BJ192M Panel Mounting Energy Meter User Manual Version

image

Contents

1. 12 6 OPERATING INSTRUCTIONS 13 7 SETUP PROCEDURE 14 7 1 Password Enter 14 7 2 System Display Settings 14 7 3 Input Signal Selection 16 7 4 Communication Preferences 20 7 5 Menu Structure 22 7 6 Display Character instructions 23 8 SAFETY CONSIDERATIONS 24 9 MAINTENANCE 9 2 9 2 22 22 2222 2 2 n ne 24 10 TECHNICAL SERVICE 25 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 2 i BLUE JAY Product Manual Technolog
2. i BLUE JAY Product Manual Technology of Electronic Automatic Directory CONTENTS Page 1 SUMMARIZE 3 2 APPLICATIONS 3 3 FEATURES 4 3 1 Electricity metering 4 3 2 Specifications 5 4 INSTALLATION AND START UP _ 7 4 1 Installation T 4 2 Connection Terminal see label on the rear part 8 4 3 Connection Drawing for the BJ192M 9X4 10 5 SCREEN DISPLAY 12 5 1 Panel Diagram 12 5 2 Display Summary
3. BLUE JAY Product Manual Tecnology of Electronic Automatic BJ192M Panel Mounting Energy Meter User Manual Version 1 1 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing i BLUE JAY Product Manual Technology of Electronic Automatic Read me When you use BJ192M 9X4 series Energy Meter be sure to carefully read this user manual and be able to fully understand the implications the correct guidance of operations in accordance with user manual which will help you make better use BJ192M 9X4 series Energy Meter and help to solve the various problems at the scene 1 Before the meter turning on the power supply be sure that the power supply within the provisions of the instrument 2 When installation the current input terminal must non open voltage input terminals must Non short circuit 3 Communication terminal RS232 or RS485 is strictly prohibited to impose high pressure 4 Be sure the instrument wiring consistent with the internal system settings 5 When communicating with the PC instrument communication parameters must be consistent with the PC Please read carefully before using this user manual Please save this document Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing
4. to choose item DISP You will see the meter show Display like this d i5P Press then enter the level 3 menu user can use and A to choose number 0 6 meaning as the following 0 Rotary screen display Meter can show data as this cycle Current Voltage Active power Reactive Power Power factor Frequency Active Energy Reactive Energy All 5 screens are successively shown at intervals of 5 s 1 5 Fixed screen 1 Three phase current display Meter display always three phase current data in 3 line LED display shows each phase current data 2 Three phase voltage display Meter display always three phase voltage data in 3 line LED display shows each phase voltage data 3 Active reactive power and power factor display On line 1 LED meter shows total active power data On line 2 LED meter shows total reactive power data On line 3 LED meter shows total power factor 4 Frequency display Meter display frequency data on line 1 LED 5 Active energy display Meter display active energy on 2 line LED show 8 digital data 2 decimal 6 Reactive energy display Meter display reactive energy on 2 line LED show 8 digital data 2 decimal Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 15 i BLUE JAY Product Manual Technology of Electronic Automatic 7 2 2 Clear ene
5. and current are not zero for this phase check out following points Assure that A B and C phases coincide in voltage and current Correct polarity Reverse the current transformer placed at this phase Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 11 BLU E JAY Product Manual Technology of Electronic Automatic 5 SCREEN DISPLAY 5 1 Panel diagram K DO amp mw BEGETS 4 6 8 c sa 5 2 Display Summary No Display Explanation Three lines 4 digital LED show power data include voltage current power power factor frequency etc And the contents of the programming menu 2 Indicator of the data Unit K means thousand M means million Digital display module Indicator of the current display 4 LED show the display module data reading data Enter key For menu selection and confirmation Used to open the menu and return to 5 Menu ke y previous menu Up and Down key Set the programming value Note Please see detail instructions of items at OPERATION MODE Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 12 BLU E JAY Product Manual Technology of Electronic Automatic 6 OPERATION MODE The instrument has three line disp
6. the wiring mode must match actual wiring or the reading data will go wrong 7 3 2 Choice voltage measure range In level 1 menu of INPT Choose item U SCL meter show like this inet ii ot Wo then press enter the level 3 menu user can change the voltage range tOr I Or j nP i nl i IIT or IIC WJ WJ z nn EEEE Lies Lia 400V Maximum measured value is 400V Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 17 i BLUE JAY Product Manual Tecnology of Electronic Automatic 100V Maximum measured value is 100V Note Select a different range will affect the accuracy of measurements if the accuracy is 0 5 Select 100V range means the minimum scale value is 0 5V 100 x 0 5 Select 400V range means the minimum scale value is 2V 400 x 0 5 7 3 3 Current measure range select In level 1 menu of INPT Choose I SCL meter show like this ini Sel then press enter the level 3 menu user can change the current range InP InP i Or ot Gel LICL L 5A Maximum measured value is 5A 1A Maximum measured value is 1A Note Select a different range will affect the accuracy of measurements if the accuracy is 0 5 S
