        Compact™ 1769-OW8 AC/DC Relay Output Module
         Contents
1.             10 removable terminal block             n  RTB  with finger safe cover  8b 10a    RTB upper retaining screw       10b   RTB lower retaining screw          Publication 1769 5 2    Compact    1769 OW8 AC DC Relay Output Module 3    Module Installation    Compact I O is suitable for use in an industrial environment when installed in  accordance with these instructions  Specifically  this equipment is intended for  use in clean  dry environments  Pollution degree 2    and to circuits not exceeding  Over Voltage Category Ir   IEC 60664 1      Prevent Electrostatic Discharge    ATTENTION  Electrostatic discharge can damage integrated  circuits or semiconductors if you touch bus connector pins   Follow these guidelines when you handle the module     e Touch a grounded object to discharge static potential   e Wear an approved wrist strap grounding device    e Do not touch the bus connector or connector pins    e Do not touch circuit components inside the module    e If available  use a static safe work station     e When not in use  keep the module in its static shield box     Remove Power    ATTENTION  Remove power before removing or inserting   this module  When you remove or insert a module with power   applied  an electrical arc may occur  An electrical arc can cause   personal injury or property damage by    e sending an erroneous signal to your system   s field devices   causing unintended machine motion    e causing an explosion in a hazardous environment    Electr
2.    lbs      Note  If you need to remove the finger safe cover  insert a screw driver into one  of the square  wiring holes and gently pry the cover off  If you wire the  terminal block with the finger safe cover removed  you will not be able to  put it back on the terminal block because the wires will be in the way     Wire Size and Terminal Screw Torque    Each terminal accepts up to two wires with the following restrictions     Terminal Screw    Retaining Screw       Wire Type Wire Size Torque Torque  Solid Cu 90  C  194  F     14 to  22 AWG   0 68 Nm  6in lbs    0 46 Nm  4 1 in lbs   Stranded   Cu 90  C  194  F     16 to  22 AWG   0 68Nm  6in lbs    0 46 Nm  4 1 in lbs                    Publication 1769 5 2    10 Compact    1769 OW8 AC DC Relay Output Module    I O Memory Mapping    Output Data File    For each module  slot x  word 0 in the output data file contains the control  program   s directed state of the discrete output points  For the 1769 OW8  bits 8  to 15 are not used           _ Bit Position   o     15114113  12111019 817 651413121110  010 1 OO MON NO NO MONO WIWIWIWwWIwWIIwIwIw                                                    w   write    Output Module   s Input Data File    For each module  slot x  input data file word 0 contains the state of the module   s  output data  output data echo  file word 0  During normal operation  these input  bits represent the logic state that the outputs are directed to by the control  program  They are also dependent upon 
3.  aside  This reduces remounting time during  drilling and tapping of the next group     7  Repeat steps 1 to 6 for any remaining modules     DIN Rail Mounting    The module can be mounted using the following DIN rails  35 x 7 5 mm  EN 50  022   35 x 7 5  or 35 x 15 mm  EN 50 022   35 x 15      Before mounting the module on a DIN rail  close the DIN rail latches  Press the  DIN rail mounting area of the module against the DIN rail  The latches will  momentarily open and lock into place     Publication 1769 5 2    Compact    1769 OW8 AC DC Relay Output Module 7    Replacing a Single Module within a System    The module can be replaced while the system is mounted to a panel  or DIN rail      1   2    Remove power  See important note on page 3     On the module to be removed  remove the upper and lower mounting  screws from the module  or open the DIN latches using a flat blade or  phillips style screw driver      Move the bus lever to the right to disconnect  unlock  the bus     On the right side adjacent module  move its bus lever to the right  unlock   to disconnect it from the module to be removed     Gently slide the disconnected module forward  If you feel excessive  resistance  check that the module has been disconnected from the bus  and  that both mounting screws have been removed  or DIN latches opened      Note  It may be necessary to rock the module slightly from front to back  to remove it  or  in a panel mounted system  to loosen the screws of  adjacent modules     
