Home
Matrix M100 Operating instructions
Contents
1. WARNING THE BOILER FITTINGS CAN T SUPPORT ANY WEIGHT SUPPORT ALL OF THE PLUMBING SYSTEM EXTERNALLY DO NOT APPLY TORQUE TO THE PLUMBING FITTINGS HOLD THE FITTING WHEN INSTALLING OTHERWISE DAMAGE TO THE UNIT WILL OCCUR This appliance is designed to operate in residential and commercial heating systems and is not intended for 1 Outdoor installations or unheated spaces which can cause freezing 2 Process heating of potable water or any other fluids 3 Un pressurized and gravity feed heating systems 4 Heating systems with very low pressures or flow IMPORTANT Understand and follow the plumbing requirements provided in this section Keep serviceability in mind when installing plumbing around the furnace cabinetry Install fittings that will allow the system to be flushed if needed during annual check ups Add inhibitor Fernox Protector F1 NTI Part Number 83448 to the system water to help prevent limestone and magnetite deposits and galvanic corrosion Bottle provided will treat an average 100 liter 26 US gallon system 16 _Matrix Installation and Operation Instructions 6 1 Plumbing Minimum Requirements Pressure Regulator Fill Valve Supplied The Matrix operates as a boiler to provide heat thus it must be installed and operated as such A 12 15 PSI pressure regulator is provided with the Matrix and must be field installed as per the installation instructions Note Local authorities
2. Plenum Sensor The Matrix is equipped with a plenum temperature sensor that must be field installed in the supply plenum and wired to the furnaces external terminal strip When installed the Matrix fan control displays the plenum temperature and will use it to detect problems in the supply of heat to the space Call for Circulating Fan 24VAC G Matrix operates at the programmed air circulation rate according to the FAN setting in the Fan blue controller 400 1600 CFM If HRV is set to See 8 2 Fan Controller the HRV will ventilate at the low Continuous ventilation rate Call for Dehumidification 24 DH Matrix operates at the minimum air circulation rate 400 CFM HRV will ventilate at the high Override ventilation rate Call for Cooling Fan 24VAC 9 Y1 Matrix operates at the prescribed air circulation rate Y 1x10 CFM See 8 2 Fan Control HRV will not operate during a call for cooling unless there is a concurrent call for DH Dehumidification or G Continuous and HRV is set to ON Call for Cooling Fan 24 Y2 Matrix operates at the prescribed air circulation rate Y2x10 CFM See 8 2 Fan Control HRV will not operate during a call for cooling unless there is a concurrent call for DH Dehumidification or G Continuous and HRV is set to ON 10 2 Duct Sizing When sizing ductwork a maximum flow velocity of 800 fpm is Table 10 3 Maximum Air Flow Rates desired Table 1
3. IMPORTANT Boiler system cleansers and corrosion inhibitors must not be used to flush contaminants from water heaters or potable water systems 16 1 Combustion Chamber Cleaning Procedure Units operating with LP Gas or in an industrial environment will have to be cleaned a minimum of once per year Other applications will require the combustion chamber to be cleaned after the first year of operation with subsequent cleanings scheduled based on the condition of the combustion chamber at the time Unless a step 1s identified as model specific the following combustion chamber cleaning procedure is the same for all models IMPORTANT Crystalline Silica Read carefully the warnings and handling instructions pertaining to Refractory Ceramic Fibers before commencing any service work in the combustion chamber Take all necessary precautions and use recommended personal protective equipment as required l Initiate a post purge cycle to clear any gas from the combustion chamber then turn gas valve off 2 Access the combustion chamber by removing the aluminum burner door assembly of the appliance Remove the insulation disc P N 83112 located in the back of the combustion chamber to avoid damaging it during the cleaning process The disc is held in place with a 2 5mm Allen head screw 4 Usea vacuum with a high efficiency filter to remove any loose debris or dust 5 Wetthe inside of the combustion chamber with water Use a garden hose with a trigge
4. Throttling Valve Installed a throttling valve after the mixing valve to regulate the maximum hot water flow rate The Matrix is limited to a firing rate of 150 therefore excessive flow rates will result in cooler hot water temperatures Drain and Isolation Valves Install drain and isolation valves on the inlet and outlet of the brazed plate heat exchanger as shown in Figures 7 1 and 7 2 so it can be flushed free of possible build up caused by dirt or hard water Hard Water To prevent the formation of scale on the inside of the brazed plate heat exchanger and other components in the domestic hot water system water with hardness higher than 50 ppm Calcium Carbonate must be treated with a Water Softener prior to entering the appliance Plugging of the domestic system by scaling or accumulation of dirt is not the responsibility of NY Thermal Inc and suitable steps shall be taken to avoid it 24 _Matrix Installation and Operation Instructions Cleaning Brazed plate heat exchangers operate with high turbulence flow even at low flow rates This high turbulence keeps small particles in suspension minimizing fouling and scaling However in some applications the fouling tendency can be very high e g when using extremely hard water at high temperatures In such cases it is always possible to clean the exchanger by circulating a cleaning liquid Use a tank with weak acid 5 phosphoric acid or if the exchanger is frequently cleaned
5. or removing this appliance This appliance contains materials that have been identified as carcinogenic or possibly carcinogenic to humans Table 16 1 Handling Instructions for Refractory Ceramic Fibers RCF Reduce the Risk of Exposure Precautions and Recommended Personal Protective Equipment Avoid contact with skin and eyes e Wear long sleeved clothing gloves and safety goggles or glasses Avoid breathing in silica dust Wear a respirator with a N95 rated filter efficiency or better e Use water to reduce airborne dust levels when cleaning the combustion chamber Do not dry sweep silica dust Pre wet or use a vacuum with a high efficiency filter Avoid transferring contamination e When installing or removing RFCs place the material in a sealable plastic bag e Remove contaminated clothing after use Store in sealable container until cleaned e Wash contaminated clothing separately from other laundry First Aid Measures If irritation persists after implementing first aid measures consult a physician e Skin Wash with soap and water Eyes Do not rub eyes flush with water immediately e Inhalation Breathe in fresh air drink water sneeze or cough to clear irritated passage ways Notes Respirator recommendations based on CCOHS and OSHA requirements at the time this document was written Consult your local regulatory authority regarding current requirements for respirators personal protec
6. 16 000 cu ft 16 000 x 3 air changes per hour 4 800 cu ft hr 4 800 cu ft hr 60 80 cfm 80 cfm is ventilation requirement 39 Matrix Installation and Operation Instructions 11 2 Types of Installation There are two basic methods of installing the ventilator in the Matrix Exhaust at the source Stale air is drawn from the kitchen and bathrooms External Ducting to be 6 Warm Air insulated with Vapor Barrier Supply Cold Air Return 7 18 min Stale Air From Kitchen and Bathroom d Exhaust from the return Simplified System Stale air is drawn from the return plenum 4 External Ducting be 6 Warm Air insulated with Vapor Barrier Supply 1 6 0 min Cold Air Return 18 Stale Air From Cold Air Return Connection to be 4ft from where return plenum attaches to Matrix 40 Matrix Installation and Operation Instructions IMPORTANT When using the Simplified System method exhaust connection to the return must be 4 from where the return connects to the Matrix IMPORTANT All main HRV ductwork to be 6 round Exterior connections are to be insulated and include a vapor barrier 11 3 Damper Box Included in the installation kit is a damper box This damper box eliminates the infiltration of cold outside air when the HRV is off or in defrost mode It is to be installed with the actuator on the top side and screw
7. 5 oxalic acid Pump the cleaning liquid through the exchanger For optimum cleaning the cleaning solution flow rate should be a minimum of 1 5 times the normal flow rate preferably in a back flush mode After use do not forget to rinse the heat exchanger carefully with clean water A solution of 1 2 sodium hydroxide NaOH or sodium bicarbonate NaHCO3 before the last rinse ensures that all acid is neutralized Clean at regular intervals 7 2 1 Instantaneous DHW w o Storage Tank The Matrix will provide domestic hot water continuously when flow is sensed by the flow meter This method is the most efficient means of heating water by allowing the boiler to operate at a lower return water temperature thus increasing combustion efficiency and by minimizing standby losses See Figure 7 1 for installation details DHW Limitations As the Matrix produces domestic hot water instantaneously there are inherent limitations of the system o NO STORAGE As there is no water storage the boiler can only provide water at the temperature specified at the corresponding flow rates Flow through the fixtures must be regulated so not to exceed the ability of the boiler to heat the water MORE FLOW LESS TEMPERATURE See Table 7 1 and Procedure for Setting up Domestic Hot Water DOESN T MAINTAIN TEMPERATURE When there is no call for domestic the unit is off From a dead stop the unit will detect flow and start providing heat in 15 seconds and be up t
8. AM101 US 1 Extended air tube Plate heat exchanger LA1430 Flow Meter 3 way Valve VU54S2016B 3 4 way actuator VU844A 1003B PCB Optocoupler CVI Venturi 01 CVI Venturi Gasket Matrix Air Metering Assembly Outdoor Air Sensor Pressure Switch 1 4 NPT Divider Plate Insulation c w hardware Tee Brass 1 4 8 OTM gt g 3 X 8 8 SIS Sla elo BEE 8 oa Bie alk 58 8 N Furnace Blower ECM Motor Expansion Tank Pump Grundfos UP15 42B7 Fin Tube Coil 22 5 x 18 2 818 8 8 5 8 8 HRV Fan HRV HVC Board HRV Filter x 2 HRV Core HRV Damper Actuator 24V Matrix HRV Assembly 5 a Matrix Plenum Sensor Door Safety Switch Auto Air Vent 1 8 6 Double Colar 818 orn 8 8 8 a N Keeper for 6 Collar HRV Door Switch al alo R a
9. Controlled Temperature Only Temperature Sensor S1 a System Temperature Circulator Air Sensor S3 1 Separator A Injection Circulator NTI Make Up Backflow Water Preventer Pressure Expansion Reducing Tank Valve n 22 Matrix Installation and Operation Instructions 6 3 4 B Single Controlled Temperature Zones Injection System Wiring Tekmar 356 5 6 7 8 9 Boiler Power T R C Injection Circulator 120 VAC 3 WIRE ZONE VALVES iOUTDOOR SENSOR 24VAC SINGLE POLE ESI Y2 SINGLE THROUGH N O 24V THERMOSTAT 6 3 5 Multiple Controlled Temperature Zones Injection System tign Tomp gones Multiple Controlled Temperatures Temperature Sensors System Circulators Injection Boiler Circulators Circulator Separator NTI Make Up Backflow Water Preventer Pressure Expansion Reducing Tank Valve 23 Matrix Installation and Operation Instructions 7 0 Domestic Hot Water System 7 1 DHW Description of Operation The Matrix heats domestic hot water on demand indirectly using a brazed plate heat exchanger Using an internal flow meter the Matrix recognizes a DHW demand when the DHW flow rate is greater then 0 4gpm The Matrix immediately goes into domestic mode regardless of what other systems may have been operating the burner fires and the Ma
10. Section 7 2 2 and Figure 7 2 7 2 2 Matrix w DHW Storage Tank To completely avoid the DHW limitations inherent with on demand hot water heating install a DHW storage tank as per the DHW plumbing schematic shown in Figure 7 2 When the tank temperature 1s insufficient an aqua stat T stat located within the storage tank completes a 120VAC circuit to a potable bronze or Stainless Steel circulating pump The pump circulates water from the bottom of the storage tank typical location of a drain fitting to the DHW inlet fitting of the Matrix Rear fitting to the Flow Meter and Brazed Plate Heat Exchanger The Matrix Flow Meter senses the water flow and triggers a DHW demand heated water flows from the Matrix and enters the inlet fitting of the storage tank 26 Matrix Installation and Operation Instructions Figure 7 1 DHW Piping Tankless On demand NTI MATRIX OUTLET HIGH TEMPERATURE SUPPLY FRONT Figure 7 2 DHW Piping w Storage Tank HIGH TEMPERATURE SUPPLY LOW TEMPERATURE SUPPLY Dx gt STORAGE TANK NTI MATRIX OUTLET FRONT PS ER INLET REAR E gt Ux LEGEND SYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION ISOLATION THROTTLE VALVE BRONZE PUMP Q FLOW METER H THERMOSTATIC MIXING DRAIN VALVE Ky VALVE Ki Y STRAINER EXPANSION TEMPERATURE AND BRAZED PLATE HEAT TANK PRESSURE RELIE
11. a temperature sensor that is to be field installed in the supply plenum When installed the Matrix Fan blue controller with display the plenum temperature and may provide additional features depending on the application Outdoor Outdoor Temperature Sensor Each Matrix is provided with an outdoor temperature sensor that may be field Sensor installed to provide Outdoor Reset for applications were the Matrix is providing heat to a Hydronic Heating System Hydronic Heat Input Input requiring 24VAC from terminal to initiate a demand for Hydronic Heat Switch is H made using an isolated end switch dry contact e g hydronic zone controller Not used in applications w o Hydronic Heating Boiler temperature setting is made via the HYD setting in the red Boiler Controller see Table 9 4 DHW Heat Input Input requiring 24VAC from terminal R to initiate a demand for DHW Heat Switch is made using FS an isolated end switch dry contact e g dhw flow switch or tank aqua stat Note this input is normally not used as the Matrix incorporates a DHW Flow Meter to detect DHW demands De Humidistat Input Input requiring 24VAC from terminal R to initiate a demand for high ventilation with the optional built in HRV Heat Recovery Ventilator Switch is made using an isolated end switch dry contact e g DH centrally located De humidistat may be incorporated in Thermostat or wet room timers Note this function only
