9125 PowerPass
Contents
1. Power Output Receptacles Load Segment 2 Load Segment 1 DIU U U j X i D U U U D UI Il cuit Breaker Access Mounting Screw Power Output Receptacles Load Segment 2 Load Segment 1 Bypass Switches Mounting Screw Laser Printer Receptacle 4 BYPASS UPS l O l Er EEE a 2 Circuit Breaker Mounting Screw Access Input Connector Figure 4 PowerPass for 700 2000 VA 240V UPS Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy CHAPTER 2 OPERATION Load Segments 0 The PowerPass allows for the removal of the UPS while providing power to your protected equipment This Maintenance Bypass feature is useful when replacing the UPS for maintenance or upgrades Load segments are sets of receptacles that can be controlled by power management software providing an orderly shutdown and startup of your equipment For example during a power outage you can keep key pieces of equipment running while you turn off other equipment This feature allows you to save battery power See your power management software manual for details NOTE If the power management software is not used the individual load segments cannot be controlled NOTE When the PowerPass is in Bypass mode all load segments are switched to utility power and cannot be controlled until the PowerPass is switched back to the UPS Each PowerPass has two load segments as shown in Figure 2 on page 5
2. POWERWARE 9125 PowerPass User s Guide WWWw powerware com Requesting a Declaration of Conformity Units that are labeled with a CE mark comply with the following harmonic standards and EU directives Harmonic Standards EN 50091 1 1 and EN 50091 2 EU Directives 73 23 EEC Council Directive on equipment designed for use within certain voltage limits 93 68 EEC Amending Directive 73 23 EEC 89 336 EEC Council Directive relating to electromagnetic compatibility 92 31 EEC Amending Directive 89 336 EEC relating to EMC The EC Declaration of Conformity is available upon request for products with a CE mark For copies of the EC Declaration of Conformity contact Powerware Corporation Koskelontie 13 FIN 02920 Espoo Finland Phone 358 9 452 661 Fax 358 9 452 665 68 Class B EMC Statements FCC Part 15 NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which ca
3. Tighten the two PowerPass mounting screws Do not overtighten Start the UPS by pressing the On button The indicator stops flashing Toggle both Bypass switches on the PowerPass to the UPS position The bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy CHAPTER 3 SPECIFICATIONS Table 1 Mechanical PowerPass Models 05146519 001 for 700 1500 VA 120V UPS 05146519 002 for 700 2000 VA 240V UPS 05146520 001 for 2000 VA 120V UPS Dimensions WxDxH 11 0 x 45 x 3 5 27 9 x 11 4 x 8 9 cm Weight 2 5 lb 1 1 kg Table 2 Technical 120V Models 240V Models Surge Supression 180V MOVs across input L and N 320V MOVs across input L1 and L2 100 joule 6500A peak current rating 160 joule 6500A peak current rating 320V MOVs each across L to G and N to G 160 joule 6500A peak current rating Electrostatic Discharge Withstands 25 kV Input Connection to 700 1500 VA 6 ft 5 15P power cord IEC 320 C14 input connector PowerPass 2000 VA 6 ft 5 20P power cord Input Connection to UPS 700 1500 VA 5 15R mates with IEC 320 plug mates with UPS 5 15P power cord UPS IEC 320 receptacle 2000 VA 5 20R mates with UPS 5 20P power cord Output Receptacles 700 1500 VA 6 5 15R 1 5 15R for 6 IEC 320 C13 laser printer unprotecte
4. power from the UPS output receptacles Unplug the UPS from the power outlet the UPS shuts down in five seconds All front panel indicators flash briefly prior to shutdown On 240V units also disconnect the input power cord from the UPS Disconnect the power cord s between the protected equipment and the UPS Remove the two screws on the UPS rear panel and discard see Figure 1 Figure 1 Removing the UPS Screws Verify that both Bypass switches on the PowerPass are in the UPS position see Figure 2 through Figure 4 Plug the PowerPass into the rear panel of the UPS Secure the PowerPass with the two mounting screws and retaining washers Do not overtighten Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy 0 Bypass Switches Installation 10 Reconnect the power cord s of the protected equipment to the power output receptacles located on the PowerPass see page 7 for more information on load segments NOTE The receptacle marked LASER is provided for laser printers The power from this outlet does NOT come from the UPS output but from utility power Therefore in the event of a power outage this outlet loses power 11 Plug the UPS power cord into the UPS input connector or input connector for 240V models on the PowerPass Plug the power cord into a power outlet All
5. UPS front panel indicators flash briefly and the UPS conducts a self test When the self test is complete the indicator flashes indicating the UPS is in Standby mode Start the UPS by pressing the On button The indicator stops flashing and the bar graph indicators display the percentage of load being applied to the UPS The UPS is now in Normal mode and supplying power to your equipment Mounting Screw Power Output Receptacles Load Segment 2 BYPASS UPS O o Power Cord e U U UW ll W el Laser Printer n O m BL ml Lg i Receptacle I Y Y Y BI u n 5 Load Segment 1 Screw UPS Input Connector Figure 2 PowerPass for 700 1500 VA 120V UPS Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy 5 Installation Bypass Switches Mounting Screw Circuit Breakers BYPASS UPS Power Cord e O Figure 3 PowerPass for 2000 VA 120V UPS Q C UPS Input Connector
