Home
        Manual iCHILL 200 L
         Contents
1.                                                           PARAMETER CORRESPONDING  VALUE DESCRIPTION LABEL  dP02 01 NTC temperature probe of the evaporator water inlet Ein  dP02 02 NTC temperature probe of the evaporator water outlet 1 and 2 Out  circuit 1  Out2 circuit 2  dP02 03 NTC temperature probe of the common evaporator water outlet Eout  dP02 04 NTC temperature probe of the condenser water inlet Cin circuit 1    CIn2 circuit 2  dP02 05 NTC temperature probe of the common condenser water inlet Cin  dP02 06 NTC temperature probe of the condenser water outlet Coul circuit 1           2 circuit 2  dP01 07 NTC temperature probe of the common condenser water outlet Cout  dP02 08 NTC temperature probe of the dynamic external air setpoint Et  dP02 09 NTC temperature probe of the free cooling water inlet FCIn  dP02 10 NTC temperature probe of the free cooling external air value FCEt  dP02 11 NTC temperature probe of the remote terminal 1 trt1  dP02 12 NTC temperature probe of the remote terminal 2 trt2    dEF1 circuit 1  dP02 13 NTC temperature probe of the combined defrost dEF2 circuit 2  Cdt1 circuit 1  dP02 14 NTC temperature probe of the condenser       circuit 2     Cdt1 circuit 1  dP02 15 Pressure probe of the condenser 4 20       0 5V Cdi  circuit 2  A LP1 circuit 1  dP02 16 Pressure probe of the evaporator 4 20mA   0 5V LP2 circuit 2  dP02 17   Clock  2             TOP DISPLAY  CUSTOM EXAMPLE  Parameter dP01 01  The default read out for the circuit 1 and the circuit 2 
2.                                                        Capacity 2596 5096 7596 10096  Compr  Compressor ON Compressor ON Compressor ON Compressor ON  Out relay   Step P 1 ON Step P 1 ON Step P 1 ON Step P 1 OFF  Outrelay   Step P 2 ON Step P 2 ON Step P 2 OFF Step P 2 OFF  Out relay   Step P 3 ON Step P 3 OFF Step P 3 OFF Step P 3 OFF  Inverse action with sequential step  Compressor P1 P2 P3 Potenza   0 96   25 96   50 96   75 96   100 96             Pg 66 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    ATTENTION  When working with capacity control in sequential step in direct or reverse modes  if the power requested is 50  and 75  the unit turn  on also the step 25  that must be enabled to make run the other two     28 1 MINIMUM LOAD START  UP    Par  CO07 configuration of the start up with minimum load and compressor type    It allows to configurate the 1   partialization valve of the compressor that can be the partialization start up valve of an alternative  compressor or the minimum load for screw compressor    In this way the lower value of partialization  normally is configured as the 1   output with the 25   can be used as minimum start up load  and also as thermoregulation step or only as minimum start up load and never as thermoregulation step    EXAMPLE   Having one compressor with 3 partializations  at the compressor start up  with CO07 0  the partialization valve is enabled only for the  time CO13 but it won t be never used during the
3.                                     VALUE DESCRIPTION LABEL  dP01 01 NTC temperature probe of the evaporator water inlet Ein  dP01 02 NTC temperature probe of the evaporator water outlet 1 and 2          ez p p    Out2 circuit 2  dP01 03 NTC temperature probe of the uscita common evaporator water outlet Eout  dP01 04 NTC temperature probe of the condenser water inlet       1 circuit 1      CIn2 circuit 2  dP01 05 NTC temperature probe of the common condenser water inlet Cin  dP01 06 NTC temperature probe of the condenser water outlet Coul circuit 1      Cou2 circuit 2  dP01 07 NTC temperature probe of the common condenser water outlet Cout  dP01 08 NTC temperature probe of the dynamic external air setpoint Et  dP01 09 NTC temperature probe of the free cooling water inlet FCIn  dP01 10 NTC temperature probe of the free cooling external air value FCEt  dP01 11 NTC temperature probe of the remote terminal 1 trt1  dP01 12 NTC temperature probe of the remote terminal 2 trt2      dEF1 circuit 1   dP01 13 NTC temperature probe of the combined defrost dEF2 circuit 2  Cdt1 circuit 1   dP01 14 NTC temperature probe of the condenser Cdt2 circuit 2             Pg 48 103       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005    15 2 DEFAULT READ   OUT OF THE              DISPLAY    To set the default value displayed on the bottom display   1  Set the parameter dP03   0  it means configurable   2  Selectthe dP02 parameter into the range 1  17 descripted here below     Preliminary   
4.            5           1                                               1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary       Power supply                      230Vac Input  0   230Vac output   10   65     Operating temperature  Naylon supports  D 15mm  Height  Model XVO5PK XV10PK XW22PK  Y 25mm 42mm 64mm                Connections       A 1        PWM input control       PWM output repetition signal       2        3     4     F    Phase       Neutral       5 6    Fan output          Terminals 3 and 4 allows to connect another board in parallel to control two separate fans with the same input control        Terminals 1   2   3   4 are for screw for a 2 5mm wire          Terminals 5   6   F   N are 6 3mm faston          47 2 INVERTER  MICROFAN 380VAC UP TO 4KW OR 8KW  Dixell models XV340GS  power up to 8KW  scheme 2         Scheme 2     47 3 TRANSFORMER    86     The standard power supply is 12 volt AC DC or 24 volt AC DC  optional   The TF10 trasnformer models  230 12 Vac   230  24 Vac  110   12 Vac  24  12 Vac       Pg 98 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    48 TECHNICAL DATA    Housing  self extinguishing ABS   Case  frontal 185x38 mm  depth 70mm  L format   Mounting  panel mounting in a 150x31mm panel cut out  Frontal protection  IP65 with gasket  Display    Top Display 3 digits with d p    Bottom Display 4 digits with d p   Connections  Removable screw terminal block 2 5mm2   Power supply    12Vac dc  10   15    
5.         7           WALL MOUNTING  use the vertical V KIT  black  white and grey  as described in the following scheme     Pg 96 103    23 02 2005    r1 0    1592015300 User manual iCHILL 200 L GB Preliminary          46 ELECTRICAL CONNECTIONS    The instrument is provided with       3 removable terminal blocks MOLEX with 0 5 mm  wires  16   8  22 ways for digital   analogue inputs and modulating outputs    e  4removable screw terminal block STELVIO for 2 5 mm  wires connection  3 4 5 6 ways for the relay outputs       5 ways connector for TTL RS485 interface outputs    e 2 ways connector for remote panels to be connected with the cable CAB CJ30  The remote panels have two terminals for 2 5 mm   wires     e The LW30 KIT is the complete kit with MOLEX   3 mt wires already connected and the STELVIO terminals        Check the connecitons and the line voltage before turning on the power supply   Keep low voltage cables  such as analogue digital inputs outputs and probes  away from power cables and terminals   Respect the maximum load current of each relay output  in case of power loads use filtered contactors     47 ACCESSORIES    47 1 MONOPHASE FAN CONTROL  230VAC AND CUT PHASE CONTROL                                     Models XV05PK XV10PK XV22PK  Power 500W 1000W 2200W  Ampere 2A 4A 9 5A  Scheme 1 1 1           lt   x T x x x   amp  9 2              8  3l              mg   S   8  i    XY E  Tu T Fj                      LL  Y t  nh w  E    Y                                    
6.        Label o the display    b1AC  anti freeze alarm of the circuit  1 in chiller   b2AC  anti freeze alarm of the circuit  2 in chiller   b1Ac  anti freeze alarm signalling of the circuit  1 in chiller   b2Ac  anti freeze alarm signalling of the circuit  2 in chiller     Both the labels are displayed when the alarm is coming from the evaporator inlet probe or  evaporator common outlet probe or when there is only one digital input configured                       Origin Normal conditions  stand by  remote OFF  when the anti freeze probe value is lower than AL26 for  AL28 seconds   With the anti freeze digital input is active    Reset When the anti freeze probe value is higher than A26  AL27  differential   With the anti freeze digital input is active    Restart Automatic     Manual after AL29 events per hours  Reset procedure in Menu function     Icon Blinking   N   Action If AL30 0 only the compressors are turned off and than display shows b1Ac b2Ac  the buzzer and    the alarm relay are not activated     If AL30 0 only the compressors are turned off and than display shows b1Ac b2Ac  the buzzer and  the alarm relay are activated     If the alarm comes from the digital input also the anti freeze heaters are turned on           41 20 B1AH   B2AH ANTI FREEZE ALARM   LOW OUTLET AIR TEMPERAURE AIR AIR UNIT ONLY   ON HEAT PUMP MODE       Label o the display    b1AH  anti freeze alarm of the circuit  1 in heat pump   b2AH  anti freeze alarm of the circuit  2 in heat pump   b1Ah  a
7.      OFF Step P 3 OFF Step P 3 ON Step P 3 OFF          Step control process       Compressor Part  1    Part  2    Part  3       Power involved  0           25            50            75                             100            Par CO06   1 direct action with sequential step  1  the steps are turned on in sequential mode  the outputs are anabled or disabled depending on the output polarity  In case of  thermoregulation request one of the step is turned on or off while the other steps do not change their status        Eg    1 capacity compressor with 3 partializations  4 Power steps                                Capacity 25  50  75  100   Compr  Compressor ON Compressor ON Compressor ON Compressor ON  Out relay   Step P 1 ON Step P 1 ON Step P 1 ON Step P 1 OFF  Outrelay   Step P 2 OFF Step P 2 ON Step P 2 ON Step P 2 OFF  Out relay   Step      OFF Step P 3 OFF Step      ON Step P 3 OFF          Direct action with sequential step       Compressor P1    P2    P3       Power involved          0 96          25            50            75                              100            Par CO06   2 inverse action with sequential step  1  the steps are turned on in sequential mode  the outputs are anabled or disabled depending on the output polarity  In case of  thermoregulation request one of the step is turned on or off while the other steps do not change their status        Eg    1 capacity compressor with 3 partializations  4 Power steps                                        
8.      Relay ON time of the Solenoid valve Intermittent for screw compressor  with 0 0 250 S  SUY ec  the function is not enabled   CO 9 Relay OFF time of the Solenoid valve Intermittent for screw compressor 250 Sec  Compressor start up  CO 10 Kind of compressor start up  0  Direct   vedi avviamento compressors   0 2  1  Part   winding  2  Star delta  CO 11 If CO10  1 part   winding start up time  To change the time delay between the  two contactors of the two compressor circuits  Dec  Se CO10  2 Star delta start up time  To change the time delay between the 0 100 di Sec 0 1 sec  contactor of the line 1 and the contactor of the centre of the star   see part      winding  start triangle functioning   CO 12 If CO10  2 Time of Star delta start  Time delay to turn off the centre star 0 50 Dec  0 1 sec  contactor and to turn on the line 2 contactor  see Star delta functioning  di Sec    CO 13 By pass gas valve start up time   automatic start unloading valve  capacity 0 250  sec  step control   Rotating     Balancing     Compressors Thermoregulation  CO 14 Compressor rotation  See compressor rotation   0   Sequential 0 2  1   Compressors rotation based on time running hours  2   Compressors rotation based on number of starts up  CO 15 Circuit balancing  See Circuit balancing   07 Circuit saturation 0 1  17 Circuit balancing  Evaporator water pump  CO 16 Operative mode of the evaporator pump   supply fan  See Evaporator pump  function   07 Not enabled  evaporator pump or supply fan   
9.     During the normal running condition a disabled compressor is displayed with a blinking label alternated with the measurement value of  the display    If the compressor is disabled these the corresponding labels  C1dS   compressor 1 disabled   C6dS   compressor 6 disabled   The label C1dS   C6dS are available only if the corresponding compressor is configured     17 11 READ OUT OF THE COMPRESSOR DISCHARGE TEMPERATURE PROBE    The menu function allows to read out the compressor temperature probes    COdt FUNCTION shows the discharge temperatures   Label involved in Codt function  CO1t Compressor 1 discharge temperature    CO6t Compressor 6 discharge temperature  1  Use the UP or DOWN keys to select COdt   2  Push SET key  bottom display   CO1t  top display   temperature value of that probe    3  Use the UP or DOWN kys to scroll the list  CO1t or CO2t or CO3t or CO4t or CO5t or CO6t   4  To exit the COEn function push MENU key or wait the timeout   ATTENZIONE   The labels Codt are available only if the corresponding compressor probe is configured    The display resolution is 0 1  C until the read out is 99 9  over 100  C it is 1  C     17 12 READ OUT OF THE RUNNING HOURS    This menu allows to shows all the time running hours of the compressors  supply fan and pumps   Hour FUNCTION to show the controlled load consumption   Label involved in the Hour function    CO1H Compressor 1 running hours    CO6H Compressor 6 running hours    EP1H Evaporator water pump or Supply fan runn
10.    16    The reset becomes manual after AL21   1   15    RESET   e The Automatic Reset is activated when the next compressor thermoregulation is requested  in this case the pressure condition of  the pump down must be satisfied    e The Manual Reset needs to enter the function Menu under the AIrM label  After the reset the next thermoregulation restarts if the  pump down pressure is in normal condition    ATTENTION   If the pump down function is enabled  during the unit start up from digital input as pump down pressure switch and also from   analogue input as low pressure transducer  the compressor will restart only if both the inputs are satisfied        29 6 PUMP DOWN INFORMATION    ATTENTION   SELECTION OF THE COMPRESSOR  for pump down in switching off    Eg  Unit with 2 circuits and 3 compressors each    Having an active digital input as remote off  if the compressor running hours are the same for all the compressors the unit will use the 1    compressor of the 1   and the 2  circuit  therefore the number 1 and 4    If the running hours are not equal for all compressors the unit will use the compressor having the less running time  this for any circuit  configuration    During the pump down process the led of the running mode  chiller   heat pump  is blinking  while if one of the circuits are disabled from  the keyboard the running mode led is not blinking     30 UNLOADING    30 1 HiGH TEMPERATURE OF THE EVAPORATOR WATER INLET    The function is always enabled in chiller 
11.    and buzzer on          41 23 B1LP   B2LP LOW EVAPORATING PRESSURE OF THE CIRCUIT  WITH PRESSURE  TRANSDUCERS ONLY        Label o the display    b1IP  low evaporator pressure from analogue input  1   b2IP  low evaporator pressure from analogue input  2                          Origin The alarm is activated when at least one of the probes   configured as evaporating control  is  lower than ALO3 setpoint if      In chiller or heat pump mode      Stand by or remote OFF when AL08   1     In defrost when AL06 1  The alarm is not signalled if      In defrost  for the time AL07  when the 4 way valve is turned on      For the time set in AL01 after turning on the compressor   Reset When the condensing probe temperature is higher than AL03   AL04  differential   Restart Automatic  Manual after AL05 events per hour  Reset procedure in Menu function    Icon Blinking ZN  Action Alarm Relay   and buzzer on       ATTENTION When the pressure transducers are configured the low pressure alarms are related only to transducer values     41 24 B1TF  B2TF CONDENSER FAN OVERLOAD ALARM          Label o the display       b1tF  Condenser fan overload alarm of the circuit  1   b2tF  Condenser fan overload alarm of the circuit  2                    1592015300 User manual iCHILL 200 L GB      1 0 23 02 2005 Preliminary                   Origin When the digital input is active   Reset When the digital input is not active  Restart Manual  reset from the function menu   Icon Blinking ZN   Action Alarm re
12.   C Dec   10 53   F int   5 0 5 0 bar dec   72 72 psi int  CF 23 PB6 Offset  12 0   12 0   C Dec   10 53   F int   5 0 5 0 bar dec   72 72 psi int  CF 24 PB7 Offset  12 0   12 0   C Dec   10 53      int  CF 25 PB8 Offset  12 0   12 0   C Dec   10 53   F int  CF 26 PB9 Offset  12 0   12 0   C Dec   10 53   F int  CF 27 PB10 Offset  12 0   12 0   C Dec   10 53 E int  CF 28 Pressure value at 4mA or 0 5 Vdc of the PB3 transducer 0 50 0 Bar Dec  0 725 psi int  CF 29 Pressure value at 20mA or 5 Vdc of the PB3 transducer 0 50 0 Bar Dec  0 725 psi int  CF 30 Pressure value at 4mA or 0 5 Vdc of the PB4 transducer 0 50 0 Bar Dec  0 725 psi int  CF 31 Pressure value at 20mA or 5 Vdc of the PB4 transducer 0 50 0 Bar Dec  0 725 psi int  CF 32 Pressure value at 4mA or 0 5 Vdc of the PB5 transducer 0 50 0 Bar Dec  0 725 psi int  CF 33 Pressure value at 20mA or 5 Vdc of the PB5 transducer 0 50 0 Bar Dec  0 725 psi int  CF 34 Pressure value at 4mA or 0 5 Vdc of the PB6 transducer 0 50 0 Bar Dec  0 725 psi int  CF 35 Pressure value at 20mA or 5 Vdc of the PB6 transducer 0 50 0 Bar Dec  0 725 psi int  Digital Inputs  CF 36 Configuration of ID1 0 01   c62  CF 37 Configuration of ID2 0 01   c62  CF 38 Configuration of ID3 0 01   c62  CF 39 Configuration of IDA 0 01   c62  CF 40 Configuration of ID5 0 01   c62  CF 41 Configuration of ID6 0 01   c62  CF 42 Configuration of ID7 0 01   c62  CF 43 Configuration of ID8 0 01   c62  CF 44 Configuration of ID9 0 01   c62  CF 45 Configuration of ID10 0 01 
13.   Condenser  2 pump maintenance                                Origin Pump running hours  gt  Hour counter setpoint  Reset Hour reset in function menu   Restart Manual   Icona Blinking   N   Action Alarm relay   buzzer ON   Regulation   Action Only display warning messages       Pg 90 103                   1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Loads Not changed    41 38 ALARM RELAY AND BUZZER    Alarm relay   buzzer outputs                         Origin Alarms still active   Alarms not reset  Reset relay alarm Whitout alarms   In stand  by or remote ON O FF if AL42   1  Buzzer silencing By pushing one of the key of the front panel       The alarm relay is enabled only by configurating the corresponding output resource     42 AUTOMATIC TO MANUAL ALARM PROCEDURE    NUMBER OF EVENTS PER HOUR    Each hour counting is divided in 16 intervals  each made of 3600   16   225 seconds  3 minuts and 45 seconds                           int   2  Int   3  lnt   4  lnt  5   nt  6 Int  7   Int  8  nt  9 Int   10  lnt   11 Int   12  Int   13  lnt   14 Int   15  lnt   16  lnt    After the unit start up  each interval is marked as    not active     During the interval counting  for 255seconds  if at least an alarm event  appears  the interval itself is marked    Active       Starting from the first interval the instrument calculates the 16 intervals and  at the end  it restats overwriting from the first    In this way the last hour is always monitored and count
14.   When the temperature pressure probe value is lower than the     06    rC07 differential     Unloading start after the time delay         rC08  Restart Automatic  Icona Blinking   N  Action Alarm relay   buzzer OFF          41 33 B1PH   B2PH  PUMP DOWN STOP ALARM FROM PRESSURE SWITCH   LOW PRESSURE    SWITCH          Label on the display       b1PH  Pump down stop alarm of the circuit 1   b2PH  Pump down stop alarm of the circuit 2                       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary                      Origin Pressure switch  if CO36   1 2 3 4 and ID not active  the pump down stops because of the timeout  CO39   Transducer  if CO36   1 2 3 4 and the set CO37 is not reached  the pump stops because of the  timeout CO39   Reset From thermoregulation start up and ID not active  From thermoregulation start up with evaporating pressure higher than CO37   CO38  differential   Restart Automatic     Manual and logged after AL21 events per hour  reset procedure in function menu    Icona Blinking AN  Action Alarm relay   buzzer ON when it becomes manual       41 34 B1PL   B2PL ALARM DURING THE PUMP DOWN START UP FROM PUMP DOWN PRESSURE  SWITCH   LOW PRESSURE TRANSDUCER       Label o the display    b1PL  pump down alarm in start up of circuit  1   b2PL  pump down alarm in start up of circuit  2                          Origin Pump down pressure switch   CO36   1 2 3 4 and compressors start up and digital input not active  for the time set in CO39  
15.   c62  CF 46 Configuration of ID11 0 01   c62  CF 47 Configuration of ID12 0 01   c62  CF 48 Configuration of ID13 0 01   c62  CF 49 Configuration of ID14 0 01   c62  CF 50 Configuration of ID15 0 01   c62  CF 51 Configuration of ID16 0 01   c62  CF 52 Configuration of ID17 0 01   c62  CF 53 Configuration of ID18 0 01   c62  Relay Outputs  CF 54 Configuration of RL1 0 01   c52  CF 55 Configuration of RL2 0 01   c52  CF 56 Configuration of RL3 0 01   c52  CF 57 Configuration of RL4 0 01   c52  CF 58 Configuration of RL5 0 01   c52  CF 59 Configuration of RL6 0 01   c52  CF 60 Configuration of RL7 0 01   c52  CF 61 Configuration of RL8 0 01   c52  CF 62 Configuration of RL9 0 01   c52  CF 63 Configuration of RL10 0 01   c52  CF 64 Configuration of RL11 0 01   c52  CF 65 Configuration of RL12 0 01   c52  CF 66 Configuration of RL13 0 01   c52  CF 67 Configuration of RL14 0 01   c52       Pg 30 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005    Condensing proportional outputs    Preliminary       CF 68    Circuit 1 output signal    0  0     10Vdc   1  4   20mA   2  PWM for mono phase fan control board       CF 69    Circuit 2 output signal    0  0     10V   1  4   20Ma   2  PWM for mono phase fan control board       Uscite modulanti       CF 70    Proportional output 1   0  Not enabled   1  Free cooling Dumper   Mixing valve  2  3 way valve for hot water   3  Dumper for air change   4  auxiliary output   Relay driver ON   OFF    01    c22       CF 71    Proportiona
16.   when cir1 and cir2 blink at the same time   it means you are entering in programing mode m  Blinking when   set energy saving or  set paint dinamic in On       ON unit in free cooling mode mP  9 ON unit in recovery made    1592015300 User manual iCHILL 200 L GB r1 0    4 4 KEY FUNCTION    23 02 2005 Preliminary       KEY    ACTION    FUNCTION       Push and release    Show chiller set point SetC and heat pump SetH       Push two times    In chiller or heat pump if the Energy saving or the Dynamic  setpoint are enabled it shows the real setpoint Setr  the led is  blinking        Push for 3 seconds the release    Change between chiller   heat pump       During the programming  push one time    Select a parameter or confirm a value       Push one time with probe label showed on  the bottom display    Change between the read out of the circuit 1 and the circuit 2 and  viceversa          e    UP KEY    Push one time    Select the readings of the first circuit       Pushing one time during the programming    To change the parameter code or value       Push for 1 second during the programming    1 time shows the Pr2 programming level  2 time shows the Pr3 programming level       cir2    0            o       TO DO    Push one time    Select the readings of the second circuit       Pushing one time during the programming    To change the parameter code or value       Push one time    Turn the chiller on  if the unit is on led is on  The led is blinking if there is a power on delay o
17.  1  Continuous  When the unit is running in Chiller or HP the pump or the 0 2  supply fan is running   2  With compressor  When a compressor is running also the pump or the  supply fan is running   CO 17 ON compressor delay after water pump   supply fan start up  See water pump 4 250 S  Sx ec  functioning    CO 18 OFF delay evaporator water pump   supply fan after compressor switching  OFF  This delay is also active when the unit is turned in stand by  See 0 250 Sec  evaporator water pump function    CO 19 bia of time running hours for pump rotation  See water pump group 0 999            10Hr  CO 20 Time to make run the pumps together before rotating from one to the other  0 250 Sec   See water pump group function   Condenser water pump  CO 21 Operative mode for condenser water pump  See condenser water pump  function   07 Not enabled  0 2  1  Continuous  When the unit is running in Chiller or HP the is running   2  With compressor  When a compressor is running also the pump is running   CO 22 Free  CO 23 OFF delay condenser water pump after compressor switching OFF  This  delay is also active when the unit is turned in stand by  See evaporator water 0 250   Sec  pump function    CO 24 pde time running hours for pump rotation  See water pump group 0 999   10Hr 40Hr                                                                                                                                                          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preli
18.  250 Sec  dF 5 Maximum defrost duration  1 250 Min  dF 6 Time delay between the defrost of two circuits 0 250 Min  dF 7 OFF compressor delay before the defrost 0 250 Sec  dF8 OFF compressor delay after the defrost 0 250 Sec  dF 9 Defrost interval time of the same circuit 1 99 Min  dF 10 Temperature setpoint for combined defrost of the 1   circuit after parameter    30 0   70 0   C Dec  DF10 counting   22 158   F int  dF 11 Temperature setpoint for combined defrost end of the 1   circuit   30 0   70 0   C Dec   22 158   F int  dF 12 Temperature setpoint for combined defrost of the 2    circuit after parameter    30 0   70 0   C Dec  DF10 counting   22 158   F int                                                                                                                               1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  dF 13 Temperature setpoint for combined defrost end of the 2  circuit   30 0   70 0   C Dec   22 158   F int  dF 14 Activation of all the steps of the 1   circuit during the defrost   0  Not enabled 0 1  1  Enabled  dF 15 Activation of all the steps of the 2    circuit during the defrost   0  Not enabled 0 1  1  Enabled  dF 16 Time delay between two compressor ON in defrost mode 0 250 Sec  dF 17 Fan control during defrost   dripping time  0  Not enabled 0 2  1  Only in defrost  2  For both functions defrost   dripping time  dF 18 Pressure   temperature setpoint to force the ventilation ON during the defrost     30 0   70 0   C
19.  5   C is divided by the number of resources 6 compressors therefore the step for each resource  is 0 8  C  each 0 8  C if the temperature is increasing or decreasing one of the resource is turned on or off    Par  ST08 Regulation band in heat pump mode   The configured resources are distributed inside the regulation band    Example Unit configured with 2 circuits  3 compressors per circuit and thermoregulation controlled by the evaporator outlet NTC probe   Chiller setpoint  evaporator inlet water   40      evaporator outlet water 45      when the evaporator outlet water is 40     all the  compressor outputs are on while when the evaporator outlet water is 45  C all the compressors are OFF    Thermoregulation parameters  Par  ST04   40   C           ST08   5   C   Functioning  the regulation band ST08 5   C is divided by the number of resources 6 compressors therefore the step for each resource  is 0 8  C  each 0 8  C if the temperature is increasing or decreasing one of the resource is turned on or off    Par  ST08 Regulation band in heat pump mode   The configured resources are distributed inside the regulation band    Par  STO9 Defines the thermoregulation probe in chiller    02 NTC Temperature probe of the evaporator inlet   1  NTC Temperature probe of the evaporator circuit  1   2  NTC Temperature probe of the evaporator circuit  2   3  NTC Temperature probe of the common evaporator   4  Probe temperature of the remote front panel  1    5  Probe temperature of the remot
20.  Actions      1 0 23 02 2005 Preliminary    Only signalling          Loads    Not modified          41 17 B1HP   B2HP HiGH PRESSURE SWITCH CIRCUIT 1 AND 2       Label on display    b1HP  high pressure switch circuit  1   b2HP  high pressure switch circuit  2                       Reason The unit is running and the digital input of the high pressure switch is active  Reset Digital input not active   Restart Manual  Reset procedure in Menu function    Icon blinking ZN   Action Alarm Relay   and buzzer on   Regulation          Condensing fan       Maximum speed for 60 seconds       41 18 B1LP    21   Low    TEMPERATURE   LOW CONDENSING PRESSURE OF THE CIRCUIT       Label o the display    b1IP  low pressure digital input of the circuit 1   b2IP  low pressure digital input of the circuit 2                          Origin When the condensing probe value is lower than ALO3 setpoint if       In chiller or heat pump      Stand by o remote OFF when AL08   1      In defrost when AL06 1   The alarm is not signalled if       In defrost  for the time AL07  when the 4 way valve is turned on       For the time set in AL01 after turning on the compressor   Reset When the condensing probe temperature is higher than AL03   AL04  differential   Restart Automatic  Manual after AL05 events per hour  Reset procedure in Menu function    Icon Blinking A  Action Alarm Relay   and buzzer on    41 19 B1AC   B2AC     1       B2Ac ANTIFREEZE ALARM   LOW OUTLET TEMPERATURE  AIR    AIR UNIT IN CHILLER MODE 
21.  Attention  If during the Stand by or remote off there is an anti freeze alarm event  and  the AL35  lt  gt 0  starting the heat pump mode  from keyboard or digital input  In  this case the anti freeze alarm is aborted and the compressor starts for the 0 250 Sec  AL35 time to heat the air or the water   After the AL35 time if the antifreeze probe value is still lower than AL33  setpoint  for maximum AL36 seconds  the unit is stopped and the anti freeze  alarm is generated again   AL 36 Anti freeze alarm delay for low air ambient temperature or low outlet air  temperature in heat pump normal condition  0 250 Sec  The detected temperature must be lower than AL33 for the time AL36 before  giving the alarm  AL 37 Maximum number of anti freeze alarm events for low air ambient temperature  or low outlet air temperature in heat pump  It sets the alarm reset condition   Always manual reset AL37   0 0 16  Always automatic reset AL37   16  From automatic to manual reset if AL37   1  15  AL 38 Anti freeze alarm configuration in heat pump  0  to turn the compressors off when the anti freeze control probe is lower  than AL33  after the time delay   the display shows the alarm label   Buzzer and Alarm relay are not activated  0 1  1  to turn the compressors off when the anti freeze control probe is lower  than AL33  after the time delay   the display shows the alarm label   Buzzer and Alarm relay are activated   Compressor high discharge temperature  AL 39 Compressor high discharge tempera
22.  Auxiliary relay circuit 2  US 5 Auxiliary relay 2 operating mode  See graph and auxiliary relay functions   0  Not enabled  1  Always available with direct action 0 4  2  Available only when the unit is on with direct action  3  Always available with reverse action  4  Available only when the unit is on with reverse action  US6 Analogue input configuration for auxiliary relay 2 control   Allows to select 1 10  which probe value Pb1  Pb10 controls the relay  US 7 Auxiliary setpoint 2  See graph and auxiliary relay functions   30 0   70 0    Dec   22 158   F int  0 0   50 0 Bar Dec  0 725 Psi int  US 8 Auxiliary differential 1  See graph and auxiliary relay functions  0 0 25 0   C Dec  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Condenser fan  Parameters   Description min max            Resolution  FA1 Fan configuration output  0  Not enabled  1  Always on 0 2  2  ON OFF regulation  3  Proportional speed control  FA 2 Fan operating mode  0  Dependent from the compressor 0 1  1  Independent from the compressor  FA3 If the condenser fan control is the triac output  when the regulation starts the  trigger output will drive the condenser fan at the maximum voltage for the time 0 250 Sec  FA 3 then  then the regulation will follow the temperature pressure of the  probe   FA4 Phase shifting of the fan motor 0 8 paa 250us  FA5 Condenser control outputs  0  Same function 0 1  1  Independents  FA6 Pre ventilation time befor
23.  COMPRESSOR CONTROL    Not yet available on this version    Compressor regulation in chiller    Compressor regulation in heat pump    22 4 GRAPH PROPORTIONAL INTEGRAL COMPRESSOR REGULATION CONTROL    Not yet available on this version    Compressor regulation in chiller    Compressor regulation in heat pump    23 THERMOREGULATION OF THE ANTI FREEZE  INTEGRATION HEATING OR    BOILER       23 1 THERMOREGULATION OF THE HEATERS IN CHILLER    The Par  Ar06 selects the probe s control for the anti freeze alarm and the relay outputs configured as anti freeze   support   boiler  heaters for the circuits 1 and 2 in chiller mode    Par  Ar06   0  the function is disabled   Par  Ar06   1  the thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit 1 and 2  or both together  is  controlled only throughout the NTC probe configured as evaporator water inlet    Par  Ar06   2  the thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit  1 is controlled with NTC probe  configured as evaporator probe outlet of the circuit  1    The thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit  2 is controlled with NTC probe configured as  evaporator probe outlet of the circuit  2    ATTENTION  It is not possible to control the heaters of the crcuit  1 with the probe of the circuit  2 and viceversa    Par  Ar06   3  the thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit 1 and 2  or both togethe
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
