Home
        IM 660-1 MicoTech/Network Controls Water Source Heat Pump
         Contents
1.     In addition to the various heating and cooling options  the water  source heat pump product line provides several  factory configured options that affect installation requirements  and unitcontrol  These options can befactory programmed and  factory wired  Factory installation and wiring canaccommodate  only one option at a time  The model number code string  specifles which options are present in a particular water source  heat pump  Field installation will allow all four options simulta   neously utilizing an auxiliary module  The following options are  described in this section       Boilerless System Relay    Motorized Valve Relay     Fresh Air Damper Relay    Timed Output Relay    Boilerless system relay    Relay receives loop water temperature input from MicroTech  Loop Water Controllerthrough the gateway panel and provides  relay output to electric heat on a call for heat after loop  temperature falls     Motorized valve relay    Relay provides relay output to motorized valve to shut off water  through the unit when compressor is not operating     Fresh air damper relay    Provides relay output to open damper whenever the fan is  operating in the occupied cycle     Page 4  IM 66 1    Timed output relay    Provides relay output auxiliary load to control its operation  based onaspecific time schedule differentf rom thatofthe heat  pump unit     MicroTech network    A varlety of MicroTech unit and auxiliary controllers can be  interconnected to form a MicroTech networ
2.    Low pressure    The  Low Pressure  fault is an indication that the low pressure  switch input  J 4 11  sensed an open circuit while the controller  was calling for the compressor to run    Thelow pressure switch willopen when the temperature falls  below its setpoint  Refer to  Test Procedures  in the  Service  Information  section of this manual for information on trouble   shooting digital input faults     Effects    e Compressor immediately de energized by software    e Normal unit operation disabled until manual correction  and reset of fault condition     Condensate overflow    The  Condensate Overflow  fault is an indication that the  condensate overflow sensor  J 4 14  sensed a grounded signal  while the controller was calling for the compressor to run    Refer to  Test Procedures  in the  Service Information   section of this manualforinformation ontroubleshooting analog  input faults     Effects    e Compressor immediately de energized by software    e Normal unit operation disabled until manual correction and  reset of fault condition     Brownout    The    Brownout    faultindicates thatthe watersource heat pump  is sensing low voltage levels  Itis a safety intended to protectthe  compressorand contactors from low line voltage or    brownout     conditions    The controller is programmed with a brownout setpoint that  corresponds to 8296 of the water source heat pump s name   plate line voltage value  Ifthe watersource heat pump controller  senses a voltage leve
3.    Pre Start    Required tools and literature    The following tools and additional literature may be required  to properly commission a MicroTech Water Source Heat P ump  Controller     Tools    e Digital voltmeter   Digital ohmmeter   Digital thermometer   General technician s tools   PC equipped with Monitor  software  NetworkWaterS ource  Heat Pumps only     Literature    e Model specific water source heat pump installation bulletin   see Table 1    e Program specific sequence of operation bulletin   e MicroTech Monitor Program User s Manual  if PC is used     Water source heat pump identification    Although the water source heat pumps look similar  there are  significant intemal differences which are defined by the model  number code string  In additionto the basic heating and cooling  equipment  the model number code string specifies which  factory configured options have been provided  These options  determine the internal wiring configuration and the field wiring  requirements     IM 660 1  Page 5    Obviously  it is extremely important that the correct water  source heat pump be placed in the correct location in accor   dance with job requirements  Proper water source heat pump  location should have been determined during the installation  process  Nevertheless  proper location must be verified during  the commissioning process     Field wiring check    The water source heat pump factory configured options deter   mine the low voltage field wiring requirements  If a
4.  fault  conditions    Each new MicroTech WSHP controller is factory wired and  factory programmed  The controller is capable of complete   stand alone unit control if desired  or can be incorporated into  a MicroTech network using a MicroTech gateway panel     This new controller utilizes LonWorks technology   the  technology geared toward total interoperability of products  among different manufacturers  This innovative technology  allows the utilization of a central LonWorks based building  control system capable of communicating with all internal  building systems  The controller s intelligence  code written in  the Neuron C programming language  is contained within an  on board Neuron chip     Component Data    Microprocessor    The new MicroTechWSHP unit controller is a preprogrammed  microprocessor containing the software required to monitor  and control the unit  The controller supports a minimum of 6  analog inputs  4 digital inputs and 5 digital outputs  including the  LED   All electrical connections to the board are provided by  three mass termination style headers  Two of the headers are  designated strictly for factory wiring  the other for a field wiring  harness which terminates to a screw type terminal strip on the  unit s exterior    The controller uses field adjustable setpoints and fixed   preprogrammed parameters to maintain unit control  many of  the preprogrammed parameters can be adjusted with a PC  equipped with Monitor software on network units      S