4. A                       1  Surge Suppression   Connecting surge suppressors across your external inductive load will extend the life  of the relay contacts  For additional details  refer to Industrial Automation Wiring and Grounding Guidelines   Allen Bradley publication 1770 4 1    2  For dc voltage applications  the make break ampere rating for relay contacts can be determined by dividing  28 VA by the applied dc voltage  For example  28 VA 48V dc   0 58A  For dc voltage applications less than  48V  the make break ratings for relay contacts cannot exceed 2A        Publication 1769 5 2    14 Compact    1769 OW8 AC DC Relay Output Module    Hazardous Location Considerations    This equipment is suitable for use in Class I  Division 2  Groups A  B  C  D or  non hazardous locations only  The following ATTENTION statement applies to  use in hazardous locations     ATTENTION  EXPLOSION HAZARD    e Substitution of components may impair suitability for Class I   Division 2     e Do not replace components or disconnect equipment unless  power has been switched off     e Do not connect or disconnect components unless power has  been switched off     e This product must be installed in an enclosure     Environnements dangereux    Cet   quipement est con  u pour   tre utilis   dans des environnements de Classe 1   Division 2  Groupes A  B  C  D ou non dangereux  La mise en garde suivante  s    applique    une utilisation dans des environnements dangereux     ATTENTION  DANGER D   EXPLO
5. A removable  write on label is provided with the module  Remove the label from  the door  mark the identification of each terminal with permanent ink  and slide  the label back into the door  Your markings  ID tag  will be visible when the  module door is closed        1  Surge Suppression   Connecting surge suppressors across your external inductive load will extend the life  of the relay contacts  For additional details  refer to Industrial Automation Wiring and Grounding Guidelines   Allen Bradley publication 1770 4 1     Publication 1769 5 2    Removing the Finger Safe Terminal Block    Compact    1769 OW8 AC DC Relay Output Module 9    upper retaining screw T     lower retaining screw        np                   IS          wiring the       finger safe  terminal block    SY    To remove the terminal block  loosen the upper and lower retaining screws  The  terminal block will back away from the module as you remove the screws  When  replacing the terminal block  torque the retaining screws to 0 46 Nm  4 1 in lbs      Wiring the Finger Safe Terminal Block    When wiring the terminal block  keep the finger safe cover in place     1  Loosen the terminal screws to be wired     2  Route the wire under the terminal pressure plate  You can use the bare wire  or a spade lug  The terminals will accept a 6 35 mm  0 25 in   spade lug     3  Tighten the terminal screw making sure the pressure plate secures the wire   Recommended torque when tightening terminal screws is 0 68 Nm  6 in
6. B    Compact    1769 OW8  AC DC Relay Output Module    Installation Instructions    Inside   Module Description    2  Module    Install  tion   ss ss 3  System Assembly  amenant menthe  4  Mounting Expansion IQ  5  Replacing a Single Module within a System    7  Field Wiring Connections    8  VO Memory Maping   228 remettent nan 10  SPecifications terre eae nt nent nn 11  Hazardous Location Considerations   0 00    cesseeseseee 14  Environnements dangereux           seccccceseescsseseseseecsseeessnsseeeeeeeeesnssteeseteetsneess 14  For More Information         c cccessescssesecesseecseeeeseeseeceaeeessneaeeceaeeessneseeeeeeetsneess 15    Rockwell  Automation    Publication 1769 5 2    2 Compact    1769 OW8 AC DC Relay Output Module    Module Description    Item Description    2a bus lever     with locking function                 2a  upper panel mounting tab                         Ee                   2b   lower panel mounting tab  10a       3  I O diagnostic LEDs       4 module door with terminal  identification label       10b    i   2580585888       5a movable bus connector  With female pins                                                    5b stationary bus connector  with male pins                   6  nameplate label       7a  upper  tongue and groove slots          7b lower  tongue and groove slots             5b             8a  upper DIN rail latch                   8b lower DIN rail latch                                     9  write on label  user ID tag           