6. d 1 IEC 320 C13 for 2000 VA 6 5 15R laser printer unprotected UPS AC Output to 2 5 15P connect to UPS AC output 2 IEC 320 C13 plugs connect to PowerPass Plug UPS AC output Operating Temperature 0 C to 40 C 32 F to 104 F Optimal battery performance 25 C 77 F Storage Temperature 20 C to 60 C 4 F to 140 F Relative Humidity 5 96 noncondensing Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy 9 Specifications 10 Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy 164201324 A
7. ls Safety Warnings Powerware 9125 PowerPass User s Guide e 164201324 A Uncontrolled Copy IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries Please read all instructions before operating the equipment and save this manual for future reference CAUTION There are NO USER SERVICEABLE PARTS inside the PowerPass All repairs and service should be performed by AUTHORIZED SERVICE PERSONNEL ONLY To reduce the risk of fire or electric shock install this UPS in a temperature and humidity controlled indoor environment free of conductive contaminants Ambient temperature must not exceed 40 C 104 F Do not operate near water or excessive humidity 95 max ow Installation The following instructions describe the PowerPass installation only Follow the instructions in your Powerware 9125 User s Guide for installing the UPS and optional Extended Battery Modules EBMs 1 Install the UPS and optional EBMs according to the user s guide Do not start up the UPS before installing the PowerPass Continue to Step 6 If the UPS is already installed and operating prepare your equipment for shutdown and continue to Step 2 Turn off the equipment that is connected to the UPS Press and hold the Off l button for approximately three seconds The UPS switches to Standby mode and removes
8. n be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures e Reorient or relocate the receiving antenna Increase the separation between the equipment and the receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help ICES 003 This Class B Interference Causing Equipment meets all requirements of the Canadian Interference Causing Equipment Regulations ICES 003 Cet appareil num rique de la classe B respecte toutes les exigences du Reglement sur le mat riel brouilleur du Canada Powerware and PowerPass are registered trademarks of Powerware Corporation Copyright 2000 Powerware Corporation Raleigh NC USA All rights reserved No part of this document may be reproduced in any way without the express written approval of Powerware Corporation CHAPTER 1 INSTALLATION The PowerPass is designed to operate with a Powerware 9125 uninterruptible power system UPS and allows you to Replace or upgrade the UPS without losing power to your equipment see Using Maintenance Bypass on page 7 Provide surge protection if the UPS is not present Provide extra surge protection when the UPS is present Protect a laser printer against power surges without overloading the UPS not available on 2000 VA 120V mode
9. through Figure 4 on page 6 Using Maintenance Bypass Powerware 9125 PowerPass User s Guide 164201324 A Uncontrolled Copy Use the following procedure to transfer your equipment to Maintenance Bypass AC Line operation and remove the UPS 1 Toggle both Bypass switches on the PowerPass to the BYPASS position see Figure 2 on page 5 through Figure 4 on page 6 The PowerPass is now powering your equipment from utility power 2 Press and hold the Off l button for approximately three seconds The UPS switches to Standby mode Operation If an optional EBM is installed unplug the EBM cable from the battery connector on the UPS rear panel 120V models only Disconnect the UPS power cord from the PowerPass UPS input connector Loosen the two PowerPass mounting screws Remove the PowerPass from the UPS being careful not to loosen the power cords plugged into the PowerPass Use the following procedure to reinstall the UPS and transfer your equipment from Maintenance Bypass AC Line operation to the UPS 1 If an optional EBM is installed reconnect the EBM cable to the battery connector on the UPS rear panel 120V models only Plug the UPS power cord into the PowerPass UPS input connector Plug the PowerPass into the rear panel of the UPS All UPS front panel indicators flash briefly and the UPS conducts a self test When the self test is complete the indicator flashes indicating the UPS is in Standby mode
Download Pdf Manuals
Related Search
Related Contents
Zotac ZBOX AD02 PLUS leben am limit.... ....feiern bis zum umfallen M24LR64-R tool driver install guide es fr de gb it griglia ceramica gas gas chargrill gas BioMate 5 USER MANUAL RGA Series User`s Manual ALLEGATO “1” : PIANO DI SICUREZZA Product Manual - Field Environmental Instruments, Inc. Concours pour l`aménagement de petites parcelles à jardiner Here - XILS-lab Copyright © All rights reserved.