12. ignition device that automatically lights the burner Do not try to light the burner by hand Turn the gas shut off valve to the off position and then remove the front cover Wait five 5 minutes to clear out any gas Then check for gas including near the floor If you smell gas Stop and follow B above If you don t detect any gas proceed to the next step Turn the gas shut off valve to the on position wait an addition five 5 minutes and check for gas Replace the front cover Set the thermostat to the highest setting and then turn on all power to the appliance Ignition sequence is automatic combustion will occur after a brief fan purge Ignition will retry 3 times If ignition does not occur Turn off the gas and electricity to the appliance and contact a professional service technician or gas supplier Turning Off The Appliance 1 2 Set the thermostat to the lowest setting and then turn off all power to the appliance Turn the gas shut off valve to the off position 45 Matrix Installation and Operation Instructions 13 0 TROUBLE SHOOTING This section is intended to assist the service technician in detecting and correcting common errors The Matrix Boiler and Fan Controls are equipped with an internal diagnostic system that verifies control operation The following series of error codes has been developed to aid in diagnosing control problems Symptom Detected Pr
13. may require the installation of a certified back flow preventer immediately before the pressure regulator Circulating Pump Supplied The Matrix has a built in circulator to pump water from the boiler to either the internal forced air heating coil or the internal domestic coil brazed plate heat exchanger An external circulator is only required if the Matrix is also being used to supply heat to a hydronic heating system the external circulator must be sized for the requirements of the hydronic heating system Relief Valve Supplied A 30PSI Relief Valve is provided with the system it is to be mounted with the discharge in the horizontal Ensure that the discharge is piped to a location were steam or water won t cause personal injury or appliance and property damage Air Purging Supplied Boilers are designed to operate with airless water in the system The Matrix design allows for the evacuation of air from the internal plumbing For installations in conjunction with a hydronic heating system an Air Scoop installed as shown in the following diagrams must be installed to remove air as it circulates through the system If air continues to be a problem air scrubber must be used recommend Spirovent VJR 100TM Expansion Tank Supplied The Matrix comes with a built in expansion tank that is sized to handle the volume of water in the Matrix unit An external expansion tank must be field sized supplied and installed for Matrix unit
14. of 1020 BTU per cubic foot For areas with lower heating values a combustion test is required to obtain optimum operation Using a calibrated flue gas analyzer check the combustion and compare it with the acceptable requirements The test should be performed at maximum fan speed Gas Input Value Adjusting Combustion Use the input screw to adjust the amount of gas available for combustion Increasing gas increases CO and Reducing gas decreases CO and Table 5 1 Normal Range of Combustion Products CO At maximum fan speed the CO reading is At maximum fan speed 240 the most critical to the safe operation of the boiler 4 Natural Propane The CO should be no higher than 175 PPM at any Carbon Dioxide CO 96 8 9 5 9 10 5 condition If the CO is over 140 PPM the input Carbon Monoxide CO ppm 25 175 25 175 should be reduced until the CO is less than 140 NOx ppm 10 50 10 50 1 0 0 PPM or the is reduced to 8 9 for LP Gas Note On colder days should be closer to the lower number on warmer If the CO is over 140 PPM and the CO is less than days it should be closer to the higher number CO should be highest at the 8 9 for LP Gas contact NTI for assistance maximum firing rate CO At minimum fan speed should be checked and the CO should be less than the reading recorded at high fan speed The CO at low fan speed must not be at least as high as the CO recorded
15. the HRV fan in percentage In the case of EOR the number shown represents the speed of the exhaust E fan during a call for high ventilation override while the air handler blower is running at the high heating speed The maximum speed setting is 100 the minimum 30 Adjust the speed up or down until the desired flow rate is achieved Table 11 1 on the following page has been provided to help in explaining the different settings 5 Complete the table adjusting each of the setting to the HRV Ventilation Rate provided These rates are a guideline only and can be adjusted to meet the specific application Note When adjusting the exhaust speeds the supply fan will increase to full speed When the balancing is complete the HRV will maintain balance at any ventilation rate during any air handler blower condition This is a unique feature of the Matrix and is essential in providing efficient and adequate ventilation in this integrated system ATTENTION The HRV balance must be checked and if necessary rebalanced every time the Heating HEA setting is changed or if there is change to the system which would significantly change the static pressure at the return plenum or the exterior ducts to the HRV 42 Matrix Installation and Operation Instructions Figure 11 1 Sample Balancing Setup P n en Table 11 1 HRV Balancing Table 6 Flow Measurement Station Averaging Pitot Tube or Pitot Tra
16. to the Matrix using the four screws provided Damper Box with Collar Installed 11 4 Condensate Drain Condensation from defrost will collect in the ventilator and drain from the sloped drain pan This condensation must be evacuated from the q unit The condensate tubing provided must be routed through the hole in the side of the appliance and attached to the 90 elbow directly undemeath the ventilation module From there the condensate tube must be emptied into a suitable floor drain or if necessary the emptying drain must have trap to prevent the infiltration of toxic gases This End to Appropriate Drain or Condensate Pump Attach End of Supplied Tubing to 41 Matrix Installation and Operation Instructions 11 5 HRV Balancing The HRV must be balance properly in order to operate at maximum efficiency and avoid problems The balancing process ensures the volume of fresh air from outside is equal to the amount of stale air being expelled from the home over all air handler conditions A variation of 10 is acceptable with the greater volume being stale air drawn from the home The Matrix uses motor speed to balance airflows This method of balancing provides quieter operation and reduced energy consumption over the traditional balancing damper approach Flow is measured with the use of a Magnehelic 0 25 inwg range and an airflow grid flow collar or Flow Measuring Station N
17. 1 shows common duct sizes at specified flows The maximum flows that can be expected are shown in Table 10 3 It is Fan Control Setting important to maintain the return plenum pressure as low as possible Heating Cooling ESPmax CFM ipe i HEA COO Keeping this ductwork as free flowing as possible will offer more supply static pressure to overcome A C coils closed registers while 160 max 35 inwg 1600 maintaining constant flow 160 max 6 inwg 1500 160 max 75 inwg 1400 Any additional filtration humidification or de humidification 120 3 Ton 1200 equipment should be installed external to the return or supply ducts so 80 2 Ton 800 tt t iti restriction not to create additional restriction EIE 1208 Table 10 2 Duct Size vs Air Flow PF2 No Cooling lt 1 inwg 1100 PF1 No Cooli 11 1000 Airflow Area Duct Sizing 228008 saft inches Example 1 No cooling function with Heating 1600 2 24x12 20x16 profile of PF2 selected Maximum airflow will be 1100 CFM 1200 1 5 24x10 20x12 18x12 1000 1 25 20x10 18x10 16x12 Example 2 Cooling set to 800 CFM for 2 tons of cooling with Heating profile of PF3 selected 800 1 18x8 16x10 12x12 Maximum airflow will be greater of cooling or heating function Maximum 1200 CFM Based on 800 fpm max airflow velocity Measured from return plenum to supply plenum prior to A C coil ECM motor can
18. 10 210 HYD 10 210 F Heat Circ Off On On On On On On Primary Auxiliary Shared Call Forced Air Forced Pehl d Call W1 Call W2 Air Hydronic T Storage Storage Aux Heat Shared W1 W2 Domestic A Condition Off On Heat W1 W2 and H Hydronic Call Only Greater of SP HI H20 to 1 Note 1 Set Point 160 F SP HI car ca and HY Deate HY Deatc H20430 Burner On 140 HI cas No eet HYDca DIF H20 30 Burner Off 180 210 210 210 F 10 210 F Heat Circ Off On On On On On On Note 1 SP Setpoint received from Matrix Fan Controller 9 2 1 Setting Matrix Boiler Control Sentry Programming is accomplished by a series of three push buttons located on the bottom side of the control Function f and 2 enter the programming mode press the function key once To scroll through the various menu options depress until the menu is displayed To alter the value press Function once and the current value will be displayed then use for up and for down until the desired value is obtained To enter the selected value press Function which will return to the menu When all desired values are selected scroll to the RUN menu and press Function which exits the Programming Mode and initiates normal operation A safety feature has been added to ensure that if the control is left in the Program Mode the unit will t
19. 2 Leave the manual with the customer so they know when to call for annual maintenance and inspection A WARNING This appliance must have water flowing through it whenever the burner is firing Failure to comply may damage the unit void the warranty and cause serious injury or death A WARNING Allowing the appliance to operate with a dirty combustion chamber will adversely affect its operation and void the warranty Failure to clean the heat exchanger on a frequency that matches the need of the application may result in fire property damage or death 51 Matrix Installation and Operation Instructions 16 0 ANNUAL MAINTENANCE AND INSPECTION This unit must be inspected at the beginning of every heating season by a Qualified Technician Annual Inspection Checklist 1 Lighting is smooth and consistent and the combustion fan is noise amp vibration free The condensate freely flows from the unit and is cleaned of sediment Relief Valve and air vents are not weeping Low water cut off is flushed if applicable Examine all venting for evidence of leaks Ensure vent screens are cleaned and clear of debris Check the burner plate for signs of leaking The combustion chamber must be inspected and cleaned Listen for water flow noises indicating a drop in appliance water flow rate Important The hydronic system may need to be flushed to eliminate hard water scale Use Fernox DS 40 Descaler NTI PN 83450 OOOOOOOO ANANDA gt
20. 5100 850 138 122 46700 900 152 132 58700 3 7 860 127 114 38800 910 145 127 54200 975 163 139 70200 53 8 900 130 115 42500 970 152 131 61800 1050 172 144 81800 9 950 133 117 46300 1030 158 134 69400 1120 181 149 93400 3 10 1000 136 118 50000 1100 164 137 77000 1200 190 153 105000 Example At stage 4 Profile 1 the Matrix provides 720 CFM across the fan coil which is receiving 117 F water from the boiler The coil then supplies plenum air at 108 F or 27700 BTU hr On an initial thermostat call 24 W1 space heating begins by providing heat at Stage 3 24 000 BTU hr if hydronic heat is also calling 24VAC H heating will begin at stage 1 and so long as the thermostat is not satisfied incrementally increases to a maximum of Stage 10 maximum output When the thermostat becomes satisfied an average of the heat output rate during the call is calculated The boiler remains lit and the space heat output begins an incremental decrease in heat output rate beginning with the stage just below the calculated average and ending with either the thermostat re calling or if the thermostat never re calls the output rate decreases to minimum stage after which the boiler shuts off If the thermostat re calls prior to the minimum heat stage a new calculated average of the thermostat off cycle is calculated and the boiler again begins an increasing ramp only this time it begins at the calculated stage and not necessar
21. 918 HSAH 2 42018 NOLINGINLSIC EN omnem ng gna d MUN DC In 2 na wor D NUN m o 05 3 diMIS TVNIWH3L 1314 anus 9 nmaa 58 81 u342n 0 N02 na a3u 91 Jes HOLMS AL34VS X000 1041NO2 18A Nu5 2 gs k is OVA 021 elt ol ne Nv Ag 32 u Matrix Installation and Operation Instructions 9 0 CONTROL SETUP The Matrix used two devices to control the functions required by the Matrix The Matrix Boiler Control red face controls and ensures the safe operation of the boiler functions of the Matrix much the same as the Sentry 2100 does in the Trinity products The Matrix Fan Control blue face controls all of the operation and safety functions related to air handling and hot water dispatching The fan controller controls the forced air modulation ventilation as well as priority of domestic hot water and secondary heating systems ATTENTION The Matrix Boiler Control Sentry is different from the Sentry controller used on any other NTI products and is NOT INTERCHANGEABLE 9 1 Controller Displays 9 1 1 Matrix Boiler Control Sentry
22. DOS DQ O FOO 7 24V COM THERMOSTAT o Matrix Installation and Operation Instructions 6 3 2 A Multiple High Temperature Zones Zone Circulators Zone 3 Zone 2 Zone 1 Check lt Valves aa Zone Circulators Air _ Separator NTI Make Up Backflow Expansion Water Preventer Pressure Reducing Tank Valve 6 3 2 B Multiple High Temperature Zones Zone Circulators Wiring w Zone Controller TACO SR504 SWITCHING RELAY ZONE 4 PRIORITY sas 02 eco oo oo MATRIX TERMINAL STRIP O FOUR ZONE SWITCHING RELAY WITH OPTIONAL PRIORITY 2 6 9 OUTDOOR senso X ZONE1 ZONE2 ZONES ZONE4 POWER END 2 28 SWITCH 420 VOLT CIRCULATORS INPUT eoe oo eo eo eo eo ee v FUSE 7 AMP OO 120 VAC INPUT THERMOSTAT 21 Matrix Installation and Operation Instructions 6 3 3 Multiple Controlled Temperature Zones Tempering Valves e Use wiring configuration in 6 3 2 B Temp 3 Temp 2 Temp 1 Zone Circulators Tempering Valves E Air _ Separator NTI Make Up Backflow Water Preventer Pressure Expansion Reducing Tank Valve 6 3 4 A Single Controlled Temperature Zones Injection System Zone 3 Zone 2 Zone 1 Jana Valiss One
