Home
        Auto-Ohm 200 S3 / DMOM-200 S3 / DMOM-600
         Contents
1.    Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2       Press the  STOP  key to return to the     START UP    menu        Press the  v  key  The test record  details will be displayed as shown  below        Press the  STOP  key to return to  the    START UP    menu     2  PRINTTO PRINTER    Press the  2  key  PRINT TO  PRINTER  to print the test results on  the unit   s built in thermal printer   The test results will be printed and  you will be returned to the    START   UP    menu        REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL    3 5 2  Saving Test Results to a Test Record    After performing a test  the user is presented the option to save the test results to the unit   s  Flash EEPROM or to a USB Flash Drive  If the test results are not saved immediately after  performing a test  they will still remain in the working memory and can be saved later  as long  as a new test has not been performed and the unit has not been turned off  Follow the steps  below to save the test results from the working memory to a test record  the following  procedure can also be used to re save a restored test record to a new memory location or to a  USB Flash Drive      a  Performatestor restore a test record to the working memory  see section 3 5 3 and  3 5 4   and then start from the    START UP    menu         Press the  2  key  SETUP      b  The following screen will be displayed     Press the  3  key  SAVE RESTORE RECORD     c  The following screen will b
2.    RESTORE RECORD  L EHTER RECORD HUMBER  2   SCROUC TO SELECT         If you have a USB Flash drive inserted in the unit   s    USB MEM    port  the  following screen will be displayed instead of the above screen           NOTE 1  IMNTERM amp L STORAGE  2 THUME DRIVE             Press the  1  key  INTERNAL STORAGE    The following screen will be displayed   RESTORE RECORD    1 EHTER RECORD HUMBER  2  SCROLL TO SELECT       Continue with the steps below     1  ENTER RECORD NUMBER    Press the  1  key  ENTER RECORD NUMBER  if you know the record number that  you would like to restore     1 1  The following screen will be displayed     RESTORE RECORD  HUMBER        Type the record number using the alpha numeric keypad and then press  the  ENTER  key     i IR    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       1 2  The following screen will be displayed     RECORD RESTORED   REVIEM RECORD   dl  vES  Za  HO                   Press the  1  key  YES  to display the test record     1 3  The basic information about the restored test record will be displayed as  shown     Bie  i ll ATi qiz    HUM TESTS  1       Press the  v  key  The test record details will be displayed as shown     TEST HUMBER  1  TEST CURRENMT  ZIA  RAMP  SS BURM  SS    CUR  25 810  RES  497 UO       Press the  STOP  key to return to the    START UP    menu  The restored  test record will remain loaded in the working memory     2  SCROLL TO SELECT    Press the  2  key  SCROLL TO SELECT  to scroll 
3.    b  The following screen will be displayed        RECORD ID     REVIEW RECORD      SAYE RESTORE RECORD    SET MIME      SET LANGUAGE                   Press the  3  key  SAVE RESTORE RECORD      c  The following screen will be displayed     a RESTORE RECORD      SAVE RECORD      RECORD DIRECTORY     ERASE RECORD   a CORY TO THUME DRIVE                   Press the  5  key  COPY TO THUMB DRIVE      REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       d  The following screen will be displayed   COPY REC TO THUME DEN    1 COP       SINGLE RECORD  2  COPY ALL RECORDS       1  COPY SINGLE RECORD    Press the  1  key  COPY SINGLE RECORD  to copy a single test record from the  unit   s Flash EEPROM to the connected USB Flash drive  The following screen will  be displayed     ENTER RECORD HUMBER  TO COPY TO FLASH DRY    HUMBER        Type the record number using the alpha numeric keypad and then press the   ENTER  key  The test record will be copied to the USB Flash drive and the  following screen will be displayed     REC 813 SAVED TO  THUMB DRIVE       Press any key to return to the    START UP    menu     Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       2  COPY ALL RECORDS    Press the  2  key  COPY ALL RECORDS  to copy all test records from the Auto   Ohm s Flash EEPROM to the connected USB Flash drive  All test records will be  copied from the unit to the connected USB Flash drive  The following screen will  be displayed when the process is fin
4.   and DMOM 600 operate on voltages between 120 240  Vac  50 60 Hz     2 2 LCD Screen Contrast Control    To increase the LCD screen contrast  press and hold the  A  key for two seconds  Release the  button when the desired contrast level has been reached     To decrease the LCD screen contrast  press and hold the  v  key for two seconds  Release the  button when the desired contrast level has been reached     2 3 Safety Ground    Always ground the Auto Ohm S3 to the substation ground before connecting test cables to the  circuit breaker     2 4 Printer Paper  DMOM 200 S3 and DMOM 600 Only     The DMOM 200 S3 and DMOM 600   s built in thermal printer uses 2 5 inch wide thermal paper  for printing test results  To maintain the highest print quality and to avoid paper jams  the use  of thermal paper supplied by Vanguard Instruments Company is highly recommended   Additional paper can be ordered from the following sources     Vanguard Instruments Co  Inc   1520 S  Hellman Avenue  Ontario  CA 91761   Tel  909 923 9390   Fax  909 923 9391   Part Number  VIC TP 3 paper    BG Instrument Co    13607 E  Trent Avenue  Spokane  WA 99216   Tel  509 893 9881   Fax  509 893 9803   Part Number  VIC TP 3 paper       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2    3 0 OPERATING PROCEDURES  3 1 Connection Diagrams       100000200000   TOYO    jHIWVSS  WOMEN MOOS                                                   Figure 8  Typical Auto Ohm S3 Connection Diagram    008000000008  JA
5.   to print the test  results on the unit   s built in thermal  printer  sample test results printouts are  shown in Figure 10 and Figure 11   The  following screen will be displayed     KEEF THIS READING   LES  2   HO                   Press the  1  key  YES  to save the reading     If you had saved a test reading before the current test  the data will still be in    the unit   s working memory  The following screen will be displayed   PREVIOUS DATA IH BUF    APPEHD PREY DATA  2  CLEAR PREV DATA    3  SAVE PREY DATA AND  START HEH RECORD       3  APPEND PREV DATA  Press the  1  key  APPEND PREV DATA  to append the current test  reading to the previous test record    4  CLEAR PREV DATA  Press the  2  key  CLEAR PREV DATA  to erase the previous reading  from the test record and replace it in the working memory with the  current test reading    5  SAVE PREV DATA AND START NEW RECORD  Press the  3  key  SAVE PREV DATA AND START NEW RECORD  to save  the previous test reading in a test record and then create a new test    i IR    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       The following screen will be displayed        Press any key to continue     The following screen will be displayed        Press the  2  key  NO      The following screen will be displayed     Press the  1  key  YES  to save the test record     The following screen will be displayed        Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2     SAVE INTERMALL       SAVE TO THUMB D
