Contents

1. e RedLED on transmitter lit e Voltage signal at testpoints is 5 mVdc 5 mA output e PLC displays negative value i e 2150 ppm e Controller indicates sensor fault or sensor failure Possible Cause Solution e Sensor exposed to liquid Replace sensor element see page 9 for more info e Loose connection Check and tighten sensor wires Constant or Intermittent high signal or alarms Indications e Erratic or constant high concentration reading at controller or PLC Possible Cause Solution e Weeping relief valve Check valve by drawing a sample from the header with an accurate portable refrigerant detector Be sure to sample 1 to 3 from inside the header to ensure a good reading or loosen union nut and remove sensor assembly from header If signal returns to normal in fresh air investigate relief valve s and replace if necessary e Condenser steam Re install the 2 plug or install pipe in its place lowered below the condenser steam level to allow a fresh air vent to the sensor e Sensor aged beyond its useful life hypersensitive Replace sensor element see page 9 for more info 10 Specifications Detection Principle Solid state Detection Method Diffusion Gas CFC HFC HCFC refrigerants R11 R12 R22 R134a R404a R410a R434a R507a etc Range 0 1 10 000 ppm Output Signal Linear 4 20 mA max input impedance 700 Ohms Power Supply 24 VDC 250 mA Response Time Too l
2. for continuity shorts grounds etc It is usually best to disconnect external alarms and other equipment from the sensor until the initial start up procedures are completed After power up allow at least 12 hours for the system to stabilize before testing the sensors Because sensors are normally located at a distance from the main unit the test time required and accuracy of the response checks will be improved if two people perform the start up procedures and use radio contact Response Test 1 One person removes the 7 plug in the tee and injects a small amount of propane butane from an unlit plumber s torch 2 The second person stays at the control panel to determine that each sensor when exposed to the gas is connected to the proper input and responds causing appropriate alarm functions Calibration The GasGuard VL R sensor comes factory calibrated and should not require any adjustments after installation If any adjustments are required there are two pots on the preamp that are used for calibration GasGuard VL R Operating and Instruction Manual Note Never measure sensor output in mA Always use mVDC or VDC voltmeter settings Zero Calibration After the unit is installed and has been powered up for a minimum of 24 hours the unit can be zero calibrated by the following e Besurethe unit is in clean air This can be accomplished by removing the sensor from the mounting kit into fresh air e Adjust the zero
3. hole facing down GasGuard VL R Operating and Installation Manual Wiring Electrical wiring must comply with all applicable l a codes Tost mune Test Electrical Power 24 VDC regulated 250 mA o e ac Output Linear 4 20 mA output Monitoring 1 a Fault Power er equipment may have a maximum input impedance O N o of 700 ohms vi mn hi Cable Recommendation 20 3 shielded cable General Cable C2525A or equivalent Length of cable to sensor should be no greater than 1 500 ft Monitoring Monitoring equipment must be configured to indicate a fault if the signal is below 1 MA All signals over 20 mA must be considered high gas concentrations Alarm setpoints should not be lower than 50 of full scale range Sensor Connector Wiring Guidelines e Use only the existing conduit hole for connections to the sensor e Always use three conductor insulated stranded shielded copper cable e Do not pull sensor wiring with AC power cables This can cause electrical interference M P e f cable runs cannot be made without a splice all L to Ground terminal of power supply _ splice connections should be soldered to case ground of monitoring equipment e Ground the shield at the main control panel Connect the shield wire in the sensor terminal block labeled SHLD Figure 2 Wiring diagram to signal input of monitoring equipment _ Start up Before applying power make a final check of all wiring
4. ACT TORT OR RELIANCE OR ANY OTHER THEORY 11 04 2014 ALIBRATION SPECIALISTS IN nj ES Gas Detection NC
5. GASGUARD VENT LINE refrigerant Sensor GasGuard VL R Operating and Instruction Manual Table of Contents General description 0 4 Installation aan 4 Locating the sensor 4 Installation guidelineS 5 WIIG PRE Ta A dst 6 OPERAUOM suor asas o r la aa 7 Soliti 7 CalibDrallOMm oi so cee Aa 7 Maintenance illa 9 TROUDIGSMOOUNG za toscana dada 10 Specifications lia 10 Wal ciar a una tn Koh ion 11 Calibration Technologies 866 394 5861 GasGuard VL R Operating and Installation Manual General Description The GasGuard Vent Line sensor is a 24 VDC three wire 4 20 mA sensor for CFC HFC and HCFC refrigerant gases It provides an industry standard linear 4 20 mA output signal compatible with most gas detection systems and PLCs The GasGuard VL R provides real time continuous monitoring of refrigerant vapors in refrigeration system vent lines Utilizing a rugged and long life solid state sensor the GasGuard VL R sensor can withstand continuous exposures to high concentrations of vapors without shortening the life of the sensor The sensor is housed in the mounting kit which is connected to the backside of the sensor enclosure The union of the mounting kit breaks apart allowing for simple sensor field replacement The transmitter circuit board is sealed in potting compound protecting sensitive electronic components and