25.  Dec   22 158      int  0 0 50 0 bar Dec  0 725 psi Int  Forced defrost  dF 19 Minimum time delay before a forced defrost 0 250 sec  dF 20 Pressure   temperature setpoint for a forced defrost  30 0   70 0   C Dec   22 158   F int  0 0 50 0 bar Dec  0 725 psi int  dF 21 Forced defrost differential 0 1 25 0   C Dec  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int  Defrost operative mode  dF 22 Defrost start up with 2 circuits  0  Independent 0 2  1  If both have reached the necessary requirements  2  If one has reached the necessary requirements  dF 23 End defrost for two circuits and common ventilation   0  Independent 0 2  1  If both have reached the necessary end defrost requirements  2  If one has reached the necessary end defrost requirements  Pri Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Recovery  Parameters   description min max  udm   resolution  rC 1 Recovery modes  0   not enabled 0 2  1   2 indipendent circuit  2   both the circuit in parallel  rC 2 Delay time delay with step forced off 0 250 Sec  rc 3 Delay time delay with step forced off after the recovery valve activation 0 250 Sec  rc 4 Recovery minimum time 0 250 Min  rc 5 Minimum interval time between the end and the beginning of the next 0 250 Min  recovery  rC 6 Temperature setpoint to disable the recovery  30 0   70 0   C Dec   22 158   F int  0 0 50 0 Bar Dec  0 725 Psi int  rC 7 Temperature differential to restore the recovery 0 1 25 0   C Dec  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int  rc 
26.  Duration of the pressure switch   oil level switch in normal operating conditions    Duration of the oil level switch activation during normal running condition    It allows to set the time delay before signalling the alarm  AL11 defines the delay counting  it helps to override the low pressure or the  low oil level determined  for example  by a new partialization step of the compressor itself             AL13 Maximum number of alar    m events per hour     It determs the maximum number of alarm events before switching the restart from automatic to manual     41 27 C1DT     20      C3pT   C4pT   C5pT   C6DT HIGH COMPRESSOR DISCHARGE    TEMPERATURE ALARM       Label o the display    C1dt  High discharge temperature of the compressor  1      C6dt  High discharge temperature of  the compressor  6                          Origin The compressor discharge temperature is higher than AL39 setpoint   ATTENTION  The display resolution is 0 1  C until the read out is 99 9  over 100 C it is 1 C   Reset If the probe value of the high discharge temperature is lower than  AL39   AL40  differential    Restart Automatic  Manual when there are AL41 per hour  Reset procedure in Menu function    Icon Blinking AN  Action Alarm Relay   and buzzer on       41 28 C1TR   C2TR   C3    TR   C4TR   C5TR   C6TR COMPRESSOR OVERLOAD ALARM       Label o the display    C1tr  Compressor  1 overload alarm      C6tr  Compressor  1 overload alarm 6                    Origin With active digital input  The alarm 
27.  NTC of circuit 1 or 2      If the condensing or evaporating probe value of the 1    circuit is lower than dF10 and lower than dF12 for the 2  circuit the process  step on the 3  phase       Otherwise th unit waits until the probe values decrease under dF10 and dF12    If any of the probe is configured as combined defrost NTC the process steps on the 3  phase    When the circuit condition are satisfied to execute the 3   phase the display shows the dF1  circuit1  and dF2  circuit2   labels     To enter the FASE 3 of the defrost the following conditions have to besatisfied     3    inversion valve management Par  dF07  OFF compressor before the defrost    If dF07 0  the valve is activated without stopping any conmpressor and the defrost cycle is immediately activated  If the  thermoregulation or the dF14 parameter require more compressors the dF16  on compressor delay during defrost cycle  is loaded    If df07  lt  gt  0     The compressors and the steps are turned off   the compressor s led is blinking  the defrost led    4 is on   Start the dF07   2  half time  time counting    The valve is activated    Start the     07   2  half time  time counting     PON    The 4  phase start condition  if the thermoregulation or the dF14 parameters require to turn ON more than one compressor for circuit    the delay on time between the compressors depends on the parameter dF16    The partialization s  if configured always OFF during the defrost cycle  the compressor is always 10096      
28.  Pump down process is inhibited and the solenoid valve works in parallel with the compressor     PAR  CO36   4 UNIT START STOP WITH PUMP DOWN in HEAT PUMP  In Heat pump mode the Pump down process is inhibited and the solenoid valve works in parallel with the compressor     29 4 Pump DOWN ALARM DURING COMPRESSORS START  UP  ACTIVATION    Pg 68 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    If within the CO39 delay time  Maximum pump down restart time  the compressor s do not restart because of the low pressure  the  instrument will signal APd1  pump down alarm at the start up of the circuit 1  or the label APd2  pump down alarm at the start up of the  circuit 2   With active alarm the restart procedure is disabled  The alarms can be    e with Automatic Reset that is not logged  the buzzer and alarm relay are not activated    e with Manual Reset that is logged  the buzzer and alarm relay are activated    The Parameter AL22 determines the number of pump down alarm events to turn from automatic to manual reset   The Reset is always manual if AL22   0   The Reset is always automatic if AL22   16   The reset becomes manual after AL22   1   15 events and the configuration of Par  AL23    Par  AL23 defines if the reset of the AL22 alarm events can be forced from manual to automatic  In this case the alarm events  after  reaching AL22  is automatically reset but it is logged while the buzzer and the alarm relay are on    In this way  in case of particula
29.  SetH  HP  labels while the top display shows the set value   If the energy saving is active the next pressure on the SET key shows the label    SEtr     real setpoint   and the top display shows the  real set value active in that moment   The regulation is enabled if    e In chiller mode the parameter Sd01 is not equal to 0    e Inheatpump mode the parameter Sd02 is not equal to 0    e    4 20     analogue input is configured as dynamic setpoint control or a NTC analogue input is configured as external air   temperature for dynamic setpoint control    With UP or DOWN keys within the circuit measurement read out is possible to show the external air temperature indicated by the Et  label     19 1 DYNAMIC SETPOINT GRAPH    4 20ma probe configured as dynamic setpoint analogue input     5001 5402  gt 0          9001 Sd02   0       NTC probe with positive differential     5403 5404    5001 5002  gt 0  5001 5002   0        lt  P    Sd05 Sd06 gt 0    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    NTC probe with negative differential     Sd03 Sd04    Sd01 Sd02  gt 0      Sd03 Sd04   0       Sd05 Sd06 lt 0    20 AUXILIARY RELAYS    The auxiliary relays can be configured to manage two independent  from heat pump or chiller mode  output controls    Each output can be managed with a dedicated temperature or pressure probe input   NTC probe  4  20mA or 0  5V transducers  or with  the common available temperature or pressure configurable inputs    The probe selectio
30.  The output relay of the line  1 and line  2 are switched off together                          Fig  3    27 9 STAR   DELTA START  UP Or A CAPACITY COMPRESSOR    If one or more capacity compressors are configured and the thermoregulation requires the full load control  the controller turns the  solenoid valve on  then after 1 second the centre of the star relay is turned on  relay K2 Fig  3   Then the star delta procedure will be    1592015300 User manual iCHILL 200 L GB      1 0 23 02 2005    Preliminary    completed with the other two contactors  Durning the CO13 time delay the step valve is forced on  minimum power  When the C013 is    expired if the thermoregulation requires more power the valve will be switched off  maximum power      28 CAPACITY CONTROL    CO06 capacity control operative mode   The relay configured as capacity control are managed by the thermoregulation as shown in the graph and into the tables here below     Par CO06   0 ON OFF step    0  Step control  Depending on the thermoregulation requests and the output polarity a power step can be enabled or disabled  The step  is activated only after the previous is turned off     Eg    1 capacity compressor with 3 partializations  4 Power steps                                   Capacity 25  50  75  100   Compr  Compressor ON Compressor ON Compressor ON Compressor ON  Out relay   Step P 1 ON Step P 1 OFF Step P 1 OFF Step P 1 OFF  Out relay   Step P 2 OFF Step P 2 ON Step P 2 OFF Step P 2 OFF  Out relay   Step 
31.  Use the UP or DOWN keys to select Cnd1 or Cnd2  the top display always shows the value  between 0  and 100   of the  proportional output of the selected circuit    4  To exit the Hour function push MENU key or wait the timeout     17 17 READ OUT OF THE FOUR PROPORTIONAL OUTPUT    The four proportional outputs  4  20ma or 0 10V  can be showed in the menu function    Pout FUNCTION selects the proportional outputs    Label involved in Cond function    Pout Proportional output for dumper control or to drive the external relay 1   Pou2 Proportional output for dumper control or to drive the external relay 2   Pou3 Proportional output for dumper control or to drive the external relay 3   Pou  4 Proportional output for dumper control or to drive the external relay 4   The labels are displayed only if the corresponding output is present and configured    TO SEE THE FOUR OUTPUT PERCENTAGE    Enter the function menu   1  Use the UP or DOWN keys to select Pout    2  Push SET key  the bottom display shows Pou1  the top display shows the output percentage    3  Use the UP or DOWN keys to select Pou1  Pou2  Pou3 or Pou4 the top display always shows the value  between 0  and 100   of  the proportional output of the selected circuit    4  To exit the Hour function push MENU key or wait the timeout     ATTENTION   If the proportional output Pou1   Pou2   Pou3   Pou4 are configured to drive an external relay the display will show O relay off  and 100 relay on     17 18 READ OUT OF THE TIME COU
32.  before  defrosting    dF07 Compressor off time before the defrost  the led of the compressor is blinking    After the dF09 delay and before activating the defrost  the compressors are stopped for the dF07 time    Exactly in the middle of the dF07 time the 4 way valve is activated to equalise the pressure of the unit and when dF07 is completely  expired the compressors and the defrost can start    This procedure does not respect the compressor on delay protection therefore the compressor is immediately turned off and then on  If  dF07   0 the compressor is not stopped and the 4 way valve is immediately turned    dF08 Compressor off time after the defrost  the led of the compressor is blinking    After the defrost cycle the compressors are stopped for the dF08 time    Exactly in the middle of the dF07 time the 4 way valve is activated to equalise the pressure of the unit and to drain the external  exchange unit  when dF08 is completely expired the unit restart in heat pump mode    This procedure does not respect the compressor on delay protection therefore the compressor is immediately turned off and then on  If  dF08   0 the compressor is not stopped and the 4 way valve is immediately turned    DF09 Delay time to next defrost   It starts when the condensing evaporating temperature pressure probe value is lower than     02 setpoint  This time is reloaded if the  power supply fails  after a defrost cycle or from a digital input request of defrost    The time counting is interru
33.  counter remains active     37 CONDENSER FAN REGULATION    The FA01 and FA02 parameters define the operative mode of the condenser fans  The CF68 and CF69 selects which are the output  signals    Par  CF68 Condenser fan control signal of the circuit  1   0  0  10V   1  4 20       2  PWM   Par CF69 Condenser fan control signal of the circuit  2   0  0   10V   1  4 20       2  PWM   Par  FA01 Fan regulation   0   Output not enabled   1   always on   2   ON OFF regulation   3   proportional fan speed   Par  FA02 Fan operative mode   0   Fan on only if compressor on   1   Independent from the compressor  off during the stand   by   or from remote OFF  Parameter combination FA01     FA02   Par  FA01   1   Par  FA02   0   Fans on when the compressor on  the fans work following the same output algorithm           FA01   1   Par  FA02   1   Independent from the compressor status but off in stand   by    Par  FA01   2   Par  FA02   0   Fans on  with ON OFF regulation and with temperature pressure transducer control  only when the compressor is on  at least one relay  is configured as fan control   When the compressor turns off also the fans are forced off     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Par  FA01   2   Par  FA02   1   Fans on  with ON OFF regulation and with temperature pressure transducer control  only when the compressor is on  at least one relay  is configured as fan control   When the compressor turns off the fans are thermoregulated depe
34.  dF23 1 dF23 2   dF22 0 Yes not possible  ACF1  not possible  ACF1   dF22 1 Yes Yes Yes   dF22 2 not possible  ACF1  Yes not possible  ACF1   ATTENTION     The configuration error ACF 1 is displayed if the parameter value of dF22 and dF23 is not permitted   For only one condensing unit the dF22 and dF23 values must be not equal to 0     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    38 6 AUTOMATIC DEFROST PROCEDURE    Phase 1  time counting of dF09  Interval defrost of the same circuit   unit is working in heat pump mode and at least one compressor is    running  the defrost led        is blinking   the condensing evaporating temperature or pressure must be lower than dF02 value     Functioning of the time counter    1  The dF09 counter is reloaded se if the power supply fails  after a defrost cycle and after the unit changes from chiller to HP    2  The dFO09 counter is stopped if the last compressor turns off or if the pressure temperature of the condensing evaporating probe  becomes higher than dF02 parameter value    3  The counter is decremented if the condensing or evaporating temperature pressure probe value becomes lower than the dF02  parameter value     2  phase  starts after the dF09 counting and check if the initial condition are satisfied to defrost  If one digital input si configured as  defrost end  of the circuit 1 or 2 and the contact is active  the unit waits until the contact is de   activated     Probe configured as combined defrost
35.  defrost immediately start    The defrost ends when the NTC combined defrost probe 1 or 2 increases over      11  circuit1  or dF13 circuit2     If the defrost is enabled the display allows to show the external temperature on the top display and the labels dEF1  circuit1  or  dEF2 circuit2  on the bottom display aof the circuit read out function     38 3 MANUAL DEFROST    The manual defrost key function is enabled if the unit is on with at least one compressor running    The defrost start temperature pressure of the controlled probe must be lower than dF02 setpoint value while if the combined defrost is  active the detected temperature must be lower than dF10 or dF12    At this point by pushing SET   UP for more than 5 seconds the manual defrost starts     ATTENTION  the manual defrost is not related to the dF09  dF06 delay times  therefore the forced defrost cycle  if condition are OK   is immediately executed for both circuits     38 4 DEFROST START CONDITION WITH TWO CIRCUIT UNIT    Parameter involved  dF22   07 Independent   17 Only if both circuit conditions are satisfied  2  At least one circuit condition is satisfied    38 5 END OF THE DEFROST IN A TWO CIRCUITS WITH ONE CONDENSING FAN CONTROL UNIT    Parameter involved  dF23   07 Independent   1  Both circuits have reached the conditions to stop the defrost  2  At least one circuit has reached the end defrost condition    Table of defrost cycle for units with 2 circuits                                  Parameter dF23 0
36.  e        keyboard selection is disabled   e        key on the front panel can start stop the unit only with the digital input selection    Par  CF79  2  Automatic selection of the Chiller   Heat Pump through analogue input   The analogue input selection or change over function overrides the digital input C HP function  If the external air temperature are within  the CF81 differential  the user can change the running mode from the keyboard    If the unit is running with CF79   1 or CF79 2  and it is requested a running mode change  the controller turns off all the outputs  starts  a fixed delay time signalled by the chiller or heat pump blinking led  This blinking led indicates which running mode will be activated after  the compressor delay time protection     12 2 CHANGE OVER    To change the running status the following condition must be respected otherwise the unit remains in stand   by    1   CF02 71  heat pump selected    2  CF79 2 and a        probe configured as NTC external air temperature for dynamic setpoint  boiler   change over   3  This probe is working properly    Parameters involved with the change over function    CF80 Change over Setpoint  If the analogue input control  from probe  function is enabled  it represents the limit temperature of the  probe value under which the unit runs the Heat Pump mode    CF81 Change over Differential  If the analogue input control  from probe  function is enabled  it represents the limit differential  temperature of the prob
37.  first probe that goes below the setpoint    ATTENTION   The two outputs are controlled in parallel if configured with only by one NTC probe control for common evaporator outlet     FUNCTIONNING OF THE ANTI FREEZE  INTEGRATION HEATING  BOILER HEATERS DURING THE DEFROST CYCLE   The Ar05 defines the support heaters    Par  Ar05 z 0  The heaters are activated only by the thermoregulation algorithm    Par  Ar05 z 1  The heaters are activated only by the thermoregulation algorithm and are always on during the defrost  They turn on  when the 4 way valve change from heat pump to chiller and turn off only after the dripping time and the compressors restart     23 3 THERMOREGULATION OF THE SUPPORT HEATERS FOR AIR AIR UNIT    The NTC control in chiller mode depends on the Ar06 parameter value while from the Ar07 value in heat pump mode  With one relay  configured as heaters for circuit  1   With one output configured as heater of the circuit  1 the output is enabled both for chiller and heat pump request    With two outputs configured as heater of the circuit  1 and two the outputs are enabled both for chiller and heat pump request     FUNCTIONNING OF THE SUPPORT HEATERS DURING THE DEFROST CYCLE   The Ar05 parameter defines the support heaters operating mode during the defrost    Par  Ar05 z 0  the heaters are controlled only through the thermoregulation algorithm    Par  Ar05   1  heaters are controlled only through the thermoregulation algorithm and are always on during the defrost c
38.  for chiller  heat pump inversion if Par  CF80 2     30 0   22    70 0  158      C    F    Dec  int       CF 81    Change over temperature differential if Par  CF80 2    25 0      C    F    Dec  int       U  m  Unit of measurement       CF 82         C or   F selection  0    C     BAR  1    F    psi                      Voltage frequency                                                                                                                                                       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  CF 83 Power supply frequency  0  50 Hz  1  60 Hz  27 cc voltage b 2    ATTENTION with Par  CF81   2       proportional outputs for fan control         not enabled and the frequency alarm is inhibited   Serial Address  CF 84 Serial address 1 247  CF 85 Firmware Release  CF 86 Eeprom parameter map  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Dynamic Setpoint  Parameters   Description min max           Resolution  Sd1 Maximum dynamic Offset in chiller mode  30 0   30 0   C Dec   54 54   F int  Sd 2 Maximum dynamic Offset in heat pump mode  30 0   30 0   C Dec   54 54   F int  Sd    External air setpoint in chiller mode  30 0   70 0   C Dec   22 158   F int  Sd 4 External air setpoint in heat pump mode  30 70 0   C Dec   22 158   F int  Sd 5 External air differential in chiller mode  30 0   30 0   C Dec   54 54   F int  Sd 6 External air differential in heat pump mode  30 0   30 0   C Dec   54 54    int  Pr1 Passwor
39.  if dF14 1  all the circuit  1 resources are forced to ON   during the defrost cycle the compressors and steps of the circuit  1 are  ON while  if dF14 0   compressors and steps are thermoregulated       if dF15 1  all the circuit  2 resources are forced to ON   during the defrost cycle the compressors and steps of the circuit  2 are  ON while  if dF15 0   compressors and steps are thermoregulated     4  PHASE  Defrost ON   Parameter involved  dF17  condensing fan management      If dF17 0  The condensing fan are always off      If dF1721  The condensing fans start if the condensing temperature pressure value is higher than dF18  they will following the  normal chiller thermoregulation algorithm    ATTENTION during the defrost cycle  both for chiller and the heat pump modes  the fan are controlled with the condensing probe even if   the evaporator probe is present and configured    The 4  phase lasts at least for the dF04 time counting and can terminate for these conditions     1  IfdF02 0      The combined NTC probe value is higher than dF11 of the 1    circuit      The combined NTC probe value is higher than dF13 of the 2  circuit      When the condensing temperature probe s is are higher than dF03 parameter value   2  IfdF02 2  the dF05 counting  maximum defrost timeout  is expired  step on 5  PHASE   3  If dFO2 3  if the end defrost digital input is deactivated  step on 5  PHASE     5  PHASE  Inversion valve management Par  dF08  OFF compressor after defrost cycle     If 
40.  n  Yes Yes after 60 seconds  b n P   Low pressure switch of the circuit  n  Yes Yes  b n AC  Anti freeze in chiller of the circuit  n  Yes Yes  b nAH   Anti freeze in heat pump of the circuit  n  Yes Yes  b n P   High condensing pressure of the circuit  n  Yes Yes after 60 seconds  b n P   High condensing temperature from NTC of the circuit  n  Yes Yes after 60 seconds  b n LP o condensing pressure    evaporating with low pressure transducer  with transducer of Yes Yes  e circuit of the  n   b n IP Low condensing temperature NTC circuit  n  Yes Yes  b n tF Fan overload circuit  n  Yes Yes  b nPH   Pump down alarm in stop regulation of the circuit  n  Yes Yes  b n PL   Pump down in regulation start up of the circuit  n  Yes Yes  b n dF   Bad defrost circuit  n   b n u   Unloading from condenser high temp press of the circuit       b nCu   Unloading from evaporator low temp press of the circuit  n  Yes Yes  b n rC   Recovery function disabled in circuit  n   b n ds   Circuit  n  disabled from keyboard Yes Yes  b n Ac   Anti freeze circuit  n  message in chiller  b n Ah   Anti freeze circuit  n  message in heat pump                       n  identifies the circuit 1 or 2    43 3 ALARM           TYPE AND CORRESPONDING COMPRESSOR OUTPUT OFF                                     Alarm Alarm description Compressor Compressors not involved  Code  n    C n HP Compressor n  high pressure switch Yes   C n oP Compressor n  oil pressure switch   Oil level switch Yes   C n tr Compressor n  o
41.  not correct the top display blinks  0 while the bottom shows PAS  If within 5 seconds no value is inserted the display label come back to     1   function    6  Toexitthe COtr function push MENU or wait the timeout     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7  Repeat operation 1     5 to reset the other alarms     17 3 COMPRESSOR OVERLOAD PASSWORD     The default value is 0 to change this value enter Pr3 level under the AL parameter family  Par  AL43     17 4 ALARM LOG LIST    ALOG FUNCTION TO SEE THE ALARM LOG   The function and the alarm codes are visible only if there are alarm events  If many events are active at the same time the list displayed  by increasing order    Enter the function Menu   1  Select ALOG   2  Push SET one time  Nothing happens if there are no active alarm events    3  The bottom display shows the alarm label  the top display shows the a number in the range 00 to 99    4  Usethe UP or DOWN keys to scroll the list    5  To exit the ALOG function push MENU or wait the timeout     17 5 ERASE THE ALARM LOG LIST  ALOG FUNCTION TO ERASE THE LOG LIST    Enter the function Menu    Use the UP or DOWN keys to select ALOG on the bottom display    Push on e time the SET key    Within the ALOG function select with UP or DOWN keys  the ArSt label on the bottom display while the top display shows PAS   Push SET  the bottom display shows PAS and the top display a blinking O    Insert the password  See parameter family AL    If the pas
42.  or three phase fan control board    2  PWM  only for external mono phase fan control board with cut phase control     8 6 PROPORTIONAL OUTPUT CONFIGURATION 0   10 VDC  4 OUTPUTS     Parameters involved    CF70   Proportional output 1 configuration  CF71   Proportional output 2 configuration  CF72   Proportional output 3 configuration  CF73   Proportional output 4 configuration     Not enabled   1 Free cooling dumper   mixing valve   2 3 way valve for hot water   3 Dumper for air change   4 Auxiliary output   After the read out number 4 the display goes from the label    o 1  to    c22     see input output polarity   that allow to configure the output  as digital output to control an external relay     8 7 OTHER OUTPUTS    Hot key connection  TTL connection  Remote keyboard connection    9 TABLE OF THE PARAMETERS    MENU SELECTION                         Label Description   ALL Shows all the parameters   ST Shows only the Thermoregulation parameters  CF Shows only the Configuration parameters   SD Shows only the Dynamic Setpoint parameters  ES Shows only the Energy Saving  RTC parameters       Shows only the compressor parameters                                                                                                                1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  US Shows only the Auxiliary Output parameters  FA Shows only the Fan Control parameters  Ar Shows only the Antifreeze Control parameters  DF Shows only the Defrost paramete
43.  shows PAS while the bottom display shows Pr1 labels    2  Push UP key for 2 seconds and the top display will show Pr2    3  Push SET key and the top display shows a blinking 0  with UP or DOWN insert the Pr2 password  Push SET and  if the value is  correct  top display will show the first family of parameters  ALL   Otherwise set the password again    4  Select a parameter family with DOWN or UP keys    5  Push SET to enter  the bottom display shows the first available parameter label while the top display shows its value    The user can shows and modify all the paramters belonging to this family     Parameter status  leds and bottom display in Pr2       led n  2    Leds 1 2 are blinking  the parameter can not be changed   All the leds are off  the parameter ca not be seen in Pr1 level   Led 3 is on  the parameter can be seen in Pr1 level     Leds 1 2 are blinking and led 3 is on  the parameter can be showed and changed in Pr2  showed but not changed in Pr1   Leds 1   2   3 are blinking  the parameter can be showed and changed in Pr2 and in Pr21    In Pr2 level the user can not see and change any parameter of Pr3 level    The MENU key allows to exit from a family to reselect another without exit the Pr2 level    The MENU key allows to pass to Pr1 starting from a family label    To exit completely the programming push SET   UP     11 7 ENTER THE PROGRAMMING LEVEL PR3    Enter the Pr3  OEM level        1  Push the SET   DOWN keys together for 3 seconds  The top display shows P
44.  signal  With the two 0     10V outputs  the iCHILL can drive a mono phase or three phase controllers  such as the Dixell inverter models XV340GS  up to 8KW           Fan speed module  circuit n   1          Power  supply  230V                  ziale  8 ohanu e     gt     Fan speed module  circuit n   2    Power  supply  230       gt        7 9 FAN CONDENSING CONTROL WITH 4 20MA OUTPUT    With only one condensing circuit configured  the Out1   Out2 outputs work together giving the same signal  With the 4  20mA outputs the  iCHILL can drive a mono phase or three phase controllers  such as the Dixell inverter models XV340GS  up to 8KW     Fan speed module  circuit n  1    Pose  supply  2x          Fan speed module  circuit n   2    Power  supply  230      he       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 10 PROPORTIONAL OUTPUTS 0   10V DUMPER CONTROL  GND   common    IC260L   IC261L   IC280L   IC281L       7 11 PROPORTIONAL OUTPUTS CONFIGURED FOR AUX RELAY CONTROL    GND   common  By parameter programming is possible to connect a 12 volt  40mA relay     IC260L   IC261L   IC280L   IC281L    External relay     1 857  e nans        Pg 22 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 12 HoT KEY 64 CONNECTION  The programming HOT KEY 64 allows to upload or download a copy of the parameters of the instrument  see HOT KEY paragraph          HOT KEY FOR  PROGRAMMING    7 13 XJ485 CONNECTION    The XJ485 interface is a co
45.  some seconds and then shows the next parameter   Exit the programming pushing SET   UP together or wait the timeout    nside the Pr3 level it is possible to change also the Pr1 and Pr2 passwords                   11 5 ENTER THE PROGRAMMING LEVEL     1    Enter the Pr1    User level        1  Push the SET   DOWN keys together for    seconds  The top display shows PAS while the bottom display shows Pr1 labels    2  Push SET key and the top display shows a blinking 0  with UP or DOWN insert the Pr1 password  Push SET and  if the value is  correct  top display will show the first family of parameters    ALL     Otherwise set the password again    3  Selecta parameter family with DOWN or UP keys    4  Push SET to enter  the bottom display shows the first available parameter label while the top display shows its value    The user can shows and modify all the parameters belonging to this family     Parameter status  leds and bottom display in Pr1       Xo    Pg 42 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    If the selected parameter can not be changed the leds 1 and 2 are blinking    In Pr1 level the user can not see and change any parameter of Pr2 and Pr3    The MENU key allows to exit from a family to reselect another without exit the Pr1 level   To exit completely the programming push SET   UP     11 6 ENTER THE PROGRAMMING LEVEL PR2    Enter the Pr2    maintenance level        1  Push the SET   DOWN keys together for    seconds  The top display
46.  the parameter is visible in Pr1 but can t be changed   Pr2 PARAMETER VISIBILITY   Enter the Pr3 level   1  Select the parameter    2  Keep pushed the SET key    3  Push 1 time the MENU key and the led 4 change from on to blinking the parameter is visible in Pr2 but can t be changed   Leds 3  4 blinking  the parameter is visible in Pr1 and in Pr2 but in those levels now they can t be changed     TO SET THE ORIGINAL TAG FOR THE PARAMETER Pr1   Pr2  1  Keep pushed the SET key     2  Push one time the MENU key  the leds 3   4 turn on  the parameter can be seen and modified in Pr1 and Pr2     11 11 PROGRAMMING  DIGITAL INPUT AND OUTPUT POLARITY    The parameters that allow to configure different options such as    1  Digital inputs   2  Digital outputs  relay    3  Proportional output configured as ON OFF   4  Analogue input configured as digital input   have a different parameter description that allows to configure the operating mode and the corresponding polarity     Example of programming   The bottom display shows the parameter label  CF36  Digital input ID1 configuration   Note that the top display shows  c  or    o    before the configuration number    lt        i    CF 36    The selection 7 for the digital input ID1  CF36  means that it is the    high pressure switch of circuit 1      Pg 44 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    The label    o    means that the digital input is active for open contact     Otherwise if the selection i
47.  thermoregulation  After the compressor stops running the time CO13 will be reloaded   Having one compressor with 3 partializations  at the compressor start up  with CO07 1  the partialization valve is enabled for the time  CO13 and it will be considered also as thermoregulation step  After the compressor stops running the time CO13 will be reloaded     EXAMPLE WITH SCREW COMPRESSOR   Having one compressor with    partializations  with CO0722 when the compressor is off the partialization valve is always on  so as  in  case of start up  it allows to have the minimum load  After the compressor is started the valve is on only for CO13 time and it won t be  considered as regulation step  After the compressor stops running the time CO13 will be reloaded    Having one compressor with    partializations  with CO0723 when the compressor is off the partialization valve is always on  so as  in  case of start up  it allows to have the minimum load  After the compressor is started the valve is on for CO13 time but it will be  considered as regulation step  After the compressor stops running the time CO13 will be reloaded     28 2 By  PASS GAS VALVE DURING COMPRESSOR START  UP    It allows to manage  with the partialization valve  also the valve to run the compressor with no load by passing the circuit    On time of the by pass gas valve during the compressor start up    The funcrion is enabled if the CO13  lt  gt 0 and one of the relay output is configured as by pass valve compressor 1  