23. Display Red Face Plate The Matrix Boiler Control communicates to the user what is happening in the system by using an LED display and a series of LED indicators Table 9 1 Matrix Boiler Control Display Display Description BureUBr teur Indicates that the ignition system is activated Indicates a call for forced air heat Forced Air Please note There may still be a call Demand for forced air heat even when thermostat is satisfied off Hydronic Demand Indicates a call for hydronic heat DHW Demand Indicates a call for domestic hot water When illuminated display is showing boiler water temperature When illuminated display is showing boiler water set point When illuminated display is showing outdoor temperature When illuminated display is showing Gas Input Value current gas input value See chart to determine input rate Boiler Temp 2 gt Matrix Boiler Control Boiler Setpoint 9 1 2 Matrix Fan Control Display Blue Face Plate Table 9 2 Matrix Fan Control Display Display Description Space Heat Indicates a call for forced air heating Cooling Indicates a call for cooling 2 DHW Indicates a call for domestic hot water E Hydronic Indicates a call for hydronic heat ReCirc Indicates a call for continuous E circulation ventilation iia HRV On Indicates the HRV is ventilating m Defrost Indicates the HRV is
24. F VALVE EXCHANGER 27 Matrix Installation and Operation Instructions 8 0 WIRING 8 1 Field Wiring to Matrix All wiring must be in accordance with the Canadian Electrical code CSA C22 2 and any applicable local codes Ensure that the wiring is in accordance with this manual The boiler must be electrically grounded in accordance with the National Electrical Code ANSI NFPA 70 or local codes and or the Canadian Electrical Code CSA C22 1 All connections to the Matrix are made at the terminal board provided This terminal board can be found on the left side of the appliance just above the plumbing connections The following connections are available and provide different functions according to which inputs are energized Figure 8 1 Line Voltage Field Wiring MATRIX JUNCTION BOX 120VAC SUPPLY LINE NEUTRAL GND SERVICE SWITCH FIELD SUPPLIED Po Fo 2251 2 I WARNING THE MATRIX TERMINAL STRIP IS FOR LOW VOLTAGE 24 VAC AND LOW LOAD MAX 1 CONNECTIONS ANY ELECTRICAL LOADS IN EXCESS OF 24VAC OR 1 AMP MUST BE ISOLATED USING RELAYS FAILURE TO FOLLOW THESE INSTRUCTION CAN RESULT IN FIRE ATTENTION Before providing 120 Volts to the appliance do a continuity check between all wires and ground to make sure that there are no electrical leaks that could damage the Matrix circuitry Before providing 120 Volts to the appliance do a polarity check of th
25. Manual and 3 Natural to LP Conversion Kit The conversion kit is required to convert the appliance so it will safely operate with Propane Gas Read and understand this entire document prior to proceeding with the installation of the Matrix Failure A DANGER to follow the instructions outlined in this document will result in property damage serious injury or death User Responsibilities This appliance must be installed and serviced by a qualified installer or service technician This appliance must be serviced and inspected annually when operating in normal residential applications Demanding applications or extreme conditions i e commercial may require more frequent service and inspection As the User Owner of this equipment you are responsible for ensuring the maintenance is performed at the required intervals It is also the Users responsibility to ensure Vent and Combustion Air Intake termination is kept clear of ice and snow or any other obstruction Failure to follow these instructions could result in fire serious injury or death JN WARNING Failure to have the appliance properly serviced and inspected on a regular basis may result in property damage serious injury or death Failure to keep the Vent and Combustion Air Intake clear of ice snow and other debris may result in property damage serious injury or death WARNING Installer Responsibilities As the installing technician it is your responsibility to ensur
26. NTI MATRIX INSTALLATION AND OPERATING INSTRUCTIONS VERSION DATE 9 15 10 TABLE OF CONTENTS 1 0 SPECIFICATIONS 3 2 0 INSTALLATION REQUIREMENTS cccseessessseesseesseessneessnessnescae eee 4 3 0 6 4 0 CONDENSATE DRAIN cronan 22222 13 5 0 INSTALLING GAS 1 nennen nnne nennen snas asinis 14 6 0 BOILER 16 7 0 DOMESTIC HOT WATER 5 24 2 28 9 0 CONTROL SETUP 33 10 0 MATRIX BLOWER OPERATION 37 11 0 HEAT RECOVERY VENTILATION eren nennen nnne nnne nn intr intr astra asina sonas snis drea runnen nenene nana 39 120 LIGHTING X 44 13 0 ie SI elenco 46 14 0 SEQUENCE OF 50 15 0 INSTALLATION 16 1 1 1 esee eene enne ninh nnn nn s
27. Operation Instructions 3 3 Venting Rules and Guidelines 1 It is highly recommended that the vent terminal be located where it will not be exposed to normal prevailing winds 2 The exhaust must be a minimum of 18 above the air inlet and the air inlet must always be a minimum of 12 plus snow allowance above any surface that will support snow Two feet plus snow allowance is highly recommended Consult your weather office for the maximum typical snowfall for your region Example New Brunswick Canada the typical maximum snowfall is 19 Thus in figures of Section 3 3 the inlet must be 12 19 31 off the ground the exhaust must be 31 18 49 3 Under normal operating conditions this appliance will produce a plume of white gases and should be taken into consideration when selecting an adequate location A 3 diameter stainless plastic or vinyl shield can be used to flash the exterior of the residence 4 If the horizontal distance between the inlet and exhaust is more then 12 increase minimum vertical separation by the same amount If horizontal distance is greater then 6 no additional vertical spacing is required Example horizontal separation equal to 24 requires a minimum vertical separation of 18 24 12 230 Vertical separation is never required to be greater then 36 5 Elbows on outside of wall must be no greater than 1 2 away from the wall 6 All indoor exhaust piping must be on a
28. TI offers an airflow grid PN 83554 that is designed to be installed in a 1 hole located in a 6 duct It is important that the flow grid be the same size as the ductwork and be installed according to the manufacturers instructions Typically a straight run of 18 on either side of the flow grid is adequate to avoid false readings It is helpful if a flow grid is installed in each of the supply and exhaust ducts Procedure 1 Attach the upflow port of the flow grid to the positive pressure port of the Magnehelic and the down flow port to the negative port 2 Zero the Magnehelic 3 Begin by selecting the heating profile required in the Matrix Fan Controller HEA menu Refer to the heating section of the manual for more explanation The heating profile selected dictates the air handler blower speeds and is important to the proper functioning of the HRV Every time the heating profile is changed the HRV will require re balancing 4 Once the heating profile is selected advance to the BAL menu By pressing the FUNCTION button you will enter the balancing mode of the HRV Press the up arrow button and advance through the menus until you reach the EOR menu item By pressing the FUNCTION button you will enter the EOH menu A number will appear You will notice the HRV start if it is not already running and the main blower of the air handle will come up to speed The number on the display represents the speed of
29. a sidewall vented fuel burning appliance is installed Installers must abide by local code requirements regarding the installation of CO detectors The use of a certified carbon monoxide detector is recommended but not required by NTI IMPORTANT IN THE STATE of MASSACHUSETTS ONLY a For all horizontally vented gas fueled equipment installed in every dwelling building or structure used in whole or in part for residential purposes including those owned and operated by the Commonwealth and where the side wall exhaust vent termination is less than seven 7 feet above finished grade in the area of the venting including but not limited to decks and porches the following requirements shall be satisfied 1 INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back up is installed on the floor level where the gas equipment is to be installed and on each additional level of the dwelling building or structure served by the equipment It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors a the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detec
30. aced If the condensate drain gets blocked the boiler will become flooded and terminate operation as the flame rod becomes immersed This will damage the flame probe To correct free the drain blockage and permanently prevent it from reoccurring Remove and dry off the probe Reinstall the probe and try for ignition if it fails to stay lit leave the fan run for up to three hours to dry out the insulation and probe Three Flashes on Ignition Lockout Fenwal Reset Boiler so it will attempt to ignite Check for proper operation of ignition components Make sure igniter glows and gas valve opens Check for proper line pressure at gas valve when it opens If boiler lights check for flame signal between FC1 and FC2 on Fenwal control If lower then 1 2 DC see Boiler will not stay lit Check combustion properties 47 _Matrix Installation and Operation Instructions Symptom Boiler will not stay lit Boiler bangs or hisses General Boiler Lights rough or pulsates Fan appears to be creating a noise in the house Detected Problem Indicates lack of a flame signal In order to stay running the flame signal must be at least 0 7 Amps Bangs or sounds like a kettle while burner is running indicates insufficient flow Typically an imbalance in the Air to gas ratio Slight vibration can cause noise in the residence This is not a warranty issue Making a rubbing noise Th
31. acts to de humidify during colder weather by increasing ventilation it is not intended for de humidification during warmer months Circulation Fan Input Input requiring 24VAC from terminal R to initiate a demand for the Circulation Fan Switch is G made using an isolated end switch dry contact normally incorporated in the home thermostat Air circulation rate is set via the FAN setting in the blue Fan Controller see Table 9 5 R 24V AC Hot Power supply for inputs FS W1 W2 Y1 and Y2 Forced Air Central Heat Input Input requiring 24VAC from terminal R to initiate a demand for the Forced Air W1 Central Heat Switch is made using an isolated end switch dry contact normally incorporated in the home thermostat Forced Air Central Heat Input Stage 2 Input requiring 24VAC from terminal R to initiate a demand for Stage 2 Forced Air Central Heat Switch is made using an isolated end switch dry contact normally incorporated in the home thermostat Note most application will not require the use of input W2 NTI recommends using W1 only for Forced Air Central Heating Air Conditioning Heat Pump Input Stage 1 Input requiring 24VAC from terminal R to initiate a demand for Y1 stage 1 cooling or heat pump Switch is made using an isolated end switch dry contact normally incorporated in the home thermostat CFM rate adjustable via Y1 setting in the blue Fan Controller see Table 9 5 Air Conditioni
32. alled 2 Inlet air o Gas Vent Directly Below o A NS Keep Free of Obstructions 2 EN d Exhaust Exhaust x Inlet air a DO Must be 1 i L e from wall Semin 36 min NE Note inlet pipe must always 0 IDEEN be connected to the boiler 7 4 or greater p than 24 12 Ps plus snow re allowance Must insert plastic bird screen Use NTI part 82666 or York part 1CT0303 Instructions included with vent terminal contain more detailed assembly and installation instructions Clearances and requirements of this manual supersede those of the instructions included with the vent terminal Terminal must be cemented together during installation 8 Matrix Installation and Operation Instructions 3 2 3 Roof Venting Exhaust Figure 3 4 Roof Venting Inlet Air 24 Roof weather seal Flashing field supplied auc a gt Si Support Field supplied Jeo i intet Air i Exhaust Note inlet pipe must always be connected to the boiler IMPORTANT USE OF EXISTING CHIMNEY It is permissible to run vent pipe through an existing chimney as long as The chimney is not to be used by any other appliance Flue gases don t enter the vacant chimney Only Trinity certified venting materials are used see Section 3 1 Vent lengths are within the maximums specified Matrix Installation and
33. anel 8 Setthermostat to highest setting Turn on all electric power to the appliance 9 Ignition sequence is automatic Combustion will occur after a brief fan purge 10 If ignition does not occur follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier TO TURN OFF GAS TO THE APPLIANCE STOP Read the safety information above very carefully 2 Turn off all electric power to the appliance 3 Turn the manual gas valve to the OFF position 44 Matrix Installation and Operation Instructions The initial lighting of the appliance must be performed by a licensed Gas Technician Failure to follow WARNING instructions may result in property damage serious injury or death Ensure the appliance is wired in accordance with this manual Ensure the gas shut off valve is turned on and that the gas system has been fully tested for leaks Ensure the system is completely filled with water and that ALL the air is purged out NGER Allow primers cements to cure for 8 hours prior to Start up If curing time is less than 8 hours first perform Steps 2 through 6 of Mandatory Pre commissioning Procedure for Plastic Venting in Section 3 0 Failure to follow these instructions can result in explosion serious injury or death Initial Start Up 1 19 gt Turn on power to the Trinity Lx and turn up the Thermostat s The appliance should run through purge and combustion should o
