USER`S MANUAL FC10KLAC5B

image

Contents

1. 240 pue N 0 pes 104 euo oeuuoo OU indui S N e Buisn indui eseud 114 ON S SIUL LNV LHOdMWI Input Power Connections and Grounding System Ground Connection The Earth Ground should be provided by the utility This is normally the GREEN wire provided by the utility which at some point is routed to a secure earth ground such as a water pipe This wire should be connected to the screw post marked GND on the Converter See photo for location Note that there are no internal electrical connections to this wire with the exception of a small high freguency bypass capacitor for RF suppression Therefore the function of the Earth Ground is simply to maintain the case of the Converter at ground potential Visicomm Industries LLC does not recommend any other connection to the Earth Ground wire which may introduce significant amounts of current and thereby defeat the intended purpose of this wire which is the safety of the operating personnel In particular do not connect this wire to the system neutral wire at any point Output Connection The Power OUTPUT Connections are provided by three barrier terminal posts labeled L1 and L2 These three terminals constitute the three terminals of an internal auto transformer were L1 is the center tap This is fed by the output winding of a switching transformer Since the only other internal connections are a resonating capacitor
2. 11
3. the cooling fans and sensing circuits to maintain an output sine wave these output terminals are electrically isolated from any other circuits including the system neutral The Converter is shipped with these OUTPUT connections electrically isolated If a digital voltmeter is connected between any one of these OUTPUT terminals and the Earth Ground a significant voltage reading will be obtained This voltage is due to a small leakage current and is not considered a problem since only 1 or 2 ma is involved Output Isolation Many applications require an isolated output primarily for safety reasons when supplying power to a device under test especially if there will be other monitoring equipment connected to the device Other applications can take advantage of the low leakage current of the Converter about 1 or 2 ma This can be useful in systems where the individual leakage currents of the components might exceed the allowed leakage current of a ground fault interrupter Other applications require that the output have a connection to the utility NEUTRAL Normally this would be OUTPUT terminal N The exception would be a two phase output where L1 would be the connection to the system NEUTRAL The Converter is supplied with a short jumper wire If the system NEUTRAL is used to power the INPUT terminals and it is required that the OUTPUT be connected to NEUTRAL this jumper can be employed to make this connection If the INPUT is supplied by t
4. SE OUTPUT BATTERY INPUT GND PHASE 1 PHASE 2 PHASE 3 DO NOT CONNECT THIS LEAD SYSTEM NEUTRAL IF PRESENT DO NOT CONNECT THIS LEAD EARTH GROUND OUTPUT POWER CONNECTIONS The frequency of the output power can be 50 or 60 Hz and is not related to the input frequency CAUTION The output is floating and is electrically isolated from the input It is necessary to connect the output using one of the following three methods Note that these output voltages are widely adjustable using the voltage adjust rheostat A SINGLE PHASE 120V OUTPUT CASE OUTPUT BATTERY INPUT GND SYSTEM NEUTRAL 120 VAC HOT LEAD B SINGLE PHASE 220V OUTPUT CASE OUTPUT BATTERY INPUT GND SYSTEM NEUTRAL 220 VAC HOT LEAD C SPLIT PHASE 220V OUTPUT CASE OUTPUT BATTERY INPUT GND 120 VAC HOT LEAD Phase 2 180 phase from Phase 1 SYSTEM NEUTRAL 120 VAC HOT LEAD Phase 1 GROUND 4 SPECIFICATION Mode TOKVAJBKW Voltage 120 or 220VAC 15 20 Frequency 50 Hz 60 Hz 5 Output ery 120 or 220VAC 20 adjustable Frequency 50Hz or 60Hz 400Hz available Frequency Stability 0 5 Transient 3 100 Load variation No load to full load with full recovery Response within 5 cycles Waveform Sine wave THD lt 3 at 0 100 linear load Overload Capacity 110 continuous 110 150 load 30 seconds over 150 causes ap ut unitto shut down Auto restart upon removal of the o
5. USER S MANUAL 4 Edition Visicomm Industries LLC 4525 Sheridan Rd Racine WI 53403 1 INTRODUCTION The conversion of electrical power is an essential reguirement for export testing or operation of eguipment brought to the U S from abroad The KSS series Freguency Converter is designed to meet these needs as it supplies reliable pure and stable power at an affordable price This Converter is designed with the following unigue features e Double Conversion IGBT module Single control board design eliminates adjustment and minimizes maintenance LCD display for unit status user friendly design Special overload capacity design 150 overload for 30 sec Built in isolation transformer to ensure total isolation between the input and output e Special airflow control to avoid dust accumulation Suitable for rough operating environments Front door access for ease of installation and servicing Compact size light weight The complete package includes Main Converter x 1 User s manual x 1 Front door key x 1 Battery Bank x 1 Screw to secure battery plug to battery receptacle box 2 1 FRONT PANEL 11 LCD Display Selector Switch 12 Freguency Selector Switch 13 Main Input breaker SW1 Controls the A C commercial input power in addition this breaker trips if the output power is subjected to a dead short 14 Input terminal The input power lea
