         Contents
1.        3 3 Status Relay    The O  has two alarm relays  R01   R02  and two open collector outputs  R03   R04   In the following description  they are referred to as alarm relays   Display of the actual status of alarm relays  Manual operation of the alarm relays     Symbol Setting Status   Function  R01 Relay No  01 o   Select Relay No        OFF   Relay OFF  No gas alarm   ON   Relay ON  Gas alarm   OFF ie OFF Manual OFF   Relay manual OFF  Manual ON   Relay manual ON    3 3 1 Manual Operation of the Relays  The manual operation of the alarm relays is managed in the menu    Status Relay     If a relay is in the manual  ON or OFF status  the orange  red alarm LED at the Gas Controller is lit continuously     The external operation of the alarm relay via an assigned digital input has priority to the manual operation  in the menu    Status Relay    and to gas alarm     Relays manually operated in the menu    Status Relay    are deleted again by selecting the function    Auto   matic        Acknowledging the relays in latching mode is also effected in this menu       Manwaton   Select the function of manual operation    Manual ON   Relay ON   Select the function Manual OFF   Relay OFF    Automatic   Delete manual operation  Reset    Reset a latching mode     Manual orF   Take over the function    10    A Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 4 Menu Measuring Values   This menu is for displaying the current value  CV  o
2.     O Display and change of the system parameters  See from point 3 7     HE    H    Automatikprodukter MIN     lt C gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       3 1 Fault Management   The integrated fault management records the last 15 faults in the menu    System Errors    with a stamp indicating  how many days the error has already existed  The day counter subtracts    active ones    from 365  Additionally a  record of the faults occurs in the    Error Memory     which can be selected and reset only by the service technician     An actual fault is displayed in plain text in the starting menu  The failure relay which is defined in the system  parameter    Failure relay    is activated  The yellow LED in the front of the gas controller flashes     In case of fault of a measuring point  MP  the alarms defined in the menu    MP Parameter    are activated addition   ally     3 1 1 Acknowledge a Fault  Attention   Acknowledging a fault is only possible after having removed the cause     Select menu    System Errors     Example  Failure MP 01  lt 3 mA    Reset the fault     Fault reset Cause not eliminated  Reset not possible          3 1 2 Error Memory   The menu    Error Memory    in the main menu    System Error    can only be opened via code level 2    In the error memory the last 15 faults are listed for the service technician even if they were already acknowledged  in the menu    System Error     The deletion of each individual message is effected 
3.    Relay function static   gt  0   Relay function flashing    Time period in sec    Impulse   Break   1 1    3 5 3 Latching Mode  Definition of latching function    Symbol Setting Status  Function S  Relay No  Selection of relay       Latching Mode No   Latching mode non active  Yes   Latching mode active       Acknowledging a latching relay in the menu    Status Relay    is only possible if the gas concentration is again lower  than the alarm threshold including hysteresis  In this case the status latching occurs in the display     Example  Alarm relay R2 with latching mode    On  Alarm 2 ge Gasconcentration higher   lower than threshold    Display in the Menu R2 R2 R2 R2 R2 R2  Status Relay logs on On On Latching Off    On  wn TT  Of  Reset in the Menu On  Status Relay   l      Of    13    A Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 5 4 Horn Function    The internal horn is connected to alarm relay R3  open collector     This alarm output is defined as horn relay by this parameter with the following possibilities to reset   e By pressing any of the 4 push buttons  only possible in the starting menu    e Automatic reset at the end of the fixed time   e By an external push button  assignment of the digital input     The horn function is only activated if at least one of the two parameters  time or digital input  is set     Special function Response    After acknowledging the output  by push button or externally  time st
4.    gt  R2   SPNO SPNC  30 VACIDC  0 5 A  tor tO a R3 R4  Open Collector  30 VDC  50 mA  2 10 VDC 6 11  1 24 VDC 7   K      V M  X4 8 E 14 E    24 VDC RE 2 0 VDC 9 K2  LIN PE 1 24VDC 110 l14 112  i   X4 X5 Option Power Relay  Option Power Supply 90   230 VAC   max  250 VAC 5A  Fig  2 Connection diagram    The analog input function is determined by the hardware  Each PCB has got a label with the specific type   See fig  4   26    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       4 3 Connector Block   Overview O  Module    g O E  a Anal  Output    ENA Start  Point  nput2    209  4 20 mA HE   20         M   oa bk o ON  90000090       Anal  Output  EE  V DC  D   mA    Fig 3 PCB    Fig  5 Housing          Jumper 0  20     Jumper V A Output signal  0 20 mA  4 20 mA     Notset   s  fo 10v  2 10V       oO ON DOA FF WN  gt        o    Fig  4 Selection Output Signal    Option   Power Supply 90 230 VAC     4             ee2e2e  0202020  ASSAS    Option Power Relay           O        O  05050605050    O  O  O  O  O  O    O       27    Automatikprodukter MN    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       5 Commissioning  5 1 Commissioning  Prior to commissioning  the wiring of the O  including all field devices must be completely terminated     Check the optional external transmitter input signal  current or voltage signal   It has to be the same as indicated on  the label of the PCB  See fig  3     Select the cont
