1. B Definition    ALARMS    This is a single bitmapped integer     Variable OID  Event Log 3 5 1 0  Bit Id Alarm   0x01 Supply 1 Bad  0x02 Supply 2 Bad  0x04 Not on Preferred  0x08 Synchronisation Loss  0x10 Load Fault   0x20 High Temperature  0x40 Forced Supply  UTILISATION    Type  Integer    Description  Bitmapped alarm    This is a set of variables indicating the unit s general statistics     Variable  Hours 1  Hours 2  Hours Preferred    Hours Operation  Hours no Output    Number Forced    Transfers  Number Sync Losses    Last Load Fault    Number Supply  Outages  Last Supply Outage    OID    3 6 1 0    3 6 2 0    3 6 3 0    3 6 4 0    3 6 5 0    3 6 6 0    3 6 7 0    3 6 8 0    3 6 9 0    3 6 10 0    Type  Integer  Integer  Integer  Integer  Integer  Integer  Integer  Time Stamp    Integer    Time Stamp    Description   Hours on supply 1  Rounded to nearest hour   Hours on supply 2  Rounded to nearest hour   Hours on the preferred supply  Rounded to nearest  hour    Hours the unit has been in operation  Rounded to  nearest hour    Hours the unit has not been able to supply output   Rounded to nearest hour    The number of times the unit has been forced onto  a supply    The number of times the unit has lost  synchronisation between supplies    Timestamp of the last load fault  This is in seconds  since 1    of January 2002    Number of supply outages that have occurred  during units operation    Timestamp of the last supply outage   seconds since 1    of January 2002     
2. RAP INFORMATION    The Trap table stores details for up to two receivers  O is the index of the first entry into the table   Entries are writeable     Variable OID Type Description  Trap Receiver Id 2 1 1 1 0 Integer Index into the Trap Table  Receiver Enabled 2 1 1 2 0 Integer Boolean indicator of whether receiver enabled  Receiver IP 2 1 1 3 0 Dotted IP Address of Trap receiver  Notation IP  Trap Community 2 1 1 4 0 String Trap Community Id    CONTROL AND OPERATIONAL VARIABLES    These can be further split into several sections    OPERATIONAL VARIABLES    Variable OID Type Description  Active Supply  3 1 1 0 Integer The currently active supply  The possible values 1  Transfer Command or 2 are writeable     A Value of3 activates the inhibit  A Value of4 releases the inhibit   A Value of5 Alarm Cancel    Reset  amp  Release all other Inhibits     Preferred Supply 3 1 2 0 Integer The preferred supply  The possible values 1 or 2  are writeable    Frequency Supply 1 3 1 3 0 Integer 10 x the frequency of supply 1  le 501 indicates  50 1 Hz    Frequency Supply 2 3 1 4 0 Integer 10 x the frequency of supply 2    Synchronisation 3 1 5 0 Integer Synchronisation between the two supplies   Neutral Current 3 1 6 0 Integer 10 x the Neutral current  This may not be available    on some models        MIB Definition 3    INPUT VARIABLES    This is a table of either one or three entries  depending on the model of the Static Transfer Switch  It    represents the phases  O is the index of eith
