Technical Reference Note UFE / UFR Series Product Description

image

Contents

1. 5 can ENABLE all Active LOW UFE Units contained within the rack when it is connected to Pin 4 Gnd If Emerson UFR6000 Rack is supplied then the Global PS En signal at J16 Pin 5 can DISABLE all Active HIGH UFE Units contained within the rack when it is connected to Pin 4 Gnd Rack Signal Connector Pinout Function Pin No Function 1 48V Sense 14 48V Ishare 2 Ground 15 Unit 1 Present 3 48V Sense 16 Ground 4 Ground 7 Unit 2 Present 5 PS EN Control 18 Ground 6 DC1 OKO L 19 Unit 3 Present 7 DC2 OK L 20 Ground 8 DC3 OK L 21 sel 9 I2C En H 1 Comm En H 22 Ground 10 12C En H 2 Comm En H 23 SDA 11 12C En H 3 Comm En H 24 Ground 12 Ground 25 SMBALERT 13 12V Aux 26 N C Link to ENABLE Active LOW UFE Units Link to DISABLE Active HIGH UFE Units A Embedded Power for Business Critical Continuity Rev 02 26 10 UFE UFR Series To 14 1 Installation continued B Hardware Connections continued 2 UFE Unit Addressing in Multi Rack systems a If the system contains more than 1 x URF6000 Rack then paralleling of Pin 21 Pin 22 Pin 23 at appropriate J16 connectors of each additional UFR6000 Rack to a single USB Dongle will be required b If there are more than 1 x UFR6000 Shelf then select dip switch according to table below for appropriate UFE Unit address recognition UFRBOOO 0 ON Down Rack Dio Switch 1 OFF UP SW MICRO Pal Siibus ADDRESS EEROM PC A
2. BASIC Screen press the Test Tab Add ON_OFF_CONFIG command 02 amp STORE_USER_ALL Command 15 to the Sequence Lists Select amp press Edit On Dialog box Check Address Command amp change Transaction to Write amp enter 13 in Hex window Press OK button 6 Press Single button for the new command to take affect 7 Send STORE_USER_ALL command 15 for the new instruction to be registered in default memory 3 4 5 N Na SNS Note a The UFE unit may turn off since its factory setting was Active Low On The global PS Enable on UFR6000 rack J16 pin 5 to 4 will need to be opened to allow the new Active High version to start b The Active HIGH instruction is only stored it the units present memory Thus if the mains is recycled the unit will revert to Active LOW One needs to activate the STORE_USER_ALL Command 15 to ensure that the Active HIGH instruction is stored in the Units default Memory a ea nee cewa se tet fitoenia lateant Vaio ar 3 TEH wi ii Eine wae Lt rada tae ca E ginp Clear Export te Fae Rev 02 26 10 UFE UFR Series 14 of 14 Americas 5810 Van Allen Way Carlsbad CA 92008 USA Telephone 1 760 930 4600 Facsimile 1 760 930 0698 Europe UK Waterfront Business Park Merry Hill Dudley West Midlands DY5 1LX United Kingdom Telephone 44 0 1384 842 211 Facsimile 44 0 1384 843 355 Asia HK 14 F Lu P
3. Warning Limit 13 0002 v LV Faut Limit POC A Warning Limit 112 00 gt A 3 Output Vonage comror 12 000 v jii Fault Response co Fault Limit 0 00 gt w LV Fault Response s Warning Limit 09 Ww Taw 0 000 sly Under Voltage Warning Limit 11 000 v EN Faut Response Faut Limit 10 200 Sv Faure umn p0 a Faut Response 0 Fault Response l Ose After making appropriate adjustments then press write command tab to send new values to presently addressed UFE Unit Refer to Universal PMBus GUI User manual for further details Rev 02 26 10 UFE UFR Series 10 of 14 1 Installation continued C Software Notes 2 Programming b Basic Programming The easiest way to vary Basic UFE variables is by clicking the appropriate Config tab on the BASIC Panel 2 Output Configuration continued Notes a To communicate to a different UFE via the GUI one needs to select a different appropriate UFE address by clicking on the address drop down button on the Basic Panel see attached screen Successi Address FA requency 100KHz Poling Deisy 10msec PEC Disabled USB Tol2C Ver 16 click to select new address b Changing the Output Voltage of UFE Units from Standard Factory settings may cause Current Unbalance between Paralleled Modules unless all modules are set to the same output Volage setting at time of paralleling Changing the output voltage of a UFE Unit via the Output Config Screen Vout co
