        SPM-4000 - Paragon Controls
         Contents
1.                                                                          Field Setup Menu Flow ACH Room Volume  More Options  lt up gt  Flow ACH ON OFF  Output Cal  Flow Range FT   Control Settings Room Volume  gt   Temp  Options Flow Alarm ON OFF  00000   Humidity Flow Alarm Values  Flow ACH  gt  ACH Alarm ON OFF  More Options  lt down gt  More Options  lt down gt                       3 20 4  Flow Alarm ON OFF  The Flow Alarm ON OFF menu allows the user to turn the Flow alarm ON or OFF  The default is ON                             Field Setup Menu Flow ACH Flow Alarm  More Options  lt up gt  Flow ACH ON OFF  Output Cal  Flow Range  OFF ON   Control Settings Room Volume  Temp  Options Flow Alarm ON OFF    gt   ON   Humidity Flow Alarm Values  Flow  ACH  gt  ACH Alarm ON OFF  More Options  lt down gt  More Options  lt down gt                                                     3 20 5  Flow Alarm Values    The Flow Alarm Values menu allows the user to enter the flow Low and High alarm values  The default for the  Min  value is 000000  The Max  value will be the values entered into the Flow Range menu  refer to  Section 3 20 2                                          Field Setup Menu Flow ACH Flow Alarm Value  More Options  lt up gt  Flow ACH ON OFF  CFM   Output Cal  Flow Range  Control Settings Room Volume Low Alarm  Temp  Options Flow Alarm ON OFF  000000   Humidity Flow Alarm Values  gt   Flow ACH ACH Alarm ON OFF High Alarm  More Options  lt down gt  More Options  lt down
2.     Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 7  OPERATING MODE    The Operating Mode menu allows the user to change the room being monitored from an OFF room to a  positive  POS  or negative  NEG  room  Selection of an OFF room disables alarm status lights  process  display alarm text  audible alarm and remote alarm relay  Space 2 will only be displayed if turned on in  the Factory menu  Selection of options described under the Operating Mode text is determined by the  unit   s application  Default is the POS mode                                   Field Setup Menu Operating Mode  Operating Range  OFF POS NEG   Zero Cal  Room Identifiers Space 1  Operating Mode  gt   Display Filter  Pos   Output Filter  More Options  lt down gt                                   3 8  DISPLAY FILTER    The Display Filter menu allows the user to vary the Display Filter rate from 0 to 100 seconds to reach  98  of a step change  Space 2 will only be displayed if it is selected in the Factory menu           Field Setup Menu Space 1 Filter  Operating Range  Zero Cal  O Min  100 Max    Room Identifiers  Operating Mode  003  sec   Display Filter  gt    Output Filter   More Options  lt down gt                                3 9  OUTPUT FILTER    The Output Filter menu allows the user to vary the Output Filter rate from 0 to 100 seconds  If the  optional Space 2 is selected  both spaces will have the same filter rate value         
3.   Field Setup Menu Output Filter  Operating Range  Zero Cal  O Min  100 Max     Room Identifiers  Operating Mode  003  sec   Display Filter  Output Filter  gt   More Options  lt down gt                                            10 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ka  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 10  BACKLITE TIMER   The Backlite Timer menu allows the user to control how long the backlite will remain on after a keypad  button is pressed  Selection options will be 0 to 30  0   backlite on all the time and 1 to 30 represents  the number of seconds until the backlite is turned off   The default is 0           Field Setup Menu Backlite Timer  More Options  lt up gt   Backlite Timer  gt   Engineering Units  DP Display Format  00   Alarm options  Transducer Cal   More Options  lt down gt            0 On  30 Max                                    3 11  ENGINEERING UNITS    A list of engineering units are available for the user to select for display purposes to meet customer  requirements  If the engineering units are changed  the Op Range values and Alarm Values will also be  corrected  If two rooms are selected in the factory menu  both rooms will have the same engineering  units  Default to be Inch w c  When engineering units are changed  the decimal point will default to the  maximum resolution           Field Setup Menu    Engineering Units          More Options  lt up gt     Backl
4.  0 10V  Flow Analog Input S1 4 and S9 4 On  4 20 mA   S1 4 and S9 4 Off  0 10V                   Auxiliary Analog Input S1 5 and S9 5 On  4 20 mA   S1 5 and S9 5 Off  0 10V  2 2 15 4  Jumper Functions  See Figure 2 0     Jumper   Function  JP1  Spacel Analog Output  Jumper 1 2 Pos  4 20mA  Jumper 2 3 Pos 0 10V  JP2  Space2 Analog Output  Jumper 1 2 Pos  4 20mA  Jumper 2 3 Pos 0 10V  JP3  Controller Analog Output  Jumper 1 2 Pos  4 20mA  Jumper 2 3 Pos 0 10V                                                 Caution  Making output current voltage changes requires selecting the correct JP1  JP2 or JP3  position and making the same current  voltage selection in the Output Selection menu  See  example in Section 3 16         7 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3  DISPLAY MENUS  3 1  POWER UP DISPLAY    The Power Up menu displays the product name  software revision installed  work order number and  optional BACnet revision        Guardian Infinity  Software Rev  60 xxx  W O  Number xxxxx  Bacnet Rev  10 xxx                      3 2  SYSTEM DATA MENU    The System Data menu includes alarm values  operating modes and set point values  The alarm values  shown will be determined by the operating mode selected  If positive mode is selected  the display will  show only the positive alarm and set point values  If negative mode is selected  the display will show  o
5.  Connecting a single pole 3 position switch to pins 20  21  amp  22 of  J5  connector allows the user to  remotely change SP1 and SP2 operating mode to Positive  Negative or Off  To activate the remote  operating mode select input  the user must enter the Operating Mode menu and select the OFF mode   see section 3 7      2 2 7  RPM Output    Pins 37 38 of  J3  are used to connect to a Paragon Remote Pressure Monitor  RPM      2 2 8  Lonworks   Bacnet Output    Pins 39 40 of  J4  are used to connect to a LonWorks   or BACnet   MS TP communication network   The output requires an optional LonWorks or BACnet daughter board to be installed into the main  board     2 2 9  System Start    Pins 26 27 of  J6  are used to indicate that a fan system is enabled and to activate the internal control  algorithm        4 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    2 2 10  Door Interlock    Pins 28 29 of  J6  are used to interface with a door interlock switch that when activated causes the  controller output to either lock at that position or offset by a predetermined percentage     2 2 11  IrDA Port    The Guardian Infinity provides IrDA communication with a handheld PDA or PC software  MGUSim V2xx  For proper communication  the IrDA instrument must be aligned with the unit IrDA  window and the maximum distance must be kept to 1 foot or less     2 2 12  LCD    A 128x64 grap