5.   0   No overlay function  AV Overlay  120 ppm 120 ppm ppm   Alarm threshold of average overlay    1800 s 1800 s sec    Time for the calculation of the average value    23    Automatikprodukter MN        lt i gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       3 7 5 Customer Password  Code 4   Change the system password for level 4    Symbol Default Status  Function         XXXX cutone Password XXXX   Bennon of an individual 4 digit  customer   s password  level 4     3 7 6 Analog Output   The Single Point Gas Controller has one analog output  A001  with  0 4 to 20 mA    0 2 to 10 V signal  The signal of  MP01 or and MPO2 can be assigned to the analog output  The assignment is effected in the menu    MP Parameters     for each MP  The measuring point sends the signal  which is defined in the menu    C A Mode        The output signal  mA   V  and starting point  0   20   is selected at the I O Board by means of jumper  See fig  5     Out of the signals of all assigned measuring points the Single Point Gas Controller determines the minimum  the  maximum or the average value and transmits it to the analog output  The definition  which value is transmitted  is  effected in the menu    Analog Output 1        The analog output can be calibrated at 4 and at 20 mA  only in mA mode  Therefore an ampere meter  measuring  range 25 mA  can be attached to the AO and the respective factor has to be changed until the analog output corre   sponds to 4 and or 20 mA  During 
6.  User Manual   Single Point Controller  Oxygen  O     Mar  13       3 6 3 Measuring Range    The measuring range can be defined arbitrarily between 10 and 10000  The measuring ranges in the table gas type  are only recommendations without obligation     The measuring range for MPO1  inside toxic sensor  is factory set  the measuring range for MPO2 must agree with  the signal  4 to 20 mA    0 2 to 10 V  of the attached gas transmitter      4 mA    0 2 V   Display O  ppm   20 mA   10 V   Display of the ultimate value of the measuring range     3 6 4 MP Signal    Gas transmitters using electro chemical or catalytic beat gas sensors normally produce a linear 4 to 20 mA    0 2 to  10 V signal  proportional to the gas concentration     Semiconductor gas sensors produce a non linear  exponential  signal  This signal leads to a non linear 4 to 20 mA     0 2 to 10 V signal of the gas transmitter     The Single Point Gas Controller O  is prepared for gas transmitters with linear signal as well as for Gard analog  transmitters with semiconductor sensor and non linear signal  The classification of signals is defined in this menu     Symbol  Description   Setting Status  Function 22  MP 01  Measuring Point  __  Selection of MP No     Linear MIP Signal Linear Linear   Transmitter with linear output signal  Non linear   Transmitter with non linear output signal       3 6 5 Threshold   Hysteresis   For each measuring point four alarm thresholds are available for free definition  If the gas c
7.  doctor     e Open window MP 01 in menu    Measuring Value       e Connect calibration adapter carefully to the sensor element    e Apply calibration test gas O   150 ml min  1 Bar  14 5 psi    10      e Wait three minutes until the measuring value is stable  adjust the value with potentiometer    Gain    until the  value corresponds to the Calibration gas concentration    e Remove calibration adapter with a careful light turn  Check the sensor for correct mounting   By limiting the gain factor  calibration will not be possible any more when the sensitivity of the sensor  reaches a residual sensitivity of 30   Then the sensor has to be replaced     9 Inspection and Service   Inspection  service and calibration of the SPCX3 should be done by trained technicians and executed at regular  intervals  We therefore recommend concluding a service contract with Automatikprodukter or one of their author   ized partners     According to EN 45544 4  inspection and service has to be executed at regular intervals  The maximum intervals  have to be determined by the person responsible for the gas warning system according to the legal requirements     AP recommends checking the Transmitter every three months and maintaining it every 12 months  If different inter   vals are indicated  always consider the shortest interval     Inspections and services must be documented  The date for the next maintenance has to be affixed to the transmit   ter     9 1 Inspection  The Single Point Controller  H
8.  ee ewe bbe Bee bees wea a eS 37   E E Maintenance tia ow oe wt teeter Ge ad BROS AA EE 37  12 4  Limited Warranty soc sacret SSR BESS EEE eee OEE ee eee EROS eee ea 37   3    ee Au tomatikprodukter MA     lt C gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       Single Point Gas Controller SPC 93    1 Intended Use   The SPC 93 Gas Controller is used for measuring  monitoring and warning of hydrogen sulphide in the ambient air   The Gas Controller is provided with an internal gas sensor  MP01  for O   In addition an external gas transmitter   MPO2  can be connected to the controller for controlling toxic or combustible gases or even Freons  Four alarm  thresholds are freely adjustable for each Measuring Point  MP   Every alarm threshold can be assigned to one of the  maximum 4 alarm outputs  RX   The Gas Controller can interface via the  0 4 to 20 mA or  0 2 to 10 V output signal  with any compatible electronic analog control  DDC PLC control or automation system     The freely adjustable parameters and alarm threshold make a very flexible use within the gas measuring possible   Simple and comfortable commissioning is possible due to factory adjusted parameters     The configuration  parameter settings and operation are easy to do without programming knowledge    The intended sites within the ambient conditions as specified in the Technical Data are all areas being directly  connected to the public low voltage supply  e g  residential  commercial and industr
9.  maintenance message  service phone no    When the days counter reaches zero  the failure signal is activated  the following morning at 9 o   clock  and the phone no  of the service technician occurs in the display     The remaining days until the next maintenance can be read from the menu    Maintenance in        The service phone no  can be entered individually in the next menu     Symbol Default Status  Function S  XXX   Maintenance in    Remaining days until the next maintenance    XXX Maintenance 365 Reset of the maintenance message by entering the  interval number of days until the next maintenance     0853      PhoneNo      Input of the individual service phone no        3 7 4 Average Function   For each active measuring point the Single Point Gas Controller calculates the arithmetic average value out of 10  measurements got within the time unit defined in the menu    AV Time     This average value is indicated in the menu     Measuring Values    next to the current value  At each measuring point the control mode  current or average value   is defined for the alarm evaluation     The alarm evaluation of the control mode average value is overlaid by the current value  when the current value    exceeds the alarm threshold defined in the menu    AV Overlay     The overlay is delayed by the time factor defined in  this menu  With time factor O sec  the overlay is not active    Symbol   Description   Default  Status       120s 120s sec    Delay time of average value overlay