48.  top display shows the  real set value active in that moment    During the Energy Saving cycle the setpoint is incremented with these parameter values ES10   ES12  SET   ES10 for Chiller mode  and SET   ES12 for HP mode    The differential values  during the energy saving thermoregulation  are defined with parameter ES11 for chiller mode and ES13 and HP  mode     18 2 ENERGY SAVING TIME TABLE WITH RTC    The Energy Saving function with a daily RTC time table is available only if the RTC circuit  optional  is on board    This function allows to set three start and stop energy saving daily periods  ES1  ES2  ES3  ES4  ES5  ES6     The energy saving activation is signalled by the SET key led on  When working in Chiller or HP the first pressure on SET key shows the  actual setpoint SetC  chiller  or SetH  HP  labels while the top display shows the set value    If the energy saving is active the next pressure on the SET key shows the label    SEtr     real setpoint   and the top display shows the  real set value active in that moment    During the Energy Saving cycle the setpoint is incremented with these parameter values ES10   ES12  SET   ES10 for Chiller mode  and SET   ES12 for HP mode    The differential values  during the energy saving thermoregulation  are defined with parameter ES11 for chiller mode and ES13 and HP  mode     The function can work if the following requirements are satisfied   1  RTC circuit mounted   2  Parameters ESO1   ES06 are not equal to 0 and are not 
49.  valve and and the  regulation restarts with its normal running condition     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    ATTENTION   For both the circuits  when the compressor are off because of the thermoregulation and the digital input of the recovery function is  active  the recovery valve is disabled     40 CONDENSER TEMPERAURE   PRESURE CONDITION TO ENABLE DISABLE THE       RECOVERY CYCLE    The recovery can be disabled depending on the condenser condition to avoid a possible high pressure alarm  The function can be  executed by programming the analogue input as condenser transducer 1 or 2  Par CF07 0 temperature control or CF07  1 pewssure  control     FUNCTIONING    40 1 RECOVERY DISABLED    With the recovery function is activated  if the temperature pressure is equal or higher than the set rC06  limit of the recovery cycle  the  recovery cycle  of the circuit detected by that transducer  is disabled  When the recovery is disabled the bottom display shows the  following blinking icons  b1rC   for circuit 1  b2rC   for circuit 2     40 2 RECOVERY ENABLED    If the temperaTure pressure decreases under the set     06     07  differential  the recovery cycle  of the circuit detected by that  transducer   is anabled again     40 3 NOTE ABOUT RECOVERY ENABLED DISABLED    To avoid long periodof time with recovery function disabled and the temperature pressure within the range     06     07  the units starts  counting the delay set in rCO8  After th
50. 0 L GB   1 0 23 02 2005 Preliminary    41 12 ARTC CLOCK ALARM       Label o the display    ArtC  clock alarm                                   Origin Wrong setting   Reset Clock adjusted   Restart Manual in function menu  Icona Blinking   N   Action Alarm relay   buzzer ON  Regulation   Loads Not changed   Energy saving Disabled if based on RTC  Unit ON OFF Disabled if based on RTC          41 13 AEUN  UNLOADING ALARM FROM HIGH TEMPERATURE OF THE EVAPORATOR WATER INLET       Label o the display    AEUn Unload signalling from evaporator       Origin    During normal running condition when the temperature pressure of evaporator water inlet is higher  than CO40 setpoint for the CO42 time delay                       Reset   If the water temperature is lower than CO39    CO41  differential     Da funzione unloading inserita dopo il tempo impostato             43  Restart Automatic  Icon Blinkin gA  Action Alarm relay   buzzer OFF       41 14 ALTI  LOW AIR AMBIENT TEMPERATURE  AIR   AIR UNIT ONLY        Label o the display    ALti  low temperature value of the evaporator air inlet        Origin    Chiller mode  CF01 0 and evaporator inlet NTC probe lower than AL26 for AL28 seconds    Heat pump  CF01 0 and evaporator inlet NTC probe lower than lower than AL33 forAL36 seconds  In stand by or remote OFF  the evaporator inlet NTC probe lower than the lowest value compared  between AL28 and AL36                 Reset Chiller  evaporator inlet NTC probe higher than AL26   AL27  different
51. 2  3 or 4   Functionning  When thermoregulation requires the relay is turned ON 1 second before turning in the compressor and goes off after the  time set in parameter CO13  After the compressor stops running the time CO13 will be reloaded     28 3 SOLENOID VALVE INTERMITTENT FOR SCREW COMPRESSOR    If configured this output is ON when the compressor is ON  in case of Part Winding or Star delta it corresponds with the first relay on   for the time set in Par  CO08 and then OFF for the time set in Par  COO9  The cycle CO08     COO09 of the valve is repeated until the  compressor is ON    ATTENTION    When the valve output is configured  the intermittent cycle is activated only if the Par  CO08  lt  gt  0     29 PUMP DOWN    The Pump down process is enabled only if the CO36 parameter is not equal to 0     29 1 OFF UNIT WITH PUMP DOWN AND WITH LOW PRESSURE SWITCH CONTROL    The process is enabled if the low pressure switch of the circuit is configured with parameter CO36   1 or 3 and one of the relay output is  configured as pump down solenoid circuit 1 or 2   CO36   2 or 4 are related to a pressure switch dedicated to this function or the  pressure transducer     When the thermoregulation is going to stop  before turning off the last compressor  the solenoid valve is closed  The compressor runs  until the low pressure switch connected to the digital input becomes active for a maximum time set in CO39  In this case there is no Low  pressure alarm and no alarm message will be dis
52. 24 Vac dcx1096  50 60 HZ  opzionale   Power absorption  10VA max   Inputs  10 NTC or 6 NTC   4  4   20ma   0   5Volt    Digital inputs    18  free voltage   Relay outputs  14 SPDT 5 2  A  250Vac   Data storing  on the non volatile memory  EEPROM    Operating temperature  0 60   C   Storage temperature   30 85   C   Relative humidity  20 85   no condensing   Measuring range    30 70   C    22   158  F  NTC   07150   C   04302   F   PTC or 0  50 bar  07725 psi   Resolution  0 1   C or 1   F  selectable   Accuracy of the controller at 25       0 7   C  1 digit    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    NOTE    Pg 100 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Dixell S p A  2 1  Via dell Industria  27  32010 Pieve d Alpago  BL  ITALY    tel   39   0437   98 33   fax  39   0437   98 93 13  E mail dixell gdixell com   http   www dixell com       Pg 102 103    
53. 3  Compressor 3 high pressure   14  Compressor 4 high pressure   15  Compressor 5 high pressure   16  Compressor 6 high pressure   17  Compressor 1 overload   18  Compressor 2 overload   19  Compressor 3 overload   20  Compressor 4 overload   21  Compressor 5 overload   22  Compressor 6 overload   23  Condenser fan overload of circuit 1  24  Condenser fan overload of circuit 2  25  Water pump overload of evaporator 1  26  Water support pump overload of evaporator    OANA OP ON sO    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    27  Water pump overload of condenser 1   28  Water support pump overload of condenser   29  Recovery request for circuit 1   30  Recovery request for circuit 2   31  Defrost end of circuit 1   32  Defrost end of circuit 2   33  Energy Saving   34  Pressure switch   compressor 1 oil   35  Pressure switch   compressor 2 oil   36  Pressure switch   compressor 3 oil   37  Pressure switch   compressor 4 oil   38  Pressure switch   compressor 5 oil   39  Pressure switch   compressor 6 oil   40  Pump down pressure switch of circuit 1   41  Pump down pressure switch of circuit 2   42  Generic alarm from digital input with stop regulation   43  Digital input of thermoregulation request  motocondensing unit   44  Digital input of cooling request  motocondensing unit    45  Digital input of heating request  motocondensing unit    46  Request  partialization 1 of compressor 1  motocondensing unit   47  Request  partialization 2 of compress
54. 49   1  1 power steps per circuit  in case of unloading there will be 2 compressor running  1 per circuit    With capacity compressors and with unloading active  to avoid having a not well balanced circuit after reducing the power  step valve  on  the resource  the valve  is activated for the time set in CO50 even if the unloading function is not more activated and the  thermoregulation requires 10096 of power  If CO50 0 the function is disabled and if necessary the valve is immediately off to have the  10096 of the power     UNLOAD DE ACTIVATION in HEAT PUMP MODE    If the evaporator temperature increases the value determined by  CO46 CO47  setpoint  differential  the unloading is disengaged  the  compressors are all available for the thermoregulation     Pg 70 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    30 7 OTHER INFORMATION ABOUT THE UNLOADING IN HEAT PUNP    To avoid having long period of unloading function activated when the temperature or the pressure value is continuously within the SET  and SET  differential  if the temperature or the pressure is higher than CO46  the CO48 time delay forces the unloading function off for  timeout event  even if the temperature   pressure is not lower than CO46 CO47     31 SOLENOID VALVE FOR LIQUID INJECTION    There are two outputs relay that can be configure as solenoid valve compressor 1 and 2  The function is enabled when       For compressor 1  one output relay is configured as solenoid valve com
55. 8 MOVE A PARAMETER LEVEL FROM PR2 TO PR1    Enter Pr2 programming level  Select the parameter and if the led   3 is off  the parameter is available only in Pr2   To show the parameter also in Pr1   1  Keep pushed SET key   Push 1 time the DOWN key and the led 3 should be on  the parameter is now available in Pr1   To hide the parameter in Pr1   Keep pushed SET key   2  Push 1 time the DOWN key and the led 3 should be off  the parameter is now removed from Pr1          11 9 MOVE A PARAMETER FROM PR3 TO PR2 TO PR1    Enter Pr3 programming level  here the parameter are all visible   Select the parameter  if all the leds are off the parameter is available only in Pr3   To show the parameter also in Pr2 and Pr1   1  Keep pushed SET key   2  Push 1 time the DOWN key and the leds 3 and 4 should be on  the parameter is now available also in Pr2       1   To show the parameter only in Pr2   1  Keep pushed SET key   Push 1 time the DOWN key and the leds 3 is off  the parameter is now available also in Pr2   To show the parameter only in Pr3   1  Keep pushed SET key  Push 1 time the DOWN key and the leds 3 and 4 are off  the parameter is now available only in Pr3     11 10 VisiBILITY AND PARAMETER VALUE LOCKED    To set the only visibility and lock the parameter value it is necessary enter Pr3 programming level    Pr1 PARAMETER VISIBILITY   Enter the Pr3 level   1  Select the parameter    2  Keep pushed the SET key    3  Push 1 time the MENU key and the led 3 change from on to blinking 
56. 8 Maximum time with recovery disabled  if temperature pressure within rC6     rC7  0 250 Min  Pri Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Alarms  Parameters   Description min           m u    Resolution  Low alarm  AL 1 Low pressure alarm delay from digital input 0 250 Sec  AL 2 Low pressure alarm delay from digital input after compressor stop if the low 10 250 S               pressure switch is used for the pump down   AL    Low pressure alarm setpoint from analogue input  30 0   70 0   C Dec   22 158   F int  0 0 50 0 bar Dec  0 725 psi int                            Pg 38 103                                                                                                          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  AL 4 Low pressure alarm differential from analogue input 0 1 25 0   C Dec  0 45   F int  0 0 14 0 bar Dec  0 203 psi Int  AL 5 Maximum number of low pressure events from digital analogue inputs   Manual reset if AL05   0 0 16  Automatic reset if ALO5 216  From automatic to manual reset if ALO5  1  15  AL 6 Low temperature pressure alarm during defrost  0  Not enabled 0 1  1  Enabled  AL 7 Low temperature pressure alarm delay during defrost 0 250 Sec  AL 8 Low temperature pressure alarm with unit in OFF or stand     by   0   Not enabled 0 1  1  Alarm enabled  High Alarm  AL 9 High temperature pressure alarm from analogue input  30 0   70 0   C Dec   22 158    int  0 0 50 0 bar Dec  0 725 psi int  AL 10 High temperat
57. 9   2  the power supply configuration is Vcc  CF83   0   ACF3    e Two digital  analogue inputs configured with the same function or without the necessary  resources  es  compressor   3 overload but compressor 3 relay not configured     ACF4      CF79   1 and its digital input not configured or CF79   2 and no external temperature probe  configured    ACF5    Circuito   2 not configured but at least one of its resources are present  relay  solenoid pump   down  heaters  inversion valve  fan condensing ON   OFF  recovery  auxilairy           1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Causa attivazione    ACF6   e Thetotalnumber of compressor of the 2 circuits   CF04   CF05   is    Y  gt 6   Y  gt 4 with no direct compressor start up  CO10   0  or the number of steps is   0  CF06    Y    2 and the intermittent valve is configurated with ON  CO08  and OFF  CO09     0    Pump down function but at least in one circuit     The pump down solenoid relay is not present  Y No pump down pressure switch or evaporating probe when     the pump down is enabled with unit in start  Or     No low pressure switch configurated   e        compressor configuration with CF04 and CF05 but not the relay outputs   Main  Intermittent valve when enabled with the ON   OFF time  CO08   CO09   0  When the by pass time   0 and there is no partialization or by pass valve configured  Motor part 2   centre of the star with part winding or star delta  The necessary step valve configu
58. AS while the bottom display shows Pr1 labels    2  Push UP key for 2 seconds and the top display will show Pr2    1  Push UP key again for 2 seconds and the top display will show Pr3   3  Push SET key and the top display shows a blinking 0  with UP or DOWN insert the Pr3 password  Push SET and  if the value is  correct  top display will show the first family of parameters  ALL   Otherwise set the password again    4  Select a parameter family with DOWN or UP keys    5  Push SET to enter  the bottom display shows the first available parameter label while the top display shows its value    The user can shows and modify all the paramters belonging to this family     Parameter status  leds and bottom display in Pr3    Led n 1    n p b  2 b D        7      bar Flow           tj    X  amp               dig gn       Leds 1   2 are blinking  the parameter can not be changed         1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    e All the leds are off  the parameter is available only in Pr3       Led 4 on  the parameter can be changed also in Pr2       Led 4 blinking  the parameter is visible also in Pr2        Leds 3   4 on  the parameter is available in Pr2 and in Pr1       Leds 3   4 blinking  the parameter is visible in Pr1 and in Pr2    e        MENU key allows to exit from a family to reselect another without exit the Pr2 level   e The MENU key allows to pass to Pr1 starting from a family label    e To exit completely the programming push SET   UP     11 
59. ATION ANTIFREEZE   BOILER FUNCTION    To determine the electrical heater control in chiller or heat pump mode because the electrical heaters can be used as anti freeze or can  also be used to integrate or heating the heat pump mode or in particular situation in chiller mode    The function is enabled when    1        NTC probe configured as external air for dynamic setpoint   boiler function    2  Parameter Ar11   20     Integration control Ar11 1   When the air temperature value detected by the external air probe decreases under the Ar12 setpoint  the Ar14 delay starts counting  If  during the Ar14 counting the external air increases above the Ar12   Ar13  differential  the function is aborted and the Ar14 time is  reloaded    When the time Ar14 is expired and the external air temperature is still under the Ar12 setpoint and the water temperature detected by  the evaporator probe is lower than Ar15 in chiller mode or Ar17 in heat pump mode  the heaters are turned on  When the temperature  rises over Ar15   Ar16 differential  in chiller mode or Ar17 Ar18 in heat pump the heaters are turned off    With the heaters on if the temperature of the external air rises above the Ar12  set    Ar13 differential  immediately they are turned off  and the Ar14 delay is reloaded     Pg 62 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Attention With Boiler function activated and external air temperature value lower than Ar12 if the air temperature decreases un
60. Compressor malfunction  ump down management  With dedicated pressure switch  Low pressure switch  Low pressure transducer  nloading circuit  High temperature of the evaporator inlet water  High temperature of the condenser inlet water  unit with recovery   High condensing pressure    e       C                                       gt  9                      Pg 8 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary       Low evaporating pressure   Maintenance messages      Compressors      Evaporator pumps      Condenser pumps   Auxiliary relays   e Two configurable relay outputs not depending from the control algorithm can be managed through NTC  PTC or pressure probes    Weekly Energy saving   e Three different time bands per day  only with RTC onboard       From digital input   Weekly ON OFF    e Three different time bands per day  only with RTC onboard    Dynamic setpoint       Determined by analogue NTC input or 4 20     current input    Change over     e Automatic chiller or heat pump functioning depending from NTC analogue input    Remote OFF       From configurable digital input    Remote change over       From configurable digital input    Hot start     e  Air air unit   Defrost management       Combined control with temperature and pressure      Forced defrost with low temperature of external air      From configurable digital input      Manual from keyboard   Boiler       For electrical integration heating or anti freeze heaters   Two proportio
61. F A CiRCUIT NOT ENABLED    If one circuit is disabled the bottom display shows diS alternated with the label name of the measurement selected   Circuit 1   diS the bottom display shows b1dS   circuit 1 disabled    Circuit 2   diS the bottom display shows b2dS   circuit 2 disabled    The 6245 label appears only if the 2    circuit is configured     17 9 ENABLE OR DISABLE A SINGLE COMPRESSOR    Through the instruments keyboard is possible to disable a single compressor for maintenance or to lock it when malfunctioning     COEn FUNCTION compressors running status    Label involved in COEn function  CO1E   Compressor 1 status    CO6E   Compressor 6 status   The COEn function uses only the compressors configured by the corresponding output parameters    Enter the function Menu   1  Use the UP or DOWN keys to select COEn    2  Push SET key  bottom display   COTE  top display   En   3  Select the compressor with UP or DOWN  CO2E   COSE   CO4E              COGE if available    4  Push SET for 3 seconds when the label corresponds to the compressor to disable  CO1E   CO2E   CO3E   CO4E              CO6E   The top display shows the blinking En label  use the UP or DOWN key and change to diS  Compressor disabled  or En   compressor enabled  then push SET to confirm  the display shows next item     Pg 52 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    5  To exit the COEn function push MENU key or wait the timeout     17 10 READ OUT OF A COMPRESSOR NOT ENABLED
62. G TEMPERATURE   PRESSURE IN CHILLER  B1CU     B2CU  UNLOADING FROM LOW CONDENSING TEMPERATURE   PRESSURE IN HEAT PUMP   B1RC     B2RC RECOVERY DISABLED FROM HIGH CONDENSING TEMPERATURE PRESSURE IN CHILLER  B1PH   B2PH  PUMP DOWN STOP ALARM FROM PRESSURE SWITCH   LOW PRESSURE SWITCH   B1PL   B2PL ALARM DURING THE PUMP DOWN START UP FROM PUMP DOWN PRESSURE SWITCH   LOW  PRESSURE TRANSDUCER   C1MN   C2MN   C3MN   CAMN   C5MN   C6MN COMPRESSOR MAINTENANCE   AEP1   AEP2 PUMP  SUPPLY FAN MAINTENANCE   ACP1   ACP1 CONDENSER PUMP MINTENANCE   ALARM RELAY AND BUZZER    AUTOMATIC TO MANUAL ALARM PROCEDURE  TABLE OF THE OUTPUT STATUS IN ALARM CONDITION    ALARM     A    TYPE AND CORRESPONDING OUTPUT OFF  ALARM     A    TYPE AND CORRESPONDING OUTPUT OFF  ALARM     A    TYPE AND CORRESPONDING COMPRESSOR OUTPUT OFF    BLACK OUT  INSTALLING AND MOUNTING    PANEL CUT  OUT   PLEXIGLASS PROTECTION BOTTOM OPEN  PLEXIGLASS PROTECTION TOP OPEN  METAL FRONT FRAME    45 5    46    47    47 1  47 2  47 3    48    VERTICAL BOARDS VI620     VI820 PANEL CUT OUT    ELECTRICAL CONNECTIONS  ACCESSORIES    MONOPHASE FAN CONTROL  230VAC AND CUT PHASE CONTROL  INVERTER  MICROFAN 380VAC UP TO 4KW OR 8KW  TRANSFORMER    TECHNICAL DATA    96  97    97  97    98    99    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    1 GENERAL ADVICE    e 1 1 PLEASE READ BEFORE USING THIS MANUAL   e   This manual is part of the product and should be kept near the   e instrument for easy and quick referenc
63. GITAL INPUT CONTROL  HOT START    WATER PUMP OF THE CONDENSER    CONDENSER WATER PUMP CONTROL    PUMP GROUP OF THE CONDENSER    CONDENSER WATER PUMP ROTATION  CONDENSER WATER PUMP ROTATION THROUGH DIGITAL INPUT CONTROL    LOAD MAINTENANCE  COMPRESSOR MAINTENANCE RESQUESTS    CONDENSER FAN REGULATION    PWM OUTPUT FOR FAN CONTROL   CONDENSING UNIT  COMMON OR SEPARATE   GRAPH  PROPORZIONAL REGULATION OF CONDENSER FANS  GRAPH  ON   OFF REGULATION OF THE CONDENSER FAN    DEFROST CYCLE    38 1  38 2  38 3  38 4  38 5  38 6  38 7  38 8    39    39 1  39 2    40    40 1    43 1  43 2  43 3    44  45    45 1  45 2  45 3  45 4    FORCED DEFROST   COMBINED DEFROST   MANUAL DEFROST   DEFROST START CONDITION WITH TWO CIRCUIT UNIT   END OF THE DEFROST IN A TWO CIRCUITS WITH ONE CONDENSING FAN CONTROL UNIT  AUTOMATIC DEFROST PROCEDURE   OTHER INFORMATION ABOUT THE DEFROST   DEFROST PARAMETER DESCRIPTION    RECOVERY    UNIT WITH TWO SEPARATE IDRAULIC CIRCUITS  UNIT WITH TWO IDRAULIC CIRCUIT WORKING IN PARALLEL    CONDENSER  TEMPERAURE    PRESURE CONDITION TO  ENABLE DISABLE THE RECOVERY CYCLE    RECOVERY DISABLED  RECOVERY ENABLED  NOTE ABOUT RECOVERY ENABLED DISABLED    MESSAGES   ALARM CODES        1   AP2            AP4       5   AP6   AP7   AP8   AP9   AP10 PROBE FAILURE  AEFL  EVAPORATOR FLOW ALARM  DIFFERENTIAL PRESSURE SWITCH    ACFL  CONDENSER FLOW ALARM  DIFFERENTIAL PRESSURE SWITCH    ATSF  OVERLOAD ALARM OF THE SUPPLY FAN   ATE1         2 EVAPORATOR PUMP OVERLOAD ALARM   ATC1   A
64. ION THROUGH  DIGITAL INPUT    THERMOREGULATION AND COMPRESSORS ROTATION  SATURATION   CIRCUIT BALANCING  COMPRESSORS    COMPRESSORS START  UP   DIRECT START  UP   DIRECT START  UP OF A CAPACITY COMPRESSOR   PART WINDING   COMPRESSOR START  UP WITH PART WINDING   PART WINDING START  UP OF COMPRESSORS OR CAPACITY COMPRESSORS  STAR   DELTA START   STAR   DELTA START OF A COMPRESSOR   STAR   DELTA START  UP OF A CAPACITY COMPRESSOR    CAPACITY CONTROL    MINIMUM LOAD START  UP  BY  PASS GAS VALVE DURING COMPRESSOR START  UP  SOLENOID VALVE INTERMITTENT FOR SCREW COMPRESSOR    PUMP DOWN    OFF UNIT WITH PUMP DOWN AND WITH LOW PRESSURE SWITCH CONTROL  PUMP DOWN WITH DEDICATED PRESSURE SWITCH   PUMP DOWN FUNCTION WITH DEDICATED PRESSURE PROBE   PUMP DOWN ALARM DURING COMPRESSORS START  UP   PUMP DOWN ALARM DURING COMPRESSORS SWITCHING OFF   PUMP DOWN INFORMATION    UNLOADING    HIGH TEMPERATURE OF THE EVAPORATOR WATER INLET   UNLOADING DESCRIPTION   UNLOADING INFORMATION   UNLOADING WITH PRESSURE  CONDENSING TEMPERATURE OR EVAPORATING PRESSURE CONTROL  REGULATION   OTHER INFORMATION ABOUT THE UNLOADING IN CHILLER   OTHER INFORMATION ABOUT THE UNLOADING IN HEAT PUMP    SOLENOID VALVE FOR LIQUID INJECTION    FUNCTIONNING    WATER PUMP OF THE EVAPORATOR   SUPPLY FAN    WATER PUMP OF THE EVAPORATOR   SUPPLY FAN  AIR AIR   HOT START   SUPPLY FAN  ONLY FOR AIR   AIR UNIT IN HEAT PUMP MODE    EVAPORATOR PUMP GROUP    EVAPORATOR WATER PUMP ROTATION  EVAPORATOR WATER PUMP ROTATION THROUGH DI
65. L INPUT    DISPLAY LAYOUT    HOW TO SHOW THE MEASUREMENT LIST   SHOW THE CIRCUIT 1 OR 2    CUSTOM DISPLAY    DEFAULT READ   OUT OF THE TOP DISPLAY   DEFAULT READ   OUT OF THE BOTTOM DISPLAY   FORCED READ   OUT OF THE TOP AND BOTTOM DISPLAY   DEFAULT DISPLAY READ   OUT OF THE REMOTE PANELS VI620S AND VI820S  DEFAULT DISPLAY READ   OUT OF THE REMOTE PANELS VI620S AND VI820S    DISPLAY INFORMATION    SHOW THE SET POINT VALUE   MODIFY THE SET POINT   SHOW THE ACTIVE SETPOINT DURING ENERGY SAVING OR DYNAMIC SETPOINT  DISPLAY IN REMOTE OFF   DISPLAY IN MOTOCONDENSING CONFIGURATION    FUNCTION MENU     M  KEY    ALARM LIST  SHOW AND RESET   COMPRESSOR OVERLOAD ALARM RESET   COMPRESSOR OVERLOAD PASSWORD    ALARM LOG LIST   ERASE THE ALARM LOG LIST   PASSWORD VALUE OF THE ALARM LIST   DISABLE     ENABLE A SINGLE CIRCUIT   READ OUT OF A CIRCUIT NOT ENABLED   ENABLE OR DISABLE A SINGLE COMPRESSOR   READ OUT OF A COMPRESSOR NOT ENABLED   READ OUT OF THE COMPRESSOR DISCHARGE TEMPERATURE PROBE   READ OUT OF THE RUNNING HOURS   RESET THE RUNNING HOUR   READ OUT OF THE COMPRESSOR STARTS UP   RESET THE STARTS UP NUMBER   READ OUT OF THE PROPORTIONAL OUTPUT PERCENTAGE OF THE CONDENSER FAN CONTROL  READ OUT OF THE FOUR PROPORTIONAL OUTPUT   READ OUT OF THE TIME COUNTING TO THE NEXT DEFROST   READ OUT OF THE PROBES CONFIGURED TO CONTROL AN AUXILIARY OUTPUT RELAY  HOW TO DISPLAY THE TEMPAERATURE OF THE INTERNAL TEMPERAURE SENSOR OF THE REMOTE  TERMINALS 1 OR 2    ENERGY SAVING    ENERGY SAVING FR
66. L15 after the water pump is on and  after the digital input  itself is activated  for the time set in AL17    Alarm not enable if AL14 0   Alarm enabled in chiller only if AL14 1   Alarm enabled in heat pump only if AL14 2   Alarm enabled in chiller and heat pump if AL14 3    Reset Digital input not active for the time AL18   Restart Automatic     Manual after AL16 events per hours  Reset procedure in Menu function                           Pg 80 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary                Icon Blinking Flow   Action Alarm Relay   and buzzer on only during normal running conditions   ATTENTION    The alarm relay and the buzzer are activated only if the alarm appears during normal running conditions   When the temperature setpoint has been reached and CO16 CO21  2  the icon Flow  blinks without alarm   NOTE ABOUT THE FLOW ALARM   CO16   CO21 0 Water pump not enabled     The alarm is managed only if one digital input is configured as flow switch  the restart is always automatic    CO16   CO21 1 Water pump with continuous control    The alarm is managed only if one digital input is configured as flow switch  the restart is always automatic  in stand by or remote  OFF   pump off   it becomes manual after AL16 events per hour    In chiller or heat pump only  During the functioning of the unit any flow alarm stop the loads described in the table  the water pump  follow its regulation algorithm and is turned off  after AL16 events per ho
67. MENU one time or wait the timeout     17 2 COMPRESSOR OVERLOAD ALARM RESET    COtr function resets the compressor overload alarm event    Within the COtr function all the active compressor overload alarms are displayed in a list    Labels involved in COtr  CO1r   compressor 1 overload reset     CO6r   compressor 6 overload reset  Labels CO1r     CO2r   CO3r      CO4r     CO5r            are available if the digital inputs have been previously configured    ATTENTION   In the COtr function the alarm is displayed only after the number of events per hour have reched the Par  AL20 value only after that  number of events per hour the alarm becomes MANUAL     MANUAL ALARM RESET PROCEDURE   Enter Menu function   1  Use UP or DOWN key and select the COtr on the bottom display    2  Push SET one time  if there are active alarms the bottom display shows the alarm label eg  CO1r  for compressor 1  while the top  display shows the label rSt to reset the alarm or NO if the alarm can not be reset  Use the UP or DOWN keys to scroll all the alrm  list    3  Nothing happens by pushing SET when the label NO is displayed    4  Pushing SET when the rSt label is displayed the corresponding alarm will be reset after the password  bottom display   ArSt while  the top display   PAS    5  Push SET and the top display blinks O while the bottom shows PAS  Insert the password using UP or DOWN key  see AL  parameter family   If the password is OK the ArSt blinks for per 3seconds  if the password value is
68. NTING TO THE NEXT DEFROST    The 2 times delay to next defrosts of the two circuits can be showed in the menu function   dF FUNCTION time to next defrost    Label involved in dF function    dF1 delay time to next defrost of the circuit 1   dF2 delay time to next defrost of the circuit 2   The labels apperas on if the heat pump configuration is enabled     Enter the function menu      1  Use the UP or DOWN keys to select dF  2  Push SET key  the dF1 label is showed on the top display  the bottom display shows the time delay to next defrost in minutes      seconds  The    icon is on   3  Use the UP or DOWN keys to select dF1 or dF2   4  To exit the Hour function push MENU key or wait the timeout     17 19 READ OUT OF THE PROBES CONFIGURED TO CONTROL AN AUXILIARY OUTPUT RELAY    The probe values  configured to control the auxiliary relay output  can be showed in the menu function    uS FUNCTION temperature pressure value of the control probe for auxiliary output    Label involved in uS function    uSt1 auxiliary probe value of the circuit 1   uSt2 auxiliary probe value of the circuit 2   Enter the function menu   1  Use the UP or DOWN keys to select uS    2  Push SET key  the label uSt1  temperature probe   or uSP1  Pressure probe  is showed on bottom display  the top display shows  the the temperature or pressure value    3  Use the UP or DOWN keys to select uSt1 auxiliary probe for circuit 1or uSt2 auxiliary probe for circuit 2    4  To exit the Hour function push MENU key or 
69. Not active flow input duration   Within this time the flow alarm must be not active and  after this time  the previous alarm is automatically reset  if automatic  or  if  manual  the unit can be restarted     41 4 ATSF  OVERLOAD ALARM OF THE SUPPLY FAN       Label o the display AtSF  Overload alarm of the supply fan                         Origin CF0120  After on fan when the ID is activated for AL15 time  After on pump when the ID is  activated for AL17    Reset Digital input not active for AL18 time   Restart Automatic     Manual after AL16 events hour  Reset procedure in Menu function     Icon Blinking Flow    Action Alarm relay   buzzer ON          MANUAL RESET OF THE OVERLOAD ALARM OF THE SUPPLY FAN   After AL16 events hour it is necessary to restart manually the unit  reset procedure in Function Menu with blinking label rSt if the alarm  is not active from Al18otherwise label NO  can not be reset    Push SET key to reset the alarm  the label disappears  the fan restarts  and the alarm is by passed for AL15 time delay to allow the start up if within this interval the alarm does not appear again     41 5 ATE1   ATE2 EVAPORATOR PUMP OVERLOAD ALARM                         Label o the display AtE1  overload pump alarm of evaporator 1   AtE2  overload pump alarm of support evaporator 2   Origin Active ID when it is configured as overload pump of evaporator 1  Active ID when it is configured as overload pump of support evaporator 2   Reset With active digital input  Restart Ma
70. OM DIGITAL INPUT   ENERGY SAVING TIME TABLE WITH RTC   RTC DAILY TIME TABLE PROGRAMMING   ENERGY SAVING OR UNIT ON OFF ACTIVATION WITH RTC PROGRAMMING    DYNAMIC SETPOINT    DYNAMIC SETPOINT GRAPH    AUXILIARY RELAYS    AUXILIARY RELAY WITH DIRECT ACTION  AUXILIARY RELAY WITH INVERSE ACTION    COMPRESSOR THERMOREGULATION    THERMOREGULATION PARAMETER DESCRIPTION    SELECTION OF THE KIND OF THERMOREGULATION    GRAPH OF THE COMPRESSOR THERMOREGULATION IN CHILLER   GRAPH OF THE COMPRESSOR THERMOREGULATION IN HEAT PUMP  GRAPH NEUTRAL ZONE COMPRESSOR CONTROL   GRAPH PROPORTIONAL INTEGRAL COMPRESSOR REGULATION CONTROL    THERMOREGULATION OF THE ANTI FREEZE  INTEGRATION HEATING  OR BOILER    THERMOREGULATION OF THE HEATERS IN CHILLER  THERMOREGULATION OF THE HEATERS IN HEAT PUMP    23 3  23 4  23 5  23 6  23 7    24    25  26  27    27 1  27 2  27 3  27 4  27 5  27 6  27 7  27 8  27 9    28    28 1  28 2  28 3    29    29 1  29 2  29 3  29 4  29 5  29 6    30    30 1  30 2  30 3  30 4  30 5  30 6  30 7  31    31 1    32    32 1  32 2    33    33 1  33 2  33 3    34    34 1    35    35 1  35 2    36    36 1    37    37 1  37 2  37 3  37 4    38    THERMOREGULATION OF THE SUPPORT HEATERS FOR AIR AIR UNIT   CONDENSER ANTI FREEZE HEATERS REGULATION   THE THERMOREGULATION OF THE ANTI FREEZE HEATERS OF THE CONDENSER RECOVERY  GRAPH OF THE ANTI FREEZE  INTEGRATION HEATING  BOILER HEATER RELAYS   BOILER THERMOREGULATION ANTIFREEZE   BOILER FUNCTION    ANTI   FREEZE ALARM AND HEATERS REGULAT
71. ORTANT  To change from chiller to heat pump and viceversa the unit must be set in stand by before continuing     key allows to start in chiller mode if CF78  0  in heat pump if CF78  1  When the unit is running the    key allows to start in heat pump mode if CF78  0  in chiller if CF78 21er  When the unit is running the    STAND  BY   OR UNIT OFF  NOT RUNNING       The unit is considered in stand by when the leds Ye and vel are both off  The stand by is reached each time the Chiller or  the Heat Pump are turned off  During the stand by the user can       Show all the probe measurements     Detect and reset the alarm events     13 2 UNIT START  STOP FROM DIGITAL INPUT    Turn on or off the unit from digital input  Set the digital input as remote ON OFF  depending on the input polarity it can generate the unit off    e The digital input overrides the keyboard command   e        keyboard can run only if the digital input is not active   e When the digital input is not active the instrument restore its status  had before the digital input activation      14 DISPLAY LAYOUT    As default  In normal condition  the display shows the circuit 1 information   The displayed circuit is indicated from the corresponding led Cir1 on  UP key   or Cir2  circuit 2  DOWN key      14 1 How TO SHOW THE MEASUREMENT LIST     With the led Cir1 on  push UP or Down keys to display the labels of the information of the circuit 1   With the led Cir2 on  push UP or Down keys to display the labels of the in