5.  faults   Brownout fault    Microprocessor problems    Thestatus LED indications canaid in WSHP controller  diagnos   tics    Status LED  Approximately 40 seconds after power is  applied to the WSHP  the status LED should illuminate as    shown in Table 2  If the LED fails to respond properly  either  there is a software problem orthe WSHP controller is defective     Power supply problems    The WSHP controller requires a 24 VAC power supply  It is  connected to the board at the section labeled 24V GND and  24VAC  terminais J 4 1 and J 4 2   Refer to the unit wiring  diagram    If a problem with the WSHP controller power supply is  suspected  check the following     1  Verify that the main power switch is at  On      2  Check the voltage at the secondary of transformer  It should  be approximately 24 VAC  load dependent      IM 660 1   Page 9    Erroneous temperature readings    If it is suspected that the WSHP controller is operating using  erroneous temperature data  the following procedure may be  used to check the sensors     1  Measure the temperature at the suspect sensor using an  accurate thermometer     2  Determine the sensor s analog input number  Refer to the  unit wiring diagram orto the input output tables  Table 8      3  Remove the connector from its WSHP controller terminals  and measure the resistance of the sensor  through the  sensor connections   Using the thermistor chart  Table 9    compare this value with the measured temperature    If the measured res
6.  specific  option is present on a particular water source heat pump  as  denoted by the model number   the associated field wiring  if  any  must be checked    A unit wiring diagram is provided with each unit shipped   along with a modelspecific Installation and Maintenance Guide   Referring to this literature and using the following checklists  the  start up technician should thoroughly check the electrical in   stallation before the commissioning process proceeds     Wall sensor packages    1  Check that the cable is twisted  shielded with drain wire   Belden 8729 or equivalent  22GA      2  Check that four  4  conductors are available     3  Check that the conductors have been terminated at the unit  and the wall sensor package to screw terminal board  1 in    Table 3  Network WSHP default setpoints and adjustability    accordance withthe field wiring diagram  on which terminals  are clearly labeled  Terminal 4 is used for both the room  sensor common and the shield wire     4  Check that the cable length between the wall sensor pack   age and its water source heat pump controller does not  exceed 260 feet     MicroTech network communications  units    1  Check that the cable is a twisted  unshielded pair of copper  strand conductors     2  Check thatthe conductors have been terminated at the units  to terminals 5 and 6 of Terminal Board  1 in accordance with  the field wiring diagram     3  Check that the conductors have been terminated at the  MicroTech gateway panelin a
7. Installation  amp  Maintenance Data    Group  WSHP    Part Number  106018961       MicroTech   Water Source  Heat Pump Unit Controller    Date  May 1999                   Contents  Introduction  co eh ed teo beret 2 Pre Start iusso perder e rrt decide 5 6  General Description                        senes 3 Start  Up    centre een ro dene rc 6 7  Component Data             sssseeeememe enn 3 Diagnostics and Service                  sssseseee 7 8  Standard Control Features                  sse 3 4 Service Information    9  Factory Configured Options                    sse 4 5 Test Procedures               sse 9 11  Commissioning      eterne ten tte 5            1999 AAF M cQuay Incorporated    IM 660 1  Rev  5 99     Introduction                This manual  in conjunction with the Operation  amp  Maintenance Table 1  Model specific water source heat pump  Manual  provides information about the new MicroTech Water installation literature  Source Heat Pump  WSHP  controller and control system used INSTALLATION  amp   in the AAF M cQuay Incorporated WSHP product lines  The WSHP UNIT MODEL MAINTENANCE DATA  manual describes the controllers components  input output BULLETIN NUMBER  configurations  and service procedures  CCH HWH  007 120    For network installation or commissioning instructions refer CCH HWH  006 060   to the Operation  amp  Maintenance manual for the MicroTech FCV VWH  007 060   gateway panel  For general information on a particular WSHP LHP VWH  07 27   unit  refe
