Home

User Manual(MAI-P) revised

image

Contents

1. will set parameter Ctrl to 3 which will prevent the A M key from triggering auto tune This will preventan accidental repeat of the auto tuning thermostat When the temperature passes the set point the heater or cooler will be turned off When the temperature drops back to below the hysteresis band dF the heater will turn on again To use the On off mode set Ctri 0 Then set the Hy to the desired range based on control precision requirements Smaller dF values result in tighter temperature control but also cause the on off action to occur more frequently PV 103 SV dF 100 SV 97 t SV dF Retay On if the process value is less than SV dHAL dF 1 6 Cycle time t exit from auto tuning mode press and hold the A M key for about 2 seconds until the 1 10 Input offset SC 1 11 Output definition oP 1 1 5 3 Manual mode Manual mode allows the user to control the outputas a percentage of the total heater power Itis like a dial on a stove The outputis independent of the temperature sensor reading One application example is controlling the strength of boiling during beer brewing You can use the manual mode to control the boiling so thatit will not boil over to make a mess The manual mode can be switched from PID mode but not from On off mode This controller offers a bumpless switch from the P ID to manual mode If the controller outputs 75 of power at PID mode the controller w
2. If you didn t use up all the steps for programming you can use one of the unused steps for that For example assuming step 10 and 11 are unused setC 10 100 C 11 10 and t10 9999 This sets Step 10 to control the temperature at 100 degrees for 9999 minutes To begin the program startRun V key press SET once to display StEP use Ato go to StEP 10 Press SET twice The controller will run just like regular controller with PV displayed ontop and SV in the bottom Youdon thave to do this every time the controller powers up assuming the A M parameter has not changed from default lt will remain running StEP 10 until 9999 minutes 7 days runs out or until you reset it for another application 2 Put the program on hold mode This can be done either by manually pressing the Hold button at the desired temperature or by programming a hold step by setting tXX 0 7 3 just want to run the oven at 800 degrees for 120 minutes When I setC01 800 t01 120 the controller SV first displays 800 then it starts dropping with time Did do something wrong This is the most common mistake first time users make Since this is a ramp controller nota step controller the time t01 or tXX is not the time that controller will stay at C01 or CXX itis the ramping time that controller will take from temperature C01 to C02 To hold the temperature constant for 120 minutes you need to set two steps at the same temperature or a 0 degree ramp C02 C03 800 in this case Then set
3. 0X2 0X4 0X8 1X16 17 this is the factory default setting Note Unlike controllers that can be set to only one alarm type allows both alarm types to function simultaneously If you only wantone alarm minimum HIAL dHAL and dLAL to 9999 LoAL to 1999 to stop its function 1 14 System function selection CF Parameter CF is used to set the heating or cooling alarm suppression and power restriction function Its value is determined by the following formula CF AX1 BX2 CX 16 A 0 reverse action control mode for heating control A 1 direct action control mode for cooling control B 0 without alarm suppressing when turned on or when set point changes B 1 alarm suppressing at power up or Set point changes C 0 without power restricted function C 1 with power restricted function The factory setting is A 0 B 0 C 0 heating without alarm suppression without power restricted function Therefore CF 0X1 0X2 0x16 0 1 15 Input digital filter dL If measurement input fluctuates due to noise then a digital filter can be used to smooth the input dL may be configured in the range of 0 to 20 Stronger filtering increases the stability of the readout display but causes more delay in the response to change in temperature dL 0 disables the filter 1 16 Manual and Automatic Mode Selection run Parameter run is for selecting automatic or manual control mode run 0 manual control mode run 1 automatic control mode eit
4. 1 9 Limiting the control range dIL and dIH 1 For temperature sensor input the dIL and dIH values define the set value range dIL is the low limit and dIH is the high limit e g Sometimes you may want to limit the temperature setting range so that the operator can tseta very high temperature by accident If you setthe dIL 100 and dIH 130 operator will only be able to set the temperature between 100 and 130 2 For linear input devices dIL and dIH are used to define the display span e g If the inputis 0 5V dIL is the value to be displayed at OV and dIH is the value at 5V SC is used to setan input offset to compensate the error produced by the sensor or input signal itself For example if the controller displays 5 C when probe is in ice water mixture setting SC 5 will make the controller display 0 C This parameter is not used for this model Itshould not be changed 1 12 Output range limits oPL and oP H oPL and oPH allow you set the output range low and high limit oPL is a useful feature fora system that needs to have a minimum amount of power as long as the controller is powered e g If oP L 20 the controller will maintain a minimum of 20 power output even when input sensor failed oPH can be used when you have an overpowered heater to control a small subject e g If you set the oP H 50 Page 2 5 e g If you setthe oP H 50 the 5000 watt heater will be used as 2500W heater
