Home
        instruction manual for transformer differential
         Contents
1.                                                                                                                                                                                   22 eee COMS 25 1 PADDLE  D 490 e      See  COM   2      2        28 1 BARS                   GSE SER         4 iam   L 25 451  w Y      YX     POWER  SUPPLY  STATUS m  9                     ray AA A L9 3        7 ee Own                  s E  GROUND AAAS 4  TERMINAL       INTERNAL V  CIRCUITRY  e      TARGET TARGET POWER  E    zA S U PP LY    UNRES RES  TRIP TRIP      e  MEJEJE                10   8   6   4   2  P0012 31  05 29 02                   Figure 4 12  Internal Connections  Three Phase  Two Input  Sensing Input Type E   Output Option E    9171300990 Rev R    BE1 87T Installation    4 13    SUPPLY  STATUS    EXTERNAL  CASE  GROUND    TERMINAL    PADDLE  OPERATED  SHORTING    BARS       BE1 87T  D983 025  2 18 93    Figure 4 13  Internal Connections  Three Phase  Two Input  Sensing Input Type E   Output Option F    4 14    BE1 87T Installation    9171300990 Rev R    PADDLE   OPERATED   SHORTING  BARS    SUPPLY  STATUS    EXTERNAL  CASE  GROUND  TERMINAL    BE1 87T  D983 023  2 18 93    UNREST REST                      Bet 87T               S71  9 19 POWER  TARGET TARGET A   OPTIONAL   OPTIONAL      gt  J      d 877  87T 5 20  RESTRAINED LEGEND   87T 87T TRANSFORMER DIFFERENTIAL  RELAY    86 LOCKOUT RELAY    A OPTIONAL CURRENT OPERATED  TARGETS       AUXILIARY OUTPUT OPTION FOR  SINGLE PHASE  NO 
2.                  H X  C          C  B i H         B  H t  A 1   4          H    Switch     BE1 87T  board     18  terminal   16   WYE  blocks 15  13  14    12 141  11 4             D2751 23    03 12 98                              Phase shift jumper        position on analog  board  2     Figure 4 29  Three Phase Connections  Wye Delta Configuration  Internal Phase Compensation    The transformer in the example shown in Figure 4 29 has a delta connection on the secondary winding   The currents in each winding of the delta are A  B and C respectively as reflected from the wye  connected primary winding  The delta connection of the transformer windings causes the current flowing  in the phase leads connected to the delta winding to be A C  B A and C B respectively  The CT currents  on the wye side must be combined similarly to provide A C  B A and C B to compensate  This is shown in  Figure 4 27 by selecting phase compensation jumper position A1 for the wye side input     4 28    BE1 87T Installation    9171300990 Rev R                                                                                     H     3 PC ott X     si     lt ie  ile  B   H  Br  E      B  3     Bills  316  H X        1 n      1 A  pile       5116  Er mie i    Switch 7  board   18  terminal m 16  blocks 15  13  14  12                               np    D2751 24       Phase shift jumper _  V ABS H  X  position on analog  board  2     Figure 4 30  Three Phase Connections  Delta Delta Configuration    91713
3.                  in pu  OR Ex  gt  gt     slp  Ti      ore  100 100  the value of 12 trip max  is defined as   h trip        balance                 pu   l T  OR           1 19   100 Ti  2  When   0 35       balance  lt   in pu              100  the maximum trip point is established as     12 trip 7      balance   0 35  in pu     1       I2trip max           035     1    Example Three   Assume     tap    2  tap    3 8  slope   15    Inputs 7  22 A  1 pu   1  3 8 A  1 pu     9171300990 Rev R BE1 87T Test Procedures     Equation 3      Equation 3a      Equation 4      Equation 4a     5 5    Check   0 35    Iobalance     gt  slope       1  lt  2 333    Therefore  Use Equation 4 or 4a   From Figure 1 2  the percentage restraint characteristic of the BE1 87T at 15  slope   the minimum    current where trip occurs is   Ip trip   1 pu   0 35      0 65 pu    In terms of current  the trip current is   I5 trip    0 65 pu   Tap        0 65   3 8    2 47      6    100 mA    2  Using Equation 4a  I2trip    2   035               247A  Example Four   Assume   tap    2  tap    3 8  slope   15    Inputs      6 A  3 pu   I   11 4A  3 pu   Check   0 35          balance  lt   gt             pu   100  Bas ve 0 35  0 15  3    2 333    Therefore  Use Equation 3 or 3a     From Figure 1 2  the percentage restraint characteristic of the BE1 87T at 1596 slope   the minimum    current where trip occurs is     3pu 1 0 15       2 55 pu    12             In terms of current  the trip current is   I5 trip 2
4.              1 2 00222 20 000 00 000610      a          1 4  Style Number                                   4  l    U    U    1 4  SPEGIFIGATIONS                        enter ed au                                   1 5  Current Sensing 1                                                           1 5  Current Sensing Burden                                n n snn    1 5  Tap Setting Control  Scaling                                                                                    1 5  Restrained    Outputs       re err eicere dese           1 5  Front  Panel Setting                 aee               aer Re    1 6  Unrestrained OUtpUL          tre e iPad dd rere e P eh Ue Pee epe 1 6           aarti iet 1 7                             2  2                                     tendunt tante tanus 1 7                                                          1 7  Moe                e LEE 1 7  Sola iON us otc edet                          a      1 9  Power Supply                                         eer                                          1 9  Surge Withstand Capabillfyi y L u uu G itu qa uaqta en nennen rnit             1 9  Radio Frequency Interference  RF I                            l Q s a    1 9  WIE RECOGNITION s L          eat eeu cea ecu pal scm nai deca natn eee 1 9  GOST R Certificato Nesie 1 ette eoim                 ME Dee m EE CLER S Un meme 1 9             enin te i edt      Satu Ria    eset es 1 9  SHOCKS               cee CRT Pere Dt tu a MM LL I E 1 9  VIDE 
5.            H  B            e    o o       J     H  X         AYA    o               A       i id  X     T  Lo o         SWITCH BOARD    TERMINAL BOARDS  BE1 87T 1         B              2  12    aja 14    h  A9          A  BE1 87T 1     ga       2  12       a 14        AQ  BE1 87T 1   e 2  12  11   1     3   14   v N D1186 04             H  X  03 12 98  BE1 87T B TYPE SENSING    Figure 4 26  Single Phase Connections  Delta Wye Configuration With Two Load Busses    Three Phase Input Sensing Connections    Phase Shift Compensation       Three phase units must be connected in a way that will negate any phase shift introduced by the  protected power transformer  This is accomplished by one of two methods     1  By connecting the system CTs to complement the power transformer connections  i e   a  wye delta CT can negate the phase shift of a delta wye power transformer  and vice versa     2  By utilizing the internal 30   Phase Shift Compensation that is a feature of three phase BE1 87T  relays     Advantages of Internal Phase Compensation    Three phase units provide for internal phase angle compensation  Among the advantages of this method  is the ability to connect all the CTs in wye  This not only simplifies the connections but also facilitates  sharing the CTs with other devices  Furthermore  the wye connection reduces the burden on the CTs     A set of movable jumpers  Figure 4 27  determines the direction of the compensating internal phase shift  for each input  Because eac
6.         1304 3            HIGH TERTIARY LOW  2863  Ip  2 3563   IE           6 0         2 0 E 2 5  524 zb 524  Step 18  Determine the unrestrained pickup level in multiples of tap  X TAP   Refer to Appendix A   Setting Note 4    X TAP    0 7   Ig Max    HIGH TERTIARY LOW  Ij not maximum 1        maximum X TAP    0 7 24      16 8    Note    The restrained element will not operate due to the large 2nd harmonic component  present in the highly distorted current        Step 19  Using the results of Step 18  set the UNRESTRAINED PICKUP LEVEL control  Referring to  the table on the BE1 87T front panel  select the tap position  X TAP  that is higher than the  result obtained in Step 18  Therefore  for this example  select SET position P   19 X TAP   which is higher than the above result of 18 2 A     Slope Setting    Step 20  Determine the multiples of self cooled current   7   Refer to Appendix A  Setting Note 5     _ IR  MVASELF COOLED        T MVAFORCED COOLED   Where   In   relay current  from Step 4   T   the input tap  from Step 9     MVA SELF COOLED and MVA FORCED COOLED are given in Figure 4 33     9171300990 Rev R BE1 87T Installation 4 39    Step 21     4 40    HIGH TERTIARY LOW    iE  6 04  Q00  r    169040  1    05900    2 0   250   6 0  50   2 5  250     2 42  2 24  2 42    Select the restrained slope setting     The recommended restrained slope setting  S  is a function of the total mismatch and the  power transformer exciting current  This provides an ample security 
7.         E                      steaks cules 4 1  RELAY OPERATING PRECAUTION S        Ring               er tne deed tt beds 4 1  eye 4 1  DIELECTRIC TEST uiii itta et iba usai eee e rdg                     cet ode dan 4 9                        5  etico ia ecrit eR ie      te te edle ete E        4 9  RELAY DISASSENMBLY  iu er rt e eat ee ale reni io                            4 17  PIOCAUTIONS EET 4 17  Circuit Board Removal Procedure                                             entrent nnns 4 17  DISABLING                                                                                       4 18  Single Phase Units                 dad                        Era Linie                       FORE tr rapa 4 20  Three Phase Units                    L                                    4 20  SENSING CONNECTION                           7            4 20  Single Phase Input Sensing Connections                           L    u    4 20  Three Phase Input Sensing                                      4 20  SETTING  THEBEN 8         a      eoa teret sae anu vst date Pasa DOR eve eap edu e ea adus 4 33  Iso TELE 4 33  Procedure  One  o rite n ie ce eI i tete tne ra pierre Retos tk RA Lane               4 33  Procedure TAO M                                4 42  CHECKING THE RELAY SETTINGS AND SYSTEM INPUTS                   seen 4 49  MAINTENAN GE      2 2     eit eec        Eee dete pea is nte abet d eR RR LER                              4 50  SORA GE    dedit b susunan    aie tede     
8.        VCE    800     200   533 3    Step 16  Determine the saturation factor  Sp      VB is the largest of the burden voltages calculated in steps 13 and 14     Vg  SF   VCE  HIGH LOW  Sr  22 4 Sr   98 0  200 533 3   0 11  0 18    NOTE  Maximum Recommended S    0 5     Larger saturation factors will make the relay insecure for external faults  The only solution is to increase  the CT quality     Instantaneous  Unrestraint  Unit Setting    Step 17  Determine the maximum external fault multiple   g       For wye connected CTs and with WYE jumpers on Analog Board  2  shown in Figure 2   4   Ir Maximum Relay Fault Current                     Corresponding           4 46 BE1 87T Installation 9171300990 Rev R       For delta connected CTs  or with  1 or   2 jumpers on Analog Board  2  shown in Figure  2 4   and based on phase to phase fault    See Setting Note 3      18643   fps       HIGH LOW  32 66 43   I SS oe  E730 IgE    2   15 96 E    Step 18  Determine the unrestrained pickup level in multiples of tap  X TAP    See Setting Note 4     X TAP    0 7XIg Max      HIGH LOW  X TAP    0 7 15 96 Ig  not maximum   11 17    This calculation assumes that the CTs carrying the maximum fault saturate severely  yielding only 30  of  the expected ratio current  This leaves 70  of the fault current as a false differential current     NOTE    The restrained element will not operate due to the large 2nd harmonic component  present in the highly distorted current        Step 19  Using the resul
9.     RESTRAINED  ye    oA   C RESTRAINED  is UNRESTRAINED  INPUT 1     OUTPUTS                COM  M    FK        oA POWER SUPPLY  STATUS       CONTACTS    INPUT 2 4     gC    com  P0012 32  05 30 02       Figure 4 9  Case Terminals  Three Phase  Two Input  Sensing Input Type E   Output Option F    4 10 BE1 87T Installation 9171300990 Rev R      BET 87T  POWER    INPUT 1 2         RESTRAINED  COM  COM       OUTPUTS  UNRESTRAINED    POWER SUPPLY  STATUS    CONTACTS    9    INPUT 2                  COM   on               INPUT 3 4  gC       P0012 33  05 30 02       Figure 4 10  Case Terminals  Three Phase  Three Input  Sensing Input Type G   Output Option E    9171300990 Rev R BE1 87T Installation 4 11    INPUT   4 CO                                                                                                                                                 1 PADDLE  E OPERATED  17 15 13 C1  SHORTING  NPUT   5 INPUT 3 NPUT 2 BARS  20      16  14  12                 X  gt  x Ny      YY             p  POWER    SUPPLY VA AA     f  STATUS  EREN A  rn  N   e          EXTERNAL  CASE       GROUND M I    TERMINAL INTERNAL CIRCUITRY                  POWER  TARGET TARGET      AUX SUPP a  UNREST REST  TRIP TRIP  AN     e        9   5     COM AUX AUX  10      com           P0012 30  UNREST RES AUX COM  3 05 29 02                         Figure 4 11  Internal Connections  Single Phase  Five Input  Sensing Input Type D   Output Option E    4 12    BE1 87T Installation    9171300990 Rev R   
10.     Target Reset Switch Resets the electronically latched targets     Auxiliary Relay Control Two internal slide switches  61 and S2  enable the   Switches Option optional Auxiliary Output Relay to close only when a  restrained output occurs  S1 ON   only when an  unrestrained output occurs  S2 ON   or to close when  either output occurs  S1 and S2 ON      When shipped from the factory  the Auxiliary Relay will  be configured with S1 and S2 ON     NOTE  The switches are located on the  mother board and are only accessible  by withdrawing the relay case     ELEMENT Targets Option Electronically latching LED targets indicate the phase   three phase units ONLY  that caused a trip operation     RESTRAINED PICKUP Thumb wheel switches  one per phase element  are   LEVEL Switches used to adjust the desired percent of allowable  through current restraint from 15 to 60 96 in 5 96  increments   Through current is the greatest relative  individual input current      The through current restraint characteristic is  individually adjustable for phases A  B  and C     In a three phase unit  all three switches are typically  kept at identical settings     UNREST  TRIP Indicator Red LED lights when there is an unrestrained pickup   E REST  TRIP Indicator Red LED lights when there is a restrained pickup     M Indicator Red LED lights when the   OF TRIP pushbutton P is  pressed and the restraint current is below the slope  characteristic kneepoint as defined in Table 1 1  That  is  the relay wi
11.    27 are in the WYE WYE position   Relays are shipped with all jumpers in this position     If one of the inputs requires a shift in phase  the jumpers for all three phases are moved as  follows     1  The A2 position develops A B  B C  C A   2  The A1 position develops A C  B A  C B   NOTE    The result of each of these vector differences has a magnitude of the square root of three  times each component        The internal phase shift compensation is performed electronically as shown in the chart of Figure 4 27   The internal compensation can apply to any power transformer with any combination of wye  delta or  autotransformer winding connections     A procedure to check the differential balance is described later in this section  CHECKING THE RELAY  SETTINGS AND SYSTEM INPUTS     9171300990 Rev R BE1 87T Installation 4 25     gt  gt     lA 1  TAD    1  1    2          CompensatedI magnitude  is J3x          30          I     30    Compensated  magnitude       D638 002  03 12 98  I     A1 Compensation for A Phase I  Ic A1  A2 Compensation for A Phase    Figure 4 27  30   Phase Shift Compensation Jumpers    The transformer in the example shown in Figure 4 28a and 4 28b has a delta connection on the primary  winding  The currents in each winding of the delta are A  B and C respectively as reflected from the wye  connected secondary winding  The delta connection of the transformer windings causes the current  flowing in the phase leads connected to the delta winding to be A B 
12.    MOTHERBOARD    MOTHERBOARD    FRONT  PANEL          5636 003  THREE PHASE 2 23 93       Figure 4 19  Side View of Cradle Assembly       DISABLING UNUSED INPUTS    To eliminate the possibility of a spurious input from induced currents within the relay  special internal  jumpers have been provided to disable any inputs that are not connected to CT wires        CAUTION    Disabling unused inputs requires disassembly of the relay and must be done when the  relay has been taken out of service  Access to the input disabling jumpers requires the  removal of the Analog  1 Board  shown in Figure 4 19  To avoid personal injury or  equipment damage  do NOT proceed unless thoroughly familiar with the instructions in  sections RELAY OPERATING PRECAUTIONS and RELAY DISASSEMBLY   Precautions           4 18 BE1 87T Installation 9171300990 Rev R    NOTE     FOR ALL 2 INPUT RELAYS  BOTH SINGLE  AND  THREE PHASE   ALL JUMPERS MUST BE IN  THE DISABLE POSITION AT ALL TIMES     FOR OTHER RELAYS  SEE CHART BELOW     x  E    RIGHT HAND EDGE OF ANALOG BOARD  1     LOOKING FROM FRONT OF RELAY   anaes    9 21 94            374 172 NW AE             Figure 4 20  Unused Input Disabling Jumpers  Analog  1 Board  Option 1 0         FACTORY J9 NOT FIELD  ADJUSTMENT ADJUSTABLE    BE1 87T  D1924 12  9 21 94            foo oy WP  e        at         Figure 4 21  Unused Input Disabling Jumpers  Analog  1 Board  Option 1 1    9171300990 Rev R BE1 87T Installation    Single Phase Units    Single Phase Units wi
13.    Serial No  XXXXXXXXXXXX   PUSH TO   ENERGIZE   See Fig  2 4 QUTPUT   A B C R U     ELEMENT      L FUNCTION         U S  PATENT 5 014 153  PATENTED IN CANADA  1993    P0052 24    Figure 2 1  Sensing Input Range 1 or 3 Three Phase  Three Inputs    2 4 BE1 87T Controls and Indicators 9171300990 Rev R    ES  Basler Electric    INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5  1 00 1 60  1 00 1 60  1 00 1 60  1 00 1 60  1 00 1 60                                           REST  UNREST   TRIP TRIP      RESTRAINED PICKUP LEVEL    amp   o o          ma       cf of ef    of    o   D L  THRU CURRENT  15  20  25  30  35  40  45  sof 55  60         1 87       lt               K  TRANSFORMER DIFFERENTIAL      POWER  WAY Style No  D4E A1J DOS5F  Serial No  XXXXXXXXXXXX          PUSH TO  ENERGIZE  OUTPUT    See Fig  2 4 R UC          io    E  FUNCTION         U S  PATENT 5 014 153  PATENTED IN CANADA  1993    P0052 23    Figure 2 2  Sensing Input Range 1 or 3  Single Phase  Five Inputs    9171300990 Rev R BE1 87T Controls and Indicators    See Fig  2 4    ES Basler Electric    INPUT 2  100 1 60  C   yv    UNREST   TRIP             PHASE A      THRU       UNREST   TRIP                           UNREST      L  TRIP PHASE C            TRANSFORMER DIFFERENTIAL                                           WAY Style No  E2E A1J DOSOF  Serial No  XXXXXXXXXXXX    See Fig  2 4              P0052 25        ELEMENT       h    CURRENT   D   See Fig  2 4  POWER  PUSH TO  ENERGIZE  OUTPUT  R uO  L  eunction       
14.    Step 1     Step 2     Step 3     Connect Input 1 current to terminals A and N    Connect Input 2 current to terminals A and N    This verifies the A  and C phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The B   phase differential circuit sees no current and does not respond    Connect Input 1 current to terminals B and N    Connect Input 2 current to terminals B and N    This verifies the A  and B phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The C   phase differential circuit sees no current and does not respond    Connect Input 1 current to terminals C and N    Connect Input 2 current to terminals C and N    This verifies the B  and C phase differential circuits which respond together as provided earlier    in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The A   phase differential circuit sees no current and does not respond     Jumper Positions A1 A2    Step 1     Step 2     Step 3     Connect Input 1 current to terminals A and N    Connect Input 2 current to terminals N and B    This verifies the A  and B phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The C   phase differential circuit sees no current and do
15.    The unit is designed to operate from the secondary of current  transformers rated at either 1 Aor 5A  Frequency range is  5 Hz of  nominal     4 Acontinuous  50 A or 50 X tap  whichever is less  for 1 second     20 Acontinuous  250 A or 50 X tap  whichever is less  for 1  second     For ratings other than one second  the rating may be calculated as   me  t   Where    tis the time  in seconds  that the current flows   K   50 Aor 50 X tap  whichever is less  1 Amp CT Units   or   K   250 Aor 50 X tap  whichever is less  5 Amp CT Models   Less than 0 02 ohm per phase     Front panel rotary switches  labeled INPUT  permit scaling the  sensed input current  or tap setting  over the range of     0 4t01 78in0 02A increments   2 01t108 9A in0 1Aincrements     Front panel thumbwheel switches adjust pickup of the restrained  output as a percentage of the through current  The range is 15 to  60   of the operating current in 5 96 increments      6 96 of pickup  100 mA  5 Ampere Units  or  20 mA  1 Ampere  units      0 35  6   of tap setting  Refer to Table 1 1 and Figure 1 2  Table  1 1 provides calculated intersection points of the slope  characteristic and the minimum pickup  in multiples of tap  as  shown in Figure 1 2  The calculation was derived from the formula   Minimum Pickup    Maximum I Restraint    estrain  percent of Slope    For example     Minimum Pickup _ 0 35  Percent of Slope 20    The relay operates when the per unit difference current  operating    current  is above