34. ap 13 Matrix Installation and Operation Instructions 5 5 0 INSTALLING GAS PIPING 1 Installation Figure 5 1 Gas Inlet Connection Refer to the current National Fuel Gas Code ANSI Z223 1 NFPA 54 or CAN CGA B149 1 installation WS codes and local codes for gas piping requirements and It is highly recommended to use n flexible gas pipe the gas valve and Gas cock shut Sizing blower cannot support the weight of 4 Off Valve to be piping If piping is used ensure that T type handle Pipe size running to the unit depends on the valve supports NO WEIGHT o Length of pipe m o Number of fittings o of gas o Maximum input requirement of all gas appliances 4 Gas valve in the residence 1 Ensure that Flexible gas pipe is used if acceptable by local codes The gas valve and blower cannot support the weight of piping leading to blower vibration and damaged components If rigid piping is used ensure that the valve supports NO WEIGHT You plan the installation so that the piping does not interfere with the vent pipe or the removal of the valve burner and serviceable components The Boiler shall be installed such that the gas ignition system components are protected from water dripping spraying rain etc during installation and servicing The gas piping is large enough for all the appliances in the home No appreciable drop in line or manifold pressure should occur when any uni
35. at high fan speed but not more then 9 5 10 5 for LP Gas Figure 5 3 Gas Input Screw Adjustment Input Screw Adjustment Input Screw Is a multiple turn needle Decrease gas ow valve Fully open to close is approximately Turn Clockwise 17 turns Typical adjustment for Natural Gas is 0 1 full turns in or out Typical adjustment for LP Gas is 0 3 full turns in or out after conversion is performed Increase gas Turn counterclockwise ATTENTION IF FOR ANY REASON THE INPUT SCREW IS ADJUSTED A COMBUSTION ANALYZER MUST BE USED TO ENSURE SAFE AND PROPER OPERATION 15 Matrix Installation and Operation Instructions 6 0 BOILER PLUMBING 1 WARNING THIS APPLIANCE CONSISTS OF LOW MASS BOILER AND MUST HAVE ADEQUATE WATER FLOWING THROUGH IT WHENEVER THE BURNER IS ON FAILURE TO DO THIS WILL DAMAGE THE UNIT AND VOID THE WARRANTY PLUMBING MUST INCORPORATE A PRESSURE REGULATING FILL VALVE AND PRESSURE RELIEF VALVE I WARNING HYDRONIC SYSTEMS OLD AND NEW MUST BE FLUSHED TO REMOVE SEDIMENT FLUX FILINGS ETC FAILURE TO DO SO WILL SERIOUSLY DAMAGE THE BOILER VOIDING WARRANTY CLEAN WITH FERNOX CLEANER NTI PART NUMBER 83449 WARNING WATER WITH A TOTAL HARDNESS GREATER THEN 100PPM 6 GRAINS GALLON MAY RESULT IN HEAT EXCHANGER FAILURE AND WILL VOID YOUR NTI WARRANTY TREAT ALL SYSTEMS WITH FERNOX PROTECTOR F1 NTI PART NUMBER 83448 WHICH IS INCLUDED WITH THE MATRIX PACKAGE
36. can result in explosions injury or death Prior to turning the gas supply on and lighting the appliance ensure all aspects of the installation are Bf ez complete and in conformance with the instructions provided in this manual including the Vent Air Intake Condensate Drain and System Water Piping Failure to precisely follow these instructions will cause a fire or explosion resulting in property damage serious injury or death Do not store or use gasoline or other flammable vapors amp liquids in the vicinity of this or any other appliance Failure to follow instructions could result in explosion causing property damage serious injury or death If you do not follow these instructions exactly a fire or explosion may result causing property damage serious injury or death JN Should overheating occur or the gas supply fail to shut off turn off the manual gas control valve to the WARNING appliance Failure to follow instructions could result in explosion causing property damage serious injury or death FOR YOUR SAFETY READ BEFORE OPERATING A This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand B BEFORE OPERATING smell all around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to lig
37. ccur The control system has a built in ignition retry allowing the system to try at least three times before locking out With the unit operating at full capacity verify that the gas line pressure is 4 10 5 inches w c for Natural gas and 9 13 inches w c for Propane See Section 5 0 for details Using an appropriate Oxygen or Carbon Dioxide analyzer take a sample of the flue gas The sample must fall within the acceptable ranges for Carbon Dioxide which is 8 5 9 5 for Natural gas and 9 5 10 5 for propane See Section 5 0 for details Perform at least three lights in succession to ensure proper operation After the three successive lights unplug the flame probe and allow the unit to cycle again Ensure that it tries to light and locks out on safety reset Once you have successfully activated the flame safety system replace the wire on the flame sensor and reconfirm proper lighting IN WARNING If the unit fails to light consistently and smoothly contact NTI for assistance at 1 800 688 2575 Never allow the appliance to continue to operate if the ignition or operation of the burner is rough or erratic Failure to follow these instructions could result in serious injury or death Re lighting Unit 1 2 3 e 20990 Stop and read these instructions very carefully Set the thermostat to the lowest setting and then turn off all power to the appliance This appliance does not have a pilot It is equipped with an
38. chedule 40 ANSI ASTM F441 ULC S636 approved em in 5 must ANSI ASTM D2564 Sec E DEO TUE meet the Standards isted in Pipe Cement appropriate temperature Table 3 1 Failure to CPVC ANSI ASTM F493 cuis comply could result in fire Primers PVC CPVC ANSI ASTM F656 serious injury or death Notes Refer to Table 3 2 for Allowable Vent and Air Intake Pipe Sizes and Lengths 2 Closet alcove installations US and Canada require approved CPVC vent pipe fittings cements and primers The Air Intake does not require high temperature pipe material Check applicable local codes for acceptable materials ULC S636 PVC is approved for flue gas temperatures up to 149 F 65 C and must only be used for low temperature applications High temperature applications requiring appliance supply water temperatures greater than 140 F 60 C must use ULC S636 approved CPVC Mandatory Pre commissioning Procedure for Plastic Venting WARNING 1 Do not apply power to the appliance prior to Step 4 in the Mandatory Pre commissioning Procedure for Plastic Venting Working with the power turned off to the appliance completely install the vent and air intake system securely cementing joints together If possible allow primers cements to cure for 8 hours before firing the burner If curing time is less than 8 hours proceed with Steps 2 through 6 Maintain the appliance gas supply shut off valve in the off position Disconnect electr
39. d Soap It is recommended to use products that are environmentally friendly 54 Matrix Installation and Operation Instructions 17 0 PARTS LIST Replacement parts are available from your stocking wholesaler Homeowners must contact their local Installer or Wholesaler Installers or Wholesalers may contact NY Thermal Inc for assistance at 506 657 6000 No P N Description Premix bumer 135 8 Premix Burner Gasket Transformer 24V Matrix Fan Control XA 2 LEE Matrix Boiler Control Sentry 2100 l lt D 2 Blower RG1 30 lt Gas Valve VK8115F1134B Gas Valve 1 2 elbow Gas Valve Vent connection Air switch Huba 2 wc Thermister 1 4 NPT 8 8 a BIS R als Ed Ignition Module Fenwal IGNTER 601 c w SS shield Rauscchert Flame Rod 3 amp Composit Flue Box Composit Flue Box Gasket Composit Flue Outlet Gasket Flue Adapter As sembly 4 5 Manifold Limit 1 4 Heat Exchanger Canada Heat Exchanger US LP orifice 5 20mm Stack Limit 1 4BSP 190F Dif 30 Blower Outlet Gasket 3 4 Water Connection Gasket Condensate Y Drain Siphon Condensate Trap 8 3 amp JE N o 8 218 8 amp 8 N 8 D RIR Ss amp S 8 8 Cast aluminum Burner door Ceramic burner door disc Bumer door gasket Igniter gasket Tempering valve
40. de only enough capacity for these functions Additional secondary systems require appropriately sized air removal and expansion capability 6 3 Hydronic Heating Additions Optional ATTENTION LOW TEMPERATURE APPLICATIONS i e In floor require the use of mixing controls such as a Tekmar injection system or thermostatic mixing valves See 6 2 3 to 6 2 4 During a call for Forced Air Heat the Matrix will operate at a constantly varying boiler water temperature this temperature may at times exceed the maximum allowable temperature for some or all of the hydronic zones HI TEMPERATURE APPLICATIONS i e finned tube baseboard do not require mixing controls however when the Matrix is operating during a call for Forced Air Heat the hydronic system will only receive the heat leftover from the Matrix air handler keep this in mind during system sizing and design In applications that do not use zone valves it is important to incorporate into the system design means necessary to prevent THERMAL SIPHONING Note the following drawings are to be used as a reference only for the system designer 18 Matrix Installation and Operation Instructions 1 Hydronic Call 24 VAC without a call for forced air heating A boiler demand is initialized by sending a Hydronic Demand The boiler will then maintain a set point of HYD See Table 9 3 2 Hydronic Shared Call 24 VAC concurrent with a forced air call Wi
41. e commissioning Procedure for Plastic Venting in Section 3 0 Failure to follow these instructions can result in explosion serious injury or death 1 Turn gas shut off valve to the ON position 2 Turn Power on to appliance O 3 Set Controller to the desired settings 4 Turn thermostat up Ignition will occur Operational Checklist 1 System is free of gas leaks 2 System is free of water leaks 3 Water pressure is maintained above 15 PSI 4 All air is purged from the heating system piping 5 Ensure proper water flow rate unit must not kettle bang hiss or flash the water to steam 6 Ensure gas line pressure is in accordance with Section 5 0 7 System is free of combustion leaks 8 Unit must operate smoothly 9 Ensure the flue gas combustion readings are within the tolerances listed in Table 5 1 L1 10 Each ignition must be smooth 11 Verify that all condensate lines are clean and drain freely L1 L1 EI L1 EJ P1 EJ E1 P Before Leaving 1 Remove line pressure gauge from gas valve tighten bleed screw test screw for leaks See Section 11 0 2 Install plug into the flue gas test port and test for leaks 3 Allow the appliance to complete at least one heating cycle or to operate for at least 15 minutes 4 Always verify proper operation after servicing OOOO Instructions to Installing Contractor O 1 Ensure that the customer receives the Warranty Documentation included with the installation manual
42. e is reading a minimum of 12PSI Replace water pressure switch if plumbing and pressure is correct and if it measures an open circuit Water Sensor Open Circuit ER3 Control has sensed an open circuit in the Water Sensor circuit 24V Limit Error Control has sensed a lack of 24V ER4 on the outlet of the burner relay B1 Lockout lasts for one hour before automatically resetting 8 3 Check for continuity through the 24VAC limit wiring and manifold and stack limits replace limits or wiring that are not a closed circuit Flame Lock Out There is a problem in the ignition sequence it could be caused by a faulty igniter Control has sensed a lack of 24V flame sensor gas valve or improper line pressure or combustion Check ignition tc ER6 5 ua s to the gas valve during operation sequence to determine which component is not functioning Control will retry 9 or a Fenwal ignition lockout ignition sequence 1 hour after ER6 code originally occurs or if control is reset amp 9 Internal Controller Fault Indicates that the Controller has lost communication with an internal processor contact NTI E Uie bes ER IS 1 Ensure the vinyl tubes connected between the air switch and the ports on b rac d rossi d the inlet pipe are in the proper locations Negative side of switch connects when the o ihe pani en tre I 12 PYG elbow ASO 9 2 Check for bloc
43. e line and neutral wires line must be connected to black and neutral must be connected to white Do not use magnetic tip screwdriver near the Matrix control boards Ensure that the wiring for the plenum and outdoor air sensor is not damaged or grounded Caution Label all wires prior to disconnecting them when servicing controls Wiring errors can cause improper and dangerous operation 28 Figure 8 2 Low Voltage Filed Wiring Matrix Installation and Operation Instructions IVLSOWYSHL WOOD Ave ON 4 M M M 9 NoILO3S 33 SNO dQv OVAVZ WOO HLIM ANO 5 NOILVINOUID 9 dH OV 6 ADVLS ZA dH OV JOVLS LA f 1VNOLLdO LVSH 30vdS 2 3915 ZM L 39 15 1 39vdS LAW LOH OVAVZ wer See VOIdAL LVLSOWYSHL 1 1 zl 03118815 12 MOSN3S YOOALNO aariadns 12 MOSN3S WANNITA N divs TVNIWH31 558 CO aariddns Ad012V3 A3012v3 299 13WWO9 GALVINSNI 7103 314000 520 9 5 z o 1V1S32334 ANIOd 13S 3408Y 3univs3dWal 9NILVH3dO TVIWHON BNISV3HO30 NO SN3dO Matrix Installation and Operation Instructions Table 8 1 Low Voltage Field Connections See Figure 8 2 Terminal Description Plenum Temperature Sensor Each Matrix is provided with
44. e that will support snow Two feet plus snow allowance is highly recommended Consult your weather office for the maximum typical snowfall for your region 8 Underneath a wooden verandah porch or deck 9 Underneath cement verandah porch or deck unless both ends are open and the exhaust pipe is installed at least 24 under the deck floor 10 So situated that the flue gases are directed towards brickwork siding or other construction in such a manner that may cause damage from heat or condensate from the flue gases 11 Less than 3 from an inside corner of an L shaped structure including walls and fences 12 Install the warning plate Gas Vent Directly Below 4 feet above the location of the air inlet pipe so it is visible from at least eight 8 feet away Plastic Label included in the Installation Manual Package see figure 3 5 Determining Vent Lengths Use the following chart to determine the maximum amount of vent pipe that can be used This chart calculates sweep and 45 elbows and 90 elbows at 5 equivalent feet Note chart shows allowable equivalent vent lengths for intake and exhaust vents separately thus an M100V operating on Natural Gas can be installed with 105 equivalent feet of intake venting and 105 equivalent feet of exhaust venting IMPORTANT The length of one vent pipe intake or exhaust may not exceed the length of the other vent pipe by more then 20 equivalent feet The three 90 elbows o