7. xx xx xx r Phase phase votage v xx xx xx eme o a e de sxe Actveeneray dwn x x x xx Reactive energy vam x x lt xx Notes Phase phase voltage is Uab Ubc Uca voltage data determined by the different wiring Available x Display and communications xx Communications The 192M 9X4 delivers the visualization of above listed parameters by means of three line 4 digit led type displays Upper line for parameter indicate lower tow line total 8 digital for energy data read in the screen V Indicator LED shows currently displayed the parameters o K means in thousands o M means in million OTHER FEATURES Low size 96 x 96 mm panel mounting meter True R M S measuring system Energy measurement indication through two line 8 led Optional display total energy in the display RS 485 or RS 232 type communication to a PC optional Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 4 BLU E JAY Product Manual Technology of Electronic Automatic 3 2 Specifications 1 Reference standard Basic electricity GB T13850 1998 IEC688 1992 Active power GB T17215 2002 IEC61036 2000 Reactive power GB T17882 1999 IEC61268 1995 2 Accuracy standards aoe Voltage Current Active Energy Reactive Energy varh varh 3 Input Voltage Rated
8. 2 input 6 Current B phase S1 input 7 Current B phase S2 input 8 Current C phase S1 input 9 Current C phase S2 input 11 Voltage A phase input 12 Voltage B phase input 13 Voltage C phase input 14 Neutral Voltage input Three phase network 3 wires 4 5 6 7 8 9 41 12 13 14 Aphase Current C phase Current Ua Uc Ub 4 Current A phase S1 input 5 Current A phase S2 input 8 Current C phase S1 input 9 Current C phase S2 input 11 Voltage A phase input 13 Voltage C phase input 14 Voltage B phase input Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 9 BLUE JAY Product Manual Technology of Electronic Automatic 4 3 Connection Drawing for the BJ192M 9X4 a Three phase network 4 wires low voltage Power Supply whe ee aS M O ee 1 2 oo 29 BU 46 4 7 46 44 g 11 12 14 14 o ES a a Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 10 BLUE JAY Product Manual Tecnology of Electronic Automatic b Three phase network 3 wires low voltage Power Supply i 2 og 54 60 46 4r 46 48 11 12 13 14 IMPORTANT REMARK If power 0 01 is shown for any of the phases and voltage
9. 400V optional 100V Current Rated 5A optional 1A Frequency 45 65Hz 4 Load Voltage lt 0 5VA phase rated 220V Current lt 0 5VA phase rated 5A 5 Overload Current 1 2 times rated continuous 10 seconds for 10 times the rated Voltage 1 2 times the rated continuous 10 seconds for 800V 6 Dielectric strength IEC 688 IEC 255 3 1989 2kV AC RMS 1 minute between input output case power supply Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 5 BLU E JAY Product Manual Tecnology of Electronic Automatic 7 EMC Test po Standard Test voltage Electrostatic discharge immunity IEC 61000 4 2 test level 4 Electrical fast transient burst pe aa level 3 Input 1kV Power supply 2kV immunity test l IEC61000 4 5 common mode test voltage 8 Work environment Temperature 20 C 60 C Humidity RH 20 95 No condensation 9 Protection Panel IP40 10 Storage Conditions Temperature 25 C 70C Humidity RH 20 95 11 Working Power AC 80 265V 45 65Hz DC 80 380V DC 20 60V Optional Maximum power consumption 6W 12 Dimensions L x W x H 96mmx96mmx128mm 13 Installation hole size L x W 91 0 8mm x 91 0 8mm Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jian
10. BJ 192M once cabled and connected is seen to give an incoherent Power factor and Cos reading 0 01 or similar This is again a current transformer and voltage phase connection error phase A must correspond to the current transformer installed in phase A phase B must correspond to the current transformer installed in phase B and phase C must correspond to the current transformer installed in phase C This connection is clearly shown on the back of the analyzer 3 The BJ 192M is measuring in average voltage and is displaying the secondary voltage for example 110 volts Ensure that the voltage Transformer ratio has been correctly set see section on 7 3 4 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing mAs BLU E JAY Product Manual Tecnology of Electronic Automatic 4 The BJ 192M does not correctly display the current reading It shows values varying between 0 to 5 amps of current Ensure that the Transformer ratio has been correctly set once correctly set the current measurement shall be shown correctly see section on 7 3 5 For any inquiry about the instrument performance or whether any failure happens contact to Blue Jay s technical service Blue Jay After sales service Building 13 2 8 Jialing third village Pioneer Park Jiangbei District 400020 Chongqing Tel 0086 023 86850812 F