8. WSHP controller senses the AC voltage atthe power input  section terminais J 4 1 and J 4 2  see unit wiring diagram   If the  voltage at these terminals is less than 19 68VAC for atleast 1  second  the brownout fault will occur  The fault will automati   cally clear if the voltage at the terminals remains greater than  21 6 VAC for atleast 1 second    Ifa brownoutfaultoccurs  checkthe line voltage to the water  source heat pump  If itis less than 8296 of the nameplate value   contactthe power company  Ifthe line voltage remains greater  than 9096 ofthe nameplate value formore than 1 second butthe  fault does not reset  perform the following procedure     1  Measurethevoltage between terminais J 4 1 and  4 2 onthe  WSHP controller   If the voltage is unacceptably low or fluctuates around  19 68 VAC  the WSHP controller is functioning properly  Go  on to step 2   If the voltage remains above 21 6 VAC for 1 second but  the fault does not reset  the WSHP controller is defective     2  Checkthe primary and secondary voltages of power supply  transformers     3  Checkforfaulty wiring orconnections throughoutthe power  supply circuit     WSHP controller replacement    Data relating to the water source heat pump controller  configuration and characteristics are stored at the factory  when each unit is built and tested  If a WSHP controller is  defective and must be replaced  its unit specific software   defined by the above data  must be loaded into the replace   ment controller at t
9. anel trunk must have a unique address  Press and hold the  tenant override switch for at least 10 seconds or press and  release the service pin at each individual heat pump to  requestthe assignment of the next sequential address from  the MicroTech gateway panel     3  Check the status LED     The status LED should illuminate 30 to 40 seconds after  power up  If a wall sensor package is used  the remote  status LED should also illuminate     4  Verify that network communications between the water  source heat pump and the MicroTech gateway panel have  initiated    Atthe network PC  change the operating mode to unoc   cupied and checkthatthe status LED responds accordingly   Forfurther information on verifying communications  referto  the MicroTech Monitor P rogram User s Manual     5  Verify that the water source heat pump is operating in  accordance with its sequence of operation as outlined in the  appropriate documentation    Since the sensed temperatures are fixed at any given  moment  adjust the water source heat pump heating and  cooling setpoints  atthe network P C to obtain the expected  heating or cooling control actions    Adjust any other applicable parameters to obtain the  expected water source heat pump control actions     6  Check that any desired network  executed control features  are working properly  load shed  etc       7  Review the submittal drawings and make any necessary  changes to the default water source heat pump setpoints  and parameters     8  C
10. ating setpoint     Unoccupied cooling setpoint cannot be lower than low warning setpoint     Occupied cooling setpoint cannot be lower than unoccupied cooling setpoint   GOccupied heating and occupied cooling setpoints must differ by at least the differential     Start Up    Following are WSHP start up procedures foreach communica  PC access    tion type  The start up procedure must be performed by a  qualified technician for every WSHP on a job  Connections for  network wiring are made atterminals 5 and 6 of Terminal Board   1  The FTT 10  free topology transceiver  on the MicroTech  WSHP Controller is polarity insensitive  thus polarity issues  need not be addressed     Stand alone    Becausestand alonecontrollers areindependentofeach other   they may be started in any order     Page 6  IM 66 1    APC cannotbe used forstand alone WSHP start up  however   the start up process will be easier and faster if a PC and  MicroTech Network are used  If a PC is used  it must be  equipped with Monitor  software  Forfurtherinformation  refer  to  PC Connection  in the  Service Information  section of this  manual     Procedures for each stand alone WSHP   1  Apply powerto the unit  Turn the main power switch to  On      2  Check the status LED and operating mode changeover  devices    The status LED should illuminate 30 to 40 seconds after  power up  If a wall sensor package is used  the remote  status LED should also illuminate    Referring to Table 2  verify that the tenant override 
11. cal charge by touching the bare metal inside the main control panel before performing any service work  Never  unplug cables  circuit board terminal blocks  relay modules  or power plugs while power is applied to the panel        NOTICE     This equipment generates  uses and can radiate radio frequency energy and  if not installed and used in accordance with this instruction  manual  may cause interference to radio communications  Ithas been tested and found to comply with the limits fora Class B digital device   pursuant to part 15 of the FCC rules  Operation is subject to the following two conditions    1  This device may not cause harmful interference    2  This device must accept any interference received  including interference that may cause undesired operation    These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a  commercial environment  Operation of this equipment in a residential area is likely to cause harmful interference in which case the user  will be required to correct the interference at his own expense  McQuay International disclaims any liability resulting from any  interference or for the correction thereof              Page 2  IM 66 1    General Description    The new MicroTech WSHP controller is a control system  designed to provide control of McQuay and AAF water source  heat pumps  The controller enables the mode of operation   monitors the water and air temperatures  and indicates