6.  V ON 1  FIGURE 2 0  2 Paragon Controls Incorporated  Rev V1 6  7 30 09    Phone 707   579 1424  Fax 707   579 8480    SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual       2 1 2  Back Component and Connector Layout  Refer to Figure 2 1 for clarification on the back component and connector layout        GUARD PLATE      ID LABEL CONNECTOR LABEL     A X ROOM PRESSURE  x a      CONNECTION  4 T x  CLEAR TUBING   SPACE 1 REFERENCE PRESSURE  CONNECTION    TRANSDUCER     BLACK TUBING                 ce  i E ROOM PRESSURE  8 c  CONNECTION  a o  CLEAR TUBING   SPACE 2  lt  REFERENCE PRESSURE  TRANSDUCER CONNECTION     BLACK TUBING   Ji  J6 J5 J2  36 35 34 33 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16   15 14 13 12 11 10 9 8 7 6 5 4 3 2 1  Ji J3 J6  3   f  24VAC  50 60HZ    CONNECTION TO RPM   SYSTEM START  EARTH GROUND  DOOR INTERLOCK  J4  j   CONTROLLER SETPOINT INPUT  LONWORKS   BACNET COMMUNICATIONS  J2 r   CONTROLLER SETPOINT INPUT  39   CONTROLLER OUTPUT    TEMP  INPUT    CONTROLLER OUTPUT    TEMP  INPUT J5  COM    RH INPUT 16   SP 1 PROCESS OUTPUT  NO AUX  RELAY    RH INPUT 7   SP 1 PROCESS OUTPUT   A  56 N    CFM INPUT 3   SP 2 PROCESS OUTPUT    CFM INPUT 1   SP 2 PROCESS OUTPUT    AUX  INPUT 2 POSITIVE ROOM SEL  3 POSITION      POS NEG OFF    AUX  INPUT P NEGATIVE ROOM SEL  N ROOM SELECT   15VDC 29 GROUND   SWITCH  LOOP POWER     15VDC 23 COM  24 NO SPACE PRESSURE ALARM  AUX  DI  NC  3 Paragon Controls Incorporated  Rev  V1 6  7 30 09    Phone 707   579 
7.  gt   999999           3 20 6  ACH Alarm ON OFF  The ACH Alarm On OFF menu allows the user to turn the ACH alarm ON or OFF  The default is ON           Field Setup Menu                More Options  lt up gt   Output Cal   Control Settings  Temp  Options  Humidity  Flow ACH  More Options  lt down gt                                                                       Flow ACH       ACH Alarm                   Flow ACH ON OFF  Flow Range  Room Volume  Flow Alarm ON OFF  Flow Alarm Values  ACH Alarm ON OFF  More Options  lt down gt               OFF ON      ON                          22    Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 20 7  ACH Alarm Value    The ACH Alarm Value menu allows the user to enter the ACH Low alarm value  The default value    is 00   Field Setup Menu Flow ACH ACH Alarm Value  More Options  lt up gt  More Options  lt up gt   Output Cal  ACH Alarm Value Low Alarm  Control Settings Lonworks Flow ACH  00                    More Options  lt down gt        Temp  Options  Humidity  Flow ACH                                                             3 20 8  LonWorks Flow ACH    The LonWorks Flow ACH menu allows the user to disable the FLOW  CFM  analog input and enter the       flow value via LonWorks network communications                                      Field Setup Menu Flow ACH Lonworks Flow ACH  More Options  lt up gt  More Option
8.  gt  Audible Alarm  gt   On Off   Backlite Timer Alarm Values  On    Engineering Units Alarm Delay   DP Display Format Audible Alarm Mode  Alarm options  gt   Transducer Cal   Continuous    More Options  lt down gt                                                  3 13 2  Alarm Values  Space 1 Negative Alarm     The Alarm Values  Space 1 Negative Alarm  menu allows the user to enter negative room alarm values   Engineering units displayed in the menu will change if the selection in the Engineering Units menu  changes  If the engineering unit is changed  the values displayed will be converted to the new  engineering unit  The decimal point resolution will represent the selection made in the DP Display  Format menu  refer to Section 3 12                                    3 13 3  Alarm Values  Space 1 Positive Alarm     The Alarm Values  Space 1 Postive Alarm  menu allows the user to enter positive room alarm values   Engineering units displayed in the menu will change if the selection in the Engineering Units menu  changes  If the engineering unit is changed  the values displayed will be converted to the new  engineering unit  The decimal point resolution will represent the selection made in the DP Display  Format menu  refer to Section 3 12                  Field Setup Menu Alarm Options Alarm Values Space 1 Negative  More Options  lt up gt  Audible Alarm  Inch w c    Backlite Timer Alarm Values Space 1 Neg   Engineering Units Alarm Delay Space 1 Pos  Low Alarm  DP Display For
9.  the 1  Verify two devices do not have the same Instance  Guardian Infinity Number and MAC code  Change to an unused  Instance Number and MAC code     2  Verify wires connected to J4 pins 39  amp  40 are  correct  If not swap wires and retest     3  Contact Factory Service Department     11  Field Setup Password is rejected 1  Incorrect password was entered  Verify password  accuracy                 2  Contact Factory Service Department        28 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    PC    PARAGON    CONTROLS  INCORPORATED    Paragon Controls Incorporated    P O  Box 99  Forestville  CA 95436  http  www paragoncontrols com  Phone 707   579 1424   Fax 707   579 8480   IOM  SPM 4000RevV1 6  7 30 09  Copyright    2009    
10. 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    2 2  HARDWARE SPECIFICATIONS OF INPUTS AND OUTPUTS    2 2 1  Power Input    The power input requirement is 20 28VAC at 50 60Hz  Line power is connected to input socket  J1    The unit has an isolated DC DC converter  which creates electrical isolation between the power input  and the unit     2 2 2  Pressure Sensor Inputs    The SPM 4000 is factory configured for bi directional or uni directional pressure inputs  Bi directional  pressure input provides both positive and negative pressure values  Uni directional pressure input  provides only positive pressure values     2 2 3  Analog Inputs    The Guardian Infinity supports five analog inputs  controller set point input  temperature sensor input   humidity sensor input  flow sensor input  and auxiliary analog input  Slide switches S1 and S9 are used  for voltage current input selection  For details  see Section 2 2 10     2 2 4  Analog Outputs    The Guardian Infinity provides three channels 4 20mA or 0 10VDC analog outputs  Jumpers JP1  JP2  and JP3 are used in conjunction with the menu for voltage current output selection  The maximum  output load impedance for current output is 500 ohms  The minimum load impedance for voltage output  is 1000 ohms     2 2 5  Remote Space Pressure Alarm relay  The contact rating of the SPDT alarm relay is 0 6A at 125VAC or 110VDC and 2 0A at 30VDC     2 2 6  Remote Operating Mode Select Switch   