10.  open collector output    Power consumption  without options     Alarm relay  R1   Alarm relay  R2   Binary output  R3  R4   Visualization   Display   Status LED  4   Operation    Two lines  each 16 characters  Normal operation  Fault  Alarm 1  Alarm 2  4 push  buttons  menu driven    Operation Environment  Humidity 15     90   RH non condensing     10   Cto   40   C  14   F to 104   F   5   Cto   30   C  41   F to 86   F   Atmospheric   10      Working temperature  Storage temperature  Pressure range  Physical   Stainless steel V2A   Natural  brushed   113 x 135 x 45 mm  4 48 x 5 35 x 1 8 in    Approx  0 6 kg  1 32 Ibs     IP 55   Wall mounting  pillar mounting   Standard 2 x M 20   Plastics GWPLAST   UL 94V2   RAL 7032  light grey    130 x 130 x 75 mm  5 11 x 5 11 x 2 95 in    Approx  0 6 kg  1 32 Ibs     IP 65   Wall mounting   Standard 3 x M 20   Screw type terminals min  0 25 to 2 5 mm    14 to 30 AWG     EMC Guidelines 2004 108  EEC  pf year on material  without sensor     Enclosure stainless steel  type 5  Colour   Dimensions  W x H x D    Weight   Protection class   Installation   Cable entry   Enclosure plastic version  type C  Flammability   Colour   Dimensions  W x H x D    Weight   Protection   Installation   Cable entry   Wire connection       32    A Au tomatik prod ukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       Options    4     20 mA  input resistance 200 Q   Analog input  1   0  2     10V  input resistance 25 kO   overload  
11. Single Point Controller for  Oxygen  O      0    Un         a             User Manual    Mar  2013    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O        Mar  13  1 Intended Use  e e a a a A a a 4  1 4  Normal Mode os odia a a a ee ee ee ee gE 4  12 Alarm Mode 4 oe 468 ee a ee we E Ch Peewee BRR REE e 4  ES EQUIEIVIOJE  rata ara Bk BO a ae ad de 4  2 Operating InSTrUCTION    s ss sa sa Ne a o NEE de e a dde da al el 28 5  2 1 Description Keypad User Interface       o oo 5  2 2 Setting   Changing Parameters or Set points           ee 6  2 3 Code Levels  sudden dd a te a es i ee ee Pw A ee Be ws 6  3 Menu Overview   sessa A ee ee et ee ee a ew we el we ee DA EN See r   7  31  Fault Management a i moede sk ae Soe alah ee os oe ewe ee we ed BRE we Re Boe ew E 8  3 14   Acknowledge   a Fault    4 2 2 eier oe eB dk Be oo e e   e ee er A i 8  3 152 EFOr Memory iia corn Echo A Roa  eee E Spa ee Se We ee ee gs ee a  a 8  3 1 3  System Errors    6 3 e le BS EEE EES Ea eA OS Ge dare SEE ESE GSE E EES A 8 9  3 2 Status Alarm ticas re el a aw At ee A oe a ewe es E 9  373 Status Relay     amp  m   4  4 8  E Ale ee ee a ee ES eee RE aa as eS 10  3 3 1 Manual Operation of the Relays             ennen 10  3 4 Menu Measuring Values    aaua aaa a 11  3 5 Menu Relay Parameters    12  3 5 1 Elei EE EEN 13  3 5 2 Relay Function Static   Flash            a 13  3 5 3 Latching Mode  13  3 5 4  Horn FUNCHION     s ee   KE a RE BD MOR a A EO Oe ee EEN A 14  3 5 5  E
12. Status    MPo1   Measuring Point    SelectionMPNo     A 0   MP Signal not assigned to analog output  1   MP Signal assigned to analog output 1       21    A Au tomatikprodukter MA     lt C gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       3 7 Menu System Parameters  Displays and changes the system  parameters of the Gas Controller  module     Main menu        l    See Menu 3 7 1    See Menu 3 7 2    See Menu 3 7 3    See Menu 3 7 3    See Menu 3 7 4    See Menu 3 7 4    See Menu 3 7 3    See Menu 3 7 5    See Menu 3 7 7    See Menu 3 7 8    HEHH           HH        See Menu 3 7 7    See Menu 3 7 7    22    ee Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 7 1 Service Mode  When the service mode is active  ON  the alarms are not transmitted to the alarm relays  in case of calibration or  service work   The service mode is reset automatically after 60 minutes or manually in the menu    Service Mode        Symbol Default Status    Off Service Mode Off   Alarms activate the associated alarm relays  On  Alarms are not transmitted to the alarm relays       Symbol  Description  DefaultStatus   Function O  SPCO3 XX_   Software version    XX Software Version    3 7 3 Maintenance Concept  Integrated in the O  system there is a control of the maintenance intervals required by law or by the customer     At commissioning or after maintenance the number of days until the next due maintenance is entered   Reset of  the
13. act for relay 2 with jumper NC NO  See fig  2 and 3    Select the analog output signal with jumper V A and 0 20   See fig  3 and 4    After switching the power supply    ON    and at the end of the Power ON Time  the O  is ready for use    The O  is delivered with standard parameters and set points for the on board sensor  MP 01   These parameters  have to be checked at commissioning and adjusted if necessary  If an additional external transmitter is connected     then you have to set the parameters for MPO2 according to the intended application     The standard parameters can be taken from the following configuration and parameter card  We recommend regis   tering the individual parameters and set points into the list     We recommend checking the parameters and set points according to the following check list     28    A Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       5 2 Checklist Commissioning    E   Parameter faveragefunction      Password level  customer s password         Function analog outpar O     Define teutre O   Power on me    Service phomeo     DEER    Peay le laa  sch TTT   Function static  fash III  latchingmode II  Weier     Externat relay operation III   belay oNtme ITT  beyon ITT       MP mode   Gas type   Measuring range   MP signal   Threshold 1   Threshold 2   Threshold 3   Threshold 4   Hysteresis   Delay ON time   Delay OFF time   C A mode   Assigned failure  lt  gt  alarm  Assigned alarm  lt  gt  alarm 