3. This is in       MIB Definition    TYPICAL WALK OUTPUT                   Name OID Value Type  BysDescr 0 PICDEM  net running Microchip SNMP Agent OctetString  bysObjectID O 1 3 6 1 4 1 32796 OID  bysUpTime O 6 minutes 43 seconds TimeTicks  BysContact 0 techsupport microchip com OctetString  FysName 0 PICDEM net OctetString  BysLocation O Near Your Desk OctetString  bysServices  0 7 Integer  L1 3 6 1 4 1 32796 1 1 0 Microchip SNMP Agent OctetString   1 3 6 1 4 1 32796 1 2 0 v1 0 OctetString  L1 3 6 1 4 1 32796 1 3 0 May 2003 OctetString   1 3 6 1 4 1 32796 2 1 1 1 0 0 Integer   1 3 6 1 4 1 32796 2 1 1 1 1 1 Integer  L1 3 6 1 4 1 32796 2 1 1 2 0 0 Integer  L1 3 6 1 4 1 32796 2 1 1 2 1 0 Integer  L1 3 6 1 4 1 32796 2 1 1 3 0 0 0 0 0 Ip  ddress  1 3 6 1 4 1 32796 2 1 1 3 1 0 0 0 0 IpAddress  L1 3 6 1 4 1 32796 2 1 1 4 0 OctetString  L1 3 6 1 4 1 32796 2 1 1 4 1 OctetString  L1 3 6 1 4 1 32796 3 1 1 0 1 Integer   1 3 6 1 4 1 32796 3 1 2 0 0 Integer   1 3 6 1 4 1 32796 3 1 3 0 500 Integer   1 3 6 1 4 1 32796 3 1 4 0 500 Integer   1 3 6 1 4 1 32796 3 1 5 0 123 Integer   1 3 6 1 4 1 32796 3 1 6 0 0 Integer  L1 3 6 1 4 1 32796 3 2 1 0 0 Integer   L1 3 6 1 4 1 32796 3 2 2 0 234 Integer  L1 3 6 1 4 1 32796 3 2 3 0 234 Integer   L1 3 6 1 4 1 32796 3 3 1 0 0 Integer  L1 3 6 1 4 1 32796 3 3 2 0 233 Integer  L1 3 6 1 4 1 32796 3 3 3 0 3 Integer  L1 3 6 1 4 1 32796 3 3 4 0 1 Integer   1 3 6 1 4 1 32796 3 3 5 0 0 Integer  L1 3 6 1 4 1 32796 3 3 6 0 0 Integer   1 3 6 1 4 1 32796 3 3 7 0 0 Inte
4. er the main entries  or Red phase     Variable OID Type  Input Variables 3 2 1 0 Integer  S1 3 2 2 0 Integer  S2 3 2 3 0 Integer  OUTPUT VARIABLES    Description   The index into the Input Variables table  The voltage of Supply 1   The voltage of Supply 2    This is a table of either one or three entries  depending on the model of the Static Transfer Switch  It    represents the phases  O is the index of either the main entries  or Red phase     Variable   Output Variables  s3   Current   kVA   kW   PF   CF   THDI    THDV    EVENT LOG    OID Type   3 3 1 0 Integer  3 3 2 0 Integer  3 3 3 0 Integer  3 3 4 0 Integer  3 3 5 0 Integer  3 3 6 0 Integer  3 3 7 0 Integer  3 3 8 0 Integer  3 3 9 0 Integer    Description   The index into the Output Variables table   The voltage of the output   10 x the current delivered   10 x the calculated kVA   10 x the calculated kW   10 x Power Factor   10 x Crest Factor   10 x the percentage of Total Harmonic Distortion of  the current   10 x the percentage of Total Harmonic Distortion of  the Voltage     This is a table of event entries  There is a variable amount of entries up to a maximum of 100     When receiving next index of OxFF  it indicates end of table     Variable  Event Log  Event Item    EVENT_TIME  EVENT_NUM  EVENT_VAL    OID Type  3 4 1 0 100 Integer  3 4 2 0 100 Integer    Timestamp  Integer  Integer    Description   The index into the Event Log   The value returned also is now the number of seconds  since 1 Jan 1970 00 00 00  Th
5. ger   1 3 6 1 4 1 32796 3 3 6 0 9999 Integer   1 3 6 1 4 1 32796 3 3 9 0 10791 Integer  L1 3 6 1 4 1 32796 3 4 1 0 0 Integer  L1 3 6 1 4 1 32796 3 4 1 1 i Integer  L1 3 6 1 4 1 32796 3 4 1 2 2 Integer   1 3 6 1 4 1 32796 3 4 1 3 3 Integer  L1 3 6 1 4 1 32796 3 4 1 4 4 Integer  L1 3 6 1 4 1 32796 3 4 1 5   Integer  L1 3 6 1 4 1 32796 3 4 1 6 6 Integer   1 3 6 1 4 1 32796 3 4 1 7 7 Integer  L1 3 6 1 4 1 32796 3 4 1 8 8 Integer   L1 3 6 1 4 1 32796 3 4 1 9 3 Integer   L1 3 6 1 4 1 32796 3 4 1 10 10 Integer   1 3 6 1 4 1 32796 3 4 1 11 11 Integer  L1 3 6 1 4  1 32796 3 4 1 12 12 Integer   1 3 6 1 4 1 32796 3 4 1 13 13 Integer  L1 3 6 1 4 1 32796 3 4 1 14 14 Integer   L1 3 6 1 4 1 32796 3 4 1 15 15 Integer          MIB Definition       i STS    Manufacturing is a subsidiary of  STATIC POWER PTY  LTD   ABN42101765913    Postto   Box 2003 Manufactured at  Phone   613 9437 0494    5 Candlebark Court Fax    613 9437 0939  Research Delivery Centre      Research VIC 3095 Email  sales i sts com au  Research VIC 3095       Australia Web  www i sts com au    Australia    Copyright O 2014 STATIC POWER PTY  LTD     This user manual is protected under international copyright laws  No part of this user manual may be  reproduced  distributed  translated  or transmitted in any form or by any means  electronic or  mechanical  including photocopying  recording  or storing in any information storage and retrieval  system  without the prior written permission of STATIC POWER PTY  LTD       