12. ccordance with the field wiring  diagram supplied with the panel     Setpoint initialization   network units    The Water Source Heat Pump setpoint values are held  in memory and can only be modified over the MicroTech  network  Initially  before any changes are made over the  network  the WSHP will use the default factory set setpoints  shown in Table 3     DESCRIPTION FACTORY PROGRAMMED SETPOINT ADJ USTABILITY RANGE    Occupied Heating Setpoint 70  F  21  C  35   120  F  1 7   49  C  99  Occupied Cooling Setpoint 74  F  23  C  35   120  F  1 79 49 C 88  Fan   Occupied On On  Cycle  Heat  Cycle Cool On  Unoccupied Heating Setpoint 60  F  16  C  35   120  F  1 7   49  C     Unoccupied Cooling Setpoint 85  F  29  C  35   120  F  1 7   49  C     Fan   Unoccupied Cycle On  Cycle   Tenant Override   1st press 1 00 Off  0 30   8 00   Tenant Override   2nd press Off Off  0 30   8 00  Differential 2  F  1 2  C  1   10  F  0 6   5 6  C     Auto   Manual Auto Manual  occupied  unoccupied  fan only  off   Next Filter Change  hours  600 100 5000   Clock Schedule 1 up to 32   Load Shed Start Level Off Off  1 to7   Tenant Setpoint Adjustment Off  0  F  0  C  Off  On  3  F  1 7  C    Low Temperature Waming 55  F  13  C  35  F  1 7  C    high not used  High Temperature Warning 95  F  35  C  low not used   120  F  49  C                                                      Unoccupied heating setpoint cannot exceed high warning setpoint     Occupied heating setpoint cannot exceed unoccupied he
13. dth Modulation     Table 7    TYPE AC RMS CURRENT  DESCRIPTION RATING    E M Pilot Duty Relay  9 300 ma AC   SPST N 0 contacts    E M Pilot Duty Relay  9 300 ma AC   SPST N O contacts    E M Pilot Duty Relay or SS Random  tum on Triac   600 ma AC    SPST N O contacts     Fan Contactor       Compressor Contactor       Reversing Valve Solenoid       Leaving Water Temp Sensor Lvg Water Line  Condensate Drain Pan   On Board   Remote Basic Wall Sensor  Remote Wall Sensor       Condensate Overflow Sensor  Brown Out  supply voltage  Sensor  Room Air Temp Sensor   Tenant Override S etpoint Adjust                Digital inputs   The water source heat pump controller has four standard  digital inputs  Digital input conditioning includes RC filtering  with a time constant of at least 4 7 milliseconds  The base  module provides additional filtering using software filtering  techniques        On Board Status LED Yellow    DC sourced signal     current limited to 10 ma DC   E M Pilot Duty Relay  9 600 ma AC   J umper selectable isolated or  24VAC sourced SPDT contacts     Off Board Status LED       Multi Purpose  Spare   Isolated E M Contacts    Inputloutput tables    All WSHP controller input and output connections and their  corresponding watersource heatpump components areshown  in Table 8  page 11      Test Procedures    This section contains troubleshooting procedures for the  following     e Microprocessor problems  Power supply problems  Erroneous temperature readings  Digital input
14. e network  regardless of  whether power is cycled     Wall mounted sensor    There are four optional wall sensor packages avallable  All wall  sensors include a remote status LED and tenant override  button  Setpoint adjustment and thermometer are optional wall  sensorfeatures that are available in addition to the basic sensor    The wall mounted sensor must be field installed and field  wired to the water source heat pump  Terminal Board  1  provides the connections for all room temperature sensor field  wiring  Refer to the unit wiring diagram provided and to Bulletin  No  IM 529  MicroTech Room Temperature Sensors  for infor   mation on wall sensor package installation     Remote room setpoint adjustment    The remote setpoint adjustment potentiometerallows the room  setpoint to be adjusted up or down by as much as 3  F  1 7  C    Itis available with several ofthe optional wall sensor packages     Tenant override    A wall mounted tenant override switch is available for use with  all MicroTech WSHP unit controllers    A single press ofthe tenantoverride button lasting 1 0 to 6 0  seconds provides a momentary contact closure that causes the  unit to enter the    tenant override    operating mode fora settime  period  default   60 minutes   Except for the fact that it is  temporary  tenant override operating mode is identical to the  occupied operating mode    Pressing and holding the tenant override button for at least  6 0 seconds but not more than 10 0 seconds will activa
15. ended    e 144 MB  3    floppy disk drive   e Bus mouse card and mouse   e RS 232C serial communications port   e Parallel printer port   e Printer that supports Windows version 3 1   e  Optional  2400 Baud internal modem  9600 Baud  recommended    e DOS 5 0 or higher   e Windows 3 1 or higher    e MicroTech Monitor  software    Analog inputs    The MicroTech WSHP unit controller has six standard analog  inputs  The controller can sense temperatures in the range of  O F to 158  F   70  C to 70  C      Table 5     DESCRIPTION LOCATION    Discharge Air Temp Sensor Inlet to Fan    The digital inputs sense the presence or absence of an  extemal 24 VAC   2096 power source with a minimum of 10 ma  AC current flowing through the following isolated contacts     Table 6     DESCRIPTION LOCATION    Refrigerant High P ressure   N C HP Switch  Refrigerant Low Pressure   N C LP Switch  Refrigerant Low Temp   N C LT Switch  Remote Start Stop   N O Remote Switch                Refer to the wiring diagram supplied with your unit for  specific wiring details     Digital outputs    Ail digital outputs  with the exception of the on board and  offboard status LEDs  are capable of controlling electrome   chanical or solid state relays which switch inductive loads  9  24VAC   20   0 4 pF   steady state AC RMS currents listed  below  assuming 10x single cycle surge currents on initial turn  on  The on board and off board status LEDs are controlled by  one ofthe Neuron s I 0 pins capable of Pulse Wi