5. SV 700 oC When the probe temperature PV is above 705 the deviation alarm will be on When the temperature is above 1000 oC the process high alarm will be on Later when SV changes to 600 oC the deviation alarm will be changed to 605 but process high alarm will remain the same Here the Hysteresis Band dF setting is ignored Please see 1 5 2 for details 2 Alarm Suppression feature Sometimes user may not want the low alarm to be turned on when starting the controller at a temperature below the low alarm setting The Alarm Suppression feature will suppress the alarm from turning on when the controller is powered up or SV changes The alarms can only be activated after the PV has reached SV 3 Activate the AL1 and AL2 by time instead of temperature For the controllers with the ramp and soak function AL1 and AL2 can be activated when the process reaches a specific time This is discussed in the section 3 7 of Supplementary Instruction Manual for ramp soak version 1 4 2 Hyste resis Band dF The Hysteresis Band parameter dF is also referred as Dead Band or Differential It permits protection of the on off control from high switching frequency caused by process input fluctuation Hysteresis Band parameter is used for on off control 4 alarm control as wellas the on off control at auto For example 1 When controller is set for on off heating control mode the output will turn off when temperature goes above SV
6. StEP 6 StEP6 C06 100 t06 181 Alarm 1 is switched off unless itis also being triggered by an alarm condition outside the program and the program jumps to StEP 1 to start from the beginning The command for switching Alarm 1 off is 6 so t06 30 6 1 181 StEP 1 C01 100 t01 30 Since the temperature is still at 160 C the program will pause until the controller can bring the temperature within the alarm range of the new set point Since the deviation high alarm is setto 5 C the program will resume from the beginning as soon as the temperature drops below SV dHAL dF 105 C The temperature control block is shown below Alarm on 0 Temp c Alarm off Alarm off Alarm 1 2 Constant temp 400 3 Cool down 6 ump section Bring up alarm 1 off es 5 Hold ras 4 ump section 7 100 alarm 1 on Ready section Vx Circle from no timing selection 30 90 210 i i Figure 2 Ramp Soak Example 2 Time M in 5 Quick list of the New Key Functions for the Ramp S oak Model The following list contains a brief description of each key function for when the controller is in basic operation mode 1 Mode Key SET When pressed momentarily PV display shows the current step that the program is processing When pressed again the PV display shows the settime length of the current step The SV display shows how long the currentstep has run in minutes Press again to have the display return to the basic display mode The PV shows the process temperature and S
7. address bAud Communication baud dL PV _ input filter run System runing status m Loc Configuration priviledge EP1i EP8 Field parameters definition nonE A M nonE Page 1 5 1 4 1 Alarm This HIAL High turn o parameters controller offers four types of alarm HIAL LoAL AHAL ALAL imit absolute alarm If the process value is greater than the value specified as HIAL dF dF is the Hysteresis Band then the alarm will turn on It will when the process value is less than HIAL dF LoAL Low limit absolute alarm If the process value is less than the value specified as LoAL dF then the alarm will turn on and the alarm will turn off if the process value dHAL Deviation high alarm If the temperature is above SV dHAL dF the alarm will turn on and the alarm will turn o we will discuss the role of dF in the later section is greater than LoAL dF dLAL Deviation low alarm If the temperature is below SV dLAL dF the alarm will turn on and the alarm will turn off if the temperature is greater than SV dLAL dF The things you should know about alarm 1 Ab High solute alarm and deviation alarm or low limit absolute alarm is set by the specific temperatures that the alarm will be on Deviation high or low alarm is set by how many degrees above or below the control target temperature SV that the alarm will be on e g Assuming HIAL 1000 oC d HAL 5 oC
8. and AL2 A 4 Stop the instrument B must be set tol when A 4 A 5 switch off AL2 A 6 switch off AL2 A 7 switch off AL1 and AL2 Examples Jump from StEP4to StEP5 and switch on AL2 Time setup is t04 1x30 5 35 Jump from StEP6 to StEPland switch off AL2 Time setup is t06 5x30 1 151 Stop program atStEP8 Time setup is t08 4x30 1 121 The controller does not let a jump command jump to itself for example t06 6 because the Hold status would never be released 3 8 Displaying and modifying the running StEP number StEP of the program Sometimes it is convenient to jump directly to a particular StEP and execute from there 4th StEP and Ramp series controller can start the program from any one of its B steps Press the SET key briefly to display the StEP number Press the A V keys to change it The StEP number increases or decreases automatically as the program executes If the StEP number is manually changed the running time will be cleared to Oand the program will begin with the new StEP If the StEP number is not changed pressing the SET key will not affect the operation of the program 3 9 Multiple Curves The flexible programming format of the Ramp amp Soak controller can be used to store and recall multiple programmed curves If a temperature curve doesn t require all 50 steps the unused steps can be used to store another program Several different curves can be stored and executed individually as long as there are n