14. and short circuit proof    SR E  CIT A  EE  SE  Serial interfase  Wem  Ee       33    A Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       8 Gas Sensor    8 1 Description   The integrated sensor is a sealed electro chemical cell with three electrodes  sensing  counter and reference  The  ambient air to be monitored diffuses through a membrane filter into the liquid electrolyte of the sensor  The chemi   cal process of the measurement is one of oxidation where one molecule of the target gas is exchanged for one  molecule of oxygen  The reaction drives the oxygen molecule to the counter electrode  generating a microampere  signal  mA  between the sensing and reference electrodes  This signal is linear to the volume concentration of the  sensed gas  The signal is evaluated by the connected amplifier and transformed into a linear output signal     Electrochemical processes always lead by and by to a loss of sensitivity  Typical life time for this sensor is approxi   mately 2 years in normal operation  This will vary somewhat from sensor to sensor  with some working lifetimes  less than 2 years and some more than 2 years  This wear also changes the characteristics of the sensor  requiring  periodic re calibration with the potentiometer Gain  It is recommended that the sensor accuracy be verified every  twelve months and recalibrated as necessary     8 2 Calibration  Required instruments to calibrate the transmitter     e Test gas bottl
15. arm 20     0   gt    a            2 1 Description Keypad User Interface    Exits programming  returns to the previous menu level     Enters submenus  save settings     Scrolls up in main menu and submenus  increases or decreases a value     Moves the cursor     Y e m  e     LED orange  Flashes when alarm one or more alarms are active   Permanently on  when at least one of the relays is manually operated     LED red  Flashes when alarm two or more alarms are active   Permanently on  when at least one of the relays is manually operated     LED yellow  Flashes at system or sensor failure or when maintenance needed     LED green  Power LED    5    A Au tomatik prod ue ter MA     lt C gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       2 2 Setting   Changing Parameters or Set points    Open desired menu window      mM  Code window opens  if no code level approved     After inputting the valid code the cursor jumps on the first position segment to be changed       gt   Push the cursor onto the position segment  which is to be changed    a  Change the parameter   set point     mM  Save the changed value    Finish    2 3 Code Levels  All inputs and changes are protected by a four digit numeric code    password  against unauthorised intervention   All menu windows are visible without entering a code     Level 1   1234   Code level 1 allows the operator to acknowledge alarms and to manually activate the alarm relays     Level 2   Code level 2 is intended for the serv
16. arts  When this time has run out  and the alarm is still acting  the relay is set again     Symbol Setting Status   Function 22222222  Relay No  Po Selection of relay    O   Reset of the relay after time having run out  or by  push button   Quit Mode 1   Reset of the relay by push button  after time having run out  and when alarm is still acting  relay is set again   Response  function      Time Time for automatic reset function or response function  O   no reset function    am Assignment  which digital input resets the output        Acknowledge the horn output    On  Alarm 3    Gas concentration higher  lower than threshold    Time    Relay 3       Acknowledging On  signal       Special function    Response      Return of the horn relay     je  Alarm 3 ee Gas concentration higher   lower than threshold         _   _       Q  Relay 3 j  Of  Acknowledging         signal oF  14    A Au tomatik prod ukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       3 5 5 External Relay Operation    Assignment of the digital input  DI  for external switching of the alarm relay  ON and or OFF   This function has  priority to gas alarm and or manual switching in the menu    Status Relay        Symbol Setting Status  Relay No    Relay Selection     DION   ExternalOn  o   If digital input closed  relay switches ON  DI OFF External Off po   If digital input closed  relay switches OFF       3 5 6 Delay Mode of the Relay     Delay time ON starts when the alarm is releas
17. calibration evaluation of the measuring point signals is not possible  This calibra   tion is effected by the factory  The factors shall not be changed     Symbol   Description Default  Status    Min    Displays the minimum value of all assigned MP  Max    Displays the maximum value of all assigned MP  Average   Displays the average value of all assigned MP    Select    Output Mode    4 0 Calibration 4 0 4    Calibration factor at 4 mA  20 0 20 0 20 0   Calibration factor at 20 mA       3 7 7 Define the Failure Relay  Definition of the failure relay  See also fault management  3 1     Symbol Default Status  Function    Fault Relay RX   Define the fault relay    3 7 8 Power On Time   Gas sensors need a running in period  until the chemical process of the sensor reaches stable conditions  During  this running in period the current signal can lead to an unwanted releasing of a pseudo alarm  Therefore the power  on time is started at theO  after having switched on the power supply  While this time is running out  the Gas Con   troller does not activate any alarms  The power on status occurs in the starting menu     Symbol  Description   Default Status Function o  XX   Define the power on time  sec     24    ee Au tomatikprodukter MA     lt C gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       4 Mounting   Electrical Connection  The Gas Controller is fixed to the wall through the mounting holes at the 4 corners of the housing  These mounting  holes are accessibl
18. cidental or otherwise  The above warranty is in lieu of all other express warranties  obligations or liabilities     This warranty applies only to the SPC X3  Automatikprodukter shall not be liable for any incidental or consequential  damages arising out of or related to the use of the SPC X3     37    A Au tomatikprodukter MA    