11. 8  3 3  FIELD SETUP  amp  INITIAL PASSWORD MENU    rennes 8  3 4     OPERATING  RANGE  ota 9  Js     ZEROSCAEIBRATION oda 9  3 0    ROOMIDENTIFHERS aaa 9  Sr    OPERATING MODE o n   e O 10  3 8 DISPLAY FILTER sun al 10  39 COMPUT UR A dali sad piece oy eek ea avec dey nna dats ee eine 10  3 10  BACRELR   TIMER ene ie eo a dt id 11  3 11  ENGINEERING UNITS ooo a nine 11  3 12  DEDISPLA Y FORMA Sen ne Cr er a a A sn atten che si  11  3 13  AFARM OPTIONS onnea nd 12  Sol A A A nea ened 12  3 13 2  Alarm Values  Space 1 Negative Alarm  ss 12  3 13 3  Alarm Values  Space 1 Positive Alarm     12  DAS AAA DCI ENE 13  3 14  TRANSDUCER CALIBRATION ia 13  3 15  OUTPUT CALIBRATION usais ici 14  3 16  OUTPUT SSELEC PIONS tant 14  3 17  CONTROL TUNING AND SETTINGS ss ne a loons oN 15  i Paragon Controls Incorporated  Rev V1 6 7 30 09    Phone 707 579 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual       SA7 1    Tuning Parametros 15  A O 15  21735  A O 15  3 17 4  Setpoint Internal Extertial sise 16  317 5     Controller Setpoint Valle iria iii 16  EI 11 610   Sh O 16  SIT   AS ON OFF R renn Len N SET tte tte een 17  2178   Output Oyeride a dl e e de e ds 17  317 9  System Alarm Delay iii as 17  3 18  TEMPERATURE OPTIONS aaa 18  318 1     Temperature Display OFF ON 0 sita Bete A a aca A A 18  3 18 2   Temperature Units  ends 18  SAS De AAA A EN 18  3 184      Temperature Alarm ON OFF tac a Ai 19  318 5  Temperature Alarm AAA A A acess a E sal
12. PARAGON    CONTROLS  INCORPORATED       SPM 4000    Guardian Infinity Space Pressurization  Monitor and Controller    Operation  amp  Maintenance Manual    Engineered for accuracy  applicability   durability and simplicity    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual       TABLE OF CONTENTS  TABLEOF CONTENTS a na a a aa NN o AE E aE EASE i  dhe     INTRODUCTION siisii nannan acta T e ca ta tan i 1  Til     BASIC OPERATION sis cdas 1  125 OEE ON  cso NS ETA 1  121  Electrical COMEN a 1  1 2 2  Static Electricity acid 1  2   HARDWARE CONFIGURATION  ui ii 2  2 1  GUARDIAN INFINITY COMPONENT LAYOUT eee 2  Zt     Front Component layout  see Sen M M Ne AGA ee ea Ses Side 2  2 12  Back Component and Connector Layouts 3  2 2  HARDWARE SPECIFICATIONS OF INPUTS AND OUTPUTS coccooconcccnocccincnconncconacnnnccnncnnns 4  2 2 1  POWeErINput ES E EN 4  222  Pressure SENS Or TUES Secs actos rayne An ce ee aera ee   Se 4  22 3  Analog Input  ida 4  2 2 4  Analog OUPS toda 4  22 5  Remote Space Pressure A Enr la Stan iaa 4  2 2 6  Remote Operating Mode electo WC Ti rin Reis 4  22 7  RPM COU UE nent DA ne ne nette 4  2 2 8  Lonworks   Bacnet Dutpltiiiin ia 4  2 2 9  DAIA SAIT Se A ATE E T EEE E AE E Nr 4  22106 B16 es 1 Ce  dd 5  2 211  IDA Porta ia AR 5  2 2  l2 MO A Todos 5  A SN A O 5  A D D RSR A E E EE E T EE E AE T eer oP fe 6  2213        BULWONS Ge  WI 6  3   DISPLAY MENUS susi ir 8  Sl    POWER UP  PIS PLATS nn Se a T a E A eee 8  32  SYSTEM DATAMENU dl oia is 
13. State  On Alarm state and ACK ok   Off No Alarm state  Blink Alarm state but no ACK                      2 2 14 3  Surface Mount LED   s DL1 2   LED State Status LED DL1  Diag  LED DL2   On IrDA Comm     Established  Off      Blink   BACnet Data Sending                               2 2 15  Buttons  amp  Switches    The Guardian Infinity unit has a 6 button keypad  The Unit also has 4 switches and 3 jumpers  Buttons  are used for menu navigation  data entering and alarm acknowledge  The functions are shown below     2 2 15 1  Button Functions                      Button Button Function  UP Menu Browser Parameter Setting  DOWN Menu Browser  Parameter Setting  LEFT Parameter Setting  RIGHT Parameter Setting  MENU ENTER Menu Browser  Parameter Setting  ESC ACK Menu Browser AlarmAcknowledge                2 2 15 2  Switch Functions                               Switch   Function  S2  Slide switch  Unit Power On Off  S1 1  Dip switch  BACnet Rs 485 Termination On Off   1 2  Dip switch  Not Used  6 Paragon Controls Incorporated  Rev V1 6  7 30 09    Phone 707   579 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    2 2 15 3  Analog Input Select Switch Functions    Analog Input   Switch Pos   Controller Setpoint Analog Input S1 1 and S9 1 On  4 20 mA   S1 1 and S9 1 Off  0 10V  Temperature Analog Input S1 2 and S9 2 On  4 20 mA   S1 2 and S9 2 Off  0 10V                Humidity Analog Input S1 3 and S9 3 On  4 20 mA   S1 3 and S9 3 Off 
14. actory installed     3 20 1  Flow ACH Display ON OFF    The Flow ACH ON OFF menu allows the user to turn the Flow value  CFM  and Air Changes per Hour   ACH  on the display On or Off  The formula for calculating ACH value is   Flow x 60    Room    Volume                                         More Options  lt down gt                 More Options  lt down gt                 Field Setup Menu Flow ACH Displayed  More Options  lt up gt  Flow ACH ON OFF  Flow ACH Flow Range Flow ACH  MAC Address Room Volume  OFF ON   Instance Number Flow Alarm ON OFF  Password Timeout Flow Alarm Values  OFF   Field Password ACH Alarm ON OFF                3 20 2  Flow Range    The Flow Range menu allows the user to enter the maximum flow value which corresponds to 10vdc or    20ma                       Field Setup Menu Flow ACH Max  Flow Value  More Options  lt up gt  Flow ACH ON OFF  Output Cal  Flow Range CFM  Control Settings Room Volume  Temp  Options Flow Alarm ON OFF  999999   Humidity Flow Alarm Values  Flow ACH ACH Alarm ON OFF  More Options  lt down gt  More Options  lt down gt                                                  21    Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480                Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 20 3  Room Volume    The Room Volume menu allows the user to enter the room volume in cubic feet for ACH calculations   The formula for ACH calculation is   Flow x 60    Room Volume    
15. city    The circuit board contains components which are susceptible to damage caused by static electrical  discharge  Should it be necessary to remove the circuit board from the enclosure  appropriate  precautions must first be taken to ensure that the operator and the circuit board are at the same electrical  potential        1 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    2  HARDWARE CONFIGURATION    The Guardian Infinity consists of the pressure measurement circuits  digital input outputs  analog  inputs outputs  Voltage Current   BACnet   LonWorks and IrDA communication and Graphical LCD  unit in a single board     2 1  GUARDIAN INFINITY COMPONENT LAYOUT    2 1 1  Front Component Layout  Refer to Figure 2 0 for clarification on the front component layout     DISPLAY  TEXT INTENSITY                                        SPACE1    OO  Y 2   NORMAL    gt  AUDIBLE        ALARM  Ge      ALARM Sr SPARE  i S10  ON  Il  Te     BACNET  LCD GRAPHICS DISPLAY TERMINATOR  SPACE 2     jroo O     REF O     lele  ele e  e a e e a ele   SP1 SP2 CONTROLLER  OUTPUT OUTPUT OUTPUT  JP3  pa  I I V  POWER SWITCH Y SP1   SP2   CONTROLLER  OUTPUT SELECTION  VOLTAGE CURRENT INPUT SELECTION   EXAMPLE  CURRENT En  INPUT SWITCH S1 SWITCHS9  I V SELECTION  CONTROLLER SETPOINT 1 1 OFF  V ON 1 VOLTAGE ma  TEMPERATURE 2 2 OFF V ON 1  RH 3 3 OFF V ON 1  CFM 4 4 OFF   V ON 1  AUX  5 5 OFF  