16.   A 10       9171300990 Rev R BE1 87T Introduction ix    This page intentionally left blank        BE1 87T Introduction 9171300990 Rev R    SECTION 1   GENERAL INFORMATION       INTRODUCTION    These instructions provide information concerning the operation and installation of BE1 87T Transformer  Differential Relays  To accomplish this  the following is provided     Specifications  Functional characteristics  Mounting information    e   e   e   e Setting procedures and examples    WARNING     To avoid personal injury or equipment damage  only qualified personnel should perform  the procedures presented in these instructions        These instructions may be used in place of all earlier editions  For change information  see Section 8     NOTE FOR USERS OF SENSING INPUT TYPE F RELAYS    Users of BE1 87T relays with Sensing Input Type F  three phases three inputs per  phase  will find Difference Data in Section 6 of this manual that describes features  specific to these relays  The three phase  three inputs per phase design  previously    available as Sensing Input Type F  has been modified and is now available as Sensing  Input Type G  Due to differences in components and output terminal connections  Type G  relays are not compatible with earlier versions of the BE1 87T with Sensing Input Type F   There are also differences in the output connections as described in Section 6   Difference Data           DESCRIPTION    BE1 87T Transformer Differential Relays provide primary prote
17.   Application Example  Autotransformer With Tertiary Winding   See Figure 4 32 for 3 phase connections         SPECIFICATIONS HIGH SIDE   TERTIARY LOW SIDE    CT Ratio 600 5        2000 5  um  600 5  T  1200 5    CT Accuracy Class C400    One Way Lead Burden  ohms  0 7    CT Connection  Three Phase    WYE WY WYE             NOTE    Three phase is the most common application of the BE1 87T  Using single phase relays    requires a Delta connection for the High side and Low side CTs        to match the  tertiary connection in the example detailed in Figure 4 32         Step 3                        Units Only  Adjust the phase compensation jumpers on Analog Board  2   shown in Figure 2 4 and Figure 4 27   or use the procedure listed in TESTING THREE PHASE  UNITS WITHOUT CHANGING JUMPERS  in Section 5      Because of the grounded winding in this example  as shown in Figure 4 33 and 4 32  the high     side and low side zero sequence currents must be canceled  A2 position is selected to align  the High side and Low side secondary current phasors with the tertiary phasors which lead by  30  in this example    HIGH TERTIARY LOW    Jumper A2 WYE A2  Position     9171300990 Rev R BE1 87T Installation 4 35    Step 4  Determine the relay current  lp      Ig   Ig    Conversion Factor    Three Phase Units only  When using either A2 or A1 jumper positions  shown in Figure 2 4   multiply the secondary current 7  by the conversion factor  square root of three  just as if the  CTs were connect
18.   Maintenance to Section 4  Installation   e Added GOST R certification to Section 1  General Information    Q  10 05 e In Section 1  General Information  Specifications  corrected values for    Maximum Current per Input for 1 Ampere CT Units    e  n Section 5  Test Procedures  corrected values inside CAUTION box  for 1 AMP CT on page 5 14    P  05 03 e Added a thumbscrew to the figure on the manual front cover    e Added    not all styles  to the Power Supply Output heading on page 3   4 as well as added  NOTE  and a text box around the second last  paragraph on page 3 4    e Added the new thumbscrew to Figure 4 1 and changed the height  dimensions in Figure 4 2    e Clarified the terminal numbers on Figure 4 6b    e Added a shorting bar between terminals 6  amp  7 in Figure 4 11     e Added a shorting bar and normally open contact and normally closed  contact effecting terminals 1  2   amp  5 in Figure 4 12     e Step 13 was corrected on pages 4 31 and 4 39 to include Ry in the          formulas   e Values were changed to Table 5 4 under Option 1 0 for Unrestrained  Trip   N  09 00 e Corrected Table 1 3 to show power supply ranges     e Changed instruction manual front cover  Figures 4 1  4 3  and 4 5 to  show new unit case covers     e Changed Figure 4 32 per markup     M  04 99 e Table 3 1 changed mid range nominal volt 125 Vac to 120 Vac   e Corrected Figures 4 24  4 31a  and A 3    e Corrected page 4 38  Step 10  added note to page 4 39  Step 13  and  corrected Steps 14
19.   Step 8     5 14    Relays without Changing Jumpers at the end of this section     Replace all circuit boards and reassemble the relay     Refer to Table 1 1 and Figure 1 2 for multiples of tap and percentage restraint characteristics   Set the RESTRAINED PICKUP LEVEL switches and the INPUT 1 and INPUT 2 tap switches  to the values shown in Table 5 5     Apply power to the relay  Apply input current as indicated in Table 5 5 for each input  Then  reduce the Input 2 current or increase the Input 1 current until the REST  TRIP LED lights  This  should occur as the input current being adjusted reaches the level given in the Trip Amperes  column for the respective input     If the relay has more than two inputs  reconnect the relay by substituting the Input 3 terminals  for the Input 2 terminals  Then repeat step 6 and 7 using the Input 2 values of Table 5 5 for  Input 3     If there are more than three inputs  as in some single phase units   continue substituting every  higher numbered input for Input 2  each time comparing the input under test against Input 1 as  in Steps 6 and 7     BE1 87T Test Procedures 9171300990 Rev R    Step 9     Three Phase Units Only  Repeat Steps 6  7 and 8 for phases B and C   Refer to Figures 5 2  through 5 5  as appropriate  for the terminal numbers of the phase B and C inputs of the relay  under test      Table 5 5  Restraint Pickup Test  1 A  50 or 60 Hz       15  15  15  15  2  2  2  2  5  5  5  5  3  3        O                        O  CO RP
20.   The trip time should be less than that shown in Table 5 4     Three Phase Units Only  Repeat Steps 1 through 5 for Phases B and C     Place the UNRESTRAINED PICKUP LEVEL switch to the A setting  6 X TAP   Place all of the  INPUT switches to the 2 0 A tap position     With 0 0 A at Input 1  terminals 11  amp  13   apply 24 A  2 x Pickup  to Input 2  terminals 12 and  13 on single phase and terminals 15  amp  18 on three phase   Note the time interval between  initiation of the simulated fault and the closure of the unrestrained output contact  The interval  should be less than that shown in Table 5 4     Repeat Steps 7 and 8 at 10 x Pickup  Note that  with Input 1 at 0 0 A  it will be necessary to  step the Input 2 current to 120 0 A for an unrestrained trip  The trip time should be less than  that shown in Table 5 4     Three Phase Units Only  Repeat Steps 8 and 9 for phases B and C     Table 5 4  Timing  5 A  50 or 60 Hz       Option 1 0 Option 1 1  Timing Maximum   Timing Maximum    Function   Differential Current   50Hz   60Hz   50 or 60 Hz  Restrained Trip 49 ms  Restrained Trip 37 ms  Unrestrained Trip 57 ms             Unrestrained Trip 10 x Pickup 32 ms 28 ms 10 ms       9171300990 Rev R BE1 87T Test Procedures 5 13       VERIFICATION TESTS  1 AMP CT  50 OR 60 HZ UNITS          CAUTION    Current supplied to the BE1 87T input terminals must not exceed 4 A continuous or 50 A  for 1 second  Whenever 4 A must be exceeded  provisions must be made to cut off the  sensing 
21.   When the Target option is specified as either C or D  shown in the seventh position of the Style Number   electronically latched indicators  labeled FUNCTION  are incorporated in the front panel  The  electronically latched and reset targets consist of red LED indicators  The appropriate target is tripped  when either a restrained  R  or unrestrained  U  output occurs  Latched targets are reset by operating the  target reset switch on the front panel  If relay operating power is lost  any illuminated  latched  targets are  extinguished  When relay operating power is restored  the previously latched targets are restored to their  latched state     When targets are specified for three phase relays  three additional ELEMENT targets are incorporated to  indicate the phase involved  Only the FUNCTION targets  restrained  R  or unrestrained  U  are available  for single phase units     Relays can be equipped with either internally operated targets  Type C  or current operated targets  Type  D   Both target types are reset by operating the target reset switch     e Type    target  referred to as internally operated  is actuated by an integral driver circuit that responds  directly to the relay internal logic  This type of target is tripped regardless of the amount of current  flowing through the associated output contact     e Type D target  referred to as current operated  is actuated when a minimum of 0 2 A flows through  the associated output contacts  To accomplish this  a spe
22.   Xo OR H  X  BUSHING  151A t A1 OR A2       AS APPROPRIATE 18 N 1  terminal 14 C  blocks 12 B         141 OR A2    13 N   D2751 26        03 12 98 Phase shift jumper     position on analog   board  2    NOTES      THE BE1 87T MUST USE THE SAME PHASE COMPENSATION JUMPER  POSITION ON ALL INPUTS     Figure 4 31b  Three Phase Connections  Wye Wye or Autotransformer Configuration  Internal Phase  Compensation    9171300990 Rev R BE1 87T Installation 4 31                                                                                                                                              X  C  x    B  X               P        H          3     2              H  B Y  B   lt      H Y  A 1 d 1   A        MN  TR         5  Switch    board   in  terminal dis ji  blocks      I L  14 12  11 13 2 5  6  7 18 15 16 17  Lo w BE1 87T       J        lt       A  A2 WYE A2       D2751 27 vsd  09 07 00          A    Figure 4 32  Three Phase Connections  Autotransformer With Loaded Delta Tertiary    The transformer in the example shown in Figure 4 32 has a delta connection on the tertiary winding  The  currents in each winding of the delta are A  B  and C respectively as reflected from the wye or auto  connected winding  The delta connection of the transformer windings causes the current flowing in the  phase leads connected to the delta winding to be A B  B C and C A respectively  The CT currents on the  wye or auto windings must be combined similarly to provide A B  B C and C A to compensat
23.  05 28 02                   Inches  Millimeters     Figure 4 1  Outline Dimensions  Front View    BE1 87T Installation    9171300990 Rev R    5 56   141 3                 5 56   141 3                 00000  00000     20    Oh  GO e  eO   2 9       e                                 000000  00000      20       9171300990 Rev R    PROJECTION MOUNTING    SEMI   FLUSH MOUNTING    Inches  Millimeters     Figure 4 2  Outline Dimensions  Rear View    BE1 87T Installation 4 3       22  S lt            A 2            EN          Inches  Millimeters     Figure 4 3  Outline Dimensions  Side View  Semi Flush Mounting     4 4 BE1 87T Installation 9171300990 Rev R          9171300990 Rev R                   Inches  Millimeters     Figure 4 4  Panel Drilling Diagram  Semi Flush Mounting     BE1 87T Installation    4 5                   l          N      I       Inches  Millimeters     Figure 4 5  Outline Dimensions  Side View  Projection Mounting     4 6 BE1 87T Installation 9171300990 Rev R    7 41   188 1     6 20   157 6        D1427 12 a   NOTES  01 16 98   N OPTIONAL RECTANGULAR CUTOUT MAY REPLACE 10 DRILLED HOLES     2  TERMINAL NUMBERS SHOWN ARE AS VIEWED FROM REAR OF RELAY     3  BOTTOM HALF OF PANEL DRILLING DIAGRAM  FROM CENTERLINE    DOWN  IS SHOWN IN FIGURE 4 6b   Inches  Millimeters     Figure 4 6a  Panel Drilling Diagram Top Half  Projection Mounting     9171300990 Rev R BE1 87T Installation 4 7                                                                                    
24.  55 pu  Tap    2 55   3 8       9 69 A   6    100 mA    5 6 BE1 87T Test Procedures 9171300990 Rev R    I2trip    1  0 15  x 6 x       9 69 A    Using Equation 3a     NOTE    The relay operates on maximum restraint  By reducing the current of one input  the  published trip non trip regions are as defined by Figure 1 2           TEST SETUP DIAGRAMS    Refer to the appropriate test setup diagram under    Related Topics        Figure 5 2  Test Setup  Single Phase    Figure 5 3  Test Setup  Three Phase  Sensing Input Type E  Output Option E    9171300990 Rev R BE1 87T Test Procedures    5 7    Figure 5 4  Test Setup  Three Phase  Sensing Input Type E  Output Option F    Figure 5 5  Test Setup  Three Phase  Sensing Input Type G  Output Option E    5 8 BE1 87T Test Procedures 9171300990 Rev R       VERIFICATION TESTS  5 AMP CT  50 OR 60 HZ UNITS          CAUTION    Current supplied to the BE1 87T input terminals must not exceed 20 A continuous or 250  A for 1 second  Whenever 20 A must be exceeded  provisions must be made to cut off  the sensing current automatically after a suitable time interval  Sensing current can be  calculated by using the following equation     K  IE  Jr    Where  K   250 or 50 x tap  whichever is less  t  the time  in seconds  that the current flows       Restrained Pickup Verification    Step 1     Step 2     Step 3     Step 4     Connect the relay as appropriate  refer to Figures 5 2 through 5 5  beginning with input  terminals 11 and 13 for the initial t
25.  B C and C A respectively  The CT  currents on the wye side must be combined similarly to provide A B  B C and C A to compensate  This is  done in Figure 4 28a by connecting the wye side CTs in delta such that the currents sent to the relay are  A B  B C and C A  This is shown in Figure 4 28b by selecting phase compensation jumper position A2 for  the wye side input     4 26 BE1 87T Installation 9171300990 Rev R             ALA             V ALA          Switch  board  terminal  blocks          CAAK                                                                                     D2751 21  03 12 98             Phase shift jumper        position on analog  board  2      An alternative to grounding one corner of the delta  connected CTs is to connect the ground to a lead  connected to terminal 18     Figure 4 28a  Three Phase Connections  Delta Wye Configuration  CT Compensation              Y VY                      V NP WP NP    CYN YN          Switch  board  terminal  blocks       CYN YA                                                                 18       17          16          15          13          14       12          11       02751 22  02 05 98          Phase shift jumper        position on analog  board  2     Figure 4 28b  Three Phase Connections  Delta Wye Configuration  Internal Phase Compensation    9171300990 Rev R    BE1 87T Installation    4 27                                                                                                                 
26.  Hz Units  Range 3   One Ampere CT  60 Hz Units  Range 4  and One Ampere CT  50 Hz Units  Range 2     Within each group are separate tests that can be performed individually to make it easier to focus on a  particular problem  However  all of these tests should be performed prior to putting the relay into service     To help field users understand the verification procedures  four examples for restrained pickup testing are  provided before the actual Verification Tests begin  Two examples are for increasing one input from  balance and two examples are for decreasing one input from balance  These examples are not a  necessary part of verification testing  but are provided for clarification     For routine assurance that the BE1 87T is operating correctly  the simplified OPERATIONAL TESTS may  be performed     Before starting a test program  check the Style Number of the relay against the Style Number  Identification Chart  Figure 1 1  to identify the specific features and options to be tested  For location of  the switches and controls  refer to Figures 2 1 and 2 2 for Input Range 1 or 3  and Figures 2 3 and 2 4 for  Input Range 2 or 4     NOTE    LEDs and targets  if provided  should be checked for proper operation and targets reset  after they have been tripped  Current operated  Type D  targets will only operate when a  minimum of 0 2 A is present in the trip circuit     Similarly  the auxiliary contacts  if present  should be checked for proper operation   Switches S1 and 
27.  NC  OR SPDT    BE1 87T    D240 008  4 21 94    Figure 4 15  Control Circuits  Single Phase  Output Option E    9171300990 Rev R BE1 87T Installation 4 15          87T  19 POWER                   TARGET SUPPLY   OPTIONAL  A             STATUS           720  87T  RESTRAINED LEGEND   87T 87T TRANSFORMER DIFFERENTIAL  RELAY    86 LOCKOUT RELAY      N OPTIONAL CURRENT  OPERATED  TARGETS   AUXILIARY OUTPUT OPTION FOR   SINGLE PHASE  NO  NC  OR SPDT    BE1 87T  D240 015  4 21 94    Figure 4 16  Control Circuits  Three Phase  Two Input  Sensing Input E   Output Option E               87T    877  9  TARGET o 877  TARGET 19   OPTIONAL  A  OPTIONAL                STATUS  87T 87T 87T 87T 6 877  RESTRAINED 7 RESTRAINED  T RESTRAINED  T UNRESTRAINED  20  PHASE A PHASE B PHASE C  87T  1 2 8 10  LEGEND  87T  87T TRANSFORMER POWER  DIFFERENTIAL RELAY  86 LOCKOUT RELAY 87T BE1 87T     3       OPTIONAL CURRENT  9  OPERATED LT   TARGETS    Figure 4 17  Control Circuits  Three Phase  Two Input  Sensing Input E   Output Option F    4 16 BE1 87T Installation 9171300990 Rev R                              Figure 4 18  Control Circuits  Three Phase  Three Input  Sensing Input      Output E                RELAY DISASSEMBLY    Precautions    The following procedures require the removal and handling of the internal printed circuit boards  Figure 4   19 shows the location of major components and assemblies  Because some of the components are  vulnerable to electrostatic charge  the following precautions 
28.  O  O   C OPR O    O   aja    4  5  5    ajo             Input 1  Tap   2 0   Input 2  Tap   3 8 Increasing Input 1   Decreasing Input 2    1 2 3 2 28 3 2 667   0 180 1 026   0 082          Input  or Tap  Switch Verification  Each input is scaled using a combination of two rotary switches  Verify the switches as follows     Step 1     Step 2     Step 3     Determine the Sensing Input Type  the first digit of the Style Number shown on the front panel    Single phase  two inputs   Single phase  three inputs   Single phase  four inputs   Single phase  five inputs   Three phase  two inputs each phase   G Three phase  three inputs each phase                      Connect the input being tested to the current source as shown      the appropriate diagram   Figures 5 2 through 5 5     Set the INPUT under test to the 0 78 tap position as shown in Table 5 6  Set the RESTRAINED  PICKUP LEVEL switch to position A  15    Apply current to the input under test  increasing  the current until the REST  TRIP LED lights  At this point  the input current should be 0 273 A     6   20 mA     9171300990 Rev R BE1 87T Test Procedures 5 15    Step 4  Repeat Step 3 for the additional tap positions shown in Table 5 6  This verifies the accuracy of  all the binary combinations of the rotary switches     Step 5  Test the other inputs by reconnecting to the next pair of terminals for your relay and repeating  Steps 3 and 4   The successful completion of these tests will verify the electrical integrity of a
29.  and 16     e Page A 2  changed 3 Phase fault ratio current to 3 phase fault  current     e Page A 3  corrected formulas for Figure A 3     e Under Section 4  Procedure One  Verify CT Performance  changed  the procedure to the ANSI accuracy class method  This forced  changes in the following steps  12  13  14  16  18  20  and 21     e Under Section 4  Procedure Two  Verify CT Performance  changed  the procedure to the ANSI accuracy class method  This forced  changes in the following steps  12  13  14  and 16     e Added ECO revision information to Table 8 1      Added Setting Note 7  ANSI Accuracy Class Method  to Appendix A     L  05 97 e      delete the part number from the front cover of the manual                 9171300990 Rev R BE1 87T Introduction iii    Manual  Revision and Date    Change       K  03 97    Deleted all references to Service Manual 9171300620     Changed the Title of Section 2 from    Controls and Indicators    to     Human Machine Interface        Replaced the Power Supply Options paragraphs with a new Power  Supply paragraph explaining the new power supply design     Deleted Figure 3 2 and added Table 3 1  Wide Range Power Supply  Voltage Ranges     Changed Power Supply Status Output for Type G power supply on  the formerly page 3 6  now page 3 4  from terminals 9 and 20 to  terminals 9 and 19     Added information to Section 4 to help the user understand the  procedures better     Deleted all NOTES FOR USERS OF SENSING INPUT TYPE F  RELAYS and added 
30.  desired pickup   LEVEL Switches setting for all phases of the unrestrained output  The  adjustment range is from 6 to 21 times the phase tap  setting  in increments of 1     CALIBRATE Switch A two position switch is located on each Analog  1    three phase units ONLY  Board and is easily accessible on the right side of the  relay when it is withdrawn from the case  In the  CALIBRATE position  these switches inhibit the  harmonic share feature when calibrating the 2nd  Harmonic Restraint  In the NORMAL position  the relay  will operate normally           30   Phase Shift Jumpers These jumpers control the internal phase shift of the    POWER Indicator This LED will illuminate when operating power is  supplied to the internal circuitry of the relay     9171300990 Rev R BE1 87T Controls and Indicators 2 1    PUSH TO ENERGIZE Two momentary pushbutton switches are accessible by   OUTPUT Switches Option inserting a 1 8 inch diameter non conducting rod  through access holes in the front panel  Switch R   when actuated  closes the Restrained Output Relay  contacts  Switch U  when actuated  closes the  Unrestrained Output Relay contact s      NOTE  The optional Auxiliary Relay contacts   Option 3 1  3 2 or 3 5  will also be  operated by the PUSH TO ENERGIZE  switches if enabled by the two internal  Auxiliary Relay Control Switches    Refer to LETTER         FUNCTION Targets Option Electronically latched LED targets that indicate an  unrestrained or restrained output has occurred      