6.  Record From a USB Flash Drive                  iii 45  3 5 5  Copying Test Records to a USB Flash Drive            cccssccccssssececeesseeeeessseeeessseeeeeeeees 48  3 5 6  Viewing the Test Record DIrectory             i 51  3 5 7  Erasing Test Records from the Flash EEPROM                     53  3 5 8  Erasing Test Records from a USB Flash DrIVe               i 58   4 0 Getting the Latest Firmware  Software  and ManualSs              ii 61       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       LIST OF TABLES    Table 1  Auto Ohm 200 S3 Technical SpecificatiOnS                   9  Table 2  DMOM 200 S3 Technical Specifications                   10  Table 3  DMOM 600 Technical Specifications    11    LIST OF FIGURES    Figure 1  Furnished Current and Sense Combination Cables                  7  Figure 2  Furnished Current Cable and Sense Cables for DMOM 600                                 7  Figure 3  Optional Cable with C Clamp    ssciicar a e a 8  Figure 4  Optional Hand Spike  ria 8  Figure 5  Auto Ohm 200 S3 Controls and Indicators                  i 12  Figure 6  DMOM 200 S3 Controls and Indicators              uccisi 13  Figure 7  DMOM 600 Controls and Indicators                  14  Figure 8  Typical Auto Ohm S3 Connection Diagram                i 16  Figure 9  Typical Auto Ohm S3 Connection Diagram with Dual Ground Option                           16  Figure 10  Sample DMOM 200 S3 DMOM 600 Printout                        i 32  Figure 11  Sample DM
7.  of 100 120 Vac  the maximum    recommended test current is 300A   NOTE    If you had selected the normal test mode  continue to step e   If you had selected the automatic test mode  continue to step f       For an automatic test  the burn in time is 5 seconds and cannot be    changed   NOTE    i E    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       e  The following screen will be displayed        Select the burn in time by pressing the corresponding numeric key on the keypad     f  The following screen will be displayed           Select the ramp time by pressing the corresponding numeric key on the keypad     Ramp Time Burn in Time Ramp Time    Test Current       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       g  The test parameters summary screen will be displayed as shown below   TEST PARAMETERS  CURRENT  56 AMPS  BURH IH  AUTO  RAMP  SaR     START  TO RUM TEST       Press the  START  key to start the test     h  The following screen will be displayed temporarily     AUTO TEST MODE    The screen will be updated as shown below while the current is being ramped up     RAMPIHNG CURRENT  12  30A 2T     TEST IH PROGRESS          Once the current is ramped up to the selected test current  the initial test results will be  displayed and the burn in sequence will be initiated  The following screen will be  displayed if the continuous burn in time was NOT selected in step e     BURNING IN  604    437 uQ    QU il A    TEST IN PROGRESS          REV 2 Au
8.  screen will be displayed     1  ENGLISH  Za TURKISH  3  SPANISH       Select the preferred interface language by pressing the corresponding key on the  keypad   1    2   or  3    The interface language will be set and a confirmation screen  will be displayed as shown below     ENGLISH SET       Press any key to return to the    START UP    menu     I S     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 4 Testing Procedures  3 4 1  Entering Test Record Header Information    You can enter the test record header information before performing tests  The record header  includes identifying information such as the company  station  circuit  manufacturer  etc  Once  the header information has been set  it will apply to all subsequent test records  Follow the  steps below to enter the test header information     a  Start from the    START UP    menu     1  FUH TEST   a SUE   Za QUICE TEST  TIME  145 Zir 34  DATE  65 24 11                   Press the  2  key  SETUP      b  The following screen will be displayed           RECORD IT   REVIEM RECORD      SAVYE RESTORE RECORD     SET TIME      SET LANGUAGE          OF E LH Po je       Press the  1  key  RECORD ID      c  The following screen will be displayed     COMPANY     Te  TO POSITION   ENTER  TO ACCEPT       Type the company name using the keypad  Press the  ENTER  key when you are done  typing the company name        Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    d  The following screen wi
9. 0A  1   1 micro ohm    1 Ampere to 200 Amperes  selectable in 1A steps    Thermally protected DC power supply    Backlit LCD  128 x 64 pixels   viewable in direct sunlight and low light levels  Rugged  44key  QWERTY  membrane keypad  128 test records  Each record can contain up to 64 readings    Up to 999 test records on external USB Flash drive     RS 232C  Windows XP Vista 7 Analysis Software  included with purchase   Designed to meet IEC 61010  1995   UL 61010a  and CASC22 2 standards    Operating  10  C to 50  C  15  F to  122  F   Storage  30  C to 70  C  22  F to  158  F     90  RH   40   C  104   F  non condensing  2000m  6562 ft  to full safety specifications  30 ft  9 1 m    1 AWG test cables  power cord  ground cable    Shipping case  15 ft test cables  C Clamp set  Hand Spike Set  Dual Ground  option    One year on parts and labor          Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    1 6    DMOM 200 S3 Technical Specifications    Table 2  DMOM 200 S3 Technical Specifications    TYPE  PHYSICAL SPECIFICATIONS  INPUT POWER    RESISTANCE READING  RANGE    ACCURACY    TEST CURRENT RANGE    DISPLAY  KEYPAD    INTERNAL TEST RECORD  STORAGE    EXTERNAL TEST RECORD  STORAGE    COMPUTER INTERFACE  PRINTER   PC SOFTWARE  SAFETY   ENVIRONMENT    HUMIDITY  MAX   ALTITUDE  MAX   CABLES  OPTIONS    WARRANTY    Portable Micro Ohmmeter   18    W x 7    Hx 15    D  45 7cm x 17 8cm x 38 1cm   Weight  19 8 Ibs  8 9 Kg   100 240 Vac  14A  50 60Hz   10 milliohms at 
10. 16 8    W x 12 6    H x 12    D  42 7cm x 32cm x 30 5cm   Weight  33 Ibs  15 Kg     100 120 Vac  20A  50 60 Hz     Up to 300A load  220 240 Vac  20A  50 60Hz     Up to 600A load    1 milliohm at 600A to 450 milliohms at 10A    10A to 49 9A  1   2 micro ohms  50A to 600A  1   1 micro ohm    10 Amperes to 600 Amperes  selectable in 1A steps   Thermally protected DC power supply    Backlit LCD  128 x 64 pixels   viewable in direct sunlight and low light levels  Rugged  44key  QWERTY  membrane keypad  128 test records  Each record can contain up to 64 readings    Up to 999 test records on external USB Flash drive     RS 232C   Built in 2 5    wide thermal printer   Windows XP Vista 7 Analysis Software  included with purchase    Designed to meet IEC 61010  1995   UL 61010a  and CASC22 2 standards    Operating  10  C to 50  C  15  F to  122  F   Storage  30  C to 70  C  22  F to  158  F     90  RH   40   C  104   F  non condensing   2000m  6562 ft  to full safety specifications   15 ft  4 6 m    1 0 AWG test cables  power cord  ground cable  Shipping case  C Clamp set  Hand Spike Set  Dual Ground option    One year on parts and labor       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       1 8 Auto Ohm 200 S3 Controls and Indicators    The Auto Ohm 200 S3   s controls and indicators are shown in Figure 5  The purpose of the  controls and indicators may seem obvious  but users should familiarize themselves with them  before using the Auto Ohm 200 S3  Accidental mis
11. 200 A to 5 ohms at 1A    1A to 4 99A  1   10 micro ohms  5A to 9 99A  1   2 micro ohms  10A to 200A  1   1 micro ohm    1 Ampere to 200 Amperes  selectable in 1A steps    Thermally protected DC power supply    Backlit LCD  128 x 64 pixels   viewable in direct sunlight and low light levels  Rugged  44key  QWERTY  membrane keypad  128 test records  Each record can contain up to 64 readings    Up to 999 test records on external USB Flash drive     RS 232C   Built in 2 5    wide thermal printer   Windows XP Vista 7 Analysis Software  included with purchase    Designed to meet IEC 61010  1995   UL 61010a  and CASC22 2 standards    Operating  10  C to 50  C  15  F to  122  F   Storage  30  C to 70  C  22  F to  158  F     90  RH   40   C  104   F  non condensing  2000m  6562 ft  to full safety specifications  30 ft  9 1 m    1 AWG test cables  power cord  ground cable    Shipping case  15 ft test cables  C Clamp set  Hand Spike Set  Dual Ground  option    One year on parts and labor          REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL    1 7    DMOM 600 Technical Specifications    Table 3  DMOM 600 Technical Specifications    TYPE  PHYSICAL SPECIFICATIONS  INPUT POWER    RESISTANCE READING  RANGE    ACCURACY  TEST CURRENT RANGE    DISPLAY  KEYPAD    INTERNAL TEST RECORD  STORAGE    EXTERNAL TEST RECORD  STORAGE    COMPUTER INTERFACE  PRINTER   PC SOFTWARE  SAFETY   ENVIRONMENT    HUMIDITY  MAX   ALTITUDE  MAX   CABLES  OPTIONS  WARRANTY    Portable Micro Ohmmeter  