16. he factory  To do this  the factory needs the  following information     Full model number   Serial number   Date code for time of manufacture   Software version of code loaded in controller    The unit model and serial numbers are listed on the unit  dataplate  The date code and software version of code are  printed onthe MicroTech unitcontroller adhesive backed label   This information must be included with the replacement WSHP  controller part order     Table 8  Inputs and outputs for WSHP units Table 9  Thertnistor chart    CONNECTION COMPONENT DESCRIPTION    J1 1  TB 2 E Remote Digital Source  J1 2 TB 2 L Remote Digital Signal  J1 3 TB 2 U Spare Relay Normally Closed  J 1 4 TB  2 P Spare Relay Common  J 1 5   TB 2 C Spare Relay Normally Open  J 2 6  TB 1 1 Room Sensor LED  J 2 7   TB 1 2 Tenant Override  J 2 8   TB 1 3 Room Sensor Input  J 2 9   TB 1 4 Room Sensor Common  J 2 10   TB 1 5 Lon Talk Connection  J 2 11  TB 1 6 Lon Talk Connection  J  2 12   TB 1 7 24 VAC Common  J4 1 24 V Ground  J 4 2 24 VAC   4 3 Fan Relay Output  J4 4 Fan Relay Common   4 5 Compressor Contactor Output   4 6 Compressor Contactor Common   4 7 Reversing Valve Solenoid Output  J4 8 Reversing Valve Solenoid Common  J4 9 High Pressure Switch Signal  J4 10 Low Pressure Switch Source  J 4 11 Low Pressure Switch Signal  J 4 12 Low Temperature Switch Signal    4 13 Low Temperature Switch Source  J 4 14 Condensate Overflow Sensor   5 8 Leaving Water Temperature Sensor Input  J5 9 Leaving Water Tempe
17. heckthatthefan interlock feature works properly  Ifthe unit  is heating or cooling  the fan will be on  Ifthe compressor is  running  the fan will be on  In the unoccupied mode  if the  fan occupied setpoint is on  the fan will always be on  If  the setpoint is heat cycle cool on  the fan will cycle with the  compressor in heating and be on continuously in cooling     Diagnostic Service    Unit identification  Wink  command    Upon receiving a  Wink  command from a network manage   mentnode  theheatpump will exhibitthefollowing identification  sequence  LED and fan sequences occur simultaneously      LED  Flashes  on 0 5 sec  off 0 5 sec  for 15 seconds   Fan The heatpump fan will turn offfor5 seconds  turn onfor  5 seconds  then off again for 5 seconds     The  Wink  action will disrupt unit operation  The compres   sor will shut off during this period and the minimum off timer  must expire before the compressor will be allowed to run again    This function allows verification of an individual unit network  address without a need to open the unit access panels     Alarm monitoring  amp  control    The Water Source Heat Pump Controller is programmed to  monitor the water source heat pump for specific alarm condi     tions that may occur on the various model types  If an alarm  condition exists and is detected by the controller  a  fault  will  occur  The water source heat pump controller will indicate the  fault and execute appropriate control actions for the alarm  condition
18. igh pressure  switch input  J 4 9  sensed an open circuit while the controller  was Calling for the compressor to run    The high pressure switch  HP  is wired in series with the  compressor relay output  J 4 5  and the compressor relay coil   Therefore  if a high pressure condition occurs  the compressor  willbe immediately shut down by the switch  then unit operation  willbe disabled by the WSHP controller software  Refer to  Test  Procedures    in the    Service Information    section of this manual  for information on troubleshooting digital input faults     Effects  as applicable     e Compressor immediately de energized    e Normal unit operation disabled by software until manual  correction and reset of fault condition     Low temperature    The  Low Temperature  fault is an indication that the low  temperature switch input  J 4 12  sensed an open circuit while  the controller was calling for the compressor to run    The low temperature switch will open when the temperature  falls below its setpoint  model and size dependent   Refer to   Test Procedures  in the  Service Information  section of this  manual for information on troubleshooting digital input faults     Effects    e Unit will fail safe to cooling for sixty  60  seconds for coil  defrost    e After sixty  60  seconds in cooling  compressor and fan  immediately de energized by software    e Normal unit operation disabled by software until manual  correction and reset of fault condition     Page 8  IM 66 1    
19. istance and temperature match  the  WSHP controller may require factory service  or it may be  defective    If the measured resistance and temperature do not  match  elther there is a wiring problem or the sensor is  defective  Check the wiring connection and the sensor  circuit wiring for defects     Digital input faults    Usually  a digital input fault is caused by high pressure  low  pressure or low temperature alarrn conditions that are due to  mechanical problems in the water source heat pump  However   this type of fault could also be caused by a problern in the digital  input circuit    Following is a procedure that may be used to check for  problems in the digital input circuit  If the probable cause of the  fault is found using the procedure  attempt to clear the fault by  cycling power to the WSHP  If the probable cause of the fault  is not found using the procedure  assume that mechanical  problems exist and have a qualified technician service the unit  before attempting to reset the WSHP Controller     1  Check the voltage at the secondary of transformer  it should  be approximately 24 VAC     2  Determine the switch s digital input number  Referto the unit  wiring diagram or to the input output tables  Table 8      3  Check the wiring and connections throughout the digital  input circuit     4  Measure the resistance through the switch contacts  with at  least one wire disconnected   The switches are normally  closed     Page 10  M 66 1    Brownout fault    The 