4. continued B Hardware Connections continued Pinout Assignments a UFR6000 Rack Mating Connector from I2C Dongle to URF6000 J16 is Molex 52316 2619 or Tyco 2 5175677 4 UFR Rack signal connector J16 _ a oa iat sd rae iL MP OOOMOODO wW HREBBEL Photo 1 UFR6000 mating 3 connections Photo 2 Back view of UFR6000 with J16 for I2C lines mating Note Sometimes a cable maybe supplied with the Dongle 73 769 001 which is for use with different Power Units ref iMP iVS This cable maybe used for connection to the UFR6000 J16 connection using the following color code references Red Sclock pin 21 Black SData pin 23 White Gnd pin 22 A Embedded Power for Business Critical Continuity Rev 02 26 10 UFE UFR Series 4 of 14 1 Installation continued B Hardware Connections continued Pinout Assignments b Dongle I2C 73 769 001 Mating Connector for UFR6000 cable to Dongle is Landwin 2050 Series with 2 0 mm Pitch Fin Signal Name Description i Wer OS SV sappy fom PC TC serial daca sigma DC som TC serial clock ial Programming positive supply for logic and IO pins Programming volaze api Standard USE Pin out and Cable Color Code Wire Color Functon Rev 02 26 10 UFE UFR Series 5 of 14 1 Installation continued B Hardware Connections continued Notes on Hardware Set Up 1 Remote ON OFF Control PS Enable a Check Unit Model Number to determin
5. DDRESS A Table 3 UFE Numbering Reference EEPROM ie optional Shelf DIP Switch Table Shelf Number DIP Switch DIP Switch 1 Up Up 2 Up Down 3 Down Up 4 Down Down The UFE PSU addresses from Left to Right are F8 Left FA Middle or FC Right for the 1st UFR6000 Rack in single or multi rack system The UFE PSU addresses from Left to Right are FO Left F2 Middle or F4 Right for the 2nd Rack is a 2 or multi rack system The UFE PSU addresses from Left to Right are EB Left EA Middle or EC Right for the 3rd Rack is a 3 or multi rack system The UFE PSU addresses from Left to Right are EO Left E2 Middle orE4 Right for the 4th Rack is a 4 rack system Rev 02 26 10 UFE UFR Series 8 of 14 1 Installation continued C Software Notes 1 Installation a The Emerson Universal PMBus GUI requires a Software Framework Platform in order to operate The preferred Framework is Microsoft NET Framework 3 5 If not yet installed on your PC download and install Net 3 5 at http www microsoft com downloads details aspx FamilyID 333325fd ae52 4e35 b531 508d977d32a6 amp DisplayLang en b Create a Universal PMBus folder amp extract contents of UniversalPMBusGUI_v00 09 00Beta_w o_ NET3 5installer zip to it Universal PMBus GUI can be downloaded at this link http www powerconversion com pmbusqui c Inside Universal PMBus folder run setup exe d Extract ail_HID_std zip file in windows sys
6. Embedded Power for Business Critical Continuity Technical Reference Note Rev 02 26 10 UFE UFR Series 1 of 14 UFE UFR Series Up to 6000 Watts Total Power Input Voltage of Outputs Output Up to 6000 W 85 264 Vac stale hs a w y EE EDIS n 24V amp 48 V di anes Fe Se lie i n Product Description The UFE series is a digitally controlled high density bulk front end supply Rated at 1300W for wide range input for 24V and 48V this supply is well suited for Telecom Datacom and Indus trial applications At high line input the 48V unit is rated at 2000W The UFR is a 3 slot 1U rack for use with the UFE series power supplies Up to 6 UFR s can be parallelled for a total system power of 36KW Special Features e Rack mounted chassis 1U 19 e 3 hot pluggable rectifiers per 1U chassis up to 4 kW redundant or 6 kW available power 180 264 Vac input Up to 2 6 kW redundant or 3 9 kW available per shelf at 90 132 Vac input Stackable to 6U high to provide up to 36 kW available power Class B conducted EMI EN55022 See Note 1 Automatic fan speed control with fault reporting Auxiliary standby output 11 V at Electrical Specifications Input range 88 264 Vac 176 264 Vac Switching frequency 450 kHz fixed approximately 2 8 W High density up to 22 W in3 High efficiency up to 91 Floating as well as isolated main output voltage allows positive or negative polarity operation EU d