12. 600 USER S MANUAL       e  The following screen will be displayed   ERASE RECORD    1 ERASE SIHGLE REC   Z ERASE ALL RECORDS    SlpPs TO EAT       1  ERASE SINGLE REC     Press the  1  key  ERASE SINGLE REC   to erase a single test record from the  connected USB Flash drive  The following screen will be displayed     ERASE THUME DRIVE    RIEG       Type the record number that you would like to erase using the alpha numeric  keypad and then press the  ENTER  key  The test record will be erased from the  USB Flash drive and the following screen will be displayed     THUME DRIVE REGGI  ERASED        Press any key to continue  You will be returned to the beginning of step e  Press the   STOP  key to return to the    START UP    menu     2  ERASE ALL RECORDS    Press the  2  key  ERASE ALL RECORDS  to delete all test records from the connected  USB Flash drive  The following warning screen will be displayed     ERASE ALL THUMB DRIVE  RECORDS     ARE YOU SURE        ENTER    T0 CONTINUE        Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       Press the  STOP  key if you do not want to erase all the test records  You will be  returned to the    START UP    menu     Press the  ENTER  key to proceed with deleting all the test records from the  connected USB Flash drive  The following screen will be displayed when all the  records have been erased        Press any key to return to the    START UP    menu        REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MA
13. Auto Ohm 200 S3   DMOM 200 S3   DMOM 600  True DC Digital Micro Ohmmeters    USER S MANUAL       Vanguard Instruments Company  Inc   1520 S  Hellman Ave     Ontario  California 91761  USA    TEL   909  923 9390 July 2014    FAX   909  923 9391 Revision 2 2       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2       SAFETY SUMMARY    This manual applies to the Auto Ohm 200 S3  the DMOM 200 S3  and the DMOM 600 digital micro ohmmeters   The operating procedures are virtually the same for all three models  and any differences are clearly described  where applicable     FOLLOW EXACT OPERATING PROCEDURES  Any deviation from the procedures described in this user s manual may create one or more safety hazards   damage the Auto Ohm 200  3 DMOM 200 S3 DMOM 600  or cause errors in the test results  Vanguard  Instruments Co   Inc  assumes no liability for unsafe or improper use of the Auto Ohm 200  3 DMOM 200  S3 DMOM 600  The following safety precautions must be observed during all phases of test setup  test hookups   testing  and test lead disconnection     SAFETY WARNINGS AND CAUTIONS  The Auto Ohm 200 S3 DMOM 200 S3 DMOM 600 shall be used only by trained operators  All circuit breakers  under test shall be off line and fully isolated     SERVICE AND REPAIR  e Do not install substitute parts or perform any unauthorized modification to any Auto Ohm 200 S3 DMOM 200  S3 DMOM 600 test unit   e Repairs must be performed only by Vanguard Instruments Company factory personnel o
14. MANA  aacoanaS    NAVA              x                               Figure 9  Typical Auto Ohm S3 Connection Diagram with Dual Ground Option    i y     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 2 Setting the Date and Time  To set the date and time     a  Start from the    START UP    menu     L ELUH TEST  FSB   3  QUICK TEST  TIME  145 21354  DATE  Bae 24 11                   Press the  2  key  SETUP      b  The following screen will be displayed     RECORD ID   REVIEM RECORD  SAVE RESTORE RECORD  DSETORINE   SET LANGUAGE                LI AHI       Press the  4  key  SET TIME     c  The following screen will be displayed   ENTER DATE    MM i  Y       Type in the date using the keypad  The following screen will be displayed   SS TIHE    HH  Ms SS       Enter the time using the alpha numeric keypad  When the time has been entered  you  will be immediately returned to the    START UP    menu     C    Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       3 3 Setting the Interface Language  Follow the steps below to set the interface language  English  Spanish  or Turkish      a  Start from the    START UP    menu     i FUH TEST  2a SE TUE   z  QUICK TEST  TIME  145 21534  DATE  GS  z4 11                   Press the  2  key  SETUP      b  The following screen will be displayed        RECORD ID      REVIEW RECORD      SAVYE RESTORE RECORD    SET  TIME      SET LANGUAGE                   Press the  5  key  SET LANGUAGE      c  The following
15. MBER 1  HAS EEEH SAVED        2  SAVE TO THUMB DRIVE  Press the  2  key  SAVE TO THUMB DRIVE  to save the test record to  the connected USB Flash drive  The following screen will be displayed   REC BEG SAVED TO  THUME DRIVE       Press any key to return to the    START UP    menu     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 5 Working With Test Records  3 5 1  Viewing the Contents of the Working Memory    Whenever a test is performed and the reading is kept  the data is temporarily stored in the  Auto Ohm   s working memory  You can view the test reading in the unit   s working memory  using the steps below     a  Start from the    START UP    menu     La FUR TEST  COSETTE   Soa UTCE TEST  TIME  145 21354  DATE  BS 24 11                   Press the  2  key  SETUP      b  The following screen will be displayed     RECORD ID   REVIEM RECORD  SAVE    RESTORE RECORD  Ser WINE   SET LANGUAGE                UL LH jb        Press the  2  key  REVIEW RECORD    c  The following screen will be displayed   Auto Ohm 200 S3 DMOM 200  3 DMOM 600    The basic test record information will be PRIHT RECORD  1  PRINT TO LCD  2  PRINT TO PRINTER    displayed as shown   BS 26 11 ATr4z 23    HUM TESTS  1       1  PRINT TOLCD    Press the  1  key  PRINT TO LCD  to  display the test results on the unit   s  LCD screen  The basic test record  information will be displayed as  shown     C       Press the  v  key  The test record details  will be displayed as shown below     
16. NUAL    4 0 Getting the Latest Firmware  Software  and Manuals    The latest firmware  software  and user s manuals can be downloaded from the Vanguard    Instruments Company   s web site at http   www vanguard instruments com  In order to    download these items from our site  you will first need to sign up for a FREE user account on  our site  Also  your account must be approved before it can be used to download firmware   software  and user s manuals  Follow the steps below to sign up for an account and download  the latest firmware  software and user s manuals     a  Visit our site at http   www vanguard instruments com     b  Onthe left hand side of the page  click on the    Create new account    link     Username              Password                    Create new account    Request new password  c  You will be presented with a sign up form  Please complete all the required fields on the  form and click on the    Create new account    button at the bottom of the page     d  Once your account has been created  it will be reviewed by our staff and usually  approved within the hour during regular business hours     e  Once you have received the account approval email  visit our site again at    http   www vanguard instruments com and login to your account using your username    and password     f  Click on the    Downloads    link at the top of the page     Products v Find a Sales Rep v Downloads v Contact Us About    All Downloads    Software Firmware Downloads       g  T