31.  es at uta Fate tke pasasqa             4 50  FEST Ju cp EET ER 4 50  SECTION 5 e TEST PROCEDURES                      irre neri teer ined dn u    u    u                                      5 1  OVERVIEW mL 5 1  EQUIPMENT  REQUIRED aieiaa iei ave      dei duse tg                            5 1  MUNERE 5 1  RESTRAINED PICKUP TESTING EXAMPLES                sess a    5 2  Increasing One Input from                                  1  00 L nennen nnns nennen nnns 5 2  Decreasing One Input from                  2       2 4  0     0000000                 eene enne 5 5  TEST  SETUP BIAGRAMS         tuii diee id ae        av ee            Ma dc d n deg ut 5 7  VERIFICATION TESTS  5 AMP CT  50 OR 60 HZ UNITS                     entren 5 9  Restrained Pickup Level Verification                             ua    5 9  Input  or Tap  Switch                            I n n                   5 10  Unrestrained Pickup Verification                          U    U    5 11  Second Harmonic Restraint Verification                                                           5 11  Fifth Harmonic Restraint                                              5 12  Response  Time  VerificatlOni                                     e P tee e e               5 13  VERIFICATION TESTS  1        CT  50 OR 60 HZ       5            5 14  Restrained Pickup Level Verification                                   a    5 14  Input  or Tap  Switch Verification                                                             nnne 
32.  ignored in fault current calculations        Procedure One    Refer to Figure 4 33 for a one line drawing of this example  Refer to Figure 4 32 for the three line  representation of this transformer     Tap and Phase Shift Settings    Step 1  Determine the primary current   p  of each winding         MVA rating of transformer   X 1 000      V LINE   LINE   amp 3      Use the MVA rating of the highest rated winding for all the other windings when making the  calculations   This procedure assures that the taps follow the voltage ratios  Refer to Appendix  A  Setting Note 1      Ip          HIGH TERTIARY LOW   _ 250 000    _ 250 000     _ 250 000   P   34543 P 432 3 P   138 3  Ip  418 Ip  10 935 Ip  1 046    Step 2  Determine the CT secondary current   s of each winding           Ip  Is       CT ratio   HIGH TERTIARY LOW  418 10 935 1046  Is Em Ill Is   Is ea   120 600 240   Is 2349 Is   18 22 1  4 36   9171300990 Rev    BE1 87T Installation 4 33    Table 4 1  List of Variables    The driving input number  a procedural term designating the current input  terminal whose tap is the first selected   The setting procedure is simplified if  the driving input is the input of least current  1       Maximum external fault current in multiples of tap  the larger of three phase or  line ground values     Driving input relay current used for matching in amperes  The larger of 7r  and Irc    Relay input current at the maximum external three phase fault level in  secondary amperes    Relay 
33.  pu    9171300990 Rev R BE1 87T Test Procedures 5 3    In terms of current  the trip current is               1 35 pu x tap       1 35  2 0    2 70A   6    100mA    3 8  Using Equation 2a            38 a 035            2 7 A  Example Two   Assume   tap     2  tap2   3 8  slope   15   h 6  Inputs       6A  3 pu   4                     2  2 114    114    3 pu 2 04     i         m 38 P  Check   0 35    T balance  lt   gt  C lope        100  slope  1 zw             100    3  lt   gt  0 35  0 15       0 15   3  gt  1 983    Therefore  Use Equation 1 or 1a   From Figure 1 2  the percentage restraint characteristic of the BE1 87T at 15  slope   the minimum  current where trip occurs is   l tri     P 1 0 15    3 53 pu  In terms of current  the trip current is   I  trip   3 53 pu x tap   3 53   2 0     7 06 A   6    100 mA       114 2  x    1 015 38    7 06 A               min      Using Equation 1a     5 4 BE1 87T Test Procedures 9171300990 Rev R    Decreasing One Input from Balance    The formula to determine the unbalance value at which the restrained trip occurs is     slope       unbalance  gt   maximum restraint     or 0 35 pu  whichever is greater  Where   unbalance   absolute value of J    I in per unit  pu   slope   the RESTRAINED PICKUP LEVEL setting  15 to 60     maximum restraint   larger of T  or L  in pu  I     By decreasing the     input current from balance     T2  The balance current is 7      1 x      1             1  When   0 35    1 0 35  I 2balance  gt   gt       
34.  restraint   larger of 7  or L  in pu i e      or      T   T2    unbalance   absolute value of  I    I   in per unit  pu  i e           Ti  By increasing the I  input current from balance   The balance current is  1 I2 x     Amps                T2  1  When   0 35 I2 0 35                 gt       R      gt                  R  in pu    sere T2  seve  100 100  ie  seve 1   seve  100 100    This means the pu restraint current is to the right of the intersection of the slope characteristic with the  0 35 MPU horizontal line  see Figure 1 2      5 2 BE1 87T Test Procedures 9171300990 Rev R    the minimum trip point is established as     N balance    E y 1n pu  slope RE     Equation 1    100                min         OR       x    in Amps   Equation 1a   2    2  When     0 35    l balance  lt   in pu                 100  slope    100       1    the minimum trip point is established as     Iitrip min   balance   0 35       pu   Equation 2     OR    I  Trip min    2   0 5       Amps   Equation 2a   2    Example One   Assume     tapi   2  tap     3 8  slope   15          2  Inputs       2    1 pu  2 2 1 4     1  1 pu  2 5 P    I     38A  1 pu  2      1 pu     T2 B 38  Check     0 35 i  balance  lt   gt      in pu     slope    100    slope    ae  oo       E oe      0 15    1 0 15   1    1 983  Therefore  Use Equation 2 or 2a     From Figure 1 2  the percentage restraint characteristic of the BE1 87T at 15  slope   the minimum  current where trip occurs is     I trip  1 pu   0 35   1 35
35.  the 0 35 pu or the slope line in Figure 1 2   Calculation examples are found in Section 5         1 75    BE1 87T General Information 1 5    Table 1 1  Multiples of Tap     Front          Seting      20  25                     50       Maximum Restraint 2 33  1 75  1 40  1 17   1 00  0 875  0 778  0 700   636 KA 583  Current At Minimum   Pickup In Multiples of   Tap       Figure 1 2  Percentage Restraint Characteristic    Second Harmonic Restraint Inhibit of the restrained output occurs when the second   harmonic component exceeds a pickup setting  which is  internally adjustable over the range of 8   to 15   of the  operating current for single phase Units or 11 to 27   for  three phase units  The factory setting is 12   for single   phase units and 18   for three phase units     Fifth Harmonic Restraint Inhibit of the restrained output occurs when the fifth harmonic  component exceeds a pickup setting which has an internally  adjustable range of 25 to 45   of the operating current  The  factory setting is 35       Unrestrained Output    Pickup Range Front panel thumbwheel switches adjust the pickup point of  the unrestrained output over a range of 6 to 21 times the tap  setting in increments of 1 x Tap     Pickup Accuracy  3   of the front panel setting     1 6 BE1 87T General Information 9171300990 Rev R    Outputs Output contacts are rated as follows     Resistive   120 240 Vac Make 30 A for 0 2 seconds  carry 7 A continuously and break  7 A    250 Vdc Make and carry 30 
36.  this  example  as shown in Figure 4 35  the high side and low side zero sequence currents must be  canceled  Because the CTs are connected in wye and the high side currents lead the low side  currents by 30    select the A2 position  This connection advances the low side phasors by 30    to match the phasors from the high side     HIGH LOW  Jumper Position  WYE A2    On single phase units  the zero sequence currents must be canceled by connecting the low  side CTs in delta     Step 4  Determine the relay current  lp               x Conversion Factor    Three Phase Units Only  When using either  1 or A2 jumper positions  shown in Figure 2 4   multiply the secondary current 7  by the conversion factor  square root of three  just as if the  CTs were connected in delta  If the system CTs are connected in delta  either three phase or  single phase units   the same square root of three conversion factor must be applied     HIGH LOW  In    2 79   1  Ig   57943  IR   2 79 Ig   10 02    Step 5  Determine the spread ratio of the relay currents  largest smallest  which must be less than the  4 45 capability of the BE1 87T     Spread   10 02 2 79   3 59  If the spread exceeds 4 45  consider changing CT ratios or use auxiliary CTs     Step 6  Determine the Driving Input  DP  which we define as the input assigned to the smallest current  in Step 4     DP ly  DP HIGH  INPUT 1     9171300990 Rev R BE1 87T Installation 4 43    Step 7     Step 8     Step 9     Step 10     Step 11     4 44    
37.  to be changed in the field        SENSING CONNECTION DIAGRAMS    Each connection diagram provides  as an example  typical transformer terminal markings and voltage  diagrams that might be found on a transformer nameplate with the winding interconnections shown  The  designations for high side and low side windings are for illustrative purposes only  For example  a  diagram for a delta wye transformer is applicable to a wye delta transformer if the winding  interconnections are the same  The phase shifts shown in the voltage diagrams assume A B C Phase  sequence  rotation      Each connection diagram shows the CT circuit safety ground located at the switch board panel terminal  block as recommended in ANSI Standard C57 13 3    Single Phase Input Sensing Connections   Typical single phase input sensing connections are illustrated in Figure 4 22     Single phase units may also be used in three phase configurations  one on each phase  Figure 4 23  through Figure 4 26 show several typical three phase sensing examples using three BE1 87T single   phase relays  Many other configurations are possible     4 20 BE1 87T Installation 9171300990 Rev R               BE1 87T BREAKER  Sn BREAKER     ne     Y    INPUT 5                                                                                                                           INPUT 4 OPTIONAL  INPUTS  INPUT 3  INPUT 2  INPUT  87T  Figure 4 22  Typical Single Phase Sensing Connections  c HOA z naam 26      c     CY H      X  ee 
38.  together  as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The C   phase differential circuit sees no current and does not respond    Step 2  Connect Input 1 current to terminals A and C   Connect Input 2 current to terminals A and C   This verifies the A  and C phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The B   phase differential circuit sees no current and does not respond    Step 3  Connect Input 1 current to terminals B and C   Connect Input 2 current to terminals B and C   This verifies the B  and C phase differential circuits which respond together  as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The A     phase differential circuit sees no current and does not respond     Jumper Positions WYE A1   Step 1  Connect Input 1 current to terminals A and B   Connect Input 2 current to terminals A and N   This verifies the A  and B phase differential circuits which respond together  as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The C   phase differential circuit sees no current and does not respond     Step 2  Connect Input 1 current to terminals A and C     Connect Input 2 current to terminals N and C     9171300990 Rev R BE1 87T Test Procedures 5 21    Step 3     This verifies the A  and C 
39. 0     1 9  I    453  704 210    120  240   I    43  704 90    120  120   I    43  704 330    1 0 1 43  20  210    170  240   I 43  0  90    1704 120   I 43  20   330    1 0 1    3  40  150    140  240   I    V3  20  30    1 0   120   1    V3  70  270         1  Table 4 4 is for reference only and applies to three phase units with Input    at zero amperes     2      For A B C rotation        MAINTENANCE    BE1 87T relays require no preventative maintenance other than a periodic operational check  If the relay  fails to function properly  contact Technical Sales Support at Basler Electric to coordinate repairs        STORAGE    This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in  excess of 10 years at storage temperatures less than 40 C  104 F   Typically  the life expectancy of a  capacitor is cut in half for every 10  C rise in temperature  Storage life can be extended if  at one year  intervals  power is applied to the relay for a period of 30 minutes        TEST PLUG    Test plugs  Basler p n 10095  provide a quick  easy method of testing relays without removing them from  their case  Test plugs are simply substituted for the connection plugs  This provides access to the  external stud connections as well as to the internal circuitry     4 50    BE1 87T Installation 9171300990 Rev R    Test plugs consist of a black and red phenolic molding with 20 electrically separated contact fingers  connected to 10 coaxial binding po
40. 00990 Rev R BE1 87T Installation 4 29                                          s A      B      B      ae   B  Ae B Pu                                  5               L                            _    1 87         M  y  Switch Hy Xo  OR H  X  BUSHING  AS 16 BA     WE  board APPROPRIATE 18 N  terminal 14 E  blocks TA we  N          13   D2751 25 m  04 16 99 en         Phase shift jumper    position on analog  board  2         WITH UNLOADED TERTIARY     NOTES     A AN ALERNATIVE TO GROUNDING THE CORNER OF THE THE DELTA CONNECTED CTs  IS TO CONNECT THE GROUND TO LEADS CONNECTED TO TERMINALS 13 AND18     A IF THERE IS NOT A DELTA TERTIARY  OR IF THE WYE WINDING IS UNGROUNDED  IT IS  UNNECESSARY TO DELTA SHIFT THE CURRENTS FOR ZERO SEQUENCE BLOCKING     Figure 4 31a  Three Phase Connections  Wye Wye or Autotransformer Configuration  CT Compensation    The Wye Wye or Autotransformer does not require phase shift compensation  However  it is necessary to  Delta compensate the currents to block zero sequence currents being supplied by the transformer bank   This is shown in Figure 4 31a by connecting the CTs in Delta  In Figure 31b  compensation is shown by  internal phase compensation jumper setting     4 30 BE1 87T Installation 9171300990 Rev R                                                                                                                   H           3 X  C   B T H  X            es   H  X  E A      as els                 BE1 87T   L 17 C   Switch E 16      board Ho
41. 11  amp  13  Input 1 for both single phase and three   phase units      Step 2  Set the UNRESTRAINED PICKUP LEVEL switch to position A  6 x TAP   Increase the input  current until the UNREST  TRIP LED lights  disregard the REST  TRIP LED   This should occur    at 12 0 A  3  as indicated in Table 5 3     Step 3  Repeat Step 2 using the other UNRESTRAINED PICKUP LEVEL switch positions given in  Table 5 3     Step 4         Three Phase Units Only  Repeat Steps 1 through 3 for phase B of input 1  terminals 12  amp   13  and Phase C of input 1  terminals 14  amp  13      Table 5 3  Unrestrained Pickup Verification  5 A  50 or 60 Hz          Unrestrained Input 1 Tap Input Current at  Pickup Level Position Pickup  3   A  6 x TAP  12 0A  J  14 x TAP  28 0A  S  21 x TAP  42 0A             Second Harmonic Restraint Verification    Step 1  Set the INPUT 1  tap  switches to the 2 0 A position  Connect the relay as appropriate  refer to  Figures 5 2 through 5 5  using terminals 11  amp  13  Input 1 for both single phase and three   phase units      9171300990 Rev R BE1 87T Test Procedures 5 11    Step 2     Three Phase Units Only  Set the Calibrate toggle switch S2  letter 2 of Figure 2 4  to the  CAL position on each of the three Analog  1 boards  These three toggle switches are readily  accessible on the right side of the relay when withdrawn from the case   It is not necessary to  pull out the circuit boards      NOTE    With two current sources in parallel  apply the fundamental frequ
42. 71300990 Rev R BE1 87T Setting Notes A 9    Figure 5 illustrates how a lower Rs value reduces the difference between SF and SF        SF and SF for Zc 2  ZB 0 5  Rs 0 2    0 4       0 20 40 60 80 100  IF    Figure 5  Reducing the Difference between SF and SF     Conclusion    This analysis shows that the easy to apply SF based on the ANSI Accuracy Class may yield optimistic  results in cases where the CT internal resistance is significant  The Excitation curve method  requiring  more data  yields more accurate results and should be used when the SF is marginal     A 10 BE1 87T Setting Notes 9171300990 Rev R      Basler Electric    ROUTE 143  BOX 269  HIGHLAND  IL 62249 USA  http   www basler com  info basler com  PHONE  1 618 654 2341 FAX  1 618 654 2351    
43. 751 28  02 12 98  Figure A 5  BE1 87T Slope vs       and Ir    D2751 29  02 12 98    Figure A 6  BE1 87T Margin vs      and Ir    9171300990 Rev R BE1 87T Setting Notes          HdO IS    NIDAVIN    SETTING NOTE 6    Inrush vs  Unrestraint Tap    RCH RCL   N             LOAD       D2751 20    87T 02 03 98    Compare the unrestraint pickup setting defined in NOTE 4 to the transformer in rush current           I  The UR tap is set at 70  of IE  the maximum pu through fault current   r         Tx RCH    The worst case 3 Phase fault occurs when the source impedance is negligible       0      1  Then Ir   X  pu at the transformer OA base   T          Fora X7 6         06   167PU    The unrestraint tap MPU would be set for 0 7 x 16 7   117 pu   Note that 11 7 pu value is different from  the relay UR tap setting   The inrush current is generally assumed to be less than 10 times the nominal  transformer current  10 pu on the OA base      For this worst case example  the maximum inrush current is below the UR threshold  For significant  source impedance values  we assume that the inrush current will decrease in proportion to the decrease  in the fault current and thus maintain security with the recommended settings     A 6 BE1 87T Setting Notes 9171300990 Rev R    SETTING NOTE 7    CT Performance Evaluation  Saturation Factor    The secondary current delivered by a current transformer to a relay circuit is always less than the current  available from an ideal CT  The ideal or ratio cu
44. 90 Rev R BE1 87T General Information 1 7    1 8    Figure 1 3  Unrestrained Response Times    Figure 1 4  Restrained Response Times    BE1 87T General Information             9171300990 Rev R    Isolation In accordance with IEC 255 5 and ANSI IEEE C37 90 1989   one minute dielectric  high potential  tests  as follows     All circuits to ground  2121 Vdc  Input to output circuits  1500 Vac or 2121 Vdc  Power Supply Refer to Table 1 3     Table 1 3  Power Supply Specifications    Burden at Burden at  Nominal Input Input Voltage Nominal Nominal  Type Voltage Range  Energized   De energized     J  Mid 125 Vdc 62     150 Vdc 9 0 W 64W  Range  120 Vac 90     132 Vac 21 0 VAx 19 8 VA   K  Mid 48 Vdc 24   60 Vdc 85W 62W  me        22 48        24   60        8 5 W     2W  5  250        140     280        9 5W 6 4W      At 55   65 Hz        T Type L power supply may require 14 Vdc to begin operation  Once  operating  the voltage may be reduced to 12 Vdc     Surge Withstand Capability Qualified to ANSI IEEE C37 90 1 1989  Standard Surge  Withstand Capability  SWC  Tests for Protective Relays and  Relay Systems  and IEC 255 5 Impulse Test and Dielectric  Test     Radio Frequency Interference     Maintains proper operation when tested in accordance with    RFI  IEEE C37 90 2 1987  Trial Use Standard Withstand  Capability of Relay Systems to Radiated Electromagnetic  Interference from Transceivers     UL Recognition UL Recognized per Standard 508  UL File No  E97033  Note   Output contact
45. A for 0 2 seconds  carry 7 A continuously  and break 0 3 A    500 Vdc Make and carry 15 A for 0 2 seconds  carry 7 A continuously  and break 0 1 A    Inductive    120 240 Vac  125 250        Make and carry 30 A for 0 2 seconds  carry 7 A continuously  and break 0 3 A   L R   0 04      Target Indicators Target indicators may be either internally operated or current   operated  operated by a minimum of 0 2 A through the output  trip circuit   When the target is current operated  the  associated output circuit must be limited to 30 A for 0 2  seconds  7 A for 2 minutes and 3 A continuously     Single Phase Units Either an internally operated or a current operated target is  supplied  as selected by the Style Number  for each trip  output  i e   the restrained and the unrestrained functions      Three Phase Units Either internally operated or current operated targets  as  selected  indicate the function  restrained or unrestrained   that caused the trip  and the tripped phase  A  B  C      Harmonic Attenuation Refer to Table 1 2     Table 1 2  Harmonic Attenuation    Parameter Minimum Attenuation at Indicated Fundamental   50 Or 60 Hz Models     50 60 Hz   100 120   2  150 180 Hz  250 300 Hz  Through Current 12 dB    2nd Harmonic Restraint   12 dB   m5 12 dB 12 dB 12 dB  5th Harmonic Restraint 12 dB 12 dB 12 dB   s  12 dB    Timing Refer to Figure 1 3 for Unrestrained Response Times and   For 60 Hz units only  Figure 1 4 for Restrained Response Times     ET  KI   e       91713009
46. B  qe    Hea        2        5 X      SWITCH BOARD  amp  TENE     5 5 5  TERMINAL BLOCKS  BE1 87T 1      e  13 Coy  2 12   y  BE1 87T 2  i EN 12  111   BE1 87T 3  13    W 2  12  11 17                             H  X  D1186 02  H  H   A          Figure 4 23  Single Phase Connections  Delta Wye Configuration  9171300990 Rev R BE1 87T Installation 4 21                                                       c He                   H X      o5                            A Heer                        9       Ho e o  X      SWITCH BOARD  TERMINAL BLOCKS    4 22                               BE1 87T 1    13 12    o    2  11   4        1 87   2  2   12                      13            1111    BE1 87T 3  13     2  12    11 1      H  X     D1186 20 vsd       p p p    Figure 4 24  Single Phase Connections  Wye Wye Configuration                                           BE1 87T Installation 9171300990 Rev R                                                                                                                   SWICH BOARD     TERMINAL BLOCKS       BE1 87T 1    c  1   11  12 e rV                                                                                                          Figure 4 25  Single Phase Connections  Delta Delta Wye Configuration    9171300990 Rev R BE1 87T Installation 4 23                                                                                                                                                                                            