7. d name transaction status Read or Write 11 of 14 Rev 02 26 10 UFE UFR Series 12 of 14 1 Installation continued C Software Notes 2 Programming c Advanced Programming Notes a The commands in the sequence list view are Read Transactions by default but can be selected to Write via the down arrow b The appropriate Hex Code needs to be entered followed by OK button The Hex Code is developed from the UFE2000 96S48 PMBus excel Spread sheet The excel spreadsheet has macros which will not run unless you enable such When opening the spreadsheet one needs to enable macros when asked and also verify that the Analysis Tool Pak in excel is active This is achieved by checking excel under Tools gt Add in options If such are not enabled then when you change the values in the command spreadsheet the resultant value s will not change c Pressing the Single or Continuous button executes the new command d The Test Panel allows you to connect to multiple UFE Units because the Address Column is changeable per command You can also arrange the command sequence save amp load it for future use Example For adjusting the Output Voltage from 48 to 50 Vdc using Hex Code developed from the UFE2000 96S48 PMBus xcel Spread sheet 1 Insert the UFE Module on the left most side 2 Run the PMBus Universal GUI amp on the BASIC Screen press the Test Tab 3 Add VOUT_Command 21 to the Sequence Listi
8. e type of PS Enable Signal present Rated Output Input Standard Type of Output Communications Option Code Special RoHS Power Range Compliance Output Voltage Type Modification Compliance 9 UFE 2000 XX J Product Family UFE e 1300 1300 W 9 Universal 6 UL CSA VDE S Single 48 48 V P PMBus serial None Active Ishare J Pb free Front En 2000 2000 W Input Class A B 24 24V communications D Droop Ishare ROHS 6 6 with PFC HD PS Enable compliant HI Droop Active Low Enable means that the UFE unit s will not START until its PS EN Control signal on A6 is pulled Low Gnd Active High Enable means that the UFE unit s will not STOP until its PS EN Control signal on A6 is pulled Low Gnd Power Supply Connector Pinout D B P1 L1 R2 Lz P3 PEG Power Supply Connector 1 Sense Sense GND Shortpin 2 Present L GND PS IDO GND POWER SIGNAL eee 3 PS ID3 PS ID2 GND 12V AUX Dow E 4 GND SCL PS ID1 GND 5 SDA GND GND I2 C En H We yf i Comm En H 6 SMBALERT Ishare DCOK L PS EN Control P4 DC_N Power Connections Layout Be DC_N Looking into Connector Side of UFE Power Supply P6 DC P P7 DC_P 1 Installation continued B Hardware Connections continued Rev 02 26 10 UFE UFR Series 6 of 14 b If Emerson UFR6000 Rack is supplied then the Global PS En signal at J16 Pin
9. irective 2002 95 EC compliant for ROHS 2 year warranty PMBus compliant Safety e VDE EN IEC60950 1 e UL cUL60950 1 Output power Line regulation Load regulation Auxuliary Output 11 V 15 2 875 W 0 15 max Low line to high line 0 15 max Full load to min load Environmental Specifications Thermal performance MTBF 33 C to 70 C Operating 40 C to 100 C Non operating 40 C Cold start 279 069 hours Telcordia SR 332 Issue 1 4 S EMERSON Network Power Installing Programming UFE UFR6000 with Universal PMBus GUI 1 Installation A Minimum Requirements e PC with 1 GHz CPU e Emerson USBI2C iMP Dongle p n 73 769 001 e WIN XP e Admin rights during Software Installation e Internet connection during Software Installation e 500 MB HD space e 512 MB RAM e USB port Others e PMBus Application notes for PSU available at www PowerConversion com e Universal PMBus GUI User Manual Feb 2009 e UFE2000 96S48 PMBus xcel Spreadsheet Optional for Advanced Programming B Hardware Connections UFR6000 Rack modified UFR to USB dongle wire connector assembly _ USB Printer Cable Desktop or Laptop with Universal PMBus GUI USB I2C Dongle Figure 1 Hardware Setup Rev 02 26 10 UFE UFR Series 2 of 14 A Embedded Power for Business Critical Continuity Rev 02 26 10 UFE UFR Series 3 of 14 1 Installation
10. laza 2 Wing Yip Street Kwun Tong Kowloon Hong Kong Telephone 852 2176 3333 Facsimile 852 2176 3888 For global contact visit www PowerConversion com techsupport embeddedpower emerson com While every precaution has been taken to ensure accuracy and completeness in this literature Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions Emerson Network Power The global leader in enabling business critical continuity AC Power E Connectivity E Dc Power E Embedded Computing IE Embedded Power Monitoring Outside Plant Power Switching amp Controls Precision Cooling I Racks amp Integrated Cabinets I services a Surge Protection EmersonNetworkPower com Emerson Network Power and the Emerson Network Power logo are trademarks and service marks of Emerson Electric Co 2010 Emerson Electric Co