6. i STS    SNMP MIB  User Manual    CONTENTS       Contents 1  Introduction 2  Conventions 2  MIB Definition 3  Basic System Information 3  Trap Information 3  Control and Operational Variables 3  Operational Variables 3  Input Variables 4  Output Variables 4  Event Log 4  Alarms 6  Utilisation 6  Typical Walk Output 7  Contents 1    INTRODUCTION    This MIB documentation aims to provide all necessary definitions to provide basic control and  monitoring capabilities of the Static Transfer Switch via SNMP version 1 0     There are three sections to the MIB     1  Basic System Information   2  Trap Information   3  Control and Operational Variables  CONVENTIONS    The i STS Manufacturing Private Enterprise Number is 32796  Therefore  the prefix for all OIDs is   43 6 1 4 1 32796    For all table variables  O is the first index  and is referenced by adding an   index   to the end of the  OID  ie  for the trap receiver IP   43 6 1 4 1 32796 2 1 1 3 0    Some variables may be represented as a base 10 multiple of the actual value  so as to avoid floating  point values  The multiplier will be indicated where appropriate   Note also that all variables are read only unless otherwise specified        Introduction 2    MIB DEFINITION    BASIC SYSTEM INFORMATION    Variable OID Type Description   Product Name 1 1 0 String Name and variant of the Static Switch  Product Version 1 2 0 String Version number of the Static Switch  Product Date 1 3 0 String Date stamp for the product version    T
7. is is the well known Unix  timestamp that practically all 32 bit timestamps are  based off  There are many software libraries that can  convert that to text of any format  so the returned  number needs to be formatted using your SNMP  Management Software  As an example  see the  following URL   http   www onlineconversion com unix_time htm    43 6 1 4 1 32796 3 4 2  43 6 1 4 1 32796 3 4 3  43 6 1 4 1 32796 3 4 4       MIB Definition    EVENT_NUM can be one of     Boot   Initialise  Watchdog  Stack   Blank Index  EEPROM   ROM   Battery  Communications  Calibration  Supply 1 Average  Supply 1 Transient  Supply 1  Freguency  Sync   Supply 2 Average  Supply 2 Transient  Supply 2   On   off   Force   Supply 3  Overload   Load   Fail   Transfer    EVENT_ VAL can be one of   0 1 2 3 4 5 6 7 8 9    10 Nothing    11 OK  12 HI   13 LOW  14 FLT  15 CLR  16 LOS  17 ON  18 OFF  19 TMR  20 1   21    o ON ao un BO MM MO    NNNNNNRPRPRPRP RRP RP RPP EH  OBWNPRP OW WAN DU BWNPRP       Transfer   Low Power Mode  Current   Manual Bypass  Preference   Varf   Total Harmonic Distortion Current  Total Harmonic Distortion Voltage  Ambient   Magnetics   Heat sink   Fan   Thermal   Debug   Remote Power   Remote Transfer Reguest  Local Transfer Reguest  Blank   Breaker Open   Breaker Closed   Tripped   Thyristor Short circuit  Thyristor Open circuit  Alarm Cancel   Power Supply   Back Feed    25  26  27  28  29  30  31  32  33  34  35  36  37  38  39  40  A1  42  43  44  45  46  47  48  49  50       MI
    