47. BE1 87T Introduction i    First Printing  June 1990  Printed in USA     1990 1997  1999 2000  2003  2005  2007 Basler Electric  Highland Illinois 62249 USA  All Rights Reserved    September 2007       CONFIDENTIAL INFORMATION    of Basler Electric  Highland Illinois  USA  It is loaned for confidential use  subject  to return on request  and with the mutual understanding that it will not be used in  any manner detrimental to the interest of Basler Electric              It is not the intention of this manual to cover all details and variations in equipment  nor does this manual  provide data for every possible contingency regarding installation or operation  The availability and design  of all features and options are subject to modification without notice  Should further information be    required  contact Basler Electric     BASLER ELECTRIC  ROUTE 143  BOX 269  HIGHLAND IL 62249 USA  http   www basler com  info basler com  PHONE  1 618 654 2341 FAX  1 618 654 2351    ii BE1 87T Introduction 9171300990 Rev R       REVISION HISTORY       The following information provides a historical summary of the changes made to the BE1 87T instruction  manual  9171300990   Revisions are listed in reverse chronological order           Manual  Revision and Date Change   R  09 07 e Replaced magnetic type targets with electronic type targets   e Updated power supply burden data and output contact ratings   e Updated front panel illustrations to show laser graphics   e Moved content of Section 6
48. Determine the Driving Input Tap  T      If both relay currents are between 2 0 and 8 9 amperes  the tap settings can be set equal to the  relay currents  to the nearest 0 1 ampere   However  choosing the 2 0 tap setting for the  minimum input will yield maximum sensitivity           2 00  Determine the desired Tap        for Input 2     I  Tp  2      qm    10 02  0           7 18    Select taps by rounding Tp to the nearest tenth   T    2 0  To   7 2    Determine the CT mismatch                     My  100 Current Ratio   Tap Ratio  the smaller of the above  Fri fi  Ig  T     100 Smaller  2 79 20  10 02 7 2 2  ET  _ 100278 0 2778   Smaller   02778           0216 or 0 22 96    Determine the total mismatch  M 7     Mrz My  LTC  Add the maximum CT mismatch My  based on the power transformer in the neutral tap  position  to the total permissible tap excursion from neutral  In this example  a  10   load tap    change  LTC  must be accommodated  Therefore          0 22   10   10 22     BE1 87T Installation 9171300990 Rev R    Verify CT Performance       NOTE  This procedure uses the ANSI accuracy class method  See Appendix A  Setting Note 7  for more information              Step 12  Determine the maximum CT secondary fault current for external faults at F        for three phase          lrg for single phase   Refer again to Figure 4 35 for this example     HIGH LOW  1916 10603            69          160   32A  66A  1171 11231  TFG   90 IFG   T60  2195    70A    Step 13  Determine 
49. ERATING PRECAUTIONS on page 4 1 and RELAY DISASSEMBLY  Precautions on page 4 11     Step 1     Step 2        Insert the cradle assembly into the relay case  then     Three Phase Units with Sensing Input Type G  Remove the lower connection plug first   Then remove the upper connection plug  Insert two Test Plugs  P N 10095 or equivalent  in  place of the top and bottom connection plugs  For further information  refer to TEST PLUG in  Section 6  MAINTENANCE  Terminal 20  trip output common  shown in Figure 4 10  must be  isolated for this test     All other styles  Replace the top connection plug with a Test Plug  P N 10095 or equivalent    For further information  refer to TEST PLUG in Section 6  MAINTENANCE  Terminal 9  trip  output common  shown in Figures 4 7 through 4 9 must be isolated for this test     Using an ammeter and phase angle meter  measure the magnitude and phase angle of each  current input  testing two inputs at a time  Begin with Inputs 1 and 2        CAUTION    When more than two inputs are present  all inputs not being tested must be shorted to       Step 3     ground     Single Phase Units  Relay must not trip when the current to each input  of the pair being  tested  is equal to the other in magnitude and the two currents are 180   out of phase  e g    Inputs 1 and 2 measured  with Inputs 3  4 and 5 shorted   For input terminal numbers  see  Table 4 3     Three Phase Units  Relay must not trip when the current to Input 1 is equal to that of Input 2 in  m
50. INSTRUCTION MANUAL  FOR    TRANSFORMER DIFFERENTIAL RELAY  BE1 87T         Basler Electric    INPUT 1 INPUT 2 INPUT 3 INPUT 4  5 0 8 0   5 0 8 0   5 0 8 0   5 0 8 0            UNRESTRAINED PICKUP LEVEL       RESTRAINED PICKUP LEVEL   OF TRIP    RU   ws ull    oo        00000009     TRIP ACTIVE          K    r  THRU current  15  20  25          3s   4o   as   so            BE1 87T P  TRANSFORMER DIFFERENTIAL Q  TAM Style No  D2E A1J 0150   POWER   Serial No  XXXXXXXXXXXX      99   OO           FUNCTION                                U S  PATENT 5 014 153  PATENTED IN CANADA  1993          P0052 22         Basler Electric    Publication  9171300990  Revision  R 09 07    INTRODUCTION       This instruction manual provides information about the operation and installation of the BE1 87T  Transformer Differential relay  To accomplish this  the following information is provided     e General Information and Specifications     Controls and Indicators   e Functional Description   e Installation   e Test Procedures       WARNING     To avoid personal injury or equipment damage  only qualified personnel should  perform the procedures in this manual           NOTE    Be sure that the relay is hard wired to earth ground with no smaller than 12 AWG  copper wire attached to the ground terminal on the rear of the unit case  When  the relay is configured in a system with other devices  it is recommended to use a  separate lead to the ground bus from each unit                 9171300990 Rev R 
51. OL ay EIER 1 9  Operating Temperature                  sssssssssssesseeeeeeene eene nnne nnn nisi nnns innen rens nnn sn nene nanna 1 10  Storage  Temperatures                                        orae                           de dca dt va de                1 10  ep  1 10  CaSe ipa PEERS 1 10   SECTION 2 e CONTROLS AND INDICATORS                     2                            inna sa          u    u    u                2 1  LOCATION OF CONTROLS AND INDICATORS                   sse ener nnne ns 2 1   SECTION    e FUNCTIONAL                                                                         3 1  GENERAL  SS T 3 1                         Wes 3 1   Current TransfOFm  ls     iiec ice                        n eee Ere                    3 1  snot 3 1                   PES 3 1  30  Internal Phase Shift  Three Phase Relays                     3 1  Restrained Trip Output                                                      sentent nnns Hua aa sia aa as 3 3  Unrestrained          OUtP  t  q  u u sua aus                            aa aa tren tenens 3 3  Auxiliary Relay OPton NP  3 4  geo 3 4  Power Supply Status Output  Optional                                                                    3 4               Indicators                                                                       3 4    OF TD                                         Tapa n                                   3 5       9171300990 Rev R BE1 87T Introduction vii    GENERAL                                 
52. S2  located on the mother board and shown in Figure 2 4 allow the  auxiliary output to operate in conjunction with a restrained trip  an unrestrained trip  or  both           EQUIPMENT REQUIRED    The following test equipment  or equivalent  is required for either the Operational Tests or the  Verification Tests     1  Two current sources with independently regulated current outputs  Must be able to produce  outputs 180  out of phase  If harmonic testing is desired  harmonic capability is also required     Counter  0 to 0 5 second range    Two Test Plugs  Basler p n 10095  see Test Plug in Section 4  Installation     Extender Card  Basler p n 9165500100  as shown in Figure 5 1    Phase angle meter or oscilloscope with an ungrounded plug or ground isolation transformer     oF ON    9171300990 Rev R BE1 87T Test Procedures 5 1    CAUTION    If an oscilloscope or meter is to be connected to the internal relay circuitry  it must be  isolated from ground  The internal circuits are not grounded to the case or isolated from  the power inputs source        BE1 87T  D439 001  1 81 94             Figure 5 1  Illustrating Use of Extender Board       RESTRAINED PICKUP TESTING EXAMPLES    Increasing One Input from Balance  The formula to determine the unbalance value at which the restrained trip occurs is   sl  unbalance  gt  ET  maximum restraint     or 0 35 pu  whichever is greater  Where     I2    T   T2    slope   the RESTRAINED PICKUP LEVEL setting  15 to 60             1 I2  maximum
53. Section 7  Difference Data     Changed previous Section 7  Manual Change Information  to Section    Added an Appendix A to clarify the setting procedures   Added an index to help the user find information easier   Changed the format of the manual        J  01 96    Deleted    Difference Data     formerly Section 7  and included notes for  users of Type F relays     Moved all information regarding relay settings and checking relay  setting from Section 5  Testing and Setting  to Section 4  Installation   Section 5 now contains information on test procedures    Combined 50 and 60 Hz Verification Tests    Various editorial changes    Reformatted instruction manual as Windows Help file for electronic  documentation        1  01 95    Added outline  box  to Figure 5 8 to highlight the figure     Page 5 42  Step 5  changed     should be less than 4 45    to     must be  less than 4 45        Added note to page 5 43  Step 10 and corrected the formula in Step  10     Page 5 45  Step 18  corrected formula and high side results  and  Step 19  changed last sentence from H  13 x tap  to S  21 x tap      Page 5 46  Steps 20 and 21  corrected figure references        H  12 94    Page 1 6  changed Specification for Restrained Output  Pickup  Accuracy    Changed Section 5  Testing and Setting  Verification Tests  all  models   Steps 1  4  5  and 8  and Table 5 4    Page 5 50  Jumper Positions Wye Delta 1  Step 3  Corrected Input 2  terminal identifications    Page 5 51  Jumper Positions Delt
54. U S  PATENT 5 014 153  PATENTED IN CANADA  1993    Figure 2 3  Sensing Input Range 2 or 4 Three Phase  Two Inputs    BE1 87T Controls and Indicators    9171300990 Rev R    LH EDGE OF ANALOG  2   BOARD  THE 4TH BOARD   DOWN  COUNTING THE   der ues BOARD   BE1 87T         VR2  Ll  TP 12V         P0052 26    SECTION OF THE  VERTICAL      lt  MOTHER BOARD AT LEFT  j REAR OF RELAY    Figure 2 4  Controls Mounted Inside the Relay    9171300990 Rev R BE1 87T Controls and Indicators 2 7    2 8    Ede              P0052 27    ES Basler Electric    INPUT 1 INPUT 2 INPUT 3 INPUT 4 INPUT 5  5 0 8 0 5 0 8 0      semNG    A s c p  e r e na     x c w wu pe n s    xme      7               1  12  13   14  5  t6  17  18  v9  20  24      UNRESTRAINED PICKUP LEVEL         OF TRIP             BE1 87T x  TRANSFORMER DIFFERENTIAL Q  FAX Style No  D3E A1J D1S0F POWER    Serial No  XXXXXXXXXXXX    PUSH TO  ENERGIZE  OUTPUT  O       L Function                            U S  PATENT 5 014 153  PATENTED IN CANADA  1993          BE1 87T Controls and Indicators    Figure 2 5  Sensing Input Range 2 or 4  Option 1 1  Single Phase  Five Inputs    OF TRIP Option    9171300990 Rev R    SECTION 3   FUNCTIONAL DESCRIPTION       GENERAL    BE1 87T relays are solid state devices that protect transformers by providing output contact closure when  the scaled current into the protected transformer does not equal the scaled current out  within defined  limits  These relays are harmonically restrained to prevent trippi
55. VEL setting  slope  to S 60      9171300990 Rev R BE1 87T Installation 4 41    Procedure Two  Refer to Figure 4 35 for a one line drawing of this example     Data    12 20MVA    2 2  100       69      gt     1247      600 5MR         1200 5MR  zs    300 5T    LOAD       800 5T  1171  19     11 231  19   x1 O LTC D1873 21  Z  5  12MVA 0371598    Figure 4 35  Two Winding Transformer Relay Setting Calculation Example    SPECIFICATIONS    CT Ratio   CT Tap   CT Accuracy Class  CT Resistance  ohms     One Way Lead Burden   ohms     XFMR Connection   CT Connection    Input      Fault Current  Three   Phase     Fault Current  Single   Phase          Standard connection  High voltage leads low voltage by 30     Tap and Phase Shift Settings    Step 1  Determine the full load primary current  lp  of each winding     u  MVA ratingof transformer   x 1 000    VLINE   LINE    V3         Ip    Use the top kVA rating of the transformer when making the calculations           HIGH LOW      20 000 r  20000  P   SN P   12 413  Ip   167 35 Ip   925 98    4 42 BE1 87T Installation 9171300990 Rev R    Step 2  Determine the CT secondary current  16               Ip  Ts      CT ratio  HIGH LOW     167 35 I  925 98  S  60 S  160  Is  2 79 1   5 79    Step 3                        Units Only  Adjust the phase compensation jumpers on Analog Board  2   shown in Figure 2 4  or use the procedure listed in TESTING THREE PHASE UNITS  WITHOUT CHANGING JUMPERS  in Section 5   Because of the grounded winding in
56. a2 Delta2  Step 2  Corrected  verification statement        G  09 94       Changed all sections to reflect new Option 1 1     Added to Section 5 four examples for testing relays to clarify test  procedures     Added to Section 5 one procedure for setting relays   Corrected typographical and illustration errors        BE1 87T Introduction 9171300990 Rev R    Manual  Revision and Date    Change       F  03 93    Changed formula pages 5 4  5 10  5 16  and 5 22 from     the square  root of K over t  to     K over the square root of t        E  01 93    Manual was revised to incorporate a revision in the relay that made  sensing input type F obsolete and included the 1 A  60 hertz and 5 A   50 hertz model relays     Section 5  Test Setup  diagrams were changed to clarify relay  connections    Added three relay Internal Connection diagrams    Changed unrestrained maximum time to trip  reference old Tables 5 4  and 5 8  new Tables 5 4  5 8  5 12  and 5 16     Renamed Section 7  Manual Change Information to Section 8   Manual Change Information and added new Section 7  Difference  Data to support BE1 87T relays with Sensing Input Type F        D  06 92    Manual was revised to include the 1 A  50 Hz model relay and  reformatted to a new Instruction Manual style     Additional connection diagrams were included in Section 4 and test  plug information was added to Section 6     Minor typographical errors were also corrected        C  03 91    Table 5 1 was expanded and Figure 5 4 Test S
57. ach phase   G Three phase  three inputs each phase    moou  r    Step 2  Connect the input being tested to the current source  as shown in the appropriate TEST  SETUP  Figures 5 2 through 5 5     Step 3  Set the input under test to the 3 9 tap position as shown in Table 5 2  Set the RESTRAINED  PICKUP LEVEL switch to position A  1596   Apply current to the input under test  increasing    5 10 BE1 87T Test Procedures 9171300990 Rev R    the current until the REST  TRIP LED lights  At this point  the input current should be 1 36 A   6   100 mA     Step 4  Repeat Step 3 for the additional tap positions shown in Table 5 2  This verifies the accuracy of  all the binary combinations of the rotary switches     Step 5  Test the other inputs by reconnecting to the next pair of terminals for your relay and repeating  Steps 3 and 4   The successful completion of these tests will verify the electrical integrity of all  the tap switches      Table 5 2  Input Verification  5 A  50 or 60 Hz                      Position Input Current Range at Pickup  3 9 1 18 1 55A  4 3 1 31   1 70A  6 4 2 01   2 47     7 8 2 47   2 99               Pickup occurs at 0 35 x Tap  See Figure 1 2   T        setting of the upper and lower INPUT switches of the input being tested    Reference LOCATION OF CONTROLS AND INDICATORS      Unrestrained Pickup Verification    Step 1  Set the INPUT 1  tap  switches to the 2 0 A position  Connect the relay as appropriate  refer to  Figures 5 2 through 5 5  using terminals 
58. agnitude and the phase angle is as shown in Table 4 4  If there are three inputs per phase   interchange Inputs 2 and 3 and repeat the procedure  this time with magnitudes and phase  angles as shown in Table 4 4   Testing may require six synchronized current sources      Using the Test Plug  reestablish all input connections and verify that the front panel REST   TRIP and UNREST  TRIP LEDs are extinguished     This assures that the X TAP settings and jumper settings  refer to Figures 4 20  4 21 and 4 27   are within acceptable parameters and that the differential current is below pickup     If the REST  TRIP or UNREST  TRIP LEDs light  recheck the system current inputs and relay  settings     If actual waveforms  as sensed by the BE1 87T are desired  a procedure using a circuit board  Extender Card shown in Figure 5 1 and an oscilloscope is available     Table 4 3  Single Phase Input Terminals       9171300990 Rev R BE1 87T Installation 4 49    Table 4 4  Input Conditions For Non Trip Three Phase Sensing    30   Phase Shift  Compensation Jumper  Settings     Ref  Figure 4 27     WYE WYE  A1 A1  or A2   A2      In these cases  input  currents are equal and    180  out of phase      Input 1 is   1  Input 2 is  WYE     Input 1 is WYE  Input 2 is  A1     Input 1 is A2  Input 2 is  WYE     Input 1 is WYE  Input 2 is  A2     NOTES     Input 1   Input 2    1 0  180    140  240   170   60   1 04 120   170 4 300      1 0 16 3   0  150    1 0  2407 1 43  704 30    10  120  I 43  704 27
59. ained slope setting  S  is a function of the total mismatch and the  power transformer exciting current  This provides an ample security margin with respect to the  characteristic kneepoint of the BE1 87T  Refer to Figure 4 34     Specifically  if the maximum saturation factor 5   from Step 16  exceeds 0 5  set the  RESTRAINED PICKUP LEVEL to setting K  which is equal to 60 as shown in the table on the  front panel     For all other cases  including this example  use the following equation     ses rn  Where   S   restrained slope setting  Mr   total mismatch in percent         rated self cooled current of the power transformer in multiples of tap    Mris 10 2  from Step 11  and 7  is 0 84  Step 20      35 10 2   3   23   4 0 84     26 596      3     Because the maximum saturation factor S  for this example is less than 0 5  from Step 16   use  the next highest slope  Select position D  which   30      For examples of suitable slope settings  see Table 4 2     BE1 87T Installation 9171300990 Rev R       CHECKING THE RELAY SETTINGS AND SYSTEM INPUTS    Steps 1 and 2 check that the current inputs from the power transformer are correct and consistent with  the BE1 87T settings  The remaining steps check that the relay settings are within acceptable  parameters        CAUTION    Do NOT install connection plugs  apply power  remove circuit boards or carry out any of the other    instructions given unless you are thoroughly familiar with the instructions in the sections on RELAY  OP
60. cial reed relay is placed in series with the  contact to signal the target indicator   The series impedance of the reed relay is less than 0 1 ohm    Current in the output circuit must be limited to 30 amperes for 0 2 seconds  7 amperes for 2 minutes  and 3 amperes continuously     3 4 BE1 87T Functional Description 9171300990 Rev R       NOTE    Prior to September 2007  the BE1 87T target indicators consisted of magnetically  latched  disc indicators  These mechanically latched target indicators have been  replaced by the electronically latched LED targets in use today                of Trip    When the   of trip pushbutton Q is pushed  eight LEDs  shown in Figure 2 5  are used to indicate the  percentage of operating current to  Minimum pickup  LED M also lights   or Slope characteristic pickup   LED S also lights   The eight LEDs represent the following percentages     1 LED  3   Yellow LED   2 LEDs  7   Yellow LED   3 LEDs  11   Yellow LED   4 LEDs  20   Red LED   5 LEDs  40   Red LED   6 LEDs  60   Red LED   7 LEDs  80   Red LED   8 LEDs  100   Red LED     A bar chart above the LEDs shows the relative percentage of trip     9171300990 Rev R BE1 87T Functional Description 3 5    3 6    This page intentionally left blank     BE1 87T Functional Description    9171300990 Rev R    SECTION 4   INSTALLATION       GENERAL    When not shipped as part of a control or a switchgear panel  the relay is shipped in a sturdy carton to  prevent damage during transit  Immediately upon rec
61. ction for power transformers and are  available in either Single Phase or Three Phase configurations  The solid state BE1 87T compares the  currents entering and leaving the protected transformer  If a fault is detected  the relay initiates a trip  signal to isolate the power transformer  This limits damage to the transformer and minimizes the impact  on the power system     BE1 87T relays use three types of restraint     e Percentage of through current  e Second harmonic  e Fifth harmonic    Selectivity in differential relaying is based on the ability to distinguish between internal and external faults   This is achieved by comparing the currents into and out of a power transformer  Comparing these  currents often requires more than two inputs  For example   e Power transformers may have a significant portion  greater than 10 96  of the current flowing in a  third or tertiary winding   e Power transformers can have multiple breakers for a given winding  e g   ring bus or breaker   and a half bus      BE1 87T relays are available with up to five restraint inputs for the single phase unit and up to three  restraint inputs per phase for the three phase unit     9171300990 Rev R BE1 87T General Information 1 1       APPLICATION    In general  power transformers have different values of current flowing through their primary  secondary   and tertiary windings  These currents have specific phase relationships depending upon the connections  of the individual windings  e g   wye del