9. dF and on again tuning when it drops to below SV dF 2 Ifthe high alarm is set at 800 C and hysteresis is setfor2 C the high alarm will be on at 802 C ALM1 dF and off at 798 F ALM1 dF Please note that the cycle time can also affect the action If the temperature passes the dF setpoint right after the start of a cycle the controller will not respond to the dF set point until the next cycle If cycle time is setto 20 seconds the action can be delay as long as 20 seconds Users can reduce the cycle time to avoid the delay 1 4 3 Control mode Ctrl On off control It works like a mechanical thermostat It is suitable for devices that do not like to be switched at high frequency such as motor and Ctrl 0 valves Ctrl 1 Ctrl 2 Ctrl 3 This configuration is automatically set after auto tuning is done Auto tuning from the front panel is inhibited to prevent accidental re starting of th Gets the controller ready to start the Auto tuning process by pressing the A M key Start auto tuning The function is the same as starting auto tuning from front panel auto tuning process To start auto tuning again set Ctrl 1 or Ctrl 2 1 5 Control 1 5 1 PID action explanations Please note that because this controller uses fuzzy logic enhanced PID control software the definition of the control constants P and d are different than that of the traditional proportional integral and derivative parameters well wi
10. preparation B 2 with the function of PV preparation and without the function of Safety Start B 3 with the function of Safety Start and PV preparation About Safety Start and PV Preparation Safety Start Function Atthe first step of program when the ambient temperature is differ from the C01 Set point of first step the controller will automatically adjust the running time to make the expected set point the same as the current PV Forexample in a system where the program configured from 25C to 625C within 600 minutes at the firststep but after the power on in the system the process value is already at 100C which is higher than the original setpoint 25C for first step in this case the controller will automatically adjust the running time to 75 minutes and run the program Please noted that Safety Start function only applicable for 1ststep of a program PV Preparation Function In a system where the ambient temperature is differ from the Set point of executed steps the controller will adjust the PV to SV and maintain the integrity of the program Forexample in a heating step from 100C to 600C the system suffers power off when temperature at 125C and when power comes back the PV of the system is actually at105C the controller will automatically adjust the process value to 125C where the power failed point and without increase the running time of the system after process value reaches 125C the program goes onas planned before 3 11 Privilege for param
11. the ramping time for 120 minutes Please see example 1 Page 5 5
12. 50 even when the PID wants to send 100 output 1 13 Alarm output definition ALP Parameter ALP may be configured in the range of 0 to 31 It is used to define which alarms HIAL LoAL dHAL and dLAL is output to AL1 or L2 Its function is determined by the following formula LP AX1 BX2 C X4 DX8 E X16 A 0 then AL2 is activated when Process high alarm occurs IfA 1 then AL1 is activated when Process high alarm occurs B 0 then AL2 is activated when Process low alarm occurs IfB 1 thenAL1 is activated when Process low alarm occurs C 0 then AL2 is activated when Deviation high alarm occurs If C 1 then AL1 is activated when Deviation high alarm occurs D 0 then AL2 is activated when Deviation low alarm occurs IfD 1 then AL1 is activated when Deviation low alarm occurs E 0 then alarm types such as HIAL and LoAL will be displayed alternatively in the lower display window when the alarms are on his makes it easier to determine which alarms are on If E 1 the alarm will not be displayed in the lower display window except for orAL enerally this setting is used when the alarm output is used for control purposes For example in order to activate AL1 when a Process hig arm occurs trigger AL2 by a Process low alarm Deviation high alarm or Deviation low alarm and not show the alarm type in the lower display indow setA 1 B 0 C 0 D 0 and E 1 Parameter ALP should be configured to ALP 1X1
13. T and hold for roughly 2 seconds until the parameter setup menu is displayed display mode 5 Please refer to figure 3 setup flowchart 1 3 Setup flow chart nS Ins eT 2S Derivative time HI AL HIAL SET g g g 9 Process high alarm P gt Ke Proportional Band LoAL GD 4 g g g Process low alarm l Integral time dHAL Jana CD 9999 De ito High alarm Cel c tl Cycle time Sn Input type diH Display high limit Sc Input offset oPl Output mode oPL Output low limit oPH Output high limit run Ic Alarm output definition EFI 8868 Ctrl Jom GET Field parameter definition Control mode cF System function selection ED 8888 2588 1 4 Parameter Setting Figure 3 system parameter setup flow chart Table 1 System Parameters Code Description Setting Range Initial setting Remarks HIAL Process high alarm 1999 9999 C 9999 LoAL Process low alarm 1999 9999 C 1999 dHAL on 9999 C dLAL Deviation low alarm og 9999 C N 0 200 0 C OF Hysteresis Band or 0 2000 for linear input Ctrl Control mode 0 4 M5 Derivative time og 999 9 C P t Intergral time j 5 for SSR Cti cycle time 20 for relay Sn Input type dIP Decimal point position diL dIH Display high limit 1999 9999 C Sc Input offset 1 990 400 0 C oP1 Output mode 0 4 oPL Output low limit 0 110 oPH Output high limit 0 110 ALP CF System funtion selection Addr Communication