72. Pump down transducer  CO36   1 2 3 4  compressors start up and the set CO37 is not reached in  the interval time CO39   Reset From thermoregulation start up and ID not active  From thermoregulation start up with evaporating pressure higher than CO37   CO38  differential   Restart Automatic   Manual and logged after AL21 events per hour if AL23 1  reset procedure in function  menu    If AL23   0 it is automatic and not logged   Icona Blinking   N  Action Alarm relay   buzzer ON when it becomes manual       41 35 C1MN   C2MN   C3MN   CAMN   C5MN   C6MN COMPRESSOR MAINTENANCE       Label o the display    C1Mn  Compressor  1 maintenance        C6Mn  Compressor  6 maintenance                             Origin Compressor running hours  gt  Hour counter setpoint  Reset Hour reset in function menu   Restart Manual   Icona Blinking   N   Action Alarm relay   buzzer ON   Regulation   Action Only display warning messages   Loads Not changed       41 36 AEP1   AEP2 PUMP  SUPPLY FAN MAINTENANCE       Label o the display    AEP1  Evaporator  1 pump maintenance   AEP2  Evaporator  2 pump maintenance                                   Origin Pump supply fan running hours  gt  Hour counter setpoint  Reset Hour reset in function menu   Restart Manual   Icona Blinking   N   Action Alarm relay   buzzer ON   Regulation   Action Only display warning messages   Loads Not changed       41 37 ACP1   ACP1 CONDENSER PUMP MINTENANCE       Label o the display    ACP1  Condenser  1 pump maintenance   ACP1
73. R mode  the maximum probe value compared between the temperature pressure probe of the two circuits       HEAT PUMP  no evaporator probe configured  the minimum probe value compared between the condenser  temperature pressure probe of the two circuits       HEAT PUMP  evaporator probe configured  the minimum probe value compared between the evaporator temperature pressure  probe of the two circuits    If par  FA05   1 and if the evaporating pressure probe are not configured  the fan output controls are separated and are controlled by   the condenser temperature pressure probes  When the evaporator probes are configured  in heat pump the ventilation is controlled by   these transducers     37 3 GRAPH  PROPORZIONAL REGULATION OF CONDENSER FANS    Speed      Heat pum  FA21 pump    FA1    OFF       37 4 GRAPH  ON   OFF REGULATION OF THE CONDENSER FAN    Heat pump Chiller  OFF       Pbr Pbr       FA19 FA09 FA10    Pg 74 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    38 DEFROST CYCLE    The defrost cycle starts only if all these steps are determined      CF02 1 heat pump unit      DF01  lt  gt 0  defrost enabled      Unit working in heat pump mode and at least one compressor running      The condenser evaporator probe is configured  per circuit   if the evaporator probe s is are defined  the defrost cycled is always  controlled by it   them      38 1 FoRCED DEFROST    The function is enabled if the parameter dF19 lt  gt 0  It allows to make a forced d
74. RESSURE    IN CHILLER       Label o the display    b1CU  unloading high temperature from condenser of the circuit   1   b2CU  unloading high temperature from condenser of the circuit   2                    Origin When the temperature pressure of condenser probe control is higher then CO44   Reset   When the temperature pressure of condenser probe is lower than CO44    CO45  differential     After unloading is activated        after             47   Restart Automatic   Icon Blinkin   N   Action Alarm relay   buzzer OFF          41 31 B1CU     B2CU  UNLOADING FROM LOW CONDENSING TEMPERATURE   PRESSURE IN HEAT    PUMP       Label o the display    b1CU  unloading message from condenser  1   b2CU  unloading message from condenser  2                       Origin During normal running condition when the temperature pressure of evaporator condenser probe is  lower than    CO46 setpoint   Reset   when the temperature pressure of evaporator condenser probe value is higher than     46         47     After unloading is activated        after             48   Restart Automatic   Icon Blinking   N   Action Alarm relay   buzzer OFF          41 32 B1RC     B2RC RECOVERY DISABLED FROM HIGH CONDENSING TEMPERATURE PRESSURE IN    CHILLER       Label on the display    b1rC  recovery disabled message from circuit  1   b2rC  recovery disabled message from circuit  2                       Origin In normal running condition when the temperature pressure probe value is higher than the set rC06  Reset 
75. TC2 CONDENSER RECOVERY PUMP OVERLOAD ALARM   AEE EEPROM ALARM   AFR  POWER SUPPLY FREQUENCY ALARM   ALOC  GENERIC ALARM WITH STOP REGULATION   ACF1   ACF2   ACF3   ACF4   ACF5   ACF6   ACF7   ACF8   ACF9 CONFIGURATION ALARM OF THE UNIT  ARTF CLOCK FAILURE   ARTC CLOCK ALARM   AEUN  UNLOADING ALARM FROM HIGH TEMPERATURE OF THE EVAPORATOR WATER INLET   ALTI  LOW AIR AMBIENT TEMPERATURE  AIR   AIR UNIT ONLY    AEP1   AEP2 EVAPORATOR PUMPS   SUPPLY FAN MAINTENANCE REQUEST   ACP1   ACP12 CONDENSER PUMPS MAINTENANCE REQUEST   B1HP   B2HP HIGH PRESSURE SWITCH CIRCUIT 1 AND 2   B1LP   B2LP LOW TEMPERATURE   LOW CONDENSING PRESSURE OF THE CIRCUIT   B1AC   B2AC   B1AC   B2AC ANTIFREEZE ALARM   LOW OUTLET TEMPERATURE  AIR   AIR UNIT IN CHILLER  MODE    B1AH   B2AH ANTI FREEZE ALARM   LOW OUTLET AIR TEMPERAURE AIR AIR UNIT ONLY  ON HEAT PUMP  MODE   B1HP   B2HP HIGH PRESSURE   CONDENSING HIGH TEMPERATURE OF THE CIRCUIT   B1LP   B2LP LOW PRESSURE SWITCH CIRCUIT  1 OR 2   B1LP   B2LP LOW EVAPORATING PRESSURE OF THE CIRCUIT  WITH PRESSURE TRANSDUCERS ONLY   B1TF  B2TF CONDENSER FAN OVERLOAD ALARM   C1HP   C2HP   C3HP   CAHP   C5HP   COHP COMPRESSOR HIGH PRESSURE ALARMS              C20P              C4OP   C50P   C6OP   PRESSURE SWITCH ALARM   COMPRESSOR OIL   C1DT  C2DT   C3DT   C4DT   C5DT   C6DT HIGH COMPRESSOR DISCHARGE TEMPERATURE ALARM  C1TR   C2TR   C3TR   CATR   C5TR   C6TR COMPRESSOR OVERLOAD ALARM   B1DF     B2DF DEFROST ALARM   B1CU     B2CU UNLOADING DISABLED FROM HIGH CONDENSIN
76. TH PRESSURE  CONDENSING TEMPERATURE OR EVAPORATING PRESSURE  CONTROL    The function is always enabled for both the running mode in order to reduce the load and helps the unit to start  in chiller for high  temperature of the external air to avoid high pressure alarms  in heat pump for low temperature of external air to avoid the low pressure  alarms    The compressor unloading in chiller mode is managed by the analogue input configured as condenser probe circuit 1 or 2 and  determined by CF07  O temperature  1   pressure    The compressor unloading in heat pump mode is managed by the analogue input configured as evaporator probe circuit 1 or 2  If not  configured the heat pump unloading is managed from the condenser transducer     30 5 REGULATION    UNLOADING IN CHILLER MODE   When the chiller thermoregulation request begins to start the compressors  if the condenser pressure temperature is equal or bigger  than     44 setpoint the unloading process  of that circuit probe  is engaged  The bottom display shows  alternated with the  measurement  the b1Cu or b2Cu labels  The number of active compressors step is determined by the CO49 parameter     EXAMPLE   Unit with 2 circuits with 3 compressors each    If Par  CO49   2  2 power steps per circuit  in case of unloading there will be 4 compressor running    With capacity compressors and with unloading active  to avoid having a not well balanced circuit after reducing the power  step valve  on  the resource  the valve  is activat
77. TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP   Circuits 1 and 2 configured with more than one step of power  eg each circuit with three compressors   After the rC04 time delay   minimum on time of the recovery function when activated  if the digital input of the recovery is not active the units stops the new  resources for the time set in rC02  After this delay the recovery valve is turned off and the regulation restarts with its normal running  condition     RECOVERY START OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED   When the system is running with 10096  eg all the three compressor of a circuit are on  of power and the digital input start the recovery  function  before turning on the recovery valve one of the step  depending on the time running hours   is turned off for the time set in  rC02  After rC02 the recovery valve is turned on  Then  after the rC03 time  this delay keeps off all the other steps after the recovery is  started  the resource forced off if necessary is turned on again     RECOVERY STOP OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED   When the system is running with 10096  eg all the three compressor of a circuit are on  of power and the digital input stop the recovery  function  after the rC04 time delay  minimum on time of the recovery function when activated  and before turning off the recovery valve   one of the step is turned off for the time set in rC02  When the delay is expired the unit turns off the recovery
78. UTS NTC            PROBES    PbC   Common terminal    IC260L   IC261L   IC280L   IC281L             74 DIGITAL INPUTS  GND   Common terminal    IC260L   IC261L   IC280L   IC281L               sleet dt     25 27 29 31 33 35 3739 41 43 45   26 28 30 32 34 36138  40 4244  46             Jj Jj J     7 5 ANALOG INPUT FOR PRESSURE TRANSDUCER PP30  4   20MA SIGNAL   Using 4 20mA pressure transducer set the Parameter CF07   0   1    IC260L   IC2  1L   IC280L   IC281L       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 6 ANALOG INPUT FOR PRESSURE RATIOMETRIC TRANSDUCER PPR30  0   5V SIGNAL   Using 5V ratio metric pressure transducer set the Parameter CF07 2 2 3    IC260L   IC261L   IC280L   IC281L          7 7 PWM OUTPUT FOR CONDENSING FAN SPEED CONTROL   With only one condensing circuit configured the TF1  TF2 outputs work together  The PWM signal can control the cut phase controllers  for the following mono phase models    Mod  XV05PK mono phase   cut phase control 500 Watt  2A    Mod  XV10PK mono phase   cut phase control 1000 Watt  4A    Mod  XV22PK mono phase   cut phase control 2200 Watt  9A         Fan speed module  circuit n  1    Power  supply  23N           Fan speed module  circuit n  2    Power  supply  230      gt     Pg 20 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 8 FAN CONDENSING CONTROL  0   10VDC OUTPUTS    With only one condensing circuit configured  the Out1   Out2 outputs work together giving the same
79. active unloading  1  1  step 1 3  2  2    step  3  3   step  CO 50 Minimum ON time of the capacity step after the unloading function start  only     0 250   Sec  for capacity compressor   Compressor liquid injection  CO 51 Setpoint of the solenoid valve  on  of the liquid injection 0 150 HC Dec   int  0 302   F int  CO 52 Setpoint of the solenoid valve  off  of the liquid injection 0 0 25 0   C Dec  0 45   F int  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Auxiliary relay menu function  Parameters   Description min           M U    Resolution  Auxiliary relay of the circuit 1  US 1 Auxiliary relay 1 operating mode  See graph and auxiliary relay functions   07 Not enabled  1 7 Always available with direct action 0 4  2  Available only when the unit is on with direct action  3  Always available with reverse action  4  Available only when the unit is on with reverse action  US2 Analog input configuration for auxiliary relay 1 control  Allows to select which 4 10  probe value Pb1  Pb10 controls the relay                         Pg 34 103                                                                                           1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  US3 Auxiliary setpoint 1  See graph and auxiliary relay functions   30 0   70 0   C Dec   22 158   F int  0 0 50 0 Bar Dec  0 725 Psi int  US 4 Auxiliary differential 1  See graph and auxiliary relay functions  0 0 25 0   C Dec  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int 
80. alogue inputs  NTC probes or through configuration 6 NTC   PTC and 4 pressure transducer 4 20mA or ratio metric 0  5 0Volt  6 modulating outputs   1 output for remote panel  max 2 remote panels    1 TTL output for    Hot Key 64    connection or for XJ485  interface module for monitoring system  connection    MAX current on the relay contacts rel   5 2 A 250V   MAX common current 12A 250V    IC260L IC280L    5 2 A  250V        II I  N  Di DI6 7 de 0       D  31 33 35 37 39 41  43  45  32 34 36 38 40 42 44 46    16   0118   Pb8  D17                 0110   0112   DH4   DI  DH        DHS       7 2 HARDWARE RESOURCES FOR IC261L   IC281L MODELS    14 digital outputs  relays    18 digital inputs  free of voltage    10 analogue inputs  NTC probes or through configuration 6 NTC   PTC and 4 pressure transducer 4 20mA or ratio metric 0  5 0Volt  6 modulating outputs   1 output for remote panel  max 2 remote panels    1 TTL output for  Hot Key 64  connection or for XJ485  interface module for monitoring system  connection    MAX current on the relay contacts rel   5 2 A 250V   MAX common current 12A 250V    IC261L IC281L  RLI RLIT RLI2 RLIS RLM       Di4 06       ND  DI5   DI7    09 9    Pb2   PbC   Outl       02        DH   1 315 7 9     9   1 33 35 37   39 41   2 4 6        2 14 16  2   28 30 32 34 3e 38 40 42 44 46    DI    Pb8       10 1 D12 1 DH4   0 16   0118  DH DH3 0115 DI           Pg 18 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 3 ANALOG INP
81. alve  2 compressor  2  35  Capacity step valve  3 compressor  2  36  By pass gas valve compressor  2 start  37  Direct start  compressor  3 relay  PW start  relay PW  1 of the compressor  3  Star delta start  relay line  1 of the compressor  3  38  PW start  relay PW  2 of the compressor  3  Star delta start  relay line  1 of the compressor  3  39  Star centre of the Star delta start of the compressor  3  40  Capacity step valve  1 compressor  3  41  Capacity step valve  2 compressor  3  42  Capacity step valve  3 compressor  3  43  By pass gas valve compressor  3 start  44  Direct start  compressor  4 relay  PW start  PW 1 of the compressor  4  Star delta start  relay line  1 of the compressor  4  45  PW start  relay PW  2 of the compressor  4  Star delta start  relay line 1 of the compressor  4  46  Star centre of the Star delta start of the compressor  4  47  Capacity step valve  1 of the compressor  4  48  Capacity step valve  2 of the compressor  4  49  Capacity step valve  3 of the compressor  4  50  By pass gas valve compressor  4 start  51  Compressor  5 relay  52  Compressor  6 relay    8 5 CONDENSER PROPORTIONAL CONTROL CONFIGURATION  2 OUTPUTS     Proportional outputs used to configure a proportional output signal to condenser fan control  Parameters involved    CF68   Condenser control configuration for circuit 1   CF69   Condenser control configuration for circuit 2   07 0   10Vdc  for external mono or three phase fan control board    17 4 20mA  for external mono
82. alve of the circuit is on     UNIT WITH BOTH THE CIRCUITS RUNNING   If recovery function is enabled  if the condenser temperature pressure condition are whithin the limits the circuit  1 starts the recovery   recovery valve  1 on  when the digital input  1 is activated and the circuit  2 starts the recovery  recovery valve  2 on  when the digital  input  2 is activated     After starting  the recovery function will run at least for the time set in parameter rC04  minimum time with recovery on    Between the end of a recovery cycle and the next start the unit waits the time set in Par  rC05 before starting it again     RECOVERY START STOP OF THE CIRCUITS 1 AND 2 CONFIGURED WITH ONE STEP EACH  Both for recovery start or stop  the delay time     02 and rC03 are not counted and the recovery valve is immediately turned on or off     RECOVERY START OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP   Circuits 1 and 2 configured with more than one step of power  eg each circuit with three compressors   if the thermoregulation requires  to turn on one or more resources and the recovery is activated from the digital input the unit turns on only one step and then waits the  rC02 delay  this delay keep off all the other steps after the recovery is started   After the delay the recovery valve is turned on and  after  the rC03 time  this delay keeps off all the other steps after the recovery is started   the other resources if necessary are turned on     RECOVERY STOP OF THE 
83. apacity steps  the successive resource is turned on after the CO03  delay in seconds      Both for sequential or rotation regulation with                        or capacity steps  the successive resource is turned off after the           delay in seconds      If the power supply fails all the outputs are forced off for the CO005 time delay     27 COMPRESSORS    27 1 COMPRESSORS START  UP    Parameter CO10 defines the compressor start up    CO10 0  direct    CO10 1 part winding    CO10 2  Star delta    To configure the compressor start up it is necessary check the CF parameters of the relay outputs    After selecting the compressor start up mode  if the output resources are not properly configured  eg  more or less relay outputs than  the necessary  the ACF6 alarm is displayed     27 2 DiRECT START  UP    Configure one relay output for each compressor  K1 relay Fig  1   One relay output controls the corresponding compressor up to 6  resources    EXAMPLE   Direct start up configuration for one compressor   Set the Parameter CF54   21  Direct start up RL1 compressor   1             Fig  1    27 3 DIRECT START  UP OF A CAPACITY COMPRESSOR    When working with capacity compressors and with full power start up  the controller turns the solenoid valve on first and then  after 1  second  the compressor motor  Durning the CO13 time delay the valve is forced on  minimum power  When the C013 is expired if the  thermoregulation requires more power the valve will be switched off  maximum 
84. ation by hour  Depending on the time running hours the first compressor called by the thermoregulation is the one with less time  running hours  This algorithm is aborted if the unit is configured with one capacity compressor    CO14  2   Rotation by starts up  Depending on the number of starts up per hour the first compressor called or turned off is the one with less  starts up number  This algorithm is aborted if the unit is configured with one capacity compressor     26 SATURATION   CIRCUIT BALANCING    CIRCUIT SATURATION       15 0   Depending      the thermoregulation all the compressors of the first        turned on before using the second circuit    Eg  2 circuits  2 step for each circuit  total of 4 resources    Activation    The thermoregulation immediately requires all the 4 resources  the controller turns on the compressor with less running hours  then the  second compressor of the same circuit  Then it is turned on the compressor with less running hours of the other circuit and then the  second compressor of the other circuit    De activation    It is selected first the the circuit having less resources on  if the running resources are equals for both circuits  the first compressor  turned off is the one with the greater number of running hours or less number of starts up  then  in the same circuit  the other resources  are turned off  With the same algorithm the controller will turn off the resources of the other circuit     CIRCUIT BALANCING   CO15   1  the circ
85. ator water  ALti Low evaporator inlet temperature in air air unit   AEP1 Evaporator  1 water pump maintenance   AEP2 Evaporator  2 water pump maintenance   ACP1 Condenser  1 water pump maintenance   ACP2 Condenser     2 water pump maintenance        1    with probe configured as anti freeze   boiler control and Ar10   0    2    with probe configured as auxiliary relay control    3    with manual alarm procedure    4    Off compressors spenti with only 1 water pump configured or with 2 pumps but both in alarm from the corresponding digital inputs     5    Boiler heaters off with only 1 water pump configured or with 2 pumps but both in alarm from the corresponding digital inputs  in this case the boiler heaters are on only with thermoregulation anti   freeze setpoint as evaporator protection function              Alarm   Evap  Cir1 Cir2 i                 Anti freeze  Support Condens Auxiliary  code Alarm description 2 Pump  condenser  boiler heaters Supply fan er pump fans relay  igi No data communication betweeen the kwyaboard and the  regulator                                      1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005    43 2 ALARM           TYPE AND CORRESPONDING OUTPUT OFF    Preliminary                                                                Alarm Alarm description Compressors Compressors of Fan condensing of the Fan condensing of  Code of the circuit the other circuit circuit  n  the other circuit   n   b nHP   High pressure switch of the circuit 
86. configurable                                                 OTHER OUTPUTS   TTL   RS     485 with Mod Bus Rtu protocol o o o     Output for remote keyboard VI620  up to 2 boards         together    Output for remote keyboard VI820  up to 2 boards        together    POWER SUPPLY   12 Vac dc   15   10   o           24                10                                       DISPLAY     3 led with decimal point o o o     BOTTOM DISPLAY     4 led with decimal point o o e     OTHERS   Internal RTC opt opt opt opt  Buzzer opt opt opt opt                      configurable   configurable through parameter  opt   optional       default   free cooling  IC280L   IC281L only     Heating recovery  IC280L   IC281L only      Pg 10 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    4 USER INTERFACE    4 1 FUNCTION OF THE LEDS OF THE KEY BUTTONS    Use of the led on the IC260L   IC261L models    ON it displays the size of cir  N  1  when Girl arid       2 blink at the same time On unit irr chillar rade  it means you are entering in programing mode OFFunit in stand by  On unit in heat pump mode  OFFunit in stand by    Auxiliary output n 2    Auxiliary output n 1    Delros        ON it displays the size of cir  N   2   when       1 and cir2 blink at ihe same time ON anter in function   it means you are enterini       programing mode     Blinking when menu or RTC parameters  scl energy saving or  set point dinamic in On    Use of the led on the IC260L   IC261L metal mo
87. d 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Energy saving  Parameters   Description min           udm   Risoluzione  ES 1 Start of the Time band 1  024  0 24 00   Hr 10 Min  ES 2 End of the Time Band 1  0 24  0 24 00   Hr 10 Min  ES 3 Start of the Time band 2  0224  0 24 00   Hr 10 Min  ES 4 End of the Time Band 2  0 24  0 24 00   Hr 10 Min  ES 5 Start of the Time band 3  0 24  0 24 00   Hr 10 Min  ES 6 End of the Time Band 3  0 24  0 24 00   Hr 10         ES 7 Monday  energy saving activated 0 0 7 7  Automatic unit on off  ES 8 Tuesday energy saving activated 0 0   7 7  Automatic unit on off  ES 9 Wednesday energy saving activated      0 0   7 7  Automatic unit on off  ES 10 Thursday energy saving activated      0 0   7 7  Automatic unit on off  ES 11 Friday energy saving activated 0 0   7 7  Automatic unit on off  ES 12 Saturday energy saving activated 0 0 7 7  Automatic unit on off  ES 13 Sunday energy saving activated      0 0   7 7  Automatic unit on off  ES 14 Energy Saving setpoint offset in chiller mode  30 0   30 0   C Dec   54 54      int  ES 15 Energy Saving differential in chiller mode 0 0 25 0   C Dec  0 45   F int  ES 16 Energy Saving setpoint offset in heat pump mode  30 0   30 0   C Dec   54 54   F int  ES 17 Energy Saving differential in heat pump mode 0 0 25 0   C Dec  0 45      int  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Compressors  Parameters   Description min                    Risoluzione  CO 1 Minimum compressor ON time after 
88. dFO8   0 the valve is turned without stopping the compressors  the defrost ends and all the regulation restarts  the defrost led  i   in  heat pump is off      If dF08      0    1  All the compressors and steps are turned off   the compressor leds are blinking and the defrost led  i i  is on    2  Start the dF08   2  half time  time counting    3  Inversion valve de activated   4  Start the dF07   2  half time  time counting  all the regulation restarts and the defrost led    in heat pump is off      38 7 OTHER INFORMATION ABOUT THE DEFROST    FOR ALL THE UNIT WITH SAME DEFROST FOR THE TWO CIRCUITS  If the unit is configured with one condenser see parameter FA05    0  common condenser    1  separated condensers     Pg 76 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    For FA05 0  common condenser  the defrost of the two circuits starts at the same time    ATTENTION   Before starting the 3  phase  the dF06 counting  time delay between two circuits defrost  must be expired    ATTENTION   If the defrost ends because of the dF05 counting  Maximum defrost time  and the dF02 configuration or with the end defrost contact  the  bottom display will show  alternated with the normal measurement value  the label b1dF  circuit  1  or b2dF  circuit  2  labels to  indicate the defrost end alarms     38 8 DEFROST PARAMETER DESCRIPTION    ATTENTION IT IS NOT POSSIBLE TO DO MODIFY THE dF PARAMETERS WHEN THE DEROST CYCLE IS RUNNING    dF01 Defrost mode   0   Defros
89. dels    ON it displays the size of cir  N  1    when cir1 and cir2 blink at the same time On unit in chiller mode       it means you are entering in programing mode OFFunit in stand by           output n2 On unit in heat pump mode  Auxiliary output n  1 OFFunit in stand by   GT          Defrost       ON it displays the size of cir  N   2  when cir1 and cir2 blink at the same time ON enter in function  it means you are entering in programing mode Blinking when menuor RTC parameters    set energy saving or  set point dinamic in On       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Use of the led on the models IC280L   IC281L    ON it displays the size of cir  N    1 SES   when cir1 and cir2 blink at the same time On unit in chiller mode   it means you are entering in programing mode OFFunil in stand by  On unit in heat pump mode  OFFunit in stand by    Auxiliary output n 2    Auxiliary output n 1    ON unil in free cooling mode    Delrosl       ON il displays Lhe size ol cir      2  h  when cid snd cir2 blink at the same lime ON enler in function cl ata mode    it means you are entering in programing mode Blinking when menu or        pararnaters  set energy saving or  set point dinamic in On    Use of the led on the metal models IC280L   IC281L    ON it displays the size of cir  N   1 w  when cir1 and cir2 blink at the same time On unit in chiller mode  it means you are entering in programing mode OFFunit in stand by        Auxiliary output n  2    On 
90. der the  Ar19 setpoint the compressors are turned off  They are restarted only if the external air temperature rises above Ar19 Ar20   differential      Heating control Ar11 2   If during the functioning the external air temperature value goes down under the Ar12 setpoint  the Ar14 delay time starts counting  If  during this delay the external temperature rises above the Ar12 Ar13 the process is aborted and the time Ar14 reloaded    If after the Ar14 delay the external air temperature is still under the Ar12 setpoint and the regulation water temperature detected by the  evaporator probe is lower than Ar15  chiller  or Ar17  Heat Pump   the heaters are turned on while the compressor s  and the  condensing fan s  are turned off  The heating is made only by the heaters    When the temperature rises above the Ar15 Ar16 regulation band in chiller  or Ar15   Ar17 regulation band in HP  the heaters are  turned off    If during the functioning the external air temperature value rises above the Ar12  Ar13  the heaters are turned off and the compressor  thermoregulation is restarted  the Ar14 delay is reloaded     HEATERS of the BOILER  ANTI FREEZE  DURING the DEFROST CYCLE   The Ar05 parameters defines the functioning of the heaters of the boiler during the defrost  If Ar05 0 the heaters are activated by the  thermoregulation while if     05 1 the heaters are turned on when the 4 way valve changes the status from heat pump to chiller and then  they are turned off after the dripping ti
91. e    e  The instrument shall not be used for purposes different from those   e described hereunder  It cannot be used as a safety device    e   Check the application limits before proceeding    e 1 2 SAFETY PRECAUTIONS   e   Check the supply voltage is correct before connecting the instrument   e  Do not expose to water or moisture  use the controller only within the  e operating limits avoiding sudden temperature changes with high   e atmospheric humidity to prevent formation of condensation   e   Warning  disconnect all electrical connections before any kind of   e maintenance    e   The instrument must not be opened    e  Incase of failure or faulty operation send the instrument back to the   e distributor or to  Dixell s r l      see address  with a detailed description of  e       fault    e   Consider the maximum current which can be applied to each relay  see  e Technical Data     e Ensure that the wires for probes  loads and the power supply are separated  e andfar enough from each other  without crossing or intertwining         Fit the probe where it is not accessible by the end user    e  Incase of applications in industrial environments  the use of mains   e filters  our mod  FT1  in parallel with inductive loads could be useful     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    2 GENERAL FEATURES    iCHILL IC200L is an electronic controller for chiller unit applications having one or two circuits   e                 e Air water   e Water wa
92. e PTC for compressor  5 discharge   Temperature probe        for compressor  6 discharge   Temperature probe NTC for evaporator inlet   Temperature probe NTC for evaporator  1 outlet   Temperature probe NTC for evaporator  2 outlet   10  Temperature probe NTC for common evaporator outlet   11  Temperature probe NTC for common hot water condenser   recovery inlet   12  Temperature probe NTC for hot water of the condenser   recovery circuit  1 inlet  13  Temperature probe NTC for hot water of the condenser   recovery circuit  2 inlet  14  Temperature probe NTC for hot water of the condenser   recovery circuit  1 outlet  15  Temperature probe NTC for hot water of the condenser   recovery circuit  2 outlet  16  Temperature probe NTC for hot water of the condenser   recovery common outlet  17  Temperature probe NTC for free cooling water inlet circuit   18  Temperature probe NTC for free cooling external air temperature   19  Temperature probe NTC for dynamic setpoint external air   boiler   change over  20  Temperature probe NTC for combined defrost circuit  1   21  Temperature probe NTC for combined defrost circuit  2   22  Temperature probe NTC for auxiliary output  1   23  Temperature probe NTC for auxiliary output  2    Q op O OY      N         Pg 24 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    24  Temperature probe NTC for condensing circuit  1   25  Temperature probe NTC for condensing circuit  22   After the number 25 the display configurat
93. e front panel  2    The ST10 parameter defines the thermoregulation probe of the unit with heat pump control   0  NTC probe temperature of the evaporator inlet   17 NTC probe temperature of the evaporator  1 outlet   2 7 NTC probe temperature of the evaporator  2 outlet   3  NTC probe temperature of the evaporator common outlet   4  Remote terminal   1 probe   5  Remote terminal 1 probe   6  NTC probe temperature of the condenser common inlet   7 7 NTC probe temperature of the condenser   1 inlet   8  NTC probe temperature of the condenser    2 inlet   9  NTC probe temperature of the condenser    1 outlet   102 NTC probe temperature of the condenser    2 outlet   112 NTC probe temperature of the condenser common outlet   ATTENTION   To have the same regulation both for chiller and heat pump set the parameters ST09 and ST10 with the same value    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    22 SELECTION OF THE KIND OF THERMOREGULATION    Par  ST11 determines the type of regulation  0  Proportional   1  Neutral zone   2  Proportional integral    22 1 GRAPH OF THE COMPRESSOR THERMOREGULATION IN CHILLER    Step     STO1      CHILLER MODE                                  22 2 GRAPH OF THE COMPRESSOR THERMOREGULATION IN HEAT PUMP    Step    HEAT PUMP MODE STO4    6  Step    5  Step       4  Step       3  Step    2   Step       1   Step                Pg 60 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    22 3 GRAPH NEUTRAL ZONE
94. e relay output is configured as pump down solenoid valve for circuit 1 and 2 and one analogue input as low  pressure probe of the circuit 1 and 2    When the thermoregulation is going to stop  before turning off the last compressor  the solenoid valve is closed  The compressor runs  until the pump down pressure probe connected to the analogue input reaches the setpoint in CO37    If the last compressor stops before the pump down pressure switch because of the CO39 time out  maximum compressor on time after  turning off the P D  solenoid valve   the ICHILL calculates the AL21 parameter  maximum number of pump down alarm per hour  and if  an alarm occurs the display will show the alarm code  the buzzer and the alarm relay will be on    If the thermoregulation is stopped via digital input  as remote off  or from chiller heat pump keys  during the pump down process the  chiller or the heat pump led will blink    When the next thermoregulation restarts the PD solenoid valve turns on and after 1 seconds  if the pressure probe is higher then CO37   the compressors start    If the compressors do not restart within the CO39 time the pump down alarm will signalled and the compressor are stopped  In this case  if AL23  0 the compressor can restart only if the pressure switch becomes active  or if AL23 1 and the number of alarms per hour  becomes  AL22 only after the manual reset     PAR  CO36 3 START UNIT WITH PUMP DOWN in CHILLER MODE  No PUMP   DOWN at START UP   In Heat pump mode the