62. current automatically after a suitable time interval  This can be calculated by  using the following equation     K     Jr    Where  K   50 or 50 x tap  whichever is less  t  the time  in seconds  that the current flows       Restrained Pickup Verification    Step 1     Step 2     Step 3     Step 4     Connect the relay as appropriate  refer to Figures 5 2 through 5 5  beginning with input  terminals 11 and 13 for the initial tests  Do not apply power at this time     Observing the precautions provided in Section 4  HELAY DISASSEMBLY  remove the relay  from its case  Then remove the front panel to gain access to the printed circuit boards     Remove the Analog  1 board  one per phase  shown in Figure 4 19  Connect the Input   Grounding jumpers to the disabled position  Refer to Figure 4 20 for relays with Option 1 0 and  Figure 4 21 for relays with Option 1 1 for correct positioning  For further information  see  Grounding Unused Inputs in Section 4     After testing is complete  and prior to placing the relay in service   it may be necessary to  reposition the jumpers     Three Phase Units Only  Check that all of the 30  Phase Shift Compensation jumpers on the  Analog Board  2  shown in Figure 4 27  are in the WYE position  If not  reposition these  jumpers accordingly     NOTE  It is possible to test three phase units without changing the 30  Phase Shift    Compensation jumpers from the in service positions  Refer to Testing Three Phase       Step 5     Step 6     Step 7   
63. d by 30  or passed through unchanged   Compensating phase shift direction  shown as the Phase Shift Setting circuit in Figure 3 1  is determined  by the position of three jumpers on the internal Analog  2 Board   The location of these jumpers is shown  in Figure 2 4   The internal phase shift will accomplish the corresponding zero sequence blocking  The  current magnitude will be increased by  3 and must be taken into account in the tap setting  explained  later in detail in Section 4      9171300990 Rev R BE1 87T Functional Description 3 1       OPERATING POWER ENED  POWER SUPPLY TO INTERNAL U    OSHIFT SETTING    CIRCUITRY SENSOR POWER   30   30  0 SUPPLY       STATUS  IN  1 CALCULATE    MAXIMUM  INDIVIDUAL  CURRENT OF  TRIP  IN  2  RESTRAINED   gA Q              3  10  IN  4  SECOND  HARMONIC  IN 5 RESTRAINT  FILTERS  COM   IF lop  gt   UNREST UNREST  UNRESTRAINED  NREST  SETTIN  TRIE a    SETTING   6TO21 j THEN TRIP  TIMES TAP   TO OTHER PHASES   THREE PHASE ONLY   BE1 87T  D741 001a  7 11 94  Figure 3 1  Functional Block Diagram  NOTES    1 Present in three phase units ONLY   2 Inputs 4 and 5 are available in single phase units ONLY     3        settings are calibrated to a specified percentage of the harmonic to the fundamental  See Harmonic  Restraints for factory settings     4 Phase Targets are supplied on three phase units ONLY   5  Restrained Trip Contact     e        contact for single phase units    e One contact or one contact per phase available on three phase 
64. de system protection  Always be sure that external operating  monitored   conditions are stable before removing a relay for inspection  testing  or servicing  Be sure that  connection plugs are in place before replacing the front cover        CAUTION    To prevent possible false tripping  the upper connection plug should be in place prior to       removing or installing the lower connection plug     4  Thumbwheel switches should not be changed while the relay is in service  Momentary  undesired indications and outputs may occur        WARNING     The TEST PROCEDURES require familiarity with solid state relay circuits  To avoid  personal injury or equipment damage  do not proceed unless qualified in this area                 MOUNTING    Because the BE1 87T  Transformer Differential Relay  is of solid state design  It does not have to be  mounted vertically  Any convenient mounting angle may be chosen  The BE1 87T relay is supplied in a  standard M1 size drawout case and can be either semi flush or projection mounted  Option 4   Refer to  Figures 4 1 through 4 6 for outline dimensions and panel drilling diagrams     NOTE    Several procedures in this manual require the removal of printed circuit boards  Refer to  the topic RELAY DISASSEMBLY before installing the BE1 87T        9171300990 Rev R BE1 87T Installation 4 1    4 2    6 65                                                                                                                 168 91   15 32   389 13   D1924 28 
65. dicating that the  inhibit point has been reached  Note the magnitude of the fifth harmonic component at the  inhibit point    To calculate the fifth harmonic inhibit percentage  divide the current measured in Step 3 by the  current applied in Step 2   Divide the harmonic current by the fundamental current   Factory  setting is 35 0  3  for both single phase and three phase units     Three Phase Units Only  Repeat Steps 1 through 4 for phase B  terminals 12  amp  13  and  phase C  terminals 14  amp  13      BE1 87T Test Procedures 9171300990 Rev R    Response Time Verification    Step 1     Step 2     Step 3     Step 4     Step 5     Step 6     Step 7     Step 8     Step 9     Step 10     Connect the relay as appropriate  refer to Figures 5 2 through 5 5      Set the RESTRAINED PICKUP LEVEL switch  phase A  to A  15    Place all of the INPUT  switches on the 2 0 A tap position     Apply 2 0 A at 50 or 60 Hz  as appropriate for the style  to Input 1  terminals 11  amp  13 on both  single  and three phase styles  and to Input 2  terminals 12  amp  13 on Single Phase and  terminals 15  amp  18 on three phase      Perform a restrained trip at 2 x Pickup by stepping the Input 2 current 3 4 A  Note the time  interval between initiation of the simulated fault and the closure of the restrained output contact   The trip time should be less than that shown in Table 5 4     Repeat Step 4 at Io     10 x Pickup  Note that  with Input 1 at 2 0 A  Input 2 current should be  stepped to 9 0 A
66. e  This is  shown in Figure 4 32 by selecting phase compensation jumper position A2 for these inputs  This also  provides zero sequence blocking for these inputs since this transformer configuration is a source of zero  sequence currents     4 32 BE1 87T Installation 9171300990 Rev R       SETTING THE BE1 87T  The following setting procedures include two examples     1  Using the MVA rating of the highest rated winding for all the other windings when making the  calculations     2  Using the top kVA rating of the transformer     Each procedure can be used as a means to understand the principles involved  and by replacing the  variables of the example  can become a procedure of general application  Variable abbreviations and  definitions are provided in Table 4 1  List Of Variables     Method    Both procedures determine     1  The matching tap and slope settings required to implement the restrained function  and    2  The unrestrained pickup setting as a multiple of the BE1 87T tap setting  i e   the INPUT  switches      The matching tap procedure is conventional  providing tap values proportional to the normal currents as  seen by the relay  An exception occurs with multiple winding banks where zero balance current is  assumed in each pair of windings  successively     NOTE    The      component of the input current is effectively blocked by the gapped cores of the    input CTs  Therefore  for offset fault currents or magnetic inrush  the dc component of the  waveform can be
67. e For wye connected CTs     VBG   Irc 2RL   Rr     Where   lg    determined in Step 12  R    one way lead resistance in ohms         relay resistance in ohms   lt  0 05 ohm        For delta connected CTs  Vz  is a function of the proportion of positive sequence to zero   sequence currents but may be approximated by the same equation     Neglecting Rr  use Rw and     from Figure 4 33        HIGH TERTIARY LOW  Vac   28 2 0 7   NONE          38 2 0 7      39 2   53 2  Step 15  Determine the effective CT accuracy class  Vcg     Base Accuracy   Number of CT Turns in Use        5     Maximum Ratio  HIGH TERTIARY LOW  600 3000 1200            400         VCE   800                  400       ce   G00  En         800  5000 CE    400        400   800   240  Step 16  Determine the saturation factor  Sg    Note  Vz is the largest burden voltage from steps 13 and 14         SF   Vos  HIGH TERTIARY LOW  5    392 _ 154 5    532     400 F 800    240   0 1   0 02   0 22    4 38    BE1 87T Installation    9171300990 Rev R    NOTE  Maximum recommended S  0 5     Instantaneous  Unrestraint  Unit Setting    Step 17  Determine the maximum external fault multiple   g         For wye connected CTs and with WYE jumpers on Analog Board  2  shown in Figure 2   4      Ir   Maximum Relay Fault Current  E      T Corresponding Tap          For delta connected CTs  or with   1 or A2 jumpers on Analog Board  2  shown in Figure  2 4   and based on a phase to phase fault    Refer to Appendix A  Setting Note 3 
68. each input  then  reduce the Input 2 current or increase the Input 1 current until the REST  TRIP LED lights  This  should occur as the input current being adjusted reaches the level given in the Trip Amperes  column for the respective input     If the relay has more than two inputs  reconnect the relay by substituting the Input 3 terminals  for the Input 2 terminals  Then repeat Steps 6 and 7  using the Input 2 values of Table 5 1 for  Input 3     If there are more than three inputs  as in some single phase units   continue substituting every  higher numbered input for Input 2  each time comparing the input under test against Input 1 as  in Steps 6 and 7     9171300990 Rev R BE1 87T Test Procedures 5 9    Step 9  Three Phase Units Only  Repeat Steps 6  7 and 8 for phases    and C   Refer to Figures 5 2  through 5 5  as appropriate  for the terminal numbers of the phase B and C inputs      Table 5 1  Restrained Pickup Test  5 A  50 or 60 Hz  Input 1  Tap   2 0 Input 2  Tap   3 8   Increasing Input 1   Decreasing Input 2    25 5 33  0 42 5 70  0 44    60 6 0 3 11 4 3 15 00  1 00 4 56  0 37                Input  or Tap  Switch Verification  Each input is scaled using a combination of two rotary switches  Verify the switches as follows     Step 1  Determine the Sensing Input Type  the first digit of the Style Number shown on the front panel    Single phase  two inputs   Single phase  three inputs   Single phase  four inputs   Single phase  five inputs   Three phase  two inputs e
69. ed in delta  Remember that  if system CTs are connected in delta  the same  square root of three conversion factor must be applied     HIGH TERTIARY LOW   INPUT 1   INPUT 2   INPUT 3   Ig 23 4943 IR    1822   1  Ig 243643  Ig 26 04 IR  18 22 Ig   7 55    Step 5  Determine the spread ratio of the relay currents  largest smallest    Spread   18 22 6 04   3 0    Step 6  Determine the Driving InputError  Bookmark not defined   DP   which we define as the input  assigned to the smallest current in Step 4     DP ly  DP   HIGH  INPUT 1     Step 7  Determine the Driving Input              which must be less than the 4 45 capability of the BE1   87T     HIGH  T  22 0    Choosing the 2 0 setting for the minimum inputs will yield maximum sensitivity     Step 8  Determine the Desired Tap            TERTIARY    18 22  A      6 03    Step 9  Select taps by rounding Tp to the nearest tenth     HIGH TERTIARY  T 2 0 T  6 0    4 36 BE1 87T Installation    LOW            T   8      2 0          2 50    LOW     2 5    9171300990 Rev       Step 10  Determine the CT mismatch  My                        HIGH LOW HIGH   TERTIARY LOW TERTIARY  My  100 MN  100             Sie of      above      the smaller of dc above  Mat  the m of   above   6 04 18 22 18 22  6 0  100  753  AG    100  oo  s        100 Gaz  Gs   the smaller of dc above   the smaller of FA above   the smaller of the above   _ 90 9 80  0 80    100 3 02 3 0  100241240  0 80 3 0 2 40   0    0 6    0 4     Step 11  Determine the total misma
70. eipt of a relay  check the model and Style Number  against the requisition and packing list to see that they agree  Visually inspect the relay for damage that  may have occurred during shipment  If there is evidence of damage  immediately file a claim with the  carrier and notify the Regional Sales Office  or contact a sales representative at Basler Electric  Highland   Illinois     In the event the relay is not to be installed immediately  store the relay in its original shipping carton in a  moisture  and dust free environment  For more information  see STORAGE in Section 4  When the relay  is to be placed in service  it is recommended that the VERIFICATION TESTS  shown in Section 5  be  performed prior to installation        RELAY OPERATING PRECAUTIONS    Before installation or operation of the relay  note the following precautions     1  A minimum of 0 2 A in the output circuit is required to ensure operation of current operated  targets     2  The relay is a solid state device and has been type tested in accordance with the requirements  defined under Dielectric Test  If a wiring insulation test is required on the panel assembly in  which the relay is to be installed  it is suggested that the connection plugs  or paddles  of the  relay be removed and the cradle withdrawn from the case so as not to produce false readings  during the wiring insulation test     3  When the connection plugs are removed  the relay is disconnected from the operating circuit  and will not provi
71. ency and then add the  required harmonic        Step 3     Step 4     Step 5     Step 6     Step 7     Apply 2 0 A at 50 or 60 Hz  as appropriate for the style  to Input 1  The REST  TRIP LED  should be illuminated     Increase the second harmonic current until the REST  TRIP LED extinguishes  indicating that  the inhibit point has been reached  Note the magnitude of the second harmonic component at  the inhibit point     To calculate the second harmonic inhibit percentage  divide the second harmonic current  measured in Step 4 by the current applied in Step 3   Divide the harmonic current by the  fundamental current   Factory setting is 12 0  3  for single phase units and 18 0  3  for  three phase units     Three Phase Units Only  Repeat Steps 1 through 5 for phase B  terminals 12  amp  13  and  phase C  terminals 14  amp  13      Three Phase Units Only  Upon completion of above testing  return the three calibrate toggle  switches S2  letter D of Figure 2 4  to the NORM position     Fifth Harmonic Restraint Verification    Step 1     Step 2     Step 3     Step 4     Step 5     5 12    Set the INPUT 1  tap  switches to the 2 0 A position  Connect the relay as appropriate  refer to  Figures 5 2 through 5 5  using terminals 11  amp  13  Input 1 for both single phase and three   phase      Apply 2 0 A at 50 or 60 Hz  as appropriate for the style  to Input 1  The REST  TRIP LED  should be illuminated     Increase the fifth harmonic current until the REST  TRIP LED extinguishes in
72. es not respond    Connect Input 1 current to terminals C and N    Connect Input 2 current to terminals N and A    This verifies the A  and C phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The B   phase differential circuit sees no current and does not respond     Connect Input 1 current to terminals B and N     Connect Input 2 current to terminals N and C     9171300990 Rev R BE1 87T Test Procedures 5 23    This verifies the B  and C phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The A   phase differential circuit sees no current and does not respond     5 24 BE1 87T Test Procedures 9171300990 Rev R    SECTION 6   DIFFERENCE DATA    GENERAL    This section provides the information necessary to support BE1 87T  Transformer Differential Relays   with sensing input type F  three phases  three inputs each phase   Sensing input type F relays have a  style number with the first character F  refer to Style Number Identification Chart  Figure 6 1   Sensing  input type F relays require the lower connection plug to be removed before the upper connection plug   This procedure prevents false trips  During installation  the lower connection plug should be installed last           DIFFERENCES    Revision P to BE1 87T relays made sensing input type F obsolete and created sen
73. ests  Do not apply power at this time     Observing the precautions provided in Section 4  HELAY DISSASSEMBLY  remove the relay  from its case  Then remove the front panel to gain access to the printed circuit boards     Remove the Analog  1 board  one per phase  as shown in Figure 4 19  Connect the Input   Grounding jumpers to the disabled position  Refer to Figure 4 20 for relays with Option 1 0 and  Figure 4 21 for relays with Option 1 1 for correct positioning  For further information  see  Grounding Unused Inputs in Section 4     After testing is complete  and prior to placing the relay in service   it may be necessary to  reposition the jumpers     Three Phase Units Only  Check that all of the 30  Phase Shift Compensation jumpers on the  Analog Board  2  shown in Figure 4 27  are in the WYE position  If not  reposition these  jumpers accordingly     NOTE  It is possible to test three phase units without changing the 30  Phase Shift    Compensation jumpers from the in service positions  Refer to Testing Three Phase       Step 5     Step 6     Step 7     Step 8     Relays without Changing Jumpers  at the end of this section     Replace all circuit boards and reassemble the relay     Refer to Table 1 1 and Figure 1 2 for multiples of tap and percentage restraint characteristics   Set the RESTRAINED PICKUP LEVEL switches and the INPUT 1 and INPUT 2 tap switches  to the values shown in Table 5 1     Apply power to the relay  Apply input current as indicated in Table 5 1 for 
74. etup illustration was  added     Miscellaneous editing        B  03 91    Manual  with the exception of Section 2  was rewritten for ease of  use        A  06 90       Figure 3 1  Functional Block Diagram  corrected     Formula in caution note  formerly on p  4 17  now on p  5 2   corrected     Miscellaneous editing        9171300990 Rev R    BE1 87T Introduction    This page intentionally left blank        vi    BE1 87T Introduction    9171300990 Rev R    CONTENTS       SECTION 1 e GENERAL INFORMATION                        U         1 1  INTRODUCTION etr attente u la h B      aita ah awha uy phe date 1 1  DESCRIPTION  EE 1 1                       6       tereti u uh thats a ta aku uyu ata tea Whats 1 2   single Ph  se wie mau hte ayu        d             een baa al            1 2     TMreG PhaSe             a            tel e Td e Eae beer ee kaa                    1 2  Percentage Ftestralnt                     eo ed e SRL te fro der p care e ul 1 2  Second Harmonic  Restraint ic    udo a e Eee      eed e t      LO Pede 1 2  Fifth Elarmonic Restralbt s               eroe UT et ea eaten antes 1 3  Unrestrained Tip eie n eee hav ieee ede        1 3  Me cc ERU 1 3  Push To Energize Output                                           0   a    1 3  Auxiliary Output  Contacts    reete ei                                                      1 3                         Aiea tess          tte t      oe b                                         uD aol 1 3  MODEL AND STYLE               
75. h jumper can be shifted  30     30    or 0    a total of 60  is achievable between  two inputs for special applications  In this way  the appropriate direction of phase shift can be matched to  the shift in the protected transformer  This alleviates the need for an extra set of external CTs in most  applications     Figures 4 28 through 4 32 illustrate the use of internal phase shift in lieu of matching by external CT  connections  These are typical of the many combinations that can occur     4 24 BE1 87T Installation 9171300990 Rev R       CAUTION    Assigning 30   Phase Shift Compensation requires disassembly of the relay  and must be  done when the relay has been taken out of service  Access to the 30   Phase Shift  jumpers requires the removal of the Analog  2 Board  shown in Figure 4 27  To avoid  personal injury or equipment damage  do NOT proceed unless thoroughly familiar with  the instructions in the sections on RELAY OPERATING PRECAUTIONS and RELAY    DISASSEMBLY  Precautions           30   Phase Shift Compensation Adjustment Procedure    The position of a set of movable jumpers on Analog Board  2 determines the state of the internal  compensation  To gain access to these jumpers  it is necessary to remove Analog Board  2  Refer to the  topic RELAY DISASSEMBLY for instructions on gaining access to the circuit board then adjust the  jumpers shown in Figure 4 27 as follows     In cases where no phase shift is wanted  all three jumpers  A  6B  and  C  shown in Figure 4
76. hases  one 240 Vac i  two inputs unrestrained NOTES        each phase OPTION 2 1  All relays are      an M1 size case   F  eee SUN  N Output type must be E  and Option 3 must be      each phase   None  S  Push to  Sensing input type must be E  and Option 3 must  energize output be O   When targets are specified   a  Two targets are supplied in single  phase  IN i i    SENSING INPUT TIMING styles  restrained  unrestrained    b  Five targets are supplied      3   phase styles  RANGE jai                  oe and unrestrained  plus phase A B   1  20 H  8 9 A  Auxiliary contacts are only available if  2 Sensing Input is not F and Output is E   2  0 4     1 78A  D422 003 PAS  50 Hz          Figure 6 1  Style Number Identification Chart    BE1 87T Difference Data 9171300990 Rev R    Figure 6 2  Typical Internal Connections  Three Phase  Sensing Input Type F  Output Option E    9171300990 Rev R BE1 87T Difference Data 6 3             Figure 6 3  Case Terminals  Sensing Input Type F  Output Option E          6 4    Figure 6 4  Test Setup  Sensing Input Type F  Output Option E    BE1 87T Difference Data 9171300990 Rev R    APPENDIX A   SETTING NOTES    INTRODUCTION    These setting notes are to clarify several of the settings steps in Section 4   nstallation     SETTING NOTE 1    The procedure outlined in Step 1 assumes that 5  or S  is zero and yields the correct magnitude and ratios   This note is to point out that the relay taps are determined by the windings turn ratios  The use of 
77. i L  3 69     93 7  4 16   105 6      2 28 s     57 9     6 20   157 6  E 1 75 a 1 75      44 5   44 5   741 4     188 1          56  14 3  DIA   5 PLACES      50 Le      12 7   TYP    9    Z                 Y      69 147   17 5   37 3     XB      i     L 8    L  6  gt          1   75  19 1  DIA  1 00 25  20 PLACES  25 4   6 4   2 63      66 8   D1427 12b  05 29 02  em 5 25     133 4   NOTES       N OPTIONAL RECTANGULAR CUTOUT MAY REPLACE 10 DRILLED HOLES   2  TERMINAL NUMBERS SHOWN ARE VIEWED FROM REAR OF RELAY   3  TOP HALF OF PANEL DRILLING DIAGRAM  FROM CENTERLINE UP  IS    SHOWN IN FIGURE 4 6a   Inches  Millimeters     Figure 4 6b  Panel Drilling Diagram Bottom Half  Projection Mounting     4 8 BE1 87T Installation 9171300990 Rev R       DIELECTRIC TEST    In accordance with IEC 255 5 and ANSI IEEE C37 90 1989  one minute dielectric  high potential  tests  may be performed as follows    All circuits to ground  2121 Vdc   Input to output circuits 1500 Vac or 2121 Vdc    Note that this device employs decoupling capacitors to ground at all the output terminals  and at the  power supply terminals  3  4   Accordingly  a leakage current of approximately 15 milliamperes per 1000  Vac is to be expected        CONNECTIONS    Incorrect wiring may result in damage to the relay  Be sure to check the model and Style Number against  the options listed in the Style Number Identification Chart  Figure 1 1  before connecting and energizing a  particular relay     NOTE    Be sure the rela