20. k  A MicroTech  network provides a building operator with the capability to  perform advanced equipmentcontrol and monitoring from a PC  equipped with Monitor  software at a central or remote loca   tion  All control sequencing  stop start and safety monitoring is  displayed onthePC screen withthefollowing unique values and  parameters for each unit     e Return air and discharge air temperatures   e Compressor  fan and reversing valve status   e High pressure  low temperature  brownout and drain pan  status   e Occupied and unoccupied heat and cool setpoints  Auto   manual and occupied unoccupied fan control   e Mode  fault  system  schedule and setpoint operation   e Compressor starts and fan run hours   e Load shed level and tenant override    In addition  the following unique operation and maintenance  parameters can be displayed for each unit     e Leaving water temperature  e Return air temperature setpoint adjustment    Adaptive optimal start   Occupied unoccupied  on cycle  fan mode   Room temperature warning   Filter changes from fan hours   Compressor management  On off differential  minimum  off time  maximum cycle    Communication Fallure  fthe M icroTech network commu   nication link fails for any reason  the affected WSHP controller  will remain operational  Its operating mode will be that last  received over the network  or if power is cycled  it will default to  occupied  Its minimum position  heating  and cooling setpoints  will be those last received over th
21. l less than its setpoint for more than 1  second  it will trigger the brownout fault  The fault will reset  automatically when the sensed voltage remains at or above a  level corresponding to 9096 ofthe nameplate value for a period  of 1 second  Forinformation on troubleshooting this alarm  refer  to    Test Procedures    in the  Service Information  section of this  manual     Effects  as applicable    e Compressor is immediately de energized     Change fliter  network units only     The  Change Filter  notification indicates that the fan has  operated longer than the set number of hours  Typically  this  warning is used to alert the building operator of the need to  replace the filter  To clear the notification  the filter timer must  be reset at the network PC     Effect    An alarm message that identifies the water source heat pump  network address and time of occurrence will be sent to the  network printer     Service Information    PC specification    A personal computer may be used for monitoring network unit  operation  changing setpoints  trend logging  downloading  software  and diagnostics  The P C mustbe an IBM or100  true  compatible with the following features  minimum requirements      e 486SX CPU  Central Processing Unit    e 640 KB base RAM  Random Access Memory    e 4MB extended RAM  8 MB recommended    e 40 MB hard drive  200 MB  recommended    e VGA card and monitor  SVGA recommended color  recommended    e 640 x 480 resolution  800 x 600 resolution recomm
22. llowing events     IM 660 1  Page 3      Unit power up    Unoccupied to occupied changeover    Brownout condition    The compressorstart delay can be from 180 to 243 seconds   assuming a default initial delay of 180 seconds  and is deter   mined by the unique 48 bit unit ID     Delayed reversing valve de energization    All water source heat pump units have a 10 second reversing  valve de energization delay feature to prevent  swishing     This delay prevents the reversing valve from returning to its  normal  cooling  position for a period of approximately 10  seconds after the compressor is re energized when the unit is  in the heating mode  If necessary  an alarm condition can  override the delay timer and de energize the reversing valve  with the compressor     Condensate overflow alarm    Should a condensate overflow alarm be detected  the unit  controllerwill immediately disable the compressor  Once the  overflow alarm disappears  the unit controller will automatically  reset the WSHP unit  The condensate overflow sensor is an  exposed ring terminal located in the condensate drain pan  The  condensate overflow alarm will occur only when the unit is in  cooling mode     Brownout alarm    The on board brownout feature is meant to protect the com   pressor contactors from low voltage or  brownout  conditions   If the supply voltage to the water source heat pumps is below  8296 ofthe nameplate value  the WSHP controller will detect it     indicate it  and de energize the com