17. OM  200       10 200A True DC Low Resistance Meter    BHEEHeBou00Rt     ojuami  onaniaa      Le  w  Le    sE  HE NONE ML       Voltage Sensing Current Rugged     QWERTY    Style 2 5    Wide  Connector Jacks Lead Connectors Membrane Keypad Thermal Printer    Figure 6  DMOM 200 S3 Controls and Indicators       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       1 10 DMOM 600 Controls and Indicators    The DMOM 600 s controls and indicators are shown in Figure 7  The purpose of the controls  and indicators may seem obvious  but users should familiarize themselves with them before  using the DMOM 600  Accidental misuse of the controls will usually cause no serious harm   Users should also familiarize themselves with the safety summary information found on the  front page of this User s Manual     Current Sensing RS 232C USB Back Lit LCD Screen Circuit Input Power Ground  Connector Jacks Computer Flash Drive  128 x 64 pixels  Breaker Connector with Stud  Interface Interface Viewable in direct  25A  Third wire  sunlight and low light Safety Ground    120 240 Vac 12A  50 60 Hz     19     O0NSO0nDOOL  IMEEM O   EDEN LWUYWVEE  HEY NE MNULE       Current Voltage Sensing Rugged  2 5    Wide  Lead Connector Jacks    QWERTY    Style Thermal Printer  Conenctors Membrane Keypad    Figure 7  DMOM 600 Controls and Indicators       REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       2 0 PRE TEST SETUP    2 1 Operating Voltages    The Auto ohm 200  3  DMOM 200 S3
18. OM 200 S3 DMOM 600 Printout  with Dual Ground Option                    32    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       CONVENTIONS USED IN THIS DOCUMENT    This document uses the following conventions     The general term    Auto Ohm S3    is used in this manual to refer to the Auto Ohm 200 S3   the DMOM 200 S3  and the DMOM 600     A key  switch  or knob on the Auto Ohm S3 is indicated as  KEY    SWITCH    KNOB    Menu names are referenced as    MENU NAME       Auto Ohm S3 screen output is shown as        When instructions are provided  the menu item that should be selected is outlined with a  rectangle as shown below  option 3 should be selected         Warning messages are indicated as        Important notes are indicated as     e          Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2    1 0 INTRODUCTION  1 1 Auto Ohm 200 S3 General Description and Features    The Auto Ohm 200 S3 is Vanguard   s fourth generation  microprocessor based  true DC  micro ohmmeter  It is designed for testing EHV circuit breaker contact resistances  bushing  contact joints  welding joints  or for any low resistance measuring application  This high current  and very lightweight  16 8 Ibs  7 6 Kg  micro ohmmeter is designed to meet the IEEE  C57 09 1999  5 15  requirement for testing circuit breaker contact resistance     The Auto Ohm 200 S3 can accurately measure resistance values from 1 micro ohm to 5 ohms  A  0 1 micro ohm resolution is possible with cur
19. RIVE       1  SAVE INTERNALLY  Press the  1  key  SAVE INTERNALLY  to save the test record to the  unit   s Flash EEPROM  The following screen will be displayed     RECORD HUMBER 1  HAS EEEH SAVED        2  SAVE TO THUMB DRIVE  Press the  2  key  SAVE TO THUMB DRIVE  to save the test record to  the connected USB Flash drive  The following screen will be displayed   REC BEG SAVED TO  THUME DRIVE       Press any key to return to the    START UP    menu     k  The following screen will be displayed     SAVE THIS RECORD   1  VES  Za HO                   Press the  1  key  YES  to save the test record     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       The following screen will be displayed     RECORD HUMBER 1  HAS EEEH SAWED        If a USB flash drive is connected to the unit  the following screen will be    displayed instead     1  SAVE IHTERHALL Y  NOTE  a 2a SAYE TO THUMB DRIVE       1  SAVE INTERNALLY  Press the  1  key  SAVE INTERNALLY  to save the test record to the  unit   s Flash EEPROM  The following screen will be displayed     RECORD HUMBER 1  HAS EEEH SAWED        2  SAVE TO THUMB DRIVE  Press the  2  key  SAVE TO THUMB DRIVE  to save the test record to  the connected USB Flash drive  The following screen will be displayed   REC GAG SAVED TO  THUME DRIVE       Press any key to return to the    START UP    menu     Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    TEST RESULTS    COMPANY    STATION   CIRCUIT   MFR    MODEL    S N   K
20. TEST  TIME  14  21 54  DATE  65 24 11                   Press the  1  key  RUN TEST      b  The following screen will be displayed     EHTER FASS FAIL TEST  LIMITS     i  ES  Za HO       1  YES    Press the  1  key  YES  if you would like to set the passing resistance range for a  test  The following screen will be displayed     ENTER LOWER LIMIT   CO   3 GHHS2    A uQ       Enter the lower resistance limit for a passing test using the keypad  The screen  will be updated as shown below     ENTER LOWER LIMIT   RES Onis     450 po       Press the  ENTER  key  The following screen will be displayed     re      t      REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL    ENTER UPFER LIMIT   Ca     3 OHMS     FI uQ       Enter the upper resistance limit for a passing test using the keypad  The screen  will be updated as shown below     ENTER UPPER LIMIT   cA     3 GHMS3    528 po       Press the  ENTER  key  Continue to step c   2  NO  Press the  2  key  NO  if you do not want to enter the passing resistance range  for a test  Continue to step c   If using an Auto Ohm 200 S3 with the Dual Ground option  the following    screen will be displayed before the screen shown in step c     NOTES GROUND CURRENT FROBE   CREDUCED ACCURACY        Press the  1  key  NO  if you are not using a current probe and do not  want to use the Dual Ground option  Continue to step c    2  YES  Press the  2  key  YES  if you have connected an external current  probe and would like to use the Dua
21. USER   S MANUAL REV 2       d  The following screen will be displayed     1  INTERMHAL STORAGE  2  THUMB DRIVE                   Press the  2  key  THUMB DRIVE      e  The following screen will be displayed   RESTORE THUME DRIVE  rele       Type the record number that you would like to restore using the alpha numeric keypad  and then press the  ENTER  key     f  The test record will be restored to the unit   s working memory and the following screen  will be displayed     FEC 661 RESTORED   REVIEW RECORD     latag    Za HO          Press the  1  key  YES  to display the restored test record     g  The basic information about the restored test record will be displayed as shown below   BS 26 11 ATi q2 23    HUM TESTS  1       REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       Press the  v  key  The test record details will be displayed as shown below        Press the  STOP  key to return to the    START UP    menu  The restored test record will  remain loaded in the working memory     Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       3 5 5  Copying Test Records to a USB Flash Drive    Use the steps below to copy one or all test records from the unit   s Flash EEPROM to a  connected USB Flash drive     a  Make sure a USB Flash drive is connected to the unit   s    USB MEM    port  and then start  from the    START UP    menu     La EUH TEST   2a oe TIF   Za UTCE TEST  TIME  145 21554  DATE  Ba 24 11                   Press the  2  key  SETUP   
22. VA RATING   OPERATOR                    TEST NUMBER  1  TEST CURRENT  100 AMPS   RAMP TIME  5 Seconds  BURN IN TIME  5 Seconds    RESULTS   CURRENT  100 00 AMPS  RESISTANCE  100 uOhms CP     LOWER RES LIMIT  95 uOhms  UPPER RES LIMIT  105 uOhms                   NOTES     DATE 08720711 TIME 08 38 10    Figure 10  Sample DMOM 200 S3 DMOM 600 Printout    REC NUMBER 15    TEST RESULTS  COMPANY                   TEST NUMBER  1  TEST CURRENT  10 AMPS   RAMP TIME  5 Seconds  BURN IN TIME  5 Seconds    RESULTS   CURRENT   10 00 AMPS  RESISTANCE  56 uOhns  GND CURRENT  0 12 AMPS    NOTES           Figure 11  Sample DMOM 200 S3 DMOM 600 Printout  with Dual Ground Option     ES    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 4 3  Performing a Quick Test    A quick test can be performed without having to enter the test current  the burn in time  and  the ramp time  For a quick test  a current of 100A is used  and the burn in time and ramp time  are both set to 5 seconds  The Quick Test mode should not be used if the circuit breaker is  connected to dual grounds  if the unit has the Dual Ground option      a       Use the steps below to perform a quick test     a  Start from the    START UP    menu         Press the  3  key  QUICK TEST     b  The following screen will be displayed    Press the  START  key     c  The unit will start ramping up the current to 100A  The following screen will be  displayed        Once the current has reached 100A  the initial test res
