Home
        Output Relay Electrical Function Module
         Contents
1.  Function Modules   Output Relay Electrical Function Module 3    Application The ORE Function Module is typically used for     e control of 2 wire motor starter circuits  or similar electrical  equipment  so equipment fails to a known state when the DCM loses  power    Capabilities Table 1  ORE Function Module Capabilities    Input from DCM DCM inputs a digital Allows DCM to provide  command  automatic control of outputs     Hand Off Auto  HOA  Switch selects one of Allows for manual override  Status Switch   Auto  DCM relay control of DCM control for special  of outputs  situations   Hand  Opens the  Common N C  circuit and  closes the Common N O   circuit     Off  Opens the Common Allows for local manual  N O  circuit and closes control  even if the DCM is  the Common N C  circuit    not present     Note  Hand Off positions  mechanically force a contact  transfer     Power on Reset At low power or after power Provides controlled restart   up  relay is de energized    Output to Field Module provides Form C Provides contact closure  contact control  control for field devices        4 Function Modules   Output Relay Electrical Function Module    Theory of Figure 2 is a functional diagram of the ORE Function Module     Operation             DCM                   ORE E   Relay   NO      a LH       PA O    Control ae A       a A Le e Wo com    Field  Li jj  gt  Device     N o          N C           orel01    Figure 2  ORE Function Diagram    Under DCM control  the process is     
2.  coil  1 000 VAC  50 60 Hz   for 1 minute  between N O  and N C   contacts  Mechanical  10 000 000 operations  Electrical  300 000 operations for inductive load at 120  VAC  at   1 amp with a power factor of 0 4    Maximum  100 msec  At low power or after power up  relay is de energized     Power is from the PWR in the NCU NEU     32 to 122F  0 to 50  C   10 to 90  noncondensing RH  86  F  30  C  maximum dew point     40 to 158 F   40 to 70  C   5 to 95  noncondensing RH  86  F  30  C  maximum dew point    0 85 in  H x 2 6 in  W x 7 0 in  L    2 2 cm H x 6 6 cm W x 17 8 cm L    0 5 Ib  0 22 kg    FCC Part 15 Subpart J   Class A  UL 916  CSA C22 2 No  205    UL Listed and CSA Certified as part of Metasys         6 Function Modules   Output Relay Electrical Function Module    Installation Procedures  AAA AAA ae    General When installing and connecting function modules   Information e follow NEC and local codes    e observe maximums as specified in the specification table and in these  installation guidelines    Motor Starter Figure 3 diagrams the wiring for motor starter applications using the ORE  Function Module     X1 X2  A Motor      _H   Starter      7 Holding   7    N Coil   Overloads       Wire Gauge OO  and Length  Per Local Codes                                           A  ORE TBF  no   4 p  Relay   NL     H     E     DCM Control    gt  va A    Electronics    lt  S    o_o e COMAS    7 IES a  AN Teak  e  Nc 2      LN  Connection to DCM A J    completed through eae    
3. M    internal connector  lt  lt  TBF in left bay TBF in rightbay  gt   Es  on end of function ofNCU NEU ofNCU NEU Sa   module  Z         lt                                                                  SY 4    N Strip wire and insert in side  N set screw in front face to secure        face of TBF  Use j JI       orewire    Figure 3  Wiring for Motor Starter Applications    Function Modules   Output Relay Electrical Function Module 7    Physical  Installation  Assumptions The following procedure for the physical installation of the ORE Function  Module assumes    e Panel  NCU or NEU  is installed    e Connections to field devices are complete    e You have engineering drawings defining details for the installation     e You are familiar with Metasys Network terminology  and the location  and operation of power switches     Procedure For each ORE Function Module in the network  perform the following  steps     1  Set the HOA switch to off     2  Refer to the engineering drawings and identify the proper panel and  slot number location for this module     Open latch   4  Insert the module in the appropriate slot     5  Close latch  locking function module in place     8 Function Modules   Output Relay Electrical Function Module    Physical  Verification    Assumptions    Procedure    Software  Verification    Assumptions    Procedure    Commissioning Procedures    The following procedure for the physical verification of the  ORE Function Module assumes     e Physical installat
4. Metasys Network Technical Manual 636  Function Modules Section       METASYS 2 Technical Bulletin    Issue Date 0294       Output Relay Electrical Function Module          Introduction Page 3  e Description 3  e Application 4  e Capabilities 4  e Theory of Operation 5  e Specifications 6  Installation Procedures 7  e General Information 7  e Motor Starter 7  e Physical Installation 8  Commissioning Procedures 9  e Physical Verification 9  e Software Verification 9  Troubleshooting Procedures 11  e Troubleshooting Chart 11  e Ordering Information 13    Indicates those sections where changes have occurred since the last printing      1994 Johnson Controls  Inc  1    Order No  636 049    2 Function Modules   Output Relay Electrical Function Module    Introduction       Description The Output Relay Electrical  ORE  Function Module is an interface  between the DCM and field devices  This function module provides  on off control of field devices  The ORE features     e electrically maintained Form C relay and interface logic to enable the  DCM to control this relay    e Hand Off Auto  HOA  switch for manual control  e feedback indication of the HOA switch setting to the DCM    The ORE Function Module plugs into any one of the bottom ten slots  associated with the DCM  Figure 1 shows typical function module  locations in the NCU  A five slot panel is pictured     Output FMs                         DCMs                                        Figure 1  ORE Function Module Locations   