14. This controller is intended Advanced Temperature Controller Ramp and Soak Temperature Controller User Manual to control equipment under normal operating conditions If failure or malfunction of the controller may lead to abnormal operating conditions that may result in personal injury or damage to the equipment or other property devices limit or safety controls or systems alarm or supervisory intended to warn of or protect against failure or malfunction of the controller must be incorporated into and maintained as part of the control system 1 Front panel AUX OUT1 OUT2 ALM1 ALM and operation 1 PV display Indicates the sensor readout or process value P V 2 SV display Indicates the set value SV or output value 3 0UT1 Output indicator Itis synchronized with control output and the power to the load When itis on the heater or cooler is powered 4 0UT2 Output 2 is not applicable for this instrument 5 ALM2 Itlights up when AL2 relay is on 2 6 AUX Auxiliary output indicator when auxiliary function incorporated and activated the indicator lights up aunsmoto 7 AL1 It lights up when AL1 relay is on 9 10 Figure 1 Front Panel 8 SET key When itis pressed momentarily the controller will switch the lower SV display between set value and percentag of output Whenpressed and held for two seconds will put the controller into parameter setting mode 9 A M Auto manual control fun
15. V caneithershow the set temperature or the status of the controller Stopped Running oron Hold Pressing and holding the mode key for two seconds will put the controller into parameter setting mode just like the controllers without the ramp soak option 2 Auto Manual function key A M Press this key to have the controller enter step setting mode in order to setthe time temperature and action of each step 3 Decrement key V Press and hold this key for two seconds to start the processing Press and hold again to hold the processing 4 Increment key Press and hold this key for two seconds to stop the processing of the program Table 2 Summary of New Key Functions Check run time of currentstep Press SET briefly twice Press SET briefly Then use V or A Go to Step X to go to step Press A M key to enter programming mode Then SET key to go to next step To program the steps 7 Frequently asked questions 7 1What is the difference between Hold and Stop Hold does not stop heating It holds the temperature at the current setting or atoPL see 3 10 for details Stop will stop heating If you Hold the program V key and start Run V key again it will start from the step that was put into hold However if you Stop the program A key and start Run V key again it will start from step1 7 2 How do I run this controller as a regular controller without the ramp soak function Here are two methods 1 P rogram a very long step
16. ading to drift more than 5 C 8 4 On on off mode Although hysteresis is set to 0 3 the unitis running 5 degrees above and below If the dF is very small and temperature changes very quickly users will need to consider the delay of the cycle time the parameter t For example if cycle time is 20 seconds when the temperature passes the SV dF after the beginning of a 20 seconds cycle the relay will not act until the start of the next cycle 20 seconds later Users may change the cycle time toa smaller value such as 2 seconds to get better precision control Supplementary Instruction Manual For the Ramp Soak option of Programmable Controller Version 6 58 This is a supplementary manual for the Ramp S oak controller Itis only for operating the programmable steps ramp and soak steps functions The main manual forthe Ramp S oak is the same as the advanced temperature controller It covers all the regular set up and operation instructions The Ramp and Soak series programmable controllers with the ramp soak option are designed for applications where it is desirable to have the set point automatically adjust itself over time 1 Features 50 steps of program control for ramping and soaking process High flexibility in program and operation Ithas programmable maneuverable commands such as jump for loops run hold and stop The program can even be modified while itis running The program can also control the two relays that are used for alarms This featu
17. ction key data shift key 10 Decrement key Run or STOP the program 11 Increment key S top the program key 1 1 Display Status Power on Display mode 2 Display mode T pa an gge A Pec Ef e D i 100 sv i gt 460 means output M 60 means output ace R value 60 on automatic value 60 on manual mode mode SET CAM 2 Bresette gna nnnanned ss e lame DE Co 2s Display mode 4 Display mode 3 Next parameter i i peer Ef i Dea nous ee eee HAL GD Display mode 1 When Display mode 2 Press Next parameter 3939 Figure 2 Display modes he power is turned on the upper display window shows the measured value PV and the lower window shows the set value S V he setkey to change the display status into mode 2 the upper display window shows the process value PV and the lower dis play window shows the output value this picture shows the output percentage is 60 when in automatic P ID control mode P ressing the lt A M key will switch the controller between manual and au Display mode 3 Press shows the StEP beinge Display mode 4 Press lower display shows the Display mode 5 Press Display mode 6 Press 1 2 Basic Operati 1 2 1 Changing SetVa between PID and manual contro mode with the output unchanged This bumpless transfer allows the controller to be switched omatic mode without the output suddenly bumping to a different value he setkey under display mode 2 to change t