19. e after opening the housing  If you use the mounting holes at the bottom part of the housing  the  device loses the protection class IP 65   We recommend considering the following when choosing the mounting place    e Installation height  The specific weight of hydrogen sulphide is higher than that of air  factor 1 19     Recommended installation height is 0 3 m  1 ft   above floor    e Cables are introduced from below    e Keep a minimum distance of 150 mm on the right side in order to open the stainless steel housing    e Customer   s instructions           E         Mounting holes Mounting                        Fig  01 Standard plastic housing Stainless steel housing    4 1 Electrical Connection   The technical requirements and regulations for wiring  electrical security  as well as project specific and environ   mental conditions etc  must be observed when mounting    The electrical installation may only be completed by a qualified electrician in full compliance with pertinent regula   tions    We recommend the following cable types     e Power supply J Y St Y 2x2 x 0 8  e Alarm relay J Y St Y 2x2 x 0 8  e Gas transmitter J Y St Y 2x2 x 0 8    1 The recommendation does not consider local conditions such as fire protection etc     For the exact position of the terminals see the following connection diagram    When choosing the option    Power Supply    you have to make sure that a switch or a circuit breaker is provided in  the building automation especially for the O   I
20. e electrical and electronic equipment and also regarding this device     For private households there are special collecting and recycling possibilities  For this device isn   t registered for the  use in private households  it mustn   t be disposed this way  You can send it back to your national sales organisation  for disposal  If there are any questions concerning disposal please contact your national sales organisation   Outside the EC  you have to consider the corresponding directives     12 Notes and General Information   It is important to read this User Manual carefully in order to understand the information and instructions  The  SPC X3 gas monitoring  control and alarm system may only be used for applications in accordance to the intended  use  The appropriate operating and maintenance instructions and recommendations must be followed     Due to permanent product developments  Automatikprodukter reserves the right to change specifications without  notice  The information contained herein is based on data considered to be accurate  However  no guarantee or  warranty is expressed or implied concerning the accuracy of these data     12 1 Intended Product Application   SPC X3 is designed and manufactured for controlling  for saving energy and keeping OSHA air quality in commercial  buildings and manufacturing plants  i e  detection and automatic exhaust fan control for automotive maintenance  facilities  enclosed parking garages  engine repair shops  warehouses with for
21. e solely responsible for the activation     3 6 7 Control Mode  Definition of the alarm evaluation by means of current  CV  or average value  AV      Symbol   Description Default  Status t    MP01   Measuring Point  _  Selection MP No   cv Evaluation cv CV   Control by the current gas value  AV   Control by the average gas value    Current  average value function see  3 7 4       3 6 8 MP Fault Assigned to Alarm  Definition  which alarms are activated in case of a fault at the measuring point     Symbol Description Default  Status  MP 01   Measuring Point  __  Selection MP No     Alarm   1234   O   Alarm not ON at MP failure  Fault  0000   Failure MP FER  l  Alarm ON st MP failure    3 6 9 Alarm Assigned to Alarm Relay  Each of the 4 alarms can be assigned to any alarm relay  Unused alarms are not assigned to any alarm relay     Symbol Description Default  Status    MP01   Measuring Point    Selection MP No        Al 01 01   Alarm 1 activates alarm relay R 01  1 A2 02 02   Alarm 2 activates alarm relay R 02  A3 03 03   Alarm 3 activates alarm relay R 03  A4 00 00   Alarm 4 doesn   t activate any alarm relay    Automatikprodukter MN       20       GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 6 10 MP Signal Assigned to Analog Output   The measuring point signal can be assigned to the analog output  At this the signal defined in the control mode   current or average value  is transmitted    Analog output see also  3 7 7    Symbol Description Default  
22. e with synthetic air  20   O   80   N  or O   free ambient air    e Test gas bottle with O   ppm  in the range of 30     70   of the measuring range  Rest is synthetic air   e Gas pressure regulator with flow meter to control the gas flow to 150 ml min    e Calibration adapter with tube  Type  Calibr set AT 1110C01 See fig  06   e Small screwdriver     Note  Please observe proper handling procedures for test gas bottles   8 2 1 Zero Point Calibration  Consider the running in period of the sensor  at least 18 hour      e Open window MP 01 in menu    Measuring Value       e Connect calibration adapter carefully to the sensor element    e Apply synthetic air  150 ml min  1 Bar  14 5 psi    10    or O   free ambient air    e Wait 1 minute until the measuring signal at MP 01 is stable  push button    Zero    for 8 seconds   After successful calibration the measuring signal is corrected automatically   If the zero point is out of the admissible range   gt  10   of measuring range  before calibration  there is no cor   rection of the measuring signal  The sensor has to be replaced    e Remove calibration adapter carefully by turning lightly  Check the sensor for correct mounting     34    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       8 2 2 Gain Calibration   Notes    O  calibration gas is toxic  never inhale the gas    Symptoms  Dizziness  headache and nausea    Procedure if exposed  Take the victim into fresh air at once  call a