6. cover or attempt to service the unit on your own High Voltage may be present even when the unit is shut down e Please follow all operational instructions STORAGE The converter should only be stored if the battery is fully charged Avoid storage temperatures above 80 F as battery life is significantly shortened Every 90 days remove the unit from storage and plug in for 24 hours to recharge the batteries Batteries may be damaged if left in storage and not recharged every 90 days IMPORTANT NOTICE Please use same type and same power rating of batteries for replacement Do not attempt to replace with batteries that exceed the specified ratings 10 5 BATTERY FACTS The batteries are the only serviceable parts in the converter The expected life of the battery is approximately 3 5 years However frequent long discharges or ambient temperatures above 80 F will shorten battery life Therefore it is recommended to replace the batteries every 3 years after initiating the unit Rechargethe batteries every 3 months if not in use as the batteries have a self discharge characteristic 5 1 BATTERIES AND RECHARGING 1 Batteries will automatically recharge when the converter has AC input power applied and input breaker SW1 and battery br eaker SW2 are both on Typical time about 8 10 hours to 9096 capacity FIG 5 1 BATTERY BACKUP TIME CHART 2 Please contact Visicomm ifa battery bank with longer backup times are required
7. ds will be connected to the terminal block Either 110VAC range or 220VAC range See Specification Sheet 15 Output Terminal Two 2 ranges 120VAC L N 240VAC LN See Specification Sheet 16 Output Voltage Adjustment potentiometer 17 Ground Terminal 18 Battery Breaker 18 90 48 26 cm 33 07 84 WIRE ACCESS DEPTH CUT OUT 13 39 34 cm FC10KLAC5B FREGUENCY CONVERTER FRONT 09 29 6k H1d3G web VL NOILOANNOO Au3llva SSIIIV 0 6 7 9 8 e i 406 8l 9e web VL yovga 4314 3ANO9 09 29 61 83999 SNIMIM LONI pE 21 WS gt 0681 8 40 4318 3ANO9 95 1N0 119 5399 anis 9 8 406 8L 14014 web vL 09 28 6L HLdad WNOILdO N Ove 051 ozz OLL 0 02 05 9602 02 US Va 29 LAdLNO LAdNI OV SNOI LO3NNOO LAdLNO LNdNI 271 01 pes
8. verload Bat 192VDC Sealed Lead Acid maintenance free 12VDC 7AH Recharge Time 8 10 hours to 90 capacity Efficiency gt 85 Battery Time 11 Minute O full Load Battery Low shutdown and breaker 150 30sec cut off Current Limited Protection hort Circuit Unit will cut off and must be manually restarted Audible Alarm ounds continuously onverter status amp O P voltage amp O P frequency Indicators Line Green LED Inverter Green LED Fault Red LED Overload Yellow LED 10 100KHz at 40dB 100KHz 100MHz at 70dB ounds Every 4 sec After mains fail mute after 90 sec Operation Temp 10 50 C 14 122 F Relative Humidity 20 90 non condensing Audible Noise Less than 58dB at 1 meter Input Terminal Block Physical Dimensions 18 90 48cm s 20 A gt SE gt t ounds Every second when battery approaches low level n ounds continuously n o o m oj oj u lt 0 301 lt lt m WARNING Only a gualified technician should replace the battery Batteries have a high short circuit capacity Mistakes in connecting or disconnecting the batteries can cause connections to arc or weld and could result in severe burns e Please keep battery fully charged to extend battery life e There no customer serviceable components inside Don t open the
9. wo phase AC or by two phases of a three phase system in other words if you have only two incoming power wires this NEUTRAL would not be present and an external wire from the desired OUTPUT terminal to the system NEUTRAL would be required See INPUT CONNECTION DIAGRAM on next page d E Basic diagram of output stage INPUT POWER CONNECTIONS The freguency of the input power can be 50 or 60 Hz and is not related to the output freguency CAUTION The Input is Electrically Isolated from the output Itis necessary to connect the input using of the following four methods A SINGLE PHASE 220V INPUT This connection is usually used in 50Hz countries where a neutral is normally available CASE OUTPUT BATTERY INPUT GND 1 12 a 220 HOT LEAD EARTH SYSTEM NEUTRAL GROUND B SPLIT PHASE 220V INPUT This connection is usually used in 60Hz countries where a 220V line is not normally available and where the input amperage makes using 120V inconvenient CASE OUTPUT BATTERY INPUT GND 120 VAC HOT LEAD Phase 2 180 phase from phase 1 120 VAC HOT LEAD Phase 1 SYSTEM NEUTRAL DO NOT CONNECT THIS LEAD EARTH GROUND C SINGLE PHASE 120V INPUT CASE OUTPUT BATTERY INPUT GND SYSTEM NEUTRAL 120VAC HOT LEAD GROUND D THREE PHASE 120 208VAC USING LINE TO LINE INPUT To be used if the 120V line to neutral connection is limited by the amperage available CA