1. At least 5 size M8 screws Not included in de livery The type and size of the bolts depends on the flooring material e The same type number and size of anchor sleeves depending on the flooring material 4x e A drill with bits of the corresponding size 6 1 5 Bolt the anchor stand part 2 to the air curtain EZ 8 Keep the air curtain stable while you slide it on Immediately after sliding the air curtain into assembly position secure anchor frame part 1 to anchor frame part 2 using 4 size M8 bolts Included in delivery 6 INSTALLATION 6 1 7 Cover the anchor stand e The water intake and outlet positions can be chosen as you wish left right orientation The maximum water temperature is 100 C The maximum pressure is 1 6 MPa We recommend installing a stop valve on the intake and outlet of the heater to allow the water supply to be shut off e 4 e The water coil is equipped with two air release valves which can also be used for bleeding and are located at each end of the water coil Put the anchor stand covers on and bolt them down horizontally with 4 anchor bolts 6 2 1 Regulating the water coil with a ZV 3 three way valve eet Regulation of the VENESSE Comfort air cur tain s water coil must be handled separ
2. PARTNER IN VENTILATION VENESSE Comfort VCV B 25E VCV B 25F VCV B 25W VCV B 25S Full manual INSTALLATION 1 BEFORE YOU BEGIN _ Symbot sid Meaning AN ATTENTION Warhinglesaticn Before installation thoroughly read the section Safe use of air curtains It con tains all instructions on the safe and correct use of the product This manual contains important instructions to ensure correct installation of the air curtain Before installation read all of the following instructions thoroughly and then adhere to them The manufacturer reserves the right to make changes including to technical documentation without prior notice Save this user manual for further use The instructions in this manual are a part of the product Conformity disclosure VCV air curtains adhere to the following European Norms EN EN 55014 1 EN 55014 2 EN 60335 1 EN 60335 2 30 EN 61000 3 2 EN 61000 3 3 EN 61000 6 3 You will find the disclosure text on the CD supplied with the product 2 1 CHECK THE SHIPMENT After delivery immediately check to see if the packaged product is damaged If the packaging is damaged contact the delivery service If the complaint is not filed in time your claim may not be valid later e Check to see if it is the same product you ordered If there are any discrepancies do not unpack the air curtain and immediately report the defect to the supplier e
3. Select any air curtain as the controller MASTER and connect the control panel to it Then connect to this air curtain the air curtains that will be controlled SLAVE The same type of communication cable works for connecting the air curtains to one another and to the control panel MASTER SLAVE 1 5 U DK Door Switch SH Time switch Chained air curtains can be supplemented 6 7 COVERING THE AIR CURTAIN with these components After connecting the power supply the water intake and outlet and all external control elements close and secure the air curtain s The timer switch is service cover connected to the master air curtain Just one timer switch can be used for the entire chain of air curtains The timer switch shuts off Timer switch SH all air curtains in the chain A room thermostat TER P can be connected in place of the timer switch Door switch DK This can be connected individually to each air curtain When linked each air curtain will respond to its own contact Before putting the air curtain into operation check the following e Have any tools or other objects which could damage the air curtain been left inside it e Is there a proper supply of electricity and if necessary heating water e Has the air curtain been properly closed e Has the control panel been connected properly Us
4. from them Take care that during connection the connector snaps into place when mounting the cable to the wall make sure its insulation is not damaged If you do not connect the cable immediately after mounting the control panel and cur tain cover the connector or cable ends with insulation tape in order to prevent possible mechanical damage or short circuiting The cable connector must come into contact with water or any other liquid 6 5 CONNECT THE EXTERNAL COMPONENTS Optional accessories Wiring examples all types of air curtain KABEL 05M max 8mA e When connecting external components the electricity to the air curtain must be turned off All external control components must be connected according to the electrical schematic The connectors must be connected to the electrical board using reasonable force and always vertically to the base sa vn J is A Header Connector e For each component the original cable or one conforming its individual specifications must be used 13 6 INSTALLATION 6 5 1 Door switch DK nfe Isolated switching contact with a maximum voltage of 12V 6 Cable Dual core cable with a diameter of 0 5 mm Maximum length 50 Connector on the air curtain 17 18 AN Not included in delivery 6 5 2 Timer Switch SH Isolated switching contact with a maximum v
