CONTROLS ADVANTAGE AIR SINGLE VAV CONTROL SYSTEM

image

Contents

1. SUBSTITUE BEIGE CABLES WITH STANDARD TELEPHONE CABLE REVISION 05 10 02 I VAV 6 ADVANTAGE AIR SINGLE VAV CONTROLS ADVANTAGE AIR SINGLE VAV USER MANUAL SCREEN STANDBY AUTO BUTTON SETPOINT TEMPERATURE UP BUTTON SETPOINT TEMPERATURE DOWN BUTTON GETTING STARTED 1 Ensure A C unit is running 2 Set ZONE CONTROLLER to required temperature 3 To switch air off to zone set ZONE CONTROLLER to STAND HOW TO GET THE BEST OUT OF YOUR SYSTEM 1 In summer ensure the A C unit control is set at or slightly below the lowest ZONE CONTROLLER set point In winter ensure the A C unit control is set at or slightly above the highest ZONE CONTROLLER set point 2 Run the system for longer periods this will enable the ZONE CONTROLLERS to stabilise the system 3 Keep unused zones in STANDBY 4 Run the A C unit fan in continuous mode if appli cable 5 If rapid response from your system is required ad just the ZONE CONTROLLER setpoint to its ex treme setting For example if you enter the zone on a very hot day and want to cool the zone down as quickly as possible set the ZONE CONTROLLEH setpoint to 15 Remember to put it back to your normal comfort level once the zone has reached the desired temperature WHAT TO DO IF ZONES ARE NOT REACHING YOUR COMFORT LEVEL 1 Change setting on zone controller 2 Change setting on A C unit controller REVISION 05 10 02 AdvantageAir ZONE REQUIRES COO
2. CONTROLS ADVANTAGE AIR SINGLE VAV CONTROL SYSTEM AdvantageAir TYPICAL DAMPER ACTUATOR FEATURES e lowcost e Suitable for a limited number of controls off a central air conditioning system such as corner offices conference rooms and computer rooms or executive offices e Provides occupant with independent adjustable temperature control in each zone Automatically adjusts the required air quantity to maintain the required room zone temperature e All damper motors are pre installed and tested on Advantage Air Exact Air fittings e Can be used in conjunction with any make of air conditioning heating or evaporative unit e Can be easily retro fitted to existing systems e Supplied with all the necessary wiring and fittings The only electrical work necessary is a power point in the ceiling e Detects if the A C unit is in a cooling or heating mode and will automatically inverse operation e Attractive simple to use digital room thermostats with touch pad will maintain room temperature within T 1 C e Intelligent 24 damper motor with quick connect colour coded wiring does not require an electrician e Simple commissioning eliminates the need to balance air to zones TYPICAL DAMPER ACTUATOR REVISION 05 10 02 TYPICAL ZONE CONTROLLER TYPICAL CABLE TYPICAL CABLE JOINER uu APPLICATIONS Suitable for small commercial or residential ducted reverse cycle air co
3. LING TO ACHIEVE SETPOINT TEMPERATURE SETPOINT TEMPERATURE ZONE CONTROLLER SHOWN IN AUTO MODE HOW DOES THE ADVANCED AIR CONTROL SYS TEM WORK The Advantage Air single VAV works by measuring the temperature in the zone room temperature then compares the zone temperature with the setpoint and the system supply air temperature The VAV then takes the necessary action to reduce or increase the amount of air entering the room to enable the room temperature to match the setpoint It should be noted that the VAV can only make use of the supply air temperature being provided by the air conditioning unit The VAV cannot provide heating while the A C unit is running in a cooling mode In the event that the zone requires cooling while the A C unit is in a heating mode the VAV will close of the air supply to the zone until such time as cool supply air is available I VAV 7 ADVANTAGE AIR SINGLE VAV CONTROLS ADVANTAGE AIR SINGLE VAV USER MANUAL SYMPTOM POSSIBLE CAUSES REMEDY Zone too hot Zone too cold REVISION 05 10 02 A C unit not running A C unit control setpoint too high Zone controller on standby Zone controller setpoint too high A C unit not running A C unit control setpoint too low Zone controller on standby Zone controller setpoint too low Switch A C unit on Adjust A C unit control setpoint down Switch zone controller out of stand by and into auto mode Adjust zone co
