of  vibration to the duct system  a flexible connector is recom   mended for both discharge and return air duct connections on  metal duct systems  The supply and return plenums should  include internal duct liner of fiberglass or be made of duct  board construction to maximize sound attenuation of the  blower  Installing the WSHP unit to uninsulated ductwork in an  unconditioned space is not recommended since it will sweat  and adversely affect the unit   s performance     To reduce air noise  at least one 90 degree elbow could be  included in the supply and return air ducts  provided system  performance is not adversely impacted  The blower speed can  also be changed in the field to reduce air noise or excessive air   flow  provided system performance is not adversely impacted     EXISTING DUCT SYSTEM     If the unit is connected to  existing ductwork  consider the following     e Verify that the existing ducts have the proper capacity to  handle the unit airflow  If the ductwork is too small   install larger ductwork    e Check existing ductwork for leaks and repair as  necessary     NOTE  Local codes may require ventilation air to enter the  space for proper indoor air quality  Hard duct ventilation may  be required for the ventilating air supply  If hard ducted venti   l
72. trical hookup   The installing  or electrical  contractor must make the field  connections when using field supplied disconnect     Operating voltage must be the same voltage and phase as  shown in Electrical Data shown in Table 3     Make all final electrical connections with a length of flexi   ble conduit to minimize vibration and sound transmission to  the building     Table 2     Water Quality Guidelines    CONDITION ACCEPTABLE LEVEL  pH 7 to 9 range for copper  Cupronickel may be used in the 5 to 9 range   Total Calcium and magnesium carbonate should not exceed 350 ppm   Hardness    Iron Oxides Less than 1 ppm   Iron Bacteria   No level allowable        Corrosion  Max Allowable Level Coaxial Metal  Ammonia  Ammonium Hydroxide 0 5 ppm Cu  Ammonium Chloride  Ammonium Nitrate 0 5 ppm Cu  Ammonium Sulfate 0 5 ppm Cu  Chlorine Chlorides 0 5 ppm CuNi  Hydrogen Sulfidet None Allowable     Brackish Use Cupronickel heat exchanger when concentrations of calcium or sodium chloride are    greater than 125 ppm are present   Seawater is approximately 25 000 ppm       If the concentration of these corrosives exceeds the maximum allowable level  then the potential for serious cor   rosion problems exists    tSulfides in the water quickly oxidize when exposed to air  requiring that no agitation occur as the sample is  taken  Unless tested immediately at the site  the sample will require stabilization with a few drops of one Molar  zinc acetate solution  allowing accurate sulfide determi
73. ts     GROUND LOOP APPLICATIONS     Temperatures between      4 to 43 C and a liquid flow rate of 0 040 to 0 054 I s per kW of   cooling capacity is recommended  In addition to complying   with any applicable codes  consider the following for system   piping    e Limit piping materials to only polyethylene fusion in the  buried sections of the loop    e Do not use galvanized or steel fittings at any time due to  corrosion    e Avoid all plastic to metal threaded fittings due to the  potential to leak  Use a flange fitted substitute    e Do not overtighten connections    e Route piping to avoid service access areas to unit    e Use pressure temperature  P T  plugs to measure flow of  pressure drop     Step 8     Electrical Wiring    A WARNING    To avoid possible injury or death due to electrical shock   open the power supply disconnect switch and secure it in  an open position during installation     A CAUTION    Use only copper conductors for field installed electrical  wiring  Unit terminals are not designed to accept other  types of conductors        All field installed wiring  including the electrical ground   MUST comply with applicable local  national and regional  codes     Refer to unit wiring diagrams Fig  9 12 for a schematic of  the field connections  which must be made by the installing  or  electrical  contractor  Refer to Electrical Data for fuse sizes     Consult the unit wiring diagram located on the inside of the  compressor access panel to ensure proper elec
74. uction Pressure    Low Discharge Air  Temperature in Heating    High Humidity    LEGEND  RV     Reversing Valve    Table 16     Troubleshooting  cont     HEATING   COOLING POSSIBLE CAUSE SOLUTION  Check G wiring at heat pump  Jumper G and R for fan operation     X X Fan motor relay Jumper G and R for fan operation  Check for line voltage across BR  contacts   Check fan power enable relay operation  if present    Check for line voltage at motor  Check capacitor     X X Thermostat wiring Check Y and W wiring at heat pump  Jumper Y and R for compressor  operation in Test mode     X Reversing valve Set for cooling demand and check 24 vac on RV coil and at control   If RV is stuck  run high pressure up by reducing water flow and while  operating  engage and disengage RV coil voltage to push valve         x  Thermostat setup Check for  O  RV setup not  B        x  Thermostat wiring Check O wiring at heat pump  Jumper O and R for RV coil  Click    Dirty filter Replace or clean     X Reduced or no airflow in Check for dirty air filter and clean or replace   Check fan motor operation and airflow restrictions   External static too high  Check blower Table 4   X Reduced or no airflow in Check for dirty air filter and clean or replace   Check fan motor operation and airflow restrictions   External static too high  Check blower Table 4     X X Leaky ductwork Check supply and return air temperatures at the unit and at distant duct  registers if significantly different  duct leaks are prese
75. ystem to  avoid galvanic corrosion     WATER LOOP APPLICATIONS     Water loop applications  usually include a number of units plumbed to a common pip   ing system  Maintenance to any of these units can introduce air  into the piping system  Therefore  air elimination equipment  comprises a major portion of the mechanical room plumbing     The flow rate is usually set between 0 040 and 0 054 1 s per  kW of cooling capacity  For proper maintenance and servicing   pressure temperature  P T  ports are necessary for temperature  and flow verification        In addition to complying with any applicable codes  consid   er the following for system piping     e Piping systems using water temperatures below 10 C  require 12 7 mm closed cell insulation on all piping  surfaces to eliminate condensation    Avoid all plastic to metal threaded fittings due to the  potential to leak  Use a flange fitted substitute    Teflon tape thread sealant is recommended to minimize  internal fouling of the heat exchanger    Use backup wrench  Do not overtighten connections   Route piping to avoid service access areas to unit    Flush the piping system prior to operation to remove dirt  and foreign materials from the system     GROUND WATER APPLICATIONS     Typical ground   water piping is shown in Fig  8  In addition to complying  with any applicable codes  consider the following for sys   tem piping    e Install shut off valves for servicing    Install pressure temperature plugs to measure flow and  te
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Manual do utilizador do computador portátil  User`s Manual Profile For a better understanding of this  P45DE3 - ASRock  APTr 1.2 – Procedimiento Gestión de Stock en HRR V4-2015  Manual - Vermont Castings Group  取扱説明書 - オリンパス  5088 NF 5088 A+++ 5088 A+++NFY  MANUAL DO PROPRIETÁRIO      Copyright © All rights reserved. 
   Failed to retrieve file