11. TA i Data Format Protocal Ine f Input protocal F Hani Format B ua e BOBO ens GLI word l IJI Word Mode a ERRI eeel a BYE P masas Ii L Three Line Net byte J Byte Mode E Three phase _ a AST aes w Wi h LI scl J JL L Voltage Range Varn E JI inn Reactive Powe Voltage L Transformation Fatio scl foci ee Current Range E I Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 23 BLUE JAY Product Manual Tecnology of Electronic Automatic 8 SAFETY CONSIDERATIONS All installation specification described at the previous chapters named INSTALLATION AND STARTUP INSTALLATION MODES and SPECIFICATIONS Note that with the instrument powered on the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts This instrument is factory shipped at proper operation condition 9 MAINTENANCE The 192M does not require any special maintenance No adjustment maintenance or repairing action should be done when the instrument open and powered on should those actions are essential high qualified operators must perform them Before any adjustment replacement maintenance or repairing operation is carried out the instrument must be disconnected from any power supply source When any protection failure is suspected to exist the i
12. aling third village Pioneer Park Jiangbei District Chongqing 13 i BLUE JAY Product Manual Technology of Electronic Automatic 7 SETUP PROCEDURE The SETUP procedure of the BJ192M 9X4 is performed by means of several SETUP options Once into the SETUP use the keyboard to select different options and enter required variables 1 Password enter 2 Choice of default initial screen 3 Input signal selection 4 Communication preferences 7 1 Password enter A 4 figure password is required to be entered in case that this password is not correct will not be set on the meter At normal display mode press Manu to enter the programming mode meter display then press 41 Lod 99599 Ask for the password Press and A to increase or decrease the number to switch password After password switch press _ to confirm the input Meter display If password is correct meter can enter next setting 7 2 System display settings 7 2 1 Choice of default initial screen This option allows choice among fixed or rotary screen After password you will see the meter show Set like this i Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 14 i BLUE JAY Product Manual Technology of Electronic Automatic Press to go to the level 2 menu use Y and A
13. ax 0086 023 67636974 E mail tech cqbluejay com Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 26
14. elect 1A range means the minimum scale value is 0 005A 1 x 0 5 Select 5A range means the minimum scale value is 0 025A 5 x 0 5 7 3 4 Voltage transformation ratio In level 1 menu of INPT Choose item T U meter show like this Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 18 BLU E JAY Product Manual Tecnology of Electronic Automatic then press enter the level 3 menu allowing us to set the current transformer net E it a CI jen C3 i Ii To write or modify the value just repeatedly press or pressing the key and or and Manu the instantaneous at the same time value can increase or decrease the number x10 Input value is 1 9999 Ome Note The input values represent the voltage transformer primary side voltage secondary side voltage Secondary side voltage is 100V or 400V user set it at section 7 3 2 7 3 5 Current transformation ratio In level 1 menu of INPT Choose the item T I meter show like this Pi i 1 7 i 25 aes then press enter the level 3 menu allowing us to set the current transformer B Pi in ewes E E To write or modify the value just repeatedly press or pressing the key AN and or and Manu the
15. gbei District Chongqing 6 BLUE JAY Product Manual Tecnology of Electronic Automatic 4 INSTALLATION AND START UP The manual you hold in your hand contains information and warnings that the user should respect in order to guarantee a proper operation of all the instrument functions and keep its safety conditions The instrument must not be powered on and used until its definitive assembly on the cabinet s door If the instrument is not used as manufacturer s specifications the protection of the instrument will be damaged When any protection failure is suspected to exist for example it presents external visible damages the instrument must be immediately powered off In this case contact a qualified service representative 4 1 Installation Mounting Instrument is to be mounted on panel cut out 91 0 8 x 91 0 8 mm All connections keep inside the cabinet Note that with the instrument powered on the terminals could be dangerous to touching and cover opening actions or elements removal may allow accessing dangerous parts Therefore the instrument must not be used until this is completely installed Notes Input signal BJ192M using a separate acquisition calculate for each measurement channel to ensure consistent in use for different load forms its a variety of connection mode A Voltage input Input voltage should not exceed the rated input voltage products 100V or 400V Otherwise should use externa