95. e turning on the compressor in chiller mode   To turn on the fan at the maximum speed before the compressor and reduce 0 250 Sec  the successive condensing temperature pressure increasing   Fan in Chiller mode  FA7 Minimum speed for condenser fan in Chiller mode   To set the minimum fan speed percentage value  30  100    it is related to  30 100 96  the fan power supply   FA8 Maximum speed for condenser fan in Chiller mode   To set the maximim fan speed percentage value  30  100    it is related to   30 100    the fan power supply   FA9 Temperature or pressure limit to enable the minimum speed FA 7   30 0   70 0   C Dec   22 158   F int  0 0 50 0 Bar Dec  0 725 Psi int  FA 10 Temperature or pressure limit to enable the maximum speed FA 8   30 0   70 0   C Dec   22 158   F int  0 0 50 0 Bar Dec  0 725 Psi int  FA11 Proportional band for condenser fan control in chiller 0 0 25 0   C Dec  To set the temperature pressure differential between the minimum and the 0 45 kim  int  maximum of the fan speed regulation  0 0 14 0 Bar Dec  0 203 Psi int  FA 12 CUT OFF differential in chiller  To set a temperature pressure differential to   0 0 25 0      Dec  stop the fan  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int                                                                                              1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  FA13 Over ride CUT  OFF in chiller  To set a temperature pressure differential to   0 0 25 0   C Dec  keep the mini
96. e value to restart in the Chiller mode    For external air temperature within CF81 the user can manually change the status from keyboard     GRAPH  AUTOMATIC CHANGE OVER  CF80    CHILLER    HEAT PUMP  PBR    CF81    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    12 3 CHILLER     HEAT PUMP FUNCTIONING MODE  IT IS DEFINED BY THE PARAMETER CF78     12 4 KEYBOARD SELECTION    CF78   0  pushing   key the unit starts in chiller  pushing 3  key the unit starts in heat pump  CF78   1  pushing s key the unit starts in heat pump  pushing    key the unit starts in chiller    12 5 ANALOG INPUT SELECTION  CF78   0 NTC  External air temperature probe  gt  CF80  CF81    the unit starts in chiller  NTC  External air temperature probe  lt  CF80  the unit starts in heat pump     CF78   1 NTC  External air temperature probe  gt  CF80  CF81    the unit starts      chiller  NTC  External air temperature probe  lt  CF80  the unit starts in heat pump     13 UNIT START  STOP    The unit start sotp can be done from one of the following operations      From keyboards      RTC Time table      Digital input configured as remote ON OFF       13 1 START     STOP AND STAND  BY FROM KEYBOARD    TURN THE UNIT ON IN CHILLER OR HEAT PUMP MODE FROM THE KEYBOARD    Push and release the NES    corresponding led is on   INPORTANT  To change from chiller to heat pump and viceversa the unit must be set in stand by before continuing     Push and release the Nel    corresponding led is on   INP
97. ed  displayed and signalled with alarm  relay   buzzer  0 16  Manual reset if AL21   0  Automatic reset if AL21  16  From automatic to manual reset if AL21  1  15  AL 22 Maximum number of pump down alarm events per hour in start up condition   After this number the alarm is logged  displayed and signalled with alarm  relay   buzzer  0 16  Always manual reset if AL22   0  Always automatic reset if AL22  16  From automatic to manual reset if AL21  1  15 and parameter AL23 config   AL 23 Select if the pump down alarm must change from automatic to manual reset   0  Always automatic reset 0 1  1  Manual reset after AL21 alarm events  Anti freeze alarm in Chiller mode  AL 24 Minimum antifreeze setpoint in chiller  from    30   C to AL24   30 0   C Dec   22   A24  oF int  AL 25 Maximum antifreeze setpoint in chiller  from AL24 to 70   C  70 0   C Dec  AL24   458     F int  AL 26 Setpoint temperature for low anti freeze alarm  low ambient temperature oi                low        air outlet  air air   From AL24 to AL25           diced                                                                                       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  AL 27 Differential of alarm reset in Chiller mode for anti freeze  low ambient air 0 25 0   C Dec  temperature or low outlet air temperature alarms  0 45   F int  AL 28 Alarm delay for anti freeze  low ambient air temperature or low outlet air  temperature  The temperature must be lower than AL26 for t
98. ed for the time set in CO50 even if the unloading function is not more activated and the  thermoregulation requires 10096 of power  If CO50 0 the function is disabled and if necessary the valve is turned immediately off to  have the 10096 of the power     UNLOAD DE ACTIVATION in CHILLER MODE  If the temperature decreases under the value determined by  CO44 CO45  setpoint     differential  the unloading is disengaged  the  compressors are all available for the thermoregulation     30 6 OTHER INFORMATION ABOUT THE UNLOADING IN CHILLER    To avoid having long period of unloading function activated when the temperature or the pressure value is continuously within the SET  and SET  differential  if the temperature or the pressure is higher than CO40  the CO48 time delay forces the unloading off for timeout  even if the temperature   pressure is not lower than CO44 CO45     UNLOADING IN HEAT PUMP MODE   The compressor unloading in heat pump mode is managed by the analogue input configured as evaporator probe circuit 1 or 2    When the heat pump thermoregulation request begins to start the compressors  if the evaporator pressure temperature is equal or  bigger than CO46 setpoint the unloading process  of that circuit probe  is engaged  The bottom display shows  alternated with the  measurement  the b1Cu  crcuit2 or b2Cu   crcuit2 labels  The number of active compressors step is determined by the CO49  parameter     EXAMPLE   Unit with 2 circuits with 3 compressors each    If Par  CO
99. ed the active intervals  when the number of active intervals reaches the thresold  set with the corresponding parameter the alarm becomes manual    By setting the thresold  parameter  0 the alarm is manual from its first activation while if the thresold 16 the alarm is always automatic   In this case  to change in manual  the thresold should be 17                                          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    43 TABLE OF THE OUTPUT STATUS IN ALARM CONDITION    The alarm codes are made of letters and numbers to define the different typologies      43 1 ALARM           TYPE AND CORRESPONDING OUTPUT OFF                                                                Alarm Alarm description Compressor Anti freeze Support Evap  Condens Ventilaz  Auxiliary  Code heaters heaters Pump  er Pump cond  relay  Boiler Supply fan Cir1 Cir2   AP1 Probe PB1 Alarm Yes Yes  1  Yes Yes Yes  2   AP2 Probe PB2 Alarm Yes Yes  1  Yes Yes Yes  2   AP3 Probe PB3 Alarm Yes Yes  1  Yes Yes Yes  2   AP4 Probe PB4 Alarm Yes Yes  1  Yes Yes Yes  2   AP5 Probe PB5 Alarm Yes Yes  1  Yes Yes Yes  2   AP6 Probe PB6 Alarm Yes Yes  1  Yes Yes Yes  2   AP7 Probe PB7 Alarm Yes Yes  1  Yes Yes Yes  2   AP8 Probe PB8 Alarm Yes Yes  1  Yes Yes Yes  2   AP9 Probe PB9 Alarm Yes Yes  1  Yes Yes Yes  2   AP10 Probe PB10 Alarm Yes Yes  1  Yes Yes Yes  2   ALti Low air temperature of the evaporator inlet  air   air unit  Alarm   AEFL Evaporator flow alarm Yes Yes  boiler  Ye
100. efrost cycle even if the dF09 timeout counting is not  expired  when the condensing evaporating temperature pressure is lower than dF20 setpoint for the dF19 time counting    If during the dF19 time counting the condensing evaporating temperature pressure rises above the value dF20 dF21  set differential   the function is disabled and the tF19 time is reloaded     ATTENTION  the forced defrost is not related to the dF09  dF06 delay times  therefore the forced defrost cycle  if condition are OK  is  immediately executed     38 2 COMBINED DEFROST    The function is enabled if one of the digital input is configured as NTC temperature for combine defrost of the 1   or 2  circuit  This  probe detects the external air temperature of the condenser  evaporator in heat pump   and its temperature value determines the start  and the stop of the defrost cycle    Description of the functioning    The count down to the defrost cycle starts when the temperature pressure of the probe  configured as condensing evaporating circuit 1  or 2 probe  is lower than dF02 parameter    After the     09 counting the instruments checks the temperature probe value  configured as combined defrost circuit 1 or 2  and if it is  lower than dF10  temperature setpoint to start the defrost of the circuit1  or dF12  temperature setpoint to start the defrost of the  circuit2  the defrost cycle starts otherwise the unit still runs in heat pump mode    When the temperature decreases under the dF10 or dF12 values the
101. el 1  5  Temperature NTC probe from remote panel 2  6  Temperature probe for water common inlet of the condenser 0 11  7  Temperature probe for water inlet of the circuit   1 condenser  8  Temperature probe for water inlet of the circuit 2 condenser  9  Temperature probe for water outlet of the circuit   1 condenser  102 Temperature probe for water outlet of the circuit   2 condenser  112 Temperature probe for water common otlet of the condenser  ATTENTION  To have the same thermoregulation for chiller and heat pump mode  set the  parameters ST09 and ST10 with the same value  ST 11 Type of thermoregulation  0  Proportional 0 2  1  Neutral zone  2  PI Proportional Integral  Pri Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Display read out  Parameter   Description min                     Resolution       1 Default read out of the top display 1 14  dP 2 Default read out of the bottom display 1 17  dP 3 Default display read out configuration top   bottom  0  Configurable  1  Top display  Evaporator IN  Bottom display  Evaporator OUT 0 3  2  Top display  Condenser IN  Bottom display  Condenser OUT  3 Top display  temperature Condensing pressure  Bottom Display   evaporating pressure  Display read out of the remote terminals  dP4 Top display default read out of the remote terminal_1  0  the read out depends on the paremeters dP01     dP02     dP03 0 1  1  the read out shows the NTC probe of the remote panel   dP5 Top display default read out of the remote terminal_2  0  
102. family select the  Pr1   1   Pr1 on the bottom display  the current password value 1 on the top display  Push the SET key  to change the value that now is blinking    4  Use the UP or DOWN key to insert the NEW PASSWORD value  then push SET to confirm the new value    5  The top display blinks for some seconds and then shows the next parameter    6  Exit the programming pushing SET   UP together or wait the timeout     Pr2 LEVEL   Remember that it is necessary to know the old password value    1  Enter the Pr2 level   2  Select a parameter family    3  Inside the family select the  Pr2   2   Pr2 on the bottom display  the current password value 2 on the top display  Push the SET key  to change the value that now is blinking    Use the UP or DOWN key to insert the NEW PASSWORD value  then push SET to confirm the new value    The top display blinks for some seconds and then shows the next parameter   Exit the programming pushing SET   UP together or wait the timeout    nside the Pr2 level it is possible to change also the Pr1 password           Pr3 LEVEL   Remember that it is necessary to know the old password value    1  Enter the Pr3 level   2  Select a parameter family    3  Inside the family select the  Pr3   3   Pr3 on the bottom display  the current password value  3  on the top display  Push the SET  key to change the value that now is blinking    Use the UP or DOWN key to insert the NEW PASSWORD value  then push SET to confirm the new value    The top display blinks for
103. formation of the circuit 2     Pg 46 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Each measurement is defined by a label that indicates which if it is a pressure a temperature or a time     14 2 SHOW THE CIRCUIT 1 OR 2  To swap between the information of the two circuits use the UP and DOWN key to select a label then push SET  check the led     Example in fig 1   Led cir1 is on  the top display shows the value of the output evaporator temperature   7 8  C  of the circuit 1    The bottom display shows Out 1  Push SET key to swap to the circuit 2  Fig2   Led cir2 is on  the top display shows the value of the output evaporator temperature   7 9  C  of the circuit 2  the bottom display shows  Out 2        Fig 2          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005    Preliminary    15 CUSTOM DISPLAY    The dP family of parameters allows to set a custom display read out  The user can change the default read out  both for instrument and    remote terminals  of the measurements depending on the application               Display    Display superiore    nuin NRE n p p     C     7               47  47        bar Flow  6 9  OOO          Display inferiore  Bottom display    15 1 DEFAULT READ   OUT OF THE TOP DISPLAY    To set the default value displayed on the top display   1  Set the parameter dP03   0  it means configurable   2  Select the dP01 parameter into the range 1  14 descripted here below        PARAMETER    CORRESPONDING             
104. fter the delay in Par  AL43   Reset Digital input configured as generic alarm with stop regulation not active after the delay in Par   AL44   Restart Automatic     It becomes manual after AL42 events hour  procedura di reset in menu funzioni    Logged only if manuale   Icona Blinking   N   Action Alarm relay   buzzer ON   REGULATION   Alarm Alarm relay   buzzer ON   Other loads OFF   ATTENTION    If during AL44 the alarm stop and start again the AL44 time delay is reloaded     Pg 82 103                1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    41 10 ACF1   ACF2   ACF3   ACFA   ACF5   ACF6   ACF7   ACF8   ACF9 CONFIGURATION    ALARM OF THE UNIT          Significato label display       ACF1     Heat pump unit without 4 way valve not configured     Defrost wrong parameters  dF22 23   ACF2     Condensing control without probe configuration    one probe per circuit with 2 separate circuits  at least 1 probe for common cond       Fan proportional control algorithm not respected   FA09   FA11   FA12  lt  FA10  FA12  lt  FA13  FA07  lt  FA15  lt  FA08     Fan proportional control algorithm not respected and pump enabled   FA18   FA21   FA20  lt  FA19  FA21  lt  FA22  FA16  lt  FA23  lt  FA17     Fan ON   OFF regulation algorithm not respected   FA09  lt  FA10     Fan ON   OFF regulation algorithm not respected and pump enabled   FA18  lt  FA19  e With pump and defrost enabled there are      evaporating condensing probes   e With triac regulation  CF68  CF6
105. his time duration 0 250 Sec  before having the alarm event   AL 29 Maximum number of alarm events anti freeze  low ambient air temperature or  low outlet air temperature before changing from automatic to manual alarm  reset  0 16  Always manual reset if AL29   0  Always automatic reset if AL29   16  From automatic to manual if AL29   1   15  AL 30 Anti freeze alarm configuration in chiller  0  to turn the compressors off when the anti freeze control probe is lower  than AL26  after the time delay   the display shows the alarm label   Buzzer and Alarm relay are not activated  0 1  1  to turn the compressors off when the anti freeze control probe is lower  than AL26  after the time delay   the display shows the alarm label   Buzzer and Alarm relay are activated   Anti freeze alarm in Heat pump mode  AL 31 Setpoint of the minimum limit in heat pump  va da     30   C a AL32   30 0   C Dec   22   AL31   of int  AL 32 Setpoint of the maximum limit in heat pump  va da AL31 a 70   C  70 0   C Dec  AL31    3  158 F int  AL 33 Anti freeze alarm setpoint in heat pump  Setpoint temperature for low anti freeze alarm  low ambient temperature   AL31   AL32     C   F Dec int   air air   low temperature air outlet  air air    from AL31 to AL32   AL 34 Alarm differential in heat pump  To reset the anti freeze  low ambient 0 25 0   C Dec  Temperature  air air   low temperature air outlet  air air  alarms  0 45 ck int  AL 35 Anti freeze alarm delay in HP for low outlet air temperature  air air  
106. iCHilL    IC2OOL Series       dixell    10 1  10 2    11    11 1  11 2  11 3  11 4  11 5  11 6  11 7  11 8  11 9  11 10  11 11  11 12    12    12 1  12 2    INDEX    GENERAL ADVICE  GENERAL FEATURES    MAIN FUNCTION  IC200 L TABLE OF THE FEATURES    USER INTERFACE    FUNCTION OF THE LEDS OF THE KEY BUTTONS   USE OF THE LED ON THE MODELS VI620   VI620S REMOTE PANELS  USE OF THE LED ON THE MODELS VI820   VI820S REMOTE PANELS  KEY FUNCTION   KEY COMBINANTION   LED AND ICONS   DISPLAY AND ICONS   MEANING  FUNCTIONNING OF THE BOTTOM DISPLAY LED    REMOTE TERMINAL  FIRST INSTALLING    ON BOARD CLOCK  OPTIONAL   RTC SETUP    WIRING CONNECTIONS    HARDWARE RESOURCES FOR IC260L   IC280L MODELS   HARDWARE RESOURCES FOR IC261L   IC281L MODELS   ANALOG INPUTS NTC     PTC PROBES   DIGITAL INPUTS   ANALOG INPUT FOR PRESSURE TRANSDUCER PP30  4   20MA SIGNAL   ANALOG INPUT FOR PRESSURE RATIOMETRIC TRANSDUCER PPR30  0   5V SIGNAL   PWM OUTPUT FOR CONDENSING FAN SPEED CONTROL   FAN CONDENSING CONTROL  0   10VDC OUTPUTS   FAN CONDENSING CONTROL WITH 4 20MA OUTPUT   PROPORTIONAL OUTPUTS 0   10V DUMPER CONTROL  PROPORTIONAL OUTPUTS CONFIGURED FOR AUX RELAY CONTROL  HOT KEY 64 CONNECTION   XJ485 CONNECTION   REMOTE PANELS VI620     VI820    ANALOG AND DIGITAL OUTPUT CONFIGURATION    ANALOG INPUT PB1   PB2   PB7   PB8   PB9   PB10   ANALOG INPUT CONFIGURATION          PB4   PB5   PB6   DIGITAL INPUT CONFIGURATION ID1     ID18   DIGITAL OUTPUT  RELAY  CONFIGURATION RL1  RL14   CONDENSER PROPORTIONAL
107. ial    Heat pump  evaporator inlet NTC probe higher than AL33   AL34  differential    n stand by or remote OFF  the evaporator inlet NTC probe higher than AL26 AL27 or AL33 AL34   Restart Automatic  Icon Blinking A  Action Alarm Relay   and buzzer on          41 15 AEP1   AEP2 EVAPORATOR PUMPS   SUPPLY FAN MAINTENANCE REQUEST       Label description    AEP1  Main water pump   AEP2  Support water pump                                Activation Load running hours  gt  counter setpoint for that load  Reset Running hour reset  Hour label in Menu function   Restart Manual   Icon AN blinking   Actions Alarm relay and buzzer activated   REGULATIONS   Actions Only signalling   Loads Not modified          The parameters CO34   CO35 define the hour set counters for the condenser water pump   Support water pump   They establish the load running hours limit of the pump s or the supply fan to give a maintenance signalling  If one of these parameters  is equal to 0 the maintenance signalling of that load is disabled but the running hours counter remains active     41 16 ACP1   ACP12 CONDENSER PUMPS MAINTENANCE REQUEST       Label description    ACP1  main water pump   ACP2  support water pump                    Activation Load running hours  gt  counter setpoint for that load  Reset Running hour reset  Hour label in Menu function   Restart Manual   Icon A blinking   Actions Alarm relay and buzzer activated             REGULATION                      1592015300 User manual iCHILL 200 L GB   
108. ing hours  air air    EP2H Support evaporator water pump running hours   CP1H Condenser water pump running hours   CP2H Support condenser water pump running hours   The labels are displayed only if the corresponding output is present and configured    The running hours is displayed on the top display  the resolution is x 10 hours  eg 2 means 20 hours  20 means 200hours   Enter the function Menu    1  Use the UP or DOWN keys to select Hour    2  Push SET key  bottom display   above labels  top display   hours x10  The time   is on   3  Use the UP or DOWN keys to scroll the list   4  To exit the Hour function push MENU key or wait the timeout    17 13 RESET THE RUNNING HOUR    Enter the function Menu   1  Within the Hour function select  with UP or DOWN  the interested label  CO1H  CO2H  CO3H  CO4H  CO6H  EP1H  EP2H  CP1H   CP2H    2  Push the SET keys for 3seconds  the top display shows the running hours blinking value  then it shows 0 to confirm the reset  The  next load label is automatically loaded    To exit the Hour function push MENU key or wait the timeout    17 14 READ OUT OF THE COMPRESSOR STARTS UP    For each compressor is possible to show the number of starts up    COSn FUNCTION  number of starts up of the compressor   Label involved in COSn function  C18 number of compressor 1 starts up    C6S number of compressor 6 starts up   The labels are displayed only if the corresponding output is present and configured   The number of starts up is displayed on the top disp
109. ion  Ar 13 Boiler function  OzNot enabled 0 2  1 Enabled for integration heating  2  Enabled for heating  Ar 14 External air temperaure setpoint for boiler heaters  on   30 0   70 0   C Dec   22 158   F int  Ar 15 Temperature differential for boiler heaters  off  0 25 0   C Dec  0 45   F int  Ar 16 Time delay before turning the boiler on 0 250 Min  Boiler function in Chiller mode  Ar 17 Setpoint for boiler heaters  on  in chiller  30 0   70 0   C Dec   22 158   F int  Ar 18 Proportional band for boiler heaters in chiller  30 0   70 0   C Dec   22 158 aF  int  Boiler function in heat pump  Ar 19 Setpoint for boiler heaters  on  in HP  30 0   70 0   C Dec   22 158   F int  Ar 20 Proportional band for boiler heaters in HP 0 1 25 0   C Dec  0 45   F int  Ar 21 External air setpoint to stop the compressor as integration function  30 0   70 0   C Dec   22 158   F int  Ar 22 External air differential to stop the compressor as integration function 0 1 25 0   C Dec  0 45    int  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Defrost  Parameter   Description min           udm  Risoluzione  dF1 Defrost configuration   0  Not enabled  1  Temperature   pressure 0 3  2  Time duration  3  External contact  dF 2 Temperature or pressure of the defrost start up  30 0   70 0   C Dec   22 158 F int  0 0 50 0 bar Dec  0 725 psi Int  dF 3 Temperature or pressure of the defrost stop  30 0   70 0   C Dec   22 158   F int  0 0 50 0 bar Dec  0 725 psi Int  dF 4 Minimum defrost duration  0
110. ion can be selected from o 1 to c62 that allows to set an analogue input as digital input  see  polarity of the digital input outputs      8 2 ANALOG INPUT CONFIGURATION PB3   PB4   PB5   PB6    Parameter involved    CF10   Configuration PB3   CF11   Configuration PB4   CF12   Configuration PB5   CF13   Configuration PB6   Not enabled   Temperature probe PTC for compressor 1 discharge   Temperature probe PTC for compressor 2 discharge   Temperature probe PTC for compressor 3 discharge   Temperature probe PTC for compressor 4 discharge   Temperature probe PTC for compressor 5 discharge   Temperature probe PTC for compressor 6 discharge   Temperature probe NTC for evaporator inlet   Temperature probe NTC for evaporator outlet   1   Temperature probe NTC for evaporator outlet   2   10 Temperature probe NTC for common evaporator outlet   11 Temperature probe NTC for common hot water condenser   recovery inlet   12 Temperature probe NTC for hot water condenser   recovery inlet circuit  1   13 Temperature probe NTC for hot water condenser   recovery inlet circuit  2   14 Temperature probe NTC for hot water condenser   recovery outlet circuit  1   15 Temperature probe NTC for hot water condenser   recovery outlet circuit  2   16 Temperature probe NTC for hot water condenser   recovery common outlet circuit  17 Temperature probe NTC for free cooling water inlet   18 Temperature probe NTC for free cooling external air   19 Temperature probe NTC for external air dynamic setpoint  boile
111. ion is enabled when the digital input of  the running pump becomes active  That pump is turned off while the other is forced on    If only one digital input is configured as condenser water pump alarm or only as condenser water pump alarm the active digital input  alarm stops the corresponding pump     During the defrost and when the compressor is off in dripping time the pump is on     PARAMETERS CO26  CO31 are the set of the running hour counters of the compressors   They establish  for each load  the number of running hours limit to display a maintenance message   If one of these parameters is equal to 0 the maintenance signalling is disabled but the running hours counter remains active     36 1 COMPRESSOR MAINTENANCE RESQUESTS                               Label description ACP1  maintenance comp  1        ACP6  maintenance comp  6   Activation Compressor running hours  gt  counter setpoint for that compressor  Reset Running hour reset  Hour label in Menu function    Restart Manual   Icon ZN blinking   Actions Alarm relay and buzzer activated   REGULATIONS   Actions Only signalling   Loads Not modified                The parameters CO32   CO33 define the hour set counters for the evaporator water pump   Support    evaporator water pump   Supply fan   They establish the load running hours limit of the pump s or the supply fan to give a maintenance signalling  If one of these parameters  is equal to 0 the maintenance signalling of that load is disabled but the running hours
112. is delay if the decreasing temperature is still within the rCO6 rC07 range  the recovery cycle is  forced on again     41 MESSAGES   ALARM CODES    the alarm codes are defined by letters and numbers    Alarm typology    e  A alarm of the unit      b   alarm of the circuit      C   alarm of the compressor    41 1 AP1   AP2   AP3  AP4  AP5   AP6   AP7   AP8   AP9   AP10 PROBE FAILURE                      Label on display AP1   PB1 probe alarm   AP10   PB10 probe alarm  Reason Probe configured but the read out is not in the range  Reset Probe not configured or probe in the right range  Restart Automatic   Icon blinking         Action Alarm Relay   and buzzer on                41 2 AEFL  EVAPORATOR FLOW ALARM  DIFFERENTIAL PRESSURE SWITCH     Label o the display AEFL evaporator flow alarm   Origin Available only for air water   water water units   Digital input active for the time set in AL15 after the water pump is on and  after the digital input  itself is activated  for the time set in AL17                             Reset Digital input not active for the time AL 18    Restart Automatic     Manual after AL16 events per hours  Reset procedure in Menu function    Icon Blinking Flow    Action Alarm Relay   and buzzer on only during normal running conditions           41 3 ACFL  CONDENSER FLOW ALARM  DIFFERENTIAL PRESSURE SWITCH     Label o the display ACFL condenser flow alarm    Origin Available only for air water   water water units   Digital input active for the time set in A
113. is not detected within the AL19 time delay after the on compressor  Reset When the digital input is not active  Restart Manual after AL20 events hour  to reset the alarm enter the function menu under cOtr   Icon Blinking   N  Action Alarm relay   buzzer ON       Compressor involved    If AL47 0 or 1  OFF          Compressor not involved       If AL47 0  it follows its regulation  If AL47 1  OFF       ATTENTION    Pg 88 103                   1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    The parameter AL47 determines the functioning of the overload alarm of the compressors   If AL47   0 single compressor locked when its digital input protection is active  on the display the corresponding alarm message   If AL47   1 all the circuit of the compressor is locked when one digital input protection is active  on the display the corresponding alarm    message     41 29 B1DF   B2DF DEFROST ALARM       Label o the display    b1dF  Defrost alarm of the circuit  1   b2dF  Defrost alarm of the circuit  2                          Origin Only in defrost if DF01   1 3  defrost en temperature pressure or external contact   when the  defrost ends after the DF05 timeout    Reset   Stand   by or remote ON OFF     Next defrost ends for temperature pressure    Restart Automatic if next defrost ends for temperature pressure  otherwise manual    Icon Blinking   N   Action Alarm relay   buzzer OFF       41 30 B1Cu     B2CU UNLOADING DISABLED FROM HIGH CONDENSING TEMPERATURE   P
114. is the NTC probe value of the evaporator water inlet     Parameter dP01 02  The default read out for the circuit 1 is the evaporator outlet 1 temperature  while for the circuit 2 is the evaporator  2 outlet temperature     BOTTOM DISPLAY  CUSTOM EXAMPLE  Parameter dP02 03  The default read out for the circuit 1 and the circuit 2 is the NTC probe value of the evaporator water outlet     Parameter dP02 14  The default read out for the circuit 1 is the condenser 1 temperature  while for the circuit 2 is the condenser 2    temperature     15 3 FORCED READ   OUT OF THE TOP AND BOTTOM DISPLAY    To force the display read out   1  Setthe          parameter not equal to 0  2  Select the value range 1  3    These configurations allow to show together two temperatures or two pressures of the same circuit in order to have an easier reading of  the measurements     Par  dP03   1    Top display  for both the circuits 1 2       Evaporator water inlet  with the Ein label   Bottom display  circuit 1       Evaporator 1 water outlet  with the label OuT1       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Bottom display  circuit 2       Evaporator 2 water outlet  with the label OuT2    Par  dP03   2   Top display of the circuit 1       Condenser 1 water inlet temperature with the label CIn1  Bottom display of the circuit 1   e Condenser 1water outlet with the label COu1    Top display of the circuit 2    Condenser 2 water inlet temperature with the label Cin2  Bottom di
115. k together for the time set in this parameter  If CO24 0 the  rotation is immediate and CO20 is not counted     ATTENTION  The CO17 CO18 values  on and off delay between compressors and pumps  are calculated also for the pump group     33 2 EVAPORATOR WATER PUMP ROTATION THROUGH DIGITAL INPUT CONTROL    With two digital inputs configured as overload alarm of water pump and support pump the rotation is enabled when the digital input of  the running pump becomes active  That pump is turned off while the other is forced on    If the digital inputs are configured as evaporator water pump alarm and condenser water pump alarm the active digital input alarm stops  the corresponding pump     Note  During the defrost and when the compressor is off in dripping time the pump is on     33 3 Hor START    FA25 Hot start Setpoint   Low temperature value of PB2 to stop the supply fan    This function is available only with air   air unit configured as heat pump and allows to run the supply fan only when the air temperature  is enough hot    FA26 Hot start differential    Temperature differential of the hot start function     34 WATER PUMP OF THE CONDENSER    34 1 CONDENSER WATER PUMP CONTROL    If one relay is configured as condenser water pump the CO24   CO25 parameter values do not affect the pump functioning     Water pump regulation    Operative mode of the condenser water pump parameter CO21   CO21   0 Not enabled  pump not controlled        21   1 Continuous control  The water pump is 
116. l output 2   0  Not enabled   1  Free cooling Dumper   Mixing valve  2  3 way valve for hot water   3  Dumper for air change   4  auxiliary output   Relay driver ON   OFF    01    c22       CF 72    Proportional output 3   0  Not enabled   1  Free cooling Dumper   Mixing valve  2  3 way valve for hot water   3  Dumper for air change   4  auxiliary output   Relay driver ON   OFF    01    c22       CF 73    Proportional output 4   0  Not enabled   1  Free cooling Dumper   Mixing valve  2  3 way valve for hot water   3  Dumper for air change   4  auxiliary output   Relay driver ON   OFF    01    c22       Terminale remoto       CF 74    Remote Panel 1 configuration   0  Not enabled   1  6 keys   2  6 keys and NTC ambient temperature sensor  3  8 keys   4  8 keys and NTC ambient temperature sensor       CF 75    Remote Panel 2 configuration   0  Not enabled   1  6 keys   2  6 keys and NTC ambient temperature sensor  3  8 keys   4  8 keys and NTC ambient temperature sensor       CF 76    Offset of the NTC probe of the remote terminal   1     12 0   10    12 0  53      C    F    Dec  int       CF 77    Offset of the NTC probe of the remote terminal   2     12 0   10    12 0  53      C    Dec  int       Icon function       CF 78    Icon function  0    chiller      heat pump  1     chiller     heat pump       Chiller   heat pump selection mode       CF 79    0  from keyboard  1  from digital input  2  from analogue input       Automatic Change over       CF 80    Change over setpoint
117. lay   buzzer ON          41 25 C1HP   C2HP   C3HP   CAHP   C5HP   C6HP COMPRESSOR HIGH PRESSURE ALARMS       Label o the display    C1HP   compressor high pressure alarm 1          C6HP  compressor high pressure alarm 6                       Origin The unit is running and the digital input of the compressor high pressure switch is active  Reset Digital input not active   Restart Manual  Reset procedure in Menu function    Icon blinking ZN   Action Alarm Relay   and buzzer on          41 26 C10P   C20P    COMPRESSOR OIL    C30P   C40P   C50P   C60P   PRESSURE SWITCH ALARM         Label o the display              Compressor pressure switch  1      C6oP  Compressor pressure switch  6                       Origin The alarm is not signalled  during the ALO1 delay after turning on the compressor  during the AL12  delay that starts after the AL11 delay when the unit is properly running   Reset Digital input not active   Restart Automatic   Manual after AL013 events per hour  Reset procedure in Menu function    Icon Blinking AN   Action Alarm Relay   and buzzer on          OIL ALARM FROM PRESSURESTAT SWITCH OR OIL LEVEL SWITCH  screw   Occasionally it is possible to find both the safety systems  the delay  the active input duration and the number of events per hour allow    to set up both the protections     Par  AL11 Oil alarm delay after on c  It allows to set a time delay before s    ompressor   ignalling the oil or the oil level switch alarms after the on compressor     Par  AL12
118. lay  the resolution is x 10  eg 2 means 20 starts  20 means 200starts   Enter the function Menu    1  Use the UP or DOWN keys to select COSn    2  Push SET one time  the label of the first load C1S is showed on the top display  the bottom display shows the number x10   3  With UP or DOWN scroll the compressor list    4   Toexit the Hour function push MENU key or wait the timeout    17 15 RESET THE STARTS UP NUMBER    Enter the function Menu   1  Within the Hour function select  with UP or DOWN  the interested label  CS1  CS2  CS3  C84  CS6    2  Push the SET keys for 3seconds  the top display shows the running hours blinking value  then it shows 0 to confirm the reset  The  next load label is automatically loaded    3  To exit the Hour function push MENU key or wait the timeout     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    17 16 READ OUT OF THE PROPORTIONAL OUTPUT PERCENTAGE OF THE CONDENSER FAN  CONTROL    The proportional outputs of the two circuits  that control the fan speed  can be showed in the menu function   Cond FUNCTION selects the proportional output 1 and 2    Label involved in Cond function    Cnd1 Proportional output status of the condenser fan of the circuit 1    Cnd2 Proportional output status of the condenser fan of the circuit 2     TO SEE THE OUTPUT PERCENTAGE    Enter the function menu   1  Use the UP or DOWN keys to select Cond    2  Push SET key  the bottom display shows Cnd1  the top display shows the output percentage    3 