16. ct Factory Service Department     6  Audio Alarm not functioning but Red 1  Verify Audible Alarm is turned ON in Audible  Alarm Status LED on the front panel Alarm Menu  see Section 3 13 1    is ON  2  Verify alarm is not turned OFF via the  communication network   3  Contact Factory Service Department   7  Red Alarm LED remains ON 1  Verify correct Operating Mode  see Section 3 7      2  Verify alarm setpoint values     3  Verify input pressure tubing is connected correctly   see Section 2 1 2      4  Contact Factory Service Department   8  Alarm Mode not functioning 1  Verify correct Operating Mode  see Section 3 7    2  Verify alarm setpoint values     3  Verify input pressure tubing is connected correctly   See section 2 1 2     4  Controller Option only   All Alarms OFF section   Follow the instructions in section 3 17 7                    27 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual                TROUBLESHOOTING TABLE  SYMPTOM SOLUTION  9  LonWorks not communicating with 1  Turn power switch OFF  Remove Guardian  the Guardian Infinity Infinity from the wall box  Carefully turn power    switch ON  Press service pin located on  LonWorks board  Turn power switch to OFF and  reinstall Guardian infinity  Turn power to On     2  Swap wires on J4 pins 13  amp  14  see Section 2 1 2    3  Contact Factory Service Department     10  BACnet not communicating with
17. ctory Defaults menus  the device will  return settings to the original factory settings  The defaults are NO                                                                                                  Field Setup Menu Factory Defaults Factory Defaults  More Options  lt up gt  Set To  MAC Address Factory Defaults Verify Setting  Instance Number  NO YES   gt  Factory Defaults  Password Timeout  NO YES   Field Password  NO   Factory Password  NO   Factory Defaults  gt   25 Paragon Controls Incorporated  Rev V1 6  7 30 09    Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    4  TROUBLESHOOTING GUIDE                TROUBLESHOOTING TABLE  SYMPTOM SOLUTION  1  Status LED is not illuminated LCD 1  Verify ON OFF switch is in ON position  see  Display is Blank Section 2 1 1      2  Verify correct input power and connection at  connector J1  see Section 2 1 2      3  Verify input power wire insulation has been  properly removed and the wire fully inserted into  the J1 power plug     4  Contact Factory Service Department     2  Display characters are too dim or too 1  Remove front cover  Adjust Display Text Intensity  dark potentiometer R20 located at the top of the board     2  Contact Factory Service Department     3  Display indicates zero pressure and 1  Verify room calibration pressure tubing is  does not respond to input pressure connected as shown in Section 2 1 1   changes    2  Squeeze each room calibration tube 
18. ells  The combination of these two technologies  ensures exceptional long term stability and  0 25  measurement accuracy     Field configuration of engineering units  operating mode  operating range  process noise filtering  alarm  set points  etc  are performed via password protected intuitive menus that are accessed through the  integral six button touch pad  Device monitoring and configuration can also be performed by a building  management system through either a LonWorks   or BACnet   MS TP communication network as well  as through a local IR communication port using a laptop or handheld PDA  An additional network  communication port is available for connection to a Paragon remote pressure monitor  The front panel  includes an 8 line graphic display for local indication of the space pressure and device configuration   LED indication of operational mode and status  and an audible alarm with alarm acknowledge button     The Guardian Infinity offers an optional controller that utilizes a proprietary algorithm which results in  true three mode control incorporating proportional band  integral  reset  and inverse derivative  P  I   1 D  controller functionality and tuning  The controller will provide responsive modulation of a control  damper or variable speed drive ensuring a stable space pressure is maintained     1 2  SAFETY    1 2 1  Electrical Connections  Before any electrical connections are made  ensure the POWER SWITCH is in the OFF position     1 2 2  Static Electri
19. es R eus 19  93 18 60   LonWorks Temper atte ss saunas tentant tnt o ii 19  3 19  HUMIDITY OPTIONS css ani dune 20  SALE Hem Display ON OE ia 20  3402 Home Alarm ON FOR  O 20  3 19 3   Humidity Alarm Y ales iii ies 20  SRA  L  O WOLES Renee 21  3 20  FEOWAND ACOPHONS A a 21  3 20 1  Bow AC Display ON OBS Se nm ele A s   21  3 20 2  Flow Range ne nan he Eat Dr nd dns nee 21  AN O 22  3204 Fow Alam ONO F e 2 CAL ne tn os 22  3 20 5  Flow Alarmi Valles a Lu he ns 22  3 20 6   ACH Alarm ON OFF cui aia 22  320 7  JACH Alarm VAE cs sas  RS el Rd un 23  3206   EonWorks FlOW  ACER n O O 23  3 21  MAC ADDRES Sanninina a Ra E Ea REEE E ETTEASTE iSi 23  3 22  INSTANCE NUMBER 0s   cess te asee eae aata aae a dettes 24  3 23  PASSWORD TIMEOUT 5 205 iina AR Sa 24  3 24  FEED PASS WORD tt a e a ds aaa ee 24  3 25  FACTORY PASSWORD da 25  3 26  FACTORY DEFAULTS siii ita 25  4 gt  TROUBLESHOO TINE GUIDE a aa ne ne 26  ii Paragon Controls Incorporated  Rev V1 6 7 30 09    Phone 707   579 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    1  INTRODUCTION    This user manual provides information on product features and guides you through all basic  functionality     1 1  BASIC OPERATION    The Guardian Infinity is a true differential space pressure measurement system engineered to combine  the operability of today   s microprocessor technology with state of the art  industrial grade  highly  accurate  ultra low range  differential pressure sensing c