18. e again and the current StEP s ramping time will be displayed tin the upper display In each program StEP the temperature and the time is displayed in turn Hold down the A M key and press V to go back to the previous parameter Hold A M and press SET to exit program setup mode Modifying program steps while a program is running is permitted See section 4 for a programming example Note the above operation is inhibited if the program setup function is locked of the LocK parameter 3 2 Program Ramp To program a ramp you need to set the start temperature CXX the end temperature CXX 1 and the time duration tXX For example at step 3 if you want the controller to take 60 minutes to ramp up from 200 to 300 degrees set C03 200 C04 300 t03 60 Note Unless the deviation alarms are set to a narrow range the ramping time decides when the program is going to the next step Once the ramping time is finished the current step the controller will execute the next step regardless if the temperature reaches the target temperature Therefore the ramp speed should be always lower than the maximum speed that the oven can offer at the full power In other words the ramping time should be longer than the minimum time needed for oven to jump from C03 to C04 at full power If the ramping time is shorter than that the time programmed for the next step will not be fulfilled When program a temperature ramps down you need to consider the speed of natural coolin
19. ect one of 4 power outage startup event handing modes and B is used to select Safety Start and PV preparation function Power Outage Startup Modes A 0 When the instrumentis turned on the program will simultaneously jump to 29th program segment and clear event output status This mode is suitable for applications in which power failure is not allowed at any time The user may do error handling in segment 29 such as switching on the event output to trigger an alarm A 1 If there is no deviation alarm at power up the program will continue running from the original break point and the event output state remains Otherwise the program will jump to the 29th segment and clear event output status A 2 After power is turned on it will continue the program from the original break point and the event output state will remain This mode is suitable for the applications in which power failure does not affect production default setting A 3 After power is turned on controller goes to Stop status A 4 After power is turned on controller goes to Hold status the controllers will goes to Stop status if the controller at Stop mode before power failure Safety Start and PV Preparation functions B 0 withoutSafety Start and PV preparation function Program is executed as planned This mode guarantees constant running time of the program but it can t guarantee the integrity of the whole curve B 1 with the function of Safety Start and without the function PV
20. eter set LocK For ramp amp soak controllers with ramp soak option the LocK has slightly different functions The table 1 shows the privilege of each lock code Table 1 LocK parameter EP 1 8 Adjustment Program Adjustment Step selection when running 4 Programming Example Programs in the Ramp amp Soak controller have a uniform format of temperature time temperature The temperature set point of the current step will linearly change to the set point of the next step over the time interval of the two steps The first temperature set point should always be the ambient temperature at which the process starts to ramp up DO NOT set the first temperature set point to the target temperature see example 1 below if you are not using the safety start function The time units are in minutes Negative values of the time interval represent program commands The following example holds the oven at 800 C for 2 hours In this example itis assumed that the heater is able to heat the oven from 25 C to 800 C within 30 minutes If the heater does not have this ability the soak section can begin when the oven is below 800 C after the 30 minutes ramping time is up Please note that the value of C is the beginning temperature of the step e g C01 is always the temperature at the beginning of the step 1 Usually C01 should be the ambient temperature and t01 is the time from step1 to step2 StEP 1 C01 25 t01 30 Start linear temperature heatin
21. g or forced air cooling for the same reason If the maximum speed of the system is unknown or varies with environmental conditions users should use the safety start function to ensure that the temperature and time during ramping and soaking are kept within a reasonable range required by the process This is done by setting the deviation alarm close to the SV At the beginning of a step the timer will not start until PV is larger than SV dLAL dF and smaller than SV dHAL dF e g Set dHAL 30 dLAL 20 dF 5 and SV 100 At the beginning of the step if the temperature is below 85 SV dLAL dF 85 degrees or above 125 SV dHAL dF 125 degrees the controller will stop the timer to wait until the temperature is above than 85 degrees or below than 125 degrees be 3 3 Program Soak The soak can be considered as a special case of ramping Itis a ramp with a zero degree slope To program a soak you need to set the start and the end temperature to be the same CXX CXX 1 e g Atstep 3 if you want the controller to soak the parts at 200 degrees for 60 minutes set CO3 C04 300 t03 60 Note The StEP time is not how long the controller will stay at the set temperature for the current step It is how long the controller will take from the current step temperature set point to the next step temperature set point These two concepts are very different 3 4 Program Hold When the program reaches a StEP where the StEP time is set to zero or when a ju