7. Before installing the replacement module  be sure that the bus lever on the  module to be installed  and on the right side adjacent module are in the  unlocked  fully right  position     Slide the replacement module into the open slot     Connect the modules together by locking  fully left  the bus levers on the  replacement module and the right side adjacent module     Replace the mounting screws  or snap the module onto the DIN rail      Publication 1769 5 2    8 Compact    1769 OW8 AC DC Relay Output Module    Field Wiring Connections    Grounding the Module    This product is intended to be mounted to a well grounded mounting surface  such as a metal panel  Additional grounding connections from the module   s  mounting tabs or DIN rail  if used   are not required unless the mounting surface  cannot be grounded  Refer to Industrial Automation Wiring and Grounding  Guidelines  Allen Bradley publication 1770 4 1  for additional information     Output Wiring  Basic wiring  of output devices to the 1769 OW8 is shown below   ATTENTION  Be careful when stripping wires  Wire fragments    that fall into a module could cause damage at power up  Once  wiring is complete  ensure the module is free of all metal                                                             fragments   us Lt or DC      OUT 0   cr    OUT 1 CR L2 or  DC  CRH our2  lt   Le OUT 3  eR     Li or  DC VAC VDC  2  cr  ZN OUT 5  cr  7  L2 or  DC  cn  OUT 4  OUT 7  LCR  OUT 6  Le                                     
8. SION    e La substitution de composants peut rendre cet   quipement  impropre    une utilisation en environnement de Classe 1   Division 2     e Ne pas remplacer de composants ou d  connecter l   quipement  sans s   tre assur   que l alimentation est coup  e     e Ne pas connecter ou d  connecter des composants sans s   tre  assur   que l alimentation est coup  e     e Ce produit doit   tre install   dans une armoire     Publication 1769 5 2    Compact    1769 OW8 AC DC Relay Output Module 15    For More Information    For Refer to this Document Pub  No     A more detailed description of how to install      and use your Compact I O with MicroLogix   MicroLogix 1500 Programmable   1764 6 4          1500 programmable controller  Controllers User Manual  More information on proper wiring and Industrial Automation Wiring and 1770 4 1  grounding techniques  Grounding Guidelines i          If you would like a manual  you can     e download a free electronic version from the internet   www ab com micrologix or www theautomationbookstore com    e purchase a printed manual by       contacting your local distributor or Rockwell Automation representative      visiting www theautomationbookstore com and placing your order        calling 1 800  9NEWLIT  800 963 9548   USA Canada   or 001 330 725 1574  Outside USA Canada     Publication 1769 5 2    16 Compact    1769 OW8 AC DC Relay Output Module    Compact and MicroLogix are trademarks of Rockwell Automation        Reach us now at www roc
9. energized         Signal Delay  max       resistive load    turn on   10 ms  turn off   10 ms       Off State Leakage  max      OmA       On State Current  min      10 mA at 5V de       Continuous Current per Point  max      2 5A  Also see    Relay Contact Ratings    on page 13         Continuous Current per Common   max      8A       Continuous Current per Module  max      16A       Power Supply Distance Rating    8  The module may not be more than 8 modules away  from the power supply         Isolated Groups    Group 1  outputs 0 to 3  Group 2  outputs 4 to 7       Output Group to Backplane Isolation    Verified by one of the following dielectric tests  1836V ac  for 1 sec  or 2596V dc for 1 sec     265V ac working voltage  IEC Class 2 reinforced  insulation        Output Group to Output Group  Isolation    Verified by one of the following dielectric tests  1836V ac  for 1 sec  or 2596V dc for 1 sec     265V ac working voltage  basic insulation   150V ac working voltage  IEC Class 2 reinforced  insulation        Vendor   D  Code    1       Product Type Code    7       Product Code       86       Publication 1769 5 2    Compact    1769 OW8 AC DC Relay Output Module 13                      Relay Contact Ratings  Amperes  Voltamperes  Volts   Continuous Amps NEMA    max   per Point  max     Make   Break   Make Break   IEC 947   ICS 2 125  240V ac 7 5A   0 75A       2 5A 1800 VA  180 VA   AC15 C300  120V ac 15A   1 5A  125V de 1 0A 0 22A2 28 VA DC13 R150  24V de 2 0A 1 2A2 28 V