4. he room temperatures are above d 15 after 5 minutes check that the following has occurred Zone should open fully f Setall A C unit to 30 C g Assuming the room temperatures are below 30 C after 5 minutes check that the following has occurred Zone should close fully h Readjust the A C unit to required operating set point i Readjust the ZONE CONTROLLER to required operating set point Instruct occupant in the use and limitations of the VAV control system k Handover the user manual and installation in structions to the owner REVISION 05 10 02 I VAV 3 ADVANTAGE AIR SINGLE VAV ADVANCED AIR SINGLE VAV SPECIFICATIONS ZONE CONTROLLER PROCESSOR RISC microcontroller DIMENSION 73 W x115 H x 25 D mm OPERATING TEMPERATURE 0 45 C THERMAL CONSTANT 3 mins CONFORMIT Y C Tick Approved DAMPER ACTUATOR ADM24S PROCESSOR RISC microcontroller DIMENSION 88 W x55 H x 136 D mm OPERATING TEMPERATURE 0 70 C CONFORMITY C Tick Approved REVISION 05 10 02 I VAV 4 ADVANTAGE AIR SINGLE VAV CONTROLS ADVANTAGE AIR SINGLE VAV CONTROL SEQUENCES AdvantageAir ZONE CONTROLLER ALGORITHM STAND BY AUTO Mode of operation Close damper Read System supply air temperature Zone setpoint temperature fully Zone actual temperature Setpoint lt Actual COOL Setpoint gt Actual HEAT Zone
5. minimum of 2 x 4mm mounting holes 5 Install RED CABLES in wall cavity conduit 9 Locate a suitable position up stream of the con for each ZONE trolled damper for the SUPPLY AIR TEMPERA A TURE probe to be installed maximum 1 5 meters from the DAMPER ACTUATOR A JU Uu 10 Drill one 6mm holes on the EXACTAIR Ensure the nad gt rc ann MA 6 Install back plate using the mounting screws and plugs provided hole is clear of all gears or damper blades 11 Insert the probe into the EXACTAIR and fasten the grommet using the 4 screws supplied 12 Provide a 3 pin power point in the ceiling space SN REVISION 05 10 02 I VAV 2 ADVANTAGE AIR SINGLE VAV CONTROLS ADVANTAGE AIR SINGLE VAV INSTALLATION INSTRUCTIONS 13 14 15 16 within 25 metres of the new damper Connect BEIGE CABLES from DAMPER AC TUATORH av power suPPLY port to the POWER SUPPLY Do not substitute standard telephone cable for the beige cable as the polarity is incor rect Connect POWER SUPPLY to an RCD protected switched sockett and switch power on By pressing the STANDBY AUTO button the ZONE CONTROLLER display will be changed from STANDBY TO AUTO MODE Test the VAV as follows STANDBY STANDBY AUTO BUTTON W AdvantageAir a Switch A C unit on and set temperature to cool ing at 15 C Set the ZONE CONTROLLER to 15 C Assuming t
6. nditioning systems Can be used on ducted gas heating systems e Care should be taken to ensure there are sufficient constant volume outlets on the system to handle the additional air volume when the VAV zone s are fully closed DIMENSIONS l T Era ru mss C Bn E NS TYPICAL CABLES 25 O A Cw E 73 TYPICAL ZONE CONTROLLER 115 O A CABLE LENGTH 6M 12M OR 25M OPTIONS I VAV 1 ADVANTAGE AIR SINGLE VAV ADVANTAGE AIR SINGLE VAV AcvantageAir INSTALLATION INSTRUCTIONS 1 Ensure the Air Conditioning system is designed 7 Connect RED CABLES from ZONE CONTROL installed and running correctly LER to the corresponding DAMPER ACTUATORS Switch A C unit off Room TEMP sensor port Observe colour coding Locate the ZONE CONTROLLER in it s respec 8 Connect BLUE CABLE DUCT TEMP SENSOR tive zones as follows to DAMPER ACTUATOR sUPPLY AIR TEMP SENTSOR e Approx 1 6 metres above the floor port e Not exposed to direct sunlight through windows e Not exposed to drafts or air discharge from the A C outlet Ina position representative of the zone which it is installed e Do not place furniture such as book cases etc in front of the controller Do not locate heat generating appliances such as computers TV s fridges etc un der the ZONE CONTROLLER 4 Usethe ZONE CONTROLLER back plate right side up as a template Provide a 22mm cable access hole and a
7. ntroller setpoint down Switch A C unit on Adjust A C unit control setpoint up Switch zone controller out of stand by and into auto mode Adjust zone controller setpoint up I VAV 8 ADVANTAGE AIR SINGLE VAV
8. requirement Supply air Supply air Supply air gt Actual HEAT Supply air gt Actual HEAT Actual COOL lt Actual COOL System supply air temperature System supply air temperature Damper Damper Damper motor drive Damper motor drive motor drive motor drive direction direction CLOSE OPEN direction CLOSE direction OPEN Calculate deviation from setpoint Room minus Setpoint gt 0 1 amp lt 0 6 gt 0 6 Deviation 0 1 Damper motor Damper Damper drive re motor drive motor drive sponse time NO response response SLOW FAST Drive damper motor Use direction amp response time REVISION 05 10 02 I VAV 5 ADVANTAGE AIR SINGLE VAV ADVANTAGE AIR SINGLE VAV ORDER FORM CONTRACTOR PROJECT NAME PROJECT ADDRESS PROJECT OR ORDER NUMBER MARK WITH AN WHERE APPLICABLE TOTAL NUMBER OF VAV KITS REQUIRED RED CABLE BEIGE CABLE ZONE CONTROLLER TO DAMPER DAMPER ACTUATOR TO MASTER ACTUATOR CONTROLLER POWER lt 7 lt 6M 12M 25M TOTAL 1 pg al 5 HEN 7 9 M NUMBER OF JOINERS REQUIRED ARE EXACTAIR ORDER FORMS ATTACHED NOTES 1 CABLE FOR EACH ZONE MUST NOT EXCEED 37 METRES PER COLOUR 2 DO EXCEED 1 JOINER PER 37 METERS OF CABLE 3