20. ff     The default is ON                                Field Setup Menu Temp  Options Temperature  More Options  lt up gt  Display OFF ON  gt  Display  Output Cal  Temp  Units  OFF ON   Output Selection Temp  Range  Control Settings Alarm OFF ON  ON     Temp  Options  Humidity  More Options  lt down gt                 Alarm Values  Lonworks Temp                          3 18 2  Temperature Units    The Temperature Units menu allows the user to select the temperature units to be displayed  The default    is   F              Field Setup Menu                                  More Options  lt up gt   Output Cal   Output Selection  Control Settings  Temp  Options  Humidity  More Options  lt down gt                             Temp  Options Temp  Units  Display OFF ON  Temp  Units  gt    F    C  Temp  Range  Alarm OFF ON    F     Alarm Values  Lonworks Temp                                3 18 3  Temperature Range    The Temperature Range menu allows the user to enter the minimum and maximum temperature values  which will correspond with the 0 10vdc or 4 20ma input signals                    Field Setup Menu Temp  Options  More Options  lt up gt  Display OFF ON  Output Cal  Temp  Units  Output Selection Temp  Range  Control Settings Alarm OFF ON    Temp  Options  Humidity    More Options  lt down gt                    Alarm Values  Lonworks Temp                    Temperature Range       CF      gt  Min  Value      000     Max  Value    999                       18    Paragon Contr
21. he default is Reverse  action   Field Setup Menu Control Settings Action  More Options  lt up gt  Tuning Parameter Direct Reverse  Output Cal  Action  Output Selection Door Interlock  Reverse   Control Settings Setpoint Int Ext  Temp  Options Cont  Setpoints  Humidity Output Start  More Options  lt down gt  More Options  lt down gt                                                                                                                                               3 17 3  Door Interlock                      The Door Interlock menu allows the user to select between two output options when the door interlock  input is activated  The Lock function will lock the output at the value it was when the door interlock  input was activated  When the door interlock input is de activated  the output resumes automatic  modulation to balance the process to the setpoint value  The   Change function will add or subtract a  percent of full scale output to the output value when the door interlock input is activated  When the door  interlock input is deactivated the output will immediately go to the previous output value and resume    automatic modulation to balance the process to the setpoint value  The default value is 000                                                               Field Setup Menu Control Settings Door Interlock  More Options  lt up gt  Tuning Parameter Lock     Change  Output Cal  Action  Output Selection Door Interlock  Lock   Control Settings Setpoint Int Ext  Tem
22. hical LCD displays pressure  engineering units  and menus  The decimal point and  polarity will be selected automatically based on the engineering unit and range selection     ROOM 1204      0 0000 men w c     ROOM 1204      0 0000 Inch w c     ROOM 1204 bs    0 0000 men w c                                   ROOM 1205  10 000 CFM 10 ACH 0 0000 inch w   10 000 CFM 10ACH  75   F 55  RH 75   F 55  RH  DOOR 50  RUN  Single Room display with Dual Room Display Single Room Display with    optional CFM ACH   Temperature  amp  RH    CFM ACH  Temperature   RH  amp  Controller status    2 2 13  Buzzer   A 85dB  max   40mA buzzer is used for providing an audible alarm  The audible alarm has two sound  options  continuous and interval  The buzzer sound options and alarm ON OFF option are selected  through the Audible Alarm menu  see section 13 3               5 Paragon Controls Incorporated  Rev  V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    2 2 14  LED   s    The Guardian Infinity unit has two surface mount LED s and two solid state LED   s  Light Emitting  diodes   LED functions are shown below     Note  ACK refers to the alarm acknowledge keypad button     2 2 14 1    Normal Status LED  DL3                                                     LED State   Operation State  On Alarm goes off and ACK ok   Off Alarm state  Blink Alarm goes off with no ACK  2 2 14 2  Alarm Status LED DL4   LED State   Operation 
23. independently  with your fingers  If the display responds  proceed  to Step 3  If the display does not respond  contact  Factory Service Department     3  Turn the power switch to OFF  Remove the  Guardian Infinity from the wall box and verify the  input signal tubing is connected as shown in  Section 2 1 2     4  Contact Factory Service Department     4  Display is reading a pressure but does 1  Turn the power switch to OFF  Remove the  not respond to input pressure changes Guardian Infinity from the wall box and inspect for  possible pinched or disconnected tubing  Reinstall  and verify operation     2  Remove ROOM and REF end of Room Calibration  tubing  see Section 2 1 1   If the display returns to  a zero reading  check for pinched or plugged  tubing at the PE 4000 pressure sensor or input  signal lines  If the display does not respond   contact the factory Service Department                       26 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual                TROUBLESHOOTING TABLE  SYMPTOM SOLUTION  5  No Process output  Voltage Current  1  Verify correct output jumper selection  See JP1   or Incorrect Output JP2  amp  JP3 in Section 2 1 1   Verify selections are  correct in Output Selection menu s  see Section  3 16      2  Disconnect output signal wires and verify output  signal at Guardian Infinity connector JS is correct   see Section 2 1 2      3  Conta
24. ions Cont  Setpoints  gt  Off  Humidity Output Start  0 0000    More Options  lt down gt  More Options  lt down gt   3 17 6  Output Start    The Output Start menu allows the user to select the output condition when the System Start input is not  active  If Min  is selected  the output will start at Ovdc  4ma  and modulate from there  If Max  is  selected  the output will start at 10vdc  20ma  and modulate from there  The default is MIN                             Field Setup Menu Control Settings System OFF  More Options  lt up gt  Tuning Parameter Output Value  Output Cal  Action Min  Max   Output Selection Door Interlock  Control Settings Setpoint Int Ext  MIN   Temp  Options Cont  Setpoints  Humidity Output Start  gt   More Options  lt down gt  More Options  lt down gt                                            16 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 17 7  Alarms ON OFF    The Alarms ON OFF menu allows user to determine if all alarms will be active  ON  or inactive  OFF   when the System Start input is de activated  The default is OFF                                Field Setup Menu Control Settings System Start  More Options  lt up gt  More Options  lt up gt   Output Cal  Alarm ON OFF  gt  De activated  Output Selection Output Override All Alarm Status  Control Settings Sys  Alarm Delay  ON OFF   Temp  Options  Humidity  OFF   More Options  lt dow