119. lve one of the step  depending on the time running hours   is turned off for the time set in  rC02  After rC02 the recovery valve is turned on  Then  after the rC03 time  this delay keeps off all the other steps after the recovery is  started  the resource forced off if necessary is turned on again     RECOVERY STOP OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED   When the system is running with 10096  eg all the three compressor of a circuit are on  of power and the digital input stop the recovery  function  after the rC04 time delay  minimum on time of the recovery function when activated  and before turning off the recovery valve   one of the step is turned off for the time set in rC02  When the delay is expired the unit turns off the recovery valve and and the  regulation restarts with its normal running condition     ATTENTION   For both the circuits  when the compressor are off because of the thermoregulation and the digital input of the recovery function is  active  the recovery valve is disabled     39 2 UNIT WITH Two IDRAULIC CIRCUIT WORKING IN PARALLEL    FUNCTIONING  Par  rC01   2 unit with two circuits working in parallel   The recovery function from the digital inputs is divided in two steps     UNIT WITH ONE CIRCUIT RUNNING  If the recovery function is enabled and if the condenser temperature pressure condition are whithin the limits that circuit starts the  recovery when one of the digital inputs is activated  With active digital input the recovery v
120. me at the end of the defrost     ATTENTION   The heaters of the boiler are always off when    e Active flow alarm   e Active overload alarm of the configured water pump   e Active overload alarm of one of the two water pumps configured and any of the water pumps available for the water flow control    In this case the heaters are activated only by the anti freeze setpoint to protect the evaporator     24 ANTI   FREEZE ALARM AND HEATERS REGULATION THROUGH DIGITAL INPUT    The anti freeze alarm and the heaters regulation of the 1    circuit is managed by the digital input configured as anti freeze alarm circuit   1    The anti freeze alarm and the heaters regulation of the 2  circuit is managed by the digital input configured as anti freeze alarm circuit   2    ATTENTION   The output of the 1   circuit can not be managed by the digital input of the 2  circuit and viceversa    The regulation outputs of th1 1   and 2  circuit can be regulated together by a single digital input configured as anti freeze circuit  1 or  circui  2  In this case  with active alarm of the common digital input  the display will show both the antifreeze alarm messages     25 THERMOREGULATION AND COMPRESSORS ROTATION    The CO14 parameter determines the compressor on and off sequence    CO14  0   Sequential  Depending on the thermoregulation  the 1   compressor is turned on  then the 2  and the 3  etc   then the 3  off  the 2 and  then 1st  The first is off only if the 2  and 3  are off        14  1   Rot
121. minary  CO 25 Time to make run the pumps together before rotating from one to the other 0 250 S    ec   See water pump group function    Load maintenance  CO 26 Compressor 1 hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 27 Compressor 2 hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 28 Compressor 3 hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 29 Compressor 4 hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 30 Compressor 5 hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 31 Compressor 6 hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 32    Evaporator pump   Supply fan    hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 33 2    Evaporator pump hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 34 Condenser pump hour counter set  See maintenance request  0 999   10 Hr 10 Hr  CO 35 2    Condenser pump hour counter set  See maintenance request  0 999   10 Hr 10 Hr  Pump down  CO 36 Pump down operating mode  See pump down ON OFF function   0  Not enabled  1  Unit off with pump   down  unit on without pump down 0 4  2  Unit off with pump   down  unit on with pump down  3  Chiller mode off with pump   down  chiller mode on without pump down  4  Chiller mode off with pump down  chiller mode on with pump down  CO 37 Pump down pressure setpoint  See pump down ON OFF function  0 50 0 Bar Dec  0 725 psi int  CO 38 Pump down pressure differe
122. mode if there are at least 2 steps of power  two compressor or 1 compressor with partialization   per circuit    It is used to run the unit with high temperature of the evaporator water inlet  such as during the hot summer  to avoid a possible high  pressure alarm event    The function si managed through an analogue input configured as NTC evaporator water inlet     30 2 UNLOADING DESCRIPTION  UNLOADING ACTIVATION    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    When the thermoregulation request begins to start the compressors in chiller mode  if the evaporator water inlet is equal or bigger than  the CO40 setpoint for the CO42 time    When the unloading is active the display shows the AEUn blinking message alternated with the selected display measurement  the unit  will start with the loads selected with the CO49 parameter     EXAMPLE  Unit with 2 circuits with 3 compressors each circuit   If Par  CO49   2  2 power steps per circuit  in case of unloading there will be 4 compressor running     UNLOAD DEACTIVATION  If the temperature decreases under the value determined by  CO40 CO41  setpoint     differential  the unloading is disengaged  the  compressors are all available for the thermoregulation     30 3 UNLOADING INFORMATION    If the temperature does not decrease enough to reach the CO40 CO41 value  under the CO40 setpoint the CO43  unloading timeout   will start counting and when expired the unit will force the unloading off     30 4 UNLOADING WI
123. mum fan speed  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int  FA 14 CUT OFF time delay  To set a time delay before activating the CUT OFF  function after the fan start up   If after the compressor start up the proportional regulator requires to turn off 0 250 Sec  the fan  cut off         FA140  the fan is on at the minimum speed for the time  set in this parameter  If FA14 0 the function is disabled   FA 15 Night speed in chiller  To set the maximum fan speed percentage value 30 100     30  100    it is related to the fan power supply   Fan in Heat pump mode  FA 16 Minimum speed for condenser fan in Heat Pump mode   To set the minimum fan speed percentage value  30  100    it is related to  30 100 96  the fan power supply   FA 17 Maximum speed for condenser fan in Heat Pump mode   To set the maximum fan speed percentage value  30  100    it is related to  30 100 96  the fan power supply   FA 18 Temperature or pressure limit to enable the minimum speed FA17  30 0   70 0   C Dec   22 158 SF int  0 0 50 0 Bar Dec  0 725 Psi int  FA 19 Temperature or pressure limit to enable the maximum speed FA17  30 0   70 0   C Dec   22 158      int  0 0 50 0 Bar Dec  0 725 Psi int  FA 20 Proportional band for condenser fan control in Heat pump  0 0 25 0   C Dec  To set the temperature pressure differential between the minimum and the 0 45   F int  maximum of the fan speed regulation  0 0 14 0 Bar Dec  0 203 Psi int  FA 21 CUT OFF differential in Heat pump  To set a temperature pressure diffe
124. n is made with parameters uS02 for the circuit 1 and uS06 for the circuit 2    The function is enabled when the parameter uS01  lt  gt 0 for the circuit 1 and the parameter uS05 lt  gt 0 for the circuit 2 and at least one  output is configured as auxiliary output    Par  uS01 configuration auxiliary relay 1            uS05 configuration auxiliary relay 2   Value and function   0   Not enabled   1   Function enabled  direct action  also during stand by or remote off    2   Function enabled  direct action  only with unit running    3   Function enabled  inverse action  also during stand by or remote off   4   Function enabled  inverse action  only with unit running     20 1 AUXILIARY RELAY WITH DIRECT ACTION    RELAY  Relay ON  Relay OFF  PBr  Set Set   diff  When   PBr  lt  set   relay ON   Pbr  gt  set   differential  relay OFF   Set  lt  PBr  lt  set   differential  previous status   PBr   NTC probe or transducer selected by the parameters uS02   uS06  20 2 AUXILIARY RELAY WITH INVERSE ACTION  RELAY  Relay ON  Relay OFF    PBr  Set   diff Set    When    PBr  gt  set   relay ON    Pbr    set   differential  relay OFF    Set     differential  lt  PBr  lt  set  previous status    PBr   NTC probe or transducer selected by the parameters uS02   uS06  If    PBr    SET  relay ON   Pbr    SET  differential  Relay OFF    Pg 58 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Set     differential  lt  of PBr  lt  SET  previous state    PBr   NTC probe or t
125. n the thermoregulation is going to stop  before turning off the last compressor  the solenoid valve is closed  The compressor runs  until the pump down pressure switch connected to the digital input becomes active for a maximum time set in CO39     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    If the last compressor stops before the pump down pressure switch because of the CO39 time out  maximum compressor on time after  turning off the P D  solenoid valve   the ICHILL calculates the AL21 parameter  maximum number of pump down alarm per hour  and if  an alarm occurs the display will show the alarm code  the buzzer and the alarm relay will be on    If the thermoregulation is stopped via digital input  as remote off  or from chiller heat pump keys  during the pump down process the  chiller or the heat pump led will blink    When the next thermoregulation restarts the PD solenoid valve turns on and after 1 seconds  if the low pressure switch is not active  the  compressors start    For any compressor alarm events occur the procedure is stopped and the compressor will be stopped     PAR  CO36   2 ON OFF WITH PUMP DOWN   The function is enabled if one relay output is configured as pump down solenoid valve for circuit 1 and 2 and one digital input as pump  down pressure switch of the circuit 1 and 2   CO36   2 or 4 are related to a pressure switch dedicated to this function or the pressure  transducer     When the thermoregulation is going to stop  before t
126. nal outputs for condensing fan speed control  inverter or phase cut  with configurable signal    e PWM   e 0D0 10Volt   e 4 20mA   Four proportional control outputs 0 10V or ON OFF   e  Tocontrol the dumper in free cooling or recovery   e To control an external relay   Complete alarm management      Internal Data logger up to 100 events   Supervisor   tele assistance  monitoring   e TTL output for XJ485 interface  Mod  Bus protocol  for XWEB300   XWEB3000 Dixell monitoring system for local and remote  control   Up to 2 remote terminals with display read out customizable   e With NTC ambient temperature probe    1592015300 User manual iCHILL 200 L GB      1 0 23 02 2005    Preliminary    3 IC200 L TABLE OF THE FEATURES       FEATURES    IC260L       IC261L    IC280L       IC281L       CHILLER WITH HEAT PUMP    CHILLER WITH HEAT PUMP   FREE COOLING AND HEATING  RECOVERY       FRONTPANEL KEY BUTTONS       6       8       OUTPUT RELAYS       10       14       DIGITAL INPUTS       18    configurable    configurable    configurable    configurable       PROBE INPUTS       NTC   PTC   4 20mA   0   5Volt    configurable    configurable    configurable    configurable       PROPORTIONAL OUTPUTS       Two PWM outputs for condensing fan       Two 0 10V o 4 20mA for condensing fan    configurable    configurable    configurable    configurable       Four 0 10V outputs for Free cooling and Heating  recovery  or to drive an external relay    configurable    configurable    configurable    
127. nding on the condensing  temperature pressure    Par  FA01   3   Par  FA02   0   Fans on  with proportional regulation  PWM  4  20mA  0 10V  and with temperature pressure transducer control  only when the  compressor is on  When the compressor turns off also the fans are forced off    Par  FA01   3   Par  FA02   2   Fans on  with proportional regulation  PWM  4  20mA  0 10V  and with temperature pressure transducer control  only when the  compressor is on  When the compressor turns off the fans are thermoregulated depending on the condensing temperature pressure     37 1 PWM OUTPUT FOR FAN CONTROL    If FA01 3 and the fan control boards are connected to the PWM outputs  TF1 and2  take note of the FA03  FA04 parameters    The fan start up is always made at the maximum speed for the time set in FA03  then the speed follows the probe value    The F04 delay  in micro     seconds  allows to adjust the output for each kind of the fan motor    If FA01 3  when the compressor starts up and the proportional regulation requires to turn off the fan  cut off   if FA14z0 the fan is forced  at the minimum speed for the time set in FA14 itself  if FA14 0 the function is disabled     37 2 CONDENSING UNIT  COMMON OR SEPARATE    FA05 defines the condenser unit   Par  FAO05 type of condenser   0  Common condenser unit    1  Separate condenser units    If Pa FAO5  0 the outputs  configured as condensing fan control  will follow the same regulation algorithm    The regulation includes       CHILLE
128. nser fan ON OFF control of the circuit  1  11  Condenser fan ON OFF control of the circuit  2  12  Solenoid valve of the pump down circuit  1  13  Solenoid valve of the pump down circuit  2  14  Recovery valve circuit  1  15  Recovery valve circuit  2  16  Free cooling ON OFF valve  17  Auxiliary output circuit  1  18  Auxiliary output circuit  2  19  Pulse valve for screw compressor  1  20  Solenoid valve Intermittent for screw compressor  2  21  Solenoid valve of the liquid injection for compressor  1  22  Solenoid valve of the liquid injection for compressor  2  23  Direct start up   compressor  1 relay  PW start  relay PW  1 of the compressor  1  Star delta start  relay line  1 of the compressor  1  24  PW start  relay PW  2 of the compressor  1  Star delta start  relay linea  2 compressor  1  25  Star centre of the Star delta start of the compressor 1   26  Capacity step valve  1 compressor  1  27  Capacity step valve  2 compressor  1  28  Capacity step valve  3 compressor  1  29  By pass gas valve compressor  1start  30  Direct start  compressor  2 start  PW start  relay  1 of the compressor 2   Star delta start  relay line  1 of the compressor  2    OONAARONAROS    Pg 26 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    31  PW start  relay PW  2 of the compressor  2  Star delta start  relay line  2 of the compressor  2  32  Star centre of the Star delta start of the compressor  2  33  Capacity step valve  1 compressor  2  34  Capacity step v
129. nti freeze alarm signalling of the circuit  1 in heat pump   b2Ah  anti freeze alarm signalling of the circuit  2 in heat pump     Both the labels are displayed when the alarm is coming from the evaporator inlet probe or  evaporator common outlet probe or when there is only one digital input configured           Origin    Normal conditions  stand by  remote OFF  when the anti freeze probe value is lower than AL33 for  AL36 seconds   With the anti freeze digital input is active           Pg 86 103                   1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary                Reset When the anti freeze probe value is higher than AL33   AL34 differenziale    With digital input ont active  Restart Automatic     Manual after AL37 events per hour  Reset procedure in Menu function    Icon Blinking AN  Action If AL38 0 only the compressors are turned off and than display shows b1Ah   b2Ah  the buzzer    and the alarm relay are not activated     If AL38 0 only the compressors are turned off and than display shows b1AH   b2AH  the buzzer  and the alarm relay are activated     If the alarm comes from the digital input also the anti freeze heaters are turned on           Attention   Par  AL35 anti freeze alarm delay  low outlet air temperature air air unit  when the unit starts in heat pump mode    In stand by or remote OFF  there is an anti freeze alarm and the time delay in AL35 lt  gt 0  if the unit is manually turned on in heat pump  from keyboard or remote inpu
130. ntial  See pump down ON OFF function  0 14 0 Bar Dec  0 203 psi int  CO 39 Maximum pump down time duration at start up and stop  See pump down 0 250 Sec  ON OFF function   Evaporator Unloading  CO 40 Unloading compressor setpoint in chiller  From high temperature of the 0 50 0 Bar Dec  evaporator water inlet  See unloading function   0 725 Si int  CO 41 Unloading Differential  From high temperature of the evaporator water inlet   0 0 14 0 Bar Dec   See unloading function   0 203 Psi int  CO 42 Delay time to engage the Unloading function from high temperature of the 0 250 Sec 10sec  evaporator water inlet  See unloading function    CO 43 Maximum unloading duration time to keep activated the Unloading function             0 250 Min  from high temperature of the evaporator water inlet  See unloading function    Condenser Unloading  CO 44 Unloading compressor setpoint  From temperature   pressure in chiller mode 0 50 0 Bar Dec   See unloading function   0 725 psi int  CO 45 Unloading Differential  From temperature   pressure in chiller mode  See   0 0 14 0 Bar Dec  unloading function   0 203 Psi int  CO 46 Unloading compressor setpoint  From temperature   pressure in HP mode 0 50 0 Bar Dec   See unloading function   0 725 psi int  CO 47 Unloading Differential  From temperature   pressure in HP mode  See   0 0 14 0 Bar Dec  unloading function   0 203 Psi int  CO 48 Maximum unloading duration time from temperature pressure control  0 250 Min  CO 49 Number of steps for circuit with 
131. nual  reset procedure in function menu    Icona Blinking   N  Action Alarm relay   buzzer ON          41 6 ATC1   ATC2 CONDENSER RECOVERY PUMP OVERLOAD ALARM       Label o the display    AtC1  overload pump alarm of condenser 1   AtC2  overload pump alarm of support condenser 2                    Origin Active ID when it is configured as overload pump of condenser 1  Active ID when it is configured as overload pump of condenser 2    Reset With active digital input   Restart Manual  reset procedure in function menu               1592015300 User manual iCHILL 200 L GB    Icona      1 0 23 02 2005 Preliminary    Blinking   N             Action    Alarm relay   buzzer ON       41 7 AEE EEPROM ALAR       Label o the display    AEE                         Origin Wrong eeprom data               em   Restart Manual   Icona Blinking   N   Action Alarm relay   buzzer ON       41 8 AFR  POWER SUPPLY FREQUENCY ALARM       Label on the display    AFr  Line frequency alarm                          Origin The power supply frequency is not equal to the Par  CF81   tolerance   Reset Ferquency control parameter adjusted  disabled CF81   2  frequency within the tolerance  Restart Automatic   Icona Blinking   N   Action Alarm relay   buzzer ON       41 9 ALOC  GENERIC ALARM WITH STOP REGULATION       Label on the display    ALOC  generic alarm from digital input with stop regulation                                     Origin Digital input configured as generic alarm with stop regulation active a
132. nverter between the RS485 and the TTL connector output  The RS485 uses two terminals     and     that  must be connected respecting the polarity to build the serial line  Use the CAB RS02 to connect the XJ485 interface to the TTL  connector        RS 485 OUTPUT  WITH MODBUS   RTU       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 14 REMOTE PANELS VI620   VI820    The instrument receives up to two remote panels  Using the remote panels provided with the ambient NTC probe the display  measurement  and the control can be managed directly by this probe  Use shielded cable for the connection up to 150mt maximum  In  case of communication failure the upper display shows    noL     no link     Use the CAB CJ30 to interface the ichill connector to the shielded cable       Remote panel VI620 for models IC260L     IC261L      Remote panel VI820 for models 200 L IC280L     IC281L               TIL  HOTKEY       Remote  panel n   2    Address    8 ANALOG AND DIGITAL OUTPUT CONFIGURATION    8 1 ANALOG INPUT PB1   PB2   PB7   PB8   PB9   PB10    Parameters involved    CF08   Configuration PB1   CF09   Configuration PB2   CF14   Configuration PB7   CF15   Configuration PB8   CF16   Configuration PB9   CF17   Configuration PB10   Not enabled   Temperature probe PTC for compressor  1 discharge   Temperature probe PTC for compressor  2 discharge   Temperature probe PTC for compressor  3 discharge   Temperature probe PTC for compressor  4 discharge   Temperature prob
133. or 1  motocondensing unit   48  Request  partialization 3 of compressor 1  motocondensing unit   49  Request compressor  2   50  Request   partialization 1 of compressor 2  motocondensing unit   51  Request   partialization 2 of compressor 2  motocondensing unit   52  Request   partialization 3 of compressor 2  motocondensing unit   53  Request compressor  3   54  Request   partialization 1 of compressor     motocondensing unit   55  Request   partialization 2 of compressor     motocondensing unit   56  Request   partialization 3 of compressor     motocondensing unit   57  Request compressor  4   58  Request   partialization 1 of compressor 4  motocondensing unit   59  Request   partialization 2 of compressor 4  motocondensing unit   60  Request   partialization    of compressor 4  motocondensing unit   61  Request compressor  5  motocondensing unit    62  Request compressor  6 motocondensing unit     8 4 DIGITAL OUTPUT  RELAY  CONFIGURATION RL1  RL 14    Parameter involved   CF54z Configuration RL1   CF67  Configuration RL14  Not enabled  Alarm  Evaporator water pump   Supply fan  Support water pump of the evaporator  Anti freeze heater   integration heating   boiler circuit  1  Anti freeze heater   integration heating   boiler circuit  2  Water pump of the condenser recovery circuit  Support water pump of the condenser recovery circuit  4 way valve for chiller   heat pump inversion of the circuit  1  4 way valve for chiller   heat pump inversion of the circuit  2  10  Conde
134. own process is inhibited and the solenoid valve works in parallel with the compressor     29 3 PuMP DOWN FUNCTION WITH DEDICATED PRESSURE PROBE    PAR CO36   1 STOP UNIT with PUMP DOWN   No PUMP     DOWN at START UP    The function is enabled if one relay output is configured as pump down solenoid valve for circuit 1 and 2 and one analogue input as low  pressure probe of the circuit 1 and 2    When the thermoregulation is going to stop  before turning off the last compressor  the solenoid valve is closed  The compressor runs  until the pump down pressure connected to the analogue input reaches the set value in CO37    If the last compressor stops before the pump down set value because of the CO39 time out  maximum compressor on time after turning  off the P D  solenoid valve   the ICHILL calculates the AL21 parameter  maximum number of pump down alarm per hour  and if an  alarm occurs the display will show the alarm code  the buzzer and the alarm relay will be on    If the thermoregulation is stopped via digital input  as remote off  or from chiller heat pump keys  during the pump down process the  chiller or the heat pump led will blink    When the next thermoregulation restarts the PD solenoid valve turns on and after 1 seconds  if the low pressure switch is not active  the  compressors start    For any compressor alarm events occur the procedure is stopped and the compressor will be stopped     PAR        5   2 UNIT START STOP with PUMP DOWN   The function is enabled if on
135. p diplay shows the setpoint that the unit is really using for the thermoregulation    ATTENTION   The SEtr label appears only if the Energy saving or the Dynamic Setpoint are active    To modify the working setpoint it is necessary the setpoint values is displayed on both the display  temperature   temperature or  temperature   pressure o pressure  pressure  without any identification label  otherwise the SET key swaps to the circuit information        Pg 50 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    16 4 DISPLAY IN REMOTE OFF    From digital input configured as remote ON OFF  the active input sets the unit in OFF  even when the unit is a motocondensing unit    The top display shows    OFF      the led of the decimal point is blinking     16 5 DISPLAY IN MOTOCONDENSING CONFIGURATION    The top display shows  ON  for active input and    OFF    for not active input  If the unit is running in Chiller the top display shows OnC  otherwise OnH for heat pump    The configuration for motocondensing  as for chiller or HP  allows to show through the top and the bottom display all the detected input  measurements and alarms     17 FUNCTION MENU     M    KEY    The function Menu is composed of the following items    1  Show and reset the alarms ALrM     Compressor overload alarm reset COtr     Show and reset the alarm log ALOG     Upload the parameter into the Hot Key UPL     Enable     disable one or the two circuits CrEn     Enable     disable one of 
136. played  the digital input active function will disable the last running compressor  A  possible low pressure alarm could appear only if the digital input is still active after the ALO2 time    If the last compressor stops before the low pressure switch because of the CO39 time out  maximum compressor on time after turning  off the P D  solenoid valve   the ICHILL calculates the AL21 parameter  maximum number of pump down alarm per hour  and if an  alarm occurs the display will show the alarm code  the buzzer and the alarm relay will be on    If the thermoregulation is stopped via digital input  as remote off  or from chiller heat pump keys  during the pump down process the  chiller or the heat pump led will blink    When the next thermoregulation restarts the PD solenoid valve turns on and after 1 seconds  if the low pressure switch is not active  the  compressors start    For any compressor alarm events occur the procedure is stopped and the compressor will be stopped             CO36 3 OFF UNIT WITH PUMP DOWN      CHILLER MODE  No PUMP     DOWN at START UP   In Heat pump mode the Pump down process is inhibited and the solenoid valve works in parallel with the compressor     29 2 Pump DOWN WITH DEDICATED PRESSURE SWITCH    PAR CO36   1 OFF UNIT WITH PUMP DOWN   No PUMP   DOWN at START UP    The function is enabled if one relay output is configured as pump down solenoid valve for circuit 1 and 2 and one digital input as pump  down pressure switch of the circuit 1 and 2    Whe
137. power      27 4 PART WINDING    This algorithm allows to reduce the start up current when using hermetic or semi hermetic compressors or medium     big screw  compressors     Each compressor needs two relay outputs    One is the PW motor coil  1 of the compressor    One is the PW motor coil  2 of the compressor    The time delay between the two outputs is determined by CO11 expressed in decimal of second in a range 0  5 seconds   The maximum number of relay outputs is 8 this means 4 compressors with Part Winding start up    EXAMPLE   Part Winding configuration of the compressor relay outputs   Set the Par CF54   21  PW motor coil  1 relay of the compressor  1    Set the Par CF55   22  PW motor coil 22 relay of the compressor  1     Pg 64 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    27 5 COMPRESSOR START  UP WITH PART WINDING    First is turned on the PW motor coil  1 of the compressor  1  relay K1 of fig2   after the CO11 delay it is turned on the second motor coil  of the same compressor  relay K2 of fig2    To turn off the compressor the two relay outputs are both turned off at the same time              Fig 2    27 6 PART WINDING START  UP OF COMPRESSORS OR CAPACITY COMPRESSORS    If one or more capacity compressors are configured and the thermoregulation requires the full load start up  the controller turns the  solenoid valve on  after 1 second the first motor part of the 1  compressor  relay K1 of Fig  2  and then the complete control wi
138. pressor 1 and one analogue input is configured as  discharge temperature of compressor 1       For compressor 2  one output relay is configured as solenoid valve compressor 2 and one analogue input is configured as  discharge temperature of compressor 2     31 1 FUNCTIONNING    When the compressor is off the solenoid valve output is always OFF  When the compressor is on  if the PTC temperature of the  compressor discharge reaches CO51 setpoint the valve turns ON  while if the temperature decreases under C51 CO52  set  differential   the valve turns off     ATTENTION  The display resolution is 0 1  C until the read out is 99 9  over 100  C it is 1  C     32 WATER PUMP OF THE EVAPORATOR   SUPPLY FAN    32 1 WATER PUMP OF THE EVAPORATOR   SUPPLY FAN  AIR AIR     With only one evaporator water pump configured  the parameter CO19   CO20 values do not affect the water pump functioning itself   The water pump regulation involves the following modes    Operative modes of the parameter CO16 of evaporator pump   Supply fan   CO16 0  Not enabled  water pump supply fan not managed    Attention  The air   air unit configured with CO16  0 does not manage the output for integration heaters    CO16   1  Continuous control    The water pump  supply fan are running only if the unit is running  chiller  heat pump   After giving the start in chiller or heat pump mode  the compressor regulation starts only after the time delay CO17    The water pump  supply fan are turned off only when the unit i
139. programmed with the same value     18 3 RTC DAILY TIME TABLE PROGRAMMING    This function can be also used to turn ON or OFF the unit    Enter parameter programming    1  Select with UP or DOWN keys the ES parameter family    2  Within the ES parameters select with UP or DOWN keys the parameters   501     506 to determine the start and stop of the  energy saving daily periods     Example   Set the energy saving start with ES01 and the energy saving stop time ES02 of the first period    If ES01   8 0 ESO2   10 0 the energy saving setpoint is active from 8 to 10    If ES01   23 0   502   8 0 the energy saving setpoint is active from 23  11pm  to 8  8 am  in the morning of  the next day    If necessary repeat the operation for the others two time periods defined by   503     504 and ES05   ES06     18 4 ENERGY SAVING OR UNIT ON OFF ACTIVATION WITH RTC PROGRAMMING    Enter the parameter programming    1  Select with UP or DOWN keys the ES parameter family    2  Within the ES parameters select with UP or DOWN keys the parameters   507  Monday    ES13  Sunday  to determine which  days to include     Configuration table Energy saving or unit ON OFF activation with rtc programming    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    Par  ES07     ES13 0  RTC not enabled   1  15 period enabled   2  2  period  enabled   3  1  and 2  periods enabled   4  3     Period  enabled   5  1             3   periods enabled   6  2  and 3  periods enabled  7  1    2  and 3  pe
140. pted if the compressor is turned off or if the temperature pressure is higher then dF02    dF10 Temperature setpoint to start a combined defrost of the circuit  1    It allows to set a temperature value to determines the beginning of a combined defrost    After the     09 counting the NTC probe of the combined defrost of the circuit  1 is compared to the dF10 setpoint  if the value is lower  the defrost starts otherwise the unit runs in heat pump mode and when the temperature decreases under dF10 the defrost immediately  starts    dF11 Temperature setpoint to end a combined defrost of the circuit  1    It allows to set a temperature value to determine the end of a combined defrost    When the NTC probe of the combined defrost of the circuit  1 becomes higher than dF10 setpoint the defrost cycle stops    dF12 Temperature setpoint to start a combined defrost of the circuit  2    It allows to set a temperature value to determine the beginning of a combined defrost    After the dF09 counting the NTC probe of the combined defrost of the circuit  2 is compared to the dF12 setpoint  if the value is lower  the defrost starts otherwise the unit runs in heat pump mode and when the temperature decreases under dF12 the defrost immediately  starts    dF13 Temperature setpoint to end a combined defrost of the circuit  2    It allows to set a temperature value to determine the end of a combined defrost    When the NTC probe of the combined defrost of the circuit  2 becomes higher than dF13 
141. r   change over  20 Temperature probe NTC for combined defrost circuit  1   21 Temperature probe NTC for free cooling water inlet  2   22 Temperature probe NTC for auxiliary output  1   23 Temperature probe NTC for auxiliary output  2   24 Condenser probe circuit 1   temperature NTC   pressure 4 20 mA   ratio metric 0  5Volt    25 Condenser probe circuit 2   temperature NTC   pressure 4 20 mA   ratio metric 0  5Volt    26 Evaporator pressure probe circuit 1  pressure 4 20 mA   ratio metric 0  5Volt    27 Evaporator pressure probe circuit 1  pressure 4 20 mA   ratio metric 0  5Volt    28 Auxiliary output 1 pressure probe control  4 20 mA   ratio metric 0  5Volt     29 Auxiliary output 2 pressure probe control  4 20 mA   ratio metric 0  5Volt     30 Dynamic setpoint pressure probe  4 20 mA    After the number 30 the display read out goes from    o 1    to    c62    that allows to set an analogue input as digital input  see polarity input  of digital inputs      OANDABRWN O    8 3 DIGITAL INPUT CONFIGURATION ID1    1D18    Parameters involved    CF36   Configuration ID1   CF53   Configuration ID18  Not enabled   Remote ON   OFF   Remote chiller   heat pump   Flow switch  Supply fan overload  Flow switch of heated side  Antifreeze heater circuit 1   Antifreeze heater circuit 2   High pressure switch circuit   1   High pressure switch circuit 2   Low pressure switch circuit 1   10  High pressure switch circuit 2   11  Compressor 1 high pressure   12  Compressor 2 high pressure   1