23. option  is working properly  Do this by pressing the tenant override  switch on the wall sensor  if present  and observing the  status LED     3  Verify that the water source heat pump is operating in  accordance with its sequence of operation as outlined in the  appropriate documentation     Network    Prior to the start up of any Network Water Source Heat Pump  Controllers  the following MicroTech network devices must be  commissioned       IBM   compatible PC with Monitor  software    MicroTech gateway panel    Refer to the literature supplied with these products for  information on installing and commissioning them    After these devices have been properly commissioned  the  network water source heat pumps may be started in any order   However  if the start up order follows the daisy chain from one  watersource heat pump to the next  itwilibe easierto detectany  wiring problems that may exist in the communications trunk     Communications cable check    Perform this check for every communications trunk connected   to a MicroTech gateway panel    1  Be sure that the network communication connectors are  disconnected at every water source heat pump on thetrunk     2  Using an ohmmeter  check that there are no shorts between  any two connectors in the communications trunk     Procedures for each network water source heat pump   1  Apply powerto the unit  Turn the main power switch to  On      2  Setthe network address     Each water source heat pump on a MicroTech gateway  p
24. or is located at the inlet to  the fan  The leaving water temperature sensor is located in the  leaving water line     Standard Control Features    The following are standard MicroTech WSHP control features  as applicable to the various water source heat pump model  types    e Control heating and cooling from a room sensor    e Monitor all safety controls    e Provide fan and compressor operation    e Monitor discharge air temperature    e Monitor leaving water temperature    e Provide status of all vital unit functions    e Provide optional control outputs     Control heating and cooling from a room    sensor    All water source heat pumps are designed to control the  room  or zone  temperature in response to space temperature  detected by the room temperature sensor     Compressor short cycle protection    All water source heat pumps include compressor short cycle  protection    When a compressoris energized  it will remain energized for  atleast 2 minutes before the temperature control sequence will  be allowed to de energize it  An alarm condition can override  this    minimum on    timer and stop the compressor if necessary   Whena compressoris de energized  it will remain de energized  for atleast 5 minutes before the temperature control sequence  will be allowed to energize it again     Random start    A random start feature is provided with all water source heat  pumps  This feature will prevent simultaneous compressor  start up that could otherwise occur after the fo
25. pressor  Upon rectification  ofthe brownout condition  when supply voltage remains above  9096 of nameplate   normal unit operation will resume     High pressure refrigerant alarm    If excessive pressure in the refrigeration circuit is detected by  the high pressure switch  the compressor and reversing valve  will be de energized immediately  Should the high pressure  alarm disappear  the unit controller must be manually reset by  disconnecting and reconnecting power to the unit     Low temperature refrigerant alarm    Upon detection of a low temperature refrigerant alarm  the unit  controller will immediately putthe reversing valve in the cooling  position for sixty  60  seconds  After sixty  60  seconds  the  compressor will be disabled  Should the low temperature alarm  disappear  the unitcontroller mustbe manually resetby discon   necting and reconnecting power to the unit  The low tempera   ture alarm will occur only when the unit is in heating mode     Low pressure refrigerant alarm    Upon detection of a low pressure refrigerant alarm  the unit  controller will immediately disable the compressor  Should the  low pressure alarm disappear  the unit controller must be  manually resetby disconnecting and reconnecting powerto the  unit     Change filter  network units only     When the water source heat pump fan run time exceeds a  network adjustable setpoint  a change filter notification is indi   cated locally and over the MicroTech network     Factory Configured Options
26. r to the model specific Installation Manual  see WMH CWH  007 019        Table 1   CCW  019 060    50 Hz only           WARNING    Electric shock hazard  Can cause personal injury or equipment damage   This equipment must be properly grounded  Connections and service to the new MicroTech WSHP controller control panel must be  performed only by personnel that are knowledgeable in the operation of the equipment being controlled              WARNING    Excessive moisture in the control panel can cause hazardous working conditions and improper equipment operation   When servicing this equipment during rainy weather or high humidity conditions  the electrical components in the main control panel must  be protected             ACAUTION       Extreme temperature hazard  Can cause damage to system components    The controller is designed to operate in ambient temperatures from 32  F to 140  F  O  C to 60  C   and in relative humidity up to 95    noncondensing   The controller can be stored in ambient temperatures from  40  F to 176  F   40  C to 80  C   and in relative humidity up  to 95   noncondensing         A WARNING       Ifthe watersource heat pump is to be used for temporary heating or cooling  the unit must first be properly commissioned  Failure to comply  with this requirement will void the warranty        AN CAUTION       Static sensitive components  Astatic discharge while handling electronic circuit boards can cause damage to the components   Discharge any static electri