5. operating pressure of 1 6 MPa 6 INSTALLATION 6 1 CHOOSE THE INSTALLATION SITE 6 1 1 Installed dimensions Min 299 min 50 e The air curtain must be installed only ver tical position e The installed position of the air curtain can be chosen to accommodate the service cover Right left orientation e It must be operated dry covered indoor spaces with an ambient temperature between 5 and 35 and relative humidity up to 80 e The air curtain is not intended for moving air that contains combustible or explosive mixtures chemical fumes coarse dust soot grease poisons infectious germs etc 6 1 2 Clearance distance 2 S l 500 mm 25 lll 100 mm 100 mm vcv 8 25W 5 MATERIAL OK MATERIAL OK 500 mm 3 3 z 100 mm 1 6 INSTALLATION Only nonflammable materials those that do not burn smoulder or carbonise or fire resistant materials those that do not burn but mainly smoulder e g plaster board can be kept within 100 mm in any direc tion of the air curtain However these mate rials should not block the intake or outlet openings For air curtains with an electric heater safe distances from building structural surfaces and flammable objects are as fo
6. 04 The distance at which the average velocity of the air current flow drops to 2m s For optimal conditions and maximum performance of the equipment The value in parentheses is for two sided installation of the air curtain Two sided installation Acoustic pressure at a distance of 3 m from the air curtain With water temperature gradient of 90 70 and temperature of intake air at 18 C Air curtains with electrical heater VCV B 25E AGS 24 13 33 VCV B 25F 5400 36 20 Air curtains with a water coil for a water temperature gradient of 90 70 C and at a suction air temperature of 18 C VCV B 25W 25W 555 00 1 AY 5 TECHNICAL PARAMETERS Air curtains with a water coil for a water temperature gradient of 80 60 C and at an intake air temperature of 18 C m h kW C l s kPa VCV B 25W 25W 5100 33 8 37 6 0 41 7 Air curtains with a water coil for a water temperature gradient of 70 50 C and at an intake air temperature of 18 C m h kW C l s kPa VCV B 25W 25W 5100 26 4 33 4 0 32 5 Air curtains with a water coil for a water temperature gradient of 60 40 C and at an intake air temperature of 18 C m h kW C l s kPa VCV B 25W 25W 5100 19 29 0 23 4 The warm water temperature coil made of copper aluminium alloy is designed for EL a maximum operational water temperature of 100 C and a maximum
7. After unpacking check to see if the air curtain and other parts are in order If you have any doubts contact the supplier e Never install a damaged air curtain If you do not unpack the air curtain immedi ately after delivery it must be stored in a dry indoor environment with an ambient temper ature between 0 C and 40 C Allused packaging mate rials are environmentally friendly and may be re used or recycled Take an active part in en vironmental protection and see that packaging materials correctly disposed of or repur posed 2 2 UNPACK THE AIR CURTAIN e If the air curtain has been transported at temperatures below 0 C it will be neces sary to let it sit for at least 2 hours under nor mal operating conditions after unpacking without turning it on This will allow the air curtain s interior temperature to stabilise Anchor stand covers Service cover ee Locking bolt Upper cover Exhaust grid Anchor stand part 2 Anchor stand part 1 Anchor stand dimensions mm Air curtain dimensions mm 100 68 _ 300 S o 288 2457 5 TECHNICAL PARAMETERS 5500 56 230 6 5 55 5 24 400 335 230 65 103 5400 55 5 36 40 50 230 065 103 5100 ee 230 65 1
8. ately 6 2 CONNECT THE WATER INTAKE AND OUTLET HOSE E 6 5 5 Diagram for the connection of the VCV B 25W with accessories for the regulation of the water heater VCV B 25W O 2 N 0 IRES a Q ZV 3 A flexible hose with a G3 4 connection A e Connection and pressure testing of the hea ter must be carried out by an individual with el professional plumbing knowledge who must observe current standards and regulations of the given country e You will find a detailed explanation of regula ting the water coil using the three way valve ZV 3 including its connections in the ma nual for the ZV 3 three way valve 6 INSTALLATION 6 3 CONNECTING THE ELECTRICAL SUPPLY NOW lt The air curtain s electrical connection must be based on a professional design by a qua lified electrical systems engineer Installation must be carried out by a pro fessionally trained electrical worker All applicable national regulations and di rectives must be observed The electrical schematics on the product take priority over those presented in this manual Prior to installat
9. e the initial start up to check the basic equipment operation fan movement heat Check any other set functions according to the VENESSE Comfort Air curtain operation and maintenance guide 7 1 CONTROLS 7 1 1 Control panel VCV B 25S LED for CLEAN Turning the air curtain on and off Setting the fan speed VCV B 25E VCV B 25F VCV B 25W Turning the air curtain on and off LED for CLEAN Setting the fan speed Setting electric heater output 7 INITIAL START UP 7 1 2 Turning the air curtain on and off Press the button to turn the air curtain on Press the same button to turn the air curtain off Settings are indicated by an illuminated LED above the button 7 1 3 Setting the fan speed Press the 95 button to select of three fan speeds or to turn the fan off The setting is indicated by an illuminated LED above the button 17 7 INITIAL START UP 8 CONCLUSION 7 1 4 Setting the electric heater Press the i button to select one of two heat levels or to turn the heater off The setting is indicated by an illu