23. ates the actual  resistance value of the circuit breaker     The Auto Ohm 200 S3 features a back lit 128 x 64 pixel LCD screen that is viewable in both  direct sunlight and low light levels  The resistance readings are displayed on the LCD screen in  micro ohms or milliohms  The unit is operated via a convenient 44 key    QWERTY    keypad on  the front panel  The Auto Ohm 200 S3 can store 128 records of 64 readings internally  and up to  999 test records on an external USB Flash drive  Test header information  Company  Substation   circuit breaker ID   s  can also be entered using the 44 key keypad and is stored with each test  record     Windows   based  XP Vista 7  analysis software is provided with each unit and can be used to  remotely control the Auto Ohm 200 S3 via the RS 232C port  Using this software  the user can  retrieve test records  from the unit   s memory or a USB Flash drive   analyze test results  and  print test results on a desktop printer  Test records can also be exported to PDF  Excel  and XML  formats     ES    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       The Auto Ohm 200 S3 is furnished with a 30 ft test   1 AWG  cable set  A 15 ft test cable set is  also available as an option  Test cables are terminated with heavy duty welding type clamps   The test current and voltage sense cables are isolated and fastened to the clamp jaws  This  feature allows for a simple connection to the circuit breaker bushing  An optional voltage sense  
24. cable and probe can be used to measure resist ance in small access locations  Optional  heavy duty  welding type C clamps are also available allowing the user to connect the test leads  to a wide variety of bushing sizes  bus bars  or large conductors        Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    1 2 _DMOM 200 S3 General Description and Features    The DMOM 200 S3 is Vanguard   s fourth generation  microprocessor based  true DC micro   ohmmeter  It is designed for testing EHV circuit breaker contact resistances  bushing contact  joints  welding joints  or for any low resistance measuring application  This high current and  very lightweight  19 8 Ibs  8 9 Kg  micro ohmmeter is designed to meet the IEEE C57 09 1999   5 15  requirement for testing circuit breaker contact resistance     The DMOM 200 S3 can accurately measure resistance values from 1 micro ohm to 5 ohms  A  0 1 micro ohm resolution is possible with current greater than 5A  The DMOM 200 S3 applies a  selectable true DC test current from 1A to 200A to the resistance load to be tested  The  DMOM 200 S3 controls the test current   s rise and fall rates  The test current rise and fall rate  can be selected from 5 seconds to 10 seconds  An    Auto Test    mode is also available and can be  initiated simply by applying the sense cables    leads across the two points of interest in the  current path  This feature is very convenient when measuring a sequence of several resistance  values in a cir
25. circuit breaker contact  resistance with both sides of the breaker bushing being grounded  When a test current is  applied to a circuit breaker with both sides grounded  some of the test current flows through  the safety ground cables  Using an external current sensor  the DMOM 600 measures and  eliminates this current from the total test current  It then calculates the actual resistance value  of the circuit breaker     The DMOM 600 features a back lit 128 x 64 pixel LCD screen that is viewable in both direct  sunlight and low light levels  The resistance readings are displayed in a large font on the LCD  screen in micro ohms or milliohms  The unit is operated via a convenient 44 key    QWERTY     keypad on the front panel  The DMOM 600 can store 128 records of 64 readings internally  and  up 999 test records on an external USB Flash drive  Test header information  Company   Substation  circuit breaker ID   s  can also be entered using the 44 key keypad and is stored with  each test record  The DMOM 600 also features a built in 2 5    wide thermal printer that can be  used to print test reports in the field     Windows   based  XP Vista 7  analysis software is provided with each unit  Using this software   the user can retrieve test records  from the unit   s memory or a USB Flash drive   analyze test  results  and print test results on a desktop printer  Test results can also be exported to PDF   Excel  and XML formats     The DMOM 600 is furnished with a 15 ft   1 0 AWG  t
26. cuit breaker contact  The DMOM 200 S3 can also compare test results against  preset limits and determine if a test passed or failed  and a    Pass    or    Fail    flag is displayed  accordingly     Since a true DC current  with controlled rise fall time  is passed through the circuit breaker  contact  no magnetic transient is induced into the breaker   s current transformers  This feature  greatly reduces the risk of inductively tripping a breaker control  bus differential relay      With the Dual Ground option  the DMOM 200 S3 can also measure the circuit breaker contact  resistance with both sides of the breaker bushing being grounded  When a test current is  applied to a circuit breaker with both sides grounded  some of the test current flows through  the safety ground cables  Using an external current sensor  the DMOM 200 S3 measures and  eliminates this current from the total test current  The DMOM 200 S3 then calculates the actual  resistance value of the circuit breaker     The DMOM 200 S3 features a back lit 128 x 64 pixel LCD screen that is viewable in both direct  sunlight and low light levels  The resistance readings are displayed on the LCD screen in micro   ohms or milliohms  The unit is operated via a convenient 44 key    QWERTY    keypad on the front  panel  The DMOM 200 S3 can store 128 records of 64 readings internally  and up 999 test  records on an external USB Flash drive  Test header information  Company  Substation  circuit  breaker ID   s  can also be 
27. e displayed        Press the  2  key  SAVE RECORD      FERA a    Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       If a USB Flash drive is connected to the unit  continue to step d   If a USB Flash drive is NOT connected to the unit  continue to step e     d  The following screen will be displayed     1  SAVE INTERMALLY  Za SAVE TO THUME DRIVE       1  SAVE INTERNALLY    Press the  1  key  SAVE INTERNALLY  to save the test record to the unit   s Flash  EEPROM  Continue to step e     2  SAVE TO THUMB DRIVE    Press the  2  key  SAVE TO THUMB DRIVE  to save the test record to the  connected USB Flash drive  The following screen will be displayed     FEC 601 SAVED TO  THUME DRIVE        Press any key to return to the    START UP    menu     e  The following screen will be displayed     RECORD HUMBER 2  HAS EEEH SAVED        Press any key to return to the    START UP    menu     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 5 3  Restoring a Test Record From Flash EEPROM    Use the steps below to restore a test record from the Auto Ohm   s internal Flash EEPROM to the  working memory     a  Start from the    START UP    menu         Press the  2  key  SETUP      b  The following screen will be displayed     Press the  3  key  SAVE RESTORE RECORD      c  The following screen will be displayed        Press the  1  key  RESTORE RECORD      Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       d  The following screen will be displayed  