23. ed and or delay time OFF starts when the alarm returns to normal  condition     Symbol Setting Status   Function    Relay No  Relay Selection    Mode OFF  Relay is only deactivated at the end of the defined time   sec   O sec    No delay    Ge Delay Time ON Mode ON  Relay is only activated at the end of the defined time  sec    0 sec    No delay  i o      0 Delay Time  OFF       15    A Au tomatik prod ukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       3 6 Menu MP Parameters    Display and change of parameters  assignment of alarms to alarm relays and activation of Measuring Points  MP       Main menu      Selection of MP     vi    Activate or deactivate MP  See 3 6 1    Define gas type  See 3 6 2    Define measuring range  See 3 6 3    Adjust signal form of the transmitter  See 3 6 4    Define threshold 1  See 3 6 5    Define threshold 2  See 3 6 5    Define threshold 3  See 3 6 5    Define threshold 4  See 3 6 5    e   AAA a    16    Automatikprodukter MIN       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       Hysteresis  See 3 6 5    Set delay time ON  See 3 6 6    Set delay time OFF  See 3 6 6    Define control mode  See 3 6 7    Assign MP fault to alarm  See 3 6 8    Assign alarm to alarm relay  See 3 6 9    Assign MP signal to analog output  See 3 6 10    3 6 1 Activate   Deactivate MP    Symbol   Description  MP 01      Measuring point   AA Selection MP No     Not active   Measuring point not activated at the  contro
24. g   Electrical Connection                o                          2         25  A1 Electrical  CONNECHON  s is A A A Ew A ee Ee a al 25  42  CONNECTION DIAS A dos a a a AAA a a a aci br de 26  4 3 Connector Block   Overview O Med estriado seres reas taria 27   5 COMMISSIONING     se see ee EEN AE we Re a E hee ee ee ee EE er a 28  5 1     COMMISSIONING e ars ee ee a oe we ee ee a Se ee we ee A eek eee   28  5 2 Checklist Commissioning          eee nsn 29   6 Configuration and Parameter Card     ee 30  6 1 Configuration Card of System Parameters       30  6 2 Configuration Card of Alarm Relays                e e e a a O E E a a E a a 30  6 3 Configuration Card of Measuring Parameters    31   7 Specifications SPC 93 o aa sasaa 2 eae a a 32  8 Gas Sensor co ida a Ee EE a E eee   34  8 1  DeSCrIDUOM   2 2 earn  oo a ae ee  amp  eet eae Beh BE eRe Ee ee eh 4 Se eee eae Be  34  39 2 CanDo vi ai ah seed acl  WE a SR Re ok aa Be a de edd de Ba Alek Ee chew E ar 34  8 2 1 Zero Point Calibration    2    ee 34   8 4 4 Gain Calibration EE 35   9 Inspection and Service E cei ssar sauis ee es 35  A E EE 35  9 2 Service and Calibration              ee 35  9 3 Exchange of Sensor Element    36   10 Specification G  s Sensor s s e scema E a EL ORL  AAA AN EE 36  11    Part Disposals rriena O SS OR EE ewe Sn oe es ESE ee ok 37  12 Notes and General Information                      eee 37  12 1 Intended Product Application    2    ee 37  12 2 Installers    Responsibilities  ooo 6 ee eee eee ve
25. ial ranges as well as small  enterprises  according to EN50 082      The Single Point Gas Controller SPC 93 must not be used in potentially explosive atmospheres     1 1 Normal Mode  In normal mode  the gas concentrations of the active transmitters are continuously polled and displayed at the LCD  display in a scrolling way  The controller also monitors the communication to all active transmitters     1 2 Alarm Mode   If the gas concentration reaches the programmed alarm threshold  the alarm is started  the assigned alarm relay is  activated and the red alarm LED is flashing  The set alarm can be read from the menu Alarm Status  When the gas  concentration falls below the alarm threshold  the alarm is automatically reset  In latching mode  the alarm has to  be reset manually in the menu Relay Status     1 3 Fault Mode   If the controller detects an analog signal outside the admissible range   lt  3 mA    gt  22 mA  from an active transmitter   the assigned fault relay is set and the error LED is blinking  The error is displayed in the menu Error Status in clear  text  After removal of the cause  the error message is acknowledged in the menu Error Status     4    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       2 Operating Instruction  The complete configuration  parameterization and service are made via keypad user interface in combination with  the display screen  Security is provided via two password levels     O Alarm 1 Al
26. ice technician to change parameters and set points     Level 3    With code level 3 it is possible to register and deregister transmitters in addition to code level 1  This code is  released by Automatikprodukter only in emergency situations    Level 4    Code level 4 is intended for updating the maintenance date  Normally the code is only known by the service    technician and can be changed individually via code level 2     The release of a code level is cancelled if no button is pushed within 15 Minutes     6    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       3 Menu Overview  The operation of the Single Point Gas Controller O  is effected by a simple and logical menu structure which is easy  to learn     The operating menu contains the following levels   e Starting menu  Scrolling of the measuring points of all registered transmitters in 10 second intervals    e Main menu  e Submenu 1 and 2    Staring menu Main menu Submenu       g    O Display and reset of errors  See from point 3 1       O Displays the status of actual alarms  See point 3 2    Display of the relay status   O Manual operation of the relays  Reset function of the relays  See from point 3 3    Q Displays the measuring values  See point 3 4    Q Display and change of the relay parameters  See from point 3 5    Display and change of the measuring point parameters  Activate or Deactivate MP    m  Assignment of the alarms to the alarm relay  See from point 3 6
27. in the same way as the reset of a  fault     8    A Auto matik prod ue ter MA     lt C gt  User Manual   Single Point Controller  Oxygen  O     Mar  13       3 1 3 System Errors  The following system error messages are recorded     MP 02  gt  22 mA Current signal at analog input  gt  22 mA   11 VDC   External Transmitter    Cause  Short circuit at analog input or transmitter not calibrated  transmitter defective   Solution  Check cable to transmitter  make calibration  replace the transmitter    MP 02  lt  3 mA Current signal to analog input  lt  3 mA   1 3 VDC   External Transmitter    Cause  Wire breaking at analog input or transmitter not calibrated  transmitter defective   Solution  Check cable to transmitter  make calibration  replace the transmitter    GC Error  Internal communication error I O Board to LCD Board    Cause  Internal error    Solution  Change the Gas Controller module    Maintenance  System maintenance is necessary    Cause  Maintenance date exceeded    Solution  Make the maintenance     3 2 Status Alarm  Display of the actual alarms in plain text in the order of their arrival  Only those measuring points are dis   played  where at least one alarm is active  Changes are not possible in this menu     Symbol   Description  Function    MP 01 Measuring  MP  Point No   EA       Al   Alarm 1 ON  A2   Alarm 2 ON  AX Status alarm A3   Alarm 3 ON  A4  Alarm 4 ON    9    A Au tomatik prod ue ter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13