45. e the installation is performed in accordance with this instruction manual as well as any applicable local or National installation codes It is also your responsibility to inform the User Owner of their obligation with respect to the above description under User Responsibilities Failure to follow this warning could result in fire serious injury or death ATTENTION LIQUEFIED PETROLEUM LP PROPANE The Matrix is factory set to operate with Natural Gas BEFORE OPERATING WITH PROPANE the specified LP Conversion Kit must be installed to convert the appliance so it will operate safely with LP Propane Liquefied Petroleum LP propane gas is heavier than air therefore it is imperative that your Matrix unit is not installed in a pit or similar location that will permit heavier than air gas to collect Local Codes may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room Check your local codes for this requirement Natural to LP Propane Conversion Kit NTI Series Model Number Kit Number Matrix M100 M100V 82650 1 Failure to use the appropriate Natural to LP Conversion Kit when operating the Trinity Lx with Propane ANGER will result in extremely dangerous burner operation leading to property damage serious injury or death Refer to section titled ATTENTION LIQUEFIED PETROLEUM LP PROPANE for appliance models and corresponding conversion kit numbers Appliance Vent Air I
46. ee natns stra asma a sena sena sena asma ass assa sena sena sna 51 16 0 ANNUAL MAINTENANCE AND 52 110 5 55 HAZARD SYMBOL DEFINITIONS N DANGER Danger Sign Indicates a hazardous situation which if not avoided will result in serious injury or death Warning Sign Indicates a hazardous situation which if not avoided could WARNING result in serious injury or death Caution Sign plus Safety Alert Symbol Indicates a hazardous situation which CAUTION if not avoided could result in minor or moderate injury Caution Sign without Safety Alert Symbol Indicates a hazardous situation CAUTION which it not avoided could result in property damage Notice Sign Indicates a hazardous situation which if not avoided could result NOTICE in property damage T US fran pu US Models ENERGY STAR Matrix Installation and Operation Instructions 0 0 INTRODUCTION General Installation Requirements This document pertains to the correct installation and operation of NTI Matrix appliance models numbers M100 and M100V The instructions detailed in this document supersede any and all previous instructions provided by NTI written or otherwise Each unit is provided with the following 1 Installation and Operation Instructions 2 Matrix Users
47. enum Temperature Limit of 160 F Exceeded DHW Time Out The Control has locked out DHW due to the demand lasting longer than 2 5 hours Boiler Control Error 1 Check for error code on Boiler Control Fan controller has failed to receive 2 Check control wiring from Boiler Control to Fan Control Pins 17 and 18 run status from Boiler Control Fan Control See wiring schematic in Section 8 2 1 Check for 120V to blower ensure door switches are making the circuit AL8 Furnace Blower Error 2 Check wiring from Pin 6 at Fan Control white wire to Pin 15 at blower amp Blower Off Blower has failed to meet a motor minimum speed 3 Check for 24VDC at blower Pin 15 if present replace blower if not replace Fan Control Furnace Blower Error 1 Check wiring from Pin 5 at Fan Control black wire to Pin 16 at blower AL8 Control has failed to sense that the motor amp Blower On blower has reached a minimum 2 Check for 3 5VDC at blower Pin 16 if present replace blower if not replace speed Fan Control Escicotodo v At fan Controller Check Replace 2A fuse blown fuse indicates 24V supply shorted to ground or excessive load The Fenwal controller thinks that there is a flame prior to ignition Indicates Ignition Lockout Fan Controller Blue Face Two Flashes on Fenwal If the combustion sequence is normal and there is no flame prior to ignition the Fenwal control is defective and must be repl
48. es Zone Valves High Temperature Zones Only Valve Zone 3 Zone 2 Zone 1 Zone System Circulator Air Separator NTI Make Up Backflow Water Preventer Pressure Expansion Reducing Tank Valve 19 Matrix Installation and Operation Instructions 6 3 1 B Multiple High Temperature Zones Zone Valves Wiring w Zone Controller 24 VAC 9 OO ZONE 2 ZONE 3 ZONE 4 ZONES ZVC 405 FIVE ZONE ZONE VALVE CONTROL 24 VAC 120 VAC MATRIX TERMINAL STRIP 9 ESIIPLENUM Sensor eSifsensor LENO N O COM 3513 tas em st 000 na2ogg lt lt 686555 amp lt 4 WRE ZONE VALVE POWER OPEN SELF CLOSING DODO LJ imd as zoz System Circulator 4 ERMOSTAT 24V AC Relay Contact 6 3 1 C Multiple High Temperature Zones Zone Valves Wiring w o Zone Controller 24 VAC 23 25 MATRIX TERMINAL STRIP 3 WIRE ZONE VALVES N supe 0 P 690 4 Circulat irculator 3 c 2 OO DG z 2 Hi 5 9 Ne O t OO 24VAC SINGLE POLE DOUBLE THROUGH N O Ne O e End Switch DO
49. esired appliance location is not subjected to flooding or high moisture levels for damage to the appliance will occur voiding your NY THERMAL warranty IMPORTANT CLEARANCES For proper and safe installation adhere to the following clearances to combustibles Furnace Casing 0 Floor Combustible Flue Pipe Boxed in or enclosed 2 In free air 0 The following are the minimum clearances recommended for servicing Front 24 Back 6 optional return plenum location Top 12 Sides 24 Bottom 0 Matrix Installation and Operation Instructions 3 0 VENTING The NY Thermal Matrix is a high efficiency condensing gas furnace boiler utilizing induced power venting Exhaust gases are to be vented directly outdoors using the venting method detailed in this section Under no conditions may this unit vent gases into a masonry chimney unless it is vacant and utilizes Matrix approved venting material as illustrated in the figures in this section Attaching Vent Piping to Boiler It is extremely important for the intake and exhaust piping to be adapted to the appropriate size immediately upon exiting the boiler cabinet The Matrix comes with a 3 male PVC fitting to connect the air intake port of the boiler The Matrix exhaust connection is 3 male PVC use approved cement to connect to venting system Check the flue outlet gasket for proper insertion and sealing prior to and after attaching the venting Ensure the ventin
50. etails EOL 30 100 100 SOH 30 100 100 EOH 30 100 100 2 100 160 125 Set point for desired DHW temperature degrees Fahrenheit rAd 1 2 2 Determines the anticipated supply plenum size For units with the 20x16 Supply Plenum set to 1 For units with the 22 5x18 5 Supply Plenum set to 2 To start the control operation you must return to RUN on the menu and press Function Normal operation will begin Controller will return to RUN mode if no button is pressed for 2 minutes 35 Matrix Installation and Operation Instructions 9 3 Outdoor Sensor Operation The outdoor sensor is connected to the terminal board on the left side of the matrix The two terminals are labeled OUTDOOR SENSOR When the Outdoor sensor is not used or the outdoor temperature is below 0 the Matrix operates at a boiler water temperature equal to the HYD or HI setpoint during a call for Hydronic or Emergency Heat respectively When the sensor is used and the outdoor temperature is above 0 F the Matrix boiler control automatically reduces the operating temperature of the boiler during those calls Using the following formula the control factors in the current outdoor temperature control setpoint HYD or HI and the RES reset setpoint in determining the appropriate operating water temperature Figure 9 2 Outdoor Reset Calculation Formula Operating Temperature RES Outdoor Temp x HYD RES RES RES Note Subst
51. f the exterior vent piping two outlet and one inlet do not have to be included as they are taken into consideration in the vent calculations Propane Gas LP maximum vent length cannot exceed 50 equivalent feet Table 3 2 Maximum Vent Length vert au Max Size wh 3 T2 4 L7 100 3 Natural 105 100 95 90 85 75 70 65 60 MIN 11 _Matrix Installation and Operation Instructions 3 6 Outdoor Venting Vent piping outside the building is permitted under the following Figure 3 6 Outdoor Venting conditions o The maximum length outside the building is 20 feet Outdoor length must be included in the overall vent length calculation o All normal termination clearances are maintained o exterior exhaust vent pipes are insulated with 3 5 ID thick Closed Cell Foamed Polyolefin Tubing i e Tundra Seal Plus or equivalent o The pipe is supported every 24 o exhaust and inlet are sloped back to the boiler 4 elevation for every foot Supports every 24 Exhaust Maximum of 20 feet is permitted for outside a building using 3 pipe ONLY 12 plus allowance above rade for snow Apply Plate Here o Gas Vent Directly Below o Keep Free of Obstructions 12 Matrix Installation and Operation Instructions 4 0 CONDENSATE DRAIN This unit produces water as a product of combustion Much of this water conden
52. g system does not apply a load or stain on the flue outlet of the boiler recommend using two elbows to create a swing joint as shown above Figure 3 1 Venting Construction E It is recommended that two elbows be used so that the slope of the horizontal exhaust vent does not affect the vertical plumb of the pipe connected to the boiler Slope all horizontal indoor exhaust venting 14 to 2 per linear foot It is recommended to have a collection point for condensation in the intake venting Condensation can then be drained to an open house drain or condensate pump Drain line from intake must have an appropriate trap or shut off valve to avoid siphoning IMPORTANT The vent connection and piping must be perfectly aligned to the furnace connection AND MUST NOT APPLY ANY WEIGHT OR LATERAL FORCE TO THE FLUE BOX NTI does not warranty damages to the flue box In Canada the first 3 ft 915 mm of vent piping must be readily accessible for inspection NOTICE Matrix Installation and Operation Instructions 3 1 Vent Air Intake Pipe Material Table 3 1 Acceptable Vent and Air Intake Pipe Material Installation Standards United States Canada WARNING Vent Pipe and DWN ANSI ASTM D2265 All venting material in All plastic Vent materials Fittings PVC Schedule 40 ANSI ASTM D1785 Canadaanust be installed on gas fired CPVC S
53. hapter 10 entitled Equipment Not Required To Be Vented in the most current edition of NFPA 54 as adopted by the Board and 2 Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling building or structure used in whole or in part for residential purposes Next Page Matrix Installation and Operation Instructions Continued c MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment the instructions provided by the manufacturer for installation of the equipment and the venting system shall include 1 Detailed instructions for the installation of the venting system design or the venting system components and 2 complete parts list for the venting system design or venting system d MANUFACTURER REQUIREMENTS GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases but identifies special venting systems the following requirements shall be satisfied by the manufacturer 1 The referenced special venting system instructions shall be included with the appliance or equipment installation instructions and 2 The special venting system
54. ht any appliance Do not touch any electric switch Do not use any phone in your building mmediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions f you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water OPERATING INSTRUCTIONS 1 STOP Read the safety information above very carefully 2 Setthe thermostat to lowest setting Turn off all electric power to the appliance 3 This appliance does not have a pilot It is equipped with an ignition device which automatically lights the burner Do not try to light the burner by hand 4 Turn the manual gas valve to the OFF position Remove front access panel 5 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety information above If you don t smell gas go to the next step 6 Turn the manual gas valve ON Wait an additional five 5 minutes smelling for gas 7 Replace the front access p
55. ical leads to the Hot Surface Ensure the cables are placed in a fashion where they will not arc to ground or other conductor Turn power on to the appliance and apply a heat demand Allow for 3 complete trials for ignition consisting of pre and post purge of the combustion blower until an ignition lockout occurs Repeat the process two more times i e 9 complete ignition sequences in total Turn power off and reconnect the electrical leads to the Igniter Matrix Installation and Operation Instructions 3 2 Venting Configurations 3 2 1 Two Pipe Vent Termination Figure 3 2 Two Pipe Vent Termination Window The vertical portion of the exhaust termination does not require insulation Exhaust if less than 5 feet in total length f c i Apply Plate 4 p Ms Gas Vent Directly Below Exhaust SN 1 1 Kaen Free of Obstructions 36 mpi Coupling Xe Y 1 ZONE ME 12 Plus Snow allowance Exhaust f elbow to be le 12419 31 yp against wall yo ee ee pe Intake aS 18 play is ademit 7 A 1j acceptable Vane p 2 INN IN Must insert 47 12 or greater plastic bird pud than 36 sereen Outside Wall Y P d 4 12 Plus Snow i Allowance Min 3 2 2 Concentric Vent Termination No longer approved for Canada Figure 3 3 Concentric Vent Termination Apply Plate Here Support Field inst