22. g up from 25 C to 800 C overa time period of 30 minutes 25 8 C minute StEP2 C02 800 t02 120 Maintain 800 C for 120 minutes StEP 3 C03 800 t03 121 Stop the program and let the oven cool down The equation used to get the command number is 30 Command Next Step 30 441 121 The temperature control block is shown below Page 4 5 Temp c 800 2 C onstant Temp 3 Natural Cooling 25 30 150 Time Min Figure 1 Holding oven at 800 c for 2 hours 4 2 Example 2 The following example includes 6 steps linear temperature heating maintaining a constant temperature linear temperature cooling jump cycling ready hold and event output In the following example it is assumed that the deviation high alarm dHAL dLAL 5 C and dF 0 StEP1 C01 100 t01 30 Start linear temperature heating up from 100 C to 400 C overa time period of 30 minutes 10 C minute StEP2 C02 400 t02 60 Maintain 400 C for 60 minutes StEP3 C03 400 t03 120 Reduce the temperature ata rate of C04 C03 t03 2 C minute for 120 minutes This will bring it down to 160 C StEP4 C04 160 t04 65 Alarm 1 is triggered and the program jumps to StEP5 The command number for turning alarm 1 on is 2 The equation used to get the command number is 30 Command Next Step 30 2 5 65 StEP5 C05 160 t05 0A time value of zero puts the program in a Hold state A run operation executed by the useris needed for the program to continue to
23. give the operator limited privileges to change som of the parameters that can be viewed Table 5 shows the privileges associated with each lock code SO v T o O oa SUS Oooo yes to tke S ee ee ee aes Quick Guide for Advanced Temperature Controller 1 Wirin 1 panies the controller Connect the 90 260VAC power to terminals 1 and 2 2 Control output connection Connectterminals 3 and5 forSSR Drive output 3 for negative and 5 for positive 3 Sensor connection For thermocouples connect the positive wire to terminal 10 the negative to terminal 11 Fora three wire RTD with standard DIN color code connect the two red wires to terminals 10 and 11 and connect the white wire to terminal 9 Fora two wire RTD connect the wires to terminals 10 and 11 Then jump a wire between terminals 9 and 10 2 Setsensor type SetSn to 0 fora K type thermocouple default 5 fora type thermocouple and 21 fora Pt100 RTD 3 Switching between automatic and manual mode Set run 0 to active manual mode Press the A M key to switch between automatic and manual mode either absolute or deviation butnot both at same time this controller 8 Error Message and trouble shooting 4 Setting the controller for cooling control For cooling control set CF 1 the initial setting is CF 0 for heating control 5 Setting target temperature 6V Press the W ora key once and then release it The decimal point on the lower right corner will start to flash Press the Wor Akey t
24. he display into mode 3 which the upper display shows StEP and lower display xecuted he set key under display mode 3 to change the display into mode 4 the upper display shows the StEP time being executed the time thatthe current StEP has been running he setkey under display mode 1 for2 seconds to enter the display mode 5 where user can configure various system parameters he lt A M key under display mode 1 to enter the display mode 6 where users can configure a desired ramp soak program on ue Press the Wor A key once and then release it The decimal point on the lower right corner will start to flash Press the W or A key to change SV until the desired value is displayed If the change of SV is large press the A M keyto move the flashing decimal point to the desired digit that needs to be changed Then press the W or A key to start changing SV from that digit The decimal point will stop flashing after no key is pressed for 3seconds The changed SV willbe automatically registered without pressing the SET key 1 2 2 Display change Press the SET key to change the display mode The display can be changed between display modes 1 and 2 1 2 3 Manual Automatic mode switch Bumpless switching between PID mode and Manual mode can be performed by pressing the A M key In Manual mode the output amplitude can be increased ordecreased by pressing A and W display mode 2 1 2 4ParameterSetup Mode When the display mode is 1 press SE
25. her PID or On off control run 2 automatic control mode in this state manual operation is prohibited This parameter functions differently for controllers with the ramp soak function see supplemental manual for details Zs ouse eE ype to function setthe other alarm type parameters to maximum or 1 17 Lock up the settings field parameter EP and parameter LocK To prevent the operator from changing the settings by accident you can lock the parameter settings after initial setup You can select which parameter can be viewed or changed by assigning one of the field parameters to it Up to 8 parameters can be assigned into field parameter EP1 EP8 The field parameter can be setto any parameter listed in Table 2 except parameter EP itself When LocK is setto 0 1 2 and soon only parameters or setting values of program defined in an EP can be displayed This function can speed up parameter modification and prevent critical parameters like input output parameters from being modified If the number of field parameters is less than 8 then define the first unused parameter as none Forexample ifonlyALM1 and ALM2 need to be modified by field operators the parameter EP can be setas following LocK 0 EP1 HIAL EP2 LoAL EP 3 nonE In this case the controller will ignore the field parameters from EP 4 to EP8 If field parameters are not needed after the instrumentis initially adjusted simply setEP 1 to nonE Lock code 0 1 and 2 will