5. The DCM provides control signals to the ORE     When the relay is energized  its pair of contacts change state   The N C  contacts open  and the N O  contacts close     A manually controlled HOA switch can disable the DCM control of  the ORE outputs  and mechanically produce either an energized  H  or  de energized  O  condition  This control is mechanical  and works  even if the NCU or NEU is not powered up  The status of this switch  1s reported back to the DCM     Function Modules   Output Relay Electrical Function Module 5    Specifications    Table 2  ORE Function Module Specifications  Category Specifications For Configurations  Product Code Number    Output Range    Two states  contact open closed with respect to Common  on  each of two leads    Output Protection    Inrush Current  Relay Type    Relay Contact Rating    Relay Insulation  Resistance    Relay Dielectric  Strength    Relay Service Life    Response Time  Default Condition  Source Power    Operating  Environmental  Requirements    Storage Shipping  Environmental  Requirements    Agency Compliance    Agency Listings    Common output fused at 3 amps with a slow blow  non field  replaceable fuse     30 amps maximum    Form C relay having a Normally Open  N O   and Normally  Closed  N C   contact with a common connection between  them  Contacts are    break before make    type    120 VAC  at 1 amp max   pilot duty    1 000 M ohms  min  from contacts to coil    2 000 VAC  50 60 Hz   for 1 minute  from contacts to
6. ion at the NCU NEU panel is complete     e Power is available at the panel power supply  and at the field device     For each ORE Function Module in the network  perform the following  steps     1  Power up the appropriate DCM power supply     2  Set the HOA switch to Hand  Verify that the device is activated  and or that the appropriate device is deactivated as defined in the  engineering drawings     3  Set the HOA switch to OFF  Verify that the device is activated and or  that the appropriate device is deactivated as defined in the engineering  drawings     The following procedure for the software verification of the  ORE Function Module assumes     e Physical installation at the NCU NEU panel is complete  including  NCM  DCM  FM  etc     e The operating software for the network has been downloaded to the  NCM controlling the panel     e An Operator Workstation is available near the panel     For each ORE Function Module in the network  perform the following  steps     1  Select the System summary that includes this ORE object   2  Set HOA switch on the ORE to Auto     3  Use the software override command and verify that the object   s Value  attribute  as seen in the summary  matches the actual value for the  field device     Function Modules   Output Relay Electrical Function Module 9    10 Function Modules   Output Relay Electrical Function Module    Troubleshootin    g Chart    Troubleshooting Procedures    Use the diagram in Figure 4  next page  as a troubleshooting g
7. uide  It  applies for failures between point objects and field devices connected  through an ORE Function Module     Function Modules   Output Relay Electrical Function Module 11    Start          y    1s the     lt  lt  Summary ee   lt  containing this object E  gt  Exit     displaying correct _      values                   No          E Ponto y i Fix definition    lt  object definition 2     See Operator Workstation                o    SOK  User s Manual    NN fe      Yes    PN  ias    DOM                                                                              na LED off and Ne No Troubleshoot DCM    lt  is N2 polling and  gt        See DCM 101 Technical ARA     responding    Bulletin _   pe  fh 1 Sg  control circuit Se No Repair if JCI is a  SN power i responsible  SY OK  Pa  ls  M Replace FM   ASS See Ordering Information for  pe Usinga    ordering information  Refer  DVM  check FM  No to Material Return and  o output  Isit    Allowance Program      NOK  A Procedure 3C2700 for  SOK information on returning  defective FMs   Yes  _Z Using a HA i Troubleshoot   lt  DVM  check input  gt  e  gt   connections    Seen ue andi  ye  Repair or replace field  device if JCI is responsible  orefiow             Figure 4  ORE Troubleshooting    12 Function Modules   Output Relay Electrical Function Module       Ordering Table 3  Ordering Information  Information Product Code Number    Function Modules   Output Relay Electrical Function Module 13    Notes    14 Function Modules   O
8. utput Relay Electrical Function Module    Notes    Function Modules   Output Relay Electrical Function Module 15    Notes    JEHNSON  CONTRSLS  Controls Group FAN 636  507 E  Michigan Street Metasys Network Technical Manual  P O  Box 423 Revision Date 0194  Milwaukee  WI 53201 Printed in U S A     16 Function Modules   Output Relay Electrical Function Module    
    