56. ily at the minimum stage This computation hunts for the heat loss of the dwelling based on the reaction of the thermostat to the rise and fall of the space temperature and the heat cycle rate of the thermostat If at any time the plenum temperature exceeds 160 F the boiler will stop supplying heat until the temperature in the supply plenum drops below 140 F during which time an AL2 error message will be displayed ATTENTION The burner will remain on and the Matrix will provide heat when the thermostat is off This is normal and is required to provide constant efficient heat 37 Matrix Installation and Operation Instructions Call for Heat 24VAC W1 Normal Thermostat call Matrix operates as a step modulating furnace as described above If HRV set to ON HRV will operate at the low continuous ventilation rate Call for Auxiliary Heat 24 VAC W2 When calling furnace will provide heat at a stage 10 output rate With a call for auxiliary heating the Matrix will function as a single stage full fire appliance This means the burner will come on with a thermostat call and go off when the call is satisfied If HRV set to ON HRV will operate at the low continuous ventilation rate Outdoor Sensor The auxiliary heating function 24VAC W2 will utilize the outdoor sensor if available The outdoor reset function is not used for W1 heating This function is also active during a hydronic heat demand 24V AC
57. in defrost mode 20 DUET NOTE High Humidity Indicates a call for high ventilation of HRV 33 Matrix Installation and Operation Instructions 9 2 Operation and Set up The Matrix employs a pneumatic modulation system This modulation system increases or decreases the velocity of the combustion blower to meet the demand for heating The gas valve senses this change in blower pressure and introduces the required amount of gas to ensure correct combustion The Sentry reads the boiler water temperature compares it to the set point and adjusts the burner firing rate accordingly by varying the speed of the combustion blower The Blue Fan Controller communicates the appropriate demand and temperature set point to the Red Boiler Controller via a series of digital and analog inputs Table 9 3 shows the Boiler Controller s response to the demand For more information on RESET see section 9 3 Outdoor Sensor Operation Table 9 3 Conventional vs Outdoor Reset Mode Primary Auxiliary Shared Call J PN a Forced Air Forced Air Forced Plies d 4 Call 1 Call W2 Air Hydronic ree Storage Storage Aux Heat Shared W1 W2 Domestic A Condition Off On Heat W1 W2 and H Hydronic Call Only gt Set Point 160 spre t HYD e Q Burner On 2 140 gp iced ad HYD DIF H20430 Burner Off 180 210 2
58. ine to insolate the vibration noises between the gas valve and the line Don t hang gas lines from floor joists Use rubber insulators with gas line supports If gas valve is not held when the gas nipple is connected the force of tightening the fitting can damage the valve and warp the fan housing If pipe is used the gas line must not create any forces to the valve either vertically weight of line or horizontally misaligned connection The following are the thermistor curves for diagnosing the water and outdoor air sensors Measure the resistance of the thermistor when disconnected Using the appropriate chart find the resistance and move either vertical water probe or horizontal air probe until the line is intersected Move 90 degrees to the corresponding temperature If the temperature is plus or minus 10 degrees then the probe is operating correctly 48 Matrix Installation and Operation Instructions Figure 13 1 Matrix Thermistor Resistance Chart 1 Mohm Water Probe Low Temp Cm 50 60 70 80 90 100 110 120 130 140 Water Temperature F n m A Ny A N a a Resistance Mega Ohms N 91 Figure 13 2 Matrix Thermistor Resistance Chart 1 Mohm Water Probe Hi Temp 120 100 5 80 6 5 40 9 20 0 160 170 180 190 200 210 220 230 Water Temperature F Figure 13 3 Outdoor 10K p
59. is is not a warranty issue Solution 1 2 If the Burner light on the Burner Red Control is going out go to Burner shutting off Check condensate drain for blockage and check the inlet piping for ingested snow or water if the flame rod gets wet it may need to be replaced Check for resistance from flame rod to ground must be an open circuit O L if not remove rod and bend it away from the burner slightly Check for proper polarity of line and neutral wiring to the boiler Ensure the plumbing is as shown in manual Check to see if pumps are operating properly and water pressure is above 15psi This problem can lead to boiler overheating Boiler may be plugging with scale or magnetite clean with Fernox DS 40 Descaler and Cleanser NTI PN 83450 If glycol is being used the concentration may be to high recommend using a concentration lower then 35 Ensure that the venting lengths are in compliance with Section 3 4 Ensure that the line pressure during operation does not drop more than 20 from the static line pressure Momentarily remove the intake vent from the boiler during ignition if unit lights smoothly with intake vent disconnected reconnect and check for proper combustion if unit maintains smooth operation after ignition See Section 5 2 Calibrate for proper combustion If problem persists contact NY Thermal Heat exchanger may be dirty remove burner door and inspect clean if necessary Use flexible gas l
60. itute HYD for HI during a call for Emergency Heat Example e There is a call for Hydronic heat therefore the control uses the HYD programmed setting The HYD is programmed to be 160 F The RES is programmed to be 85 F outdoor temperature is 40 F Operating Temperature 85 40 x 160 85 85 85 125 F The following chart illustrates the effect of changing outdoor temperature on the boiler operating temperature for the above example Reset Curve for Res 85 amp Setpoint 160 T a E o E 5 10 20 30 40 50 60 70 80 90 Outdoor Temperature deg F 36 Matrix Installation and Operation Instructions 10 0 MATRIX BLOWER OPERATION 10 1 Forced Air Heating The Matrix forced air heating module is a step modulated system which provides varying heat output rates by adjusting air flow and water temperature through a fan coil Table 10 1 Fancoil Output Chart Heat Profile 1 PF1 Heat Profile 2 PF2 Heat Profile 3 PF3 ie CFM E E Btu Hr Out CFM EE TE Btu Hr Out CFM a eu Eg Btu Hr Out 1 400 108 104 14000 400 108 104 14000 400 108 104 14000 2 550 110 104 19000 550 110 104 19000 550 110 104 19000 H 3 670 113 105 24000 670 113 105 24000 670 113 105 24000 lt 4 720 117 108 27700 730 122 112 31500 750 128 116 35500 760 120 110 31400 790 131 118 39100 820 141 125 47100 53 6 810 124 112 3
61. ix Fan Control Just as the Matrix Boiler Controller controls all of the operation and safety functions of the boiler the Matrix Fan Controller controls all of the operation and safety functions related to air handling and hot water dispatching The fan controller controls the forced air modulation ventilation as well priority of domestic hot water and secondary heating systems Table 9 5 Matrix Fan Control Programming Menu Level Description Main Sub Value Default RUN When Run is displayed controller is in Prog mode Arrow up or down to scroll through menus OFF HRV Mode Always off unless call for high ventilation DH HRV ON HRV Mode Continuous Ventilation HRV will exchange air at low ventilation ON rate during a call for forced air heat W1 or W2 or continuous circulation G Will increase to high ventilation rate with a high ventilation call 24vac DH PF1 Heat Profile 1 400 to 1000CFM 50 000 Btu h max HEA PF2 PF1 Heat Profile 2 400 to 1100CFM 77 000 Btu h max PF3 Heat Profile 3 400 to 1200CFM 105 000 Btu h max Y1 40 Y2 80 Stage 1 AC HP Flow x 10 settable from 400 up to Y2 1600 max Y2 Y1 160 120 Stage 2 AC HP Flow x 10 CFM settable from Y1 400 min up to 1600 FAN 40 160 40 Fan circulation rate G x 10 CFM settable from 400 to 1600 SCL 30 100 60 ECL 30 100 60 SCH 30 100 60 BAL 1 e HRV Balancing see HRV section for more d
62. kage on the intake and exhaust vents blower turns It can occur 2 5 M Air Switch 5 3 If fan is running the air switch be faulty ensure it is set at 0 2 wc momentarily during normal ee operation A problem is indicated 4 is not running check 120V wiring to blower if ok remove low voltage p ASO is displayed harness from blower if blower fails to start replace blower if blower does continuously start the problem may be with blower or Controller This is displayed when the boiler 1 Does the combustion fan run continuously at full speed while the error is has turned the blower off and is displayed If so check for 24V from transformer also check transformer ASC expecting the air switch to be fuse If 24V is present check the low voltage wiring from Controller to Air Switch open It can occur momentarily combustion blower replace Controller or Blower Closed during normal operation A 2 Is the combustion fan off If so check for water in the air switch and air problem is indicated when ASC is switch tubes replace switch if necessary displayed continuously 3 Check venting termination with required venting described in manual Excessive noise current or Controller 2 Locks up voltage spikes in the 120V power Contact NTI supply 1 Check for 120V between terminals L1 and L2 2 f 120V exists turn power off and remove line voltage harness from Control Then check for resi
63. nd at the back of the combustion chamber contain Refractory Ceramic Fibers and should not be handled without personal protective equipment IN WARNING Potential Carcinogen Use of Refractory Ceramic Fibers in high temperature applications above 1000 C can result in the formation of Crystalline Silica cristobalite a respirable silica dust Repeated airborne exposure to crystalline silica dust may result in chronic lung infections acute respiratory illness or death Crystalline silica is listed as a potential occupational carcinogen by the following regulatory organizations International Agency for Research on Cancer IARC Canadian Centre for Occupational Health and Safety CCOHS Occupational Safety and Health Administration OSHA and National Institute for Occupational Safety and Health NIOSH Failure to comply with handling instructions in Table 14 1 may result in serious injury or death A WARNING Crystalline Silica Certain components confined in the combustion chamber may contain this potential carcinogen Improper installation adjustment alteration service or maintenance can cause property damage serious injury exposure to hazardous materials or death Refer to Table 14 1 for handling instruction and recommended personal protective equipment Installation and service must be performed by a qualified installer service agency or the gas supplier who must read and follow the supplied instructions before installing servicing
64. ng Heat Pump Input Stage 2 Input requiring 24VAC from terminal R to initiate a demand for stage 2 cooling or heat pump Switch is made using an isolated end switch dry contact normally incorporated in W2 Me the home thermostat CFM rate adjustable via Y2 setting in the blue Fan Controller see Table 9 5 Note Y2 demand overrides a Y1 demand NC Hydronic Heat Lockout Relay Contacts The Matrix Fan control incorporates a Normally Closed NC anda COM Normally Open NO relay contact that switches position on a demand for DHW The contacts are to be used to NO lockout the Hydronic Heat draw during concurrent DHW demands in order to maintain DHW priority Maximum switching capacity of 2 Amps at 24VAC 24VAC Common Neutral for the 24VAC power supply from the Matrix This contact can be used in conjunction 24V with terminal R to provide a power source for a digital thermostat NOTICE 24V COM to the A C Condenser Unit must be broken by the Matrix AC Freeze stat included with the installation package see Figure 8 2 30 _Matrix Installation and Operation Instructions 8 2 Matrix Factory Wiring Schematic 8 2 1 Boiler Control Wiring Consult diagram on unit for exact wire routing FENWAL 31 Matrix Installation and Operation Instructions 8 2 2 Fan Control Wiring Consult diagram on unit for exact wire routing 3ATVA A 19
65. nsferTube Magnehelic 0 25 inwg or Digital Manometer Men ES Sample HRV Installed Installed item Description Ventilation Ventilation Fan Rates Rates Speed EOH HRV Exhaust at Override high ventilation rate balanced during High air 120cfm circulation rate 800 1000 1200CFM 55 L s SOH HRV Supply at Override high ventilation rate balanced during High air 120cfm circulation rate 800 1000 1200CFM 55 L s EOL HRV Exhaust at Override high ventilation rate balanced during Low air 120cfm circulation rate 300 400 500CFM 55 L s SOL HRV Supply at Override high ventilation rate balanced during Low air 120cfm circulation rate 300 400 500CFM 55 L s ECH HRV Exhaust at Continuous low ventilation rate balanced during High air 70cfm circulation rate 800 1000 1200CFM 30 L s SCH HRV Supply at Continuous low ventilation rate balanced during High air 70 circulation rate 800 1000 1200CFM 30 L s ECL HRV Exhaust at Continuous low ventilation rate balanced during Low air 70 circulation rate 300 400 500CFM 30 L s SCL HRV Supply at Continuous low ventilation rate balanced during Low air 70 circulation rate 300 400 500CFM 30 L s 43 Matrix Installation and Operation Instructions 12 0 LIGHTING BOILER Before Start up refer to Mandatory Pre commissioning Procedure for Plastic Venting in Section 3 0 A Deag Failure to follow these instructions
66. ntake Piping N DANGER The Matrix is a Direct Vent appliance requiring a Special Venting System Vent and Combustion Air Intake piping must be piped to the outdoors using the vent material and rules outlined in these instructions Failure to follow instructions will result in serious injury or death 2 Matrix Installation and Operation Instructions 1 0 SPECIFICATIONS Table 1 1 General Specifications DOE Net CSA 5 FES DOE Supply Return Airflow Airflow cm Dimensions Model Input poe Een AFUE Plenum Plenum Heating Cooling H W D rd MBH MBHS MBH 95 inches inches CFM CFM inches M100 25 150 136 118 95 1 22 5x18 5 18x18 400 1200 400 1600 53 28 38 3 M100V 25 150 136 118 95 1 22 5x18 5 18x18 400 1200 400 1600 70 150 53 28 38 3 Notes 1 Listed Input and Output ratings are at minimum vent lengths at Sea Level Numbers will be lower with longer venting and or altitudes greater then 2000 feet 2 The maximum output when operating on LP Gas is limited to 145MBH 3 Based on rating plate input capacities using standard test procedures prescribed by the U S Department of Energy Ratings have been confirmed by AHRI GAMA 4 Matrix units require a special venting system use only vent materials and methods detailed in these instructions 1 1 High Altitude Operation Figure 1 1 Maximum Capacity vs Altitude The Ma