26. ill stay at 75 when itis switched to the manual mode until itis adjusted manually See Figure 2 for how to switch the display mode It is the time period in seconds that the controller uses to calculate its output e g When t 2 if the controller decides output should be 10 the heater will be on 0 2 second and off 1 8 seconds for every 2 seconds Smaller t values result in more precision control For SSR output itis setat 5 seconds or you can change to 2S For relay or contractor output it should be set longer to prevent contacts from wearing out too soon Normally itis set to 20 40 seconds Table 2 Code for Sn and its range 0 20mV 0 100 mV 0 60 mV 0 2 1V 4 20mA w 50Q Resistor 1999 9999 Defi ned by user wth diL and dl H 14V 4 20mA w 2500 Resistor E OOO O ooo Sa ae Pp o 5 o e Pp o7 O ee 380 O o a ae p85 o e 1 3 5 7 20 1 6 7 8 9 30 31 32 33 34 35 36 37 1 7 Decimal pointsetting dIP 1 In case of thermocouple or RTD input dP is used to define temperature display resolution dP 0 temperature display resolution is 1 oC dP 1 temperature display resolution is 0 1 oC The temperature will be displayed at the resolution of 0 1 oC for input below 1000 oC and 1 oC forinput over 1000 oC 2 For linear input devices voltage current or resistance input Sn 26 37 Table 3 dP parameter setting aP vale oT 2 3 Display format 0000 000 0 00 00 0 000
27. k the input setting first because most controllers are shipped with the input set for thermocouples Then check the wiring The two red wires should be connected to terminals 10 and 11 The clear wire should be connected to terminal 9 8 2 No heating When the controller output is set for relay output the O U T LED is synchronized with output relay If heat is not output when it is supposed to check the OUT LED first If itis not lit the controller parameter settings are wrong If itis on check the external switching device if the relay is pulled in or the SSR s red LED is on If the external switching device is on then the problem is either the external switching device output its wiring or the heater If the external switching device is not on then the problem is either the controller output or the external switch device 8 3 PoorAccuracy Please make sure calibration is done by immersing the probe in liquid Comparing the reference in airis not recommended because response time of the sensor depends on its mass Some of our sensors have response time gt 10 minutes in the air When the error is larger than 5C the most common problem is an improper connection between the thermocouple and the controller The thermocouple needs to be connected directly to the controller unless a thermocouple connector and extension wire is used Copper wire ora thermocouple extension wire with the wrong polarity connected on the thermocouple will cause the re
28. mping StEP transitions to another jumping StEP the program will be set to hold status You can also manually activate hold status by pressing the V key for about 2 seconds until HoLd appears in the lower display window 3 5 Program Stop When the program reaches a StEP where the StEP time is set to 121 the controller will stop running The StEP number is reset tol the event output is cleared and the control output is turned off Youcanalso manually execute the stop operation by pressing and holding the key for roughly 2 seconds until the lower display window displays StoP 3 6 Run Program In order to continue the program when the controller is in hold mode or restart it from stop mode lower window displays run When a program is running 3 7 StEP Time Command Parameter When tXX is between 1 and 9999 min itis used to set the ramp and soak time When itis set to zero or a negative number itis used for executing other commands tXX 0 The instrumentis putin hold mode on StEP number XX until manually released by the operator tXX 1 to 240 represents an operation command such as run hold stop jump and event output The number is calculated according to the equation tXX A 30 B B is the number ranging from 1 to 30 of the next step for the program to jump to and A is the event that is triggered A 0 no effect for jump function only A 1 switch on AL2 A 2 switch on AL1 A 3 switch on AL1
29. o change SV until the desired value is displayed The decimal point will stop flashing after no key is pressed for 3seconds You can press the A M key to move the flashing decimal point to the desired digit that needs to change Then press the Wora key to change SV starting from that digit 6 Auto tune You can use the auto tune function to determine the PID constants automatically There are two ways to start auto tuning 1 Set Ctrl 2 It will start automatically after 10 seconds 2 Set Ctrl 1 Then during the normal operation press the A M key to start the auto tune The instrument will perform accurate artificial intelligence control after auto tuning is finished On off mode Set Ctrl 0 to active the on off contro mode Setthe Hysteresis Band parameter dF to be a desired value 8 1 Display orAL This is an input error message The possible reasons are the sensor is not connected correctly the input setting is wrong type or the sensor is defective In this case the instrument terminates its control function automatically and the output value is fixed according to the parameter oP L If this happens when using thermocouple sensor you can short terminal 10 and 11 with a copper wire If the display shows ambient temperature the thermocouple is defective If it still displays orAL check the input setting Sn to make sure itis set to the right thermocouple type If the Sn setting is correct the controller is defective For RTD sensors chec