78. indicating overexcitation of the transformer  or when the second harmonic content exceeds 12   single   phase  or 18   three phase  of the operate current  indicating a magnetic inrush condition   an inhibit  signal is developed that blocks operation of the Restrained Trip output contact   Stated percentages  represent the factory setting      Unrestrained Trip Output    Iop is also compared against a reference established by the front panel UNRESTRAINED PICKUP  LEVEL switch is shown in Figures 2 1 through 2 5  When this reference is exceeded  the Unrestrained  Trip output relay is energized  An unrestrained trip is not affected by through current or harmonic inhibits     9171300990 Rev R BE1 87T Functional Description 3 3    Auxiliary Relay Option    Auxiliary relays  Option 3 1  3 2 or 3 5 in the tenth position of the Style Number  are accompanied by two  switches  S1 and S2  which allow the relays to respond to a restrained trip  S1 ON  or to an unrestrained  trip  S2 ON   or both  81 and S2 ON   These switches  letter   of Figure 2 4 and described in Table 2 1   are located on the mother board and are shipped in the ON position  Auxiliary relays may be disabled by  opening both switches   1        S2 OFF      Power Supply    Relay operating power is developed by a wide range  isolated  low burden  switching power supply that  delivers  12 Vdc to the relay s internal circuitry  The power supply is not sensitive to the input power  polarity  A front panel LED power indicato
79. input current at the maximum external line ground fault level in  secondary amperes    The input with the least minimum current   CT primary current in amperes   Relay input current in amperes   CT secondary current in amperes   Rated self cooled current of the power transformer in multiples of tap  Current mismatch  with power transformer on its neutral tap  Multiple rating CT  i e   a tapped CT   Total mismatch  including the maximum transformer tap excursion  Total number of CT turns available   Number of CT turns in use   One way lead resistance in ohms   CT winding resistance in ohms   Relay resistance in ohms   Restrained slope setting  from 15 to 60     Saturation factor  which equals Vz Vcr   Relay current tap  0 4 to 1 78 for 1 ACT  2 to 8 9 for            Desired tap  based on the current ratio    The larger of Vs                 The CT burden voltage with Zr  flowing    The CT burden voltage with Zrc flowing  Base accuracy class CT voltage rating    Accuracy class CT effective voltage where not all turns are used  which equals  Vc NA N     Unrestrained pickup setting  in multiples of tap  6 to 21        4 34 BE1 87T Installation 9171300990 Rev R    WYE  3                  600 5MR  345 kV  HIGH 4 ane WYE  3   SIDE 2  y  3360     3 2   3375 A  1 2    12  13 2  2000 5MR 138 kV  1200 5T  PA X    LOW SIDE  3000 5       _  gt     TERTIARY 1 8400 A  3 2     9000 A  1 2   13 280 A  3     12      12     WYE  3       1 87    D240 004  02 12 98     10  LTC  11     Figure 4 33
80. l circuits which respond together as provided earlier    in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The A   phase differential circuit sees no current and does not respond     Jumper Positions A1 A1    Step 1     Step 2     Step 3     5 22    Connect Input 1 current to terminals A and N   Connect Input 2 current to terminals A and N     This verifies the A  and B phase differential circuits which respond together  The C phase  differential circuit sees no current and does not respond     Connect Input 1 current to terminals B and N    Connect Input 2 current to terminals B and N    This verifies the B  and C phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The A   phase differential circuit sees no current and does not respond     Connect Input 1 current to terminals C and N     Connect Input 2 current to terminals C and N     BE1 87T Test Procedures 9171300990 Rev R    This verifies the A  and C phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The B   phase differential circuit sees no current and does not respond     NOTE    The same test connections are used for A1 A1 and A2 A2  The proper jumper position is  confirmed by which relay differential circuits respond for the specific condition        Jumper Positions A2 A2 
81. lectrical characteristics and operational  features included in BE1 87T relays  For example  if the Style Number were G1E A1Y D1SOF  the device  would have the following     BE1 87T Model Number  designates the relay as a Basler Electric  Class 100  Transformer Differential    Relay   G Three phase sensing with three inputs per phase  1 2 0 to 8 9 A Sensing Range at 60 Hz  E One unrestrained output contact and one restrained output contact    A1 No intentional delay in the outputs                                                                                                                                                                                                                      Y 48 125 Vdc switchable  D Current operated targets  1 Percent lop display and high speed trip  S Push to Energize outputs  0 No auxiliary output  F Semi flush mounting  STYLE NUMBER IDENTIFICATION CHART      1 87          Al  1      MODEL NO    TENES POWER     ul UTU E        TARGET  N OPTION 1 OPTION 3 AN OPTION 4  A  Single phase      Two NO J  125 Vde  amp  N  None 0  None 0  None F  Semi   Flush  two inputs contacts  one 100 120 C  Internally 1  Auxiliar Mountin  1205 1  Percent lop y ME  B  Single  phase  restrained  one Vac operated    contacts  NO P  Projection              Display and SOCTS  ject  three inputs unrestrained K  48 Vdc targets High   d 2  Auxiliary Mounting      Single phase  F  Four NO L  24 Vde D  Current    Spes contacts  NC  four inputs contacts  one Y  48 125 ope
82. lel with 150  Increase    until the REST  TRIP LED extinguishes  The inhibit percentage is           l AN  100 x 47  at the point where the LED extinguishes   50    Expected Values  12 3  for single phase  18 3  for three phase    For 60 Hz Units  Holding the 60 Hz current constant at tap value  add a 120 Hz  J 29  current in  parallel with 160  Increase 7    until the REST  TRIP LED extinguishes  The inhibit percentage is             ere  100 x p at the point where the LED extinguishes   60    Expected Values  12 3  for Single Phase    18 3  for Three Phase    Fifth Harmonic Inhibit    Step 8     Step 9     For 50 and 60 Hz Units  Apply tap value  1 pu  to Input 1  REST  TRIP LED should be  illuminated     For Three  Phase Units  Return S2 to the NORMAL position     For 50 Hz Units  Holding the 50 Hz current constant at tap value  add a 250 Hz  1  current       parallel with 150  Increase 1  until the REST  TRIP LED extinguishes  The inhibit percentage is    Iso A  100 x  um at the point where the LED extinguishes   50    Expected Values  35 3  for single phase or three phase units     For 60 Hz Units  Holding the 60 Hz current constant at tap value  add a 300 Hz  Izo  current in  parallel with 160  Increase 1  until the REST  TRIP LED extinguishes  The inhibit percentage is    I300   mm  100 x      at the point where the LED extinguishes   60    Expected Values  35 3  for single phase or three phase units        TESTING THREE PHASE UNITS WITHOUT CHANGING JUMPERS    The simp
83. lest way to test three phase units using only two test currents is to set all jumpers to the WYE  position  Then each comparison circuit is tested independently when the respective phase currents are  applied  This is not acceptable from two points of view     Requires changing the relay settings  jumpers  from the in service position   Does not verify that the jumpers have been properly set     It is possible to completely test the BE1 87T with the jumpers set to the in service position and still use  only two input current sources  When the jumpers are in the positions shown in Table 5 9  the respective  current inputs are compared     5 20    BE1 87T Test Procedures 9171300990 Rev R    Table 5 9  Input Signals to Comparison Circuits Based On Jumper Positions    Cin  Jumper    s              Am                The following connections can be used to verify proper relay jumper positions on a three phase unit or to  test an in service relay without changing the jumpers  These tests only require two input current sources   180  out of phase   In most cases  the specified input pair will properly test only two of the three phases  within the relay  In order to test all three of the relay phases  two of the three connection pairings should  be tested  This confirms relay operation    Jumper Positions WYE WYE    Step 1  Connect Input 1 current to terminals A and B   Connect Input 2 current to terminals A and B   This verifies the A  and B phase differential circuits which respond
84. ll  the tap switches     Table 5 6  Input Verification    1 A  50 or 60 Hz  Tapt Position Input Current Range  at Pickup    0 78 0 24   0 31 A    1 28 0 40   0 49 A  1 56 0 49   0 60 A      Pickup occurs at 0 35 x Tap  See Figure 1 2   T        setting of the upper and lower INPUT switches of the input being  tested   Reference Figures 2 1 to 2 4         Unrestrained Pickup Verification    Step 1  Set the INPUT 1  tap  switches to the 2 0 A position  Connect the relay as appropriate  refer to  Figures 5 2 through 5 5  as appropriate  using terminals 11  amp  13  Input 1 for both single phase  and three phase units      Step 2  Set the UNRESTRAINED PICKUP LEVEL switch to position A  6 X TAP   Increase the input  current until the UNREST  TRIP LED lights  disregard the REST  TRIP LED   This should occur  at 2 4 A  3  as indicated in Table 5 7     Step 3  Repeat Step 2 using the other UNRESTRAINED PICKUP LEVEL switch positions given in  Table 5 7     Step 4  For Three Phase Units Only  Repeat Steps 1 through    for Phase B of input 1  terminals 12  amp   13  and Phase C of input 1  terminals 14  amp  13      Table 5 7  Unrestrained Pickup Verification  1 A  50 or 60 Hz    Unrestrained Input 1 Tap Input Current at  Pickup Level Position Pickup   396    AIGXTAP    J  14 X TAP  5 6A  S  21 X TAP  84      Second Harmonic Restraint Verification       Step 1  Set the INPUT 1  tap  switches to the 0 4 A position  Connect the relay as  refer to Figures 5 2  through 5 5  as appropriate  
85. ll operate at minimum pickup  0 35 times    BE1 87T Controls and Indicators 9171300990 Rev R       M S Indicator    RN Percent of Trip Pushbutton      OF TRIP Indicators Option    Red LED lights when the   OF TRIP pushbutton P is  pressed and the restraint current is above the slope  characteristic kneepoint as defined in Table 1 1  That  is  the relay will operate based on the restraint  characteristic     Pushbutton that is used to activate the   of TRIP  LEDs     When the   OF TRIP pushbutton P is pushed  eight  LEDs  shown in Figure 2 5  are used to indicate the  approximate percentage of operating current to     Minimum pickup  LED M also lights   or  Slope characteristic pickup  LED S also lights      The eight LEDs represent the following approximate  percentages     1LED  3   Yellow LED   2 LEDs  7   Yellow LED   3 LEDs  11   Yellow LED   4 LEDs  20   Red LED    5 LEDs  40   Red LED     6 LEDs  6096  Red LED   7 LEDs  8096  Red LED   8 LEDs  100   Red LED     A bar chart above the LEDs shows the relative  percentage of trip                      9171300990 Rev R BE1 87T Controls and Indicators 2 3    ES Basler Electric    INPUT 1 INPUT 2 INPUT 3  1 00 1 60  1 00 1 60  1 00 1 60    See Fig  2 4    UNREST   TRIP       PHASE A   THRU       CURRENT    UNREST   TRIP                      PHASE B    UNREST      L  TRIP                                               See Fig  2 4    BE1 87T     lt              TRANSFORMER DIFFERENTIAL    POWER  W    Style No  G4E   1   DOSOF    
86. margin with respect to the  characteristic kneepoint of the BE1 87T  Refer to Figure 4 34           lop  1          U  L      1      L  E  S  o TOTAL MISMATCH  F  T              EXCITING CURRENT  MAXIMUM Ig IN MULTIPLES OF TAP BE1 87T  D610 010  3 2 91    Figure 4 34  Slope Needed to Accommodate Total Mismatch with Adequate Margin    Specifically  if the maximum saturation factor Sp  from Step 16  exceeds 0 5  set the  RESTRAINED PICKUP LEVEL to setting K which is equal to 60 as shown in the table on the  front panel     For all other cases including this example  use the following equation     Where   S   restrained slope setting  Mr   total mismatch in percent  Ir   rated self cooled current of the power transformer in multiples of tap    For a three winding transformer application  such as this example  the maximum of the three  values of M  and of I  is used     Mrz is 10 6  from Step 11  and  ris 2 42  Step 20      BE1 87T Installation 9171300990 Rev R    35 10 6  3   23     4 2 42       38 8    Because the maximum saturation factor Sp for this example is less than 0 5  from Step 16   use  the next highest slope  Select position F which   40      For examples of suitable slope settings  see Table 4 2     Table 4 2  Examples of Suitable Slope Settings    Maximum Current Rating of Power Recommended Minimum  Mismatch in 96 Transformer in RESTRAINED PICKUP         Multiples of             LEVEL Seiting   Slope        53 Sr V B V ce  If Sr gt 0 5  set the RESTRAINED PICKUP LE
87. nce  It  corresponds to an excitation voltage on a curve passing through point Q in Figure 2 at which the excitation  current is 10 amperes  the maximum error allowed by the accuracy class definition   The Rsx100 term  represents the voltage drop across the CT internal resistance  A new SF which takes the internal CT  resistance into account can be defined on the excitation curve  as     peer     VIO    Where Ve is the internal excitation voltage  VT Rs IF  at the maximum fault current IF and V10  is the  voltage of the curve passing through point Q where the exciting is 10A  This voltage is practically close to  the knee point voltage         which would yield nearly the same  a slightly more conservative  result        Since in all likelihood  the excitation voltage capability of the CT will be higher   passing through point R in  Figure 2 for instance   the saturation factor defined on the excitation curve appears to be lower  i e    more  favorable  A detailed analysis can be performed to compare the two saturation factor definitions     Saturation Factor Definitions Compared    Using the equivalent circuit in Figure 1 and the ANSI Accuracy Class definition that the CT must be able to  source 20 times nominal current into a standard burden Zc  we now develop a comparative analysis  between the two definitions           SF   ME   Ve  VC V10   ZB IF  pe gp IFAZB     5   100 Zc 100  Zc   Rs     A 8 BE1 87T Setting Notes 9171300990 Rev R    To compare the two expressions  we 
88. nel  Refer to Figure 2 1 through 2 4 for  location     Appropriate power must be applied to Power Supply terminals 3 and 4  shown in Figures 4 7 through 4   10  for these pushbuttons to operate the output relays  However  it is not necessary to apply currents to  the sensing inputs of the relay for these switches to function     Auxiliary Output Contacts    Three types of auxiliary output contacts are available  Normally open  normally closed and SPDT  The  contacts can be made to respond to a restrained trip  an unrestrained trip or both  Refer to the  Functional Description  Auxiliary Relay Option for further information     Power Supply    Various power supply options are available to allow the BE1 87T to be used with standard supply  voltages  See the Style Number Identification Chart  Figure 1 1  for details     9171300990 Rev R BE1 87T General Information 1 3       MODEL AND STYLE NUMBER    The electrical characteristics and operational features of the BE1 87T Transformer Differential Relay are  defined by a combination of letters and numbers that make up its Style Number  The Model Number  together with the Style Number  describe the options included in a specific device and appear on the front  panel  drawout cradle and inside the case assembly     Upon receipt of a relay  be sure to check the Style Number against the requisition and the packing list to  ensure that they agree     Style Number Example    The Style Number Identification Chart  Figure 1 1  defines the e
89. nene 5 15                                                                                           nnne nennt 5 16  Second Harmonic Restraint Verification                       sess 5 16  Fifth Harmonic Restraint                                  9      5 17  Response Time                                                                                       5 18  OPERATIONAL TEST PROCEDURES                                                         5 19  Restrained  PICKUP  s  cucurrit arcs ae ved eee ee ada Pee ae                   5 19  Sacris                                                 S 5 19  Second Harmonic Inhibit    u    uu                                                     kai didan aasi iaiia inani Kadi 5 19                              Inhibib          ient eti ertet ir eed eec tete ees i re          qaq n ck e pna 5 20  TESTING THREE PHASE UNITS WITHOUT CHANGING                                                            5 20  Jumper Positions Wye Wye                                  Aae EEEE E VAS                                5 21  Jumper Positions                                             5 21  Jumper Positions Wy   Dellag2                         5 22  Jumper Positions          1          1                              5 22  Jumper Positions          2          2                                 nnns nnn ens 5 23  Jumper Positions         1         2        2  22                1 0 000                 nennen nennen nnne nennen 5 23       viii    BE1 87T Intr
90. ng during initial energization and external  fault conditions  A through current restraint also provides security against tripping for external faults  An  unrestrained tripping element is included to provide a high speed trip in the event of a particularly severe  fault within the transformer        DESCRIPTION    The functional block diagrams of Figures 3 1 and 3 2 illustrate the overall operation of the BE1 87T  Transformer Differential Relay   Figure 3 1 shows Phase A or single phase functions  Figure 3 2 shows  the additional functions for phases B and C   Since the three phases are functionally similar  only phase A  is shown in detail in Figure 3 1  Note that in a three phase unit  there may be one restrained output for  each phase  Output Type Option E in the third position of the Style Number   or one restrained output that  serves for all three phases  Option F in the third position   When Target Option C or D is specified for a  three phase Unit  in the seventh position   an individual target is supplied for each phase     Current Transformers    In the protected zone of the power system  CTs with a 1 ampere or 5 ampere secondary winding supply  the sensing current for each input  This is not shown in Figure 3 1 or Figure 3 2  Other relays may be  connected ahead of the BE1 87T  Sensing currents are  in turn  applied to relay internal input  transformers  These transformers provide system isolation     Scaling    Input currents are scaled by the front panel INPUT r
91. nsformer overexcitation causes additional exciting current to flow into one set of terminals  This  presents an apparent differential  or operating  current not attributable to an internal fault  Although  potentially damaging  overexcitation is not an internal fault and  therefore  is not an appropriate condition  for transformer differential relay operation  One of the principal components in the complex waveform  produced during overexcitation is the fifth harmonic  BE1 87T relays use fifth harmonic restraint to inhibit  the differential relay operation     Unrestrained Trip    Severe internal transformer faults may cause CT saturation  Under such circumstances  harmonic   restraint transformer differential relays may fail to trip because of the extremely high harmonic content in  the waveform  Lack of operation can result in severe transformer damage     BE1 87T relays provide an independent unrestrained tripping function  When set above the possible  inrush current magnitude  this function provides high speed protection for the most severe internal faults        OPTIONS    Push To Energize Output Pushbuttons    Two PUSH TO ENERGIZE OUTPUT switches are available as a means to verify external output wiring  without the inconvenience of having to test the entire relay  Option 2 S provides a small pushbutton  switch for each isolated output function  Restrained and Unrestrained  and may be actuated by inserting  a thin  non conducting rod through access holes in the front pa
92. nt  That input is chosen and then called the Imax signal  The    4x output is  then scaled by the front panel RESTRAINED PICKUP LEVEL switches  shown as the Hestrained Pickup  Control in Figure 3 1   The resulting signal   Ivax    that represents the percentage of through current is  extended to the Then Trip comparator and the 7o   Divided By  Ivax function     The Then Trip circuitry compares the operating current          to  Ivax  If the operating current is greater  than  Ivax  and there is no 5th or 2nd harmonic restraint to cause an inhibit as described below   a  Restrained Trip output is produced            Divided By  Ivax contains eight comparators and compares        to the preset percentage levels of   lmax  Mf Top is greater than the preset percent of  1       for a specific comparator  the LED associated with  that comparator lights  The eight LEDs represent the following approximate percentages   First LED  3   SecondLED  7   Third LED  1196  Fourth LED  2096  Fifth LED  40   Sixth LED  60   Seventh LED  8096  Eighth LED  100     NOTE    As each successive LED lights  all previous or lesser percentage value LEDs will also  light        Harmonic Restraints    Development of a restrained trip output may be inhibited by either of two harmonic restraints  These are  generated by bandpass filters tuned to the second and fifth harmonics of the operating current   Comparators monitor these signals  When the fifth harmonic content exceeds 35  of the operate current   