25. ite Timer Inch w c   Engineering Units  gt  Pa  DP Display Format KPa   Alarm options mm w c     Transducer Cal   More Options  lt down gt                                   3 12  DP DISPLAY FORMAT    The DP Display Format menu allows the user to change the number of digits shown to the right of the  decimal point using the up down buttons  The decimal point in the display will move right or left  depending upon which button is depressed  If a change in decimal point position is made  the process  display value must reflect the corrected weight value  If no decimal point is required  move the decimal  to the far right position  If a change is made to the DP format  the Op Range  amp  Alarm Values will also  change  The default decimal point resolution is 0 0000           Field Setup Menu DP Display Format  More Options  lt up gt   Backlite Timer    Engineering Units          Decimal Resolution                                     DP Display Format  gt   0 0000   Alarm options  Transducer Cal   More Options  lt down gt   11 Paragon Controls Incorporated  Rev V1 6  7 30 09    Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 13  ALARM OPTIONS  3 13 1  Audible Alarm    The Audible Alarm menu allows the user to manually turn the audible alarm ON or OFF and select the  audible alarm to be continuous or interval                                            Field Setup Menu Alarm Options Audible Alarm   More Options  lt up
26. ld Setup Menu Output Selection SP1 Output Select  More Options  lt up gt  Sp1 Output Sel   gt   Output Cal  Sp2 Output Sel  SP1 Output  Output Selection  gt  Cont  Output Sel  Current Voltage  Control Settings  Temp  Options  D  Humidity  More Options  lt down gt                                                        14 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 17  CONTROL TUNING AND SETTINGS    The Controller menus will only be displayed on units with the controller option purchased     3 17 1  Tuning Parameters    The Tuning Parameters menu allows the user to tune the controller parameters to match the system  dynamics  The Proportional Band value can be entered as a percent value from 1 to 100   Reset and  Inverse Derivative values will range from 0 to 300 seconds  Default values will be Proportional Band    10   Reset  Integrator Tim    70 seconds and Inverse Derivative   60 seconds                 Field Setup Menu Control Settings Tuning Parameters  More Options  lt up gt  Tuning Parameter Proportional Band  Output Cal  Action  0010    Output Selection Door Interlock Integrator Tim  Control Settings Setpoint Int Ext  070  sec   Temp  Options Cont  Setpoints 1 Derivative  Humidity Output Start  060  sec   More Options  lt down gt  More Options  lt down gt   3 17 2  Action  The Action menu allows the user to select between Direct and Reverse action  T
27. ller Output Values  refer to Section 2 1 2   By applying minimum and maximum  input pressures  Zero and Span Process Output Values can be set to the output limits  Use the  UP DOWN buttons to make any correction necessary  By pressing the Enter button  these correction  values are stored in the EPROM  Use the same correction procedure to set the minimum and maximum  Controller output limits                                                                                                                 Sp1 Output Output Calibration  Sp1 Volt Zero Monitor output  Field Setup Menu Output Cal  Sp1 Volt Span  gt  Press Up Down  More Options  lt up gt  Spl Cur  Zero Buttons until  Output Cal        Sp1 Output Cal     gt  Spl Cur  Span Output is 0 000  Output Selection Sp 2 Output Cal   Press Enter   Control Settings Cont  Output Cal   Temp  Options Output Calibration  Humidity  gt  Sp1 Output Monitor output  More Options  lt down gt  Spl Volt Zero Press Up Down  Sp1 Volt Span  gt  Buttons until  Spl Cur  Zero Output is 10 000  Spl Cur  Span  Press Enter              3 16  OUTPUT SELECTION    The Output Selection menu allows the user to make Current  I  Voltage  V  output changes to Space 1   Space 2 and Controller outputs  Along with a menu change  repositioning of jumpers JP1  JP2 and JP3  is required  Refer to Section 2 1 1   The following example is shown for Space 1  Space 2 and  Controller Output Selection are performed the same                                               Fie
28. mat   0 0000   Alarm options  Transducer Cal  High Alarm  More Options  lt down gt    0 1000                                                                                                        Field Setup Menu Alarm Options Alarm Values Space 1 Positive  More Options  lt up gt  Audible Alarm  Inch w c    Backlite Timer Alarm Values Space 1 Neg   Engineering Units Alarm Delay Space 1 Pos  Low Alarm  DP Display Format   0 0000   Alarm Options  Transducer Cal  High Alarm  More Options  lt down gt    0 1000                    Paragon Controls Incorporated  Rev V1 6  7 30 09    Phone 707   579 1424  Fax 707   579 8480                Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 13 4  Alarm Delay    The Alarm Delay menu allows the user to delay alarm activation after an alarm event occurs from 0 to  9999 seconds  Space 2 is displayed only if turned ON in factory menu  The default value is 30 seconds           Field Setup Menu       Alarm Options             More Options  lt up gt   Backlite Timer  Engineering Units  DP Display Format    Transducer Cal   More Options  lt down gt                 Alarm options  gt              Audible Alarm  Alarm Values  Alarm Delay             3 14  TRANSDUCER CALIBRATION    A precision low pressure source  Paragon PS 100 or equivalent and a manometer are required to  perform the transducer calibration  The Transducer Calibration menu will give the user three calibration  points to select from  It is not necessary to perf
29. n gt                                            3 17 8  Output Override    The Output Override menu allows the user to manually set the controller output to a fixed value  The  defaults are OFF and 50                        Field Setup Menu Control Settings Output Override  More Options  lt up gt  More Options  lt up gt   OFF ON   Output Cal  Alarm ON OFF  gt   OFF   Output Selection Output Override  Control Settings Sys  Alarm Delay Output Value  Temp  Options  0 100   Humidity  50    More Options  lt down gt                                         3 17 9  System Alarm Delay    The System Alarm Delay menu allows the user to enter an alarm delay value in seconds that will start  after System Start input is activated  The default is 30 seconds                                Field Setup Menu Control Settings System Start  More Options  lt up gt  More Selections T Alarm Delay  Output Cal  Output Override  Output Selection Sys  Alarm Delay  gt   0 to 999   Control Settings  Temp  Options  030  sec   Humidity  More Options  lt down gt                                         17    Paragon Controls Incorporated  Rev  V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480          PCI SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 18  TEMPERATURE OPTIONS    Menus are displayed only if the Temperature Option is factory installed     3 18 1  Temperature Display OFF ON    The Temperature Display ON OFF menu allows user to turn the displayed temperature value on or o