16. instantaneous at the same time value can increase or decrease the number x10 Input value is 1 9999 e a ons Co Co Note The input values represent the current transformer primary side voltage secondary side current secondary side current is 1A or 5A user set it at section 7 3 3 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 19 i BLUE JAY Product Manual Technology of Electronic Automatic 7 4 Communication Preferences Press Manu return to level 1 menu In this section user will set 1 Meter communication address 2 Baud rate 3 Communication format 4 Data format Note Not all the meter have communication function please make sure your purchase meter first if no communication mode you can skip this section 7 4 1 Meter communication address setting One or some BJ194 meter can be connected to a P C With this system we can get all the parameters in one central point of reading The BJ194 has a serial RS 485 or RS 232 type output according to the model If we connect more than one device to the same communication line RS 485 we have to assign to each of them a different code or direction from 1 to 247 since the P C needs the identification of every measuring point In level 1 menu choose the item CONN the meter show like this Lo
17. l Technology of Electronic Automatic 7 5 Menu Structure Only when the correct password to enter programming e default password is The default d is 0001 Select the display mode Syst t SET automatic or individual ystem se CLR E Oo Energy will clear after confirmed Net NET N 34 and N33 Select the input signal network Di Di measurement Voltage Range 400V and 100V Select the range of measured U SCL voltage signal Password data Password CODE 9999 Current Range 5A and 1A Select the range of measured Signal input ILSCL current signal INPT t oe ti 1 9999 Setting voltage signal a a rae Fane transformation ratio 1 2 scale Current Setti l i etting current signal ie ratio iii transformation ratio 1 2 scale Address SN 1 247 Instrument address range 1 247 o Orare on Communication Parameters BAUD 4800 9600 Baud Rate 4800 9600 CONN speed BAU Protocol PROT Word or Byte Factory default communication communication mode for the word Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 22 BLU E JAY Product Manual Technology of Electronic Automatic 7 6 Display Character instructions Panel Display Panel Display OBAO on 1 OO Transformation Set Zi set Conn L EINE Communication ARE oe a bot E Communication Bright baud J H uO Baud Rate A er E Clear DA
18. l CT the input voltage to be installed in the 1A fuse B Current Input Standard input current is 5A if greater than 5A should use external CT Even if you are using on the CT are connecting with other instruments wiring methods should be used in series Before remove the current input connection must be sure to disconnect the primary circuit or shorted secondary circuit of CT Suggest using the terminal block please not directly connect to CT in order to facilitate disassembly C Please make sure that the input voltage and current corresponding to the same phase Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 7 i BLUE JAY Product Manual Technology of Electronic Automatic sequence and the same direction Otherwise the Values and symbols will wrong Power and Energy The input network configuration of instrument depends on the CT number of the system in the condition of 2 CT select the three phase three lines two components in the condition of 3 CT select the three phase four lines three component mode Instrument connection mode set of the instrument programming input network NET should be the same load wiring as measured wiring Otherwise the measurement instrument will lead to incorrect voltage or power In three phase three wire mode the measurement and shows the line voltage In three phase fou
19. lays Each one has also a LED type indicator red colour Every led will be on according to the parameter presently shown in screen When the 192M 9X4 is powered up all the LED indicator will on and meter start self test after some seconds the meter is ready for operation and shows one of the available screens Parameters on display can be switch by pressing the key or A LED on the right indicates the parameters shown on screen at any moment When the first led red is on it means that VOLTAGE values are shown on screen that is the user can read the voltage of the A phase Va voltage of the B phase Vb and voltage of the C phase Vc Whether the key is press the next led will be on so indicating that for this screen CURRENT values of each phase are now shown Pressing again the key the next led will be on and the screen will shown following parameters and so successively At programming display mode press and to increase or decrease the value pressing the key and Manu or and Manu the instantaneous at the same time value can increase or decrease number x10 Pressing the Manu key can open the programming menu and return to previous menu Pressing the Enter key you exit it with saving any modification that you might have done in menu operation press Enter key user can go to the next menu Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Ji
20. nn Then press enter the level 2 menu choose the item SN meter show like this Loan gn Then press to level 3 menu to write or modify the value just repeatedly press or pressing the key and or and the instantaneous at the same time value can increase or decrease the number x10 Input value is 1 247 Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 20 BLUE JAY Technology of Electronic Automatic Product Manual 7 4 2 Communication Baud rate setting In level 1 menu of CONN Choose item BAUD meter show like this Loan bHUd then press enter the level 3 menu allowing us to set the Baud rate 4800 or 9600 Lonn Lonn baud io Or DAHLU id qgop gs00 7 4 3 Choose communication format In level 1 menu of CONN Choose item Protocol meter show like this onn ol then press enter the level 3 menu allowing us to set the Word communication or Byte communication Factory setting word communication LONN Tel 0086 023 86850812 Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing Email tech cqbluejay com 2 i BLUE JAY Product Manua