6. ane or butane from an unlit plumber s torch e All tests and calibrations must be logged Sensor Life Typical sensor life of the GasGuard VL R sensor is five to seven years Although extremely reliable a few things can cause the sensor to become faulty including e along period of time e exposure to liquid Sensor Replacement When the sensor becomes faulty a replacement sensor can be obtained from Calibration Technologies To replace the sensor refer to Figure 5 and the following procedure Note Always assume system could discharge at any moment Stay clear of discharge path and have escape route planned 9 6 Loosen the screw terminals of sensor connector orange and red wires and disconnect the wires Unscrew the union nut of mounting kit making sure to support weight of sensor assembly This will expose the sensor Remove sensor by pulling it out through the union Install new sensor and tighten sensor screw terminals Make sure the red and orange wires are in their correct terminals Re assemble sensor mounting kit Discard old sensor The sensor can be response tested immediately after replacement Zero span calibration may be performed after a 24 hour warm up period Union nut Sensor Mounting kit with union tee nipple and test plug Figure 4 Sensor replacement GasGuard VL R Operating and Installation Manual Troubleshooting Sensor Fault low signal reading Indications any or all
7. cement of parts due to the normal wear and tear of the product arising from use c any product which in CTI s opinion has been misused altered neglected or damaged by accident or abnormal conditions of operation handling or use d any damage or defects attributable to repair of the product by any person other than an authorized dealer or contractor or the installation of unapproved parts on the product The obligations set forth in this warranty are conditional on a proper storage installation calibration use maintenance and compliance with the product manual instructions and any other applicable recommendations of CTI b the buyer promptly notifying CTI of any defect and if required promptly making the product available for correction No goods shall be returned to CTI until receipt by the buyer of shipping instructions from CTI and c the right of CTI to require that the buyer provide proof of purchase such as the original invoice bill of sale or packing slip to establish that the product is within the warranty period THE BUYER AGREES THAT THIS WARRANTY IS THE BUYER S SOLE AND EXCLUSIVE REMEDY AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE CTI SHALL NOT BE LIABLE FOR ANY SPECIAL INDIRECT INCIDENTAL OR CONSEQUENTIAL DAMAGES OR LOSSES INCLUDING LOSS OF DATA WHETHER ARISING FROM BREACH OF WARRANTY OR BASED ON CONTR
8. copper tracing from corrosion The stainless steel enclosure protects the transmitter from chemical and UV damage Recommended alarm setpoints for refrigerant vent lines are typically 0 5 1 0 12 20 mA Setpoints lower than this may result in occasional false alarms due to inclement weather or interference gases i e truck exhaust condenser steam etc 4 Installation Locating the sensor Warning Outdoor installation only Never install the sensor indoors i e Engine Room Note The 7 nipple of the supplied mounting kit should be welded to the relief header to allow airflow to the sensor Note Removing the Y plug from the mounting kit usually allows more fresh air to the sensor and prevents signal rise over time The GasGuard VL R sensor assembly should be installed outdoors three to five feet above the roofline where the relief header discharges to the atmosphere see Figure 1 Relief header opposite side of discharge Sensor cable gt Roofline ILL Figure 1 Discharge to Atmosphere Mount sensor GasGuard VL R Operating and Instruction Manual Installation Guidelines e Always assume system could discharge at any moment Stay clear of discharge path and have escape route planned e Make sure refrigerant does not discharge onto sensor assembly or personnel working on sensor i e mount sensor opposite side of discharge e Install sensor enclosure with conduit
9. ess than 30 seconds Accuracy 5 of value Zero Drift Less than 1 per month non cumulative Span Drift Less than 1 of full scale per month non cumulative Linearity 5 of full scale Repeatability 5 of full scale Wiring Connections 3 conductor shielded stranded 20 AWG cable General Cable C2525A or equivalent up to 1500 ft Enclosure 18 ga stainless steel housing Captive screw in hinged lid For non classified areas Mounting Kit Schedule 80 NPT pipe fittings Temperature Range 46 F to 140 F 46 C to 60 C Dimensions 4 8 high x 4 72 wide x 3 35 deep Weight 4 Ibs includes mounting kit Limited Warranty 8 Limitation of Liability Calibration Technologies Inc CTI warrants this product to be free from defects in material and workmanship under normal use and service for a period of one year including sensor beginning on the date of shipment to the buyer This warranty extends only to the sale of new and unused products to the original buyer CTI s warranty obligation is limited at CTI s option to refund of the purchase price repair or replacement of a defective product that is returned to a CTI authorized service center within the warranty period In no event shall CTI s liability hereunder exceed the purchase price actually paid by the buyer for the Product This warranty does not include a gas sensors that have been wetted by liquid refrigerant oil or water b routine repla
10. pot until the sensor outputs 40 mV from Test to Test see Figure 3 Span Calibration It is recommended that the GasGuard VL R sensor be response tested only every six months Refer to the Response Test procedure on this page If span calibration is required the following procedure will span the unit e Unscrew the union nut of mounting kit making sure to support weight of sensor assembly This will expose the sensor and allow for a more accurate span calibration see Figure 4 e Apply 1 target span gas at 0 8 L min e Once the output signal has peaked or one minute maximum adjust the span pot until the sensor outputs 200 mV from Test to Test see Figure 3 GasGuard VL R Operating and Installation Manual Test 4 to 200 Test Y 4 l U a LA A A SHLD GND 24 SIG A Fault Power A 1 M E Sensor Connector m n ZERO SPAN j ra 1070 eed Figure 3 Sensor output and zero span adjustments GasGuard VL R Operating and Instruction Manual Maintenance The GasGuard VL R sensor was designed for long life and minimal maintenance Calibration Technologies recommends the following maintenance schedule Maintenance Guidelines e The sensor is shipped with a factory calibration Sensor should be response tested 6 months from purchase date e Response test the sensor at least once every 6 months The response test can be performed with prop