28. e following screen will be displayed     a RESTORE RECORD      SAVE RECORD     RECORD DIRECTORY     ERASE RECORD     COPY TO THUMB DRIVE                   Press the  4  key  ERASE RECORD         Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    d  The following screen will be displayed   ERASE RECORD    1 ERASE SIHGLE REC   Z ERASE ALL RECORDS    STOP TO Ealt         If you have a USB Flash drive inserted in the unit   s    USB MEM    port  the  following screen will be displayed instead of the above screen     1 ERASE INTERHAL FEC  Z ERASE THUMB DRY REC       NOTE                Press the  1  key  ERASE INTERNAL REC    The following screen will be displayed     ERASE RECORD    1 ERASE SIHGLE REC   Z ERASE ALL RECORDS       STOP    TO Ealt       Continue with the steps below   1  ERASE SINGLE REC     Press the  1  key  ERASE SINGLE REC   to erase a single test record from the unit   s  internal Flash EEPROM  The following screen will be displayed     ERASE RECORD    L ENTER RECORD HUMBER    SCROLL TO SELECT       1  ENTER RECORD NUMBER    Press the  1  key  ENTER RECORD NUMBER  if you know the record number that  you would like to erase  The following screen will be displayed     i    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       Type the record number that you would like to erase using the alpha numeric  keypad and then press the  ENTER  key  If you do not know the test record  number  you can first view the test record directory using th
29. e instructions in  section 3 5 6     The following screen will be displayed while the record is being erased        The following screen will be displayed when the test record has been completely  erased        Press any key to continue  You will be returned to the beginning of step d     Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       2  SCROLL TO SELECT    Press the  2  key  SCROLL TO SELECT  to scroll through the test record directory  and locate the test record that you would like to erase  The following screen will  be displayed     RECORDS DIRECTORY     UP  TO SCROLL FHD   IHH  TO SCROLL EVS       Press the     or  v  key to scroll through the test record directory  The test  record header will be displayed as shown     tS BS26 11 aTi 4z    HUM TESTS  i       You can continue to scroll through the record directory by pressing the  A  and   v  keys  Once you have located the test record you would like to erase  press  the  ENTER  key  The selected test record will be erased and the following  screen will be displayed     RECORD HUMBER 9  ERASED        Press any key to continue  You will be returned to the beginning of step d     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       2  ERASE ALL RECORDS    Press the  2  key  ERASE ALL RECORDS  to erase all the test records from the unit   s  internal Flash EEPROM  The following warning screen will be displayed     ERASE ALL RECORDS   ARE YOU SURE      ENTER  TO COHNTIHUE        You can pr
30. entered using the 44 key keypad and is stored with each test record   The DMOM 200 S3 also features a built in 2 5    wide thermal printer that can be used to print  test reports in the field     Windows   based  XP Vista 7  analysis software is provided with each unit and can be used to  remotely control the DMOM 200 S3 via the RS 232C port  Using this software  the user can  retrieve test records  from the unit   s memory or a USB Flash drive   analyze test results  and  print test results on a desktop printer  Test results can also be exported to PDF  Excel  and XML  formats     rr ER    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       The DMOM 200 S3 is furnished with a 30 ft test cable set  A 15 ft test cable set is also available  as an option  Test cables are terminated with heavy duty welding type clamps  The test current  and voltage sense cables are isolated and fastened to the clamp jaws  This feature allows for a  simple connection to the circuit breaker bushing  An optional voltage sense cable and probe  can be used to measure resistance in small access locations  Optional heavy duty  welding type  C clamps are also available allowing the user to connect the test leads to a wide variety of  bushing sizes  bus bars  or large conductors        Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2    1 3  DMOM 600 General Description and Features    The DMOM 600 is specifically designed for testing EHV circuit breaker contact resistances   b
31. ess the  STOP  key to cancel the process and return to the    START UP     menu     Press the  ENTER  key to proceed with deleting all the test records from the unit   s  Flash EEPROM  The following screen will be displayed during the erasure process     ERASING RECORDS    PLEASE WAIT          The following screen will be displayed when all test records have been completely  erased     RECORDS ERASED        Press any key to return to the    START UP    menu     Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       3 5 8  Erasing Test Records from a USB Flash Drive    Follow the steps below to erase test records from a USB Flash drive     a        Make sure a USB Flash drive is connected to the unit   s    USB MEM    port  and then start  from the    START UP    menu     La FUH TEST  SEE   Za UTCE TEST  TIME  145 215 54  DATE  Ha 24 11                Press the  2  key  SETUP      The following screen will be displayed     RECORD ID   REVIEW RECORD  SAVE RESTORE RECORD  SET TIME      SET LANGUAGE                CA fe LM  ba       Press the  3  key  SAVE RESTORE RECORD      The following screen will be displayed     RESTORE RECORD  SAVE RECORD   RECORD DIRECTOR   ERASE RECORD   COPY TO THUMB DRIVE                OF    Le bo       Press the  4  key  ERASE RECORD      d  The following screen will be displayed     1 ERASE IHTERHAL FEC  2 ERASE THUMB DRY REC                   Press the  2  key  ERASE THUMB DRV REC            REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 
32. est cable set  Custom test cable lengths  are optionally available  Optional heavy duty  welding type C clamps are also available allowing  the user to connect the test leads to a wide variety of bushing sizes  bus bars  or large  conductors     1 4 Cables and Accessories    i    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL       Figure 1  Furnished Current and Sense Combination Cables  P N 8000 0076    Auto Ohm 200 S3 and DMOM 200 S3        Figure 2  Furnished Current Cable  P N 8000 0072  and Sense Cables  P N 8000 0073  for DMOM 600       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       Figure 3  Optional Cable with C Clamp       Figure 4  Optional Hand Spike    TT       REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL    1 5  Table 1     TYPE  PHYSICAL SPECIFICATIONS  INPUT POWER    RESISTANCE READING  RANGE    ACCURACY    TEST CURRENT RANGE    DISPLAY  KEYPAD    INTERNAL TEST RECORD  STORAGE    EXTERNAL TEST RECORD  STORAGE    COMPUTER INTERFACE  PC SOFTWARE   SAFETY   ENVIRONMENT    HUMIDITY  MAX   ALTITUDE  MAX   CABLES  OPTIONS    WARRANTY    Auto Ohm 200 S3 Technical Specifications    Auto Ohm 200 S3 Technical Specifications    Portable Micro Ohmmeter  17  W x 7  Hx 13  D  43 2cm x 17 8cm x 33cm   Weight  16 8 Ibs  7 6 Kg   100 240 Vac  14A  50 60Hz    1 micro ohm to 10 milliohms at 200 A  0 1 micro ohm resolution   1 micro ohm to 5 ohms at 1A    1A to 4 99A  1   10 micro ohms  5A to 9 99A  1   2 micro ohms  10A to 20
33. he    Downloads    page will be displayed listing all Vanguard products along with the  related firmware  software  and user   s manuals  Click on any of these items to download  them     SI       Vanguard Instruments  Company  Inc     1520 S  Hellman Ave e Ontario  CA 91761 e USA  Phone  909 923 9390 e Fax  909 923 9391    www vanguard instruments com    Copyright    2015 by Vanguard Instruments Company  Inc     Auto Ohm 200 DMOM 200  3 DMOM 600 User s Manual e Revision 2 3 e February 18  2015 e TA       