30. nly the negative alarm and set point values     To display the System Data menu  depress and hold the ENTER button for three seconds           System Data  SP1 Mode Pos   SP1 Low   005  SP1 High  0 49  SP2 Mode Pos   SP2 Low   003  SP2 High   045  More Selections  lt down gt                                3 3  FIELD SETUP  amp  INITIAL PASSWORD MENU   To enter the Field Setup menu from the process display  the user will need to depress the UP DOWN  buttons simultaneously  The Field Setup Password menu will appear  The initial password shipped  from the factory is 00000        Field Setup  Password   00000                          8 Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 4  OPERATING RANGE    The Operating Range value is the pressure range that correlates with the 0 to 10vdc or 4 to 20mA output  signal  The allowable Operating Range value is from 40 to 100  of the Max  F S  Value shown on the  display  If an invalid value is entered  the display will change to an error message and the value will not  be accepted                             Field Setup Menu Space 1 Op  Range  Operating Range  gt   Inch w c    Zero Cal Max  F S  Value  Room Identifiers  0 1000   Operating Mode  Display Filter Operating Range  Output Filter  0 1000   More Options  lt down gt                                         3 5  ZERO CALIBRATION    Zero Calibration allows the user t
31. ns  lt up gt  Humidity ON OFF  Output Cal  Alarm ON OFF  gt  Low Alarm  Output Selection Alarm Values  ON   Control Settings Lonworks RH  Temp  Options High Alarm  Humidity  gt   ON   More Options  lt down gt                                                           3 19 3  Humidity Alarm Values    The Humidity Alarm Values menu allows the user to enter High and Low humidity alarm values   Default values are O and 100                                                                                 Field Setup Menu Humidity Alarm Values  More Options  lt up gt  Humidity ON OFF  Output Cal  Alarm ON OFF Low Alarm  Output Selection Alarm Values  gt   000    Control Settings Lonworks RH  Temp  Options High Alarm  Humidity  gt   100    More Options  lt down gt   20 Paragon Controls Incorporated  Rev V1 6  7 30 09    Phone 707   579 1424  Fax 707   579 8480     ze  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 19 4  LonWorks RH    The LonWorks RH menu allows the user to disable the humidity analog input and enter the humidity    value via Lon Works network communications                                      Field Setup Menu Humidity Lonworks RH  More Options  lt up gt  Humidity ON OFF Lonworks  Output Cal  Alarm ON OFF Humidity  Output Selection Alarm Values  OFF ON   Control Settings Lonworks RH  Temp  Options  OFF   Humidity  More Options  lt down gt                                         3 20  FLOW AND ACH OPTIONS    Menus are only displayed 1f Options are f
32. o easily correct for any zero transducer shift  Any error found will be  added to the value created during the factory calibration procedure  This correction value will be stored  in an additional EPROM location in case the user needs to return the device to the original factory  calibration  This can be done by entering the Factory Defaults menu  see Section 3 26   Ifa Zero  Calibration is performed which exceeds factory limits  an error message stating this will appear and the  reading will not be accepted                                         Field Setup Menu Zero Cal Zero Cal  Space 1  Operating Range  Zero Cal  gt  Space 1  gt  Input Zero Value CPU Taking  Room Identifiers  0 000 Pressure  Samples  Operating Mode  gt   Display Filter  Press Enter   Please Wait   Output Filter  More Options  lt down gt                                                                 3 6  ROOM IDENTIFIERS    The Room Identifiers menu allows the user to enter upper case alpha and numeric characters to identify  Space 1 or optional Space 2 on the display  The user will be able to enter 16 characters  One character  at a time will be entered  starting with the far left character                                   Field Setup Menu Room Identifier  Operating Range Space 1  Zero Cal Identifier  Room Identifiers  gt   Operating Mode  ROOM 205   Display Filter  Output Filter Press Enter  More Options  lt down gt                                      Paragon Controls Incorporated  Rev  V1 6  7 30 09
33. ols Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    He SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 18 4  Temperature Alarm ON OFF    The Temperature Alarm ON OFF menu allows the user to enable or disable the Low or High  Temperature Alarm function  The default values are ON                                         Field Setup Menu Temp  Options Alarm ON OFF  More Options  lt up gt  Display OFF ON  OFF ON   Output Cal  Temp  Units  Output Selection Temp  Range Low Alarm  Control Settings Alarm OFF ON  gt   ON   Temp  Options  gt  Alarm Values High Alarm  Humidity Lonworks Temp   ON   More Options  lt down gt                                                     3 18 5  Temperature Alarm Values    The Temperature Alarm Values menu allows the user to enter the Temperature Low and High Alarm  values  Values and engineering unit will be automatically corrected if changed to a different  engineering unit    F or   C   The default values are the Min and Max  values entered in the Temp  Range  menu  refer to Section 3 18 3                                    Field Setup Menu Temp  Options Alarm Values  More Options  lt up gt  Display OFF ON CF   Output Cal  Temp  Units  Output Selection Temp  Range Low Alarm  Control Settings Alarm OFF ON   000   Temp  Options  gt  Alarm Values  gt   Humidity Lonworks Temp  High Alarm  More Options  lt down gt    999                                   3 18 6  LonWorks Temperature    The LonWorks Temperat
34. orm all three calibration points  The correction values  are to be store into an additional EPROM location and combined with the original calibration values  performed in the factory menu  A user can return the device to its original factory calibration by  selecting the Factory Defaults menu in the Field Setup menu  see section 3 26            Field Setup Menu                More Options  lt up gt                 Backlite Timer Trans  Cal   Eng  Units  DP Display Format Space 1    Alarm options  Transducer Cal   gt   More Options  lt down gt                              gt           Alarm Delay          0 to 9999 seconds    Space 1   30                                                                       Space 1 Input Min  Value CPU Taking  Min  Cal          0 1000  Inch we Samples  50  Cal   gt   Span Cal   Press ENTER   Please Wait    Return to Menu   Space 1 Input 50  Value CPU Taking  Min  Cal   0 0000  Inch we Samples  50  Cal   gt   gt   Span Cal   Press ENTER   Please Wait    Return to Menu   Space 1 peus CPU Taking   Min  Cal  CPOO Tuch Samples  wc   50  Cal    Span Cal   gt    Press ENTER   Please Wait     Return to Menu                                     13    Paragon Controls Incorporated  Rev  V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480          Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 15  OUTPUT CALIBRATION    The Output Calibration menu allows the user to make corrections to the minimum and maximum  Process and Contro