11. mmand sets 1 x UFE Unit at atime So before adjusting the output of a active unit there is a need to either pull out the other modules first or turn them off via PMBus command There is no blocking via the GUI software when all are enabled and one changes the voltage of one of the running units c Advanced Programming Using the Test Panel tab Ref to PMBus Gui User Guide V3 0 Pressing the Test Tab will bring up at Command Sequence Listing Fig 1 Rev 02 26 10 UFE UFR Series 1 Installation continued C Software Notes 2 Programming c Advanced Programming Using the Test Panel tab Ref to PMBus Gui User Guide V3 0 Pressing the Test Tab will bring up at Command Sequence Listing Fig 1 s5502 pE SS ee su a FULT RESPONSE FAULT IT e amn Bi 3 E a 35 2 at i a jit dt oe di DUT MF Hh els T m Fe 7 T mer 4 Figure 1 Figure 2 The Command Sequence Listing can be added subtracted to by pressing the Add button A list of PSU supported Commands will appear Fig 2 Anew sequence list can be created by selecting appropriately amp pressing Add gt button When all required commands are selected then press OK to return to the Test Panel You can change a Command within the Test Panel by selecting the required command amp press Edit button A new dialog box will appear outlining present unit address comman
12. ngs Screenshot of Test tab with the command ail ee sequences for adjusting to 50V output 21 VOUT_COMMAND PRT AE 21 VOUT_COMMAND Write 18 STORE_USER_ALL 21E Successful Successful Soot A Embedded Power for Business Critical Continuity Rev 02 26 10 UFE UFR Series 1 Installation continued 13 of 14 C Software Notes 2 Programming 3a At address F8 write on register 21 data 021E Hex Code for 50 00V Example for VOUT_COMMAND Command Number 21 Number of Data Bytes 2 Read Support i Write Support Command Name Y mX b 10 R Input Coefficients Y s J R DesredVotage Calculated Y to send Les OOO 42Vmin sv max VOUT COMMAND from the UFE2000 96S48 PMBus Spreadsheet 3b After filling in the sequence list press SINGLE button once for new Voltage to take affect Voltmeter on GUI should now read 50V Check Unit out Voltage using DVM 4 Send STORE_USER_ALL command 15 for the new instruction to be registered in default memory Otherwise the new instruction 50 Vdc will only be applied as long as the mains is not recycled 5 Power off the UFE module and wait for the Front Panel LED to go off 6 Power on again and check that 50V is set Example Modifying UFE Unit PS Enable from Active LOW to Active HIGH 1 Insert the UFE Module on the left most side of UFR6000 2 Run the PMBus Universal GUI amp on the
13. tem32 folder This is the driver file for 73 769 001 USB I2C dongle Note if your computer has a previous iMPGui installed then such can be found already 2 Programming a To run Universal PMBus GUI click on Start gt Programs gt Emerson Network Power gt Universal PMBus GUI Screen will display presently addressed UFE Unit Example Unit address FA Center UFE in Rack 1 Ep pee Communication Success Address FA requency 100KHz Poling Deisy 10msec PEC Disabled USB To2C Ver 16 click to select new address You can now perform various functions and operations through PMBus commands Rev 02 26 10 UFE UFR Series 9 of 14 1 Installation continued C Software Notes 2 Programming b Basic Programming The easiest way to vary Basic UFE variables is by clicking the appropriate Config tab on the BASIC Panel 1 Input Configuration Setting the Input Limits of the Power Supply Input Configuration x Voltage Over Voltage Faut Limit 275 00 v Warning Limit 275 00 v Sas Caira Faut Responso Fault Limit 13 00 A Warning Limit on ZA Warning Lima 12 00 v Faut Response Faust Limit 80 00 3 FauitResponse 0 After making appropriate adjustments then press write command tab to send new values to presently addressed UFE Unit 2 Output Configuration Setting the output Limits amp Voltage of the Power Supply Current Over Von Over Current aun Limie 8003 v ee