30. ot more than 50 steps total including necessary controls steps Forexample when a process curve only needs nine program If the program is still in the middle of the ore continuing Please note that the dF value should be smaller than both dHAL and dLAL Otherwise the controller will not start the next steps and you wish to finish it in advance and execute the 5th StEP the StEP modification feature will meet your need The Ramp 4 1 Example 1 steps itis possibleto store three such process curves in the instrument Simply change the StEP number to initiate a different curve Suppose 8 steps represent three groups of process parameters They are separately arranged on StEP2 StEP9 StEP10 StEP17 StEP18 StEP 25 The step time of step 1 can be setas follows to choose the desired program T01 2 Execute the program of curve 1 StEP2 StEP 9 T01 10 Execute the program of curve 2 StEP10 StE P17 T01 18 Execute the program of curve 3 StE P 18 StE P25 You can also choose the curves by manually setting the value of StEP before the program starts For example if curve 2 is needed in the current process refer to 3 11 for the introduction then setthe value of StEP to 10 3 10 Control Mode Parameter run The function of the run parameter is defined differently in the ramp and Soak controller than it is for the controller without the ramp soak option Its Operation is determined according to the equation run AX14BX8 Where A is used to sel
31. re can be used to notify the operator of the stage of the operation or to signal other equipment The safety start and ready function may allows the program to run more efficiently 6 power off power on event handling see 3 10 modes can be selected This can prevent the program control from being adversely affected by unexpected power interruptions 2 Terms and Functions Program StEP The value of the program StEP can range from 1 to 50 The current StEP is the program StEP being executed StEP temperature CXX The StEP temperature is the set temperature at the beginning of the step XX where XX can be any value from 01 to 50 StEP time tXX The StEP time is the ramping time from the current step temperature to the next step temperature The unit is in minutes and the available value range is from 1 to 9999 Running time The running time is the time that the current StEP has been running When the running time reaches the StEP time the program will jump to the next StEP automatically J ump The program can jump to any other steps in the range of 1 to 30 automatically as you programmed in the program StEP It can also be used to perform cycle control If StEP number is modified the program will also jump Furthermore if the program StEP reaches and finishes the 50th StEP the program will jump back to the first StEP and run automatically Run When the program is in the running status the timer counts down and the set point value change
32. s according to the preset ramp curve Hold When the program is in the hold status the temperature is still controlled but the timer is paused so the current set point remains Stop When the stop operation is activated the program timer and output control will stop and the running time and event output switch will reset If the run operation is activated while the instrumentis in the stop status the program will start up and run from the StEP 1 Power interrupt It means the power has turned off or an unexpected power failure has occurred during running status 6 handling modes are available to the user Event output E vent output can be programmed in to the controller It can trigger two alarm relays to make external equipment operate with interlock Safety start If the difference between the PV and SV is larger than the deviation alarm setting at the beginning of a step or when powered up the controller will adjust the PV until the alarm is turned off before the timer starts See 3 10 for example Page 3 5 3 Programming 3 1 Program Setup Press the A M key to bring the instrumentinto the program setup mode the instrument will display the temperature set point of the current StE P indicated by C in the upper display followed by the StEP number Use the A M key to choose which digit to edit indicated by the flashing decimal point After adjusting the temperature set point 1999 to 9999 press the SET key onc
33. thout changing the initial PID parameters If not users may need to use auto tune function to let the controller determine the parameters automatically s are not satisfactory you can manually fine tune the PID constants for improved performance Or you can try to modify the initial PID Ifthe auto tuning resul values and n most cases the fuzzy logic enhanced PID control is very adaptive and may work perform auto tune again Sometimes the controller will get the better parameters The auto tune can be started in two ways 1 Set Ctrl 2 It will start automatically after 10 seconds 2 Set Ctrl 1 Then you can start the auto tune any time during the normal operation by pressing the A M key During auto tuning _ the instrument executes on off control After 2 3 times on off action the microprocessor in the instrument will analyze the period amplitude waveform of the oscillation generated by the on off control and calculate the optimal control parameter value The instrument begins to perform accurate artificial intelligence control after auto tuning is finished If you want to blinking of At symbol is stopped in the lower display window Generally you will only need perform auto tuning once After the auto tuning is finished The instrument process 1 5 2 On off control mode Itis necessary for inductive loads such as motors compressors or solenoid valves that do notlike to take pulsed power It works like a mechanica

Download Pdf Manuals

image

Related Search

Related Contents

SiteLink Web Mobile Edition Overview of Features  Haier DW12-CBE7 User's Manual  KT(LW)13625 - Texas International Oilfield Tools LTD  Transferir  Manual del usuario  Manual de instrucciones  

Copyright © All rights reserved.
Failed to retrieve file