10. ion check to see if the ter minal markings correspond to the mark ings on the electrical connections diagram When in doubt contact your supplier and do not connect the air curtain under any circumstances Never reach inside the air curtain unless the main electrical supply has been turned off If the product is connected to any con trol system other than the original one the regulation and measurement compo nents must be connected by the company that supplied the system 6 INSTALLATION Minimal cable dimensions VCV B 25S VCV B 25E VCV B 25F VCV 8 25W 6 INSTALLATION 6 INSTALLATION Q 6 4 INSTALL THE CONTROL PANEL The electrical parameters are shown on the manufacturer s label which is located under the air curtain s service cover Air curtain Type U Voltage Net current f Frequency Output Speed m Weight ph Phase IP rating DM control for av Air output ver DM control for air curtain air curtain with electric without heater heater or with water p heater Serial number The air curtain must be protected by an appropriate circuit breaker in accor dance with its electrical parameters For safety reasons over designed protection is not recommen ded The air curtain must be connected using the TN S system which means that the neutral conductor must always be connected A main cut
11. llows the safe distance for flammable materials in the direction of the main air flow i e behind the outlet louvers is 500 mm the safe distance for flammable materials above the air curtain is 500 mm the safe distance for flammable materials in other directions is 100 mm 6 1 3 Measure the installation site Measure the site for installing the air curtain If the electrical cables are to run along the floor it is necessary to mark off the installation area including ports for electrical or heating fuel lines air curtain VCV B 25W Measure and mark the holes for the anchor stand The correct dimensions of the holes can be verified by placing the anchor stand on the place marked y aS SS oe eee i ee _ 6 INSTALLATION 6 INSTALLATION 6 1 CHOOSE THE INSTALLATION SITE x 6 1 4 Secure the anchor stand At least 4 size M5 bolts included in delivery part 1 to the floor A No 10 wrench 6 1 6 Slide the air curtain onto its stand part 1 Slide the air curtain with one anchor stand part 2 onto the fastened anchor stand part 1 and immediately secure the air curtain in the anchor stand with 4 vertically placed size M8 bolts Included in delivery The air curtain must be stably attached Use only high quality anchoring mate rials OL
12. minated LED above the button 7 1 5 Setting the water heater By pressing the buttons Ke it is possible to turn the water heater on or off only with version VCV B 25W For information on regulating the water heater read the manual for using the wa ter regulator e g ZV 3 TER P SMU OSMU etc 7 2 SET AIR FLOW DIRECTION This is set by tilting the air curtain s fan louvers in the desired direction 8 CONCLUSION After installing the air curtain thoroughly read the VENESSE Comfort Air curtain operation and maintenance guide as well as the Guide to air curtain safety If you have any doubts or questions do not hesitate to contact our sales or technical sup port department CONTACT Address 2VV 5 0 Pod bradska 289 530 09 Pardubice Czech Republic Internet http www 2vv cz contact distribution php Copyright c 2005 2007 2VV s r o All rights re served 01 0205 0110 00
13. off switch must be placed in the electrical supply network disconnecting all poles of the network e The electrical enclosure of the curtain is IP20 VENESSE Comfort air curtains are equipped with an 8A rated fuse This safety fuse protects the electronic panel and fans It is located on the electrical board next to the connectors for the door contact switches and other switches 11 6 INSTALLATION 6 4 1 6 4 2 6 4 3 6 4 4 6 4 5 6 4 6 6 4 7 Loosen the bolt on the under side of the control panel Open the box and remove the front cover from the upper latches Retain the back part of the box Cut a passage for the communication cable Use the areas moulded for this purpose Pull the communication cable through the passage you have cut and fasten the rear part of the panel to the wall Connect the communication cable to the electronics board located in the front cover of the panel Place the front cover with the electronics to the upper latches of the control panel box and snap the cover into the lower latches Fasten the bolt on the under side of the control panel 6 4 8 Connect the other end of the communication cable to the MASTER connector on the air curtain s electronic area a MASTER 6 INSTALLATION The cable should not be routed with power cables and should be located a sufficient dis tance away
14. oltage of 230V Cable Dual core cable with a diameter of 0 5 mm Maximum length 50 m Three conductor power cable with a diameter of 1 5 mm Connector on the air curtain 15 16 Not included in delivery The timer switch is modified for attachment on a DIN rack Placement in the distribution box is recommended The timer switch must be powered by its own supply 6 INSTALLATION 6 5 3 Room thermostat Room thermostat for the switching of the device depending on the tem perature set in the measured location e Switching contact without potential with max voltage 230 V CABLE Twin core cable with a diameter of 0 5 mm Maximum length 50 m Air curtain clamps TER Lopen Not included 6 5 4 Three way valve CABLE Three core power cable with diameter of 1 5 mm 230 50Hz dre Switching contact without potential with max voltage 230 V Air curtain clamps TER L N Not included 6 5 5 Diagram for the connection of curtain VCV B 25W with accessories for the regulation of the water heater Three way valve L N 230V 50Hz Main electrical input Room thermostat TER P 15 6 INSTALLATION 6 6 CONNECTING MULTIPLE AIR CURTAINS CHAINING The VENESSE Comfort air curtain is designed to allow up to six air curtains to be installed together as a chain and operated from one control panel

Download Pdf Manuals

image

Related Search

Related Contents

Manual Marathon 125 (Español)    The Konftel 300 User Guide  Adaptive Server® Anywhere SNMP Extension Agent User`s Guide  COMMISSION TECHNIQUE  VPAP™ ST A  Samsung S19A300N Hướng dẫn sử dụng  Trauma Recon System (TRS). Sistema de motor a pilas  3Com 1000BASE-SX Switch User Manual  SATEL NMS PC USER MANUAL  