93. oduction 9171300990 Rev R    SECTION 6 e DIFFERENCE DATA                                      U    U  U U U U nananana 6 1  ejr 6 1  DIERERENGES     etiem eie tamia t Ed ere ect tid fea reed he yma i                       6 1  COMPALTIBIEETY                    ete ett ec ettet ec             esta cotes                        Ud e o eura 6 1                        Tx 6 1   APPENDIX A e SETTING NOTES            222222201                     uu    u cR RR Ra u                   A 1  INTRODUCTION Cm    1               oii zac Imm A 1  SETIFINGNOTE2           mm    2  SEWING NOTE             ERR A 3  SEATING  NO TE    55                        aAA                   aA      A 4  SANNER O TE 5          E AE E AEE A AE ET A 4   Slope Margil 25 556  ole c tem aa a                 E end e suit Yanta a e at A 4  SETTING  N  TE a EAEE S A A AE a TAE AE A EEA EEA           A 6  Inrush vs    Unrestraint Tap  rtr EE AKRA E EIEEE        A 6                          EER AE E l Sa A E AEA A 7  CT Performance Evaluation  Saturation                                                         A 7  Saturation Factor Defined from the ANSI C Classification                                                            A 7  Saturation Factor Defined from the CT Excitation Curve                                                              A 8  Saturation Factor Definitions Compared                             U aS    A 8   GODCIUSIOD                        E FE IE E OE EPOR ETUR                               
94. of controls that are mounted inside the relay  call out letters B  D and 1  are shown in  Figure 2 4     Table 2 1  Controls and Indicators    INPUT  or TAP  Switches Front panel INPUT switches are used to scale the  transformer currents  There are two of these rotary  switches for each input     1 Ampere CT Units Each of the upper switches is calibrated to represent  the tenths and units digits  0 4 through 1 6  of tap  value  Each of the lower switches is calibrated to  represent two hundredths of tap value for each  increment  Always add the setting of the lower switch to  that of the upper switch  For example  if a setting of  1 02 is desired  the upper switch must be at 1 0 and the  lower switch must be at 0 02  The total setting range for  each input is 0 4 to 1 78     5 Ampere CT Units Each of the upper switches is calibrated to represent  the units digit  2 through 8  of tap value  Each of the  lower switches is calibrated to represent tenths of tap  value  Always add the setting of the lower switch to that  of the upper switch  For example  if a setting of 5 0 is  desired  the upper switch is set to 5 0  the lower switch  must be at 0 0  The total setting range for each input is  2 0 to 8 9      three phase units ONLY  relay  either  30     30    or 0    depending upon the  position of the jumpers provided for each input on the  Analog  2 Board  shown in Figure 2 4  Additional  information is in Section 4     UNRESTRAINED PICKUP This thumbwheel switch establishes the
95. otary switches that introduce resistances to the  internal CT secondaries  The switches are calibrated in 0 02 ampere increments from 0 4 to 1 78 ampere  for 1 ampere CT units  Options 2 or 4 in the second position of the Style Number   and in 0 1 ampere  increments from 2 0 to 8 9 amperes for 5 ampere CT models  Options 1 or 3 in the second   The many  graduations of adjustment are provided to allow each input to approach an ideal representation of the  actual operating per unit value     Summing    Analog signals representing each input contribution are vector summed  shown as Summing in Figure 3   1   This summing process produces the operating current          that is the phasor sum of the input  currents     Ideally  and with perfectly matched CTs  a transformer without an internal fault should cause Io   to be  exactly zero on a continuous basis  When not zero  a fault would be indicated  However  saturation  effects caused by heavy through current or magnetic inrush can cause a temporary imbalance even  though no internal fault has occurred  To prevent a false trip under such conditions  various types of  restraint are used  Each restraint is specific to a potential cause of misoperation  These are individually  discussed in the topic Restrained Trip Output     30  Internal Phase Shift  Three Phase Relays ONLY     For three phase units  the inputs to the Summing function are first routed through the 30  Phase Shift  circuit  There the signals may be advanced or retarde
96. phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The B   phase differential circuit sees no current and does not respond     Connect Input 1 current to terminals B and C   Connect Input 2 current to terminals B and N   This verifies the B  and C phase differential circuits which respond together as provided earlier    in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The A   phase differential circuit sees no current and does not respond     Jumper Positions WYE A2    Step 1     Step 2     Step 3     Connect Input 1 current to terminals A and B    Connect Input 2 current to terminals N and B    This verifies the A  and B phase differential circuits which respond together as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The C   phase differential circuit sees no current and does not respond    Connect Input 1 current to terminals A and C    Connect Input 2 current to terminals A and N    This verifies the A  and C phase differential circuits which respond together  as provided earlier  in the Verification Tests  5 Amp CT or Verification Tests  1 Amp CT in this section  The B   phase differential circuit sees no current and does not respond    Connect Input 1 current to terminals B and C    Connect Input 2 current to terminals N and C    This verifies the B  and C phase differentia
97. pickup tests  always decrease one current starting from a    balanced input  Since percentage restraint is derived from the maximum current at any  one input  an increase of any current increases restraint  By contrast  a decrease of one  current has no effect on restraint        Step 1  Connect the relay as appropriate  refer to Figures 5 2 through 5 5   Apply the tap value to Input  1 and to Input 2     Step 2  With Input 1 constant  decrease Input 2 until the REST  TRIP LED lights  Ensure that this  measurement is within  6  of the calculated current  Return Input 2 to tap value     Step 3  With Input 2 constant  decrease Input 1 until the REST  TRIP LED lights  Ensure that this  measurement is within  6  of the calculated current  Return Input 1 to tap value     Unrestrained Pickup    Step 4  Set the front panel UNREST PICKUP LEVEL switch to the desired multiple of the tap setting   X TAP  which is the pickup level     Step 5  Increase the input test current until the UNREST  TRIP LED lights  Ensure that this  measurement is within  3  of calculated pickup  Do NOT exceed the thermal rating     Second Harmonic Inhibit    Step 6  For 50 and 60 Hz Units  Apply tap value  1 pu  to Input 1  The REST  TRIP LED should be  illuminated     For Three Phase Units  Set CALIBRATE switch S2 to CAL Position  see Figure 2 4      9171300990 Rev R BE1 87T Test Procedures 5 19    Step 7     For 50 Hz Units  Holding the 50 Hz current constant at tap value  add a 100 Hz      current in  paral
98. r lights to indicate that the power supply is functioning properly     Style number designations and input voltage ranges for the available power supply models are provided  in Section 1  General Information     Power Supply Status Output  Optional     The Power Supply Status output relay has normally closed  NC  contacts  The relay is energized by the  presence of nominal voltage at the output of the power supply  Normal operating voltage then keeps the  relay continuously energized and its contacts open  However  if the power supply voltage falls below  requirements  the Power Supply Status output relay will de energize and close the contacts     The Power Supply Status output is not associated with any magnetically latched target  The POWER LED  on the front panel provides a visual indication of the normal operating status of the power supply     NOTE  Sensing Input Types A through E  first position of the Style Number  have paddle operated  shorting bars included in the relay case  terminals 19 and 20  so that the Power Supply  Status output terminals can provide a remote indication that the BE1 87T has been    withdrawn from its case or that it has been taken out of service by removing the connection  plugs  Sensing Input Type G relays do NOT have shorting bars on the Power Supply  Status output  Sensing Input Type G units use terminal 9  lower terminal block  and  terminal 19  upper terminal block  for the Power Supply Status output        Target Indicators  Optional   
99. r the wye winding and in wye for the delta winding  This type of connection also  eliminates the zero sequence component of current which could cause a false trip  operation  during  external ground fault conditions on the wye system     Three Phase    BE1 87T Three Phase relays can provide zero sequence filtering and compensation for phase shifts  introduced by the connections of the power transformer  This 30  Phase Shift compensation  either  30    or no compensation  is field selectable  Additionally  this feature allows sharing the transformer differential  relay CTs with other relays or instrumentation     BE1 87T relays use the highest input current  in per unit values  to operate on maximum restraint  The  relay does not have a conventional operate winding in the internal magnetics  Operating current is  developed within the electronics of the relay     Percentage Restraint    A primary concern in differential relay applications is security against high current levels caused by faults  outside the protected zone  Inevitable differences in the saturation characteristics between current  transformers require a compensating decrease in relay sensitivity  It is also necessary to be able to adjust  the sensitivity to compensate for transformer voltage taps or CT mismatches  This is accomplished by  providing a restraint factor proportional to the current flowing through the protected zone  through   current      BE1 87T relays maintain sensitivity at a specified ratio of t
100. rated ne 5  Auxiliary  D  Single phase     restrained for Vdc targets contacts  SPDT  five inputs each of 3 Z  250 Vdc       Three  phase  phases  one 240 Vac  two inputs unrestrained  each phase  G                         NOTES   three inputs  h phas  each phase 1  All relays are in an   1 size case   e a A N Output type must be E  and Option 3 must be 0   AN Sensing input type must be E  and Option 3 must  SENSING INPUT IMS be ORION Z  RANGE x NEC        When targets are specified   A1  Instantaneous a  Two targets are supplied in single phase N  None  1  2 0 8 9 A  styles  restrained  unrestrained   S  Push to  60 Hz b  Five targets are supplied in 3   phase styles energize output  2  0 4     1 78A   restrained and unrestrained  plus phase A B   50 Hz and C    3  20 8 9 A  A Auxiliary contacts are only available if  50 Hz Sensing Input is not G and Output is E   4  0 4     1 78A   60 Hz 6  This drawing based on 9 1715 50 471  REV F           Figure 1 1  Style Number Identification Chart    1 4 BE1 87T General Information 9171300990 Rev R       SPECIFICATIONS    The BE1 87T relay is available in either single phase or three phase configurations and with the following    features and capabilities     Current Sensing Inputs    Maximum Current Per Input  1 Ampere CT Units  5 Ampere CT Units    Current Sensing Burden  Tap Setting Control  Scaling     1 Ampere CT Units   5 Ampere CT Units  Restrained Output   Pickup Range    Pickup Accuracy    Minimum Pickup    9171300990 Rev R 
101. re 2 4  to the NORM position     Fifth Harmonic Restraint Verification    Step 1     Step 2     Step 3     Step 4     Step 5     Set the INPUT 1  tap  switches to the 0 4 A position  Connect the relay as appropriate  refer to  Figures 5 2 through 5 5  using terminals 11  amp  13  Input 1 for both single phase and three   phase      Apply 0 4 A at 50 or 60 Hz  as appropriate for the style  to Input 1  The REST  TRIP LED  should be illuminated     Increase the fifth harmonic current until the REST  TRIP LED extinguishes indicating that the  inhibit point has been reached  Note the magnitude of the fifth harmonic component at the  inhibit point     To calculate the fifth harmonic inhibit percentage  divide the current measured in Step 3 by the  current applied in Step 2   Divide the harmonic current by the fundamental current   Factory  setting is 35 0  3  for both single phase and three phase styles     Three Phase Units Only  Repeat Steps 1 through 4 for phase B  terminals 12  amp  13  and  phase C  terminals 14  amp  13      9171300990 Rev R BE1 87T Test Procedures 5 17    Response Time Verification    Step 1     Step 2     Step 3     Step 4     Step 5     Step 6     Step 7     Step 8     Step 9     Step 10     5 18    Connect the relay as appropriate  refer to Figures 5 2 through 5 5      Set the RESTRAINED PICKUP LEVEL switch  phase A  to A  15    Place all of the INPUT  switches on the 0 4 A tap position     Apply 0 4 A at 50 or 60 Hz  as appropriate for the style  to Inpu
102. rip current to through current  This ratio   generally referred to as slope  is front panel adjustable in 5 96 increments from 15 to 60 96     Second Harmonic Restraint    Magnetizing inrush current presents another problem unique to transformer differential relays  Relays  must be capable of detecting the small differences in current caused by the shorting of a limited number  of turns  yet remain secure against the occurrence of magnetizing currents many times the transformer  rating  as seen at one set of terminals      Although magnetizing inrush is usually associated with the energizing of the transformer  any abrupt  change in the energizing voltage may produce this phenomenon  Common causes are the transients  generated during the onset  evolution and removal of external faults  Desensitizing the relay only during  energization is therefore insufficient     1 2 BE1 87T General Information 9171300990 Rev R    Magnetizing inrush produces an offset sine wave rich in all harmonics  BE1 87T relays use the second  harmonic to restrain operation because it predominates and because it does not occur in significant  magnitude or duration at other times     Three phase BE1 87T relays use second harmonic sharing  The second harmonic content of all three  phases is summed together to derive the restraint for each phase  As a result  the second harmonic  inhibit range and the associated factory setting  is higher than on single phase relays     Fifth Harmonic Restraint    Power tra
103. rrent  Ist IP RCT  is reduced by the excitation current   Ie  to yield the actual current  Is   This relationship is illustrated in the CT equivalent circuit shown in  Figure 1     Is                Rs    RI    Rr    IP Ist                         VT                Figure 1  CT Equivalent Circuit    For relaying applications  the CT performance is considered acceptable if the ratio correction is less than  10   The ratio error is defined      C57 13 1993  Section 8 1 10 as re Is  This criterion is expressed in the  ANSI C accuracy class which is defined in the following sentence  Under steady state  symmetrical  current  conditions  the excitation current must be less than 10 amperes for a relay current of 100  amperes into the specified standard burden  Since fault currents necessarily start with some degree of  transient DC offset  good design practice requires that the ratio error remain below 1096 during the initial  transient offset period  if possible  particularly when fast tripping is in effect  It has been generally accepted  that a design for a saturation factor  SF  of 0 5 or less is acceptable  The following analysis provides two  definitions of the saturation factor using a C200 application as an example     Saturation Factor Defined from the ANSI C Classification    In Figure 2  the CT terminal voltage increases linearly with the secondary current along the V ZBx  line  where ZB is the total CT burden  leads plus relays for a particular fault and connection   A 
104. s are not UL Recognized for voltages greater  than 250 V    GOST R Certification Gost R certified  No  POCC US ME05 B03391  complies with    the relevant standards of Gosstandart of Russia  Issued by  accredited certification body POCC RU 0001 11ME05     Patent Patented in U S   1991  U S  Patent No  5014153   Patented in Canada  1993   Shock In standard tests  the relay has withstood 15 g in each of    three mutually perpendicular axes without structural damage  or degradation of performance     Vibration In standard tests  the relay has withstood 2 g in each of three  mutually perpendicular axes swept over the range of 10 to  500 Hz for a total of six sweeps  15 minutes each sweep   without structural damage or degradation of performance     9171300990 Rev R BE1 87T General Information 1 9    Operating Temperature  Storage Temperature  Weight    Case Size     40  C   40  F  to 70  C  158  F     65  C   85  F  to 100  C  212  F    22 3 lbs  10 1 kg  maximum  three phase unit   19 5 Ibs  8 85 kg  maximum  single phase unit     All units are supplied in an M1 case size  See Section 4   Installation for case dimensions     BE1 87T General Information 9171300990 Rev R    SECTION 2   CONTROLS AND INDICATORS       LOCATION OF CONTROLS AND INDICATORS    Table 2 1 lists and briefly describes the operator controls and indicators of the BE1 87T Transformer  Differential Relay  Reference the call out letters A through M to Figures 2 1 to 2 3  N through Q to Figure  2 5  Exploded views 
105. s configured with other protective devices  it is recommended to use a separate lead to  the ground bus for each relay        Connections should be made with 14 AWG stranded wire or better except as noted for the ground wire   Figure 6 3 shows case terminal designations for sensing input type F relays  And Figure 6 4 shows the  test setup  Refer to the test procedures in Section 4 for testing sensing input type F relays  Testing  procedures are the same with the exception of terminal connections and the procedures for removing  connection plugs     9171300990 Rev R BE1 87T Difference Data 6 1                                                                                                                                                                                                                         STYLE NUMBER IDENTIFICATION CHART  BE1   87T     l A 1    0  MODEL NO   POWER       OUTPUT SUPPLY TARGET    OPTION 1 OPTION                    4      Single phase      Two      J  125 Vde  amp  N  None 0  None 0  None F  Semi Flush  two inputs contacts  one 100 120 C  Internally 1  Auxiliary Mounting      Single phase  restrained  one Vac operated contacts  NO P  Projection  three inputs unrestrained K  48 Vde targets 2  Auxiliary Mounting      Single phase  F  Four NO L  24 Vde D  Current contacts  NC  four inputs contacts  one Y  48 125 operated 5  Auxiliary  D  Single phase    N restrained for Vde targets contacts  SPDT  five inputs each of 3 Z  250 Vdc   E  Three phase  p
106. should be observed     CAUTION    1  Always remove power from the BE1 87T by removing the connection plugs before  removing or installing a printed circuit board        2  Always neutralize static body charge before placing a printed circuit board on   or  removing one from   metal surfaces  This can be accomplished by placing your hand  on the metal surface before handling the boards     3  Never hand a printed circuit board to another person whose static body charge has  not been neutralized     4  Testing or troubleshooting should always be done on a conductive and grounded   static controlled  surface     5  Never test printed circuit boards with an ohmmeter  The test current from the  ohmmeter may exceed component ratings     6  Printed circuit boards or integrated circuits should be transported only in electrically  conductive containers  The use of ordinary plastic bags may result in damage from  static charge buildup           Circuit Board Removal Procedure    Step 1  Remove the front cover and connection plugs        CAUTION    To prevent possible false tripping  the upper connection plug should be in place prior to    removing or installing the lower connection plug        Step 2  Withdraw the cradle assembly  see Figure 4 19      9171300990 Rev R BE1 87T Installation 4 17    Step 3  Remove the four screws that attach the front panel to the cradle assembly  and remove the  front panel     Step 4  With a slight side to side rocking motion  withdraw Analog Board  1  
107. sing input type G  for  three phase  three inputs for each phase  Primary differences between sensing input types F and G are     e Sensing input type G relays do not require a specific procedure for removing and installing  connection plugs       Sensing input type F relays have the normally closed power supply status  PSS  output at terminals  19 and 20 and have shorting bars across the PSS terminals  refer to Figure 6 2        Sensing input type F relays have terminal 9 for the common terminal on restrained and unrestrained  outputs       Sensing input type G relays have the normally closed PSS output at terminals 9 and 19 and have  NO shorting bars across the PSS terminals  refer to Figure 4 7        Sensing input type    relays have terminal 20 for the common terminal on restrained and  unrestrained outputs        COMPATIBILITY    Revision P relays with sensing input type G are NOT compatible with previous versions of the relays with  sensing input type F        CONNECTIONS    Sensing input type F relays  three phase  three inputs per phase  provide protection for transformers  requiring three differential inputs per phase  Be sure to check the model and style number against the  options listed in the Style Number Identification Chart before connecting and energizing a particular relay     NOTE    Be sure the relay case is hard wired to earth ground with no smaller than 12 AWG    copper wire attached to the ground terminal on the rear of the relay case  When the relay  i