67. o capacity by 25 seconds Once running the unit can provide an endless amount of hot water If the flow is momentarily turned off for whatever reason the unit will turn off Once off the unit must relight and not provide heat for 45 75 seconds This will cause cold unheated water to pass through the unit and advance through the domestic plumbing between the previously heated hot water and the new hot water This can be mistaken for an inability to adequately heat the water Storage Feature 500 For improved domestic hot water comfort the Matrix incorporates a Storage feature This storage feature when enabled will keep the boiler water hot for a period of 1 to 24 hours following a call for domestic hot water See Section 9 2 1 for setting When the boiler water drops below 140 F the boiler will fire and bring the boiler to 180 F before shutting off This Storage feature helps in reducing the wait time associated with a tankless hot water system In systems where a storage tank is used See Figure 7 2 this feature should be disabled e g set to OFF 25 Matrix Installation and Operation Instructions Procedure for Setting up Domestic Hot Water If the Matrix is being installed in an application that uses municipal water often the pressure is high enough to generate flow rates at the faucets that will exceed the appliances capacity to heat it See the following table to determine what flow can be expected at various inle
68. o screens are provided in the package 12 It is extremely important that the intake and exhaust piping be adapted to the appropriate size immediately upon exiting the boiler cabinet 13 All interior vent pipe shall be supported a minimum of every 36 10 Matrix Installation and Operation Instructions 3 4 Venting Clearances These are code restrictions for the location of the Flue gas vent terminal Compliance doesn t insure a satisfactory installation good common sense must also be applied The vent terminal shall not terminate 1 Directly above a paved sidewalk or a paved driveway that is located between two buildings and that serves both buildings 2 Less than 7 feet above grade where located adjacent to a paved walkway or driveway located on public property 3 Within 3 three feet of a window or door that can be opened or non mechanical air supply inlet to any building 4 Within 6 of a mechanical air supply inlet to any building or roof eve containing soffit openings 5 Above a meter regulator assembly within 3 horizontally of the vertical centerline of the regulator 6 Within 3 horizontally of any gas service regulator vent outlet up to a height of 15 7 Less than 30 plus snow allowance above grade or any surface that will support snow ice or debris The exhaust must be a minimum of 18 above the air inlet and the air inlet must always be a minimum of 12 plus snow allowance above any surfac
69. o the rear fitting of the Brazed Plate Heat Exchanger The hot Outlet line flows directly from the front fitting of the Brazed Plate Heat Exchanger See Figures 7 1 and 7 2 for installation details Thermostatic Mixing Valve A Sparcomix AMIOI US 1 is provided with your package This valve regulates the water temperature leaving the plate heat exchanger and must be used in every instance The dial can be set to the desired temperature required Consult the Honeywell manual SD IS 50 for detailed instructions and settings Note the valve must be set to a supply temperature of not more then 120 F It is the responsibility of the installer to set the valve and remove the dial WARNING IF THE ANTI SCALD VALVE IS NOT INSTALLED TO THE HONEYWELL SHEET SD IS150 AND THIS MANUAL OPERATION MAY SUPPLY SCALDING HOT WATER TO THE OCCUPANTS Y Strainer Supplied To protect the Matrix s internal flow meter it is important to install the factory supplied Y Strainer in the location shown in Figures 7 1 and 7 2 dirt and other debris can cause the flow meter to malfunction Check Valve A check valve must be field provided and installed on the outlet of the mixing valve to prevent expansion devises down stream from back flowing when the water pressure drops during cold water draws Failure to prevent the backflow will cause water to flow forward through the flow switch activating it when the cold water draw has ended and the water pressure increases
70. oblem Solution 1 If the boiler is extremely hot check for adequate water pressure and Water Temperature Excessive circulation contact NTI for assistance 1 Sentry has sensed a water 2 If not hot check for sources of grounding or shorting at the Water Sensor temperature in excess of 250 F at electrical connections check wiring from Sensor to Boiler Red Control the Water Sensor 3 Replace Water Sensor if the resistance is not in the correct range See thermister resistance charts in Figures 13 1 and 13 2 Water Sensor Short Circuit ER2 Control has sensed a short circuit See ER1 in the Water Sensor circuit 1 Check wiring to Water Sensor for open circuits or shorting to ground Note will be displayed if temperature sensed is less then 0 F 2 Replace Water Sensor if the resistance is not in the correct range See thermister resistance charts in Figures 13 1 and 13 2 1 Reset power if error goes away the problem is intermittent and was likely caused by a tripped limit that has automatically reset check for adequate water pressure and flow rate Allow the boiler to cycle and verify proper operation including outlet water temperature and flue temperature If operation is unsuccessful and the error reoccurs 2 Matrix boilers are equipped with a low water pressure switch on the boiler return that requires a minimum of 10PSI to complete the 24VAC ignition circuit Ensure the field installed pressure gaug
71. produce near constant flow provided horsepower or maximum speed of motor is not exceeded 38 Matrix Installation and Operation Instructions 11 0 HEAT RECOVERY VENTILATION 11 1 Ventilation Needs With the evolution toward more energy efficient tighter homes air quality problems have increased With less natural ventilation pollutants such as pet dander humidity tobacco smoke and wood ash now become trapped inside the home Mechanical ventilation is the process of exhausting the polluted air from the space and replacing it with fresh air from outside The amount of ventilation required varies from home to home and can be estimated using one of the following methods 11 1 1 Room Count Calculation aA Number of Living Space Rooms CFM L S CFM Req d Master Bedroom x 20 cfm 10 L s With Basement x 20 cfm 10 L s Without Basement Single Bedroom x 10 cfm 5 L s Living Room x 10 cfm 5 L s Dining Room x 10 cfm 5 L s Family Room x 10 cfm 5 L s 51 x 10 51 6 _ oom Other Kitchen x 10 cfm 5 L s Bathroom x 10 cfm 5 L s Laundry Room x 10 cfm 5 L s Utility Room x 10 cfm 5 L s Total Ventilation Requirement sum last column 11 1 2 Air Change per Hour Method Total cu ft x 0 3 60 Total Ventilation Required Example A 25 x 40 house with basement 1000 sqft x 8 high x 2 main floor and basement
72. r nozzle to direct pressurized water through the gaps between the heat exchanger tubes The water should pass in between the heat exchanger tubes and exit via the condensate drain This process may require the use of some dry rags or plastic to protect electrical components from being damaged by dripping or spraying water OO 000 02 O 6 Usea nylon or other non metallic brush to loosen the incrustations and any other contaminates that have remained stuck on and in between the tubes O 7 Repeat steps 5 and 6 until the heat exchanger is clean and water from the condensate drain runs clear O 8 Re install the insulation disc part no 83112 to the back of the combustion chamber O 9 Inspect the insulation disc located on the back side of the burner door p n 82769 Replace if damaged 10 Re install the burner door gas supply and Air inlet pipe check for gas leaks 13 Perform the Operational Check List detailed in Section 13 0 Replace any gaskets or insulation discs that show any signs of damage and do not re use Failure to WARNING follow these instructions may result in fire property damage or death 52 Matrix Installation and Operation Instructions Refractory Ceramic Fibers RFC Personal Protective Equipment Recommended Read the following warnings and handling IMPORTANT instructions carefully before commencing any service work in the combustion chamber The insulating material on the inside of the burner door a
73. rix Installation and Operation Instructions 15 0 INSTALLATION CHECKLIST Installation O 1 Ifoperating on Propane Gas convert appliance using kit number 82650 1 2 Install the Vent Air Intake piping in accordance with Sections 3 0 this manual Ensure all joints are secured and cemented properly Both the Vent and Air Intake pipes must terminate outdoors Perform the Mandatory Pre commissioning Procedure for Plastic Venting in Section 3 1 O 3 Connect the condensate drain in accordance with Section 4 0 of this manual O 4 Connect the gas supply in accordance with Section 5 0 of this manual O 5 Install the plumbing in accordance with the Sections 6 0 and 7 0 of this Manual Flush cleanse the internals of the heating system hydronic piping of hydronic systems only Treat system water with Fernox F1 Protector O 6 Connect field wiring in accordance with Section 8 0 of this manual O 7 Advise home building owner of their responsibilities with respect to maintaining the appliance The building owner is responsible for keeping the Vent Air Intake termination free of snow ice or other WARNING potential blockages and for scheduling routine maintenance on the appliance see Section 16 0 Failure to properly maintain the appliance may result in serious injury or death Start up Allow primers cements to cure for 8 hours prior to Start up If curing time is less than 8 hours first AN DANGER perform Steps 2 through 6 of Mandatory Pr
74. robe 100 80 60 40 20 Resistance Kilo Ohms 100 75 50 25 0 Temperature F 49 Matrix Installation and Operation Instructions 14 0 SEQUENCE OF OPERATION Figure 14 1 Matrix Boiler Control Sequence Of Operation Boiler in standby mode 120v Power Applied Displays version b1 0 Furnace Control closes T C circuit Awaiting Input From Furnace Control at Contacts A C T Furnace Control closes A C and T C circuit Hydronic Demand Forced Air Demand Energizes Internal Circulator C1 Closed ak cse i EC RN Sentry 2100 Sentry 2100 VDC Signal to Combustion Sentry 2100 Pas Combustion Blower Starts SFS 80 1 1 N B fe Sete Ss Sess eee Closed 1 Power to Ignitor 120V to S1 0 Igniter warm up 5 seconds Checks Flame Probe Signal Power to Gas Valve Sentry 2100 modulates combustion blower based upon setpoint and programing Greater than 1 0 uAmp 50 Furnace Control closes A C circuit DHW Demand Water Temperature Limit amp Flue Gas Temperature Limit amp Water Pressure Limit Check Three Retries for Flame Less than 0 6 uAmp Call for flame ends Mat
75. s shall be Product Approved by the Board and the instructions for that system shall include a parts list and detailed installation instructions e A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment all venting instructions all parts lists for venting instructions and or all venting design instructions shall remain with the appliance or equipment at the completion of the installation ATTENTION LIQUIFIED PETROLEUM LP PROPANE The Matrix is set to operate with Natural Gas LP Conversion Kit Part No 82650 1 is included with each furnace and must be installed before operating with Propane Liquefied Petroleum LP propane gas is heavier than air it is imperative that your boiler is not installed in a pit or similar location that will permit heavier than air gas to collect Local Codes may require appliances fueled with LP gas be provided with an approved means of removing unburned gases from the room Check your local codes for this requirement 2 1 Location In all cases the Matrix must be installed indoors in a dry location such that the gas components are protected from dripping or spraying water or rain during operation and servicing The boiler location ambient temperature is maintained to a minimum of 50 F Determine the best location of the vent termination and if possible locate the appliance as close to the termination point as possible Ensure that the d
76. s installed in systems with hydronic heat Low Water Cutoff A certified LWCO is not provided in the package however one is to be field installed in any application where the Matrix boiler is located above the radiation or where local authorities require it Ensure that the water line of the Low Water Cutoff is at least 6 above the top of the boiler It is recommended that the LWCO be situated so that it can be tested without removing water from the Matrix Tri cocks and a gauge glass are highly recommended NTI recommends against the installation of isolation valves between the LWCO and the Matrix Use the normally open contacts of the LWCO to break 24V to the burner circuit See Wiring Diagram CAUTION DAMAGE WILL OCCUR IF THE BOILER IS FIRED WITH NO WATER IN IT OR REPETITIVE NO FLOW OPERATIONS WHICH WILL VOID THE WARRANTY 17 Matrix Installation and Operation Instructions 6 2 Matrix Boiler Connections Figure 6 1 Boiler Feed Water Connections Standard Configuration Optional Hydronic Add On Relief Valve ae Relief Valve 7 D supplied supplied Boiler Feeder Valve supplied gt Backflow Air Scoop Preventer Hot Supply lt lt x 9 Boiler Feeder Sc Valve supplied BS Cold Return Drain Valve Backflow A 5 S N Expansion Tank IMPORTANT Expansion tank and air removal device for the internal functions of the Matrix are included and provi
77. ses on the heat exchanger and in the venting system All exhaust piping must be on a slope back to the boiler 4 per linear foot of vent Steps must be taken to ensure that condensate does not collect in the venting system Condensate must be drained from the boiler into a household drain FAILURE TO PROPERLY CONNECT THE CONDENSATE LINE WILL CAUSE COMBUSTION GASES TO ENTER THE ROOM POSSIBLY CAUSING SERIOUS INJURY TO OCCUPANTS OR DEATH Note check with your municipality or local gas company to determine if disposal Figure 4 1 Condensate Drain Plumbing of combustion condensate is permitted In the State of Massachusetts the Condensate condensate must be neutralized prior to entering a drain Drain From Boiler The following are important notes that must be taken into consideration when Ju 4 constructing the condensate system n o DO NOT run condensate line outside A frozen or blocked drain will cause the 4 condensate to fill the combustion chamber This will result in a no heat j condition as the unit will shut down and damage to the flame sensor components can occur o NEVER use copper steel or galvanized piping in the construction of the condensate system condensate is very corrosive and will wrought most metals o When condensate pump is used or required select a pump that is designed for residential furnaces Drain must be open to allow overflow if C blocked Drain must include tr