142. r  is  controlled throughout the NTC probe configured as evaporator water outlet circuit  1 or circuit  2 or evaporator water common outlet  or  if they are all configured  by the first probe that goes below the setpoint     23 2 THERMOREGULATION OF THE HEATERS IN HEAT PUMP    The Par  Ar07 selects the probe s control for the anti freeze alarm and the relay outputs configured as anti freeze   support   boiler  heaters for the circuits 1 and 2 in heat pump mode    Par  Ar07 z 0  the function is disabled   Par  Ar07 z 1  the thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit 1 and 2  or both together  is  controlled only throughout the NTC probe configured as evaporator water inlet    Par  Ar07   2  the thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit  1 is controlled with NTC probe  configured as evaporator probe outlet of the circuit  1    The thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit  2 is controlled with NTC probe configured as  evaporator probe outlet of the circuit  2    ATTENTION  It is not possible to control the heaters of the crcuit  1 with the probe of the circuit  2 and viceversa    Par  Ar07 z 3  the thermoregulation  the anti freeze alarm and the relay outputs for heaters circuit 1 and 2 is controlled throughout the  NTC probes configured as evaporator water outlet circuit  1  circuit  2 and evaporator water common outlet   or if they are all  configured  by the
143. r during the pump  down       Push one time    Turn the heat pump on  if the unit is on led is on  The led is blinking if there is a power on delay or during the pump  down       Push one time    enter the function Menu       Push for 3 seconds    To set RTC parameters  if the RTC is inside        Pushing one time during the programming    To exit from a group of parameter       Push one time    Start the heating recovery of the chiller unit  with recovery active  the led is on          COOCOO       Push one time       Start the free cooling of chiller unit  with free cooling active the led  is on       Pg 14 103          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    4 5 KEY COMBINANTION       ACTION FUNCTION  Push for 3 seconds together Enter the programming          In Pr3 level  push SET and the push         DOWN        Select the parameter level visibility Pr1       2   Pr3          Push one time together Exit the programming       Push 5 seconds  heat pump with ok    condition  Manual defrost       In Pr3 programming level Push SET   In Pr3 defines if the parameter can be changed or not in the  and then the MENU key other levels                    4 6 LED ANDICONS                                     ICON LED FUNCTION  ON Auxiliary relay  1 active  OFF Auxiliary relay  1 not active  ON Auxiliary relay  2 active  OFF Auxiliary relay  2 not active  BLINKING Defrost delay counting active   amp     ON Defrost  bti OFF Defrost end          1592015300 U
144. ransducer selected with uS02   uS06 parameters    21 COMPRESSOR THERMOREGULATION    21 1 THERMOREGULATION PARAMETER DESCRIPTION    Par  ST01 Chiller Setpoint   It allows to set the chiller working temperature within the range ST02  ST03    Par  ST02 Minimum setpoint limit in chiller    The user can not program a setpoint value lower than ST02  the range is    30   C  ST01    Par  ST03 Maximum setpoint limit in chiller    The user can not program a setpoint value higher than ST02  the range is ST01  70  C    Par  ST04 Heat pump setpoint   It allows to set the Heat pump working temperature within the range ST05  ST06    Par  ST05 Minimum setpoint limit in heat pump    The user can not program a setpoint value lower than ST05  the range is    30   C  ST04    Par  ST06 Maximum setpoint limit in heat pump   The user can not program a setpoint value higher than ST06  the range is ST01  70  C    Par  ST07 Regulation band width in chiller mode    The configured resources are distributed inside the regulation band    Example Unit configured with 2 circuits  3 compressors per circuit and thermoregulation controlled by the evaporator inlet NTC probe   Chiller setpoint  evaporator inlet water   12  C  evaporator outlet water 7  C  when the evaporator inlet water is 12  C all the compressor  outputs are on while when the evaporator inlet water is 7   C all the compressors are OFF    Thermoregulation parameters  Par  STO1   7   C   Par  ST07   5   C   Functioning  the regulation band ST07 
145. rated  ne relay is configured  Too much compressors  Intermittent valve when ON   OFF time CO08   CO09   0  By pass gas when the by pass   0  Compressor Motor coil 2   center of the star with direct compressor start up  e        much step valve  ACF7  Evaporator pump  Enabled  CO16   0  but the relay is not configured  N Not enabled  CO16   0  but the relay is configured  Condenser pump  Y Enabled  CO21   0  but the relay is not configured  Y Not enabled  CO21   0  but the relay is configured  ACF8  e Thermoregulation probe  Y        thermoregulation probe  in chiller with STO9  in heat pump when enabled with ST10  is  not properly configurated  it does not exist or it is not a NTC   ACF9     Recovery cycle enabled Par  rC01 z 0    Y only some of these resources are configured  condensing probe  recovery digital input   recovery relay  or no outputd is configured        2 2 2 2 02 2 2 2 2     Programmazione errata       Reset    Programmazione corretta                Riarmo Automatico  Icona A lampeggiante  Azione Rel   allarme   buzzer attivato          41 11 ARTF CLOCK FAILURE       Label o the display    ArtF  clock failure                          Origin Clock chip failure   Reset Change clock chipset  Restart Manual in function menu  Icona Blinking   N   Action Alarm relay   buzzer ON  Regulation   Loads Not changed       Energy saving    Disabled if based on RTC          Unit ON OFF       Disabled if based on RTC       Pg 84 103          1592015300 User manual iCHILL 20
146. ree accessible levels the user can show and modify  both value and visibility of the parameters  To ensure an easy navigation through the different levels the common parameters have been  named and grouped under a family name    The three levels of programming       Pr1 User level      Pr2 Maintenance level      Pr3 OEM level    ARONA    11 1 PASSWORD DEFAULT VALUES       Password level Pr1   1      Password level Pr2   2      Password level Pr3   3   Under the function Menu  to reset the Alarm Log or the Compressor Overload  the password is 0  see parameter AL46   Each password can be changed  the range is from 0 to 999    Each parameter has two level  visibility and modify  Therefore it can be configured as follow    e The parameter can be showed and changed    e The parameter        be showed but not changed     11 2 ENTER THE PR1   PR2   PR3 PROGRAMMING LEVELS    Pr1 LEVEL    Push SET   DOWN together for 3 seconds  the top display shows the PAS label and the bottom display shows the Pr1 label  The leds  cir1 cir2 are blinking  up and down leds  to inform that you now are in PR1 programming level    Pr2 LEVEL    From the Pr1 level push the UP key for 2 seconds and the bottom display will show Pr2  The top display still shows PAS    Pr3 LEVEL    From the Pr2 level push the UP key for 2 seconds and the bottom display will show Pr3  The top display still shows PAS    After selecting the level push the SET key and the top display will show the 0 blinking value where to insert 
147. rential   0 0 25 0   C Dec  to stop the fan  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int  FA 22 Over ride CUT  OFF in Heat pump  To set a temperature pressure differential   0 0 25 0   C Dec  to keep the minimum fan speed  0 45   F int  0 0 14 0 Bar Dec  0 203 Psi int  FA 23 Night speed in Heat pump  To set the maximum fan speed percentage value 30 100     30  100    it is related to the fan power supply   Hot start  FA 24 Hot start setpoint  30 0   70 0   C Dec   22 158 F int  FA 25 Hot start differential 0 0 25 0   C Dec  0 45   F int  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999  Antifreeze heaters     Integration heating   boiler  Parameter   Description min max           Risoluzione  Ar1 Anti freeze heaters integration heating setpoint for air air unit in Chiller mode     30 0   70 0      Dec  To set a temperature value  below this value the anti freeze relay is activated   22 158   F int  Ar 2 Regulation band for antifreeze in Chiller mode  04 25 0   C ues  0 45   F  Ar 3 Set Anti freeze heaters integration heating setpoint for air air unit in HP mode     30 0   70 0   C Dec  To set a temperature value  below this value the anti freeze relay is activated     22 158 AE int  Ar 4 Regulation band for antifreeze in HP mode   30 0   70 0   C Dec   22 158   F int  Ar5 Antifreeze heaters   integration heating in defrost  0  ON only with thermoregulation control 0 1  1  ON with thermoregulation and during the defrosting cycle  Ar 6 Antifreeze alarm probe   heate
148. riods enabled          Energy saving or unit ON OFF   where  X with range 0  7 represents the energy saving  with RTC and X Y where  Y with range O  7 represents the unit on off          Example of a daily programming    Monday   Enater parameter programming   In the ES parameter family  select the parameter ES07  the top display shows 0   0   Push SET key  the top display shows 0   0 blinking  with UP or DOWN keys select the corresponding function  see next table     Push SET to confirm    Push SET   UP to exit the programming or wait the programming timeout     PON         MONDAY X   0   Y  0  The energy saving and the unit on off are both disabled     c T     bar Flow  59  C 2L     amp        l A b B     c 7 bar Flow  59  L  2L    2      WEEKLY PROGRAMMING    Repeat the daily programming for the other days of the week using parameters ES08  ES13     Pg 56 103       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    19 DYNAMIC SETPOINT    The dynamic setpoint allows to increase or decrease the setpoint with a proportional value determined by Sd01  chiller  and Sd02  HP   that depends from the 4  20mA analogue input or from the external air temperature probe  This function allows to save energy or run the  unit when the external ambient is not within the normal operative conditions     The dynamic setpoint activation is signalled by the SET key led on  When working in Chiller or HP the first pressure on SET key shows  the actual setpoint SetC  chiller  or
149. rly critical condition  the unit restarts working without the help of the maintenance personnel     RESET   e The Automatic Reset is activated when the next compressor thermoregulation is requested  in this case the pressure condition of  the pump down must be satisfied    e The Manual Reset needs to enter the function Menu under the AIrM label  After the reset the next thermoregulation restarts if the  pump down pressure is in normal condition     ATTENTION  If the pump down function is enabled  during the unit start up from digital input as pump down pressure switch and also from  analogue input as low pressure transducer  the compressor will restart only if both the inputs are satisfied     29 5 Pump DOWN ALARM DURING COMPRESSORS SWITCHING OFF  ACTIVATION    If within the time delay CO39  maximum pump down duration in off  the low pressure switch or the pump down pressure switch is not  active or the pump down setpoint is not reached  the last compressor is switched off  In this case after this timeout the instrument  signals the FPd1 or 2 alarms  in both cases when active the compressor is stopped     The alarm can be   e with Automatic Reset that is not logged  the buzzer and alarm relay are not activated   e with Manual Reset that is logged  the buzzer and alarm relay are activated     The Parameter AL21 determines the number of pump down alarm events to turn from automatic to manual reset   The Reset is always manual if AL21   0    The Reset is always automatic if AL21
150. rs   appoggio in Chiller mode   07 Not enabled  1  Evaporator inlet 0 3  2  Evaporator outlet 1 and 2  3  Evaporator outlet 1 and 2 and common outlet  Ar 7 Antifreeze alarm probe   heaters   support heaters in HP mode   0  Not enabled  1  Evaporator inlet  0 3  2  Evaporator outlet 1 and 2   3  Evaporator outlet 1 and 2 and common outlet                          Pg 36 103                                                                                                          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  Ar 8 Thermoregulation probe for anti freeze alarm   condenser heaters   0  not enabled   1  Condenser common water inlet probe  0 4  2  Condenser common water inlet and condenser inlet 1   2 probe   3  Condenser water outlet 1   2 probe   4  Condenser water outlet 1   2 and common outlet   Ar 9 Anti freeze heaters or condenser evaporator water pump control with unit in  remote OFF or stand by mode  0 1  0  Control not enable  1 Controlled by anti freeze thermoregulation   Ar 10 Thermoregulation and anti freeze alarm   Condenser anti freeze heaters  probe with recovery and water     water unit  0 1  0  Condenser water inlet probe  1  Condenser water outlet probe  Ar11 Anti freeze heaters  amp  water pump when the unit is off or stand by   0  Not controlled 0 1  1  Controlled by thermoregulation  Ar 12 Anti freeze heaters control for condenser evaporator faulty probe   0  Anti freeze heaters OFF 0 1  1  Anti freeze heaters ON  Boiler funct
151. rs  AL Shows only the Alarm parameters  Thermoregulation  Parameter   Description min  max  u m    Resolution  ST1 Chiller Setpoint org    Allow to modify the setpoint of the unit in chiller mode Ines etos er dec int  ST 2 Chiller minimum Setpoint  30 0   C    Minimum setpoint limit for ST 1  22   9101   of dec int  ST3 Chiller maximum Setpoint 70 0   C    Maximum setpoint limit for ST 1 5701 458     F          ST4 Heat pump setpoint ES    Allow te modifie setpoint of the unit in heat pump mode Sr SI06        qeclint  ST5 Heat pump minimum Setpoint  30 0 STO4   C Dec  Minimum setpoint limit for ST 4  22   F int  ST 6 Heat pump maximum Setpoint ST04 70 0   C Dec  Maximum setpoint limit for ST 4 158   F int  ST7 Regulation band in chiller mode 0 0 25 0   C Dec  0 45   F  int  ST8 Regulation band in chiller heat pump 0 0 25 0   C Dec  0 45   F int  ST9 Thermoregulation probe selection in chiller  0  Temperature probe NTC for evaporator inlet  1  Temperature probe NTC for evaporator outlet 1  2  Temperature probe NTC for evaporator outlet 2 0 5  3  Temperature probe NTC for common evaporator outlet  4  Temperature NTC probe from remote panel 1  5  Temperature NTC probe from remote panel 2  ST 10 Thermoregulation probe selection in heat pump  0  Temperature probe NTC for evaporator inlet  1  Temperature probe NTC for evaporator outlet 1  2  Temperature probe NTC for evaporator outlet 2  3  Temperature probe NTC for common evaporator outlet  4  Temperature NTC probe from remote pan
152. running only if the unit is running  chiller  heat pump   After giving the the start in  chiller or heat pump mode the compressor regulation starts only after the time delay CO17    The water pump is turned off only when the unit is turned off  stand by  and  if CO23 lt  gt 0  the water pump  supply fan turns off only after  the this delay    When the unit is in stand by or remote off and the Ar09  1  if the thermoregulation requires the antifreeze heaters also the water pump  is turned on        21   2 on compressor demand    When the compressor turns on also the water pump is turned on  In both chiller and heat pump modes the water pump  supply fan starts  CO17 before the compressor  When the last compressor is turned off the water pump  supply fan is turned of after the CO23 delay   When the unit is in stand by or remote off and the Ar09  1  if the thermoregulation requires the antifreeze heaters also the water pump  is turned on     The pump is always off when       Remote OFF from digital input       Digital input active of the condenser water pump overload       Digital input active of the condenser water pump flow with MANUAL alarm     During the defrost and when the compressor is off in dripping time the pump fan is on     35 PUMP GROUP OF THE CONDENSER    If two relay outputs are configured as condenser water pump and support pump of the condenser automatically the pump group control  is enabled    First start up of the unit  the running hours of the two pumps are bo
153. s  9  Yes   ACFL Condenser flow alarm Yes Yes  3  Yes   AtSF Fan supply overload alarm Yes Yes Yes Yes   AEUn Unloading signalling from evaporator   AtE1 Water pump overload alarm evaporator 1 Yes  4  Yes  boiler   5  Yes Yes   AtE2 Water pump overload alarm support evaporator 2 Yes  4  Yes  boiler   5  Yes Yes   AtC1 Water pump overload alarm condenser 1 Yes  4  Yes Yes   AtC2 Water pump overload alarm support condenser 2 Yes  4  Yes Yes       AEP1 Water pump maintenance evaporator 1       AEP2 Water pump maintenance support evaporator 2       ACP1 Water pump maintenance condenser 1       ACP2 Water pump maintenance support condenser 2       ArtC Clock alarm       ArtF clock failure                                     ALOC Generic alarm with unit stopped Yes Yes Yes Yes Yes  AEE Eeprom alarm Yes Yes Yes Yes Yes  ACF1 Configuration alarm Yes Yes Yes Yes Yes  ACF2 Configuration alarm Yes Yes Yes Yes Yes  ACF3 Configuration alarm Yes Yes Yes Yes Yes  ACF4 Configuration alarm Yes Yes Yes Yes Yes  ACF5 Configuration alarm Yes Yes Yes Yes Yes  ACF6 Configuration alarm Yes Yes Yes Yes Yes  ACF7 Configuration alarm Yes Yes Yes Yes Yes  ACF8 Configuration alarm Yes Yes Yes Yes Yes  ACF9 Configuration alarm Yes Yes Yes Yes Yes                                  ArtF Faulty clock          Pg 92 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary                                                    ArtC Clock error   AEUn Unloading signalling from high temp of  evapor
154. s 7 for the digital input ID1  CF36       high pressure switch of circuit 1        The label    c    means that the digital input is active for closed contact     11 12 CHANGE THE POLARITY OF THE DIGITAL INPUTS OUTPUTS    Enter the programming    1  Select a parameter with digital input output value  The top display shows the label o before the configuration number while the  bottom display shows the parameter label    2  Push SET key  the o label and the configuration number are blinking  use the UP or DOWN key and select the proper polarity   o    c   of the function  then push SET key to confirm it all    3  The top display blinks for some seconds and then it will shows the next parameter    4  To exit the programming push SET   UP together or wait the timeout  15seconds      12 SELECTION AND START OF THE RUNNING MODE    12 1 SELECT THE CHILLER OR THE HEAT PUMP MODE    The CF79 parameter allows to select and enable the running mode   Par  CF79   0  Through keyboard  the user can start and stop the unit using the keys of the front panel     Par  CF79   1  Through digital input programmed to start stop the unit from remote control    e This selection is enabled if there is one digital input configured as start stop from remote  remote chiller   heat pump     non of the  digital input are configure the unit remains in stand by    e The    open    status of the input forces the chiller running mode     e         closed  status of the input forces the heat pump running mode    
155. s on             Condenser fan  ON if at least one of the PWM or relay outputs for fan control is active          Pg 16 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    4 8 MEANING  FUNCTIONNING OF THE BOTTOM DISPLAY LED    Led n  1    n p b  A D b D        a    7 bar Flow  59  ledn20 0 0    i        lcm n  4    led n  3        Led   1     2  With RTC   If the bottom display shows the RTC the 1 and 2 leds are blinking     Led   1     2 In function Menu  During the time counting to the next defrost for one or both circuits the led 1 and 2 are blinking     LED Parameter programming  In Pr2 level  led  3 indicates the visibility while the  1 and  2 show if the parameter can be modified or not   In Pr3 level  led  3 and  4 indicate the visibility while the  1 and  2 show if the parameter can be modified or not     5 REMOTE TERMINAL    Not yet available on this version  The iCHILL can be connected with 2 remote terminals  Each remote terminal can have the NTC probe on board that is used to show the    loacl temperature and also to control the temperature regulation    for the connections use shielded cable for a maximum lenght of 150mt  In case of no communication between the instrument and the  remotes the upper display shows    noL     no link             VI620   VI620S can be connected to IC260L     IC261L           VI820   VI820S can be connected to IC280L     IC281L   Use the connection cable CAB CJ30  2x0 2 mm   to interface the ichill connector 
156. s turned off  stand by  and  if CO18 lt  gt 0  the water pump  supply fan turns  off only after the this delay    When the unit is in stand by or remote off and the Ar09  1  if the thermoregulation requires the antifreeze heaters also the water pump  is turned on    CO16   2  on compressor demand    When the compressor turns on also the water pump  supply fan are turned on  In both chiller and heat pump modes the water pump   supply fan starts CO17 before the compressor  When the last compressor is turned off the water pump  supply fan is turned of after the  CO18 delay    When the unit is in stand by or remote off and the Ar09  1  if the thermoregulation requires the antifreeze heaters also the water pump  is turned on    The pump is always off when    Remote OFF from digital input    Digital input active of the water pump overload    Digital input active of the evaporator water pump flow with MANUAL alarm     During the defrost and when the compressor is off in dripping time the pump supply fan is on   32 2 HOT START   SUPPLY FAN  ONLY FOR AIR   AIR UNIT IN HEAT PUMP MODE    The hot start function is available only for air air unit configured with heat pump and it is active only during the heat pump mode    It allows to start the supply fan only if the evaporating condensing probe temperature is hot enough to avoid to introduce cold air flows   FA24 Hot start Setpoint    It is the temperature setpoint to stop the supply fan when the NTC probe of the evaporator  1 output or 
157. ser manual iCHILL 200 L GB   1 0 23 02 2005    4 7 DISPLAY AND ICONS    Preliminary       ICON    MEANING   FUNCTIONNING         C    Celsius degrees  ON for temperature measurements of probe values or parameters         F    Fahrenheit degrees  ON for temperature measurements of probe values or parameters       g    Bar  ON for pressure measurements of probe values  setpoint or parameters       Psi  ON for pressure measurements of probe values  setpoint or parameters       ON   compressor 1 active  Blinking   compressor 1 delay counting       ON   compressor 2 active  Blinking   compressor 2 delay counting       ON   compressor 3 active  Blinking   compressor 3 delay counting       ON   compressor 4 active  Blinking   compressor 4 delay counting       ON   compressor 5 active  Blinking   compressor 5 delay counting    ON   compressor 6 active  Blinking   compressor 6 delay counting       General alarm  blinking if there is an alarm not identified by an icon        2  gt  Ep E   ES 5 F9    2    Anti freeze heaters  integration heating   boiler  ON if the output is on       Flow     Flow alarm   differential  pressure switch   supply fan thermal  air   air unit    is blinking if the configuration of the    digital input is active       Real time clock  On when the bottom display show the RTC  ON during the programming with time based parameter value  In function menu indicates the defrost delay counting       Water pump  On if at least one of the four configurable pump group i
158. setpoint the defrost cycle stops    dF14 All the resources on during the defrost of the circuit  1   07 Not enabled   12 Enabled   dF15 All the resources on during the defrost of the circuit  2   07 Not enabled   12 Enabled   dF16 Compressor step delay time in defrost    dF17 Condensing fan control during defrost and dripping cycle   07 Not enabled   1   Enabled in defrost   2  Enabled in defrost and in dripping time   If dF17   0  During the defrost the fan control is not active    If dF17   1  when the condensing temperature pressure value increases over dF18 the fans are turned on  the fan control is determined  by the same algorithm used in chiller mode     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    If dF17   2  during the dripping time  dF08  lt  gt 0  the fan are turned on for the time duration set in dF08    dF18 Pressure   temperature setpoint to force the fans on during the defrost   When the temperature pressure rises over this value the fan are turned on at the maximum speed   dF19 Time delay before starting a forced defrost   It determines a delay time before starting the defrost cycle   dF20 Temperature   pressure setpoint to force a defrost   It determines a temperature pressure setpoint under which the dF19 starts counting  when dF19 is expired if the temperature pressure  is still lower than dF20 the defrost is immediately executed    ATTENTION If during the dF19 counting the temperature rises over df20  dF21 differential  the proce
159. splay of the circuit 2      Condenser 2water outlet with the label Cou2    Par  dP03   3   Top display of the circuit 1       Condenser probe temperature Cdt1   pressure CdP1  Bottom display of the circuit 1      Evaporator pressure probe LP1   Top display of the circuit 2    Condenser probe temperature Cdt2   pressure CdP2  Bottom display of the circuit 2   Evaporator pressure probe LP2    15 4 DEFAULT DISPLAY READ   OUT OF THE REMOTE PANELS VI620S AND VI820S    If the parameter dP04   0 the upper display of the remote panels  1 and  2 depends on the parameter values dP01     dP02     dP03  to  show the temperature detected by the internal probe of the remote panel accessing the function menu under the function trEm    If the parameter dP04   1 the upper display of the remote panels  1 and  2 show their internal NTC sensor  ambient temperature   to  show the same temperature it is possible to eccess the function menu under the function trEm     15 5 DEFAULT DISPLAY READ   OUT OF THE REMOTE PANELS VI620S AND VI820S    If the parameter dP04   0 the upper display of the remote panels  1 and  2 depends on the parameter values dP01     dP02               to  show the temperature detected by the internal probe of the remote panel accessing the function menu under the function trEm    If the parameter dP04   1 the upper display of the remote panels  1 and  2 show their internal NTC sensor  ambient temperature   to  show the same temperature it is possible to eccess the function men
160. ss is aborted and the dF19 time  reloaded    dF21 Forced defrost differential   dF22 defrost mode for unit with two circuits   Operative mode    0  Independent   1  The condition are satisfied in both circuits   2  At least one circuit has reached the start condition   dF23 It determines the end of the defrost for unit having two circuit and common condensing ventilation  Operative mode    0  Independent   1  The end defrost condition are satisfied In both circuits   2  At least one circuit has reached the end defrost condition    39 RECOVERY    The recovery function is Enabled if     1 Par  rC01 not equal to 0    2 Chiller running mode    3 The recovery key is pushed to enable the function and the recovery led is on    4 The condensing temperature   pressure is lower than set rC06    rC07  differential    5 The input output resources are configured   6 The remote recovery digital input is activated     The recovery function is NOT Enabled if     1 Par  rC01   0    2 Heat pump running mode  remote OFF or stand by    3 The recovery key is pushed to disable the function and the recovery led is on  4 The condensing temperature   pressure is higher than set rC06    5 The input output resources are not properly configured  alarm ACF9     6 The remote recovery digital input is not activated     NECESSARY RESOURCE FOR THE RECOVERY OF THE CIRCUIT  1    Output relay configured as valve for recovery circuit  1   Remote recovery digital input for circuit  1   Condenser probe of the circ
161. ssure probe  configured as auxiliary output 1 and 2 are controlled with 0 5Vdc transducers   3   Pressure control with 0 5Vdc   To control the evaporating and condensing pressures it is necessary a  ratiometric 0 5Vdc transducer   CF8 PB1 Configuration 0 25  If configured as digital input    1 c62  CF 9 PB2 Configuration 0 25  If configured as digital input o1 c62  CF 10 PB3 Configuration 0 30  If configured as digital input o 1 c62  CF11 PB4 Configuration 0 30  If configured as digital input    1 c62  CF 12 PB5 Configuration 0 30  If configured as digital input    1 c62  CF 13 PB6 Configuration 0 30  If configured as digital input 01 c62  CF 14 PB7 Configuration 0 25  If configured as digital input 01 c62  CF 15 PB8 Configuration 0 25  If configured as digital input o1 c62  CF 16 PB9 Configuration 0 25  If configured as digital input o 1 c62  CF17 PB10 Configuration 0 25  If configured as digital input o 1 c62  Probe Offset  CF 18 PB1 Offset  12 0   12 0   C Dec   10 53   F int  CF 19 PB2 Offset  12 0   12 0   C Dec   10 53   F int                                                                                                                                                                               1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  CF 20 PB3 Offset  12 0   12 0   C Dec   10 53   F int   5 0 5 0 bar dec   72 72 psi int  CF 21 PB4 Offset  12 0   12 0   C Dec   10 53   F int   5 0 5 0 bar dec   72 72 psi int  CF 22 PB5 Offset  12 0   12 0 
162. sword is OK the label ArST blinks for 5 seconds then the display returns to normal condition read out  probes     If the password is not correct the display shows PAS again  in any case is possible to scroll the list with UP or DOWN   To exit push the M key one time or wait the timeout                               17 6 PASSWORD VALUE      THE ALARM LIST    The default value is 0 to change this value enter Pr3 level under the AL parameter family     THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE  WHEN THE MEMORY IS FULL ANY NEW ALARM WILL  ERASE THE OLDEST     17 7 DISABLE     ENABLE A SINGLE CIRCUIT    Through the instruments keyboard is possible to completely disable a single circuit for maintenance or to use just a cooling part of of the  unit     CrEn FUNCTION enables   disables a circuit from keyboard    Label involved with CrEn function  Cr1E   circuit 1  Cr2E   circuit 2   DISABLE A CIRCUIT   Enter the function Menu   1  Use UP or DOWN keys to select CrEn on the bottom display   2  Push SET key  the bottom display   Cr1E  top display   En    3  Select the circuit 1 or 2 with UP or DOWN  Cr1E or Cr2E     4  Push SET key for 3 seconds when one of the two Cr1E  Cr2E label are displayed  The top display shows the En blinking label   use the UP or DOWN to change in diS  Disabled  or En  Enabled   then push SET key to confirm the new selection  The display  shows next circuit status    5  To exit the CrEn function push MENU key or wait the timeout     17 8 READ OUT O
163. t  the alarm is reset so the unit can start at least for the time set in AL35 in order to heat the water or the  air  After the AL35 delay if the anti freeze probe is still lower than AL33 setpoint for AL36 seconds the unit is locked again with an anti        freeze alarm     41 24 B1HP B2HP HIGH PRESSURE   CONDENSING HIGH TEMPERATURE OF THE CIRCUIT       Label o the display    b1hP  high pressure digital input of the circuit  1   b2hP  high pressure digital input of the circuit  2                       Origin In chiller or heat pump  if the condensing probe is higher than ALO9 setpoint   Reset If the condensing probe value is lower than ALO9    AL10  differential   Restart Manual  Reset procedure in Menu function     Icon Blinking A   Action Alarm Relay   and buzzer on       41 22 B1LP   B2LP LOW PRESSURE SWITCH CIRCUIT  1 OR 2       Label o the display    b1LP  low pressure switch circuit  1   b2LP  low pressure switch circuit  2                    Origin e With the digital input is active     If ALO8 1  also in stand by or remote OFF  when the low pressure switch input is active      In defrost if AL06 1 when the compressor low pressure switch input is active   The alarm is not signalled if       In defrost for the time AL07 when the 4 way valve is activated      During the AL01 delay after turning on the compressor   Reset Digital input not active  Restart Automatic   Manual after AL02 events per hour  Reset procedure in Menu function   Icon Blinking A  Action Alarm Relay
164. t not enabled    1   Temperature pressure defrost  The dF09  time delay to the defrost  starts when the temperature decreases under the     02 setpoint   The Defrost cycle end is determined by temperature pressure    2   Time duration defrost  The     09  time delay to the defrost  starts when the temperature decreases under the dF02 setpoint  The  Defrost cycle end is determined by the maximum duration dF05    3   Defrost from digital input  The     09  time delay to the defrost  starts when the temperature decreases under the dF02 setpoint  The  Defrost cycle end is determined by the active digital input    dF02 Temperature   pressure to begin the time counting to next defrost    It allows to program a setpoint under which the     09 starts counting    dF03 Temperature   pressure to end the defrost    It allows to program a temperature pressure setpoint value to determines the end of the defrost when the probe value is rising    dF04 Minimum duration of the defrost   It determines the minimum defrost time duration after starting the defrost itself even if the conditions are not more satisfied    dF05 Maximum duration of the defrost   If dF01 2  it determines the maximum duration of the defrost and even if  for the other cases  the end defrost condition are still to be  satisfied    dF06 defrost delay time between the 1   and the 2    circuit    After the interval dF09 determined by the defrost request of one of the circuits the other 2  circuits must wait also the time dF06