27. rature Sensor Common  J 5 10 Discharge Air Temperature Sensor Input  J 5 11 Discharge Air Temperature Sensor Common  J 6 1 7 Auxiliary Module Connections                                                                                     WO  CO  SI  D  U1  A  wj N  e       m  e       m  um       m  N       m  Ww       m  A       m  ul       m  o       m  N       m  co       m  Ke        N  e       N  me       N  N       N  Ww       N  A2       N  ul       N  o       N  N       IM 660 1   Page 11    AAF McQuay Incorporated  4900 Technology Park Boulevard  Auburn  NY 13201 9030 USA   315  253 2771   1999 AAF McQuay Incorporated    e Printed on recycled paper containing at least 1096 post consumer material  IM 660 1  Rev  5 99     
28. s     Fault code interpretation    Water source heat pump faults are indicated at the status LED   on board orremote   Ifa fault exists  operating mode indication  will be replaced by a fault indication    During afaultcondition  the LED is constantly flashing  on 0 1  sec  off 0 1 sec  until the fault is cleared     Clearing faults    Before any fault can be cleared  the alarm conditions that  caused it must have returned to normal  When the alarm  conditions are gone  a fault may be cleared either automatically  or manually     IM 660 1   Page 7    Anauto reset fault will immediately clear whenever the alarm  conditions that caused it disappear    A manual reset fault can be cleared by cycling power to the  controller    Note  The cause of a manual reset fault should be investi   gated and eliminated before the unitis placed back into service     Alarm descriptions    Following are descriptions of the various faults listed in Table 4  and the low temperature fault     Table 4  Alarm and fault code summary    ALARM FAULT  DESCRIPTION TRIGGER FACTORY SETTING RESET   Fault   Clear     Opens at 395   10 psig  Closes at 250   25 psig  Opens et 7   3 psig  Closes at 22  7 psig  Conductivity trip point   2 5 microohms   Line Voltage   82    of Nameplate Voltage    Hardware Manual    High Pressure       Low Pressure Hardware Manual       Condensate    Overflow Manual    Hardware       Brownout Software Auto    High pressure    The    High Pressure    faultis an indication thatthe h
29. tatus LED    An amber  on board status LED aids in diagnostics by indicat   ing the water source heat pump operating mode and alarm  conditions  If there are no currentalarrn conditions  the LED will  indicate the unit operating mode as shown in Table 2  For more  information on alarms  referto the  Alarm Monitoring  amp  Control   section on page 7 ofthis manual    A remote status LED is provided with all optional wall  mounted temperature sensor packages  It has the same  function as the on board status LED  If used  the remote LED is    connected to the new MicroTech WSHP controller at connec   tion  1 on Terminal Board  1     Table 2  Status LED indication    STATUS LED STATE           Mob          On Continually Occupied  Occupied Load Shed   On 0 5 sec  Off 5 5 sec Unoccupied   On 5 5 sec  Off 0 5 sec Tenant Override  Override Load Shed  Alarm Condition    Condensate Overflow    Brownout  Compressor Fault              On 0 1 sec  Off 0 1 sec       Iftheunitcontrollerhas notbeen assigned a logical address   the intensity of the LED is low  If a logical address has been  assigned  the LED intensity is high     Temperature sensing    The MicroTech WSHP unit controller uses negative tempera   ture coefficient  NTC  thermistors for temperature sensing  A  thermistor chart  which provides voltage to temperature and  resistance to temperature conversion data  is included in the   Service Information  section ofthis manual  Table 9  page 11    The discharge air temperature sens
30. te the  network    query address    mode  indicating the unit address in  question at the MicroTech gateway panel    Pressing and holding the tenant override button for greater  than 10 0 seconds will activate the network    self configure     mode  requesting the assignment of the next sequential ad   dress from the MicroTech gateway panel     Commissioning    ZNWARNING       Electrical Shock Hazard  Could cause severe injury or death  Fallure to bond the frame ofthis equipmentto the building electrical ground  by use of the grounding terminal provided or other acceptable means may result in electrical shock  Service must be performed only by    qualified personnel        The following commissioning prodcedures pertain to water  source heat pumps equipped with the MicroTech Water  Source Heat Pump Controller  These procedures must be  performed in addition to the mechanical and electrical system  commissioning proceedures that are outlined in the model   specific installation literature  listing provided in Table 1      Caution  B efore power is applied to any unit  the pre start  procedures in the model specific installation literature must be  closely followed    A large part ofthe commissioned procedure is ensuring that  the water source heat pump operates according to its pro   grammed sequence of operation  The water source heat pump  sequences of operation are described in the Operation and  Maintenance Manual for the MicroTech Water Source Heat  Pump Unit Controller  
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
GPA789 Analyse et conception orientées objet  Worldwide Lighting W83178C36-CL Instructions / Assembly  User Manual Windows  pistolet de decoration a jet rond rg 3l  N /Réf : BPA 0605 Objet : Recommandations d  Mise en page 1 - Ntn  シール構造による高信頼性を実現 エンボステーピング梱包を品揃え  ∼ 取扱い上のご注意 ∼ - e    Manual - SIGMA ROX    Copyright © All rights reserved. 
   Failed to retrieve file