10. ical arcing causes excessive wear to contacts on both the  module and its mating connector  Worn contacts may create  electrical resistance        1  Pollution Degree 2 is an environment where  normally  only non conductive pollution occurs except that  occasionally a temporary conductivity caused by condensation shall be expected    2  Over Voltage Category Il is the load level section of the electrical distribution system  At this level transient  voltages are controlled and do not exceed the impulse voltage capability of the product   s insulation    3  Pollution Degree 2 and Over Voltage Category Il are International Electrotechnical Commission  IEC   designations     Publication 1769 5 2    4    Compact    1769 OW8 AC DC Relay Output Module    System Assembly    The module can be attached to the controller or an adjacent I O module before or  after mounting  For mounting instructions  see    Panel Mounting    on page 5  or     DIN Rail Mounting    on page 6  To work with a system that is already mounted   see    Replacing a Single Module within a System    on page 7     The following procedure shows you how to assemble the Compact I O system     8        Disconnect power     Check that the bus lever of the module to be installed is in the unlocked   fully right  position    Use the upper and lower tongue and groove slots  1  to secure the modules  together  or to a controller      Move the module back along the tongue and groove slots until the bus  connectors  2  line u
11. kwellautomation com    Wherever you need us  Rockwell Automation brings together leading  brands in industrial automation including Allen Bradley controls    Reliance Electric power transmission products  Dodge mechanical power  transmission components  and Rockwell Software  Rockwell Automation s  unique  flexible approach to helping customers achieve a competitive  advantage is supported by thousands of authorized partners  distributors  and system integrators around the world           Allen Bradley  ARAMEIE   DODGE    Americas Headquarters  1201 South Second Street  Milwaukee  WI 53204  USA  Tel   1  414 382 2000  Fax   1  414 382 4444 ET   R kw Il  European Headquarters SA NV  avenue Herrmann Debroux  46  1160 Brussels  Belgium  Tel   32  2 663 06 00  Fax   32  2 663 06 40 OC   e  Asia Pacific Headquarters  27 F Citicorp Centre  18 Whitfield Road  Causeway Bay  Hong Kong  Tel   852  2887 4788  Fax   852  2508 1846 Automation  Publication 1769 5 2   January 1999 40071 048 01  A        1999 Rockwell International  All Rights Reserved  Printed in USA    
12. p with each other     Push the bus lever back slightly to clear the positioning tab  3   Use your  fingers or a small screw driver     To allow communication between the controller and module  move the bus  lever fully to the left  4  until it clicks  Ensure it is locked firmly in place     ATTENTION  When attaching I O modules  it is very  important that the bus connectors are securely locked  together to ensure proper electrical connection     Attach an end cap terminator  5  to the last module in the system by using  the tongue and groove slots as before     Lock the end cap bus terminator  6      IMPORTANT  A 1769 ECR or 1769 ECL right or left end cap must be used to    terminate the end of the serial communication bus     Publication 1769 5 2    Compact    1769 OW8 AC DC Relay Output Module 5    Mounting Expansion I O    ATTENTION  During panel or DIN rail mounting of all  devices  be sure that all debris  metal chips  wire strands  etc   is  kept from falling into the module  Debris that falls into the  module could cause damage on power up     Minimum Spacing                                        Maintain spacing from   Top   enclosure walls    wireways  adjacent 2 e   2   a  equipment  etc  Allow 50 Side Controler 3 3   3 3 RTS  mm  2 in   of space on all S1S 1S 1681 S   sides for adequate   ventilation  as shown    Botiom       Panel Mounting    Mount the module to a panel using two screws per module  Use M4 or  8  panhead screws  Mounting screws are required on eve