78. slope back to the boiler a minimum of 4 per linear foot of vent For applications where excessive condensation is possible gt per linear foot is recommended See illustration in Figure 3 1 6 Exhaust vent pipe can be secured to the wall for more rigidity 7 In all roof applications the discharge must point away from the pitch of the roof Figure 3 5 Installing Venting Below Grade 8 Install adequate flashing where the pipe enters the roof to prevent water leakage 9 Install and seal a rain cap over existing chimney openings in vacant chimney applications 10 For installations that exit the wall below grade Excavate site as shown in Figure 3 5 to a point below where the pipes are to exit Ensure that the wall is fully sealed where the pipes penetrate the wall The vent piping MUST be secured to the side of the building above grade as shown to provide rigidity NTI provides a mounting bracket PN 82075 for securing the exhaust pipes Ensure that the vent clearances are maintained Inlet minimum 12 plus snow allowance from grade exhaust outlet 18 minimum above inlet 11 Install the vent screens provided into both the inlet and exhaust vent terminal elbows The screen must be on the outside of the last elbow Install the screen into the female opening of the elbow Then cut a small piece of pipe to sandwich the screen into the elbow NOTE be sure that the small piece of pipe cut does not extend past the end of the elbow Tw
79. stance between L1 and L2 of control if the circuit is open onse No power ar Gonia O L the internal fuse has blown Check for shorts in wires leading to circulator prior to replacing controller Note If fuse is good the circuit will read between 300 and 400 Ohms 3 f 120V not present check wiring and for 120V at source 46 Matrix Installation and Operation Instructions Symptom Detected Problem Communication Error with HRV Check wiring connections between HRV and Fan Controller Check door switch on HRV Cycle power to appliance contact NTI If plenum is hot check operation of blower fan contact NTI If plenum is not hot check plenum sensor and wiring for shorts or damage Remove plenum sensor PSO should be displayed if so replace plenum sensor if not inspect wiring from Terminal Strip to Fan Control Replace Fan Control if necessary Reset the AL5 error by resetting the power or cycling the DHW call Check for proper operation of the DHW call Matrix units are provided with an integrated DHW flow meter if the control is registering a flow rate when the water is turned off disconnect the electrical lead to the flow meter If the indicated flow rate drops to 0 replace flow meter if not replace fan controller Ensure nothing is connected to the FS terminal of the terminal strip unless using a DHW tank aqua stat to trigger a demand check operation of aqua 1 2 3 1 2 3 Pl
80. t or combination of units lights or runs Always use a pipe threading compound that is resistant to propane LP gas solvent action Use sparingly to all male threads starting at two threads from the end Over doping or applying dope to the female end can result in a blocked gas line DO NOT TIGHTEN FITTINGS WITHOUT SUPPORTING THE GAS VALVE as damage to the valve or motor can occur Install a manual equipment Shut Off Valve as shown Valve must be listed by a nationally recognized testing lab 5 2 Testing and settings Gas line and regulator s must be able to support a line pressure at the gas valve of 4 9 w c for Natural Gas and 9 12 w c for LP while running at maximum rate Matrix gas valves are equipped with two bleed ports to measure Line and Manifold pressure Note Line pressure adjustments can only be made at the gas regulator NOT AT THE GAS VALVE 4 WARNING IF LINE PRESSURE EXCEEDS PSI 14 INCHES W C COMPLETELY DISCONNECT LINE TO GAS VALVE THIS EXCESSIVE PRESSURE CAN DAMAGE VALVE CAUSING A LEAK RESULTING IN FIRE OR EXPLOSION 14 Matrix Installation and Operation Instructions The gas valve is equipped with a throttle input adjustment Figure 5 2 Setting Combustion screw The input screw MUST NEVER BE ADJUSTED without verifying proper combustion with a calibrated combustion analyzer Manifold Input Screw Line Pressure CAUTION The Matrix is tested with Natural Gas having a heating value
81. t and outlet water temperatures Table 7 1 Matrix DHW Flow Rates flow rates in usgpm Inlet Water Temperature deg F 40 45 50 55 60 65 70 110 3 9 4 2 4 5 4 9 5 4 6 0 6 7 5 115 3 6 3 9 4 2 4 5 4 9 5 4 6 0 5 120 3 4 3 6 3 9 4 2 4 5 4 9 5 4 z 125 3 2 3 4 3 6 3 9 4 2 4 5 4 9 130 3 0 3 2 3 4 3 6 3 9 4 2 4 5 135 2 8 3 0 3 2 3 4 3 6 3 9 4 2 140 2 7 2 8 3 0 3 2 3 4 3 6 3 9 To avoid having too much flow at the faucets use the throttling valve located at the Cold Supply in Figure 7 1 to limit the overall flow of domestic hot water Follow these instructions to achieve the best delivery of DHW o Open throttle valve fully o dial on the mixing valve to the desired setting do not exceed 120 F o Create the maximum amount of DHW flow that is likely to occur on a regular basis Usually tub faucet or choose two other faucets o Allow the boiler to reach steady state and then throttle the shut off valve until the hot water exiting the plate heat exchanger is slightly warmer than the mixed water exiting the mixing valve Ensure the boiler 1s firing at the maximum rate if not increase the H20 setting and repeat this step It 1s beneficial to keep the H20 setting as low as possible to limit short cycling and maintain efficiency If the flow rates listed in Table 7 1 are not high enough for the application install a storage tank with re circulating loop as per
82. th this demand the forced air system is given priority The set point temperature will be the higher of the HYD setting or the forced air set point During a shared call the hydronic system can only receive the water temperature returning from the fan coil If during a shared call the boiler can not supply enough heat to maintain a minimum plenum air temperature of 95 F the Fan Controller will shut off the hydronic loop using the N O N C contacts on the terminal board until the forced air temperature recovers The Matrix has a Grundfos 15 42 built into the primary loop Given the head loss of the primary loop the flow rate is fixed at 5 gpm When designing any secondary heating system it is important to allow for an increase boiler set point to ensure full capacity of the secondary system This may necessitate the use of mixing valve to protect the secondary from elevated water temperatures Example For a 75 000 Btu hr secondary system with a desired water temperature of 110 F and 20 AT the flow rate will required is BTU hr 500 AT or 75 000 500 20 7 5 gpm Since this exceeds the flow rate in the primary loop a higher boiler AT will be required to maintain the desired 110 F This is calculated as follows ATboiler ATsecondary gpMgecondary PMprimary 20 7 5 5 30 F Adding the ATboiler to the return water temperature of 90 F 110 F 20 F gives a required HYD set point of 120 F 6 3 1 A Multiple High Temperature Zon
83. tive equipment handling and disposal of RCFs For more information on Refractory Ceramic Fibers the risks recommended handling procedures and acceptable disposal practices contact the organization s listed below Canada CCOHS Telephone directory listing under United States OSHA Telephone directory listing under Government Blue Pages Canada Health and Safety United States Government Department of Labor Canadian Centre for Occupational Health and Safety or Occupational Safety and Health Administration or website website http www ccohs ca http www osha gov 53 Matrix Installation and Operation Instructions 16 2 HRV Air Handler Maintenance WARNING ALWAYS REMOVE POWER 120V TO THE UNIT PRIOR TO SERVICING Once every three months Replace furnace filter May be required more frequently in beginning especially if new construction The Matrix HRV module is relatively maintenance free but does require routine cleaning Table 14 describes the necessary maintenance Table 16 1 HRV Maintenance Items Vacuum surfaces let soak in warm water for three hours spray Heat Recovery Core Annually or as needed rinse and let dry Energy Recovery Core Annually or as needed Vacuum surfaces Fi Every 3 months or as needed Vacuum Filters ilters Annually or as needed Replace filters Clean interior of unit walls and drain pan with a mild non abrasive Inside Surfaces of Unit Annually or as neede
84. tor with alarm and battery back up may be installed on the next adjacent floor level In the event that the requirements of this subdivision can not be met at the time of completion of installation the owner shall have a period of 30 days to comply with the above requirements provided however that during said 30 day period a battery operated carbon monoxide detector with an alarm shall be installed APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified SIGNAGE A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS A plate is included with the boiler INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5 08 2 a 1 through 4 b EXEMPTIONS The following equipment is exempt from 248 CMR 5 08 2 a 1 through 4 1 The equipment listed in C
85. trix attempts to achieve a calculated set point which depends on the sensed water flow rate and the programmed H20 setting See Section 9 2 1 The H20 setting is accessed via the menu in the Matrix Fan blue controller and should be set at a value equal to or slightly greater than the temperature required at the hot water fixtures e g 125 F The Fan control will communicate to the Boiler red controller a boiler water temperature set point applicable for the sensed flow rate and the H20 setting selected The higher the flow rate and or H20 setting the higher the boiler water set point boiler water setting will not exceed the H20 setting by more then 30 F NTI provides a Thermostatic Mixing Valve adjustable from 100 to 145 F the mixing valve shall be installed between the Matrix DHW supply fitting and the hot water supply pipe to the fixtures See Figures 7 1 and 7 2 thus providing user protection from scalding hot water Note code requirements may require the maximum setting to be fixed at 120 F see Thermostatic Mixing Valve below and the instructions included with the valve 7 2 DHW System Plumbing amp Set up DHW Inlet amp Outlet Connections The Matrix has two potable water connections Inlet amp Outlet which exit the left side of the Matrix Cabinet on the inside of the cabinet the two lines are connected to the Brazed Plate Heat Exchanger The cold Inlet line flows through an integrated brass flow meter before connecting t
86. trix is designed to operate to capacity 160 in installations at 2000 feet of elevation or less As elevations higher than 2000 feet 150 have less dense air the unit is not capable of providing its specified capacity See Chart 2 140 In Canada De rate by 5 for altitudes between 2000 2 130 and 4500 feet For altitudes above 4500 feet E consult with local authorities 120 In USA De rate by 4 for every 1000 feet over 2000 110 feet 0 2000 3000 4000 5000 6000 7000 8000 9000 10000 Hevation ft AT ELEVATIONS GREATER THAN 2000 FEET THE COMBUSTION OF THE MATRIX MUST BE CHECKED WITH A CALIBRATED COMBUSTION TESTER TO ENSURE SAFE AND RELIABLE OPERATION CONSULT SECTION 5 20 FOR INSTRUCTIONS ON ADJUSTING THE INPUT TO PROVIDE PROPER OPERATION IT IS THE INSTALLERS RESPONSIBILITY TO CHECK THE COMBUSTION AND TO ADJUST THE COMBUSTION IN ACCORDANCE TO SECTION 5 20 Matrix Installation and Operation Instructions 2 0 INSTALLATION REQUIREMENTS The installation of your NY Thermal Matrix gas furnace boiler must conform to the requirements of your local authority and the National Fuel Gas Code ANSI Z223 1 and or CAN CGA B149 Installation Codes Where required by the Authority the installation must conform to the standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 IMPORTANT Carbon Monoxide Detectors Many jurisdictions require the installation of carbon monoxide detectors in buildings where
87. urn off if left in program mode longer than 30 seconds without receiving an input Press Function once to continue programming or to start boiler operation 34 Matrix Installation and Operation Instructions Table 9 4 Matrix Boiler Control Programming Menu Level Description Main Value Typical Settings Program Mode When Run is displayed controller RUN is in Prog mode Arrow up or down to scroll through menus 100 120 Infloor High Mass HYD 80 200 Hydronic Call Setpoint 140 160 Infloor Low Mass 140 160 Fan Coil HI 80 200 Auxiliary Heat Setpoint prior to outdoor reset 190 adjustment Differential Setting Applies only to Hydronic Only DIF 1 40 setpoint Temperature difference below setpoint at 10 which burner will re light Sets Outdoor Reset Curve Slope See RES 70 HI Determining Reset Temperature for more 85 information SFS 75 100 Starting Gas Input Value 80 HFS 100 240 Maximum Gas Input Value 240 LFS 46 100 Minimum Gas Input Value 48 min 46 Freeze Protection Operates burner and circulator ON if temperature drops below 40 F Storage Feature Timer Length of time in hours storage feature will keep boiler hot To start the control operation you must return to RUN on the menu and press Function Normal operation will begin Controller will return to RUN mode if no button is pressed for 2 minutes Sto OFF 24 2 9 2 2 Setting Matr
Download Pdf Manuals
Related Search
Related Contents
Vivotek PT1111M User's Manual : Free Download, Borrow, and Streaming : Internet Archive Marseille sous bonne garde - Gestionnaire de régimes de Retraite Manual Manual do usuario agente URBANBEES 原因究明調査の結果、製品に起因する事故ではないと判断するに際し 5 - Advanced Test Equipment Rentals Cloueur à air comprimé Copyright © All rights reserved.
Failed to retrieve file