165. ter      Motocondensing   Additional features        Heat pump with gas reversibility      Free cooling function      Recovery function    2 1 MAIN FUNCTION    Chiller management      One circuit up to 4 compressors  e Twocircuits with different compressor number per circuit     Double circuit up to 6 compressors  e Screw compressors  Compressor start up      Direct     Part winding     Star   delta  Compressor Sott start   e With step valve  e Automatic start unloading  without load       External by pass gas valve   Capacity step control      Continuous control     Step control     Modulation control  screw compressors   Thermoregulation of the compressors  e Time running hours     Number of start up per hour  Cooling liquid injection  e With dedicated PTC probe  High temperature alarm of the compressor discharge side  e With dedicated PTC probe  Complete management of two pump groups of the water side  e 2 pumps evaporator side  e 2 pumps condenser side  Display layout customizable  e Temperature     Pressure  e Time   RTC in real time  Other display readings  Safety digital inputs  Compressors running hours  Number of compressor start up  Pump running hours  Delay counting to the next defrost  Proportional output percentage status  Compressors discharge temperature  larm reset with custom password  Alarm list  Compressor thermal protection alarm  ingle circuit stand by  Circuit maintenance  To work with only one circuit  ingle compressor stand by  Compressor maintenance  
166. th 0  if CO21 1 or 2  continuous or on compressor demand pump  mode  by default the pump  1 is turned on  The successive restart of the unit is made with the pump  2    During the normal functioning condition when the unit changes from a stand by  remote off  power off status to chiller or heat pump  mode the pump that is running is switched off and immediately the one with less running hours is turned on    When the unit goes in stand by or remote off the pump stays on for the time set in CO23    When the unit is in stand by or remote off and the Ar09  1  if the thermoregulation requires the antifreeze heaters also the water pump  is turned on     Pg 72 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    35 1 CONDENSER WATER PUMP ROTATION    Par  CO24  lt  gt  0 to enable the function    During the normal functioning condition  both for chiller and heat pump  if one pump reaches the running hours of the CO24 parameter   the pump is turned off while the other pump is re activated    If the CO25  lt  gt  0  before changing from one to the other the two pumps work together for the time set in this parameter  If CO24 0 the  rotation is immediate and CO25 is not counted     ATTENTION  The CO17 CO23 values  on and off delay between compressors and pumps  are calculated also for the pump group     35 2 CONDENSER WATER PUMP ROTATION THROUGH DIGITAL INPUT CONTROL    With two digital inputs configured as overload alarm of water pump and support pump the rotat
167. th the  contactor K2  Durning the CO13 time delay the step valve is forced on  minimum power  When the C013 is expired if the  thermoregulation requires more power the valve will be switched off  maximum power      27 7 STAR  DELTA START    This algorithm allows to reduce the start up current when using hermetic or semi hermetic compressors or medium     big screw  compressors    Each compressor needs three relay outputs   The maximum number of relay outputs is 6 this means 2 compressors with Star delta start up    EXAMPLE   Star delta configuration of the compressor relay outputs   Set Par CF54   21  Star delta line  1 relay of the compressor  1    Set Par CF55   22  Star delta line  2 relay of the compressor  1    Set Par CF56   23  Star delta centre relay of the compressor  1     27 8 STAR  DELTA START Or A COMPRESSOR    Each compressor needs three relay outputs    One relay output as Line  1 of the compressor  1  Relay K1 of the Fig 3     One relay output as Line  2 of the compressor  1  Relay K3 of the Fig 3     One relay output as centre of the star  Relay K2 of the Fig 3    To turn on the compressor  the centre of the star relay is turned on  Relay K2 of the Fig 3   after 1 second the Line  1 relay is turned on   relay K1 Fig 3   The two relays work together for the time set in CO11  then the relay of centre of the star is switched off  relay K2  Fig 2   Then after the CO12 delay time the relay of the line  2 is turned on  relay K3 Fig 3     To turn off the compressor 
168. the compressors COEn     Display the compressor discharge temperature COdt     Show and reset the number of compressor running hour Hour     Show and reset the number of compressor starts up COSn   10  Show the condensing fan speed percentage of the proportional output Cond  11  Show the percentage of the proportional output 0   10 Vdc Pout   12  Time counting to next defrost cycle  under heat pump mode  dF   13  Show the probe temperatures that enabled to control the auxiliary output uS  14  Show the probe the temperature of the remote panels trEM    MENU FUNCTION ACCESS  Push and release the M key   MENU FUNCTION ACCESS  Push and release the M key or wait the 15seconds timeout limit   With the UP or DOWN keys move inside the label list     17 1 ALARM LIST  SHOW AND RESET    ALrM FUNCTION   Enter the function MENU pushing M key one time   1  Use the UP or DOWN to select the AlrM label   2  Push SET key  Nothing happens if there are no active alarm events    3  Bottom display  alarm label code  Top display  label rSt to reset or NO if it is not possible    4  Use the UP or DOWN to scroll the alarm list    5  Pushing SET when the rSt label is displayed the corresponding alarm will be reset  then the display shows next alarm in the list   pushing SET again the alarm is reset and the display shows next alarm etc  Nothing happens by pushing SET when the label NO  is displayed  in this case push UP or DOWN to move to another alarm label     6  To exit the ALrM reset function push 
169. the evaporator  2 output or the  evaporator common output value is lower     FA25 Hot start differential  Temperature differential of the hot start function     33 EVAPORATOR PUMP GROUP    If two relay outputs are configured as evaporator water pump and support pump of the evaporator automatically the pump group control  is enabled    First start up of the unit  the running hours of the two pumps are both 0  if CO16 1 or 2  continuous or on compressor demand pump  mode  by default the pump  1 is turned on  The successive restart of the unit is made with the pump  2    During the normal functioning condition when the unit changes from a stand by  remote off  power off status to chiller or heat pump  mode the pump that is running is switched off and immediately the one with less running hours is turned on    When the unit goes in stand by or remote off the pump stays on for the time set in CO18     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    When the unit is in stand by or remote off and the Ar09  1  if the thermoregulation requires the antifreeze heaters also the water pump  is turned on     33 1 EVAPORATOR WATER PUMP ROTATION    Par  CO19  lt  gt  0 to enable the function    Durning the normal functionning condition  both for chiller and heat pump  if one pump reaches the running hours of the CO19  parameter  the pump is turned off while the other pump is re activated    If the CO20  lt  gt  0  before changing from one to the other the two pumps wor
170. the fuction the time delay rC02 and rC03 are not counted and the valve is immediately turned on or off     RECOVERY START OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP   Circuits 1 and 2 configured with more than one step of power  eg each circuit with three compressors   if the thermoregulation requires  to turn on one or more resources and the recovery is activated from the digital input the unit turns on only one step and then waits the  rC02 delay  this delay keep off all the other steps after the recovery is started   After the delay the recovery valve is turned on and  after  the rC03 time  this delay keeps off all the other steps after the recovery is started   the other resources if necessary are turned on     RECOVERY STOP OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP   Circuits 1 and 2 configured with more than one step of power  eg each circuit with three compressors   After the rC04 time delay   minimum on time of the recovery function when activated  if the digital input of the recovery is not active the units stops the new  resources for the time set in rC02  After this delay the recovery valve is turned off and the regulation restarts with its normal running  condition     RECOVERY START OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED   When the system is running with 10096  eg all the three compressor of a circuit are on  of power and the digital input start the recovery  function  before turning on the recovery va
171. the password     Set the password level using the UP and DOWN keys then confirm with SET key    Dependening on the password value there will be the different level access  if the password is wrong the instrument shows the  password value again     ATTENTION     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    For all the programming levels Pr1 2 3  the CF family  or configuration parameters  can not be changed if the unit is running in  chiller  heat pump  The user can check the leds  1 and  2 and if they are blinking it is not possible to change this parameters  but it is necessary to set the unit in stand by and then enter the programming again    During the defrost the dF family can t be programmed     11 3 How TO CHANGE A PARAMETER VALUE    Enter the programming  1  Push the SET   DOWN keys together for    seconds   Select the parameter label with up and down keys   3  Push SET to enter the parameter value   4  Change the value with UP or DOWN keys   5  Push    SET    to confirm  after some seconds the display shows the next parameter   6  Exit  Push SET   UP together when a parameter label is displayed or wait 15seconds without pushing a key   NOTE  a new parameter value is confirmed also after the 15 seconds of timeout is expired  without pushing SET key to confirm      11 4 CHANGE THE PASSWORD VALUE    Pr1 LEVEL   Remember that it is necessary to know the old password value    1  Enter the Pr1 level   2  Select a parameter family    3  Inside the 
172. the read out depends on the paremeters dP01     dP02     dP03 0 1  1  the read out shows the NTC probe of the remote panel   Pr1 Password 0 999  Pr2 Password 0 999                         Pg 28 103                                                                                                 1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary  Pr3 Password 0 999  Configuration  Parameter   Description min                     Resolution  Unit Model  CF1 Type of unit  0  Air   air Chiller 0 2  1  Air   water Chiller  2  Water   water Chiller  CF 2 Heat pump  0  no 0 1  1  Yes         Motocondensing unit  0  no 0 1  1  si  Compressors  CF4 Compressors number for circuit  1  1  1  2 2 0 4  3 3  4 4  CF 5 Compressors number for circuit  2  0 0  1  1 0 3  2 2  3 3  CF 6 Number of compressor parzialization  07 none  12 1 0 3  2 2  3 3  Analog Inputs  CF7 Pressure or temperature analogue input functioning  0   Temperature   pressure NTC     4 20 mA    The condensing temperature is controlled with NTC probe while for the  evaporating pressures of the circuits 1 and 2 and the pressure probe  configured as auxiliary output 1 and 2 are controlled with 4 20mA  transducers   1   Pressure control with 4 20 mA   To control the evaporating and condensing pressures it is necessary a 0 3  4 20mA transducer   2   Temperature   pressure NTC     0 5Vdc   The condensing temperature is controlled with NTC probe while for the  evaporating pressures of the circuits 1 and 2 and the pre
173. the start up  0 250 Re 10 sec       2 Minimum                      OFF time after the switching off  0 250 T 16                ON delay time between two compressors or compressor and valve  During  this time the led of the next resource is blinking  1 250 Sec                         Pg 32 103                                                                            1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary         OFF delay time between two compressors or compressor and valve  During 0 250 S  deos SE TE de ec  this time the led of the next resource is blinking       5 Output time delay after the main power supply start up to the unit  10      0 250 10 sec  All the loads are delayed in case of frequently power failures  Sec  Partialization  Capacity Control          Functioning  see Capacity Control   0  With on off steps  1  Continuous with steps and direct action 0 3  2  Continuous with steps and reverse action  3  Modulating for screw compressor  CO 7 Start up with minimum compressor power   automatic start unloading valve  0   Only at the compressor start up  Minimum power automatic start   unloading valve off   1  At the compressor start up and during the termoregulation  Minimum  power   automatic start unloading valve off  0 3  2   Only at the screw compressor start up  Minimum power automatic start   unloading valve off   3  At the compressor start up and during the termoregulation  Minimum  power   Unloading valve ON with compressor off     
174. tion of both the heaters together of the circuit 1 and 2 is excecuted through the probes  configured as condenser water outlet of the circuit  1 and 2 and the NTC of the common outlet    ATTENTION   When the outputs are configured as heaters circuit  1 and 2 they are both controlled by the NTC probe of the common condenser  outlet     23 5 THE THERMOREGULATION OF THE ANTI FREEZE HEATERS OF THE CONDENSER RECOVERY    The thermoregulation depends on the configuration of the circuit  1 and 2 heaters and the NTC probe to control the cycle    The Par  Ar08 selects the probe to control the anti freeze alarm and the heaters thermoregulation    Par  Ar08   0  the thermoregulation  the anti freeze alarm and the heaters control of the circuit  1 is controlled by the NTC of the  condenser water common inlet or the circuit  1  while the relay output for circuit   2 is controlled through the NTC configured as  condenser water common inlet or circuit 2    Par  Ar08   1  the thermoregulation  the anti freeze alarm and the heaters control of the circuit  1 is controlled by the NTC of the  condenser water common outlet or the circuit  1  while the relay output for circuit  2 is controlled through the NTC configured as  condenser water common outlet or circuit 2     23 6 GRAPH OF THE ANTI FREEZE  INTEGRATION HEATING  BOILER HEATER RELAYS    SETPOINT    SETPOINT  HEATER N   2  ON  HEATER N   1                                PBr PBr       REGULATION BAND REGULATION BAND    23 7 BOILER THERMOREGUL
175. to the shielded wire     6 FIRST INSTALLING    6 1 ONBOARD CLOCK  OPTIONAL     Giving power supply the bottom display shows    rtC    alternated with a temperature or pressure value  It is necessary to set the RTC    If the probes are not connected the display shows the corresponding probe alarm messages  In this situation the RTC setup and the  programming are available    ATTENTION   The RTC function is an optional and it is not possible to update the instrument but it is necessary to order the instrument    already complete of this features   With power failure the RTC back up battery maximum duration is 1 week  After this period it is necessary to setup the clock again     6 2 RTC SETUP    Push M key for 3 seconds until the bottom display shows    Hour    and the top display shows its value    Push SET one time  the value is blinking    Use the Up and Down keys to adjust it  Push SET one time to confirm  automatically the display shows next parameter    Repeat the operations 2  3  and 4  for all the RTC parameters    Min  minutes  0 60    UdAy  day of the week  Sun   Sunday  Mon  Monday  tuE  Tuesday  UEd   Wednesday  tHu   Thursday  Fri  Friday  SAt   Saturday      dAy  day of the month  0 31      MntH  month  1712      yEAr  year  00799        PON      1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    7 WIRING CONNECTIONS    7 1 HARDWARE RESOURCES FOR IC260L   IC280L MODELS    10 digital outputs  relays    18 digital inputs  free of voltage    10 an
176. ture setpoint 0 150   C Dec   int  0 302   F int  AL 40 Compressor high discharge temperature differential 0 25 0   C Dec  0 45   F int  AL 41 Number of compressor high discharge temperature events per hour to  determine the alarm reset condition   Always manual reset if AL41   0 0 16  Always automatic reset if ALA1 216  From automatic to manual if ALA1   1  15  AL 42 Maximum number of generic alarm events  each event stop the regulation   before turning the alarm from automatic to manual   Always manual   142   0 0 16  Always automatic AL42  16  From manual to utomatic if AL42 value is between 1 and 15  AL 43 Generic alarm delay time after the digital input activation 0 250 Sec  AL 44 Generic alarm delay time after the digital input is not activate 0 250 A 10 sec  Alarm relay  AL 45 Enable alarm relay with unit in off or stand     by   0  Alarm output not enabled 0 1  1  Alarm output enabled                         Pg 40 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary                      Password reset  Alarm log     Compressor overload   AL 46 Password value to reset the alarm log or the compressor overload alarm  0 999  AL 47 Thermal alarm of the compressor   0  lock the compressor 0 1   1  lock the whole circuit  Pr1 Password 0 999  Pr2 Password 0 999  Pr3 Password 0 999                      10 PROGRAMMING WITH THE    HOT KEY 64       10 1 DOWNLOAD  HOW TO PROGRAM AN INSTRUMENT WITH A PROGRAMMED    HoT KEY       1  Turn off the instrument suppl
177. u under the function trEm     16 DISPLAY INFORMATION    16 1 SHOW THE SET POINT VALUE    Push and release the SET key  the leds of the circuits are off and the set value is displayed   In stand by the bottom display shows SetC  set chiller   by pushing SET again the next label is SetH  set heat pump     If the unit is running the only set displayed is related to the running mode     16 2 MODIFY THE SET POINT    1  Push SET key for at least 3 seconds  the leds of the circuits are off and the set value is blinking   2  Use the UP or DOWN key to modify the setpoint   3  Push SET to confirm or wait the timeout  15seconds      16 3 SHOW THE ACTIVE SETPOINT DURING ENERGY SAVING OR DYNAMIC SETPOINT  If the unit is running in chiller or HP  the Energy Saving or the Dinamic Setpoint activity is signalled by the blinking led of the SET button     Chiller mode  push SET one time  the bottom display shows the SEtC  set chiller  while the top display shows the set value  Only if the  Energy saving or the Dynamic Setpoint are active  pushing another time the SET key  the bottom display shows  SEtr   real setpoint    and the top display shows the setpoint that the unit is really using for the thermoregulation    Chiller mode  push SET one time  the bottom display shows the SEtH  set Heat pump  while the top display shows the set value  Only  if the Energy saving or the Dynamic Setpoint are active  pushing another time the SET key  the bottom display shows  SEtr   real  setpoint   and the to
178. uit  1     NECESSARY RESOURCE FOR THE RECOVERY OF THE CIRCUIT  2    Output relay configured as valve for recovery circuit  2   Remote recovery digital input for circuit  2  Condenser probe of the circuit  2     39 1 UNIT WITH TWO SEPARATE IDRAULIC CIRCUITS    FUNCTIONING  Par  rC01   1 unit with two separate circuits     CIRCUIT   1   With the recovery function enabled  the unit running in chiller and with the temperature pressure proper condition  the unit        start the  recovery of the first circuit if the corresponding digital input is active  When the digital input is active the relay of the valve for the  recovery of the first circuit is activated     CIRCUIT   2   With the recovery function enabled  the unit running in chiller and with the temperature pressure proper condition  the unit can start the  recovery of the second circuit if the corresponding digital input is active  When the digital input is active the relay of the valve for the  recovery of the second circuit is activated    After starting the function  if the digital input becomes not active the recovery function runs for the time set in rC04 before stoppping      Between the end and the next recovery function the instrument waits the time set in the parameter rC05 even if the digital input is  activated again     Pg 78 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    RECOVERY START AND STOP OF THE TWO CIRCUITS CONFIGURED WITH CAPACITY STEPS  During the start and the stop of 
179. uit balancing is applicable only if there a2 circuits and 2 resources for circuits  total of 4 resources    The circuit balancing allow to equalise the power supplied by the two circuits  the difference can be one step maximum   ES  2 circuits  2 step for each circuit  total of 4 resources    Activation     1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    The thermoregulation immediately requires all the 4 resources  the controller turns on the compressor with less running hours  then the  compressor with less running hours of the other circuit  Again the first circuit and it is turned on the 2  compressor then the second  compressor of the other circuit    De activation    It is selected first the circuit having more resources on  if the running resources are equals for both circuits  the first compressor turned  off is the one with the greater number of running hours or less number of starts up  then  in the other circuit  the other compressor with  less running hours  Again the first circuit and it is turned off the 2  compressor then the second compressor of the other circuit     COMPRESSOR REGULATION     When it is turned on each compressor runs for the CO01 minimum time  This minimum time is aborted in case of alarm  STAND   BY   ON OFF by remote  defrost or partialization through NTC transducer      When it is turned off each compressor can restart only after the CO02 time delay      Both for sequential or rotation regulation with compressors or c
180. unit in heat pump mode  Auxiliary output n  1 OFFunit in stand by x ON unit in free cooling mode            ON it displays the size of cir  N   2  when cir1 and cir2 blink at the same time ON enter in function  it means you are entering in programing mode Blinking when menu or RTC parameters  set energy saving or  set point dinamic in On    ON unit in recovery mode    Pg 12 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    4 2 USE OF THE LED ON THE MODELS VI620   VI620S REMOTE PANELS    Defrost    Auxiliary output n 2    Auxiliary output n 1    On unit in heat pump mode    iie  ON it displays the size of cir  N  4 OFruret in stand by    when cir1 and cir2 blink at the same time PEE  il means you ara entering in programing mode On unit in chiller mode    OFFunit in stand by    ON enter in tunction  menu or RTC parameters    ON it displays the size of cir  N  2   when cir1 and cir blink al Ihe same lime   it means you are entering in programing mode  Blinking when   set energy saving or  set point dinamic in On       4 3 USE OF THE LED ON THE MODELS VI820   VI820S REMOTE PANELS    Defrost  Auxiliary output n  2    Auxiliary output n 1    On unit      chiller mode  ON it displays the size ot cir        1              in stand by  whan ciri and cir2 blink al Ihe same lima    it means you are entering in programing made On unit in heat pump mode    OFFunit in stand by    ON enter in function  menu ar RTC paramelars  ON it displays the size of cir  N  2 
181. ure pressure alarm differential from analogue input 0 1 25 0   C Dec  0 45       int  0 0 14 0 bar Dec  0 203 psi int  Oil Alarm  AL 11 Low oil pressure   level delay from digital input 250 Sec  AL 12 Minimum time for low oil pressure   level from digital input activation in normal 250 S    E ec  working condition   AL 13 Maximum number of low oil pressure level events   Always manual reset if AL13  0 0 16  Always automatic reset if AL13  16  From automatic to manual reset if AL13   1  15  Flow alarm  AL 14 Configuration  0  Not enabled  1  Only for chiller 0 3  2  Only for heat pump  3  For both chiller and heat pump  AL 15    Flow switch   supply fan overload    alarm delay after pump fun activation  0 250 Sec  AL 16 Maximum number of    flow switch supply fan    alarm events  Always manual reset if AL16   0 0 1 16  Always automatic reset if AL16  16  From automatic to manual reset if AL16  1  15  AL 17 Minimum    Flow switch   supply fan overload    active time duration  0 250 Sec  AL 18 Minimum    Flow switch   supply fan overload    not active time duration  0 250 Sec  Compressor overload alarm  AL 19 Compressor overload alarm delay after compressor start up 0 250 Sec  AL 20 Maximum number of compressor overload alarm events  Always manual reset if AL20   0 0 16  Always automatic reset if AL20  16  From automatic to manual reset if AL20  1  15  Pump down alarm  AL 21 Maximum number of pump down alarm events per hour in stop condition   After this number the alarm is logg
182. urning off the last compressor  the solenoid valve is closed  The compressor runs  until the pump down pressure switch connected to the digital input becomes active for a maximum time set in CO39    If the last compressor stops before the pump down pressure switch because of the CO39 time out  maximum compressor on time after  turning off the P D  solenoid valve   the ICHILL calculates the AL21 parameter  maximum number of pump down alarm per hour  and if  an alarm occurs the display will show the alarm code  the buzzer and the alarm relay will be on    If the thermoregulation is stopped via digital input  as remote off  or from chiller heat pump keys  during the pump down process the  chiller or the heat pump led will blink    When the next thermoregulation restarts the PD solenoid valve turns on and after 1 seconds  if the low pressure switch is not active  the  compressors start    If the compressors do not restart within the CO39 time the pump down alarm will signalled and the compressor are stopped  In this case  if AL23  0 the compressor can restart only if the pressure switch becomes active  or if AL23 1 and the number of alarms per hour  becomes  AL22 only after the manual reset    PAR CO36 3 OFF UNIT WITH PUMP DOWN in CHILLER MODE  No PUMP     DOWN at START UP   In Heat pump mode the Pump down process is inhibited and the solenoid valve works in parallel with the compressor     PAR  CO36 4 ON and OFF UNIT WITH PUMP DOWN      CHILLER MODE  In Heat pump mode the Pump d
183. urs it is completely locked    CO16   CO21 2 Compressor on     pump on   The alarm is managed only if one digital input is configured as flow switch  the restart is always automatic  in stand by or remote  OFF   pump off   it becomes manual after AL16 events per hour    During the functioning of the unit any flow alarm stop the loads described in the table  the water pump follow its regulation algorithm and  is turned off  after AL16 events per hours it is completely locked    MANUAL RESTART OF THE FLOW ALARM   After AL16 events hour it is necessary to enter the function Menu to reset the alarm itself  The alarm message DOES NOT DISAPPEAR  if the alarm condition is still on  The water pump  if configured  can start and the alarm is by passed for AL18 seconds    AL15 Alarm flow delay after on pump    When the water pump starts the AL 15 delay stops any flow alarm to reach the normal flow condition    AL16 Maximum number of flow alarm events per hour    It determines maximum number of flow alarm events per hour before change the unit restart from automatic to manual  when the alarm  becomes manual the water pump is locked    ATTENTION   With air water or water water units and CF01 1 2 the minimum number of events per hour is 1    AL 17 Active flow input duration   Within this time the flow alarm must be active and after AL17 is expired the alarm is signalled  The counter starts after AL15 and allows  to filter the improvise flow reduction or the possible bubbles of air    AL18 
184. verload Yes   C n dt Compressor high discharge temperature Yes   C n dS Compressor  n  disabled from keyboard Yes   C n Mn Compressor n  maintenane        n  identifies the compressor 1 2 3 4 5 6    Pg 94 103          1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    44 BLACK OUT    After the black out is restored    1  The instrument resores the same operating mode lost after the supply failure   2  Ifactive  the defrost is aborted    3  All the timers and time parameters are reloaded    4  The manual alarm is not reset     45 INSTALLING AND MOUNTING    45 1 PANEL CUT  OUT    The instrument must be mounted on vertical panel  with panel cut out 150x31mm  and screwed 2 screws   3 x 2mm  in between  distance 165mm  The IP65 can be reached with the gasket RG L  opzionale     The ambient working temperature range should be between 0 60      Avoid locations subject to heavy vibration  corrosive gases or  excessive dirt  The same applies to the probes  Ensure ventilation around the instrument        165  150    Fd    des          ge    45 2 PLEXIGLASS PROTECTION BOTTOM OPEN       45 3 PLEXIGLASS PROTECTION TOP OPEN    2 cuck       1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    45 4 METAL FRONT FRAME       45 5 VERTICAL BOARDS VI620     VI820 PANEL CUT OUT    The remote terminals are for panel mounting  panel cut out 72x56 mm  and screwed with two screws   The IP65 can be reached with the gasket RGW V  optional                            
185. wait the timeout     17 20 How TO DISPLAY THE TEMPAERATURE OF THE INTERNAL TEMPERAURE SENSOR OF THE  REMOTE TERMINALS 1 OR 2    Inside the funcion menu it is possible to see the ambient temperature detected by the NTC sensor    Pg 54 103    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    FUNCTION trEM to show the temperature of the remote panels   Identification label trEM    trE1 value of the NTC probe of the remote  1   trE2 value of the NTC probe of the remote  2   Select with UP or DOWN the trEM function   Push SET the trE1 or trE2 label is shown on the bottom display  the top display shows the probe value   Use the UP or DOWN arrow to change beteween trE1 or trE2 read out    To exit to the normal display read out push MENU or wait the time     out time     ATTENTION     THE trEm function and the labels trE1 or trE2 appear only if the CF74    2 or 3  remote panel 1 configuration  or if the parameter CF75    2 or 3  remote panel 2 configuration      18 ENERGY SAVING    18 1 ENERGY SAVING FROM DIGITAL INPUT    The energy saving is activated when one of the digital input configured as energy saving is ACTIVE    The energy saving activation is signalled by the SET key led on  When working in Chiller or HP the first pressure on SET key shows the  actual setpoint SetC  chiller  or SetH  HP  labels while the top display shows the set value    If the energy saving is active the next pressure on the SET key shows the label    SEtr     real setpoint   and the
186. y   2  Insert the hot key    3  Turn on the power supply    4  Immediately the parameters are downloaded    During the download the regulation is locked and the top display shows the    doL    blinking label  At the end of the download will appear    End  if the programming procedure is completely OK  after 30seconds the regulation starts automatically       Err    if the programming procedure has found an error and the parameter have not been transferred  In this case turn off and then on  the instrument supply to repeat the operation or remove the hot key  with power supply off  to restart the regulation     10 2 UPLOAD  How TO PROGRAM A           KEY  WITH THE PARAMETERS OF THE INSTRUMENT    Turn on the power supply    Insert the hot key    Enter the function Menu    Select the UPL function  on the bottom display     Push SET key and immediately the instrument starts transfer the parameters into the Hot key    During the upload the regulation is locked and the top display shows the    UPL    blinking label  At the end of the UPLOAD will appear    End  if the programming procedure is completely OK  after 30seconds the regulation starts automatically       Err    if the programming procedure has found an error and the parameter have not been transferred  Repeat the procedure    To exit the UPL function push the MENU key or wait the time out  15 sec      11 PROGRAMMING USING THE KEYBOARD    Through the instrument keyboard it is possible to enter the programming  In all the th
187. ycle  They turn  on when the 4 way valve change from heat pump to chiller and turn off only after the dripping time and the compressors restart    1592015300 User manual iCHILL 200 L GB   1 0 23 02 2005 Preliminary    ATTENTION   The support heaters are always off when   e        supply fan is not configured   e        supply fan is off   e The unit is in stand by or remote off  e The probe is faulty    23 4 CONDENSER ANTI FREEZE HEATERS REGULATION    The regulation dependes on the configuration of the heater circuit  1 relay and heater circuit  2 relay and the corresponding NTC  probes used to this control    The parameter Ar08 is used to select the heaters probe control both for chiller and heat pump    Par  Ar08   0  The thermoregulation  the alarm and the heater regulation are disabled    Par  Ar08 z 1  The thermoregulation  the alarm and the regulation of both the heaters together of the circuit 1 and 2 is excecuted only  through the condesner water inlet NTC probe    Par  Ar08   2  The thermoregulation  the alarm and the heater  1 regulation is executed through the condenser water outlet NTC probe  of the circuit  1    The thermoregulation  the alarm and the heater  1 regulation is executed through the condenser water outlet NTC probe of the circuit   2    ATTENTION   It is not possible to control the heaters of the circuit  1 with the NTC probe of the condenser water outlet of the circuit  2 and viceversa   Par  Ar08   3   The thermoregulation  the alarm and the regula
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
17730-212 - gruporacsa.net    Samsung NL20J7100WB Warming Drawer Oven User Manual(User manual)    FSW-0802/1201TX User's Manual  Samsung B1930HD Brugervejledning  Betriebsanleitung Operating Instructions I nstructions de  Rolls RM65 User's Manual      Copyright © All rights reserved. 
   Failed to retrieve file