13. ry module     Panel Mounting Using the Dimensional Template    For more than 2 modules   number of modules   1  X 35 mm  1 38 in                                    Refer to host controller documentation for this dimension    35 28 5     1 38     1 12   J J T us  P jf   P  132 5 oala g  5 197 El slsls  D S R BEE  ine ok   S    amp          NOTE  All dimensions   4 82640 008                 h   arein mm  inches   Hole  spacing tolerance     4 4  0 4 mm  0 016 in            Publication 1769 5 2    6 Compact    1769 OW8 AC DC Relay Output Module    Panel Mounting Procedure Using Modules as a Template    The following procedure allows you to use the assembled modules as a template  for drilling holes in the panel  If you have sophisticated panel mounting  equipment  you can use the dimensional template provided on page 5  Due to  module mounting hole tolerance  it is important to follow these procedures    On a clean work surface  assemble no more than three modules     2  Using the assembled modules as a template  carefully mark the center of all  module mounting holes on the panel     3  Return the assembled modules to the clean work surface  including any  previously mounted modules     Drill and tap the mounting holes for the recommended M4 or  8 screw   Place the modules back on the panel  and check for proper hole alignment   Attach the modules to the panel using the mounting screws     Note  If mounting more modules  mount only the last one of this group  and put the others
14. the     e Program Mode configuration  if supported by the controller   e The Fault Mode configuration  if supported by the controller   For the 1769 OW8  bits 8 to 15 are not used           3 Bit Position   o     115 141131121110 91871615 413 21 110  0 MO 0 0 0 0 0 0 0 r r r r r r r r                                                    r   read    IMPORTANT  The output module   s input data file reflects the output data  echo of the module  not necessarily the electrical state of the  output terminals  It does not reflect shorted or open outputs     Note  Itis only important to use this input word if the controller supports the  Program Mode or Fault Mode function  and if it is configured to use them     Publication 1769 5 2    Compact    1769 OW8 AC DC Relay Output Module 11    Specifications    General Specifications    Specification    Value    118 mm  height  x 87 mm  depth  x 35 mm  width     Dimensions    height including mounting tabs is 138 mm    4 65 in   height  x 3 43 in  depth  x 1 38 in  width   height including mounting tabs is 5 43 in        Approximate Shipping Weight   with carton     280g  0 61 Ibs         Storage Temperature     40  C to  85  C   40 F to  185 F        Operating Temperature    OC to  60  C  32  F to  140   F                    Operating Humidity 5  to 95  non condensing   Operating Altitude 2000 meters  6561 feet    Vibration Operating  1 to 500 Hz  5g  0 015 in  peak to peak  Relay Operation  2g  Operating  30g panel mounted  20g DIN rail mo
15. unted   Relay Operation  7 5g panel mounted  5g DIN rail   Shock mounted   Non Operating  40g panel mounted  30g DIN rail mounted   e C UL certified  under CSA C22 2 No  142    Agency Certification   UL 508 listed      CE compliant for all applicable directives       Hazardous Environment Class    Class I  Division 2  Hazardous Location  Groups A  B  C  D   UL 1604  C UL under CSA C22 2 No  213        Radiated and Conducted Emissions    EN50081 2 Class A       Electrical  EMC     The module has passed testing at the following levels          ESD Immunity  IEC1000 4 2       AkV contact  8 kV air  4 kV indirect       e Radiated Immunity  IEC1000 4 3       10 V m  80 to 1000 MHz  80  amplitude modulation    900 MHz keyed carrier       e Fast Transient Burst  IEC 1000 4 4     2 KV  5 kHz         Surge Immunity  IEC1000 4 5     2 kV common mode  1 kV differential mode         Conducted Immunity  IEC1000 4 6        10V  0 15 to 80 MHz        1  Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range    is 30 MHz to 1000 MHz     Publication 1769 5 2    12    Compact    1769 OW8 AC DC Relay Output Module             Output Specifications  Specification 1769 OW8  Voltage Category AC DC normally open relay  Operating Voltage Range Suet  5 to 125V de  Number of Outputs 8  Bus Current Draw  max   leet al oy denen   100 mA at 24V dc  2 4W        Heat Dissipation    2 83 Total Watts  The Watts per point  plus the minimum  Watts  with all points 
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
Cypress AN20639 Computer Hardware User Manual  PRO MIXER VMX100  Hitachi SA200 User's Manual  THEA FOR SKETCHUP USER MANUAL  InnoMedia MTA 3328-2R  user manual  Triarch 29583 User's Manual  Specification  Philips SBCVL1200 User's Manual  松山市公営企業局建設工事検査技術基準(H26.4)(PDF:371KB)    Copyright © All rights reserved. 