108. sts  The 10 fingers on the black side are connected to the inner  binding posts  black thumbnuts  and tap into the relay internal circuitry  The 10 fingers on the red side of  the test plug are connected to the outer binding posts  red thumbnuts  and also connect to the relay case  terminals    When testing circuits connected to the bottom set of case terminals  the test plug is inserted with the  numbers 1 through 10 facing up  When using the test plug in the upper part of the relay  the numbers 11  through 20 are face up  It is impossible  due to the construction of the test plug  to insert it with the wrong  orientation     9171300990 Rev R BE1 87T Installation 4 51    This page intentionally left blank     4 52 BE1 87T Installation 9171300990 Rev R    SECTION 5   TEST PROCEDURES       OVERVIEW    BE1 87T Transformer Differential Relays are calibrated and tested for correct operation at the factory and  all calibration pots are sealed     Immediately upon receipt of the relay  or after extended service  it is recommended that the Verification  Tests provided in this section be performed  These comprehensive tests verify all operating parameters  including calibration     BE1 87T relay Verification Tests are divided into two groups based on the current CT ampere rating and  the nominal operating frequency   See the first position of the Style Number and the Sensing Input Range  Option as shown in Figure 1 1      Five Amperes CT  60 Hz Units  Range 1  and Five Amperes CT  50
109. t 1  terminals 11  amp  13 on both  single  and three phase styles  and to Input 2  terminals 12  amp  13 on single phase and terminals  15  amp  18 on three phase      Perform a restrained trip at 2 x Pickup by stepping the Input 2 current to 0 68 A  Note the time    interval between initiation of the simulated fault and the closure of the restrained output contact   The trip time should be less than that shown in Table 5 8     Repeat Step 4 at         10 x Pickup  Note that  with Input 1 at 0 4 A  Input 2 current should be  stepped to 1 8 A  The trip time should be less than that shown in Table 5 8     Three Phase Units Only  Repeat Steps 1 through 5 for Phases B and C     Place the UNRESTRAINED PICKUP LEVEL switch to the A setting  6 X TAP   Place all of the  INPUT switches to the 0 4 A tap position     With 0 0 A at Input 1  terminals 11  amp  13   apply 4 8 A  2 x Pickup  to Input 2  terminals 15  amp  18  on three phase   Note the time interval between initiation of the simulated fault and the closure  of the unrestrained output contact  The interval should be less than that shown in Table 5 8   Repeat Steps 7 and 8 at 10 x Pickup  Note that  with Input 1 at 0 0 A  it will be necessary to  step the Input 2 current to 24 A for an unrestrained trip  The trip time should be less than that  shown in Table 5 8     Three Phase Units Only  Repeat Steps 8 and 9 for phases B and C     Table 5 8  Timing  1 A  50 or 60 Hz          Option 1 0 Option 1 1  Timing Maximum Timing Maxim
110. ta   As inputs to a differential relay  these currents must be  compensated or scaled so that the relay can compare the inputs and determine when an unbalance  exists  Under ideal operating conditions  the scaled vector sum of these currents is zero     Because it is practically impossible to match the magnitudes of these detected currents from the various  power windings using standard CT ratios  the currents are matched within the relay by scaling each of the  applied currents by an appropriate factor called a Tap Setting  This is set by means of the front panel  INPUT dials  By selecting suitable tap ratios  the applied currents are scaled within the relay to achieve  the desired balance for normal operating conditions  BE1 87T relays offer a range of available tap  settings for inputs between 0 4 A to 1 78 A  Sensing Input Range Options 2 and 4 for a 1 ACT  or 2 0 to  8 9 A  Sensing Input Range Options 1 and    for a 5 A CT   These settings are independently adjustable in  increments of 0 02 A for Sensing Input Range Options 2 and 4  or 0 1 A for Sensing Input Range Options  1 and 3  These small increments allow more precise scaling of the applied currents and usually eliminate  the need for installing auxiliary ratio matching CTs     Single Phase    BE1 87T Single Phase relays require phase angle compensation to be accomplished externally by proper  connection of the system CT secondaries  A wye delta transformer requires that the CT secondaries be  connected in delta fo
111. take the ratio SF  SF    SF Zc  ZB   Rs    SF ZB  Zc Rs   Since this expression varies with the ratio of the actual relay circuit burden  ZB  to the accuracy class  burden  Zc  and the CT internal resistance  Rs   it is best visualized with a surface plot showing    simultaneous variations of the parameters  The following example is based on a C200  Zc 2  with Rs  varying from 0 1 to 0 8 ohms and ZB varying from 0 1 to 2 times ZC ohms   Load angles are neglected            Figure 3  SF   SF Ratio    The 0 to 20 axis represents the variations X10 of ZB  20 is 2xZC   The 0 to 8 axis represents the  variations x10 of Rs in ohms  The vertical axis  0 to 4  shows that for ZB values equal to or greater than  the burden value Zc  the two saturation factor equations are nearly identical  The ANSI Accuracy Class  method yields the larger  more conservative result  For low values of ZB and large values of Rs  the  Excitation Curve method yields a larger saturation factor  Since the Excitation Curve method is closely  following the CT characteristics  it may be said that the ANSI Class method which neglects the CT internal  resistance  is too optimistic in this range and should be discarded in favor of the Excitation Curve method   The absolute values of SF and SF are compared in Figure 4 for the particular case where Zc 2  ZB 0 5  and Rs 0 8 when IF varies from 0 to 100A     SF and SF for Zc 2  ZB 0 5  Rs 0 2  0 4    SFip         yp 02       IF    Figure 4  Comparing SF and SF       91
112. tch            Mr   Mn  LTC  Add the maximum CT mismatch My  based on the power transformer in the neutral tap    position  to the total permissible tap excursion from neutral  In this example  a  10  load tap  change  LTC  must be accommodated  Therefore           0 64 10 10 6 96  Verify CT Performance       NOTE  This procedure uses the ANSI accuracy class method  See Appendix A  Setting Note 7  for more information              Step 12  Determine the maximum CT secondary fault current for external faults    3 for three phase  and       for line to ground   Refer again to Figure 4 33 for this example  The maximum fault current  is recorded for each set of terminals for all combinations of external faults        HIGH TERTIARY LOW  _ 3360 215280     _ 8400  F190 F3 600      240   28    22    35A  3375 9000  eee     0   28    38 A    Step 13  Determine the worst case burden voltage for a three phase fault  Vas    e For wye connected CTs            Ir3 R    Rp   e For delta connected CTs  based on a three phase fault  refer to Appendix A  Setting Note 2    Vgpa         Rw  3      3         Where            determined in Step 12 p    relay resistance in ohms   lt  0 05 ohm     Ry   winding burden R    one way lead resistance in ohms    9171300990 Rev R BE1 87T Installation 4 37    Neglecting Rr  use R  from Figure 4 33     HIGH TERTIARY LOW  Vg    28 0 7  Vg   22 0 7  Vg    35 0 7    19 6  15 4   24 5    Step 14  Determine the burden voltage for    line to ground fault   Vac    
113. ted CTs    9171300990 Rev R BE1 87T Setting Notes A 3    SETTING NOTE 4    OAS    D2751 18  02 03 98                    1  Find the maximum pu fault current for external faults  ie    2  Assume that one of the input CTs saturates to 70      3  Set unrestraint pickup  gt  7 X IE                                                                                                     1  V  Iru  Rcu x       L R  I FH Sct   i       i  FH     Top       TRIP       gt    Rm Sie 78 7 A  C  x        UNRESTRAINT  M MPU SETTING     0 31      L rn 4        lt   0 3 x IrL      T   Ro  ho t L RccxTL  4 14  02751 19  03 12 98 v             Figure A 4  Unrestraint Tap Setting  SETTING NOTE 5    Slope Margin    The slope formula accounts for an operating current bias due to magnetizing current in one winding  The  magnetizing current is assumed to be 496 of the OA rating  Step 20 is used to scale this magnetizing ratio  to the corresponding ratio of relay operate current  4 x 17      The formula further assumes a conservative margin corresponding to an operation current of 2396 of tap   The actual margin varies with the tap settings  as given by the following equation     Margin   35 4x Ir    Mr  3  x2    The margin variations for different tap settings   7  can be evaluated with this equation  The following plots  show the calculated slope and the resulting margin for Mr varying from 1 to 11  and     varying from  5 to  2  plot shows 10 x Jr      A 4 BE1 87T Setting Notes 9171300990 Rev R       D2
114. terminal voltage   VT  corresponds to the maximum fault current  This voltage is lower than the maximum voltage  VC  that  the C200 CT can support  Saturation will occur  i e  ratio error will exceed 1096  for secondary currents in  excess of IFs where the corresponding terminal voltage crosses the accuracy class limit VC  point C in  Figure 2   We can define a measure of the degree of saturation with the saturation factor  SF    sp      IFs    By examination of triangles OAB and OCD  the same saturation factor can be expressed as     sr  VL  VC    9171300990 Rev R BE1 87T Setting Notes A 7                           lt           am  z     9     2  E LAM      PINE REM                    C400  2     ra  Vio a SS            Vk   mat             lo a  VK    Ve Rs 100 206        VT                             10      20 40 IF IFs 100  EXCITATION CURRENT RELAY CURRENT    Figure 2  CT Terminal and Excitation Voltages    This first definition of saturation relates the CT terminal voltage to the accuracy class of the CT  effective  class in the case of multi ratio CTs   It is practical and easy to calculate since it requires only readily  available data  An application is considered reasonably secure when SF is less than 0 5    Saturation Factor Defined from the CT Excitation Curve    The definition of the saturation factor given above appears to be conservative because it assumes the  worst case ratio error  However  a closer look is required since it neglects the CT internal resista
115. th Option 1 0  Three Input Disabling Jumpers are located on each Analog Board  1 as shown in Figure 4 20     Single Phase Units with Option 1 1    Three additional Input Disabling Jumpers are also located on each Analog Board  1 as shown in Figure  4 21  J9 is a factory adjustment and is not intended to be changed in the field     BE1 87T single phase units are shipped with all inputs enabled     Three Phase Units    Three Phase Units with Option 1 0  Three Input Disabling jumpers are located on each Analog Board  1 as shown in Figure 4 20     Three Phase Units with Option 1 1    Three additional Input Disabling jumpers are also located on each Analog Board  1 as shown in Figure  4 21  J9 is a factory adjustment and is not intended to be changed in the field     For Three Phase Units with Input Sensing Type E  two inputs per phase     The jumpers shown in Figures 4 20 and 4 21 are shipped in the disabled position and no further  adjustment should ever be necessary     For Three Phase Units with Input Sensing Type G  three inputs per phase     The jumpers shown in Figures 4 20 and 4 21 are shipped with Input 3 enabled  and Inputs 4 and 5  disabled  If only two inputs are actually used  which must be Inputs 1 and 2   it is important to disable the  unused input of each phase by means of the internal Input Disabling jumpers provided on each of the  three Analog Boards  1 as shown in either Figure 4 20 or Figure 4 21  J9 in Figure 4 21 is a factory  adjustment and is not intended
116. the MVA  rating is only a convenient way of calculating the currents  i e  taps  in proportion to their voltage rating  It  does not mean that the windings will necessarily carry the maximum rating                          L  5   V3 Vals    v    I  1     V     gt  81  4 3 Vit  3  S3   43 Vals    D2751 16  01 30 98        12  2  5  Vili  VolIo  Vsls    Hey          1 Vi    _ 5    87    S   Winding Rating  MVA        Figure A 1  Multi winding Transformer    9171300990 Rev R BE1 87T Setting Notes A 1    SETTING NOTE 2                            I I  Ry NE    R   A t     y  ty R   L I       B    R   B         y       x    1        s         Ic  R   D2751 17  01 30 98      14 15 1   0         1   10                 1Ga  Ic       Rg   En IA              zL RyE Ry RgRFRg  Ig  Rr  Rg  Ic  Rj Rg    L Ry 2R  2Rg   IgtIc   Ry Rg     Since I4     Ig Hc   V I  Rw 3R  3Rp     Where     I4   3 Phase fault current        Relay burden   R    Lead burden   Rw   Winding burden    Figure A 2  CT Burden Delta Connected CTs 3 Phase Fault    A 2 BE1 87T Setting Notes 9171300990 Rev R    SETTING NOTE 3    87T       A            100 1     IDD             2129            4       2100 2      129    gt  9     109                   02779 01  04 16 99                   Assuming Zi Z  I          155    Phase 2 carries twice the fault current returning from the relay to the CTs  Therefore  the maximum current  is     Imax   2x 109  B     s               1 3 x       Figure A 3  Phase Phase Fault Delta Connec
117. the worst case CT burden voltage for a three phase fault  Va         For wye connected CTs   Vss   Ir3 R     Rp        For delta connected CTs  for three phase fault          Iz  Rw   3R    3Ry   Note that the wye connection produces a lower burden on the CTs  see Appendix A  Note 2      Where   le    determined in Step 12       one way lead resistance in ohms    Rw   winding burden        relay resistance in ohms   lt  0 05 ohm     Neglecting Hg  use Rw and R  from Figure 4 35     HIGH LOW  Vp3    32  0 7  VB3    66  0 7    22 4V  46 2 V    Step 14  Determine the worst case burden voltage for a line to ground fault   Vac       For wye connected CTs     Vag   Iro 2R    Rp     Where   la   determined in Step 12        one way lead resistance in ohms         relay resistance in ohms       For delta connected CTs     Vao is a function of the proportion of positive sequence to zero sequence currents but may be  approximated by the same equation  for worst case      9171300990 Rev R BE1 87T Installation 4 45    Neglecting Rp  use Rw and R  from Figure 4 35        HIGH LOW  VBG  19 5 0 7           70  2 0 7     13 6V   98 0 V  NOTE        Since a phase to ground fault looks like a phase to phase fault on the delta side of a  delta wye transformer  each CT only has to carry one times the one way lead burden           Step 15  Determine the effective CT accuracy class  Vce       Base Accuracy   Number of CT Turns in Use        V  eR Maximum Ratio  NA  ver   HIGH LOW            400   
118. ts of Step 18  set the UNRESTRAINED PICKUP LEVEL control     Referring to the table on the BE1 87T front panel  select the tap position  X TAP  that is higher  than the result obtained in Step 18  Therefore  for this example  select SET position G   12 X  TAP  which is higher than the above result of 11 17 X TAP     If this value exceeds 21  max setting   raise the tap settings toward the upper end of the tap  range  If after the highest tap has been reached the unrestrained trip settings still exceeds 21   security is affected  The user should remember that the 70  saturation is conservative  A close  look at the system L R and CT performance is recommended  Chances are that the risk will be  tolerable     Slope Setting    The slope equation determines the slope setting required to maintain a margin of about 12  of        at the  breakpoint of the slope characteristic  This margin varies slightly with the actual taps but remains secure  over the tap range     Step 20  Determine the multiples of self cooled current   7   Refer to Appendix A  Setting Note 5       Ig  MVA sexr cooten    ET  MVA                                   Where   Tp   relay current  from Step 4   T   the input tap  from Step 9     MVAazir              and MVArorce              are given in Figure 4 35     9171300990 Rev R BE1 87T Installation 4 47    HIGH LOW     2 7912  y  _  00212   T   2 0  20  T               0 84   0 84    Step 21  Select the restrained slope setting     4 48    The recommended restr
119. um  Function Differential Current 50 Hz 60 Hz 50 or 60 Hz  Restrained Trip 2 x Pickup 81 ms 70 ms 49 ms  Restrained Trip 10 x Pickup 73 ms 67 ms 37 ms  Unrestrained Trip 2 x Pickup 64 ms 52 ms 57 ms  Unrestrained Trip 10 x Pickup 32 ms 28 ms 10 ms          BE1 87T Test Procedures 9171300990 Rev R       OPERATIONAL TEST PROCEDURES    The functional tests given below provide a simplified method of checking the relay trip performance  relative to the front panel settings  and indirectly  the calibration  Individual steps of the procedure are  designed as a series of tests that are performed in the sequence shown  rather than stand alone   For a  more comprehensive test  refer to Verification Tests  5 Amp CT or Verification Tests  1 Amp CT earlier in  this section        CAUTION    Do not proceed unless familiar with the Relay Operating Precautions  the procedures  described in Relay Disassembly and the procedures listed in the RESTRAINED  PICKUP TESTING EXAMPLES at the beginning of this section        These tests may be performed by removing the BE1 87T to a test station or with the relay installed     CAUTION       If testing an installed relay  be sure to isolate the current inputs and the relay outputs  from the system  Basler electric test plugs  p n 10095  are recommended for this purpose  to isolate the relay as well as simplify the test setup   For further information  see Test  Plug in Section 4  INSTALLATION           Restrained Pickup    NOTE    When making restrained 
120. units   6 Three phase units use the sum of the second harmonic from each phase to restrain each phase   7 Phase Targets are supplied on three phase units ONLY     8 Restrained Trip Contact   e One contact for single phase units   e One contact or one contact per phase available on three phase units       B SAME AS gA RESTRAINED  UNRESTRAINED         C SAME AS gA RESTRAINED       UNRESTRAINED    OPTIONAL  RESTRAINED  CONTACTS  FOR EACH OF  3 PHASES      1 87    SEE NOTE  A  D741 001b    7 11 94       Figure 3 2  Functional Block Diagram  Phase B and Phase C  3 2 BE1 87T Functional Description 9171300990 Rev R    Restrained Trip Output    Restrained trip output contacts are subject to three types of restraint  i e   inhibit  signals     e Percentage restraint  e Second harmonic restraint  e  Fifth harmonic restraint    These signals are developed within the relay in response to external conditions and block the restrained  output contacts from closing     Percentage Restraint    Percentage restraint developed from the maximum through current and the slope setting determines the  minimum operating current 7o    Figure 3 1  in a comparator where Jpop must be greater than  Ivax to  produce a Restraint Trip output  The 7o   desired trip level is adjustable on the front panel RESTRAINED  PICKUP LEVEL switches shown in Figures 2 1 through 2 3     Comparators in the Calculate Max  Individual Current circuit determine which input  of a particular phase   is receiving the greatest curre
121. using terminals 11  amp  13  Input 1 for both single phase and three   phase units      Step 2  Three Phase Units Only  Set the Calibrate toggle switch S2  letter D of Figure 2 4  to the CAL  position on each of the three Analog  1 boards  These three toggle switches are readily    5 16 BE1 87T Test Procedures 9171300990 Rev R    accessible on the right side of the relay when withdrawn from the case   It is not necessary to  pull out the circuit boards      NOTE    With two current sources in parallel  apply the fundamental frequency and then add the  required harmonic        Step 3     Step 4     Step 5     Step 6     Step 7     Apply 0 4 A at 50 or 60 Hz  as appropriate for the style  to Input 1  The REST  TRIP LED  should be illuminated     Increase the second harmonic current until the REST  TRIP LED extinguishes indicating that  the inhibit point has been reached  Note the magnitude of the second harmonic component at  the inhibit point     To calculate the second harmonic inhibit percentage  divide the second harmonic current  measured in Step 4 by the current applied in Step 3   Divide the harmonic current by the  fundamental current   Factory setting is 12 0  3  for single phase units and 18 0  3  for  three phase units     Three Phase Units Only  Repeat Steps 1 through 5 for phase B  terminals 12  amp  13  and  phase C  terminals 14  amp  13      Three Phase Units Only  Upon completion of above testing  return the three calibrate toggle  switches S2  letter D of Figu
122. y case is hard wired to earth ground with no smaller than 12 AWG    copper wire attached to the ground terminal on the rear of the relay case  When the relay  is configured in a system with other protective devices  it is recommended to use a  separate lead to the ground bus from each relay        Except as noted above  connections should be made with a minimum wire size of 14 AWG  Figures 4 7  through 4 10 show case terminals designations for four typical relay configurations  Figures 4 11 through  4 14 show the internal connections of the BE1 87T  Control circuit connections are shown in Figures 4 15  through 4 18        CAUTION    To prevent possible false tripping  the upper connection plug should be in place prior to  removing or installing the lower connection plug              BE1 87T  AUX N O     AUX COM    AUX           INPUTS RESTRAINED    OUTPUTS  COMMON    NRESTRAINED    SUPPLY  STATUS      POWER  CONTACTS       BE1 87T    CONFIGURATION IS DEPENDENT              ON STYLE SELECTED     Figure 4 7  Case Terminals  Single Phase    9171300990 Rev R BE1 87T Installation 4 9    BE1 87T       rower RESTRAINED  COMMON  OA UNRESTRAINED  INPUT 1   28  gc POWER  CO       OUTPUTS  CONTACTS  DA AUX N O   OB  INPUT 24 gc AUX COM AN  CO AUX N          1 87    D437 002  9 23 94     N CONFIGURATION IS DEPENDENT  ON STYLE SELECTED     Figure 4 8  Case Terminals  Three Phase  Two Input  Sensing Input Type E   Output Option E         RESTRAINED N                               POWER   
    
Download Pdf Manuals
 
 
    
Related Search
    
Related Contents
シリーズ  - Hitachi Construction Machinery Europe  Manual del Instrucciones  MACGTFBV - Castorama  TP de Biologie cellulaire BGF1  Acer ISDN P10 Network Card User Manual    user guide  GeoCAT USER Guide v1.0 - Dartmoor National Park  American Standard 4242.STE2 User's Manual    Copyright © All rights reserved. 
   Failed to retrieve file