35. p  Options Cont  Setpoints   Change  100  Humidity Output Start   50   More Options  lt down gt  More Options  lt down gt                          15    Paragon Controls Incorporated  Rev  V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480          PCI SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 17 4  Setpoint Internal External    The Setpoint menu allows the user to select between internal  INT  setpoint  entered by the menu or  through the network  or remote external  EXT  setpoint  The default is INT                                               Field Setup Menu Control Settings Setpoint  More Options  lt up gt  Tuning Parameter INT EXT  Output Cal  Action  Output Selection Door Interlock  INT   Control Settings  gt  Setpoint Int Ext  gt   Temp  Options Cont  Setpoints  Humidity Output Start  More Options  lt down gt  More Options  lt down gt                                               3 17 5  Controller Setpoint Values    The Controller Setpoints menu allows the user to enter Positive  Negative and Off setpoint values  The  default values is 0 0000  If values entered are outside of acceptable range  an error message will indicate  the acceptable range                                                                       Field Setup Menu Control Settings Cont  Setpoints   More Options  lt up gt  Tuning Parameter Pos   Output Cal  Action  0 0000    Output Selection Door Interlock Neg   Control Settings  gt  Setpoint Int Ext  0 0000    Temp  Opt
36. s  lt up gt   Output Cal  ACH Alarm Value Lonworks Flow ACH  Control Settings Lonworks Flow ACH  OFF ON   Temp  Options  Humidity  OFF   Flow ACH  More Options  lt down gt                                                  3 21  MAC ADDRESS       The MAC Address menu allows the user to set a unique device address when connecting a Guardian    Infinity to a Paragon Remote Pressure Monitor  RPM   The default is 201                    Instance Number       Field Setup Menu MAC Address  More Options  lt up gt   MAC Address  201      default   201     Password Timeout  Field Password  Factory Password  Factory Defaults     range   201 to 254                                            23 Paragon Controls Incorporated  Rev  V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    PCI SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 22  INSTANCE NUMBER    The Instance Number menu allows the user to set a unique device network address for BACnet    communications  The default is 1201                                   Field Setup Menu Instance Number  More Options  lt up gt   MAC Address  1201     Instance Number  Password Timeout  Field Password  Factory Password    Factory Defaults    3 23  PASSWORD TIMEOUT    Password Time Out is the amount of time a user has after the last key stroke to make changes before the                 default   1201     device will again request a password to be entered  The default is 15 minutes                                   Field Set
37. up Menu Password Timeout  More Options  lt up gt   MAC Address  minutes   Instance Number  Password Timeout  gt   15     Field Password  Factory Password  Factory Defaults                            3 24  FIELD PASSWORD    The Field Password menu allows the user to enter a unique 5 digit numeric password  An error message  will appear if the user does not enter the same password both times  The initial factory set password    is 00000                                   Field Setup Menu                            More Options  lt up gt   MAC Address  Instance Number  Password Timeout  Field Password  Factory Password  Factory Defaults                Enter New Re Enter  Password New Password   00000   gt   00000     Press Enter    Press Enter                                           24    Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 25  FACTORY PASSWORD    The Factory Password menu allows the factory personal access to the factory menu                       Field Setup Menu Enter Factory  More Options  lt up gt  Password  MAC Address  Instance Number  00000   Password Timeout  Field Password Press Enter  Factory Password  gt   Factory Defaults                            3 26  FACTORY DEFAULTS    If field changes are made to the Guardian Infinity program and it is determined that they were made  incorrectly  by selecting YES and pressing enter in both of the Fa
38. ure menu allows the user to disable the Temperature analog input and enter the  Temperature value via LonWorks network communications  LonWorks Option Required                                    Field Setup Menu Temp  Options Lonworks Temp   More Options  lt up gt  Display OFF ON Lonworks  Output Cal  Temp  Units Temperature  Output Selection Temp  Range  OFF ON   Control Settings Alarm OFF ON  Temp  Options  gt  Alarm Values  OFF   Humidity Lonworks Temp     gt   More Options  lt down gt                                                  19    Paragon Controls Incorporated  Rev V1 6  7 30 09  Phone 707   579 1424  Fax 707   579 8480    Ke  SPM 4000 Guardian Infinity Operation  amp  Maintenance Manual    3 19  HUMIDITY OPTIONS  Menus are displayed only if the Humidity Option is factory installed     3 19 1  Humidity Display ON OFF    The Humidity Display ON OFF menu allows the user to turn the Humidity value on the display on or  off  The default is OFF                 Field Setup Menu Humidity Displayed  More Options  lt up gt  Humidity ON OFF  gt  Humidity Value  Output Cal  Alarm ON OFF  Output Selection Alarm Values  OFF ON   Control Settings Lonworks RH  Temp  Options  ON   Humidity  gt   More Options  lt down gt                                               3 19 2  Humidity Alarm ON   OFF    The Humidity Alarm On OFF allows the user to enable or disable the High or Low humidity alarm  function  The default value is ON     Field Setup Menu Humidity Alarm ON OFF  More Optio
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Descargar - Instituto Nacional de Aprendizaje  CARPROPRE CARPROPRE  AYA12/ AYA8 取扱説明書  SummaSketch III Printable Help Files  Manual de Montagem  高圧電源ユニット取扱説明書PDFはこちら  ねりま食品衛生だより第53号 食中毒に気をつけよう!(PDF:510KB)  Origin Storage 500GB TLC SATA 2.5"  Je participe, nous décidons !  D`AUBERVILLIERS - Atlas du Patrimoine    Copyright © All rights reserved. 