34. iseedane eeso aE aO aE Aa einer 2  1 1 Auto Ohm 200 S3 General Description and Features                    i 2  1 2 DMOM 200 S3 General Description and Features           ccccccsssececesssceeecseeeeessseeeeseseeees 4  1 3 DMOM 600 General Description and Features                   i 6  1 4   CablesandAccessofi6s  cunniaa ae 6  1 5 Auto Ohm200S3 Technical Specifications                  i 9  1 6 DMOM 200 S3 Technical Specifications              i 10  1 7 DMOM G00TechnicalSpecificationis      celiaca 11  1 8  Auto Ohm 200 S3 Controls and Inditators      a a 12  1 9 DMOM 200 S3 Controls and Indicators                 13  1 10 DMOM 600 Controls and Indicators                 ii 14  2 0  PRE TEST SETUP gerani ira 15  21     OperalinSVolfes   lillo 15  2 2 LCD Screen Contrast Control    aaa 15  30   OPERATING PROCEDURES suroisrssirissacsercissise sunitai endana raine iiaia Eo aS Eaa Eiin 16  3 1    Connection Diagramsi    aaa e ne 16  3 3  Setting the Interface Language ll 18  BA Testing Procedures scialle a ii 19  3 4 1  Entering Test Record Header Information                 i 19  3 4 2  Performing a Test ricarica einen 22  34 3  Performing a Quick Testa 33   3 5 Working With Test RecordS jas scashecdaxestacsasnataaeccsaxsis acuvsesainaaiteaxioseeslaneeeladaamaGes 37  3 5 1  Viewing the Contents of the Working Memory           i 37  3 5 2  Saving Test Results to a Test Record    39  3 5 3  Restoring a Test Record From Flash EEPROM                     i 41  3 5 4  Restoring a Test
35. ished        Press any key to return to the    START UP    menu     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 5 6  Viewing the Test Record Directory    Use the steps below to browse through a directory of the test records stored in the Auto Ohm   s  Flash EEPROM memory     a  Start from the    START UP    menu         Press the  2  key  SETUP      b  The following screen will be displayed     Press the  3  key  SAVE RESTORE RECORD      c  The following screen will be displayed        Press the  3  key  RECORD DIRECTORY      Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2    d  The following screen will be displayed        Press the     or  v  key to scroll through the test record directory  The test record  header will be displayed as shown        You can continue to scroll through the record directory by pressing the  A  and  v  keys   Press the  STOP  key to return to the    START UP    menu     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 5 7  Erasing Test Records from the Flash EEPROM  Follow the steps below to erase test records from the Flash EEPROM    a  Start from the    START UP    menu     1  EUH TEST  To SenF   Sa  QUICE TEST  TIME  14  Zir 34  DATE  Gorz4 11                   Press the  2  key  SETUP      b  The following screen will be displayed     a RECORD ID     REVIEW RECORD   a SAVYE RESTORE RECORD     Sel TIME      SET LANGUAGE                   Press the  3  key  SAVE RESTORE RECORD      c  Th
36. l Ground option  The following  screen will be displayed     CONNECT EXT CURRENT  PROBE TO GHO CABLE     EMSURE THAT THE FROBE  IS TURMHED OH     PRESS ANY KEN       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       Connect the external current probe to the ground cable and then turn  on the probe  Press any key and continue to step c     c  The following screen will be displayed     1  HORMAL TEST  Za AUTOMATIC TEST       The Auto Ohm 200 S3 provides a convenient automatic test mode that can be used to  perform multiple tests without having to restart each test manually  When performing  an automatic test  the Auto Ohm will sense when cables are disconnected and re   connected and will initiate the test 2 seconds after sensing a re connection     Press the  1  key  NORMAL TEST  if you would like to perform a normal test  Continue  to step d     Press the  2  key  AUTOMATIC TEST  if you would like to perform an automatic test   Continue to step d     d  The following screen will be displayed     Auto Ohm 200 S3 DMOM 600    SELECT TEST CURRENT  SELECT TEST CUKRENT   16    ZIA   JHA   188A j   ZAHA CUSTOM   CUSTOM    1  2  Cf  4   da    a       Select the test current by pressing the corresponding numeric key on the keypad  If the  test current you would like to use is not listed  press the  6  key  CUSTOM  and then  enter a value from 1A to 200A for the Auto Ohm 200 S3 DMOM 200 S3 or 10 A to 600A  for the DMOM 600       When using a DMOM 600 with input power
37. ll be displayed        Type the station name using the keypad and then press the  ENTER  key     e  The following screen will be displayed        Type the circuit information using the keypad and then press the  ENTER  key     f  The following screen will be displayed        Type the manufacturer name using the keypad and then press the  ENTER  key     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       g  The following screen will be displayed     Te  TO POSITION   ENTER  TO ACCEPT       Type the circuit breaker   s model information using the keypad and then press the   ENTER  key     h  The following screen will be displayed     j     SERIAL HUMBER     Tel To POSITION     ENTER    TO ACCEPT       Type the circuit breaker   s serial number using the keypad and then press the  ENTER   key     The following screen will be displayed     EVA RATING     Te  TO POSITION   ENTER  TO ACCEPT       Type the circuit breaker   s KVA rating using the keypad and then press the  ENTER  key     The following screen will be displayed     OPERATOR     Tel TO POSITION   ENTER  TO ACCEPT       Type the operator   s name using the keypad and then press the  ENTER  key  All  header information will be saved  and you will be returned to the    START UP    menu      TE    Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       3 4 2  Performing a Test  Follow the steps below to perform a test     a  Start from the    START UP    menu     LEUH TEST  2a SETUP   Sa  QUICK 
38. r by an authorized  repair service provider  Unauthorized modifications can cause safety hazards and will void the manufacturer   s  warranty     EQUIPMENT RATINGS  IP Rating  The enclosures for Auto Ohm 200 S3  DMOM 200 S3  and DMOM 600 have an IP rating of 32     Pollution Degree  The Auto Ohm 200 S3  DMOM 200 S3  and DMOM 600 have a pollution rating of 2     Operating Voltage  The Auto Ohm 200 S3  DMOM 200 S3  and DMOM 600 are rated for use with an operating  voltage of 120V or 240V  auto ranging  10  of selected voltage     Power Cord  The Auto Ohm 200 S3  DMOM 200 S3  and DMOM 600 are supplied with a 16 AWG  16A power cord  with a NEMA 5 15P plug  Replacement cable shall have the same or better rating and is available through the  manufacturer     VENTILATION REQUIREMENTS  The Auto Ohm 200  3  DMOM 200 S3  and DMOM 600 must be operated with the enclosure lid open     SAFETY SYMBOLS  A Indicates that caution should be exercised    d Indicates location of chassis ground terminal    CLEANING  To clean the Auto Ohm 200 S3  DMOM 200 S3  and DMOM 600   e Disconnect all cables and turn the unit off   e Usea soft  lint free cloth to wipe all surfaces clean   e Avoid getting moisture in openings and connectors   e Don t use any cleaning products or compressed air     A    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       TABLE OF CONTENTS    CONVENTIONS USED IN THIS DOCUMENT                    i 1  1 0  INTRODUCTION tcrseucessnatctcedasautdeeenghineduniged coeund
39. rent greater than 5A  The Auto Ohm 200 S3  applies a selectable true DC test current from 1A to 200A to the resistance load to be tested   The Auto Ohm 200 S3 controls the test current   s rise and fall rates  The test current rise and fall  rate can be selected from 5 seconds to 10 seconds  An    Auto Test    mode is also available and  can be initiated simply by applying the sense cables    leads across the two points of interest in  the current path  This feature is very convenient when measuring a sequence of several  resistance values in a circuit breaker contact  The Auto Ohm 200 S3 can also compare test  results against preset limits and determine if a test passed or failed  and a    Pass    or    Fail    flag is  displayed accordingly     Since a true DC current  with controlled rise fall time  is passed through the circuit breaker  contact  no magnetic transient is induced into the breaker   s current transformers  This feature  greatly reduces the risk of inductively trip ping a breaker control  bus differential relay      With the Dual Ground option  the Auto Ohm 200 S3 can also measure the circuit breaker  contact resistance with both sides of the breaker bushing being grounded  When a test current  is applied to a circuit breaker with both sides grounded  some of the test current flows through  the safety ground cables  Using an external current sensor  the Auto Ohm 200 S3 measures and  eliminates this current from the total test current  The Auto Ohm then calcul