21. nstrument must be immediately put out of service The instrument s design allows a quick replacement in case of any failure Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 24 i BLUE JAY Product Manual Technology of Electronic Automatic 10 TECHNICAL SERVICE FAQ s 1 The BJ 192M Energy Meter once cabled and connected is seen to give a correct voltage and current reading but shows negative values for active power generation This is an error with the cabling for the current transformer secondary the direction of the transformer current has to be respected as shown in the connection diagram The current transformers have a two face primary the current must pass from P1 to P2 giving the result in secondary S1 and S2 of 5 amps The error stems from a The current transformers have been incorrectly installed As a result it gives the direction of the current as passing from P2 to P1 to resolve this problem the current transformer does not have to be dismantled and installed again but the transformer secondary S1 and S2 just has to be inverted b The connection of the current secondary in the current transformers have been incorrectly connected to resolve this problem just connect the S1 transformer secondary to the S1 on the meter and the S2 on the current transformer to the S2 on the meter The
22. r wire mode the measurement and shows the phase voltage Auxiliary power BJ192M Series Energy Meter with universal AC DC power input if not for a special statement we provide the 220VAC DC or 110VAC DC power interface for standard products Instruments limit work power supply AC DC 80 270V please ensure that the auxiliary power can match for BJ192M series meter to prevent damage to the product A Suggest install 1A fuse in the fire line side B For the areas with poor power quality suggest install lightning surge suppressor and rapid burst suppressor to prevent lightning strikes 4 2 Connection terminal see label on the rear part Terminal description Upper connection terminal af 2 s s9 60 4647 48 49 Power supply RS485A RS4858 GUD AP AP Re RP 1 Supply voltage input 0 V 2 Supply voltage input 220 Va c 58 RS 485 59 RS 485 60 RS 485 GND 46 Active energy Pulse output 47 Active energy Pulse output 48 Reactive energy Pulse output 49 Reactive energy Pulse output Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 8 i BLUE JAY Product Manual Technology of Electronic Automatic Lower connection terminal Three phase network 4 wires 4 5 6 7 8 9 41 12 13 14 4 Current A phase S1 input 5 Current A phase S
23. rgy counters In Set menu user can deleting energy counters Enter Set menu in level 2 menu use and A to choose item CLr E meter show like this Cer Jt il LL rE Press to confirm clear all the energy data meter display C ll SKRUE ICE JCD And then press _ again to save the operation and exit 7 3 Input signal selection Press return to level 1 menu In this section user will set 1 Input net mode 2 Voltage measure range select 3 Current measure range select 4 Voltage transformation ratio 5 Current transformation ratio 7 3 1 Choice the input net mode In level 1 menu use AV and to choose item INPT meter show like this inet Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 16 i BLUE JAY Product Manual Technology of Electronic Automatic then press enter the level 2 menu choose NET meter show Talai nei then press again enter the level 3 menu Use and to select the right wiring mode meter show like this InP InP mei x mei sy GJJ N 3 4 Three phase four wire wiring reference section 4 3 a N 3 3 Three phase three wire wiring reference section 4 3 b Note Select
24. y of Electronic Automatic 1 SUMMARIZE BJ192M 9X4 Series Energy Meter is used for power quality monitoring factory automation and building automation It can measure all of the power parameters in power grid Current Active Energy Voltage Reactive Energy BJ192M 9X4 also can provide 2 channel pulse output Used in generators motors of the distributed detection and any other three phase AC grid energy measurement automatic control system on line monitoring display It can replace the traditional mechanical type energy meter with higher measurement accuracy convenient on site wiring improve system reliability BJ192M 9X4 Energy Meter has serial port can connection to PC Uses Modbus to set programming and read the data Based on this energy meters can simply set up a monitoring system that only use the IPC and central software 2 APPLICATIONS Basic electrical parameter measurement Energy Measurement Replace the mechanical type three phase energy meter Medium and low pressure systems SCADA EMS DCS integrators Tel 0086 023 86850812 Email tech cqbluejay com Fax 0086 023 67636974 Add Building 13 2 8 Jialing third village Pioneer Park Jiangbei District Chongqing 3 i BLUE JAY Product Manual Tecnology of Electronic Automatic 3 FEATURES 3 1 Electricity metering By means of an internal microprocessor it simultaneously measures fon fn E Single phase voltage v