28. klifts  fire stations  tunnels  etc       12 2 Installers    Responsibilities   It is the installer   s responsibility to ensure that all SPC X3 units are installed in compliance with all national and lo   cal regulations and OSHA requirements  All installations shall be executed only by technicians familiar with proper  installation techniques and with codes  standards and proper safety procedures for control installations and the  latest edition of the National Electrical Code  ANSI NFPA7O   It is also essential to follow strictly all instructions as  provided in the User Manual     12 3 Maintenance   We recommended checking the SPC X3 system regularly  Due to regular maintenance differences in efficiency can  easily be corrected  Limited Warranty Re calibration and part replacement may be implemented in the field by a  qualified technician and with the appropriate tools  Alternatively  the easily removable plug in transmitter card with  the sensor may be returned for service to Automatikprodukter     12 4 Limited Warranty   Automatikprodukter warrants the SPC X3 against defects in material or workmanship for a period of one  1  year  beginning from the date of shipment  Should any evidence of defects in material or workmanship occur during the  warranty period  Automatikprodukter will repair or replace the product at their own discretion  without charge     This warranty does not apply to units that have been altered  had attempted repair  or been subjected to abuse  ac   
29. ller       MP Status Not active Active   Measuring point activated at the controller     MP01   On Board sensor   MP02   External Transmitter  optional     17    A Au tomatik prod ue ter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 6 2 Selection Gas Type  Assign gas type to attached gas transmitters     Symbol   Description   Setting   Gas Measuring range     HE type  MP 01 Measuring  point       Gas type Carbon monoxide 0 300   Oxygen  increasing   0 25  E Ozone 0 5  Toxic gas O   XX  Carbon dioxide  0 50  Humidity   0 100      Temperature 0 50   Refrigerant gas 0     2000  Refrigerant gas 0     300  Refrigerant gas 0 300  Refrigerant gas 0 300  Refrigerant gas 0 300  Refrigerant gas 0 300  Refrigerant gas 0 300  Refrigerant gas 0 300  Refrigerant gas 0 300  Refrigerant gas 0     2000  Refrigerant gas 0     2000  Refrigerant gas 0     2000  Refrigerant gas 0     2000  Air quality 0     2000  Ethylene oxide 0 20  Chlorine 0 100  Hydrogen sulphide 0   50 100 200  Sulphur dioxide 0 100  Carbon dioxide    0     2000  Oxygen  falling   0 25  Ammonia 0 300  Nitrogen dioxide 0 25  Nitrogen oxide 0 50  Combustible gas 0 100    t Recommendation without obligation   2 Oxygen measurements  Alarm at increasing concentration   3 Oxygen measurements  Alarm at falling concentration      Carbon dioxide measurements with unit ppk  1 vol    10 ppk     gt  Carbon dioxide measurements with unit ppm  1 vol    10 000 ppm     18    ee Au tomatikprodukter MA    GID
30. oncentration is higher  than the adjusted alarm threshold  the associated alarm is set  If the gas concentration falls below the alarm thresh   old inclusive hysteresis the alarm is again reset     Unused alarm thresholds have to be defined at measuring range end point  in order to avoid false alarms     Le  For O  measurement  Pay attention to the alarm activation at decreasing or increasing concentration     Symbol   Description Default  Status    MP 01   Measuring Point    __  Selection MP No     20 ppm   Threshold Threshold 1   Gas concentration  gt  Threshold 1   Alarm 1  Threshold 2   Gas concentration  gt  Threshold 2   Alarm 2    Threshold 3   Gas concentration  gt  Threshold 3   Alarm 3   Threshold 4   Gas concentration  gt  Threshold 4   Alarm 4   Hysteresis Gas concentration  lt   Threshold X    Hysteresis     Alarm X OFF       19    Automatikprodukter MN    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 6 6 Delay of Alarm ON or OFF  Definition of alarm ON and or alarm OFF delay  The function applies to all alarms of an MP     Os Delav Time ON Gas concentration  gt  Threshold  Alarm is only activated at  Y the end of the fixed time  sec    O sec    No Delay       Gas concentration  lt  Threshold  Alarm is only deacti   Os Delay Time OFF vated at the end of the fixed time  sec    0 sec    No  Delay    The delayed activation of an existing gas alarm can cause damage to persons and objects   The commissioning technician and or the operator ar
31. r the average value  AV  with gas unit and gas type for each ac   tive measuring point according to the defined mode of control  CV or AV mode   For gas type CO both values are  displayed together     Symbol Setting Status   Function    MP 01 Measuring P  No  Selection of MP No  See 3 6 2    o  po   ed  ppm  Gasunit    See 62     averagevaue    Average value  10 measured values within the time unt      controtmode    Display of selected control mode  Vora     Faime  gt    cores  lt  3 MAS ana       11    ee Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 5 Menu Relay Parameters  Display and change of the parameters for each alarm relay     Main menu           Select relay No      Relay mode  See 3 5 1    Relay function  See 3 5 2    Activate latching mode  See 3 5 3    Definition of horn function  See 3 5 4    Definition of external  relay operation  See 3 5 5    Set delay ON time  See 3 5 6    Set delay OFF time  See 3 5 6    AAA     12    Automatikprodukter MN    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       3 5 1 Relay Mode  Definition of relay mode     Symbol   Description   Setting Status  Function LL O  Relay No     Selection of relay       De energized   Relay Mode De  energized   De energized   Alarm ON   Relay ON  Energized   Alarm ON   Relay OFF    3 5 2 Relay Function Static   Flash  Definition of relay function    Description Setting  Status    Relay No fF   Selection of relay  Function 0O