40. through a directory of the stored  test records     2 1  The following screen will be displayed   RECORDS DIRECTORY       UP    TO SCROLL FHD     TWH    TO SCROLL EVS       Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    Press the  A  button or the  v  key to display the next or previous test  record  respectively     The basic test record information will be displayed as shown        When you have located the test record that you would like to restore   press the  ENTER  key  Continue to step 1 2 on page 43     REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       3 5 4  Restoring a Test Record From a USB Flash Drive    Use the steps below to restore a test record from a USB Flash drive to the Auto Ohm   s working  memory     a              Make sure the USB Flash drive containing the test record s  is inserted in the Auto   Ohm   s USB Flash drive port     USB MEM    port   Then start from the    START UP    menu     ia EUH TEST   2a SE TUF  BUICK TEST  TIME  14  21 54  DATE  Go rz4 11                Press the  2  key  SETUP      The following screen will be displayed        RECORD ID     REVIEW RECORD   a SAVYE RESTORE RECORD    SET MIME      SET LANGUAGE                Press the  3  key  SAVE RESTORE RECORD     The following screen will be displayed              a RESTORE RECORD     SAVE RECORD    RECORD DIRECTORY          ERASE RECORD     COPY TO THUME DRIVE    Press the  1  key  RESTORE RECORD      Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 
41. to Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       If the continuous burn in option was selected in step e  the following screen    will be displayed     wore   BURNING IM  XxX  4AT uQ  oH  dl A    TEST IN PROGRESS          The unit will continue measuring the resistance and current and will display  the values on the screen  To stop running the test  press the  STOP  key     i  The current will then be ramped down and then the final test results will be displayed as  shown below     TEST RESULTS       e A Pass Fail   P  or  F   will be displayed if you had entered a passing     resistance range in step b    e Ifyou had selected the automatic test mode in step c  you can now  disconnect the cables and re connect them as needed  A test will be  initiated automatically 2 seconds after the re connection is sensed    e Ifthe Dual Ground option was used  the ground current will also be  displayed as shown below     TEST RESULTS    NOTES    437 uQ  F     2H H1 A    GHO CUR  6 15 AMPS       Press the  STOP  key to continue   If you had selected the normal test option  continue to step j     If you had selected the automatic test option  continue to step k     CSS    Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2       j  The following screen will be displayed   Auto Ohm 200 S3 DMOM 200  3 DMOM 600  KEEF THIS READING  FW TEST FESULTS     la MES 1  YES  2  HO Z  HO                               Press the  1  key  YES  to save the reading  Press the  1  key  YES
42. ults will be displayed and the  burn in sequence will be initiated  The following screen will be displayed     C I    Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL REV 2    BURNING IN  604    TEST IN PROGRESS          The current will then be ramped down and then the final test results will be displayed as  shown below     TEST RESULTS       Press any key to continue   d  The following screen will be displayed     Auto Ohm 200 S3 DMOM 200 S3 DMOM 600    KEEP THIS READING  PRINT TEST RESULTS   1  WES i  WES  2  HO Za  HO                               Press the  1  key  YES  to save the reading  Press the  1  key  YES  to print the test  results on the unit   s built in thermal  printer  The following screen will be  displayed     KEEF THIS READING   i  VES  2  Ho                   Press the  1  key  YES  to save the reading     i RA    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       e  The following screen will be displayed        Press any key to continue     The following screen will be displayed     Press the  2  key  NO      g  The following screen will be displayed        Press the  1  key  YES  to save the test record     h  The following screen will be displayed        Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER   S MANUAL REV 2    1 SAVE INTERMALLY  Za  SAVE TO THUMB DRIVE       1  SAVE INTERNALLY  Press the  1  key  SAVE INTERNALLY  to save the test record to the  unit   s Flash EEPROM  The following screen will be displayed     RECORD HU
43. use of the controls will usually cause no  serious harm  Users should also familiarize themselves with the safety summary information  found on the front page of this User   s Manual     Current Sensing Back Lit LCD Screen USB RS 232C Input Power Ground  Connector Jacks  128 x 64 pixels  Flash Drive Computer Connector Stud  Viewable in bright Interface Interface with Third wire  sunlight and low light Safety Ground    120 240 Vac  12A  50 6N Hz    1 200A True DC Digital Micro Ohm Meter    Oo0aDSOOODOL  MEAN MY eee  MSTA HNN   gt  RES YY         Voltage Sensing Current Rugged     QWERTY    Style  Connector Jacks Lead Connectors Membrane Keypad    Figure 5  Auto Ohm 200 S3 Controls and Indicators    TE    REV 2 Auto Ohm 200 S3   DMOM 200 S3   DMOM 600 USER S MANUAL       1 9  DMOM 200 S3 Controls and Indicators    The DMOM 200 S3   s controls and indicators are shown in Figure 6  The purpose of the controls  and indicators may seem obvious  but users should familiarize themselves with them before  using the DMOM 200 S3  Accidental misuse of the controls will usually cause no serious harm   Users should also familiarize themselves with the safety summary information found on the  front page of this User   s Manual     Current Sensing Input Power RS 232C USB Back Lit LCD SCreen Ground  Connector Jacks Connector with Computer Flash Drive  128 x 64 pixels  Stud  Third Wire Interface Interface Viewable in direct  Safety Ground sunlight and low light    20 240 Vac 12A  50 60 Hz    DM
44. ushing contact joints  welding joints  or for any low resistance measuring application  This high  current and very lightweight  33 Ibs  15 Kg  micro ohmmeter is designed to meet the IEEE  C57 09 1999  5 15  requirement for testing circuit breaker contact resistance     The DMOM 600 can accurately measure resistance values from 1 micro ohm to 450 milliohms   A 0 1 micro ohm resolution is possible with current greater than 10A  The DMOM 600 applies a  selectable true DC test current from 10A to 600A to the resistance load to be tested  The  DMOM 600 controls the test current   s rise and fall rates  The test current rise and fall rate can  be selected from 5 seconds to 10 seconds  An    Auto Test    mode is also available and can be  initiated simply by applying the sense cables    leads across the two points of interest in the  current path  This feature is very convenient when measuring a sequence of several resistance  values in a circuit breaker contact  The DMOM 600 can also compare test results against preset  limits and determine if a test passed or failed  and a    Pass    or    Fail    flag is displayed  accordingly     Since a true DC current  with controlled rise fall time  is passed through the circuit breaker  contact  no magnetic transient is induced into the breaker   s current transformers  This feature  greatly reduces the risk of inductively tripping a breaker control  bus differential relay      With the Dual Ground option  the DMOM 600 can also measure the 
    
Download Pdf Manuals
 
 
    