32. relay    Assig  MP sig   lt  gt  analog output       1 MP 01   On Board Sensor  MP 02   external Transmitter    29    A Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       6 Configuration and Parameter    Project No    Commissioning   Company  Commissioning   Date    6 1 Configuration Card of System Parameters    Service Soft  Mainen    Service Maint  Cos  Fault Power  ware ance Phone en ance   tumer Relay  ON Time  Version   dueinx interval  days  Default   SPC 03 2a  46708 ppm Time   AV Time 365  885298  S   bechte       Max     Customer     TI       Service Technician    30s  Ss  Ss feed    Latching Horn Delay Time    Mode Function       30    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       6 3 Configuration Card of Measuring Parameters    MP MP Gas Measur  MP Thresholds  ap               Assigned MP Assigned Alarm  Delay Tinie  sec  EMAV Fault  lt  gt  Alarm  lt  gt  Alarm Gen       31    A Au tomatikprodukter MI       Y User Manual   Single Point Controller  Oxygen  O     Mar  13       7 Specifications O     Power supply 18     28 VDC AC  reverse polarity protected  100 mA  max  2 5 VA    Analog output signal  0  4     20 mA  load  lt  5000  Selectable  Current   Voltage  0  2     10 V  load  gt  50 ka    Starting point O or 20  Proportional  overload and short circuit proof    30 VAC DC  0 5 A  potential free  SPDT  30 VAC DC  0 5 A  potential free  SPNO SPNC  30 VDC  0 05 A
33. t must be installed easily accessible near the O   It has to be marked  as a disconnecting device for the SPC  This switch or circuit breaker shall meet the relevant requirements of IEC  60947 1 and IEC 60947 3     25    A Au tomatikprodukter MA                                                                                                                                                                                                                                                          lt C gt  User Manual   Single Point Controller  Oxygen  O                                                                                                                                                                                Mar  13  4 2 Connection Diagram    0 2   20V Fi i O  Option Digital  E Li  Internal Buzzer X5   Input Se eG Cin et es      24 VDC 3     es DIO 1 Dee  b LO WBC  EE al 5 5  SE R3  24V     ak    SE KZ  4  20mA lal  ES 0 V 4 A  Fali   x5  Option External    24 VDC 3     6 R  ption Internal   5          Warning Light    oun    al  Flashlight A  Oot LY  5  Analog_Inp     6  NO 1  ption External OV SxS ASSN God ES OSE Ee Sedo HERG ESE Hee  _ Transmitter  MP 02  X4    4 Analog Out mr AT nea S   A  Go 3 24 VDC Out 8  COM 1 21 4 K3    oO   i  522 2  o VDC al com2 Br hh    ASN R2 4      Pin4 Alarm4  SG 1 24 VDC re 2 440  NO NC_2 Pin 2   Alarm 3   gt    d i  5    ajO Option Power Relay K3  One iz z M max 250VAC 5A    2879  amp 3 gt Q R1  SPDT  30 VAC DC  0 5 A eee  233 95  
34. xternal Relay Operation   lt  lt    sa 445 4 Ra a    awe HR ea ae e T 15  3 5 6 Delay Mode of the Relay             15  3 6 Menu MP Parameters s    o s xe aS eee ea he REPRESSES OOM AEE AANA E r   16  3 6 1 Activate     Deactivate MP    2    ee 17  3 6 2 Selection Gas Typed    4 4 0 3s whee a a BRR See aaa SG 18  3 6 3  Measurine RANGE  gr gee eae er OS ES eo DA a ee Ge a 19  364 MP Signals  is ee a a a ee eae eee EE ESS 19  3 6 5 Threshold   Hysteresis       rrna e a e o o o La E E E a E DA 19  3 6 6 Delay of Alarm ON or OFF    20  3 6 7 Control Moge sy eect da ao de ahead a a A de a ER id Ge ae en A e wea 20  3 6 8 MP Fault Assigned to Alarm             20  3 6 9 Alarm Assigned to Alarm Belay   eee ene eus 20  3 6 10 MP Signal Assigned to Analog Output             a a a 21  3 7  Menu System  Parameters  s ss aaa Eet ede Be A A de a E E a 22  3 7 1  Service Mode    moss ee be eee eae he EEG Ee eee ee eee eee ea a 23  3 222 Software Versions  diria aa yh ot Ae wa BS woo a Dae ee oo a ow a o 23  3 7 3 Maintenance Concept  ss as 266 few dag ee eS SOR a Ee ee ee ee eS 23  3 7 4 Average Function    ee 23  3 7 5 Customer Password  Code A  24  3 726 Analog Output 238 sce oo BD Bale en ee ewe ee ES ho oe ee ee ee er 24  3 7 7 Define the Failure Relay    2  eer ere eo bk oo eee Soe A ee ee a 24  3 725 POWER OM TIME  an accrue  6 ra Ae GE  Gp woe ds Eee eon sence ge ee 24  2    A Au tomatikprodukter MA       Y User Manual   Single Point Controller  Oxygen  O        Mar  13   4 Mountin
35. ydrogen Sulphide should be controlled regularly by a competent person according to  EN 45544 4  The following has to be checked in particular     e  Maintenance  calibration interval not exceeded    e Visual inspection of the transmitter including cable for damage etc   e Remove dust deposits  especially at the gas inlet    e The filter at the gas inlet has to be replaced if extremely dirty    e Check the function of alarm relays     9 2 Service and Calibration  When performing the maintenance you have to do the calibration and the functional test in addition to the inspec   tion    e Calibration  See section 8    e Functional test  Check the output signal at the test pins during calibration     35    A Au tomatikprodukter MA    GID User Manual   Single Point Controller  Oxygen  O     Mar  13       9 3 Exchange of Sensor Element  Consider static electricity  See point 3   Sensor should always be installed without power applied     e Unplug old sensor element from the PCB    e Take the new sensor out of the original packing   e Plugin the sensor element into the PCB at X3 X7   e Calibrate according to section 8     10 Specification Gas Sensor    Sensor performere O     Calibration adapter  Fig  6  Type  Calibration set         36    Automatikprodukter MIN       GID User Manual   Single Point Controller  Oxygen  O     Mar  13       11 Part Disposal  Since August 2005 there are EC wide directives defined in the EC Directive 2002 96 EC and in national codes con   cerning the wast
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
取扱説明書~本体表示などの注意書きに従った使用状態で保証期間内に  VSP 112 User Manual V1.0  MURO VISLIDER VL71-FLR User's Manual    P-3 - Oficina de Recursos Humanos  User Manual - Origin Instruments  BOITE 250G ESP  Manuel d`instructions  Cisco Systems 32369 Overview  Model Medio Item 40850 Model Grande Item 40851 VACUUM    Copyright © All rights reserved. 